Rockwell Automation 193-DNENCATR User Manual

User Manual
Bulletin 193 EtherNet/IP Communications Auxiliary
Catalog Number
193-DNENCAT, 193-DNENCATR
Important User Information
IMPORTANT
Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/ important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
available from
) describes some
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.
Identifies information that is critical for successful application and understanding of the product.
Allen-Bradley, Rockwell Software, Rockwell Automation, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Chapter 1
Installation & Wiring
Configure the EtherNet/IP Communications Auxiliary
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Network Design. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Chapter 2
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Determining Network Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Setting the IP Network Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
EtherNet/IP Node Address Selection Switches. . . . . . . . . . . . . . . . . . 16
Assign Network Parameters via the BOOTP/DHCP Utility. . . . . . . . . 17
Assign Network Parameters Via a Web Browser & MAC Scanner
Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Other Factors to Consider When Assigning Network Parameters. 22
Duplicate IP Address Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Behavior of Modules With Duplicate IP Addresses . . . . . . . . . . . . . . 23
DNS Addressing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Electronic Data Sheet (EDS) File Installation . . . . . . . . . . . . . . . . . . . . . . . 23
Download the EDS File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Register the EDS File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Configure the DeviceNet Network
Add Devices to the DeviceNet Network
Chapter 3
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Chapter 4
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
DeviceNet Node Addressing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Node Address Basics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Set the Node Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Using the Hardware Mechanism. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Using the DeviceNet Node Commissioning Tool . . . . . . . . . . . . . . . 37
Add DeviceNet Modules to the Scan List. . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Simple . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
User-Defined. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
3 Rockwell Automation Publication 193-UM014B-EN-P - December 2011
Chapter 5
View & Configure Parameters
Automatic Device Recovery or Replace
Automation Controller Communications
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
View & Edit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Chapter 6
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Setting ADR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Chapter 7
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Ethernet Messaging. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
I/O Messaging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
ControlLogix Configuration with Add-On Profiles . . . . . . . . . . . . . 51
EtherNet/IP Network Configuration with Add-On Profiles . . . . . 53
Accessing Module Data with Add-On Profiles . . . . . . . . . . . . . . . . . . 56
ControlLogix Generic Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . 57
EtherNet/IP Generic Module Configuration . . . . . . . . . . . . . . . . . . . 58
Accessing Generic Module Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Logic Explicit Messaging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
E-mail/Text
Device Parameters
Chapter 8
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
E-mail Notifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Events . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
E-mail Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
E-mail Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Configure Device Identity. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Text Notifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Chapter 9
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Parameter Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Parameter Listing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
4 Rockwell Automation Publication 193-UM014B-EN-P - July 2011
Chapter 10
Troubleshooting
Specifications
EtherNet/IP & DeviceNet Information
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
EtherNet/IP Modules of Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Power-Up Reset Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Run Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Recoverable Error Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Unrecoverable Error Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Troubleshooting Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Appendix A
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Appendix B
Electronic Data Sheet (EDS) Files . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Common Industrial Protocol (CIP) Objects. . . . . . . . . . . . . . . . . . . . . . . . 89
Identity Object — CLASS CODE 0x01. . . . . . . . . . . . . . . . . . . . . . . . 89
Message Router Object — CLASS CODE 0x02. . . . . . . . . . . . . . . . . 90
DeviceNet Object — CLASS CODE 0x03 . . . . . . . . . . . . . . . . . . . . . 91
Assembly Object — CLASS CODE 0x04 . . . . . . . . . . . . . . . . . . . . . . 91
Connection Manager Object — CLASS CODE 0x06 . . . . . . . . . . . 95
Parameter Object — CLASS CODE 0x0F. . . . . . . . . . . . . . . . . . . . . . 96
Device Level Ring (DLR) Object — CLASS CODE 0x47 . . . . . . . 97
QoS Object — CLASS CODE 0x48 . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Non-Volatile Storage Object — CLASS CODE 0xA1 . . . . . . . . . . . 98
Port Object — CLASS CODE 0x0F4 . . . . . . . . . . . . . . . . . . . . . . . . . . 99
TCP/IP Interface Object — CLASS CODE 0xF5 . . . . . . . . . . . . . 100
Ethernet Link Object — CLASS CODE 0xF6 . . . . . . . . . . . . . . . . . 101
Rockwell Automation Publication 193-UM014B-EN-P - July 2011 5
6 Rockwell Automation Publication 193-UM014B-EN-P - July 2011

