Rockwell Automation 284G User Manual

ArmorStart® Distributed Motor Controller
USER MANUAL
Bulletin 280G/281G, 284G
3
ATTENTION
!
IMPORTANT
Important User Information
Because of the variety of uses for the products described in this publication, those responsible for the application and use of this control equipment must satisfy themselves that all necessary steps have been taken to assure that each application and use meets all performance and safety requirements, including any applicable laws, regulations, codes and standards.
The illustrations, charts, sample programs and layout examples shown in this guide are intended solely for purposes of example. Since there are many variables and requirements associated with any particular installation, Rockwell Automation does not assume responsibility or liability (to include intellectual property liability) for actual use based upon the examples shown in this publication.
Rockwell Automation publication SGI-1.1, Safety Guidelines for the Application, Installation and Maintenance of Solid-State Control (available from your local Allen-Bradley sales office), describes some important differences between solid-state equipment and electromechanical devices that should be taken into consideration when applying products such as those described in this publication.
Reproduction of the contents of this copyrighted publication, in whole or part, without written permission of Rockwell Automation, is prohibited.
Throughout this manual we use notes to make you aware of safety considerations:
Identifies information about practices or circumstances that can lead to personal injury or death, property damage or economic loss
Attention statements help you to:
identify a hazard
avoid a hazard
recognize the consequences
Identifies information that is critical for successful application and understanding of the product.
Trademark List ArmorStart and ControlLogix are registered trademarks of Rockwell Automation, Inc.
ArmorConnect, DeviceLogix, PLC, RSNetWorx, RSLogix 5000, and SLC are trademarks of Rockwell Automation, Inc. DeviceNet and the DeviceNet logo are trademarks of the Open Device Vendors Association (ODVA). ControlNet is a trademark of ControlNet International, LTD.
4
European Communities (EC) Directive Compliance
If this product has the CE mark it is approved for installation within the European Union and EEA regions. It has been designed and tested to meet the following directives.
Low Voltage and EMC Directives
This product is tested to meet Council Directive 73/23/EEC Low Voltage and 89/336/EEC and Council Directive 89/336/EC Electromagnetic Compatibility (EMC) by applying the following standard(s):
Bulletin 280/281: EN 60947-4-1 — Low-voltage switchgear and
controlgear — Part 4-1:Contactors and motor-starters — Electromechanical contactors and motor-starters.
Bulletin 283: EN 60947-4-2 — Low-voltage switchgear and
controlgear — Part 4-2: AC semiconductor motor controllers and starters.
Bulletin 284: EN 61800-3 — Adjustable speed electronic power drive
systems — Part 3: EMC product standard including specific test methods.
This product is intended for use in an industrial environment.
Table of Contents
Table of Contents i
Chapter 1 Product Overview
Chapter 2 Installation and Wiring
Introduction ....................................................................................1-1
Description .....................................................................................1-1
Safety ArmorStart............................................................................1-1
Operation .......................................................................................1-2
Mode of Operation ..........................................................................1-2
Bulletin 280G/281G — Full-Voltage Start ................................1-2
Bulletin 284G — Sensorless Vector Control..............................1-2
Description of Features ..................................................................1-3
Overload Protection .................................................................1-3
LED Status Indication ..............................................................1-5
Fault Diagnostics .....................................................................1-5
Inputs ......................................................................................1-6
Gland Plate Entrance ...............................................................1-6
ArmorStart with DeviceNet Network Capabilities ......................1-6
DeviceLogix™ ........................................................................1-6
Peer to Peer Communications (ZIP) ..........................................1-6
EMI Filter..................................................................................1-6
Dynamic Brake Resistor ...........................................................1-7
Control Brake Contactor ..........................................................1-7
Receiving .......................................................................................2-1
Unpacking ......................................................................................2-1
Inspecting ......................................................................................2-1
Storing ...........................................................................................2-1
General Precautions .......................................................................2-2
Precautions for Bulletin 280G/281G Applications.............................2-2
Precautions for Bulletin 284G Applications ......................................2-2
Dimensions ....................................................................................2-4
Bulletin 280G/281G..................................................................2-4
Bulletin 284G ...........................................................................2-6
Bulletin 1000............................................................................2-8
Wiring ..........................................................................................2-13
Power, Control, Safety Monitor Inputs, and
Ground Wiring ......................................................................2-13
Terminal Designations ..................................................................2-14
Dimensions for Safety Products.....................................................2-15
Bulletin 280G Safety Product..................................................2-15
Bulletin 281G Safety Product..................................................2-16
Bulletin 284G Safety Product..................................................2-17
Bulletin 1000 Safety Product ..................................................2-19
Safety Terminal Designations .......................................................2-26
ArmorConnect Power Media .........................................................2-29
Description ............................................................................2-29
ArmorStart with ArmorConnect Connectivity ..........................2-30
Terminal Designations............................................................2-30
ArmorStart Safety with ArmorConnect Connectivity ...............2-31
Terminal Designations............................................................2-31
ArmorConnect Cable Ratings .................................................2-31
Branch Circuit Protection Requirements for
ArmorConnect Three-Phase Power Media .............................2-32
Group Motor Installations for USA and Canada Markets ................2-32
ii Table of Contents
Wiring and Workmanship Guidelines ............................................2-32
DeviceNet Network Installation .....................................................2-33
Other DeviceNet System Design Considerations ....................2-34
Electromagnetic Compatibility (EMC) ............................................2-35
General Notes (Bulletin 284G only) ........................................2-35
Grounding .............................................................................2-35
Wiring ...................................................................................2-35
Chapter 3 Bulletin 280G/281G Programmable Parameters
Chapter 4 Bulletin 284G Programmable Parameters for Sensorless Vector Controllers
Introduction ....................................................................................3-1
Parameter Programming .........................................................3-1
Parameter Group Listing .................................................................3-2
DeviceLogix™ Group .....................................................................3-2
DeviceNet Group ............................................................................3-7
Starter Protection Group ...............................................................3-10
User I/O ........................................................................................3-14
Misc. Group .................................................................................3-14
ZIP Parameters ............................................................................3-16
Starter Display .............................................................................3-23
Starter Setup ................................................................................3-24
Introduction ....................................................................................4-1
Parameter Programming .........................................................4-1
Parameter Group Listing .................................................................4-2
DeviceLogix™ Group .....................................................................4-3
DeviceNet Group ............................................................................4-8
Starter Protection Group ...............................................................4-12
User I/O ........................................................................................4-15
Miscellaneous Group ....................................................................4-16
Drive DeviceNet Group ..................................................................4-18
Display Group................................................................................4-20
Basic Program Group ....................................................................4-25
Advanced Program Group..............................................................4-28
Clear Type 1 Fault and Restart ......................................................4-42
Clear an Overvoltage, Undervoltage, or Heatsink OvrTmp Fault
without Restarting the Drive..........................................................4-42
How Step Logic Works .................................................................4-55
Step Logic Settings .......................................................................4-55
Chapter 5 DeviceNet™ Commissioning
Establishing a DeviceNet Node Address ..........................................5-1
Node Commissioning using Hardware ............................................5-1
Node Commissioning using Software .............................................5-2
Building and Registering an EDS File ..............................................5-3
Table of Contents iii
Using the Node Commissioning Tool Inside RSNetWorx
for DeviceNet ................................................................................. 5-5
System Configuration ................................................................... 5-6
Using Automap feature with default Input and Output (I/O)
Assemblies (Bulletin 280G/281G).................................................... 5-7
Default Input and Output (I/O) Assembly Formats
(Bulletin 280G/281G) ...................................................................... 5-7
Setting the Motor FLA and Overload Trip Class
(Bulletin 280G/281G) ...................................................................... 5-8
Using Automap feature with default Input and Output (I/O)
Assemblies (Bulletin 284G)............................................................. 5-9
Default Input and Output (I/O) Assembly Formats (Bulletin 284G) .... 5-9
Setting the Motor FLA (Bulletin 284G) ........................................... 5-10
193-DCNT Product Overview........................................................ 5-11
User Manual .......................................................................... 5-11
Bill of Material ....................................................................... 5-11
Accessories........................................................................... 5-11
Tools Menu............................................................................ 5-12
Node Comissioning................................................................ 5-12
Chapter 6 Explicit Messaging on DeviceNet™
Chapter 7 Using DeviceLogix™
Chapter 8 ArmorStart® ZIP Configuration
Logic Controller Application Example with Explicit
Messaging ..................................................................................... 6-1
Programming the 1747-SLC .......................................................... 6-2
I/O Mapping ............................................................................ 6-2
Explicit Messaging with SLC .......................................................... 6-3
Setting up the Data File ................................................................. 6-4
Sequence of Events ....................................................................... 6-5
Programming the 1756-ControlLogix ............................................. 6-8
I/O Mapping ............................................................................ 6-8
Explicit Messaging with ControlLogix ............................................. 6-9
Setting Up the MSG Instruction ...................................................... 6-9
DeviceLogix Programming ............................................................. 7-1
DeviceLogix Programming Example ............................................... 7-2
ArmorStart Fault Bit, Status Bit, Outputs and Produced Network Bits in
the DeviceLogix Ladder Editor ....................................................... 7-5
Overview ....................................................................................... 8-1
ZIP Parameter Overview ................................................................ 8-1
Data Production ............................................................................. 8-3
Data Consumption ......................................................................... 8-3
Mapping Consumed Data to the DeviceLogix Data Table. ............... 8-3
Finding ZIP bits in Device Logix Editor........................................... 8-12
iv Table of Contents
Chapter 9 Diagnostics
Overview ........................................................................................9-1
Protection Programming ..........................................................9-1
Fault Display ..................................................................................9-1
Clear Fault .....................................................................................9-2
Fault Codes ....................................................................................9-2
Fault Definitions .............................................................................9-3
Short Circuit ............................................................................9-3
Overload Trip ...........................................................................9-3
Phase Loss ..............................................................................9-3
Phase Short..............................................................................9-3
Ground Fault ............................................................................9-3
Stall .........................................................................................9-3
Control Power ..........................................................................9-3
I/O Fault ..................................................................................9-3
Over Temperature ...................................................................9-3
Phase Imbalance .....................................................................9-3
Over Current.............................................................................9-4
DeviceNet™ Power Loss .........................................................9-4
Internal Communication Fault...................................................9-4
DC Bus Fault ............................................................................9-4
EEPROM Fault .........................................................................9-4
Hardware Fault ........................................................................9-4
Restart Retries .........................................................................9-4
Miscellaneous Faults................................................................9-4
Chapter 10 Troubleshooting
Appendix A Specifications
Appendix B Bulletin 280G/281G CIP Information
Introduction ..................................................................................10-1
Bulletin 280G/281G Troubleshooting .............................................10-2
Bulletin 284G Troubleshooting.......................................................10-5
Fault Definitions .....................................................................10-5
Operation and Troubleshooting of the DB1- Dynamic Brake....10-7
Internal Drive Faults .............................................................10-10
DeviceNet Troubleshooting Procedures ......................................10-14
Control Module Replacement (Bulletin 280G/281G) .....................10-15
Control Module Replacement (Bulletin 284G)...............................10-16
Base Module Replacement (Bulletin 280G/281G).........................10-17
Base Module Replacement (Bulletin 284G) ..................................10-19
Bulletin 280G/281G Specifications ..................................................A-1
Bulletin 284G Specifications............................................................A-6
ArmorConnect™ Three-Phase Power Media ................................A-11
Patchcords ............................................................................A-11
Power Tees & Reducer ..........................................................A-12
Power Receptacles ................................................................A-13
Electronic Data Sheets ...................................................................B-1
DOL Type Product Codes and Name Strings ...................................B-1
DOL Reversing Type Product Codes and Name String .....................B-2
DeviceNet Objects ..........................................................................B-2
Table of Contents v
Identity Object — CLASS CODE 0x0001 .........................................B-3
Identity Objects ..............................................................................B-3
Message Router — CLASS CODE 0x0002 ......................................B-3
DeviceNet Object — CLASS CODE 0x0003 .....................................B-4
Assembly Object — CLASS CODE 0x0004 .....................................B-5
Custom Parameter Based
“Word-wise” I/O Assemblies ..........................................................B-5
“Word-wise” Bit-Packed Assemblies ..............................................B-6
Standard Distributed Motor Controller I/O Assemblies .....................B-7
Standard Distributed Motor Controller Output
(Consumed) Assemblies ..........................................................B-7
Standard Distributed Motor Controller Input
(Produced) Assemblies ............................................................B-8
Connection Object — CLASS CODE 0x0005 .................................B-10
Discrete Input Point Object — CLASS CODE 0x0008 ...................B-14
Discrete Output Point Object — CLASS CODE 0x0009 ..................B-15
Discrete Output Point Object Special Requirements ......................B-16
DOP Instances 1 and 2 Special Behavior ...............................B-16
Parameter Object — CLASS CODE 0x000F ..................................B-18
Parameter Group Object — CLASS CODE 0x0010 ........................B-19
Discrete Input Group Object — CLASS CODE 0x001D ..................B-20
Discrete Output Group Object — CLASS CODE 0x001E ................B-21
Control Supervisor Object -CLASS CODE 0x0029 ..........................B-22
Acknowledge Handler Object — CLASS CODE 0x002b .................B-23
Overload Object — CLASS CODE 0x002c .....................................B-24
DeviceNet Interface Object -CLASS CODE 0x00B4 ........................B-25
Appendix C Bulletin 284G CIP Information
Electronic Data Sheets ...................................................................C-1
VFD Type Product Codes and Name Strings ....................................C-1
DeviceNet Objects ..........................................................................C-2
Identity Object — CLASS CODE 0x0001 .........................................C-2
Identity Objects ..............................................................................C-3
Message Router — CLASS CODE 0x0002 ......................................C-3
DeviceNet Object — CLASS CODE 0x0003 .....................................C-4
Assembly Object — CLASS CODE 0x0004 .....................................C-5
Custom Parameter Based
“Word-wise” I/O Assemblies ..........................................................C-6
“Word-wise” Bit-Packed Assemblies ..............................................C-6
Standard Distributed Motor Controller I/O Assemblies .....................C-8
Standard Distributed Motor Controller Output
(Consumed) Assemblies ..........................................................C-8
Standard Distributed Motor Controller Input
(Produced) Assemblies ............................................................C-9
Inverter Type Distributed Motor Controller Input
(Produced) Assemblies...........................................................C-10
PowerFlex Native Assemblies.................................................C-11
Connection Object — CLASS CODE 0x0005 .................................C-13
Discrete Input Point Object — CLASS CODE 0x0008 ...................C-18
Discrete Output Point Object — CLASS CODE 0x0009 ..................C-19
vi Table of Contents
Discrete Output Point Object Special Requirements ......................C-20
DOP Instances 3 and 4 Special Behavior ...............................C-20
DOP Instances 1, 2, 9, and 10 Special Behavior ....................C-22
Parameter Object — CLASS CODE 0x000F ..................................C-24
Parameter Group Object — CLASS CODE 0x0010 ........................C-25
Discrete Input Group Object — CLASS CODE 0x001D ..................C-26
Discrete Output Group Object — CLASS CODE 0x001E ................C-27
Control Supervisor Object -CLASS CODE 0x0029 ..........................C-28
Acknowledge Handler Object — CLASS CODE 0x002b .................C-29
DeviceNet Interface Object -CLASS CODE 0x00B4 ........................C-30
Appendix D Group Motor Installations
Appendix E Accessories
Appendix F Safety I/O Module and TÜV Requirements
Appendix G Renewal Parts
Appendix H PID Setup
Application of ArmorStart® Controllers in Group Installation ...........D-1
IP67 Dynamic Brake Resistor ..........................................................E-3
ArmorStart Safety-Related Parts...................................................... F-1
ArmorBlock Guard I/O Modules .......................................................F-2
Specifications ..........................................................................F-2
ArmorBlock Guard I/O Recommended Compatible
Cables and Connectors....................................................................F-3
Safety-Related Specifications..........................................................F-6
Maintenance and Internal Part Replacement....................................F-6
Troubleshooting ..............................................................................F-7
Renewal Parts.................................................................................G-1
Exclusive Control.............................................................................H-1
Trim Control....................................................................................H-2
PID Reference and Feedback...........................................................H-3
PID Deadband .................................................................................H-3
PID Preload .....................................................................................H-4
PID Limits .......................................................................................H-4
PID Gains ........................................................................................H-4
Guidelines For Adjusting PID Gains..................................................H-5
Appendix I Step Logic, Basic Logic and Timer/ Counter Functions
Step Logic Using Timed Steps.......................................................... I-2
Step Logic Using Basic Logic Functions............................................ I-3
Timer Function.................................................................................I-4
Counter Function.............................................................................. I-4
Step Logic Parameters.....................................................................I-5
Chapter 1
Product Overview
Introduction This chapter provides a brief overview of the features and
functionality of the Bulletin 280G/281G and 284G ArmorStart® Distributed Motor Controllers.
