Rockwell Automation 2094-EN02D-M01-S0 User Manual

Safety Reference Manual
Kinetix 6200 and Kinetix 6500 Safe Torque-off Multi-axis Servo Drives
Catalog Numbers 2094-SE02F-M00-S0, 2094-EN02D-M01-S0

Important User Information

IMPORTANT
Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 your local Rockwell Automation® sales office or online at http://www.rockwellautomation.com/literature/ important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
available from
) describes some
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.
Identifies information that is critical for successful application and understanding of the product.
Allen-Bradley, Kinetix, RSLogix, TechConnect, Rockwell Automation, and Rockwell Software are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
This manual contains new and updated information.

Summary of Changes

New and Updated Information

This revision includes new material for the 2090-K6CK-D44S0 low-profile connector kit and 2090-CS0DSDS-AAxx interface cable for cascading the safe torque-off signals from drive-to-drive.
Section Topic Page
Chapter 2 Chapter 3 Updated Safety Input Wiring diagram to use 24VPWR (IOD-14, IOD-15) 22
Chapter 4
Appendix A
Added a description and connection diagram for the 2090-K6CK-D44S0 connector kit. 16
Updated Cascaded Connections diagram to use 24VPWR (IOD-14, IOD-15) 27 Updated 2090-K6CK-D44M wiring examples to use 24VPWR (IOD-14, IOD-15) 28 Added 2090-K6CK-D44S0 wiring examples 29…30 Added Kinetix 6200/6500 cascading safe torque-off cable example Added 2090-CS0DSDS-AAxx cable pinout diagram and termination table Updated General Specifications with value for reset time Added footnotes to clarify the effect cascading drives has on reaction time and reset time
31
37
Rockwell Automation Publication 2094-RM002B-EN-P - May 2012 3
Summary of Changes
Notes:
4 Rockwell Automation Publication 2094-RM002B-EN-P - May 2012
Safety Concept

Table of Contents

Preface
About This Publication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Who Should Use This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Terminology. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Chapter 1
Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Safety Certification. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Important Safety Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Safety Category 4 Performance Definition. . . . . . . . . . . . . . . . . . . . . . 10
Stop Category 0 Definition. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Performance Level and Safety Integrity Level (SIL) CL3 . . . . . . . . . 11
PFD and PFH Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
PFD and PFH Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Safe State . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Safety Reaction Time. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Contact Information If Failure Occurs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Automatic Drive Replacement (ADR) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Installation and Wiring
Safe Torque-off I/O Signals
Chapter 2
Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
General Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Power Supply Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Wiring the Safety Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Using the 2090-K6CK-D44M Low-profile Connector Kit . . . . . . 14
Using the 2090-K6CK-D44S0 Low-profile Connector Kit . . . . . . 16
Using the Motion-allowed Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Terminal Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Chapter 3
Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Inputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Discrepancy Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Reset Input (Reset_In). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Safe Stop Output (SS_Out) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Safe Stop Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Safe Stop Wiring Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Rockwell Automation Publication 2094-RM002B-EN-P - May 2012 5
Table of Contents
Chapter 4
Multi-axis Cascaded Systems
Troubleshooting the Safe Torque-off Drive
Specifications
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Cascaded Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Safe Stop Wiring Examples. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
2090-K6CK-D44M Connector Kit Examples. . . . . . . . . . . . . . . . . . . 28
2090-K6CK-D44S0 Connector Kit Examples . . . . . . . . . . . . . . . . . . 29
Chapter 5
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Nonrecoverable Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Fault Recovery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Input and Output Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Fault Codes and Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Status Attributes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Guard Status Attributes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Guard Fault Attributes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Appendix A
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
General Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Index
6 Rockwell Automation Publication 2094-RM002B-EN-P - May 2012

Preface

About This Publication

This manual explains how the Kinetix® 6200 and Kinetix 6500 drives can be used in Safety Integrity Level (SIL) CL3, Performance Level [PLe], or Category (CAT) 4 applications. It describes the safety requirements, including PFD and PFH values and application verification information, and provides information on configuring and troubleshooting the Kinetix 6200 and Kinetix 6500 drives with safe torque-off functionality.

Who Should Use This Manual

Use this manual if you are responsible for designing, configuring, or troubleshooting safety applications that use Kinetix 6200 or Kinetix 6500 drives with safe torque-off functionality.
You must have a basic understanding of electrical circuitry and familiarity with Kinetix 6200 and Kinetix 6500 drives. You must also be trained and experienced in the creation, operation, and maintenance of safety systems.

Terminology

Table 1 - Common Safety Terminology
Abbreviation Full Term Definition
1oo2 One out of Two Refers to the behavioral design of a dual-channel safety system. CAT Category – EN European Norm The official European Standard.
ESPE Electro-sensitive Protective Equipment
FMEA Failure Mode and Effects Analysis
IEC International Electrotechnical Commission – IGBT Insulated Gate Bi-polar Transistors Typical power switch used to control main current.
HFT Hardware Fault Tolerance
MP Motion Power
OSSD Output Signal-switching Device
PC Personal Computer Computer used to interface with and program your safety system. PFD Probability of Failure on Demand The average probability of a system to fail to perform its design function on demand. PFH Probability of Failure per Hour The probability of a system to have a dangerous failure occur per hour. PL Performance Level ISO 13849-1 safety rating.
S0
2094-SE02F-M00-S0 Catalog number for Kinetix 6200 drives with Safe Torque-off functionality. 2094-EN02D-M01-S0 Catalog number for Kinetix 6500 drives with Safe Torque-off functionality.
The following table defines common safety terms used in this manual.
An assembly of devices and/or components working together for protective tripping or presence­sensing purposes and compri sing as a minimum:
·a sensing device.
·controlling/monitoring devices.
·output signal-switching devices (OSSD).
Analysis of potential failure modes to determine the effect upon the system and identify ways to mitigate those effects.
The HFT equals n, where n+1 faults could cause the loss of the safety function. An HFT of 1 means that 2 faults are required before safety is lost.
The component of the electro-sensitive protective equipment (ESPE) connected to the control system of a machine, which, when the sensing device is actuated during normal operation, responds by going to the OFF-state.
Rockwell Automation Publication 2094-RM002B-EN-P - May 2012 7
Preface
Table 1 - Common Safety Terminology (continued)
Abbreviation Full Term Definition
SFF Safe Failure Fraction The sum of safe failures plus the sum of dangerous detected failures divided by the sum of all failures. SIL Safety Integrity Level A measure of a products ability to lower the risk that a dangerous failure could occur. SS Safe Stop

Additional Resources

These documents contain additional information concerning related products from Rockwell Automation.
Resource Description
Kinetix 6200 and Kinetix 6500 Modular Multi-axis Servo Drive User Manual, publication 2094-UM002
Kinetix 6200 and Kinetix 6500 Safe Speed Monitoring Safety Reference Manual, publication 2094-RM001
Kinetix Safe-off Feature Safety Reference Manual, publication GMC-RM002
System Design for Control of Electrical Noise Reference Manual, publication GMC-RM001
EMC Noise Management DVD, publication GMC-SP004
Kinetix Motion Control Selection Guide, publication GMC-SG001
Safety Guidelines for the Ap plication, Installation and Maintenance of Solid State Control, publication
SGI-1.1
Information on installing, configuring, startup, troubleshooting, and applications for your Kinetix 6200 and Kinetix 6500 servo drive system.
Information on wiring, troubleshooting, and configuring your Kinetix 6200 and Kinetix6500 servo drives with the safe speed-monitoring functionality.
Information on wiring and troubleshooting your Kinetix 6000 servo drives with the safe-off feature.
Information, examples, and techniques designed to minimize system failures caused by electrical noise.
Specifications, motor/servo- drive system combinations, and accessories for Kinetix motion control products.
Describes important differences between solid state control and hardwired electromechanical devices.
You can view or download publications at:
http://www.rockwellautomation.com/literature
documentation, contact your local Allen-Bradley® distributor or Rockwell Automation sales representative.
. To order paper copies of technical
8 Rockwell Automation Publication 2094-RM002B-EN-P - May 2012
Safety Concept
Chapter 1