Installation & Wiring

Chapter
1

Introduction

Overview

The purpose of this chapter is to provide the necessary instructions to successfully install the Bulletin 193 Ethernet™/IP Communications Auxiliary and properly connect it to an EtherNet/IP and DeviceNet™ network.
The Bulletin 193 EtherNet/IP Communications Auxiliary is an EtherNet/IP to DeviceNet linking device. It provides a means for devices that primarily communicate on a DeviceNet network (e.g., a Bulletin 193 or 592 E3 Plus Overload Relay or a Bulletin 825-P Electronic Overload Relay) to communicate to EtherNet/IP-based scanners. The EtherNet/IP Communications Auxiliary allows up to six (6) DeviceNet-based devices to be scanned via Implicit Messaging and can bridge explicit messaging for all nodes on a DeviceNet network. The EtherNet/IP Communications Auxiliary uses an internal web server to configure the module, the DeviceNet network, and DeviceNet-based devices that fully support the Parameter Object.
SHOCK HAZARD: To prevent electrical shock, disconnect the EtherNet/ IP Communications Auxiliary from its power source before installing or servicing. Install in suitable enclosure. Keep free from contaminants.
ATTENTION: The EtherNet/IP Communications Auxiliary contains ESD (electrostatic discharge) sensitive parts and assemblies. Static control precautions are required when installing, testing, servicing, or repairing the EtherNet/IP Commuications Auxiliary. Component damage may result if ESD control procedures are not followed. If you are not familiar with static control procedures, refer to Rockwell Automation publication 8000-
4.5.2, “Guarding Against Electrostatic Damage”, or any other applicable ESD protection handbook.
ATTENTION: The purpose of this document is to serve as a guide for proper installation. The National Electrical Code (NEC) and any other governing regional or local code will take precedence. Rockwell Automation cannot assume responsibility for the compliance or proper installation of the EtherNet/IP Communications Auxiliary or associated equipment. A hazard of personal injury and/or equipment damage exists if codes are ignored during installation.
Rockwell Automation Publication 193-UM014B-EN-P December 2011 7
Chapter 1
ATT ENTI ON: An incorrectly applied or installed EtherNet/IP
Communications Auxiliary can result in damage to the components or reduction in product life. Wiring or application errors (e.g., supplying incorrect or inadequate supply voltage or operating/storing in excessive ambient temperatures) may result in malfunction of the product.
ATT ENTI ON: Only personnel familiar with the EtherNet/IP Communications Auxiliary and associated machinery should plan to install, set up, and maintain the system. Failure to comply may result in personal injury and/or equipment damage.
ATT ENTI ON: This is a Class A product. In a domestic environment, this product may cause radio interference in which case the user may be required to take adequate measures.
ATT ENTI ON: To remain compliant with UL/CSA Certifications, the DeviceNet power supply must meet NEC Class 2 Requirements.
8 Rockwell Automation Publication 193-UM014B-EN-P December 2011
Chapter 1

Features

Figure 1 - Features
Front View
Status
LEDs
Activity
LEDs
DeviceNet Network
DeviceNet Connector
Module
Ethernet/IP
Network
Front Port Link
Rear Port Link
Status LED
Side View
DIN Rail Mounting
Top View
Ethernet Connectors RJ-45
Rear View
Panel Mounting

Installation

Earth Ground Connector
The EtherNet/IP Communications Auxiliary may be DIN Rail or panel mounted. To avoid overheating, the unit must be mounted vertically and requires 37.4 mm (1-1/2 in.) of clearance at the top and bottom to allow proper air flow. The temperature ratings for the unit will be derated if not mounted in this manner.
Rockwell Automation Publication 193-UM014B-EN-P December 2011 9
Chapter 1
Front View
37.44 mm (1-1/2 in.)
37.44 mm (1-1/2 in.)
Figure 2 - Installation

