Rockwell Automation 283D User Manual

Page 1
QUICK START
ARMORSTART® DISTRIBUTED MOTOR CONTROLLER
Getting Started
BULLETIN 283D
Introduction This guide provides the basic information required to start up your
This guide is intended for qualified service personnel responsible for setting up and servicing these devices. You must have previous experience with and a basic understanding of electrical terminology, configuration procedures, required equipment, and safety precautions. You should understand DeviceNet network operations, including how slave devices operate on a network and communicate with a DeviceNet master. You should also be familiar with RSNetWorx™ for DeviceNet. You must use RSNetWorx for DeviceNet Revision
3.21 Service Pack 2 or later. This software package is referred to often in this manual. Rockwell Automation product EDS files are available on the internet at: http://www.ab.com/networks/eds
®
Distributed Motor Controller. Factory default settings
.
Page 2
2
Installation The ArmorStart Distributed Motor Controller is convection cooled.
Operating temperature must be kept between -20…40°C (-4…104°F).
Dimensions Dimensions are shown in millimeters (inches). Dimensions are not intended
to be used for manufacturing purposes. All dimensions are subject to change.
Figure 1 Dimensions for IP67/NEMA Type 4 with Conduit Entrance
Publication 283D-QS001C-EN-P - July 2006
Page 3
3
ArmorStart device with a 10 A short circuit protection rating ArmorStart device with a 25 A short circuit protection rating
Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. All dimensions are subject to change.
Figure 2 Dimensions for IP67/NEMA Type 4 with ArmorConnect™ Connectivity
Publication 283D-QS001C-EN-P - July 2006
Page 4
4
Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. All dimensions are subject to change.
Figure 3 Dimensions for NEMA Type 4X with Conduit Entrance
Publication 283D-QS001C-EN-P - July 2006
Page 5
5
ArmorStart device with a 10 A short circuit protection rating ArmorStart device with a 25 A short circuit protection rating
Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. All dimensions are subject to change.
Figure 4 Dimensions for NEMA Type 4X with ArmorConnect Connectivity
Publication 283D-QS001C-EN-P - July 2006
Page 6
6
Primaries
Secondaries
Wiring Power, Control, Safety Monitor Inputs, and Ground Wiring
Table 1 provides the power, control, safety monitor inputs, and ground wire capacity and the tightening torque requirements. The power, control, ground, and safety monitor terminals will accept a maximum of two wires per terminal.
Table 1 Power, Control, Safety Monitor Inputs, Ground Wire Size and Torque
Specifications
Terminals Wire Size Torque Wire Strip Length
Terminal Designations for Conduit Entrance
Primary Terminal:
10.6…21.6 lb.-in.
2
(1.2…2.4 N•m)
Secondary Terminal:
5.3…7.3 lb.-in
(0.6…0.8 N•m)
5.0…5.6 lb.-in (0.6 N•m)
0.35 in. (9 mm)
0.35 in. (9 mm)
Power
and
Ground
Control and Safety
Monitor Inputs
Primary/Secondary
Terminal:
1.0…4.0 mm
(#18 …#10 AWG)
2
0.34mm
…4.0 mm2
(#22…#10 AWG)
As shown in Figure 5, the ArmorStart Distributed Motor Controller contains terminals for power, control, safety monitor inputs, and ground wiring. Access can be gained by removing the terminal access cover plate.
Figure 5 ArmorStart Power, Control, and Safety Monitor Terminals
Publication 283D-QS001C-EN-P - July 2006
Page 7
Table 2 Power, Control, Safety Monitor, and Ground Terminal Designations
Terminal Designations No. of Poles Description
SM1 2 Safety Monitor Input SM2 2 Safety Monitor Input
A1 (+) 2 Control Power Input
A2 (-) 2 Control Power Common
PE 2 Ground 1/L1 2 Line Power Phase A 3/L3 2 Line Power Phase B 5/L5 2 Line Power Phase C
Only available with the Safety Monitor option.
7
Operation of NEMA Type 4X Disconnect Handle
To Open Disconnect Handle
1. Rotate locking ring 45° until it stops.
2. To open, push the tab on the left-hand side and lift the access cover.
Note: The access door can not be closed when 140 (black handle) is in the
OFF position.
To Close Disconnect Handle for Lockout/Tag out
With disconnect handle in the ON position, rotate lockout/tag out ring counterclockwise until the disconnect handle is in the OFF position.