Description The ArmorStart Distributed Motor Controllers are integrated, pre-
engineered, starters with Bulletin 280G/281G for full-voltage and reversing applications and Bulletin 284G for variable frequency AC drives applications. The ArmorStart offers a robust IP67/NEMA Type 4 enclosure design, which is suitable for water wash down environments.
The modular “plug and play” design offers simplicity in wiring the installation. The quick disconnects for the I/O, communications, and motor connections reduce the wiring time and eliminate wiring errors. The ArmorStart offers as standard, six DC inputs to be used with sensors for monitoring and controlling the application process. The ArmorStart’s LED status indication and built-in diagnostics capabilities allow ease of maintenance and troubleshooting.
The ArmorStart Distributed Motor Controller offers short circuit protection per UL508 and IEC 60947. The ArmorStart is rated for local-disconnect service by incorporating the Bulletin 140 Motor Protector as the local-disconnect, eliminating the need for additional components. The ArmorStart Distributed Motor Controllers are suitable for group motor installations.
Safety ArmorStart The safety version of the ArmorStart provides a safety solution
integrated into DeviceNet Safety installations. The Bulletin 280/281/ 284 Safety ArmorStart achieves Category 4 functionality by using redundant contactors. The Safety ArmorStart offers a quick connects via the gland plate to the 1732DS-IB8XOBV4 safety I/O module. The Bulletin 1732DS Safety I/O inputs will monitor the status of the safety rated contactors inside the ArmorStart. The Bulletin 1732DS Safety I/O outputs to provide 24V DC power for control power to the ArmorStart.
Note: The Bulletin 280/281/284 Safety ArmorStart is suitable for
safety applications up to Safety Category 4PL e (TÜV assessment per ISO 13849-1:2008). T available upon request.
Note: For additional information regarding the
1732DS-IB8XOBV4 safety I/O module, see publication 1791DS-UM001*-EN-P.
ÜV compliance letter is
1-2 Product Overview
00%
ge
)
Operation The ArmorStart Distributed Motor Controllers can operate three-
phase squirrel-cage induction motors as follows:
Bulletin 280G/281G: up to 10 Hp (7.5 kW) @ 460VAC, 50/60 Hz. Bulletin 284G: up to 5 Hp (3.0 kW) @ 460V AC. Bulletin 1000: 7.5 Hp (5.5 kW), 10 Hp (7.5 kW) and 15 Hp (11 kW) @ 460VAC, 50/60 Hz.
The ArmorStart Distributed Motor Controller will accept a control power input of 120VAC.
Mode of Operation Bulletin 280G/281G
Full-Voltage Start
This method is used in applications requiring across-the-line starting, in which full inrush current and locked-rotor torque are realized. The ArmorStart Bulletin 280G offers full-voltage starting and the Bulletin 281G offers full-voltage starting for reversing applications.
1
Percent
Volta
Time (seconds
Bulletin 284G
Sensorless Vector Control
Sensorless Vector Control provides exceptional speed regulation
and very high levels of torque across the entire speed range of the
drive
The Autotune feature allows the Bulletin 284G ArmorStart
Distributed Motor Controller to adapt to individual motor
characteristics.
To select this method of operation, select V for the Mode of
Operation listed in the catalog structure. See
Publication 280-SG001*.
Description of Features Overload Protection
Class 15 Overload Curves
1
100
10000
0 100 200 300 400 500 600 700
Multiples for Full Load Current
Approximate Trip Time (sec)
Cold
Hot
Class 10 Ove rload Curv es
1
10
100
1000
10000
0 100 200 300 400 500 600 700
Multiples of Full Load Current
Approximate Trip Time (sec)
Cold
Hot
Class 20 Ove rload Curv es
1
100
10000
0 100 200 300 400 500 600 700
Multiples of Full Load Current
Approximate Trip Time (sec)
Cold
Hot
Class 10
Class 15
Class 20
%
%
of
%
The ArmorStart Distributed Motor Controller incorporates, as standard, electronic motor overload protection. This overload
protection is accomplished electronically with an I ArmorStart’s overload protection is programmable via the communication network, providing the user with flexibility.
The Bulletin 280G/281G overload trip class can be selected for class 10, 15, 20 protection. Ambient insensitivity is inherent in the electronic design of the overload.
Figure 1.1 Overload Trip Curves
Product Overview 1-3
2
t algorithm. The
1-4 Product Overview
% of P132 (Motor NP Hertz) % of P132 (Motor NP Hertz)
% of P132 (Motor NP Hertz)
% of P133 (Motor OL Current)
% of P133 (Motor OL Current)
% of P133 (Motor OL Current)
The Bulletin 284G ArmorStart Distributed Motor Controller incorporates, as standard, electronic motor overload protection. This
2
overload protection is accomplished electronically with an I
t algorithm. The ArmorStart’s overload protection is programmable via the communication network providing the user with flexibility. Programming the Motor OL Current parameter provides class 10 overload protection for the Bulletin 284G Distributed Motor Controller. Ambient insensitivity is inherent in the electronic design of the overload.
Figure 1.2 Overload Trip Curves
Product Overview 1-5
LED Status Indication
The LED Status Indication provides 4 status LEDs and a Reset button. The LEDs provide status indication for the following:
•POWER LED
The LED is illuminated solid green when control power is present and with the proper polarity
RUN LED
This LED is illuminated solid green when a start command and control power are present
•NETWORK LED
This bi-color (red/green) LED indicates the status of the communication link
•FAULT LED
Indicates Controller Fault (Trip) condition
The “Reset Button” acts as a local trip reset.
Figure 1.3 Status Indication and Reset
Fault Diagnostics
Fault diagnostics capabilities built in the ArmorStart Distributed Motor Controller help you pinpoint a problem for easy troubleshooting and quick re-starting.
Fault Indication
Short Circuit X X Phase Imbalance X
Overload X X Miscellaneous Fault X
Phase Loss X X Brake Fuse Detection X
Control Power Loss X X Internal Comm. Fault X
Control Power Fuse Detection X X DC Bus Fault X
I/O Fault X X Ground Fault X
Over Temperature X X Overcurrent X
DeviceNet™ Power Loss X X Restart Retries X
EEprom Fault X X Stall X
Hardware Fault X X Phase Short X
Available on Bulletin:
Fault Indication
280G/281G 284G 280G/281G 284G
Available on Bulletin:
1-6 Product Overview
Inputs
The inputs are single-keyed (2 inputs per connector), which are sourced from DeviceNet power (24V DC), with LED status indication.
Gland Plate Entrance
The ArmorStart product offers connectivity to the ArmorConnect™ power media. Receptacles are provided for connectivity to both three­phase and control power media.
ArmorStart with DeviceNet Network Capabilities
The ArmorStart Distributed Motor Controller delivers advanced capabilities to access parameter settings and provides fault diagnostics, and remote start-stop control. DeviceNet is the communication protocol, provided with the ArmorStart Bulletin 280G/281G or 284G Distributed Motor Controller.
DeviceLogix™
DeviceLogix is a stand-alone Boolean program that resides within the ArmorStart Distributed Motor Controller. DeviceLogix is programmed using Boolean math operations, such as, AND, OR, NOT, Timers, Counters, and Latches. DeviceLogix can run as a stand­alone application, independent of the network. However, 24V DC must be supplied at the DeviceNet connector to power the inputs.
Peer to Peer Communications (ZIP)
The zone control capabilities of ArmorStart Distributed Motor Controllers is ideal for large horsepower (0.5…15 Hp) motored conveyors. The ArmorStart Distributed Motor Controllers have built­in DeviceNet communications, DeviceLogix technology, and the added Zone Interlocking Parameters (ZIP) which allow one ArmorStart to receive data directly, from up to four other DeviceNet nodes, without going through a network scanner. These direct communications between conveyor zones are beneficial in a merge, diverter, or accumulation conveyor application.
EMI Filter (Bulletin 284G only)
The EMI Filter is required if the Bulletin 284G ArmorStart Distributed Motor Controller must be CE-compliant. A shielded 4-conductor patchcord or cordset no longer than 14 meters, must be used to comply with the CE requirement.
Product Overview 1-7
Dynamic Brake Resistor (Bulletin 284G only)
The IP67 Dynamic Brake Resistor plug and play design offers simplicity in writing and installation. The factory installed option of DB1 must be selected in order to have the quick disconnect connectivity. The cable length of the IP67 Dynamic Brake Resistor is available in two lengths, 0.5 meter and 1 meter. See Appendix G, Accessories, for available IP67 Dynamic Brake Resistors.
Note: The IP67 Dynamic Brake Resistor is used only with the -DB1
factory-installed option.
Control Brake Contactor
An internal contactor is used to switch the electromechanical motor brake On/Off. The motor brake is powered from the control voltage circuit.
1-8 Product Overview
Notes:
Chapter 2
Installation and Wiring
Receiving It is the responsibility of the user to thoroughly inspect the equipment
before accepting the shipment from the freight company. Check the item(s) received against the purchase order. If any items are damaged, it is the responsibility of the user not to accept delivery until the freight agent has noted the damage on the freight bill. Should any concealed damage be found during unpacking, it is again the responsibility of the user to notify the freight agent. The shipping container must be left intact and the freight agent should be requested to make a visual inspection of the equipment.
Unpacking Remove all packing material, wedges, or braces from within and
around the starter. Remove all packing material from device(s).
Inspecting After unpacking, check the nameplate catalog number(s) against the
purchase order.
Storing The controller should remain in its shipping container prior to
installation. If the equipment is not to be used for a period of time, it must be stored according to the following instructions in order to maintain warranty coverage.
Store in a clean, dry location.
Store within an ambient temperature range of –25…+85 °C
(–13…+185 °F).
Store within a relative humidity range of 0…95%,
noncondensing.
Do not store equipment where it could be exposed to a corrosive
atmosphere.
Do not store equipment in a construction area.
2-2 Installation and Wiring
ATTENTION
!
ATTENTION
!
ATTENTION
!
ATTENTION
!
ATTENTION
!
General Precautions In addition to the precautions listed throughout this manual, the
following statements, which are general to the system, must be read and understood.
The controller contains ESD (electrostatic discharge)-sensitive parts and assemblies. Static control precautions are required when installing, testing, servicing, or repairing the assembly. Component damage may result if ESD control procedures are not followed. If you are not familiar with static control procedures, refer to Publication 8000-4.5.2, Guarding against Electrostatic Discharge, or any other applicable ESD protection handbooks.
An incorrectly applied or installed controller can damage components or reduce product life. Wiring or application errors, such as undersizing the motor, incorrect or inadequate AC supply, or excessive ambient temperatures, may result in malfunction of the system.
Precautions for Bulletin 280G/281G Applications
Only personnel familiar with the controller and associated machinery should plan or implement the installation, startup, and subsequent maintenance of the system. Failure to do this may result in personal injury and/or equipment damage.
To prevent electrical shock, open disconnect prior to connecting and disconnecting cables. Risk of shock - environment rating may not be maintained with open receptacles.
Only qualified personnel familiar with adjustable frequency AC drives and associated machinery should plan or implement the installation, startup, and subsequent maintenance of the system. Failure to do this may result in personal injury and/or equipment damage.
Precautions for Bulletin 284G
ATTENTION
!
ATTENTION
!
Applications
Installation and Wiring 2-3
The drive contains high voltage capacitors which take time to discharge after removal of mains supply. Before working on drive, ensure isolation of mains supply from line inputs (R, S, T [L1, L2, L3]). Wait three minutes for capacitors to discharge to safe voltage levels. Failure to do so may result in personal injury or death. Darkened display LEDs are not an indication that capacitors have discharged to safe voltage levels. Risk of shock-environment rating may not be maintained with open receptacles.