Introduction

Safety Certification

This chapter describes the safety performance level concept and how the Kinetix 6200 and Kinetix 6500 drives can meet the requirements for SIL CL3, CAT 4, or PLe applications.
Top ic Pag e
Safety Certification 9 PFD and PFH Definitions 11 PFD and PFH Data 11 Safe State 12 Safety Reaction Time 12 Contact Information If Failure Occurs 12 Automatic Drive Replacement (ADR) 12
The Kinetix 6200 and Kinetix 6500 drives are certified for use in safety applications up to and including SIL CL3 according to EN 61800-5-2, EN 61508, and EN 62061, Performance Level PLe and CAT 4 according to ISO 13849-1. Safety requirements are based on the standards current at the time of certification.
The TÜV Rheinland group has approved the Kinetix 6200 and Kinetix 6500 drives for use in safety-related applications where the de-energized state is considered to be the safe state. All of the examples related to I/O included in this manual are based on achieving de-energization as the safe state for typical Machine Safety and Emergency Shutdown (ESD) systems.
Rockwell Automation Publication 2094-RM002B-EN-P - May 2012 9
Chapter 1 Safety Concept
IMPORTANT

Important Safety Considerations

You are responsible for the following:
The set-up, safety rating, and validation of any sensors or actuators connected to the system
Completing a system-level risk assessment and reassessing the system any time a change is made
Certification of the system to the desired safety performance level
Project management and proof testing
Access control to the system, including password handling
When applying functional safety, restrict access to qualified, authorized personnel who are trained and experienced.
ATTENTION: When designing your system, consider how personnel will exit the machine if the door locks while they are in the machine. Additional safeguarding devices may be required for your specific application.

Safety Category 4 Performance Definition

The safety-related parts have to be designed with the following considerations to achieve Safety Category 4 according to ISO 13849-1:2006:
The safety-related parts of machine control systems and/or their protective equipment, as well as their components, must be designed, constructed, selected, assembled, and combined in accordance with relevant standards so that they can withstand expected conditions.
Basic safety principles must be applied.
A single fault in any of its parts does not lead to a loss of safety function.
A single fault is detected at or before the next demand of the safety
function, or, if this detection is not possible, then an accumulation of faults must not lead to a loss of the safety function.
The average diagnostic coverage of the safety-related parts of the control system must be high, including the accumulation of faults.
The mean time to dangerous failure of each of the redundant channels must be high.
Measures against common cause failure must be applied.

Stop Category 0 Definition

Stop Category 0 is achieved with immediate removal of power to the actuator, resulting in an uncontrolled coast to stop. Safe Torque Off accomplishes a Stop Category 0 stop.
10 Rockwell Automation Publication 2094-RM002B-EN-P - May 2012
Safety Concept Chapter 1

Performance Level and Safety Integrity Level (SIL) CL3

For safety-related control systems, Performance Level (PL), according to ISO 13849-1, and SIL levels, according to EN 61508 and EN 62061, include a rating of the system’s ability to perform its safety functions. All of the safety-related components of the control system must be included in both a risk assessment and the determination of the achieved levels.
Refer to the ISO 13849-1, EN 61508, and EN 62061 standards for complete information on requirements for PL and SIL determination.

PFD and PFH Definitions

PFD and PFH Data

Safety-related systems can be classified as operating in either a Low Demand mode, or in a High Demand/Continuous mode:
Low Demand mode: where the frequency of demands for operation made on a safety-related system is no greater than one per year or no greater than twice the proof-test frequency.
High Demand/Continuous mode: where the frequency of demands for operation made on a safety-related system is greater than once per year or greater than twice the proof test interval.
The SIL value for a low demand safety-related system is directly related to order­of-magnitude ranges of its average probability of failure to satisfactorily perform its safety function on demand or, simply, average probability of failure on demand (PFD). The SIL value for a High Demand/Continuous mode safety-related system is directly related to the probability of a dangerous failure occurring per hour (PFH).
These PFD and PFH calculations are based on the equations from Part 6 of EN 61508 and show worst-case values.
This table provides data for a 20-year proof test interval and demonstrates the worst-case effect of various configuration changes on the data.
Table 2 - PFD and PFH for 20-year Proof Test Interval
Attribute Value
PFH [1e-9] 4.09 PFD [1e-4] 3.90 SFF % 99.5
Rockwell Automation Publication 2094-RM002B-EN-P - May 2012 11
Chapter 1 Safety Concept
IMPORTANT

Safe State

Safety Reaction Time

The Safe State encompasses all operation that occurs outside of the other monitoring and stopping behavior defined as part of the drive. While the drive is in the Safe State, all safety control outputs are in their safe state (de-energized).
When you cycle power, the drive enters the Safe State for self-testing. If the self­tests pass, the drive remains in the Safe State until a successful safe stop reset occurs.
If a Safe State fault is detected, the drive goes to the Safe State. This includes faults related to integrity of hardware or firmware.
For more information on faults, refer to Chapter 5
The safety reaction time is the amount of time from a safety-related event as input to the system until the system is in the Safe State.
The safety reaction time from an input signal condition that triggers a safe stop, to the initiation of the Safe Stop Type, is 12 ms, max.
For cascaded systems, the reaction time is multiplied by the number of drives in the drive system. For example, drive systems with three cascaded drives (first, middle, and last), have a reaction time of 36 ms, max.
.

Contact Information If Failure Occurs

Automatic Drive Replacement (ADR)

If you experience a failure with any safety-certified device, contact your local Rockwell Automation distributor. With this contact, you can do the following:
Return the device to Rockwell Automation so the failure is appropriately logged for the catalog number affected and a record is made of the failure.
Request a failure analysis (if necessary) to determine the probable cause of the failure.
You can replace IAM and AM power modules, and the associated control modules, at any time without any need for configuration or program changes.
12 Rockwell Automation Publication 2094-RM002B-EN-P - May 2012
Installation and Wiring
Chapter 2

Introduction

General Safety Information

This chapter provides details on connecting devices and wiring the 2090-K6CK-D44M and 2090-K6CK-D44S0 low-profile connector kits.
Top ic Pag e
General Safety Information 13 Power Supply Require ments 14 Wiring the Safety Connections 14 Terminal Connections 18
ATTENTION: The drive is intended to be part of the safety-related control system of a machine. Before installation, a risk assessment should be performed to determine whether the specifications of this safety option are suitable for all foreseeable operational and environmental characteristics for the system to which it is to be installed.
Observe all electrical safety regulations stipulated by the appropriate technical authorities.
ATTENTION: Make sure that the electrical power supplied to the drive is switched off before making connections.
Refer to the Kinetix 6200 and Kinetix 6500 Modular Multi-axis Servo Drive User Manual, publication 2094-UM002
Rockwell Automation Publication 2094-RM002B-EN-P - May 2012 13
, for more information.
Chapter 2 Installation and Wiring
IMPORTANT
IMPORTANT

Power Supply Requirements

Wiring the Safety Connections

The external power supply must conform to the Directive 2006/95/EC Low Voltage, by applying the requirements of EN61131-2 Programmable Controllers, Part 2 - Equipment Requirements and Tests and one of the following :
EN60950 - SELV (safety extra low voltage)
EN60204 - PELV (protective extra low voltage)
IEC 60536 Safety Class III (SELV or PELV)
UL 508 Limited Voltage Circuit
21.6…28.8V DC must be supplied by a power supply that complies with
IEC/EN60204 and IEC/EN 61558-1
For planning information, refer to the guidelines in Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1
Safety, I/O, and auxiliary feedback connections are made by using the 2090-K6CK-D44M low-profile connector kit. I/O and cascading drive-to-drive safe torque-off connections can be made by using the 2090-K6CK-D44S0 low-profile connector kit. When the safety, I/O, and auxiliary feedback are not required for the application, the motion-allowed plug is used to make the drive operational.
.
Remove power to the IAM or AM power module before installing either the low-profile connector kit or the motion-allowed plug.