Note: The disconnect hanlde is designed to be used with a 1/4 in.
lockout/tag out padlock.
Publication 283D-QS001C-EN-P - July 2006
Page 8
8
RESET
OFF
Bulletin 280/281 ArmorStart
Bulletin 283 ArmorStart
Bulletin 284 ArmorStart
PLC
Bulletin 1492FB
Branch Circuit
Protective Device
Enclosure
Bulletin 1606
Power Supply
Bulletin 800F Emergency Stop Pushbutton
1606-XLSDNET4
DeviceNet
Power Supply
ArmorConnect Power Media Description
The ArmorStart Power Media offers both three-phase and control power cable system of cordsets, patchcords, receptacles, tees, reducers and accessories to be utilized with the ArmorStart Distributed Motor Controller. These cable system components allow quick connection of ArmorStart Distributed Motor Controllers and reduce installation time. They provide for repeatable, reliable connection of the three-phase and control power to the ArmorStart Distributed Motor Controller and motor by providing a plug and play environment that also avoids system mis-wiring. When specifying power media for use with the ArmorStart Distributed Motor Controllers (Bulletins 280, 281, 283, and 284) use only the Bulletin 280 ArmorConnect™ power media.
Figure 6 Three-Phase Power System Overview
Three-Phase Power Trunk- PatchCord cable with integral female or male connector on each end. (Example Part Number: 280-PWR35A-M*)Three-Phase Drop Cable- PatchCord cable with integral female or male connector on each end (Example Part Number: 280-PWR22A-M*)Three-Phase Power Tees and Reducer -
Tee connects to a single drop line to trunk with quick change connectors – Part Number: 280-T35 Reducing Tee connects to a single drop line (Mini) to trunk (Quick change) connector – Part Number: 280-RT35 Reducer connects from quick change male connector to mini female connector– Part Number: 280-RA35
Three-Phase Power Receptacles -
Female receptacles are a panel mount connector with flying leads – Part Number: 280-M35F-M1
Publication 283D-QS001C-EN-P - July 2006
Page 9
Enclosure
Bulletin 1492FB
Branch Circuit
Protective Device
Figure 7 Control Power Media System Overview
PLC
Bulletin 1606
Power Supply
1606-XLSDNET4
DeviceNet
Power Supply
9
Bulletin 280/281 ArmorStart
Bulletin 283 ArmorStart
RESET
OFF
Bulletin 284 ArmorStart
Bulletin 800F Emergency Stop Pushbutton
Control Power Media Patchcords - PatchCord cable with integral female or male connector on each end Example Part Number: 889N-F65GFNM-*
Control Power Tees - The E-stop In Tee (Part Number: 898N-653ES-NKF) is used to connect to the Bulletin 800F On-Machine E-Stop station using a
control power media patchcord. The E-stop Out tee (Part Number: 898N-653ST-NKF) is used with cordset or patchcord to connect to the ArmorStart Distributed Motor Controller.
Control Power Receptacles - Female receptacles are a panel mount connector with flying leads – Part Number: 888N-D65AF1-*
Publication 283D-QS001C-EN-P - July 2006
Page 10
10
Control Power Receptacle
Three-Phase Power Receptacle
Control Power Receptacle
Three-Phase Power Receptacle
ArmorStart devices with 10 A short circuit protection rating
ArmorStart devices with 25 A short circuit protection rating
3/4 in. Lock Nut 1 in. Lock Nut
Thomas & Betts Cord Grip Part Number: 2931NM 3/4 in. Stain Relief Cord Connector Cable Range: 0.31…0.56 in. Used with Control Power Media Cordset - Example Part Number:
889N-M65GF-M2
Thomas & Betts Cord Grip Part Number: 2940NM 1 in. Stain Relief Cord Connector Cable Range: 0.31…0.56 in. Used with Three-Phase Power Media Cordset - Example Part
Number: 280-PWR22G-M1
Cord Grips for ArmorStart Devices with 10 A short circuit protection rating
3/4 in. Lock Nut 1 in. Lock Nut
Thomas & Betts Cord Grip Part Number: 2931NM 3/4 in. Stain Relief Cord Connector Cable Range: 0.31…0.56 in. Used with Control Power Media Cordset - Example Part Number:
889N-M65GF-M2
Thomas & Betts Cord Grip Part Number: 2942NM 1 in. Stain Relief Cord Connector
Cable Range: 0.70…0.95 in. Used with Three-Phase Power Media Cordset - Example Part Number: 280-PWR35G-M1
Cord Grips for ArmorStart Devices with 25 A short circuit protection rating
ArmorStart with ArmorConnect Connectivity
Installing ArmorConnect Power Media using Cord Grips
Publication 283D-QS001C-EN-P - July 2006
Page 11
Terminal Designations Description Color Code
A1 (+) Control Power Input Blue A2 (-) Control Power Common Black
11
PE Ground Green/Yellow 1/L1 Line Power - Phase A Black 2/L2 Line Power - Phase B White 3/L3 Line Power - Phase C Red
ArmorConnect Cable Ratings
The ArmorConnect Power Media cables are rated per UL Type TC 600V 90 °C Dry 75 °C Wet, Exposed Run (ER) or MTW 600V 90 °C or STOOW 105 °C 600V - CSA STOOW 600V FT2. For additional information regarding ArmorConnect Power Media see the ArmorStart User Manual.