Only qualified personnel familiar with adjustable frequency AC drives and associated machinery should plan or implement the installation, startup, and subsequent maintenance of the system. Failure to do this may result in personal injury and/or equipment damage.
2-4 Installation and Wiring
Dimensions for Bulletin 280G/281G Dimensions are shown in millimeters (inches). Dimensions are not
intended to be used for manufacturing purposes. All dimensions are subject to change.
Figure 2.1 Dimensions for IP67/NEMA Type 4 with ArmorConnect
Connectivity
Installation and Wiring 2-5
Motor Connection
DeviceNet Connection (Mini/M18)
Local Disconnect
6 Inputs
(Micro/M12)
Ground Terminal
Control Brake
Control Power Receptacle
3-Phase Power Receptacle
LED Status Indication
Figure 2.2 Bulletin 280G/281G ArmorStart® with DeviceNet™
Communication Protocol
2-6 Installation and Wiring
Dimensions for Bulletin 284G Dimensions are shown in millimeters (inches). Dimensions are not
intended to be used for manufacturing purposes. All dimensions are subject to change.
Figure 2.3 Dimensions for 2 Hp (1.5 kW) and below @ 460V AC, IP67/NEMA
Type 4 with ArmorConnect connectivity
Installation and Wiring 2-7
Dimensions for Bulletin 284G, Continued
Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. All dimensions are subject to change.
Figure 2.4 Dimensions for 3 Hp (2.2 kW) and above @ 460V AC, IP67/NEMA
Type 4 with ArmorConnect connectivity
2-8 Installation and Wiring
Dimensions for Bulletin 1000 Dimensions are shown in millimeters (inches). Dimensions are not
intended to be used for manufacturing purposes. All dimensions are subject to change.
Figure 2.5 Dimensions for 7.5 Hp (5.5 kW) and 10 Hp (7.5 kW) @ 460V AC,
IP67/NEMA Type 4 with ArmorConnect Connectivity
Installation and Wiring 2-9
Dimensions for Bulletin 1000, Continued
Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. All dimensions are subject to change.
Figure 2.6 Dimensions for 15 Hp (11 kW) @ 460V AC, IP67/NEMA Type 4 with
ArmorConnect Connectivity
2-10 Installation and Wiring
LED Status Indication
Motor
Connector
Dynamic Brake Connector
Control Brake Connector
Ground Te r mi n a l
3-Phase Receptacle
Control Power Receptacle
DeviceNet Connection
(Mini/M18)
Local Disconnect
6 Inputs
(Micro/M12)
Figure 2.7 Bulletin 284G ArmorStart
Figure 2.8 Bulletin 1000 ArmorStart
Installation and Wiring 2-11
2-12 Installation and Wiring
Figure 2.9 Bulletin 1000 ArmorStart
Wiring Power, Control, and Ground Wiring
Table 2.1 provides the power, control, safety inputs, and ground wire capacities, and the tightening torque requirements. The power, control, ground, and safety monitor terminals will accept a maximum of two wires per terminal.
Table 2.1 Power, Control, Safety Input, Ground Wire Size, and Torque
Specifications
Terminals Wire Size Torque Wire Strip Length
Installation and Wiring 2-13
Power
and
Ground
Control and Safety
Inputs
Primary/Secondary
Terminal:
1.5…4.0 mm
(#16 …#10 AWG)
1.0 mm (#18…#10 AWG)
2
…4.0 mm2
2
Primary Terminal:
Secondary Terminal:
10.8 lb.-in. (1.2 N•m)
4.5 lb.-in
(0.5 N•m)
6.2 lb.-in
(0.7 N•m)
0.35 in. (9 mm)
0.35 in. (9 mm)
2-14 Installation and Wiring
Terminal Designations for Bulletins 280G, 281G, and 284G
As shown in the next figure, the ArmorStart Distributed Motor Controller contains terminals for power, control, and ground wiring. Access can be gained by removing the terminal access cover plate.
Figure 2.10 ArmorStart Power, Control and Terminals
Table 2.2 Power, Control, and Ground Terminal Designations
Terminal Designations No. of Poles Description
A1 (+) 2 Control Power Input
A2 (-) 2 Control Power Common
PE 2 Ground 1/L1 2 Line Power Phase A 3/L3 2 Line Power Phase B 5/L5 2 Line Power Phase C
Installation and Wiring 2-15
Dimensions for Bulletin 280G Safety Product
Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. All dimensions are subject to change.
Figure 2.11 Dimensions for Bulletin 280G Safety Product
2-16 Installation and Wiring
Dimensions for Bulletin 281G Safety Product
Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. All dimensions are subject to change.
Figure 2.12 Dimensions for Bulletin 281G Safety Product
Installation and Wiring 2-17
Dimensions for Bulletin 284G Safety Product
Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. All dimensions are subject to change.
Figure 2.13 Dimensions for 2 Hp (1.5 kW) and below @ 460V AC, IP67/NEMA
Type 4 with ArmorConnect connectivity
2-18 Installation and Wiring
Dimensions for Bulletin 284G Safety Product, Continued
Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. All dimensions are subject to change.
Figure 2.14 Dimensions for 3 Hp (2.2 kW) and 5 Hp (3.0 kW) and below @
460V AC, IP67/NEMA Type 4 with ArmorConnect connectivity
Installation and Wiring 2-19
Dimensions for Bulletin 1000 Safety Product
Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. All dimensions are subject to change.
Figure 2.15 Dimensions for 7.5 Hp (5.5 kW) and 10 Hp (7.5 kW) @ 460V AC,
IP67/NEMA Type 4 with ArmorConnect Connectivity
2-20 Installation and Wiring
Dimensions for Bulletin 1000 Safety Product, Continued
Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. All dimensions are subject to change.
Figure 2.16 Dimensions for 15 Hp @ 460V AC, IP67/NEMA Type 4 with
ArmorConnect Connectivity
Figure 2.17 Bulletin 280G Safety ArmorStart
Motor Connection
DeviceNet Connection
(Mini/M18)
Local Disconnect
6 Inputs
(Micro/M12)
A1/A2
Control Brake
Control Power Receptacle
3-Phase Power Receptacle
LED Status Indication
SM
Installation and Wiring 2-21
2-22 Installation and Wiring
Motor Connection
DeviceNet Connection (Mini/M18)
Local Disconnect
6 Inputs
(Micro/M12)
3-Phase Power Receptacle
LED Status Indication
A1/A2
Control Power
SM
Control Brake
Figure 2.18 Bulletin 281G Safety ArmorStart
Figure 2.19 Bulletin 284G Safety ArmorStart
Motor Connection
DeviceNet Connection
(Mini/M18)
Local Disconnect
6 Inputs
(Micro/M12)
Dynamic Brake
3-Phase Power Receptacle
LED Status Indication
A1/A2
Control Power
SM
Control Brake
Installation and Wiring 2-23
2-24 Installation and Wiring
Figure 2.20 Bulletin 1000 Safety ArmorStart
Figure 2.21 Bulletin 1000 ArmorStart
Installation and Wiring 2-25
2-26 Installation and Wiring
Safety Terminal Designations As shown in the next figure, the ArmorStart Distributed Motor Controller
contains terminals for power, safety I/O inputs, control, and ground wiring. Access can be gained by removing the terminal access cover plate.
Figure 2.22 Bulletin 280G ArmorStart Safety Power, Control and Terminals
Table 2.3 Power, Control, Safety Monitor, and Ground Terminal Designations
Terminal Designations No. of Poles Description
SM1 2 Safety I/O Input SM2 2 Safety I/O Input
A1 (+) 2 Control Power Input
A2 (-) 2 Control Power Common
PE 2 Ground 1/L1 2 Line Power Phase A 3/L3 2 Line Power Phase B 5/L5 2 Line Power Phase C
Installation and Wiring 2-27
Safety Terminal Designations, Continued
As shown in the next figure, the ArmorStart Distributed Motor Controller contains terminals for power, safety I/O inputs, control, and ground wiring. Access can be gained by removing the terminal access cover plate.
Figure 2.23 Bulletin 281G ArmorStart Safety Power, Control and Terminals
Table 2.4 Power, Control, Safety Monitor, and Ground Terminal Designations
Terminal Designations No. of Poles Description
SM1 2 Safety I/O Input SM2 2 Safety I/O Input
A1 (+) 2 Control Power Input
A2 (-) 2 Control Power Common
PE 2 Ground 1/L1 2 Line Power Phase A 3/L3 2 Line Power Phase B 5/L5 2 Line Power Phase C
2-28 Installation and Wiring
Safety Terminal Designations, Continued
As shown in the next figure, the ArmorStart Distributed Motor Controller contains terminals for power, safety I/O inputs, control, and ground wiring. Access can be gained by removing the terminal access cover plate.
Figure 2.24 ArmorStart Safety 2 Hp Power, Control and Terminals
Table 2.5 Power, Control, Safety Monitor, and Ground Terminal Designations
Terminal Designations No. of Poles Description
SM1 2 Safety I/O Input SM2 2 Safety I/O Input
A1 (+) 2 Control Power Input
A2 (-) 2 Control Power Common
PE 2 Ground 1/L1 2 Line Power Phase A 3/L3 2 Line Power Phase B 5/L5 2 Line Power Phase C
ArmorConnect Power Media Description
Encl
The ArmorConnect power media offers both three-phase and control power cable system of cord sets, patch cords, receptacles, tees, reducers and accessories to be utilized with the ArmorStart Distributed Motor Controller. These cable system components allow quick connection of ArmorStart Distributed Motor Controllers, there by reducing installation time. They provide for repeatable, reliable connection of the three-phase and control power to the ArmorStart Distributed Motor Controller and motor by providing a plug-and-play environment that also avoids system mis-wiring. When specifying power media for use with the ArmorStart Distributed Motor Controllers (Bulletin 280G/281G and 284G) use only the Bulletin 280 ArmorConnect power media.
Figure 2.25 Three-Phase Power System Overview
osure
Bulletin 1492FB
Branch Circuit
Protective Device
Bulletin 1606
Power Supply
1606-XLSDNET4
DeviceNet
Power Supply
Installation and Wiring 2-29
PLC
Bulletin 280/281 ArmorStart
RESET
Bulletin 280/281 ArmorStart
RESET
Three-Phase Power Trunk- PatchCord cable with integral female or male connector on each end
Example Part Number: 280-PWR35A-M*
Three-Phase Drop Cable- PatchCord cable with integral female or male connector on each end
Example Part Number: 280-PWR35A-M*
Three-Phase Power Tee and Reducer -
Tee connects to a single drop line to trunk with quick change connectors – Part Number: 280-T35 Reducing Tee connects to a single drop line (Mini) to trunk (Quick change) connector – Part Number: 280-RT35
Three-Phase Power Receptacles -
Female receptacles are a panel mount connector with flying leads – Part Number: 280-M35F-M1
Bulletin 284 ArmorStart
2-30 Installation and Wiring
RESET
Bulletin 280/281 ArmorStart
Bulletin 284 ArmorStart
RESET
Bulletin 280/281 ArmorStart
PLC
Bulletin 1492FB
Branch Circuit
Protective Device
Enclosure
Bulletin 1606
Power Supply
1606-XLSDNET4
DeviceNet
Power Supply
Figure 2.26 Control Power Media System Overview
Control Power Media Patchcords - PatchCord cable with integral female or male connector on each end Example Part Number: 889N-F3AFNU-*F
Control Power Tees - The Control Power tee (Part Number: 898N-33PB-N4KF) is used with a patchcord to connect to the ArmorStart Distributed Motor
Controller.
Control Power Receptacles - Female receptacles are a panel mount connector with flying leads – Part Number: 888N-D3AF1-*F
Installation and Wiring 2-31
Control Power
Receptacle
Ground
Term in al
Three-Phase
Power
Receptacle
Term in al Designations
Description Color Code
A1 (+) Control Power Input Black A2 (-) Control Power Common White PE Ground Green/Yellow 1/L1 Line Power - Phase A Black 3/L2 Line Power - Phase B White 5/L3 Line Power - Phase C Red
ArmorStart with ArmorConnect Connectivity
Terminal Designations
ArmorConnect Cable Ratings
The ArmorConnect power media cables are rated per UL Type TC 600V 90 °C Dry 75 °C Wet, Exposed Run (ER) or MTW 600V 90 °C or STOOW 105 °C 600V - CSA STOOW 600V FT2.
2-32 Installation and Wiring
Ground
Termi na l
Three-Phase
Power
Recepale
120V AC
Aux. Powr
for
Conto Brake
Safety Monitor
Input from
1732DS Safey
I/O Module Inpt
A1/A2 -24V DC
Control Power rm
1732DS Safety
I/O Module Outu
Term in al Designations
Description Color Code
SM1 Safety Monitor Input Brown SM2 Safety Monitor Input White A1 (+) Control Power Input Brown A2 (-) Control Power Common Blue PE Ground Green/Yellow 1/L1 Line Power - Phase A Black 3/L2 Line Power - Phase B White 5/L3 Line Power - Phase C Red
ArmorStart Safety with ArmorConnect Connectivity
Terminal Designations
ArmorConnect Cable Ratings
The ArmorConnect power media cables are rated per UL Type TC 600V 90 °C Dry 75 °C Wet, Exposed Run (ER) or MTW 600V 90 °C or STOOW 105 °C 600V - CSA STOOW 600V FT2.
Installation and Wiring 2-33
Branch Circuit Protection Requirements for ArmorConnect Three-Phase Power Media
When using ArmorConnect three-phase power media, fuses can be used for the motor branch circuit protective device, for the group motor installations. The following fuse types are recommended: Class CC, T, or J type fuses. A 100 A circuit breaker (Allen-Bradley140 H-Frame) can be used for the motor branch protective device, for the group motor installations when using only the following ArmorConnect Power Media components: 280-M35M-M1, 280-M35F-M1, 280-T35, and 280-PWRM35*-M*.