Using the 2090-K6CK-D44M Low-profile Connector Kit

The 2090-K6CK-D44M connector kit includes one motion-allowed jumper. Remove the jumper to wire the safe torque-off connections. Install the jumper when your application is not using the safe torque-off functionality, but your application requires I/O or auxiliary feedback connections.
You must remove the motion-allowed jumper to wire the safe torque-off connections.
14 Rockwell Automation Publication 2094-RM002B-EN-P - May 2012
Figure 1 - Making 2090-K6CK-D44M Safety Connections
28 27 26 25 24 23 22 21 20 19 18 17 15 14 0
AUX FEEDBACK
0 11 10 9 8 7 6 5 4 3 2 1
0 39 41 40 39 42 40 39 43 40 39 44 40
INPUTS
0 38 37 36 35 34 33 32 31 30 29 28 27 28 27 28 27 28 27
S1 ONLY
S1 ONLY
S0&S1 W/S0 DISABLED
28 27 26 25 24 23 22 21 20 19 18 17 15 14 0
AUX FEEDBACK
0 11 10 9 8 7 6 5 4 3 2 1
0 39 41 40 39 42 40 39 43 40 39 44 40
INPUTS
0 38 37 36 35 34 33 32 31 30 29
28 27 28 27 28 27 28 27
S1 ONLY
S1 ONLY
S0&S1 W/S0 DISABLED
28 27 26 25 24 23 22 21 20 19 18 17 15 14 0
2090-K6CK-D44M Low-profile Connector Kit
Use tie wraps (4x)
for stre ss relief.
Turn clamps over for smaller
diameter cables.
Aux Feedback and I/O
Wires and Cables
Motion-allowed Jumper Installation (applies to 2094-xx02x-M0x-S0 control modules)
Safety Wires
and Cables
Use shield clamps (3x) for
high-frequency bonding.
Kit pin numbering corresponds to the IOD
connector. Pins 27, 28, 39, and 40 are given
multiple terminals to accommodate
additional connections.
Refer to page 18
for safety, auxiliary
feedback, and I/O signal descriptions.
Shrink-wrapped
Insulation
Clamp
Installation and Wiring Chapter 2
Refer to the Kinetix 6200 and Kinetix 6500 Modular Servo Drive User Manual, publication 2094-UM002
, for other wiring examples using low-profile connector
kits.
Rockwell Automation Publication 2094-RM002B-EN-P - May 2012 15
Chapter 2 Installation and Wiring
IMPORTANT
P2
P1
P4
P3
P6
P5
P2
P1
P4
P3
P6
P5
40 42 39 39 41 40 0
40 44 39 39 43 40
14 25 17 26 18 15
0 0
27 28 19 20 23 24 21 22
27 28 19 20 23 24 21 22
14 25 17 26 18 15 0 0
40 42 39 39 41 40 0
40 44 39 39 43 40
S0 INS0OUT
14 25 17 26 18 15 0 0
2090-K6CK-D44S0 Low-profile Connector Kit
Turn clamps over for smaller
diameter cables.
Motion-allowed Jumper Installation (applies to 2094-xx02x-M0x-S0 control modules)
Pin numbering corresponds to the IOD (44 pin)
connector. IOD-39 = P1-39 and P2-39.
Pins 39 and 40 are given multiple terminals to
accommodate connections for each of the inputs.
Refer to page 18
for safety and
I/O signal descriptions.
Shrink-wrapped Insulation
Use shield c lamps (2) to maximize co ntact with
cable shield for high-frequency bonding.
Use tie wraps (2) for stress relief.
I/O
Cable/Wires
Cascading S0
Safe-off Cables
Safety Cable/Wire s

Using the 2090-K6CK-D44S0 Low-profile Connector Kit

The 2090-K6CK-D44S0 connector kit includes two motion-allowed jumpers. Remove the jumpers to wire the safe torque-off connections. Install the jumper when your application is not using the safe torque-off functionality, but your application requires I/O connections.
The 2090-K6CK-D44S0 connector kit lets you cascade the safe torque-off signals from drive-to-drive by using the 2090-CS0DSDS-AAxx interface cable.
You must remove the motion-allowed jumpers to wire the safe torque-off connections.
Figure 2 - Making 2090-K6CK-D44S0 Safety Connections
16 Rockwell Automation Publication 2094-RM002B-EN-P - May 2012
Refer to the Kinetix 6200 and Kinetix 6500 Modular Servo Drive User Manual, publication 2094-UM002 kits.
, for other wiring examples using low-profile connector
Installation and Wiring Chapter 2
IOD Connector
TEST_OUT_1
TEST_OUT_0
RESET_IN
RESET_REF
28
27
26
25
24
23
22
21
20
19
18
17
15
14
SLS_IN_CH3
SLS_IN_CH2
SS_OUT_CH1
SS_OUT_CH0
SS_IN_CH1
SS_IN_CH0
SCOM
SPWR
28
27
26
25
24
23
22
21
20
19
18
17
15
14
24VCOM
24VPWR
Kinetix 6200 and Kinetix 6500 Safe Torque-o ff Control Mod ule IOD (44-pin) Connector
TIP
Kinetix 6200 or Kinetix 6500 Drive
(safe torque- off control module)
I/O, safety, and auxiliary feedback (IOD) 44-pin connector with motion-allowed plug installed.

Using the Motion-allowed Plug

Because the safe torque-off feature of Kinetix 6200 and Kinetix 6500 control modules (catalog numbers 2094-xx02x-M0x-S0) is not configured, the safe torque-off functionality is always operational. If you do not want to use the safe torque-off feature, wiring of the safe stop inputs (SS_IN_CH0/1) are still required to operate the drive.
For this reason, the 2094-xx02x-M0x-S0 control modules ship with the motion-allowed plug. The plug inserts into the IOD connector and provides connections designed to defeat the safe torque-off function.
Figure 3 - Motion-allowed Plug Wiring
If your application does not require any I/O, safety, or auxiliary feedback connections, use the motion-allowed plug supplied with your drive to defeat the safe torque-off functionality.
Figure 4 - Motion-allowed Plug Installation
Rockwell Automation Publication 2094-RM002B-EN-P - May 2012 17
Chapter 2 Installation and Wiring