Branch Circuit Protection Requirements for ArmorConnect™ Three-Phase Power Media
When using ArmorConnect Three-Phase Power Media, only fuses can be used for the motor branch circuit protective device, for the group motor installations. The recommended fuse types are the following: Class CC, T, or J type fuses. For additional information, see the ArmorStart User Manual.
Publication 283D-QS001C-EN-P - July 2006
Page 12
12
Group Motor Installations for USA and Canada Markets
The ArmorStart Distributed Motor controllers are listed for use with each other in group installations per NFPA 79, Electrical Standard for Industrial Machinery. When applied according to the group motor installation requirements, two or more motors, of any rating or controller type, are permitted on a single branch circuit. Group Motor Installation has been successfully used for many years in the USA and Canada.
Wiring and Workmanship Guidelines
In addition to conduit and seal-tite raceway, it is acceptable to utilize cable that is dual rated Tray Cable, Type TC-ER and Cord, STOOW, for power and control wiring on ArmorStart installations. In the USA and Canada installations, the following guidance is outlined by the NEC and NFPA 79.
In industrial establishments where the conditions of maintenance and supervision ensure that only qualified persons service the installation, and where the exposed cable is continuously supported and protected against physical damage using mechanical protection, such as struts, angles, or channels, Type TC tray cable that complies with the crush and impact requirements of Type MC (Metal Clad) cable and is identified for such use with the marking Type TC-ER (Exposed Run)* shall be permitted between a cable tray and the utilization equipment or device as open wiring. The cable shall be secured at intervals not exceeding 1.8 m (6 ft) and installed in a “good workman-like” manner. Equipment grounding for the utilization equipment shall be provided by an equipment grounding conductor within the cable.
Publication 283D-QS001C-EN-P - July 2006
*Historically cable meeting these crush and impact requirements were designated and marked “Open Wiring”. Cable so marked is equivalent to the present Type TC-ER and can be used.
While the ArmorStart is intended for installation in factory floor environments of industrial establishments, the following must be taken into consideration when locating the ArmorStart in the application: Cables, including those for control voltage including 24V DC and communications, are not to be exposed to an operator or building traffic on a continuous basis. Location of the ArmorStart to minimize exposure to continual traffic is recommended. If location to minimize traffic flow is unavoidable, other barriers to minimize inadvertent exposure to the cabling should be considered. Routing cables should be done in such a manner to minimize inadvertent exposure and/or damage.
Additionally, if conduit or other raceways are not used, it is recommended that strain relief fittings be utilized when installing the cables for the control and power wiring through the conduit openings.
The working space around the ArmorStart may be minimized as the ArmorStart does not require examination, adjustment, servicing or
Page 13
13
maintenance while energized. In lieu of this service, the ArmorStart is meant to be unplugged and replaced after proper lockout/tag-out procedures have been employed.
Since the ArmorStart is available with a factory installed HOA keypad option this may require the ArmorStart to be selected and installed as follows if the application requires frequent use of the hand operated interface by the equipment operator:
1. They are not less than 0.6 m (2 ft) above the servicing level and are
within easy reach of the normal working position of the operator.
2. The operator is not placed in a hazardous situation when operating
them.
3. The possibility of inadvertent operation is minimized.
If the operated interface is used in industrial establishments where the conditions of maintenance and supervision ensure that only qualified persons operate and service the ArmorStart's operator interface, and the installation is located so that inadvertent operation is minimized then other installation locations with acceptable access can be provided.