Maximum Ratings
Voltage (V) 480Y/277 Sym. Amps RMS 65 kA Fuse 100 A Circuit Breaker 100 A
Group Motor Installations for USA and Canada Markets
Wiring and Workmanship Guidelines
The ArmorStart Distributed Motor Controllers are listed for use with each other in group installations per NFPA 79, Electrical Standard for Industrial Machinery. When applied according to the group motor installation requirements, two or more motors, of any rating or controller type, are permitted on a single branch circuit. Group Motor Installation has been successfully used for many years in the USA and Canada.
Note: For additional information regarding group motor
installations with the ArmorStart Distributed Motor Controller, see Appendix D.
In addition to conduit and seal-tite raceway, it is acceptable to utilize cable that is dual rated Tray Cable, Type TC-ER and Cord, STOOW, for power and control wiring on ArmorStart installations. In the USA and Canada installations, the following guidance is outlined by the NEC and NFPA 79.
2-34 Installation and Wiring
In industrial establishments where the conditions of maintenance and supervision ensure that only qualified persons service the installation, and where the exposed cable is continuously supported and protected against physical damage using mechanical protection, such as struts, angles, or channels, Type TC tray cable that complies with the crush and impact requirements of Type MC (Metal Clad) cable and is identified for such use with the marking Type TC-ER (Exposed Run)* shall be permitted between a cable tray and the utilization equipment or device as open wiring. The cable shall be secured at intervals not exceeding 1.8 m (6 ft) and installed in a “good workman­like” manner. Equipment grounding for the utilization equipment shall be provided by an equipment grounding conductor within the cable.
*Historically cable meeting these crush and impact requirements were designated and marked “Open Wiring”. Cable so marked is equivalent to the present Type TC-ER and can be used.
While the ArmorStart is intended for installation in factory floor environments of industrial establishments, the following must be taken into consideration when locating the ArmorStart in the application: Cables, including those for control voltage including 24V DC and communications, are not to be exposed to an operator or building traffic on a continuous basis. Location of the ArmorStart to minimize exposure to continual traffic is recommended. If location to minimize traffic flow is unavoidable, other barriers to minimize inadvertent exposure to the cabling should be considered. Routing cables should be done in such a manner to minimize inadvertent exposure and/or damage.
Additionally, if conduit or other raceways are not used, it is recommended that strain relief fittings be utilized when installing the cables for the control and power wiring through the conduit openings.
The working space around the ArmorStart may be minimized as the ArmorStart does not require examination, adjustment, servicing or maintenance while energized. In lieu of this service, the ArmorStart is meant to be unplugged and replaced after proper lockout/tag-out procedures have been employed.
DeviceNet Network Installation The ArmorStart Distributed Motor Controller contains the equivalent
of 30 in. (0.76 m) of DeviceNet drop cable's electrical characteristics and therefore 30 in. of drop cable must be included in the DeviceNet drop cable budget for each ArmorStart in addition to actual drop cable required for the installation.
Other DeviceNet System Design Considerations
The separation of the control power and DeviceNet power is recommended as a good design practice. This minimizes the load on the DeviceNet supply, and prevents transients which may be present on the control power system from influencing the communication controls.
Installation and Wiring 2-35
Electromagnetic Compatibility
(EMC)
The following guidelines are provided for EMC installation compliance.
General Notes (Bulletin 284G only)
The motor Cable should be kept as short as possible in order to avoid electromagnetic emission as well as capacitive currents
Conformity of the drive with CE EMC requirements does not guarantee an entire machine installation complies with CE EMC requirements. Many factors can influence total machine/ installation compliance.
Using an EMI filter with any drive rating, may result in relatively high ground leakage currents. Therefore, the filter must only be used in installations and solidly grounded (bonded) to the building power distribution ground. Grounding must not rely on flexible cables and should not include any form of plug or socket that would permit inadvertent disconnection. Some local codes may require redundant ground connections. The integrity of all connections should be periodically checked.
Grounding
Connect a grounding conductor to the terminal provided as standard on each ArmorStart Distributed Motor Controller. Refer to Table 2.2 for grounding provision location. There is also an externally available ground terminal. Refer to Figure 2.2 and Figure 2.7.
Wiring
Wire in an industrial control application can be divided into three groups: power, control, and signal. The following recommendations for physical separation between these groups is provided to reduce the coupling effect.
Minimum spacing between different wire groups in the same tray should be 6 in. (16 cm).
Wire runs outside an enclosure should be run in conduit or have shielding/armor with equivalent attenuation.
Different wire groups should be run in separate conduits.
Minimum spacing between conduits containing different wire groups should be 3 in. (8 cm).
2-36 Installation and Wiring
Notes:
Chapter 3
Bulletin 280G/281G Programmable Parameters
Introduction This chapter describes each programmable parameter and its
function.
Parameter Programming
Each Distributed Motor Controller type will have a common set of parameters followed by a set of parameters that pertain to the individual starter type.
Refer to Chapter 5, DeviceNet™ Commissioning for instructions in using RSNetWorx™ for DeviceNet to modify parameter settings.
Important: Resetting the Factory Default Values Parameter 47,
Set to Defaults, allows the installer to reset all parameters to the factory default values. It also resets the MAC ID to its factory default after DeviceNet Power is cycled if switches are set >63.
Important: Parameter setting changes downloaded to the
ArmorStart™ take effect immediately, even during a “running” status.
Important: Parameter setting changes made in a configuration tool
such as RSNetWorx for DeviceNet do not take effect in the ArmorStart until the installer applies or downloads the new settings to the device.
3-2 Bulletin 280G/281G Programmable Parameters
Parameter Group Listing The Bulletin 280G/281G ArmorStart contains eight parameter
groups. The parameters shown in the DeviceLogix, DeviceNet, Starter Protection, User I/O, Misc. Parameter, ZIP Parameters, Starter Display and Starter Setup, are discussed in this chapter.
Table 3.1 Parameter Group Listing
DeviceLogix DeviceNet
1 Hdw Inputs 10 Autobaud Enable 22 Breaker Type 30 Off-to-On Delay 45 Keypad Mode 67 AutoRun Zip 101 Phase A Current 106 FLA Setting 2 Network Inputs 11 Consumed IO Assy 23 PrFltResetMode 31 On-to-Off Delay 46 Keypad Disable 68 Zone Produced EPR 102 Phase B Current 107 Overload Class 3 Network Outputs 12 Produced IO Assy 24 Pr Fault Enable 32 In Sink/Source 47 Set To Defaults 69 Zone Produced PIT 103 Phase C Current 108 OL Reset Level 4 Trip S tat us 13 Prod Assy Word 0 25 Pr Fault Reset 56 Base Enclosure 70 Zone #1 MacId 104 Average Current 5 Starter Status 14 Prod Assy Word 1 26 StrtrDN FltState 57 Base Option 71 Zone #2 MacId 105% Therm Utilized 6 DNet Status 15 Prod Assy Word 2 27 StrtrDN FltValue 58 Wiring Option 72 Zone #3 MacId 7 Starter Command 16 Prod Assy Word 3 28 StrtrDN IdlState 59 Starter Enclosure 73 Zone #4 MacId 8 Network Override 17 Consumed IO Size 29 StrtrDN IdlValue 60 Starter Options 74 Zone #1 Health 9 Comm Override 18 Produced IO Size 61 Last PR F
19 Starter COS Mask 62 W 20 Net Out COS Mask 77 Zone #4 Health 21 DNet Voltage 78 Zone #1 Mask
Starter
Protection
ault 75 Zone #2 Health
arning Status 76 Zone #3 Health
User I/O Misc. ZIP Parameters Starter Display Starter Setup
79 Zone #2 Mask 80 Zone #3 Mask 81 Zone #4 Mask 82 Zone #1 Offset 83 Zone #2 Offset 84 Zone #3 Offset 85 Zone #4 Offset 86 Zone #1 EPR 87 Zone #2 EPR 88 Zone #3 EPR 89 Zone #4 EPR 90 Zone #1 Control 91 Zone #2 Control 92 Zone #3 Control 93 Zone #4 Control 94 Zone #1 Key 95 Zone #2 Key 96 Zone #3 Key 97 Zone #4 Key 98 Device Value Key 99 Zone Ctrl Enable
DeviceLogix™ Group
Hdw Inputs
This parameter provides status of hardware inputs
Parameter Number 1
Access Rule GET
Data Type WORD
Group DeviceLogix
Units — Minimum Value 0 Maximum Value 15
Default Value 0
Bulletin 280G/281G Programmable Parameters 3-3
Bit
543210 ————— XInput 0 ———— X —Input 1 — X Input 2 —— X ———Input 3 — X ————Input 4
X —————Input 5
Network Inputs
This parameter provides status of network inputs
1514131211109876543210
——————————————— X Net Input 0 —————————————— X — Net Input 1 ————————————— X —— Net input 2 ———————————— X ——— Net Input 3 ——————————— X ———— Net Input 4 —————————— X ————— Net Input 5 ————————— X —————— Net Input 6 ———————— X ——————— Net Input 7 ——————— X ———————— Net Input 8 —————— X ————————— Net Input 9 ————— X —————————— Net Input 10 ———— X ——————————— Net Input 11 ——— X ———————————— Net Input 12 —— X ————————————— Net Input 13 — X —————————————— Net Input 14
X ——————————————— Net Input 15
Parameter Number 2
Access Rule GET
Data Type WORD
Group DeviceLogix
Units — Minimum Value 0 Maximum Value 65535
Default Value 0
Bit
Function
Function
Network Outputs
This parameter provides status of network outputs
Parameter Number 3
Access Rule GET
Data Type WORD
Group DeviceLogix
Units — Minimum Value 0 Maximum Value 32767
Default Value 0
3-4 Bulletin 280G/281G Programmable Parameters
Bit
Function
14131211109876543210
—————————————— X Net Output 0 ————————————— X — Net Output 1 ———————————— X —— Net Output 2 ——————————— X ——— Net Output 3 —————————— X ———— Net Output 4 ————————— X ————— Net Output 5 ———————— X —————— Net Output 6 ——————— X ——————— Net Output 7 —————— X ———————— Net Output 8 ————— X ————————— Net Output 9 ———— X —————————— Net Output 10 ——— X ——————————— Net Output 11 —— X ———————————— Net Output 12 — X ————————————— Net Output 13
X —————————————— Net Output 14
Trip Status
Parameter Number 4
Access Rule GET This parameter provides trip identification
Data Type WORD
Group DeviceLogix Setup
Units — Minimum Value 0 Maximum Value 16383
Default Value 0
Bit
Function
131211109876543210
————————————— X Short Circuit ———————————— X — Overload ——————————— X —— Phase Loss —————————— X ——— Reserved ————————— X ———— Reserved ———————— X ————— Control Power ——————— X —————— I/O Fault —————— X ——————— Over Temperature ————— X ———————— Phase Imbalance ———— X ————————— Dnet Power Loss ——— X —————————— Reserved —— X ——————————— Reserved — X ———————————— EEprom
X ————————————— HW Fault
Bulletin 280G/281G Programmable Parameters 3-5
Starter Status
This parameter provides the status of the starter
131211109876543210
————————————— X Tripped ———————————— X — Warning ——————————— X —— Running Fwd —————————— X ——— Running Rev ————————— X ———— Ready ———————— X ————— Net Ctl Status ——————— X —————— Reserved —————— X ——————— At Reference ————— X ———————— Reserved ———— X ————————— Reserved ——— X —————————— Reserved —— X ——————————— Keypad Hand — X ———————————— HOA Status
X ————————————— 140M On
Parameter Number 5
Access Rule GET
Data Type WORD
Group DeviceLogix
Units — Minimum Value 0 Maximum Value 16383
Default Value 0
Bit
Function
DNet Status
This parameter provides status of the DeviceNet connection
Parameter Number 6
Access Rule GET
Data Type WORD
Group DeviceLogix
Units — Minimum Value 0 Maximum Value 32, 767
Default Value 0
3-6 Bulletin 280G/281G Programmable Parameters
Bit
1514131211109876543210
——————————————— X Explicit Connection —————————————— X — I/O Connection ————————————— X —— Explicit Fault ———————————— X ——— I/O Fault ——————————— X ———— I/O Idle ———————— X X X ————— Reserved ——————— X ———————— ZIP 1 Cnxn —————— X ————————— ZIP 1 Flt ————— X —————————— ZIP 2 Cnxn ———— X ——————————— ZIP 2 Flt ——— X ———————————— ZIP 3 Cnxn —— X ————————————— ZIP 3 Flt — X —————————————— ZIP 4 Cnxn
X ——————————————— ZIP 4 Flt
Starter Command
The parameter provides the status of the starter command.
Parameter Number 7
Access Rule GET
Data Type WORD
Group DeviceLogix
Units — Minimum Value 0 Maximum Value 255
Default Value 0
Function:
Bit
76543210
——————— X Run Fwd —————— X — Run Rev ————— X —— Fault Reset ———— X ——— Reserved ——— X ———— Reserved —— X ————— Reserved — X —————— Reserved
X ——————— Reserved
Network Override
This parameter allows for the local logic to override a Network fault 0 = Disable 1 = Enable
Parameter Number 8
Access Rule GET/SET
Data Type BOOL
Group DeviceLogix
Units — Minimum Value 0 Maximum Value 1
Default Value 0
Function:
Bulletin 280G/281G Programmable Parameters 3-7
DeviceNet Group
Comm Override
This parameter allows for local logic to override the absence of an I/O connection 0 = Disable 1 = Enable
Autobaud Enable
When this parameter is enabled, the device will attempt to determine the network baud rate and set its baud rate to the same, provided network traffic exists. At least one node with an established baud rate must exist on the network for autobaud to occur. 0 = Disable 1 = Enable
Parameter Number 9
Access Rule GET/SET
Data Type BOOL
Group DeviceLogix
Units — Minimum Value 0 Maximum Value 1
Default Value 0
Parameter Number 10
Access Rule GET/SET
Data Type BOOL
Group DeviceNet
Units — Minimum Value 0 Maximum Value 1
Default Value 1
Consumed I/O Assy
This parameter selects the format of the I/O data consumed. Enter a Consumed I/O assembly instance number to select a data format.
Produced I/O Assy
This parameter selects the format of the I/O data produced. Enter a Produces I/O assembly instance number to select a data format.