Wiring

The EtherNet/IP Communications Auxiliary can accept all forms of DeviceNet cable. However, DeviceNet shielded cable is recommended. The EtherNet/IP Communications Auxiliary complies with the Open Device Vendors Association (ODVA) DeviceNet compliance testing when the distance between end nodes is 100 m or less with 60 or fewer network drops.
Table 1 - Wire & Torque Specifications
Wire Torque
1X 2X
1X 2X
1X 2X
24…12 AWG 24…16 AWG
5 lb.•in.
0.2…2.5 mm
0.25…1 mm
0.56 N•m
0.2…2.5 mm
0.2…1 mm
0.56 N•m
2
2
2
2
10 Rockwell Automation Publication 193-UM014B-EN-P December 2011
Figure 3 - Wiring Diagram
5.85 (0.23)
105.0 (4.13)
100.5
(3.95)
98.0
(3.86)
110.0 (4.33)
Ø 4.50 (0.16)
87.0
(3.43)
31.3
(1.23)
Dimensions are shown in millimeters (inches).
DNET (Black) 24V -
CAN L (Blue)
Shield
CAN H (White)
DNET (Red) 24V +
Chapter 1
Earth Ground

Dimensions

ATTENTION: Use a shielded DeviceNet cable to comply with CISPR 22
and CISPR 24.
Figure 4 - Dimension Diagram
Rockwell Automation Publication 193-UM014B-EN-P December 2011 11
Chapter 1

Network Design

The EtherNet/IP Communications Auxiliary is available as a single Ethernet port (Cat. No. 193-DNENCAT) and dual Ethernet port (Cat. No. 193-DNENCATR) module that has RJ-45 ports to connect to Ethernet cable CAT5 type or better . Rockwell Automation offers a wide variety of Allen-Bradley Ethernet patch cables with its Bulletin 1585 line of Ethernet cables (http://ab.rockwellautomation.com/Connection-Devices/RJ45-Network-
Media).
Both the 193-DNENCAT and 193-DNENCATR devices support a Star Ethernet topology in which all Ethernet nodes wire back to a central Ethernet switch, hub, or router as shown in Figure 5 on page 12
Figure 5 - Star Ethernet Topology
.
Rockwell Automation also offers a line of managed and unmanaged Allen-Bradley Ethernet Switches with its Stratix™ family of Ethernet switches. Refer to
Ethernet-IP-Infrastructure
http://ab.rockwellautomation.com/Networks-and-Communications/
for more information.
The Cat. No. 193-DNENCATR Module also supports a Ring Ethernet topology in which all Ethernet nodes are wired in series with one another until a complete network ring is made as shown in Figure 6 on page 13
12 Rockwell Automation Publication 193-UM014B-EN-P December 2011
.
Figure 6 - Ring Ethernet Topology
Chapter 1
The Cat. No. 193-DNENCATR Module supports Rockwell Automation’s Device Level Ring (DLR) topology as a slave device in which the EtherNet/IP network will still continue to communicate in the event that one of the network chains is disrupted.
Rockwell Automation Publication 193-UM014B-EN-P December 2011 13
Chapter 1
14 Rockwell Automation Publication 193-UM014B-EN-P December 2011
Chapter
2

Configure the EtherNet/IP Communications Auxiliary

Introduction

Determining Network Parameters

This chapter describes how to configure an EtherNet/IP Communications Auxiliary to operate on an EtherNet/IP network.
When you first install an EtherNet/IP Communications Auxiliary, the module is Dynamic Host Configuration Protocol (DHCP) enabled.
To operate an EtherNet/IP network, you must define these parameters.
Table 2 - EtherNet/IP Network Parameters
Network Parameter Description
IP Address The IP address uniquely identifies the module. The IP address
is in the form xxx.xxx.xxx.xxx where each xxx is a number from
0...255. Do not use the following IP addresses, as these are reserved values:
0.0.0.1...0.255.255.255
127.0.0.0...127.255.255.255
224.255.255.255...255.255.255.255
Subnet Mask Subnet addressing is an extension of the IP address scheme
that allows a site to use a single network ID for multiple physical networks. Routing outside of the site continues by dividing the IP address into a net ID and a host ID via the class. Inside a site, the subnet mask is used to redivide the IP address into a custom network ID portion and host ID portion. NOTE: If you change the subnet mask of an already­configured module, you must cycle power to the module for the change to take effect.
Gateway A gateway connects individual physical networks into a
system of networks. When a node needs to communicate with a node on another network, a gateway transfers the data between the two networks.
If DNS addressing is used or if the module is referenced via a host name in an MSG instruction, the following parameters must be defined.
NOTE: Consult with your Ethernet network administrator to determine if these
parameters need to be specified.
Rockwell Automation Publication 193-UM014B-EN-P December 2011 15
Chapter 2
Table 3 - EtherNet/IP Network Parameters for DNS Addressing
Network Parameter Description
Host Name A host name is part of a text address that identifies the
Domain Name A domain name is part of a text address that identifies the
Primary DNS Server Address This identifies any DNS servers used in the network. You must Secondary DNS Server Address
module. The full text address of a module is: host_name.domain_name.
domain in which the module resides. The full text address of a module is: host_name.domain_name. The domain name has a 48-character limit.
have a DNS server configured if you specify an SMTP server with a name. The DNS server converts the domain name or host name to an IP address that can be used by the network.
For more information on DNS addressing, refer to page 23.