DeviceNet Network Installation
The ArmorStart Distributed Motor Controller contains the equivalent of 30 in. (0.76 m) of Device Net drop cable's electrical characteristics and therefore 30 in. of drop cable must be included in the DeviceNet drop cable budget for each ArmorStart in addition to actual drop cable required for the installation.
Other DeviceNet System Design Considerations
The separation of the control power and DeviceNet power is recommended as a good design practice. This minimizes the load on the DeviceNet supply, and prevents transients which may be present on the control power system from influencing the communication controls.
Publication 283D-QS001C-EN-P - July 2006
Page 14
14
LED Status Indication The LED Status Indication provides 4 status LEDs and a Reset button. The
LEDs provide status indication for the following:
POWER LED The LED is illuminated solid green when control power is present and with the proper polarity
•RUN LED This LED is illuminated solid green when a start command and control power are present
NETWORK LED This bi-color (red/green) LED indicates the status of the communication link
FAULT LED Indicates Controller Fault (trip) condition
The “Reset Button” as a local trip reset.
Figure 8 LED Status Indication and Reset
DeviceNet Node Commissioning Establishing a DeviceNet Node Address
The ArmorStart is shipped with a default node address of 63 and Autobaud enabled. Each device on a DeviceNet network must have a unique node address or MAC ID which can be set to a value from 0…63. Keep in mind that most DeviceNet systems use address 0 for the master device (Scanner) and node address 63 should be left vacant for introduction of new slave devices. The ArmorStart offers two methods for node commissioning as shown in the following pages.
Node Commissioning using Software
To set the node address of the ArmorStart using software or other handheld tools, leave the hardware rotary switches in their default position (99) or insure that they are set to something greater then (63). With the hardware switches set, use the software or handheld tool to change the address.
When using software to node commission a device, it may be necessary to have the EDS file stored on the computer. The EDS file defines how the software such as RSNetWorx for DeviceNet will communicate to the ArmorStart. Rockwell Automation product EDS files are available on the internet at: http://www.ab.com/networks/eds
for DeviceNet Revision 3.21 Service Pack 2 or later.
. You must use RSNetWorx
Publication 283D-QS001C-EN-P - July 2006
Page 15
15
LSDLSD
MSDMSD
See Detail A
Detail A
Node Commissioning using Hardware
The ArmorStart is shipped with the hardware rotary switches set to a value of (99). If the switches are set to a value of (64) or above, the device will automatically configure itself to the software node address. If the switches are set to a value of (63) or less, the device will be at the node address designated by the switch configuration.
To set an address using the hardware rotary switches, simply set the switches to the desired node address. To access the node address rotary switches, three-phase and control power should be turned off. Then remove the starter module from the base unit. The rotary node address switches are located on the back side of the starter module. Change the switches to the desired node address. Re-install the starter module to the base unit. Reapply power and the device will re-start at the new address.
Figure 9 Rotary Node Address Configuration
System Configuration Information
The following information is provided to identify the default method for setting up communication to the ArmorStart. Additional configuration information and advanced settings help can be found in the ArmorStart User Manual, Publication 283-UM001*-EN-P.
Using Automap feature with default Input and Output (I/O) assemblies
The Automap feature available in all Rockwell Automation scanners will automatically map the information as shown below. If manual mapping is required, the information below can be used to map a device based on the default configuration.
Publication 283D-QS001C-EN-P - July 2006
Page 16
16
Table 3 Default I/O Messaging Data
Default
Message type Polled
Consumed data size 1 byte (Rx)
Produced data size 2 bytes (Tx)
Default Input and Output (I/O) Assembly Formats
The I/O assembly formats for the ArmorStart are identified by the value in parameter 11 (Consumed IO Assy.) and parameter 12 (Produced IO Assy.). These values determine the amount and arrangement of the information communicated to the master scanner. The tables below identify the default information produced and consumed by the Bulletin 283 devices. For additional formats and advance configurations please reference the user manual:
Defaults for Standard Distributed Motor Controllers
Table 4 Instance 160 - Default Consumed data for Standard Distributed Motor
Controller Output information arrangement (1 byte)
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
User Out BUser Out ANot
0
Used
Not
Used
Not
Used
Fault
Reset
—Run Fwd
Table 5 Instance 161 - Default Produced data for Standard Distributed Motor
Controller Input information arrangement (2 bytes)
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0
1
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
140M OnHOA
Ready
Status
Running
Fwd
User In 3 User In 2 User In 1 User In 0
Warning Tripped
Publication 283D-QS001C-EN-P - July 2006
Page 17
17
ATTENTION
!