Parameter Number 11
Access Rule GET/SET
Data Type USINT
Group DeviceNet
Units — Minimum Value 0 Maximum Value 187
Default Value 160
Parameter Number 12
Access Rule GET/SET
Data Type USINT
Group DeviceNet
Units — Minimum Value 0 Maximum Value 190
Default Value 161
3-8 Bulletin 280G/281G Programmable Parameters
Prod Assy Word 0
This parameter is used to build bytes 0-1 for produced assembly 120
Produced Assy Word 1
This parameter is used to build bytes 2-3 for produced assembly 120
Prod Assy Word 2
This parameter is used to build bytes 4-5 for produced assembly 120
Parameter Number 13
Access Rule GET/SET
Data Type USINT
Group DeviceNet
Units — Minimum Value 0 Maximum Value 108
Default Value 1
Parameter Number 14
Access Rule GET/SET
Data Type USINT
Group DeviceNet
Units — Minimum Value 0 Maximum Value 108
Default Value 4
Parameter Number 15
Access Rule GET/SET
Data Type USINT
Group DeviceNet
Units — Minimum Value 0 Maximum Value 108
Default Value 5
Prod Assy Word 3
This parameter is used to build bytes 6-7 for produced assembly 120
Consumed I/O Size
This parameter reflects the consumed I/O data size in bytes.
Parameter Number 16
Access Rule GET/SET
Data Type USINT
Group DeviceNet
Units — Minimum Value 0 Maximum Value 108
Default Value 6
Parameter Number 17
Access Rule GET
Data Type USINT
Group DeviceNet
Units — Minimum Value 0 Maximum Value 8
Default Value 1
Bulletin 280G/281G Programmable Parameters 3-9
Produced I/O Size
This parameter reflects the produced I/O data size in bytes.
Starter COS Mask
This parameter allows the installer to define the change-of­state conditions that will result in a change-of-state message being produced
Bulletin 280G products. Bulletin 281G products.
Parameter Number 18
Access Rule GET
Data Type USINT
Group DeviceNet
Units — Minimum Value 0 Maximum Value 8
Default Value 2
Parameter Number 19
Access Rule GET/SET
Data Type WORD
Group DeviceNet
Units — Minimum Value 0 Maximum Value 16383
Default Value
16149 16157
Bit
Function
13 12 11 10 9 8 7 6 5 4 3 2 1 0
————————————— X Tripped ———————————— X — Warning —————————— X —— Running Fwd —————————— X ——— Running Rev ————————— X ———— Ready ———————— X ————— NET Ctl Status ——————— X —————— 140M On —————— X ——————— Reserved ————— X ———————— Input 0 ———— X ————————— Input 1 ——— X —————————— Input 2 —— X ——————————— Input 3 — X ———————————— Input 4
X ————————————— Input 5
3-10 Bulletin 280G/281G Programmable Parameters
Net Out COS Mask
This parameter sets the bits that will trigger a COS message when network outputs change state.
Bit
14131211109876543210
—————————————— X Net Output 0 ————————————— X — Net Output 1 ———————————— X —— Net Output 2 ——————————— X ——— Net Output 3 —————————— X ———— Net Output 4 ————————— X ————— Net Output 5 ———————— X —————— Net Output 6 ——————— X ——————— Net Output 7 —————— X ———————— Net Output 8 ————— X ————————— Net Output 9 ———— X —————————— Net Output 10 ——— X ——————————— Net Output 11 —— X ———————————— Net Output 12 — X ————————————— Net Output 13
X —————————————— Net Output 14
Parameter Number 20
Access Rule GET/SET
Data Type WORD
Group DeviceNet
Units — Minimum Value 0 Maximum Value 32767
Default Value 0
Function
Starter Protection Group
Dnet Voltage
This parameter provides the voltage measurement for the DeviceNet network
Breaker Type
This parameter identifies the Bulletin 140M used in this product 0 = 140M-D8N-C10 1 = 140M-D8N-C25
Parameter Number 21
Access Rule GET
Data Type UINT
Group DeviceNet
Units xx.xx Volts Minimum Value 0 Maximum Value 6500
Default Value 0
Parameter Number 22
Access Rule GET/SET
Data Type BOOL
Group Starter Protection
Units — Minimum Value 0 Maximum Value 1
Default Value 0
Bulletin 280G/281G Programmable Parameters 3-11
PrFlt Reset Mode
Parameter Number 23
Access Rule GET/SET
This parameter configures the Protection Fault reset mode.
0= Manual 1= Automatic
Data Type BOOL
Group Starter Protection
Units — Minimum Value 0 Maximum Value 1
Default Value 0
Pr Fault Enable
Parameter Number 24
Access Rule GET/SET
This parameter enables the Protection Fault by setting the bit to 1
Data Type WORD
Group Starter Protection Setup
Units — Minimum Value 0 Maximum Value 16383
Default Value 12419
Bit
Function
131211109876543210
————————————— X Short Circuit ———————————— X — Overload ——————————— X —— Phase Loss —————————— X ——— Reserved ————————— X ———— Reserved ———————— X ————— Control Power ——————— X —————— I/O Fault —————— X ——————— Over Temperature ————— X ———————— Phase Imbalance ———— X ————————— Dnet Power Loss ——— X —————————— Reserved —— X ——————————— Reserved — X ———————————— Eeprom
X ————————————— HW Fault
Pr Fault Reset
This parameter resets the Protection Fault on a transition of 0-->1.
Parameter Number 25
Access Rule GET/SET
Data Type BOOL
Group Starter Protection
Units — Minimum Value 0 Maximum Value 1
Default Value 0
3-12 Bulletin 280G/281G Programmable Parameters
StrtrDN FltState
This parameter in conjunction with Parameter 27 defines how the starter will respond when a DeviceNet fault occurs. When set to “1”, hold to last state occurs. When set to “0”, will go to DnFlt Value on DN faults as determined by Parameter 27.
StrtrDN FltValue
This parameter determines how the starter will be commanded in the event of a Device Net fault. 0 = OFF 1 = ON
StrtrDN IdlState
This parameter in conjunction with Parameter 29 defines how the starter will respond when a DeviceNet network is idle. When set to “1”, hold to last state occurs. When set to “0”, will go to DnIdl Value on DN Idle as determined by Parameter 29.
Parameter Number 26
Access Rule GET/SET
Data Type BOOL
Group Starter Protection
Units — Minimum Value 0 Maximum Value 1
Default Value 0
Parameter Number 27
Access Rule GET
Data Type BOOL
Group Starter Protection
Units — Minimum Value 0 Maximum Value 1
Default Value 0
Parameter Number 28
Access Rule GET/SET
Data Type BOOL
Group Starter Protection
Units — Minimum Value 0 Maximum Value 1
Default Value 0
StrtrDN IdlValue
This parameter determines the state that starter assumes when the network is idle and Parameter 28 is set to “0” 0 = OFF 1 = ON
Parameter Number 29
Access Rule GET
Data Type BOOL
Group Starter Protection
Units — Minimum Value 0 Maximum Value 1
Default Value 0
Bulletin 280G/281G Programmable Parameters 3-13
Last PR Fault
0 = None 1 = Hardware Short Circuit 2 = Software Short Circuit 3 = Motor Overload 4 = Reserved 5 = Phase Loss 6 – 12 = Reserved 13 = Control Power Loss 14 = Control Power Fuse 15 = I/O Short 16 = Reserved 17 = Overtemp 18= Reserved 19 = Phase Imbalance 20 = Reserved 21 = DNet Power Loss 22 = Internal Comm 23-26 = Reserved 27 = MCB EEPROM 28 = Base EEPROM 29 = Reserved 30 = Wrong Base 31 = Wrong CTs 32-100 = Reserved
Parameter Number 61
Access Rule GET
Data Type UINT
Group Starter Protection
Units
MinimumValue 0
Maximum Value 100
Default Value 0
Warning Status
This parameter warns the user of a condition, without faulting
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
X reserved
X reserved
X H a r d w a r e
X reserved
X reserved
Parameter Number 62 Access Rule GET Data Type WORD Group Starter Protection Units — MinimumValue 0 Maximum Value 65535 Default Value 0
Bit
X reserved
X Phase Loss
X reserved
X reserved
X Control Power
XIO Warning
X reserved
X Phase Imbalance
X DeviceNet
X reserved
Warning
X reserved
3-14 Bulletin 280G/281G Programmable Parameters
User I/O
Off-to-On Delay
This parameter allows the installer to program a time duration before an input is reported “ON”
On-to-Off Delay
This parameter allows the installer to program a time duration before an input is reported “OFF”
In Sink/Source
This parameter allows the installer to program the inputs to be sink or source.
0=Sink 1=Source
Parameter Number 30
Access Rule GET/SET
Data Type UINT
Group User I/O
Units ms Minimum Value 0 Maximum Value 65.000
Default Value 0
Parameter Number 31
Access Rule GET/SET
Data Type UINT
Group User I/O
Units ms Minimum Value 0 Maximum Value 65.000
Default Value 0
Parameter Number 32
Access Rule GET/SET
Data Type BOOL
Group User I/
Units — Minimum Value 0 Maximum Value 1
Default Value 0
Misc. Group
Keypad Mode
This parameter selects if the
keypad operation is maintained or momentary
0= Maintained 1= Momentary
Keypad Disable
This parameter disables all keypad function except for the “OFF” and “RESET” buttons
0=Not Disabled 1=Disabled
Parameter Number 45
Access Rule GET/SET
Data Type BOOL
Group Misc.
Units — Minimum Value 0 Maximum Value 1
Default Value 0
Parameter Number 46
Access Rule GET/SET
Data Type BOOL
Group Misc.
Units — Minimum Value 0 Maximum Value 1
Default Value 0
Bulletin 280G/281G Programmable Parameters 3-15
Set to Defaults
This parameter if set to 1 will set the device to the factory defaults
0=No Operation 1=Set to Defaults
Base Enclosure
Indicates the ArmorStart Base unit enclosure rating
Bit 0 = IP67 Bit 1 = Nema 4X Bit 2 = SIL3/CAT4 Bit 3-15 = Reserved
Base Options
Indicates the options for the ArmorStart Base unit
Bit 0 = Reserved Bit 1 = Reserved Bit 2 = CP Fuse Detect Bits 3-7 = Reserved Bit 8 = 10A Base Bit 9 = 25A Base Bit 10-15 = Reserved
Parameter Number 47
Access Rule GET/SET
Data Type BOOL
Group Misc.
Units — Minimum Value 0 Maximum Value 1
Default Value 0
Parameter Number 56
Access Rule GET
Data Type WORD
Group Misc.
Units
MinimumValue 0
Maximum Value 65535
Default Value 0
Parameter Number 57
Access Rule GET
Data Type WORD
Group Misc.
Units
MinimumValue 0
Maximum Value 65535
Default Value 0
Wiring Options
Bit 0 = Conduit Bit 1 = Round Media Bits 2-15 = 28xG Bits 3-15 = Reserved
Starter Enclosure
Bit 0 = IP67 Bit 1 = NEMA 4x Bit 2 = SIL3/CAT4 Bits 3-15 reserved
Parameter Number 58
Access Rule GET
Data Type WORD
Group Misc.
Units
MinimumValue 0
Maximum Value 65535
Default Value 0
Parameter Number 59
Access Rule GET
Data Type WORD
Group Misc.
Units
MinimumValue 0
Maximum Value 65535
Default Value
3-16 Bulletin 280G/281G Programmable Parameters
ZIP Parameters
Starter Option
Bit 0 = HOA Keypad Bit 1 = Safety Monitor Bit 2 = Source Brake
Bits 4-15 = Reserved
AutoRun Zip
Enables ZIP data production on power up
0=Disable 1=Enable
Zone Produced EPR
The Expected Packet Rate in msec. Defines the rate at which ZIP data is produced. Defaults to 75 msec.
Parameter Number 60
Access Rule GET
Data Type WORD
Group Misc.
Units
MinimumValue 0
Maximum Value 66535
Default Value
Parameter Number 67
Access Rule Get/Set
Data Type BOOL
Group ZIP Parameters
Units
MinimumValue 0
Maximum Value 1
Default Value 0
Parameter Number 68
Access Rule GET/SET
Data Type UINT
Group Zip Parameter
Units msec
MinimumValue 0
Maximum Value 65535
Default Value 75
Zone Produced PIT
The Production Inhibit Time in msec. Defines the minimum time between Change of State data production
Zone #1 MAC ID
The node address of the device whose data is to be consumed for zone 1
Parameter Number 69
Access Rule GET/SET
Data Type UINT
Group ZIP Parameters
Units msec
MinimumValue 0
Maximum Value 65535
Default Value 75
Parameter Number 70
Access Rule GET/SET
Data Type USINT
Group ZIP Parameters
Units
MinimumValue 0
Maximum Value 64
Default Value 64
Bulletin 280G/281G Programmable Parameters 3-17
Zone #2 MAC ID
The node address of the device whose data is to be consumed for zone 2
Zone #3 MAC ID
The node address of the device whose data is to be consumed for zone 3
Zone #4 MAC ID
The node address of the device whose data is to be consumed for zone 4
Parameter Number 71
Access Rule GET/SET
Data Type USINT
Group ZIP Parameters
Units
MinimumValue 0
Maximum Value 64
Default Value 64
Parameter Number 72
Access Rule GET/SET
Data Type USINT
Group ZIP Parameters
Units
MinimumValue 0
Maximum Value 64
Default Value 64
Parameter Number 73
Access Rule GET/SET
Data Type USINT
Group Misc. Option
Units
MinimumValue 0
Maximum Value 64
Default Value 64
Zone #1 Health
Read Only consumed connection status for zone 1
0 = Healthy 1 = Unhealthy
Zone #2 Health
Read Only consumed connection status for zone 2
0 = Healthy 1 = Unhealthy
Parameter Number 74
Access Rule GET
Data Type BOOL
Group ZIP Parameters
Units
MinimumValue 0
Maximum Value 1
Default Value 0
Parameter Number 75
Access Rule GET
Data Type BOOL
Group ZIP Parameters
Units
MinimumValue 0
Maximum Value 1
Default Value 0
3-18 Bulletin 280G/281G Programmable Parameters
Zone #3 Health
Read Only consumed connection status for zone 3
0 = Healthy 1 = Unhealthy
Zone #4 Health
Read Only consumed connection status for zone 4
0 = Healthy 1 = Unhealthy
Zone #1 Mask
Bit enumerated consumed data mask for zone 1. Each bit represents a byte in consumed data up to 8 bytes in length. If a mask bit is set, the corresponding consumed data byte is placed in the DeviceLogix data table
Parameter Number 76
Access Rule GET
Data Type BOOL
Group ZIP Parameters
Units
MinimumValue 0
Maximum Value 1
Default Value 0
Parameter Number 77
Access Rule GET
Data Type BOOL
Group ZIP Parameters
Units
MinimumValue 0
Maximum Value 1
Default Value 0
Parameter Number 78
Access Rule GET/SET
Data Type BYTE
Group ZIP Parameters
Units
MinimumValue 0
Maximum Value 255
Default Value 0
Zone #2 Mask
Bit enumerated consumed data mask for zone 2. Each bit represents a byte in consumed data up to 8 bytes in length. If a mask bit is set, the corresponding consumed data byte is placed in the DeviceLogix data table
Zone #3 Mask
Bit enumerated consumed data mask for zone 3. Each bit represents a byte in consumed data up to 8 bytes in length. If a mask bit is set, the corresponding consumed data byte is placed in the DeviceLogix data table
Parameter Number 79
Access Rule GET/SET
Data Type BYTE
Group ZIP Parameters
Units
MinimumValue 0
Maximum Value 255
Default Value 0
Parameter Number 80
Access Rule GET/SET
Data Type BYTE
Group ZIP Parameters
Units
MinimumValue 0
Maximum Value 255
Default Value 0
Bulletin 280G/281G Programmable Parameters 3-19
Zone #4 Mask
Bit enumerated consumed data mask for zone 4. Each bit represents a byte in consumed data up to 8 bytes in length. If a mask bit is set, the corresponding consumed data byte is placed in the DeviceLogix data table
Zone #1 Offset
The byte offset into the ZIP data portion of the DeviceLogix data table to place the chosen consumed data bytes for zone 1.