Terminal Connections

Prepare wires for termination on the IOD connector with a 5 mm (0.2 in.) strip length. Tighten all terminal screws firmly and recheck them after all connections have been made. Recommended terminal screw torque is 0.4 N•m (3.5 lb•in).
Refer to page 37
Table 3 - IOD Connector Pinouts
IOD
Description Signal
Pin
0 Chassis ground Shield
Sine differential input +
1
A differential input + Sine differential input -
2
A differential input ­Cosine differential input +
3
B differential input + Cosine differential input -
4
B differential input ­Data differential input +
5
Index differential input + Data differential input -
6
Index differential input ­7 Clock output + AUX_CLK+ 29 Reserved – 8 Clock output - AUX_CLK- 30 Reserved – 9 Encoder 5V power output EPWR_5V 31 Reserved – 10 Encoder common ECOM 32 Reserved – 11 Encoder 9V power output EPWR_9V 33 Reserved – 12 Reserved 34 Reserved – 13 Reserved 35 Reserved – 14 24V power out 24VPWR 15 24V common 24VCOM 16 Reserved 38 Reserved – 17 Safety 24V power input SPWR 39 24V power out 24VPWR 18 Safety 24V common SCOM 40 24V common 24VCOM 19 Safe stop input 0 SS_IN_CH0 41 Digital input 1 INPUT1 20 Safe stop input 1 SS_IN_CH1 42 Digital input 2 INPUT2 21 Safe stop output 0 SS_OUT_CH0 43 Digital input 3 INPUT3 22 Safe stop output 1 SS_OUT_CH1 44 Digital input 4 INPUT4
AUX_SIN + AUX_A+
AUX_SIN ­AUX_A-
AUX_COS + AUX_B+
AUX_COS ­AUX_B-
AUX_DATA+ AUX_I+
AUX_DATA­AUX_I-
(1)
(1)
for the I/O signal electrical specifications.
IOD
Description Signal
Pin
23 Safe stop input 2 SS_IN_CH2
24 Safe stop input 3 SS_IN_CH3
25 Reset reference RESET_REF
26 Reset input RESET_IN
27 Pulse test output 0 TEST_OUT_0
28 Pulse test output 1 TEST_OUT_1
36 Reserved – 37 Reserved
(2)
(1) Use this supply to power the Safety 24V (SPWR/SCOM) input. Do not connect this 24V supply to any external safet y device. Refer to Figure 8 on page 22 for an example. (2) Use signals 24VPWR and 24VCOM (IOD-39 and IOD-40) as a 24V DC source to operate the digital inputs (50 mA maximum per input).
18 Rockwell Automation Publication 2094-RM002B-EN-P - May 2012
Safe Torque-off I/O Signals
IMPORTANT
Chapter 3

Introduction

Inputs

This chapter describes the safe torque-off input and output signals of the Kinetix 6200 and Kinetix 6500 drives.
Top ic Pag e
Inputs 19 Outputs 23 Safe Stop Wiring Example 26
The Kinetix 6200 and Kinetix 6500 drives have two sets of dual-channel inputs. Each dual-channel input supports the safe stop (SS) function of the drive.
The SS_IN_CH0/1 inputs are intended for connection to a non-switching E-stop device (dry contact). It controls the safe-off request initiated by a transition from ON to OFF.
The SS_IN_CH2/3 inputs are intended for connection to an OSSD device or as a cascaded input from another safety axis. It controls the safe-off request initiated by a transition from ON to OFF.
The SS_IN_CH0/1 inputs are electrically identical and rely on a pair of pulse test outputs, TEST_OUT_0 and TEST_OUT_1.
Only one pair of dual-channel inputs can be used at the same time.
When both channels are active, if one channel’s input terminal transitions from active to inactive and back to active, while the other channel’s input terminal remains active, both channels must go inactive at the same time before the evaluated status may return to ON. This condition is called ‘cycle inputs required’.
Rockwell Automation Publication 2094-RM002B-EN-P - May 2012 19
Chapter 3 Safe Torque-off I/O Signals
Channel 0
Active
Inactive
Channel 1
Active
Inactive
Evaluated Status
ON
OFF
Cycle Inputs Required
SS_IN_CH0 or
SS_IN_CH2
SS_IN_CH1 or
SS_IN_CH3
Gate Power
and Gate Enable
RESET_IN
Fault
t
on
Ton (max) = 20 ms plus Debounce Filter Delay
(if applicable).
Safe-off inputs return to inactive state before Gate Power can be restored.
Input Discrepancy
Time (1.0 s)
Latch Input Error
Time (1. 0 s)
Figure 5 - Cycle Inputs Required
An Input fault occurs if the inputs are discrepant for longer than one second.
For SS_IN_CH0/1, use TEST_OUT_0/1 as a reference signal, or a fault occurs.
For more information on I/O faults, refer to Troubleshooting the Safe Torque-off
Drive on page 33.

Discrepancy Time

The maximum discrepancy time between two inputs is 1.0 second. If both inputs do not change within 1.0 second, an input fault is displayed, the safety circuit is activated, and torque is removed from the motor.
Figure 6 - Discrepancy Time
20 Rockwell Automation Publication 2094-RM002B-EN-P - May 2012
Behavior of reset and safe-off inputs while transitioning from Safe_Off state to Safe_Monitor state.
SS_IN_CH0 or
IMPORTANT
IMPORTANT
IMPORTANT
SS_IN_CH2
SS_IN_CH1 or
SS_IN_CH3
RESET_IN
Fault
Safe Torque-off I/O Signals Chapter 3
Figure 7 - Reset Behavior
Gate Power
and Gate Enable
RESET_REQUIRED
(waiting for reset)
SO_REQUEST_VALUE
SO_IN_VALUE
20 ms, max
When the inactive ‘OFF’ state of RESET_IN transitions to the active ‘ON’ state, following a successful reset, the time to re-enable gate power and gate enable, and set dual-channel safe-off outputs to active ‘ON’ state will not exceed 20 ms.
If SS_IN_CH0/1 are used, then additional debounce filter delay of 36 ms is applied to Ton delay.
After a successful SO Reset, the RSLogix™ 5000 software program must issue an MSF instruction prior to restarting the machine.
Rockwell Automation Publication 2094-RM002B-EN-P - May 2012 21
Chapter 3 Safe Torque-off I/O Signals
Test_Out_0 (IOD-27) Test_Out_1 (IOD-28)
Dual-channel Equivalent Safety Device
Light Curtain
or
Safety Mat
Drive
Drive
SS_IN_CH2 (IOD-23) SS_IN_CH3 (IOD-24)
Test_Out_0 (IOD-27) Test_Out_1 (IOD-28)
SS_IN_CH2 (IOD-23) SS_IN_CH3 (IOD-24)
24VPWR (IOD-14) 24VCOM (IOD-15)
SPWR (IOD-17)
SPWR (IOD-17)
SCOM (IOD-18)
SCOM (IOD-18)
SS_IN_CH0 (IOD-19) SS_IN_CH1 (IOD-20)
SS_IN_CH0 (IOD-19) SS_IN_CH1 (IOD-20)
OSSD1 OSSD2
24V DC
24VPWR (IOD-14) 24VCOM (IOD-15)
IMPORTANT
Figure 8 - Safety Input Wiring Examples
Cross wiring of Test Outputs to Inputs is not allowed. For example, do not connect TEST_OUT_0 to Input 1 or TEST_OUT_1 to Input 0.
Table 4 - IOD Connector Input Terminals
Safe Stop Function Signal IOD Pin
Input 0 = Channel 0 SS_IN_CH0 IOD-19 Input 1 = Channel 1 SS_IN_CH1 IOD-20 Input 2 = Channel 2 SS_IN_CH2 IOD-23 Input 3 = Channel 3 SS_IN_CH2 IOD-24
Short-circuits of the input loop to ground or 24V will be detected. For dual-channel inputs, cross loops will also be detected.
22 Rockwell Automation Publication 2094-RM002B-EN-P - May 2012
Safe Torque-off I/O Signals Chapter 3
RESET_IN
RESET_IN
IOD-25
IOD-26

Reset Input (Reset_In)

The Reset input is for reset and monitoring of the safety circuit. RESET_REF provides reference voltage for the RESET_IN input.
For automatic reset option, wire the reset input terminal (IOD-26) to the RESET_REF terminal, (IOD-25).
Figure 9 - RESET_IN Terminal Example

Outputs

The drive has safe-stop safety control outputs.
See the specifications in Appendix
A to verify your power requirements.