Setting the Motor FLA
Control power must be applied to the Bulletin 283 Distributed Motor Controller, to gain access to the soft starter parameters.
The product should now be configured and communicating on the network. The last step is to program the proper motor FLA setting (parameter #106). This can be accomplished by using software such as RSNetWorx for DeviceNet or a handheld DeviceNet tool.
Use the software to access the device parameters screen. By default the motor FLA is set to the minimum FLA setting for the device and the overload trip class is set to 10. Set these parameters to the desired values and download to the device.
Select FLA setting (parameter #106) and enter a value that corresponds to the FLA of the motor connected to the ArmorStart. Make sure the Single radio button is selected and then select Download to Device.
The Overload Trip class for the Bulletin 283 Distributed Motor Controller is class 10.
The proper motor protection is now in place.
Figure 10 RSNetWorx Parameter Screen
Publication 283D-QS001C-EN-P - July 2006
Page 18
18
Quick Reference Troubleshooting
There are four LEDs on the front of the ArmorStart that can provide an indication as to the health of the device. The following is a brief explanation of the operation of each LED.
Table 6 LED Status Indication
LED Definition
Power
Run
Network
Fault
Table 7 Network LED Status Indication
Network Status LED Definition Possible Causes
Off The device has not completed the initialization, is not on an
active network, or may not be powered up.
Flashes green-red-off While waiting to detect the network baud rate, the LED will
flash this pattern about every 3 seconds.
Solid Green The device is operating in a normal condition, and is
communicating to another device on the network.
Flashing Green The device is operating in a normal condition, is on-line, but
with no connection to another device. This is the typical state for new devices.
Flashing Red Recoverable fault has occurred. Check to make sure the PLC and scanner are operating
Solid Red The device has detected a major error that has rendered it
incapable of communicating on the network (Duplicate MAC ID, Bus-off, media issue).
Flashing Red and Green The device is in a communication faulted state. Power cycling the device may resolve the problem;
This LED will be illuminated solid green when control power is present and with the proper polarity.
This LED will be illuminated solid green when a start command and control power are present.
This bi-color LED is used to indicate the status of the DeviceNet network. See the Network Status LED table below for additional information.
This LED is used to indicate the fault status of the ArmorStart. When the unit is faulted, the unit will respond with a specific blink pattern to identify the fault. See the Fault LED table below for additional information.
Check to make sure the product is properly wired and configured on the network.
If the product stays in this state it means that there is no set baud rate. Insure that at least one device on the network has a set baud rate.
No action required.
The device may need to be mapped to a master scanner, placed in a scanlist, or have another device communicate to it.
correctly and that there are no media/cabling issues. Check to see if other networked devices are in a similar state.
Troubleshooting should be done to ensure that the network is correct (terminators, lengths, etc.) and there is not a duplicate node problem. If other devices on the network appear to be operating fine and power cycling the device does not work, contact Technical Support.
however, if the problem continues, it may be necessary to contact Technical Support.
Publication 283D-QS001C-EN-P - July 2006
Page 19
Fault LED indications for Bulletin 283D ArmorStart Distributed Motor Controllers
19
Table 8 Controller Fault LED Definitions
Blink
Pattern
1
2
3
4
5
6
7
8 Over Temperature This fault is generated when the operating temperature has been exceeded. This fault cannot be disabled.
9
10
11
12
13
Definitions Possible Causes or Remedies
Short Circuit The motor circuit protector has tripped, or the internal wiring protection algorithm has detected an unsafe
current range. Try to reset the protector if tripped. If the condition continues, check the power wiring. This fault cannot be disabled.
Overload trip The load has drawn excessive current and based on the trip class selected, the device has tripped. Verify
that the load is operating correctly and the ArmorStart is properly set-up. This fault cannot be disabled.
Phase Loss The ArmorStart has detected a missing phase. Verify that three-phase voltage is present at the line side
connections. This fault can be disabled and is disabled by default.
Shorted SCR Prior to every start, the unit will check all SCRs for shorts and unit load connections to the motor. If there is
a shorted SCR in the SMC-3 and/or open load, the start will be aborted and a shorted SCR/open load fault will be indicated. This prevents damage from phase imbalance. This fault cannot be disabled.