Zone #2 Offset
The byte offset into the ZIP data portion of the DeviceLogix data table to place the chosen consumed data bytes for zone 2.
Parameter Number 81
Access Rule GET/SET
Data Type BYTE
Group ZIP Parameters
Units
MinimumValue 0
Maximum Value 255
Default Value 0
Parameter Number 82
Access Rule GET/SET
Data Type UINT
Group ZIP Parameters
Units
MinimumValue 0
Maximum Value 7
Default Value 0
Parameter Number 83
Access Rule GET/SET
Data Type UNIT
Group ZIP Parameters
Units
MinimumValue 0
Maximum Value 7
Default Value 0
Zone #3 Offset
The byte offset into the ZIP data portion of the DeviceLogix data table to place the chosen consumed data bytes for zone 3.
Zone #4 Offset
The byte offset into the ZIP data portion of the DeviceLogix data table to place the chosen consumed data bytes for zone 4.
Parameter Number 84
Access Rule GET/SET
Data Type UNIT
Group ZIP Parameters
Units
MinimumValue 0
Maximum Value 1
Default Value 0
Parameter Number 85
Access Rule GET/SET
Data Type UNIT
Group ZIP Parameters
Units
MinimumValue 0
Maximum Value 1
Default Value 0
3-20 Bulletin 280G/281G Programmable Parameters
Zone #1 EPR
The Expected Packet Rate in msec. for the zone 1 consuming connection. If consumed data is not received in 4 times this value, the zone connection will time out and “Zone #1 Health” will report 1 = Not Healthy.
Zone #2 EPR
The Expected Packet Rate in msec. for the zone 1 consuming connection. If consumed data is not received in 4 times this value, the zone connection will time out and “Zone #2 Health” will report 1 = Not Healthy.
Zone #3 EPR
The Expected Packet Rate in msec. for the zone 1 consuming connection. If consumed data is not received in 4 times this value, the zone connection will time out and “Zone #3 Health” will report 1 = Not Healthy.
Parameter Number 86
Access Rule GET/SET
Data Type UINT
Group ZIP Parameters
Units msec
MinimumValue 0
Maximum Value 65535
Default Value 75
Parameter Number 87
Access Rule GET/SET
Data Type UNIT
Group ZIP Parameters
Units msec
MinimumValue 0
Maximum Value 65535
Default Value 75
Parameter Number 88
Access Rule GET/SET
Data Type UNIT
Group ZIP Parameters
Units msec
MinimumValue 0
Maximum Value 65535
Default Value 75
Zone #4 EPR
The Expected Packet Rate in msec. for the zone 1 consuming connection. If consumed data is not received in 4 times this value, the zone connection will time out and “Zone #4 Health” will report 1 = Not Healthy.
Parameter Number 89
Access Rule GET/SET
Data Type UNIT
Group ZIP Parameters
Units msec
MinimumValue 0
Maximum Value 65535
Default Value 75
Bulletin 280G/281G Programmable Parameters 3-21
Zone #1 Control
Zone 1 Control Word. Default Bit 0 and Bit 1 set, all other bits clear. Bit0=Security Enable 1=Enable data security Bit1=COS Cnxn 1=Consume DNet Group 2 COS messages Bit2=Poll Cnxn 1=Consume DNet Group 2 Poll Response msgs. Bit3=Strobe Cnxn 1=Consume DNet Group 2 Strobe Response msgs. Bit4=Multicast Poll 1=Consume Multicast Poll Response messages.
Zone #2 Control
Zone 2 Control Word. Default Bit 0 and Bit 1 set, all other bits clear. Bit0=Security Enable 1=Enable data security Bit1=COS Cnxn 1=Consume DNet Group 2 COS messages Bit2=Poll Cnxn 1=Consume DNet Group 2 Poll Response msgs. Bit3=Strobe Cnxn 1=Consume DNet Group 2 Strobe Response msgs. Bit4=Multicast Poll 1=Consume Multicast Poll Response messages
Parameter Number 90
Access Rule GET/SET
Data Type BYTE
Group ZIP Parameters
Units
MinimumValue 0
Maximum Value 255
Default Value 3
Parameter Number 91
Access Rule GET/SET
Data Type BYTE
Group ZIP Parameters
Units
MinimumValue 0
Maximum Value 255
Default Value 3
Zone #3 Control
Zone 3 Control Word. Default Bit 0 and Bit 1 set, all other bits clear. Bit0=Security Enable 1=Enable data security Bit1=COS Cnxn 1=Consume DNet Group 2 COS messages Bit2=Poll Cnxn 1=Consume DNet Group 2 Poll Response msgs. Bit3=Strobe Cnxn 1=Consume DNet Group 2 Strobe Response msgs. Bit4=Multicast Poll 1=Consume Multicast Poll Response messages
Parameter Number 92
Access Rule GET/SET
Data Type BYTE
Group ZIP Parameters
Units
MinimumValue 0
Maximum Value 255
Default Value 3
3-22 Bulletin 280G/281G Programmable Parameters
Zone #4 Control
Zone 3 Control Word. Default Bit 0 and Bit 1 set, all other bits clear. Bit0=Security Enable 1=Enable data security Bit1=COS Cnxn 1=Consume DNet Group 2 COS messages Bit2=Poll Cnxn 1=Consume DNet Group 2 Poll Response msgs. Bit3=Strobe Cnxn 1=Consume DNet Group 2 Strobe Response msgs. Bit4=Multicast Poll 1=Consume Multicast Poll Response messages
Zone #1 Key
When the “Security Enable” bit for zone 1 is enabled, this value must match the value of the Device Value Key parameter in the device whose data is being consumed for zone 1.
Parameter Number 93
Access Rule GET/SET
Data Type BYTE
Group ZIP Parameters
Units
MinimumValue 0
Maximum Value 255
Default Value 3
Parameter Number 94
Access Rule GET/SET
Data Type UINT
Group ZIP Parameters
Units
MinimumValue 0
Maximum Value 65535
Default Value 0
Zone #2 Key
When the “Security Enable” bit for zone 2 is enabled, this value must match the value of the Device Value Key parameter in the device whose data is being consumed for zone 2.
Zone #3 Key
When the “Security Enable” bit for zone 3 is enabled, this value must match the value of the Device Value Key parameter in the device whose data is being consumed for zone 3.
Parameter Number 95
Access Rule GET/SET
Data Type UINT
Group ZIP Parameters
Units
MinimumValue 0
Maximum Value 65535
Default Value 0
Parameter Number 96
Access Rule GET/SET
Data Type UINT
Group ZIP Parameters
Units
MinimumValue 0
Maximum Value 65535
Default Value 0
Bulletin 280G/281G Programmable Parameters 3-23
Zone #4 KEY
When the “Security Enable” bit for zone 4 is enabled, this value must match the value of the Device Value Key parameter in the device whose data is being consumed for zone 4
Device Value Key
This value is produced in the last 2 bytes of data when one of the ZIP assemblies is chosen for data production.
Zone Ctrl Enable
Global enable for ZIP peer-to­peer messaging. This parameter must be disabled before any changes to the ZIP configuration f or th e d e vi ce ca n be ma de . 0=Disable 1=Enable
Parameter Number 97
Access Rule GET/SET
Data Type UINT
Group ZIP Parameters
Units
MinimumValue 0
Maximum Value 65535
Default Value 0
Parameter Number 98
Access Rule GET/SET
Data Type UINT
Group ZIP Parameters
Units
MinimumValue 0
Maximum Value 65535
Default Value 0
Parameter Number 99
Access Rule GET/SET
Data Type BOOL
Group ZIP Parameters
Units
MinimumValue 0
Maximum Value 1
Default Value 0
Starter Display
Phase A Current
This parameter provides the current of Phase A measured n increments of 1/10 ampere
Phase B Current
This parameter provides the current of Phase B measured in increments of 1/10th of an ampere
th
of an
Parameter Number 101
Access Rule GET/SET
Data Type INT
Group Starter Display
Units xx.x Amps Minimum Value 0 Maximum Value 32767
Default Value 0
Parameter Number 102
Access Rule GET/SET
Data Type INT
Group Starter Display
Units xx.x Amps Minimum Value 0 Maximum Value 32767
Default Value 0
3-24 Bulletin 280G/281G Programmable Parameters
Phase C Current
This parameter provides the current of Phase C measured in increments of 1/10 ampere
Average Current
This parameter provides the average current measured in increments of 1/10th of an ampere
% Therm Utilized
This parameter displays the % Thermal Capacity used
th
of an
Parameter Number 103
Access Rule GET/SET
Data Type INT
Group Starter Display
Units xx.x Amps Minimum Value 0 Maximum Value 32767
Default Value 0
Parameter Number 104
Access Rule GET/SET
Data Type INT
Group Starter Display
Units xx.x Amps Minimum Value 0 Maximum Value 32767
Default Value 0
Parameter Number 105
Access Rule GET/SET
Data Type USINT
Group Starter Display
Units % FLA Minimum Value 0 Maximum Value 100
Default Value 0
Starter Setup
FLA Setting
The motor’s full load current rating is programmed in this parameter
Parameter Number 106
Access Rule GET/SET
Data Type INT
Group Starter Setup
Units xx.x Amps Minimum Value See Table 3.2 Maximum Value See Table 3.2
Default Value See Table 3.2
Table 3.2 FLA Setting Ranges and Default Values (with indicated setting
precision)
FLA Current Range (A)
Minimum Value Maximum Value
0.5 2.5 0.5
1.1 5.5 1.1
3.2 16.0 3.2
Default Value
Bulletin 280G/281G Programmable Parameters 3-25
Overload Class
This parameter allows the installer to select the overload class
1= Overload Class 10 2= Overload Class 15 3= Overload Class 20
OL Reset Level
This parameter allows the installer select the % Thermal Capacity which an overload can be cleared
Parameter Number 107
Access Rule GET/SET
Data Type USINT
Group Starter Setup
Units xx.x Amps Minimum Value 1 Maximum Value 3
Default Value 1
Parameter Number 108
Access Rule GET/SET
Data Type USINT
Group Starter Setup
Units % FLA Minimum Value 0 Maximum Value 100
Default Value 75
3-26 Bulletin 280G/281G Programmable Parameters
Notes
Chapter 4
Bulletin 284G Programmable Parameters for Sensorless Vector Controllers
This chapter describes each programmable parameter and its function for Bulletin 284G Sensorless Vector Controllers.
Parameter Programming Each Distributed Motor Controller type will have a common set of
parameters followed by a set of parameters that pertain to the individual starter type.
Refer to Chapter 5, DeviceNet™ Commissioning, for instructions in using RSNetworx for DeviceNet to modify parameter settings.
Important: Resetting the Factory Default Values Parameter 47, Set to
Defaults, allows the installer to reset all parameter to the
factory default values. It also resets the MAC ID to its factory default after DeviceNet Power is cycled if switches are set >63.
Important: Parameter setting changes downloaded to the ArmorStart®
take effect immediately, even during a running status.
Important: Parameter setting changes made in a configuration tool such as
RSNetworx for DeviceNet do not take effect in the ArmorStart until the installer applies or downloads the new settings to the device.
1
4-2 Bulletin 284G Programmable Parameters for Sensorless Vector Controllers
Parameter Group Listing The Bulletin 284G ArmorStart contains ten parameter groups. The
parameters shown in the DeviceLogix™, DeviceNet , Starter Protection , User I/O , Misc. Parameter , Drive DeviceNet , Display Group, ZIP Parameters, Basic Program, and Advanced Program will be discussed in this chapter.