Safe Stop Output (SS_Out)

The safe state for this signal is OFF.
These outputs are typically used in multi-axis applications. In multi-axis applications, you can use these outputs to daisy-chain the master drive to a slave.
For SS_Out to SS_In_CH2/3 cascaded signals, the interface is a dual-channel sourcing solid-state safety output connected to a dual-channel safety input. The outputs are pulse-tested.
Rockwell Automation Publication 2094-RM002B-EN-P - May 2012 23
Chapter 3 Safe Torque-off I/O Signals
Drive 1
SS_OUT_CH0
SS_OUT_CH1
Drive 2
SS_IN_CH2
SS_IN_CH3
IOD-21
IOD-23
IOD-22
IOD-24
Figure 10 - SS_Out to SS_In Connections for Multi-axis Applications
For more information on multi-axis configurations, see Cascaded Configurations starting on page 27
.
Alternately, the first SS_Out output may be used to signal a programmable logic controller (PLC) that a Safe Stop has been requested.
If the SS_In is ON (closed) and a successful Safe Stop Reset is performed, the SS_Out output is turned ON.
If the Safe Stop is initiated or if a Safe Stop is initiated due to a fault, the SS_Out output is turned OFF.
If an error is detected on either channel of the dual-channel output, a fault occurs, which initiates the Category 0 Stop. The fault is latched until the drive is successfully reset.
For more information on faults, refer to Chapter
5.
24 Rockwell Automation Publication 2094-RM002B-EN-P - May 2012
Safe Torque-off I/O Signals Chapter 3

Safe Stop Reset

Safe torque-off drives provide a Reset Input (RESET_IN) for resetting the drive after a fault, and for synchronizing restart of several cascading drives. The Reset Input (RESET_IN) is not safety certified and does not have dual-channel capability. Automatic reset functionality, if needed, can be achieved by hard­wiring the RESET_REF and RESET_IN terminals together.
The Safe-off Reset (SO Reset) is a reset from the Safe-off State to the active safe monitor state. The reset is successful if the SS_In input is ON and no faults are present. The SO Reset occurs after the SS_IN inputs have transitioned to ON and RESET_IN is ON. After a successful SO Reset, RESET_IN may transition to the OFF state.
AT TE NT IO N: A reset of the Safe Stop function can result in machine operation.
AT TE NT IO N: The Safe Stop Reset does not provide safety-related restart
according to EN 60204-1. Restart must be performed by external measures if automatic restart could result in a hazardous situation. You are responsible for determining whether automatic restart could pose a hazard.
When an SO Reset is requested, all diagnostic tests that can be performed prior to outputs being energized are performed prior to a successful SO Reset. If a diagnostic test can be performed only when outputs are energized, the test is performed immediately following the SO Reset.
Faults
If a fault occurs, the SS_In inputs in use must turn OFF and ON again to reset the GuardResetRequiredStatus bit before a successful SO Reset can occur.
Rockwell Automation Publication 2094-RM002B-EN-P - May 2012 25
Chapter 3 Safe Torque-off I/O Signals
GND
+24V DC
IOD Connector
TEST_OUT_1
TEST_OUT_0
RESET_IN
RESET_REF
28
27
26
25
24
23
22
21
20
19
18
17
28
27
26
25
24
23
22
21
20
19
18
17
SLS_IN_CH3
SLS_IN_CH2
SS_OUT_CH1
SS_OUT_CH0
SS_IN_CH1
SS_IN_CH0
SCOM
SPWR
(1)
SS
Request
Reset
Safe Stop to Next Axis (option al)
Kinetix 6200 and Kinetix 6500 Safe Torque-off Control Module IOD (44-pin) Connector

Safe Stop Wiring Example

This example illustrates safe stop wiring.
Figure 11 - Master, Safe Stop (First or Single Unit)
(1) SCOM must be at the same potential as the drive common because of the encoder signal.
26 Rockwell Automation Publication 2094-RM002B-EN-P - May 2012
Multi-axis Cascaded Systems
Test_Out_0 (IOD-27) Test_Out_1 (IOD-28)
First Unit
Axis 1
SS_IN_CH2 (IOD-23) SS_IN_CH3 (IOD-24)
24VPWR (IOD-14) 24VCOM (IOD-15)
SPWR (IOD-17)
SCOM (IOD-18)
SS_IN_CH1 (IOD-20) SS_IN_CH0 (IOD-19)
Middle Unit
Axis 2
Last Unit
Axis 3
RESET_REF (IOD-25) RESET_IN (IOD-26)
SS_IN_CH2 SS_IN_CH3
SS_IN_CH2 SS_IN_CH3
Test_Out_0 Test_Out_1
24VPWR 24VCOM
SPWR
SS_IN_CH1 SS_IN_CH0
RESET_REF RESET_IN
(IOD-21) SS_OUT_CH0
(IOD-22) SS_IN_CH1
SS_OUT_CH0
SS_IN_CH1
SS_OUT_CH0
SS_IN_CH1
SCOM
SCOM
Test_Out_0 Test_Out_1
24VPWR 24VCOM
SPWR
SS_IN_CH1 SS_IN_CH0
RESET_REF RESET_IN
Dual-channel Equivale nt Safety Device
Chapter 4

Introduction

Cascaded Configurations

This chapter describes cascaded multi-axis drive operation and provides wiring examples for cascaded multi-axis drive systems.
Top ic Pag e
Cascaded Configurations 27 Safe Stop Wiring Examples 28
For cascaded drives, connect the safety switches to the safety inputs (SS_In) of only the first axis. The inputs are cascaded from one drive to the next by connecting the outputs from the previous drive to the inputs of the next drive.
Figure 12 - Cascaded Connections
Reset
Rockwell Automation Publication 2094-RM002B-EN-P - May 2012 27
Chapter 4 Multi-axis Cascaded Systems
IOD Connector
TEST_OUT_1 TEST_OUT_0
RESET_IN
RESET_REF
28 27 26 25 24 23 22 21 20 19 18 17 15 14
28 27 26 25 24 23 22 21 20 19 18 17 15 14
SS_IN_CH3
SS_IN_CH2 SS_OUT_CH1 SS_OUT_CH0
SS_IN_CH1
SS_IN_CH0
SCOM SPWR
Reset
24VCOM 24VPWR
24VCOM 24VPWR
24VCOM 24VPWR
IOD Connector
TEST_OUT_1 TEST_OUT_0
RESET_IN
RESET_REF
28 27 26 25 24 23 22 21 20 19 18 17 15 14
28 27 26 25 24 23 22 21 20 19 18 17 15 14
SS_IN_CH3
SS_IN_CH2 SS_OUT_CH1 SS_OUT_CH0
SS_IN_CH1
SS_IN_CH0
SCOM SPWR
IOD Connector
TEST_OUT_1 TEST_OUT_0
RESET_IN
RESET_REF
28 27 26 25 24 23 22 21 20 19 18 17 15 14
28 27 26 25 24 23 22 21 20 19 18 17 15 14
SS_IN_CH3
SS_IN_CH2 SS_OUT_CH1 SS_OUT_CH0
SS_IN_CH1
SS_IN_CH0
SCOM
SPWR
SS
Request
IOD Connector
TEST_OUT_1 TEST_OUT_0
RESET_IN RESET_REF SS_IN_CH3 SS_IN_CH2
SS_OUT_CH1 SS_OUT_CH0
SS_IN_CH1 SS_IN_CH0
IOD Connector
TEST_OUT_1 TEST_OUT_0
RESET_IN
RESET_REF SS_IN_CH3 SS_IN_CH2
SS_OUT_CH1 SS_OUT_CH0
SS_IN_CH1 SS_IN_CH0
IOD Connector
TEST_OUT_1 TEST_OUT_0
RESET_IN
RESET_REF SS_IN_CH3 SS_IN_CH2
SS_OUT_CH1 SS_OUT_CH0
SS_IN_CH1 SS_IN_CH0
Reset
28 27 26 25 24 23 22 21 20 19 18 17 15 14
28 27 26 25 24 23 22 21 20 19 18 17 15 14
SCOM
SPWR 24VCOM 24VPWR
24VCOM 24VPWR
24VCOM 24VPWR
28 27 26 25 24 23 22 21 20 19 18 17 15 14
28 27 26 25 24 23 22 21 20 19 18 17 15 14
SCOM SPWR
28 27 26 25 24 23 22 21 20 19 18 17 15 14
28 27 26 25 24 23 22 21 20 19 18 17 15 14
SCOM
SPWR
Light Curtain
or
Safety Mat
OSSD1 OSSD2
24V DC