Phase Rotation When enabled, 3-phase input power will be verified before starting. If input power phasing is detected to
be incorrect, the start will be aborted and a fault indicated. This fault can be disabled and is disabled by default.
Control Power The ArmorStart has detected a loss of the control power voltage. Check control voltage, wiring, and proper
polarity. Also, check and replace the control voltage fuse ,if necessary. This fault can be disabled and is disabled by default.
I/O Fault This error indicates a shorted sensor, shorted input device, wiring input mistakes, or a blown output fuse. If
this fault occurs, the offending problem should be isolated or removed prior to restarting the system. This fault can be disabled and is disabled by default.
Phase Imbalance The ArmorStart has detected a voltage imbalance. Check the power system and correct if necessary. This
fault can be disabled and is disabled by default.
DNet Power Loss DeviceNet power has been lost or has dropped below the 12V threshold. Check the state of the network
power supply and look for DeviceNet media problems. This fault can be disabled and is disabled by default.
Internal Communication This fault occurs when communication between the main board and the SMC-3 is lost. This fault cannot be
disabled.
Heatsink Over temperature/JAM
EEPROM Fault This is a major fault, which renders the ArmorStart inoperable. Possible causes of this fault are transients
This fault indicates either an over temperature fault or a JAM fault. The heatsink is monitored by thermistors and the SCR temperature is tracked by an algorithm. When a maximum temperature is reached by either, the microcomputer switches off the SMC and indicates a fault code of 12. A fault code of 12 could also indicate a JAM fault.This fault cannot be disabled.
induced during EEprom storage routines. If the fault was, initiated by a transient, power cycling should clear the problem otherwise replacement of the ArmorStart may be required. This fault cannot be disabled.
Hardware Fault This fault indicates that a serious hardware problem exists. Check for a base/starter module mismatch. If
14
16 Miscellaneous Fault This fault cannot be disabled.
no mismatch exists, the ArmorStart may need to be replaced. (Hdw Flt is the factory-enabled default setting.) This fault cannot be disabled.
Publication 283D-QS001C-EN-P - July 2006
Page 20
20
Bulletin 283 Parameters
Table 9 Starter Display and Parameter Settings
Parameter Name String Path (hex) Min Max Dflt Type Value
SMC Display
101 Phase A Current 002C – 01 – 08 0 32767 INT xxx.x Amps 102 Phase B Current 002C – 01 – 09 0 32767 INT xxx.x Amps 103 Phase C Current 002C – 01 – 0A 0 32767 INT xxx.x Amps 104 Average Current 002C – 01 – 05 0 32767 INT xxx.x Amps 105 % Therm Utilized 002C – 01 – 07 0 100 USINT xxx %
SMC Settings
106 FLA Setting 002C – 01 – 03 See Table 10 below Min I INT xxx.x Amps 107 OL Trip Class 002C – 01 – 04 0 3 1 BYTE 1 = 10 108 OL Reset Level 0029 – 01 – 131 0 100 75 BYTE xxx % 109 Start Time 000F - 06D - 01 1 45 10 USINT sec
110 Start Mode 000F - 06E - 01 0 1 0 BOOL
111 Current Limit 000F - 06 - 01 150 600 350 UINT
112 Initial Torque 000F - 070 - 01 0 90 60 USINT % LRT 113 Soft Stop Time 000F - 071 - 01 0 90 0 USINT sec 114 Kick Start 000F - 072 - 01 0.0 1.5 0.0 USINT sec
115 SCR Temp Reset Mode 000F - 073 - 01 0 1 0 BOOL
116 Phase Rotation 000F - 074 - 01 0 1 0 BOOL
0 = Current Limit
1 = Soft Start
Display multiplier of 10.
SMC is looking for values
between 15 and 60.
0 = Manual
1 = Auto Reset
0 = Disable
xxx % FLA
1 = Enable
Table 10 FLA Setting Ranges and Default Values (with indicated setting precision)
FLA Current Range (A)
Minimum Value Maximum Value
1.1 3.0 1.1
3.0 5.5 3.0
5.3 7.6 5.3
6.3 16.0 6.3
Default Value
Publication 283D-QS001C-EN-P - July 2006
Page 21
Figure 11 Bulletin 283 ArmorStart
LED Status Indication
Motor Connection
DeviceNet Connection (Mini/M18)
Local Disconnect
2 Outputs
(Micro/M12)
4 Inputs
(Micro/M12)
Source Brake Connector
Ground Terminal
Control Power
Control Power
Three-Phase Power
Three-Phase Power
Ground Terminal
Ground Te rm i na l
21
Figure 12 Bulletin 283 ArmorStart
Publication 283D-QS001C-EN-P - July 2006
Page 22
22
Table 11 DeviceNet Media
Description Length m (ft) Cat. No.