Table 4.1 Paramerer Group Listing
DeviceLogix DeviceNet Starter Protection User I/O Miscellaneous Drive DeviceNet
1 Hdw Inputs 2 Network Inputs 3 Network Outputs 4 Tri p Sta tus 5 Starter Status 6 DNet Status 7 Starter Command 8 Network Override 9 Comm Override
Display Group ZIP Parameters Basic Program Advanced Program
101 Output Freq 102 Commanded Freq 103 Output Current 104 Output Voltage 105 DC Bus Voltage 106 Drive Status 107 Fault 1 Code 108 Fault 2 Code 109 Fault 3 Code 110 Process Display 112 Control Source 113 Contrl In Status 114 Dig In Status 115 Comm Status 116 Control SW Ver 117 Drive Type 118 Elapsed Run Time 119 Tes tpoi nt Da ta 120 Analog In 0…10V 121 Analog In 4…20 mA 122 Output Power 123 Output Power Fctr 124 Drive Temp 125 Counter Status 126 Timer Status 127 Timer Stat Fract 128 Stp Logic Status 129 Torque Current
10 Autobaud Enable 11 Consumed IO Assy 12 Produced IO Assy 13 Prod Assy Word 0 14 Prod Assy Word 1 15 Prod Assy Word 2 16 Prod Assy Word 3 17 Consumed IO Size 18 Produced IO Size 19 Starter COS Mask 20 Net Out COS Mask 21 DNet Voltage
67 AutoRun Zip 68 Zone Produced EPR 69 Zone Produced PIT 70 Zone #1 MacId 71 Zone #2 MacId 72 Zone #3 MacId 73 Zone #4 MacId 74 Zone #1 Health 75 Zone #2 Health 76 Zone #3 Health 77 Zone #4 Health 78 Zone #1 Mask 79 Zone #2 Mask 80 Zone #3 Mask 81 Zone #4 Mask 82 Zone #1 Offset 83 Zone #2 Offset 84 Zone #3 Offset 85 Zone #4 Offset 86 Zone #1 EPR 87 Zone #2 EPR 88 Zone #3 EPR 89 Zone #4 EPR 90 Zone #1 Control 91 Zone #2 Control 92 Zone #3 Control 93 Zone #4 Control 94 Zone #1 Key 95 Zone #2 Key 96 Zone #3 Key 97 Zone #4 Key 98 Device Value Key 99 Zone Ctrl Enable
22 Breaker Type 23 PrFltResetMode 24 Pr Fault Enable 25 Pr Fault Reset 26 StrtrDN FltState 27 StrtrDN FltValue 28 StrtrDN IdlState 29 StrtrDN IdlValue 61 LAST Pr Fault 62 Warning Status
131 Motor NP Volts 132 Motor NP Hertz 133 Motor OL Current 134 Minimum Freq 135 Maximum Freq 136 Start Source 137 Stop Mode 138 Speed Reference 139 Accel Time 1 140 Decel Time 1 141 Reset To Defalts 142 Reserved 143 Motor OL Ret
30 Off-to-On Delay 31 On-to-Off Delay 32 In Sink/Source
151 Digital In1 Sel 152 Digital In2 Sel 153 Digital In3 Sel 154 Digital In4 Sel 155 Relay Out Sel 156 Relay Out Level 157 Relay Out LevelF 158 Opto Out1 Sel 159 Opto Out1 Level 160 Opto Out1 LevelF 161 Opto Out2 Sel 162 Opto Out2 Level 163 DB Threshold 164 Opto Out Logic 165 Analog Out Sel 166 Analog Out High 167 Accel Time 2 168 Decel Time 2 169 Internal Freq 170 Preset Freq 0 171 Preset Freq 1 172 Preset Freq 2 173 Preset Freq 3 174 Preset Freq 4 175 Preset Freq 5 176 Preset Freq 6 177 Preset Freq 7 178 Jog Frequency 179 Jog Accel/Decel 180 DC Brake Time 181 DC Brake Level 182 DB Resistor Sel 183 S Curve % 184 Boost Select 185 Start Boost 186 Break Voltage 187 Break Frequency 188 Maximum Voltage
45 Keypad Mode 46 Keypad Disable 47 Set To Defaults 56 Base Enclosure 57 Base Options 58 Wiring Options 59 Starter Enclosure 60 Starter Options
189 Current Limit 1 190 Motor OL Select 191 PWM Frequency 192 Auto Rstrt Tries 193 Auto Rstrt Delay 194 Start At PowerUp 195 Reverse Disable 196 Flying Start En 197 Compensation 198 SW Current Trip 199 Process Factor 200 Fault Clear 201 Program Lock 202 Tes tpoint Sel
203 Comm Data Rate
204 Comm Node Addr 205 Comm Loss Action 206 Comm Loss Time 207 Comm Format 208 Language 209 Anlg Out Setpt 210 Anlg In 0…10V Lo 211 Anlg In 0…10V Hi 212 Anlg In 4…20 mA Lo 213 Anlg In4…20 mA Hi 214 Slip Hertz @ FLA 215 Process Time Lo 216 Process Time Hi 217 Bus Reg Mode 218 Current Limit 2 219 Skip Frequency 220 Skip Freq Band 221 Stall Fault Time 222 Analog In Loss 223 10V Bipolar Enbl 224 Var PWM Disable 225 Torque Perf Mode 226 Motor NP FLA
48 Drive Control 49 Drvin PrFltState 50 Drvin PrFltValue 51 Drvin DNFltState 52 Drvin DNFltValue 53 Drvin DNFltState 54 Drvin DNFltValue 55 High Speed Enable
227 Autotune 228 IR Voltage Drop 229 Flux Current Ref 230 PID Trim Hi 231 PID Trim Lo
232 PID Ref Sel
233 PID Feedback Sel 234 PID Prop Gain 235 PID Integ Time 236 PID Diff Rate 237 PID Setpoint 238 PID Deadband 239 PID Preload 240 Stp Logic 0 241 Stp Logic 1 242 Stp Logic 2 243 Stp Logic 3 244 Stp Logic 4 245 Stp Logic 5 246 Stp Logic 6 247 Stp Logic 7 248 Reserved 249 Reserved 250 Stp Logic Time 0 251 Stp Logic Time 1 252 Stp Logic Time 2 253 Stp Logic Time 3 254 Stp Logic Time 4 255 Stp Logic Time 5 256 Stp Logic Time 6 257 Stp Logic Time 7 258 Reserved 259 Reserved 260 EM Brk Off Delay 261 EM Brk On Delay 262 MOP Reset Sel
.
Bulletin 284G Programmable Parameters for Sensorless Vector Controllers 4-3
DeviceLogix Group This parameter is not available with the Bulletin 284A.
Hdw Inputs
This parameter provides status of hardware inputs.
5 4 3 2 1 0
X Input 0 — X Input 1 — X Input 2 — X Input 3 — X Input 4
X Input 5
Network Inputs
This parameter provides status of network inputs.
Parameter Number 1
Access Rule GET
Data Type WORD
Group DeviceLogix
Units
Minimum Value 0
Maximum Value 15
Default Value 0
Bit
Function
Parameter Number 2
Access Rule GET
Data Type WORD
Group DeviceLogix
Units
Minimum Value 0
Maximum Value 65535
Default Value 0
Bit
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
X Net Input 0 — X Net Input 1 — X Net input 2 — X Net Input 3 — X Net Input 4 — X Net Input 5 — X Net Input 6 — X Net Input 7 — X Net Input 8 — X Net Input 9 — X Net Input 10 — X Net Input 11 — X Net Input 12 — X Net Input 13 — X Net Input 14
X Net Input 15
Function
4-4 Bulletin 284G Programmable Parameters for Sensorless Vector Controllers
Network Outputs
This parameter provides status of network outputs.
Bit
14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
X Net Output 0 — X Net Output 1 — X Net Output 2 — X Net Output 3 — X Net Output 4 — X Net Output 5 — X Net Output 6 — X Net Output 7 — X Net Output 8 — X Net Output 9 — X Net Output 10 — X Net Output 11 — X Net Output 12 — X Net Output 13
X Net Output 14
Parameter Number 3
Access Rule GET
Data Type WORD
Group DeviceLogix
Units
Minimum Value 0
Maximum Value 32767
Default Value 0
Function
Bulletin 284G Programmable Parameters for Sensorless Vector Controllers 4-5
Trip Status
This parameter provides trip identification.
Bit
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
X Short Circuit — X Overload — X Phase Short — X Ground Fault — X Stall — X Control Power — X IO Fault — X Overtemperature — X Over Current — X Dnet Power Loss — X Internal Comm X DC Bus Fault — X EEprom — X HW Fault — X Restart Retries
X Misc. Fault
Parameter Number 4
Access Rule GET
Data Type WORD
Group DeviceLogix
Units
Minimum Value 0
Maximum Value 65535
Default Value 0
Function
Indicates DB1 Comm Fault for Bulletin 284G.
4-6 Bulletin 284G Programmable Parameters for Sensorless Vector Controllers
Starter Status
This parameter provides the status of the starter.
Parameter Number 5
Access Rule GET
Data Type WORD
Group DeviceLogix
Units
Minimum Value 0
Maximum Value 65535
Default Value 0
Bit
Function
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
X Trip pe d — X Warning — X Running Fwd — X Running Rev — X Ready — X Net Ctl Status — X Net Ref Status — X At Reference — X DrvOpto1 — X DrvOpto2 — X Keypad Jog — X Keypad Hand — X HOA Status — X 140M On — X Contactor 1
X Reserved
Refers to Control Brake contactor status.
Bulletin 284G Programmable Parameters for Sensorless Vector Controllers 4-7
Dnet Status
This parameter provides status of the DeviceNet connection.
Bit
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
X Exp Cnxn — X IO Cnxn — X Exp Flt — X IO Flt — X IO Idle — X X X Reserved — X ZIP 1 Cnxn — X ZIP 1 Flt — X ZIP 2 Cnxn — X ZIP 2 Flt — X ZIP 3 Cnxn — X ZIP 3 Flt — X ZIP 4 Cnxn
X ZIP 4 Flt
Parameter Number 6
Access Rule GET
Data Type WORD
Group DeviceLogix
Units
Minimum Value 0
Maximum Value 31
Default Value 0
Function
Starter Command
This parameter provides the command the starter.
Parameter Number 7
Access Rule GET/SET
Data Type WORD
Group DeviceLogix
Units
Minimum Value 0
Maximum Value 255
Default Value 0
Bit
Function
7 6 5 4 3 2 1 0
X Run Fwd — X Run Rev — X Fault Reset — X Jog Fwd — X Jog Rev — X Reserved — X Reserved
X Reserved
4-8 Bulletin 284G Programmable Parameters for Sensorless Vector Controllers
Network Override
This parameter allows for the local logic to override a Network fault. 0 = Disable 1 = Enable
Comm Override
This parameter allows for local logic to override a loss of an I/O connection. 0 = Disable 1 = Enable
DeviceNet Group
Autobaud Enable
When this parameter is enabled, the device will attempt to determine the network baud rate and set its baud rate to the same, provided network traffic exists. At least one node with an established baud rate must exist on the network for autobaud to occur. 0 = Disable 1 = Enable
Parameter Number 8
Access Rule GET/SET
Data Type BOOL
Group DeviceLogix
Units
Minimum Value 0
Maximum Value 1
Default Value 0
Parameter Number 9
Access Rule GET/SET
Data Type BOOL
Group DeviceLogix
Units
Minimum Value 0
Maximum Value 1
Default Value 0
Parameter Number 10
Access Rule GET/SET
Data Type BOOL
Group DeviceNet
Units
Minimum Value 0
Maximum Value 1
Default Value 1
Consumed I/O Assy
This parameter selects the format of the I/O data consumed
Produced I/O Assy
This parameter selects the format of the I/O data produced.
Parameter Number 11
Access Rule GET/SET
Data Type USINT
Group DeviceNet
Units
Minimum Value 0
Maximum Value 188
Default Value 164
Parameter Number 12
Access Rule GET/SET
Data Type USINT
Group DeviceNet
Units
Minimum Value 0
Maximum Value 190
Default Value 165
Bulletin 284G Programmable Parameters for Sensorless Vector Controllers 4-9
Prod Assy Word 0
This parameter is used to build bytes 0-1 for produced assembly 120.
Produced Assy Word 1
This parameter is used to build bytes 2-3 for produced assembly 120
Prod Assy Word 2
This parameter is used to build bytes 4-5 for produced assembly 120.
Parameter Number 13
Access Rule GET/SET
Data Type USINT
Group DeviceNet
Units
Minimum Value 0
Maximum Value 262
Default Value 1
Parameter Number 14
Access Rule GET/SET
Data Type USINT
Group DeviceNet
Units
Minimum Value 0
Maximum Value 262
Default Value 4
Parameter Number 15
Access Rule GET/SET
Data Type USINT
Group DeviceNet
Units
Minimum Value 0
Maximum Value 262
Default Value 5
Prod Assy Word 3
This parameter is used to build bytes 6-7 for produced assembly 120.
Consumer I/O Size
This parameter maps to the Scanner Tx Size.
Parameter Number 16
Access Rule GET/SET
Data Type USINT
Group DeviceNet
Units
Minimum Value 0
Maximum Value 262
Default Value 6
Parameter Number 17
Access Rule GET
Data Type USINT
Group DeviceNet
Units
Minimum Value 0
Maximum Value 8
Default Value 4
4-10 Bulletin 284G Programmable Parameters for Sensorless Vector Controllers
Produced I/O Size
This parameter maps to the Scanners Rx Size.
Starter COS Mask
This parameter allows the installer to define the change-of-state conditions that will result in a change-of-state message being produced.
Bit
13 12 11 10 9 8 7 6 5 4 3 2 1 0
X Tr ip ped — X Warning — X Running Fwd — X Running Rev — X Ready — X Net Ctl Status — X 140M On — X At Reference — X User Input 0 — X User Input 1 — X User Input 2 — X User Input 3 — X User Input 4
X User Input 5
Parameter Number 18
Access Rule GET
Data Type USINT
Group DeviceNet
Units
Minimum Value 0
Maximum Value 8
Default Value 4
Parameter Number 19
Access Rule GET/SET
Data Type WORD
Group DeviceNet
Units
Minimum Value 0
Maximum Value 16383
Default Value 16383
Function
Bulletin 284G Programmable Parameters for Sensorless Vector Controllers 4-11
Net Out COS Mask
This parameter sets the bit that will trigger a COS message on the network output.
Bit
14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
X Net Output 0 — X Net Output 1 — X Net Output 2 — X Net Output 3 — X Net Output 4 — X Net Output 5 — X Net Output 6 — X Net Output 7 — X Net Output 8 — X Net Output 9 — X Net Output 10 — X Net Output 11 — X Net Output 12 — X Net Output 13
X Net Output 14
Parameter Number 20
Access Rule GET/SET
Data Type WORD
Group DeviceNet
Units
Minimum Value 0
Maximum Value 32767
Default Value 0
Function
Dnet Voltage
This parameter provides the voltage measurement for the DeviceNet network.