Safe Stop Wiring Examples

Cascaded configurations can be wired with either the 2090-K6CK-D44M or 2090-K6CK-D44S0 low-profile connector kits. The 2090-K6CK-D44S0 connector is designed specifically for cascading the safe torque-off signals from drive-to-drive.
The examples shown are safe-stop configurations that use a dry-contact safety device.

2090-K6CK-D44M Connector Kit Examples

Figure 13 - Cascading Safe Stop Non-OSSD Device Wiring Example
Figure 14 - Cascading Safe Stop OSSD Device Wiring Example
28 Rockwell Automation Publication 2094-RM002B-EN-P - May 2012
Multi-axis Cascaded Systems Chapter 4
24VCOM 24VPWR
IOD Connector (P5)
TEST_OUT_1 TEST_OUT_0
28 27 24 23 22 21 20 19
SS_IN_CH3
SS_IN_CH2 SS_OUT_CH1 SS_OUT_CH0
SS_IN_CH1
SS_IN_CH0
IOD Connector (P5)
TEST_OUT_1 TEST_OUT_0
SS_IN_CH3
SS_IN_CH2 SS_OUT_CH1 SS_OUT_CH0
SS_IN_CH1
SS_IN_CH0
IOD Connector (P5)
TEST_OUT_1 TEST_OUT_0
SS_IN_CH3
SS_IN_CH2 SS_OUT_CH1 SS_OUT_CH0
SS_IN_CH1
SS_IN_CH0
IOD Connector (P6)
RESET_IN
RESET_REF
SCOM SPWR
26 25 18 17 15 14
IOD Connector (P6)
RESET_IN
RESET_REF
SCOM SPWR
IOD Connector (P6)
RESET_IN
RESET_REF
SCOM SPWR
Reset
28 27 24 23 22 21 20 19
28 27 24 23 22 21 20 19
28 27 24 23 22 21 20 19
28 27 24 23 22 21 20 19
28 27 24 23 22 21 20 19
26 25 18 17 15 14
24VCOM 24VPWR
24VCOM 24VPWR
26 25 18 17 15 14
26 25 18 17 15 14
26 25 18 17 15 14
26 25 18 17 15 14
Input cable from the previous 2094 power rail or other cascading device.
Output cable to the next 2094 power rail or other
cascading device.
Cascadi ng S0 Out (sockets)
Cascading S0 In
(pins)
2090-CS0DSDS-AAxx
Cascading Safe-off Cables
SS
Request
Wiring Legend
= Cable connections = Customer discrete connections
IMPORTANT

2090-K6CK-D44S0 Connector Kit Examples

The 2090-K6CK-D44S0 connector kit and 2090-CS0DSDS-AAxx safe-off cable are designed specifically for cascading the safe torque-off signals from drive-to-drive.
Figure 15 - Cascading Safe Stop Non-OSSD Device Wiring Example
For simplicity, the cables are shown connecting end-to-end with the output cable exiting right. However, all connectors are keyed to exit left as shown in
Figure 17
.
Rockwell Automation Publication 2094-RM002B-EN-P - May 2012 29
Chapter 4 Multi-axis Cascaded Systems
IOD Connector (P5)
TEST_OUT_1 TEST_OUT_0
28 27 24 23 22 21 20 19
SS_IN_CH3
SS_IN_CH2 SS_OUT_CH1 SS_OUT_CH0
SS_IN_CH1
SS_IN_CH0
IOD Connector (P5)
TEST_OUT_1 TEST_OUT_0
SS_IN_CH3
SS_IN_CH2 SS_OUT_CH1 SS_OUT_CH0
SS_IN_CH1
SS_IN_CH0
IOD Connector (P5)
TEST_OUT_1 TEST_OUT_0
SS_IN_CH3
SS_IN_CH2 SS_OUT_CH1 SS_OUT_CH0
SS_IN_CH1
SS_IN_CH0
IOD Connector (P6)
RESET_IN
RESET_REF
SCOM SPWR
IOD Connector (P6)
RESET_IN
RESET_REF
SCOM SPWR
IOD Connector (P6)
RESET_IN
RESET_REF
SCOM SPWR
Reset
28 27 24 23 22 21 20 19
28 27 24 23 22 21 20 19
28 27 24 23 22 21 20 19
28 27 24 23 22 21 20 19
28 27 24 23 22 21 20 19
24VCOM 24VPWR
24VCOM 24VPWR
24VCOM 24VPWR
26 25 18 17 15 14
26 25 18 17 15 14
26 25 18 17 15 14
26 25 18 17 15 14
26 25 18 17 15 14
26 25 18 17 15 14
Input cable from the previous 2094 power rail or other cascading device.
Output cable to the next
2094 power rail or other
cascading device.
Cascading S0 Out (sockets)
Cascading S0 In
(pins)
2090-CS0DSDS-AAxx
Cascading Safe-off Cables
Wiring Legend
= Cable connections = Customer discrete connections
Light Curtain
or
Safety Mat
OSSD1 OSSD2
24V DC
IMPORTANT
Figure 16 - Cascading Safe Stop OSSD Device Wiring Example
For simplicity, the cables are shown connecting end-to-end with the output cable exiting right. However, all connectors are keyed to exit left as shown in
Figure 17
.
30 Rockwell Automation Publication 2094-RM002B-EN-P - May 2012
Multi-axis Cascaded Systems Chapter 4
2090-CS0DSDS-AAxx Cascading Safe Torque-off Cables
Input cable from previous
2094 power rail or
other cascading device.
Output cable to next 2094 power rail or other cascading device.
2094-BCxx-Mxx-M
IAM Power Module
with
2094-xx02x-M0x-S0
Control Module
2094-BMxx-M AM Power Modules (2) with 2094-xx02x-M0x-S0 Control Modules (2)
2090-K6CK-D44S0
Cascading Connector Kits (3)
2090-K6CK-D15M Feedback Connector Kits (3)
I/O Wiring Input Connector Output Connector Safety Wiring
Bottom View
M8 x 25.4 (1.0 in.) Pins, Shielded
M8 x 25.4 (1.0 in.)
Sockets, Shielded
In this example, three safe torque-off drives are shown using the Bulletin 2090 low-profile connector kit and cables. The right-angled cable connectors are keyed to exit left as shown. Cables loop back and cascade to the next drive or other cascading device.
Figure 17 - Kinetix 6200/6500 Cascading Safe Torque-off Cable Example
3
1
4
Table 5 - Safe Torque-off Cable Catalog Numbers
Cable Cat. No. Length Description
2090-CS0DSDS-AA02 0.2 m (7.1 in.) Drive-to-drive connections (single-wide IAM or AM power module) 2090-CS0DSDS-AA03 0.3 m (1.0 ft) Drive-to-drive connections (double-wide IAM or AM power module) 2090-CS0DSDS-AA10 1.0 m (3.2 ft) Connect to next 2094 power rail or other safe torque-off device
Figure 18 - 2090-CS0DSDS-AAxx Cable Pinout
1
4
Table 6 - 2090-CS0DSDS-AAxx Cable Terminations
Cable Termination
Pins Sockets
4 18 Safety 24V common SCOM 1 21 Safe stop output 0 SS_OUT_CH0
3 22 Safe stop output 1 SS_OUT_CH1 4 1 3
2090-K6CK-D44S0 Pin Description Signal
18 Safety 24V common SCOM 23 Safe stop input 2 SS_IN_CH2 24 Safe stop input 3 SS_IN_CH3
3
Rockwell Automation Publication 2094-RM002B-EN-P - May 2012 31
Chapter 4 Multi-axis Cascaded Systems
Notes:
32 Rockwell Automation Publication 2094-RM002B-EN-P - May 2012
Chapter 5
Troubleshooting the Safe Torque-off Drive