Setting the IP Network Address

An EtherNet/IP Communications Auxiliary ships with DHCP enabled. You can set the network Internet Protocol (IP) address by using:
the EtherNet/IP node address selection switches,
a Bootstrap Protocol (BOOTP)/Dynamic Host Configuration Protocol
(DHCP) server (e.g., the Rockwell Automation BOOTP-DHCP Server Utility, which is included with Rockwell Software’s RSLinx™ Classic software), OR
a web browser and MAC scanner software.
EtherNet/IP Node Address Selection Switches
The EtherNet/IP Communications Auxiliary comes with three node address selection switches that allow the user to select the last octet for the IP address
192.168.1.xxx.
16 Rockwell Automation Publication 193-UM014B-EN-P December 2011
Figure 7 - Last Octet Selection
EXAMPLE
IMPORTANT
When the top dial is set to 1, the middle dial is set to 2, and the bottom dial is set to 3, the resulting IP address is: 192.168.1.123.
Chapter 2
x 100 Digit
x 10 Digit
x 1 Digit

Assign Network Parameters via the BOOTP/ DHCP Utility

When the node address selection switches are set to a value greater than 255, the IP address is set to DHCP Enabled or programmed for a static IP address.
By default, the EtherNet/IP Communications Auxiliary is DHCP Enabled. The BOOTP/DHCP utility is a standalone program that is located in the BOOTP­DHCP Server folder accessed from the Start menu.
Before starting the BOOTP/DHCP utility: Make sure you have the hardware MAC ID of the module, which is printed on the front of the EtherNet/IP Communications Auxiliary. The MAC ID has a format similar to: 00-0b-db-14-55-35.
This utility recognizes DHCP-enabled devices and provides an interface to configure a static IP address for each device.
To assign network parameters via the BOOTP/DHCP utility, perform this procedure:
1. Execute the BOOTP/DHCP software.
2. Choose Tool >Network Settings.
Rockwell Automation Publication 193-UM014B-EN-P December 2011 17
Chapter 2
3. If appropriate for the network, type the subnet mask, gateway address, primary/secondary server addresses, and domain name in their respective fields.
4. Click OK.
The Request History panel displays the hardware addresses of modules issuing BOOTP or DHCP requests.
5. Double-click the MAC address of the module to be configured.
NOTE: The MAC address is printed on the front of the EtherNet/IP Communications
Auxiliary. The format of the hardware address resembles: 00-0b-db-14-55-35
18 Rockwell Automation Publication 193-UM014B-EN-P December 2011
The New Entry window appears with the module’s Ethernet Address (MAC).
6. Type the IP address, host name, and a module description.
7. Click OK.
Chapter 2