Parameter Number 21
Access Rule GET
Data Type UINT
Group DeviceNet
Units V
Minimum Value 0
Maximum Value 6500
Default Value 0
4-12 Bulletin 284G Programmable Parameters for Sensorless Vector Controllers
Starter Protection Group
Breaker Type
This parameter identifies the Bulletin 140M used in this product. 0 = 140M-D8N-C10 1 = 140M-D8N-C25
PrFlt Reset Mode
This parameter is the Protection Fault reset mode. 0 = Manual 1 = Automatic
Pr Fault Enable
This parameter enables the Protection Fault by setting the bit to 1.
Parameter Number 22
Access Rule GET
Data Type BOOL
Group Starter Protection
Units
Minimum Value 0
Maximum Value 1
Default Value
Parameter Number 23
Access Rule GET/SET
Data Type BOOL
Group Starter Protection
Units
Minimum Value 0
Maximum Value 1
Default Value 0
Parameter Number 24
Access Rule GET/SET
Data Type WORD
Group Starter Protection
Units
Minimum Value 0
Maximum Value 65535
Default Value 64927
Bit
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
X Short Circuit — X Overload — X Phase Short — X Ground Fault — X Stall — X Control Power — X IO Fault — X Overtemperature — X Over Current — X Dnet Power Loss — X Internal Comm — X DC Bus Fault — X EEprom — X HW Fault — X Restart Retries
X Misc. Fault
Function
Bulletin 284G Programmable Parameters for Sensorless Vector Controllers 4-13
Pr Fault Reset
This parameter resets the Protection Fault on a transition 0 > 1.
StrtrDN FltState
This parameter in conjunction with Parameter 27 defines how the starter will respond when a DeviceNet fault occurs. When set to 1, hold to last state occurs. When set to 0, will go to DnFlt Value on DN faults as determined by Parameter 27.
StrtrDN FltValue
This parameter determines if the starter will be commanded in the event of a DevceNet fault. 0 = OFF 1 = ON
Parameter Number 25
Access Rule GET/SET
Data Type BOOL
Group Starter Protection
Units
Minimum Value 0
Maximum Value 1
Default Value 0
Parameter Number 26
Access Rule GET/SET
Data Type BOOL
Group Starter Protection
Units
Minimum Value 0
Maximum Value 1
Default Value 0
Parameter Number 27
Access Rule GET/SET
Data Type BOOL
Group Starter Protection
Units
Minimum Value 0
Maximum Value 1
Default Value 0
StrtrDN IdlState
This parameter in conjunction with Parameter 29 defines how the starter will respond when a DeviceNet network is idle. When set to 1, hold to last state occurs. When set to 0, will go to DnFlt Value on DN faults as determined by Parameter 29. 0 = Go to Idle Value 1 = Hold Last State
StrtrDN IdlValue
This parameter determines the state that starter assumes when the network is idle and Parameter 28 is set to 0. 0 = OFF 1 = ON
Parameter Number 28
Access Rule GET/SET
Data Type BOOL
Group Starter Protection
Units
Minimum Value 0
Maximum Value 1
Default Value 0
Parameter Number 29
Access Rule GET/SET
Data Type BOOL
Group Starter Protection
Units
Minimum Value 0
Maximum Value 1
Default Value 0
4-14 Bulletin 284G Programmable Parameters for Sensorless Vector Controllers
Last PR Fault
1 =Hdw Short Ckt 2 = Reserved 3 =Motor Overload (PF Fault Code 7) 4 =Drive Overload (PF Fault Code 64) 5 = Phase U to Gnd (PF Fault Code 38) 6 = Phase V to Gnd (PF Fault Code 39) 7 = Phase W to Gnd (PF Fault Code 40) 8 = Phase UV Short (PF4 Fault Code 41) 9 = Phase UW Short (PF Fault Code 42) 10 = Phase VW Short (PF Fault Code 43) 11 = Ground Fault (PF Fault Code 13) 12 = Stall (PF Fault Code 6) 13 = Control Pwr Loss 14 = Control Pwr Fuse 15 = Input Short 16 = Output Fuse 17 = Over Temp 18 = Heatsink OvrTmp (PF Fault Code 8) 19 = HW OverCurrent (PF Fault Code 12) 20 = SW OverCurrent (PF Fault Code 63) 21 = DNet Power Loss 22 = Internal Comm 23 = Drive Comm Loss (PF Fault Code 81) 24 = Power Loss (PF Fault Code 3) 25 = Under Voltage (PF Fault Code 4) 26 = Over Voltage (PF Fault Code 5) 27 = MCB EEPROM 28 = Base EEPROM 29 =Drive EEPROM (PF Fault Code 100) 30 = Wrong Base 31 = Fan RPM 32 = Power Unit (PF Fault Code 70) 33 = Drive IO Brd (PF Fault Code122) 34 = Restart Retries (PF Fault Code 33) 35 = Drive Aux In Flt (PF Fault Code 2) 36 = Analog Input (PF Fault Code 29) 37 = Drv Param Reset (PF Fault Code 48) 38 = SCV Autotune (PF Fault Code 80) 39 = Source Brake 40 = Reserved 41 = DB1 Comm 42 = DB1 Fault 43 = DB Switch Short
Parameter Number 61
Maximum Value 45
Access Rule GET
Data Type UINT
Group Starter Protection
Units
Minimum Value 0
Default Value 0
Warning Status
This parameter warns the user of a condition, without faulting
Parameter Number 62
Access Rule GET
Data Type WORD
Group Starter Protection
Units
Minimum Value 0
Maximum Value 65535
Default Value 0
User I/O Group
Bulletin 284G Programmable Parameters for Sensorless Vector Controllers 4-15
Off-to-On Delay
This parameter allows the installer to program a time duration before being reported ON.
On-to-Off Delay
This parameter allows the installer to program a time duration before being reported OFF.
In Sink/Source
This parameter allows the installer to program the inputs to be sink or source. 0 = Sink 1 = Source
Parameter Number 30
Access Rule GET/SET
Data Type UINT
Group User I/O
Units ms
Minimum Value 0
Maximum Value 65.000
Default Value 0
Parameter Number 31
Access Rule GET/SET
Data Type UINT
Group User I/O
Units ms
Minimum Value 0
Maximum Value 65.000
Default Value 0
Parameter Number 32 Access Rule GET/SET Data Type BOOL Group User I/O Units — Minimum Value 0 Maximum Value 1 Default Value 0
4-16 Bulletin 284G Programmable Parameters for Sensorless Vector Controllers
Miscellaneous Group
Keypad Mode
This parameter selects if the keypad operation is maintained or momentary. 0 = Maintained 1 = Momentary
Parameter Number 45
Access Rule GET/SET
Data Type BOOL
Group Misc.
Units
Minimum Value 0
Maximum Value 1
Default Value 0
Keypad Disable
This parameter disables all keypad function except for the OFF and RESET buttons. 0 = Not Disabled 1 = Disabled
Set to Defaults
This parameter if set to 1 will set the device to the factory defaults. 0 = No Operation 1 = Set to Defaults
Base Enclosure
Indicates the ArmorStart Base unit enclosure rating
0 = IP67 1 = Nema 4X 2 = SIL3/CAT4 3-15 = Reserved
Parameter Number 46
Access Rule GET/SET
Data Type BOOL
Group Misc.
Units
Minimum Value 0
Maximum Value 1
Default Value 0
Parameter Number 47
Access Rule GET/SET
Data Type BOOL
Group Misc.
Units
Minimum Value 0
Maximum Value 1
Default Value 0
Parameter Number 56
Access Rule GET
Data Type WORD
Group Misc.
Units
Minimum Value 0
Maximum Value 15
Default Value 0
Base Options
Indicates the options for the ArmorStart Base unit
Bit 0 = Reserved Bit 1 = Reserved Bit 2 = CP Fuse Detect Bits 3-7 = Reserved Bit 8 = 10A Base Bit 9 = 25A Base Bit 10-15 = Reserved
Parameter Number 57
Access Rule GET
Data Type WORD
Group Misc.
Units
Minimum Value 0
Maximum Value 15
Default Value 0
Bulletin 284G Programmable Parameters for Sensorless Vector Controllers 4-17
Wiring Options
Bit 0 = Conduit Bit 1 = Round Media Bits 2 = 28xG Bits 3-15 = Reserved
Starter Enclosure
Bit 0 = IP67 Bit 1 = NEMA 4x Bit 2 = SIL3/CAT4 Bits 3-15 reserved
Starter Option
Bit 0 = Reserved Bit 1 = Reserved Bit 2 = Reserved Bit 3 = Control Brake Bit 4 = Dynamic Brake Bit 5 = Reserved Bit 6 = Reserved Bit 7 = Reserved
Bits 8-15 = Reserved
Parameter Number 58
Access Rule GET
Data Type WORD
Group Misc.
Units
Minimum Value 0
Maximum Value 15
Default Value 0
Parameter Number 59
Access Rule GET
Data Type WORD
Group Misc.
Units
Minimum Value 0
Maximum Value 15
Default Value 0
Parameter Number 60
Access Rule GET
Data Type WORD
Group Misc.
Units
Minimum Value 0
Maximum Value 66535
Default Value 0
4-18 Bulletin 284G Programmable Parameters for Sensorless Vector Controllers
Drive DeviceNet Group
Drive Control
This parameter provides the status of drive parameters.
11109876543210
——————————— X Accel 1 En —————————— X — Accel 2 En ————————— X —— Decel 1 En ———————— X ——— Decel 3 En ——————— X ———— Freq Sel 0 —————— X ————— Freq Sel 1 ————— X —————— Freq Sel 2 ———— X ——————— Reserved ——— X ———————— Drv In 1 —— X ————————— Drv In 2 — X —————————— Drv In 3
X ——————————— Drv In 4
Parameter Number 48
Access Rule GET
Data Type WORD
Group Drive DeviceNet
Units
Minimum Value 0
Maximum Value 4095
Default Value 0
Bit
Function
Drvin PrFltState
This parameter, in conjunction with Parameter 50, defines how the Drive Digital Inputs 1…4 will respond when a protection trip occurs. When set to 1, Drive Digital Inputs 1…4 continue to operate as command via the network. When set to 0, Drive Digital Inputs 1…4 will open or close as determined by setting in Parameter 50. 0 = Go to PrFlt Value 1 = Ignore PrFlt
Drvin PrFltValue
This parameter determines the state of Drive Digital Inputs 1…4, assumes when a trip occurs and Parameter 49 is set to 0. 0 = Open 1 = Close
Parameter Number 49
Access Rule GET/SET
Data Type BOOL
Group Drive DeviceNet
Units
Minimum Value 0
Maximum Value 1
Default Value 0
Parameter Number 50
Access Rule GET/SET
Data Type BOOL
Group Drive DeviceNet
Units
Minimum Value 0
Maximum Value 1
Default Value 0
Bulletin 284G Programmable Parameters for Sensorless Vector Controllers 4-19
Drvin DNFltState
This parameter, in conjunction with Parameter 52, defines how the Drive Digital Inputs 1…4 will respond when a DeviceNet fault occurs. When set to 1, Drive Digital Inputs 1…4 hold to last state occurs. When set to 0, will go to DnFlt Value on DN faults as determined by Parameter 52. 0 = Go to Fault Value 1 = Hold Last State
Drvin DNFlt Value
This parameter determines the state of Drive Digital Inputs 1…4 when a DeviceNet Fault occurs and Parameter 51 is set to 0. 0 = OFF 1 = ON
Drvin DNIdlState
This parameter, in conjunction with Parameter 54, defines how the Drive Digital Input 1…4 will respond when a DeviceNet network is idle. When set to 1, hold to last state occurs. When set to 0, will go to DnFlt Value on DN faults as determined by Parameter 54. 0 = Go to Fault Value 1 = Hold Last State
Parameter Number 51
Access Rule GET/SET
Data Type BOOL
Group Drive DeviceNet
Units
Minimum Value 0
Maximum Value 1
Default Value 0
Parameter Number 52
Access Rule GET/SET
Data Type BOOL
Group Drive DeviceNet
Units
Minimum Value 0
Maximum Value 1
Default Value 0
Parameter Number 53
Access Rule GET/SET
Data Type BOOL
Group Drive DeviceNet
Units
Minimum Value 0
Maximum Value 1
Default Value 0
StrtrDN IdlValue
This parameter determines the state that Drive Digital Inputs 1…4 assume when the network is idle and Parameter 53 is set to 0. 0 = OFF 1 = ON
High Speed En
0 = Disabled 1 = Enabled
Parameter Number 54
Access Rule GET/SET
Data Type BOOL
Group Drive DeviceNet
Units
Minimum Value 0
Maximum Value 1
Default Value 0
Parameter Number 55
Access Rule GET/SET
Data Type BOOL
Group Drive DeviceNet
Units
Minimum Value 0
Maximum Value 1
Default Value 0
4-20 Bulletin 284G Programmable Parameters for Sensorless Vector Controllers
Display Group
Output Freq
Output frequency present at T1, T2, T3.
Commanded Freq
Value of the active frequency command. Displays the commanded frequency even if the drive is not running.
Output Current
Output Current present at T1, T2, T3.
Parameter Number 101
Related Parameters 102, 110, 134, 135, 138
Access Rule GET
Data Type UINT
Group Display Group
Units 0.1 Hz
Minimum Value 0.0
Maximum Value 400.0 Hz
Default Value Read Only
Parameter Number 102
Related Parameters 101, 113, 134, 135, 138
Access Rule GET
Data Type UINT
Group Display Group
Units 0.1 Hz
Minimum Value 0.0
Maximum Value 400.0 Hz
Default Value Read Only
Parameter Number 103
Access Rule GET
Data Type UINT
Group Display Group
Units 0.01
Minimum Value 0.00
Maximum Value Drive rated amps x 2
Default Value Read Only
Output Voltage
Output Current present at T1, T2, T3.
DC Bus Voltage
Present DC Bus voltage level.
Parameter Number 104
Related Parameters 131, 184, 188
Access Rule GET
Data Type UINT
Group Display Group
Units 1V AC
Minimum Value 0
Maximum Value 230V, 460V, or 600V AC
Default Value Read Only
Parameter Number 105
Access Rule GET
Data Type UINT
Group Display Group
Units 1V DC
Minimum Value
Maximum Value
Default Value Read Only
Based on Drive Rating
Loading...