Introduction

Nonrecoverable Faults

Fault Recovery

This chapter provides troubleshooting tables for diagnosing fault conditions associated with the safe torque-off safety functions.
Top ic Pag e
Nonrecoverable Faults 33 Faul t Recov ery 33 Input and Output Faults 34 Fault Codes and Descriptions 34 Status Attributes 35
In addition to the recoverable faults described in this chapter, the drive also generates nonrecoverable faults when a problem with the drive hardware is detected. These faults are Safe State faults. If a Safe State fault occurs, all safety control outputs are set to their safe state.
To clear a nonrecoverable fault, cycle power. If the nonrecoverable fault persists, the drive may need to be replaced.
If the fault is no longer present, you can clear the fault condition with a successful SO Reset and a Motion Axis Fault Reset (MAFR) via your RSLogix 5000 application program, except in the case of an Internal Hdwr fault or MP Out fault. An Internal Hdwr fault or MP Out fault is cleared at power down.
Rockwell Automation Publication 2094-RM002B-EN-P - May 2012 33
Chapter 5 Troubleshooting the Safe Torque-off Drive

Input and Output Faults

Fault Codes and Descriptions

An input or output fault indication can be caused by several wiring fault conditions during commissioning or normal operation. If an input fault occurs, check for the following:
One of the channels may have shorted to a 24V DC source.
One of the channels may have shorted to a GND source.
Two input channels have shorted together.
One or both output channels have an overcurrent condition.
An input fault will also occur if only one of the channels in a dual-channel system has changed state after a 1-second discrepancy time interval.
The drive web page can display a fault history queue, which provides a record of the faults detected by the drive. The fault history queue stores the fault codes and timestamps for the last 10 faults that occurred.
Refer to the Kinetix 6200 and Kinetix 6500 Modular Multi-axis Servo Drive User Manual, publication 2094-UM002
, for more information on accessing the
drive web page.
Table 6 - Safe Torque-off Fault Codes
Code Display Text Description
SAFE FLT 01... INTERNAL HDWR nn
SAFE FLT 03... MP OUT nn
SAFE FLT 09... SS IN nn SAFE FLT 10... SS OUT nn
(1) The nn field is a sub code that provides additional information regarding the fault. (2) Refer to Input and Output Faults
(1)
on this page for more information.
(1)
A nonrecoverable microprocessor error has occurred.
(1)
(1)
An MP Output fault occurs if an internal error is detected in the circuit that removes motion producing power from the drive terminals.
I/O Faul ts
An SS_In fault occurs if an error is detected in one of the SS_In dual-channel inputs.
(2)
An SS_Out fault occurs if an error is detected in the SS_Out dual-channel output.
34 Rockwell Automation Publication 2094-RM002B-EN-P - May 2012
Troubleshooting the Safe Torque-off Drive Chapter 5
IMPORTANT

Status Attributes

For diagnostic purposes only, you can view status attributes by accessing the AxisServoDrive.GuardStatus tag (Kinetix 6200 systems) and AxisCIPDrive.GuardStatus tag (Kinetix 6500 systems) in RSLogix 5000 software.
AxisServoDrive.GuardStatus tags must be selected as a Real-time attribute in order to receive updated attribute values. This is not required for AxisCIPDrive.GuardStatus tags.

Guard Status Attributes

These attributes are stored in the AxisServoDrive.GuardStatus tag (Kinetix 6200 systems) and AxisCIPDrive.GuardStatus tag (Kinetix 6500 systems). Each bit corresponds to a different attribute.
Table 7 - Guard Status Descriptions
Bit
0GuardOKStatus
1 RESERVED Reserved.
2
3
4
5 RESERVED Reserved. 6 RESERVED Reserved. 7 RESERVED Reserved.
8
9…22 RESERVED Reserved. 23 GuardResetInputStatus This status bit reflects the state of the Reset_In input. A 1 indicates the Reset_In input is ON; a 0 indicates the Reset_In input is OFF. 24 GuardResetRequiredStatus This bit is set to 1 if an SO Reset is required before Motion Power can be enabled. 25…31 RESERVED Reserved.
Display Text
Axis 1.
GuardGateDrive OutputSatus
GuardStopInput Status
GuardStop RequestStatus
GuardStop OutputStatus
Description
This bit indicates when there are no faults. It is set (1), when all of the Fault Status bits 1…31 are 0 (no faults). The bit is 0 if any Fault Status bit from 1…31 indicates a fault (1).
This bit shows the status of the drive’s Motion Power command to the drive. A 1 indicates Motion Power is enabled; a 0 indicates Motion Power is disabled.
This bit displays the logical value, 1 or 0, evaluated for the dual-channel SS_In input.
This bit is set to 1 when a safe stop is initiated by either a transition of the SS_In input from ON to OFF or by a Stop Category fault. This bit is reset to 0 when a successful SO Reset occurs and when the Operation mode is set to Disabled (0).
This bit is set to 1 if the dual-channel SS_Out output is being commanded to the ON state. This bit is the commanded value, not a readback value.
This bit is set to 0 if the SS_Out output is being commanded to the OFF state.
Rockwell Automation Publication 2094-RM002B-EN-P - May 2012 35
Chapter 5 Troubleshooting the Safe Torque-off Drive
Parameter Name Description Bit Values
Axis 1: Guard Status
Table 8 - Guard Status Bit Values
GuardOKStatus GuardConfigLockedStatus GuardGateDriveOutputSatus GuardStopInputStatus GuardStopRequestStatus GuardStopInProgressStatus GuardStopDecelStatus GuardStopStandstillStatus GuardStopOutputStatus GuardLimitedSpeedInputStatus GuardLimitedSpeedRequestStatus GuardLimitedSpeedMonitorInProgressStatus GuardLimitedSpeedOutputStatus GuardMaxSpeedMonitorInProgressStatus GuardMaxAccelMonitorInProgressStatus GuardDirectionMonitorInProgressStatus GuardDoorControlLockStatus GuardDoorControlOutputStatus GuardDoorMonitorInputStatus GuardDoorMonitorInProgressStatus GuardLockMonitorInputStatus GuardEnablingSwitchInputStatus GuardEnablingSwitchInProgressStatus GuardResetInputStatus GuardResetRequiredStatus GuardStopInputCycleRequiredStatus
0 = Fault; 1 = OK Reserved 0 = Off; 1 = On 0 = Off; 1 = On 0 = Inactive; 1 = Active Reserved Reserved Reserved 0 = Off; 1 = On Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved 0 = Off; 1 = On 0 = Off; 1 = On Reserved