Sealed
KwikLink pigtail drops are Insulation
Displacement Connector (IDC) with integral Class
1 round cables for interfacing devices or power
supplies to flat cable
1 m (3.3) 2 m (6.5)
1485P-P1E4-B1-N5 1485P-P1E4-B2-N5
3 m (9.8) 1485P-P1E4-B3-N5
6 m (19.8) 1485P-P1E4-B6-N5
DeviceNet Mini- T-Port Tap
Gray PVC Thin Cable
Thick Cable
Right Keyway
Left Keyway
Connector
Mini Straight Female
Mini Straight Male
Mini Straight Female
Mini Right Angle Male
Mini Right Angle Female
Mini Straight Male
Mini Right Angle Female
Mini Straight Male
Mini Straight Female
Mini Straight Male
Mini Straight Female
Mini Right Angle Male
Mini Right Angle Female
Mini Straight Male
Mini Right Angle Female
Mini Straight Male
1485P-P1N5-MN5NF
1485P-P1N5-MN5KM
Cat. No.
1485G-P➋N5-M5
1485G-P➋W5-N5
1485G-P➋M5-Z5
1485G-P➋W5-Z5
1485C-P➌N5-M5
1485C-P➌W5-N5
1485C-P➌M5-Z5
1485C-P➌W5-Z5
See publication M116-CA001A-EN-P for complete cable selection information.
Replace symbol with desired length in meters (Example: 1485G-P1N5-M5 for a 1 m cable). Standard cable lengths: 1 m, 2 m, 3 m, 4 m, 5 m, and 6 m.
Replace symbol with desired length in meters (Example: 1485C-P1N5-M5 for a 1 m cable). Standard cable lengths: 1 m, 2 m, 3 m, 4 m, 5 m, 6 m, 8 m, 10 m, 12 m,
18 m, 24 m, and 30 m.
NOTE: Stainless steel versions may be ordered by adding an “S” to the cat. no. (Example: 1485CS-P1N5-M5)
Publication 283D-QS001C-EN-P - July 2006
Page 23
23
DC Micro Patchcord
DC Micro V-Cable
DC Micro Y-Cable
AC Micro Patchcord
Table 12 Sensor Media
Description
0
ArmorStart I/O
Connection
Pin Count Connector Cat. No.
Straight Female
Straight Male
889D-F4ACDM-
Input 5-Pin
Straight Female
0
0
Right Angle Male
Straight Female
889D-F4AACDE-
879D-F4ACDM-
Input 5-pin
0
Right Angle Male
0
Input 5-pin
0
Straight Female
Right Angle Male
879D-R4ACM-
879D-F4ACTE-
Straight Female
Straight Male
Output 3-pin
Straight Female
Right Angle Male
See publication M116-CA001A-EN-P for complete cable selection information.
Replace symbol with desired length in meters (Example: 889D-F4ACDM-1 for a 1 m cable). Standard cable lengths: 1 m, 2 m, 5 m, and 10 m.
NOTE: Stainless steel versions may be ordered by adding an “S” to the cat. no. (Example: 889DS-F4ACDM-1)
Table 13 Sealing Caps
Description Used on I/O Connection Catalog Number
Plastic Sealing Cap (M12) Input
Aluminum Sealing Cap Output 889A-RMCAP
To achieve IP67 rating, sealing caps must be installed on all unused I/O connections.
889R-F3AERM-
899R-F3AERE-
1485A-M12
Publication 283D-QS001C-EN-P - July 2006
Page 24
Registered Trademark List ArmorPoint and ArmorStart are registered trademarks of Rockwell Automation, Inc.
Trademark List ArmorConnect, RSLogix5000, PLC, RSNetWorx, and SLC are trademarks of Rockwell Automation, Inc. DeviceNet and the DeviceNet logo are trademarks of the Open Device Vendors Association (ODVA).
Publication 283D-QS001C-EN-P — July 2006 41053-384-05 (1)
Superecedes Publication 283D-QS001B-EN-P — September 2005 Copyright ©2006 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.
Loading...