Guard Fault Attributes

Parameter Name Description Bit Values
1 = GuardInternalFault 2 = Reserved 3 = GuardGateDriveFault 4 = Reserved 5 = Reserved 6 = Reserved 7 = Reserved 8 = Reserved 9 = GuardStopInputFault 10 = GuardStopOutputFault 11 = Reserved 12 = Reserved 13 = Reserved
Axis 1: Guard Faults Bit-encoded faults
14 = Reserved 15 = Reserved 16 = Reserved 17 = Reserved 18 = Reserved 19 = Reserved 20 = Reserved 21 = Reserved 22 = Reserved 23 = Reserved 24 = Reserved 25 = Reserved 26 = Reserved 27 = Reserved 28 = Reserved
36 Rockwell Automation Publication 2094-RM002B-EN-P - May 2012
Specifications
Appendix A

Introduction

General Specifications

This appendix provides product specifications for the safe torque-off safety functions.
Top ic Pag e
General Specifications 37 Certifications 38
These specifications apply to the safe torque-off safety functions.
Attribute Value
Standards IEC/EN60204-1, ISO12100, IEC 61508, IEC 61800-5-2 Safety category Cat. 4 and PLe per EN ISO 13849-1;
Power supply
Vol tag e
Current, max Power cons umptio n 3 W SS outputs 24V DC, 20 mA, short-circuit protected Pulse outputs 24V DC, 30 mA, short-circuit protected SS inputs, max 5 mA per input Input pulse rejection, max 700 μs Input ON voltage, min 16.5V Input OFF voltage, max 5V Input OFF current, max 2 mA Safety reaction time, max Reset_In Input, max 5 mA per input Reset time, max Conduc tor size Strip length 5 mm (0.25 in.) Terminal screw torque 0.22…0.25 N•m (1.9…2.2 lb•in)
(2)
(3)
SIL CL3 per IEC 61508 and EN 62061
21.6…28.8V DC (24V nom), 0.9…1.2 x rated voltage PELV or SELV
0.105 A
(1)
12 ms
20 ms
0.25…0.75 mm2 (24…18 AWG)
(1) When multiple drives are cascaded together, the safety reaction time for the last drive is the total of all drives times 12 ms. (2) When multiple drives are cascaded together, the safety reset time for the last drive is the total of all drives times 20 ms. (3) Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Rockwell Automation Publication 2094-RM002B-EN-P - May 2012 37
Appendix A Specifications

Certifications

See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certifications details.
Agency Certification
(2)
c-UL-us CE European Union 2004/108/EC EMC Directive, compliant with:
C-Tick Australian Radiocommunications Act, compliant with:
Functional Safety TÜV Certified for Functional Safety: up to SIL CL3, according to EN 61800-5-2, EN 61508, and
(1) When product is marked, refer to http://www.ab.com for Declarations of Conformity Certificates. (2) Underwriters Laboratories Inc. has not evaluated the safe-o ff, safe torque-off, or safe speed-monitoring options in these products.
Value
(1)
UL Listed, certified for US and Canada.
EN 61800-3; categories C2 and C3
EN 62061; EM Immunity
EN 61800-3; categories C2 and C3
EN 62061; up to Performance Level PLe and Category 4, according to EN ISO 13849-1; when used as described in this Kinetix 6200 and Kinetix 6500 Safe Torque-off Safety Reference Manual, publication 2094-RM002.
38 Rockwell Automation Publication 2094-RM002B-EN-P - May 2012

Index

Numerics
2090-K6CK-D44M 14
2090-K6CK-D44S0
16
A
additional resources 8
12
ADR automatic drive replacement automatic reset
23, 25
12
C
cascaded configurations 27
cascaded connections
7, 9
Cat 4
performance definition
certification 38
7, 9
Cat 4 ISO 13849-1 PLe
7, 9
SIL CL3 7, 9
connector kit
14, 16
wiring
cycle inputs
20
24
10
9
D
discrepancy time 20
documentation
additional resources
drive replacement 12
8
E
emergency shutdown systems 9
EN 61508
EN 61508-5-2 EN 61800-5-2
EN 62061 11
European Norm
11
SIL CL3 certification
38
SIL CL3 certification
7
definition
9
9
G
guard faults 36
guard status
36
I
input faults 34
19
inputs ISO 13849-1
9, 10, 11, 38
M
motion-allowed plug 17
multi-axis
configurations wiring
27
24
O
output faults 34
23
outputs
P
PFD
11
data definition
7, 11
PFH
11
data definition 7, 11
pinouts
18
11
PL
7
definition
PLe
7, 9, 38
power supply pulse test outputs
14
19
R
reaction time 12
recover from fault reset behavior Reset input wiring
Reset_In input
risk assessment
33
21
23
13
F
failure
33
34
12
34
Safe State
safety
shutdown, EDS
contact information
fault codes
34
input nonrecoverable output
34
33
recovery Stop Category Faults
fault history queue fault recovery
Rockwell Automation Publication 2094-RM002B-EN-P - May 2012 39
33
S
12
definition
certification, TÜV Rheinland information power supply reaction time
13
14
12
9
9, 38
Index
SIL CL3 7, 9, 38
certification, user responsibilities
single-channel operation
25
SO Reset specifications
37
general
SS_Out output status attributes stop category
definition
23
35
10
T
terminal screws
connections strip length 18 torque
timing diagrams
discrepancy time reset behavior 21
18
18
20
W
wiring
connector kit
2090-K6CK-D44M 2090-K6CK-D44S0
motion-allowed plug multi-axis connections 24 safety input examples
wiring example
Safe Stop mode
26, 28
10
19
14
16
17
22
40 Rockwell Automation Publication 2094-RM002B-EN-P - May 2012
Rockwell Automation Support
Rockwell Automation provides technical information on the Web to assist you in using its products. At http://www.rockwellautomation.com/support code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools. You can also visit our Knowledgebase at http://www.rockwellautomation.com/knowledgebase information, support chat and forums, software updates, and to sign up for product notification updates.
, you can find technical manuals, technical and application notes, sample
for FAQs, technical
For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer
SM
Te c h C o n n e c t representative, or visit http://www.rockwellautomation.com/support/
support programs. For more information, contact your local distributor or Rockwell Automation
.
Installation Assistance
If you experience a problem within the first 24 hours of installation, review the information that is contained in this manual. You can contact Customer Support for initial help in getting your product up and running.
United States or Canada 1.440.646.3434 Outside United States or Canada Use the Wo rldw ide Locat or at http://www.rockwellautomation.com/support/americas/phone_en.html, or contact your local Rockwell
Automation representative.
New Product Satisfaction Return
Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.
United States Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your
Outside United States Please contact your local Rockwell Automation representative for the return procedure.
distributor to complete the return process.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002
Publication 2094-RM002B-EN-P - May 2012
Supersedes Publication 2094-RM002A-EN-P - January 2010 Copyright © 2012 Rockwell Auto mation, Inc. All rights reserved. Pr inted in the U.S.A.
, available at http://www.rockwellautomation.com/literature/.
Loading...