Assign Network Parameters Via a Web Browser & MAC Scanner Software

8. Cycle power to the module by removing and reapplying the DeviceNet connector.
9. To permanently assign this configuration to the module: Select the module in the Relation List panel and click Disable BOOTP/DHCP.
When module power is cycled, it uses the assigned configuration and does not issue a DHCP request.
If you do not click Disable BOOTP/DHCP, on a power cycle, the module clears the current IP configuration and will again begin sending DHCP requests.
In the event that a user does not have access to a DHCP software utility, a user can assign network parameters via a web browser (e.g., Microsoft® Internet Explorer) and Media Access Control (MAC) scanner software (e.g., MAC Scanner from Colasoft® - http://www.colasoft.com/ configure the module using this method.
1. Locate and identify the MAC ID printed on the label of the EtherNet/IP Communications Auxiliary. This address has a format that is similar to: 00-0b-db-14-55-35
). Follow these steps to
2. Connect the EtherNet/IP Communications Auxiliary to the same wide area network (WAN) as your personal computer.
3. Initiate the MAC scanner software.
Rockwell Automation Publication 193-UM014B-EN-P December 2011 19
Chapter 2
4. Select the appropriate subnet to scan for available MAC addresses.
5. Scan the Subnet for all available MAC addresses.
6. Identify the IP address assigned to the MAC ID of the EtherNet/IP
Communications Auxiliary. The IP address will have a format that is similar to 192.168.0.100.
7. Open a web browser and type the IP address on the address line to view the internal web server of the EtherNet/IP Communications Auxiliary.
8. Select Administration Settings>Network Configuration to change the IP address of the EtherNet/IP Communications Auxiliary to a static IP address.
20 Rockwell Automation Publication 193-UM014B-EN-P December 2011
Chapter 2
9. The module will prompt the user for a User Name and Password. Type “Administrator” as the user name, leave the password field blank, then click OK.
10. Assign the appropriate network settings per the recommendation of the network administrator for the network that this module will be communicating on and click Apply.
11. Remove and reapply the DeviceNet connector to allow the communications changes to take affect.
Rockwell Automation Publication 193-UM014B-EN-P December 2011 21
Chapter 2
Other Factors to Consider When Assigning Network Parameters
There are other factors to consider when assigning networks parameters, which include the:
network isolation from or integration into the plant/enterprise network.
network size.
For large networks, even isolated networks, it might be more convenient and safer to use a BOOTP/DHCP server rather than RSLinx software. The BOOTP/DHCP server also limits the possibility of assigning duplicate IP addresses.
company policies and procedures associated with plant floor network installation and maintenance.
level of involvement by information technology personnel in plant floor network installation and maintenance.
type of training offered to control engineers and maintenance personnel.
If the Rockwell Automation BOOTP or DHCP server is used in an uplinked subnet where an enterprise DHCP server exists, a module may get an address from the enterprise server before the Rockwell Automation utility even sees the module. In this case, disconnect the uplink to set the address and configure the module to retain its static address before reconnecting to the uplink. This is not a problem if you have node names configured in the module and leave DHCP enabled.
ATT ENTI ON: The EtherNet/IP Communications Auxiliary must be assigned a fixed network address. The IP address of this module must not be dynamically provided. Failure to observe this precaution may result in unintended machine motion or loss of process control.

Duplicate IP Address Detection

When you change the IP address or connect the module to an EtherNet/IP network, the module checks to make sure that the IP address assigned to this module does not match the address of any other network device. If the module determines that another device on the network with a matching IP address, the EtherNet/IP port of the module goes into conflict mode where the Network Status LED indicator is solid red.
To resolve this conflict, use the instructions below to change the IP address of the module. Then, cycle power to the module or reset the modules by disconnecting and then reconnecting the Ethernet cable.
Two modules could possibly detect a conflict simultaneously. If this occurs, perform this procedure.
1. Remove the module with the incorrect IP address and correct its conflict.
2. Cycle power or disconnect the Ethernet cable from the second module and
reconnect it.
22 Rockwell Automation Publication 193-UM014B-EN-P December 2011
Chapter 2
Behavior of Modules With Duplicate IP Addresses
Devices in conflict over an IP address behave differently depending on whether connections have been established to either of the modules and whether both modules support duplicate IP address detection.
Table 4 - Device Conflict over Duplicate IP Addresses
If then
both modules support duplicate IP address detection,
both modules support duplicate IP address detection and are started at roughly the same time,
one module supports duplicate IP address detection and a second module does not,
the first started module uses and retains its IP address. The other module will detect a conflict, give up the IP
address and enter conflict mode.
one of the modules surrenders the IP address and enters conflict mode.
the second module generally keeps its IP address, regardless of which module first obtains the IP address.
The module that supports duplicate IP address detection will detect the conflict and give up the IP address.

DNS Addressing

To further qualify a module’s address, use DNS addressing to specify a host name for a module, which also includes specifying a domain name and DNS servers. DNS addressing makes it possible to set up similar network structures and IP address sequences under different domains.
DNS addressing is only necessary if you refer to the module by host name, such as in path descriptions in MSG instructions.
To use DNS addressing, perform this procedure.

Electronic Data Sheet (EDS) File Installation

Before the EtherNet/IP Communications Auxiliary is configured to communicate on an EtherNet/IP network, it must be registered to the software that configures the network (e.g., Rockwell Automation RSLinx Classic and RSNetWorx for EtherNet/IP software). A user registers the module by installing an EDS file. The EDS file for the EtherNet/IP Communications Auxiliary can be obtained from one of two locations:
1. Assign a host name to the module.
NOTE: Contact the network administrator ro have a host name assigned. Valid host
names should be IEC-1131-3 compliant.
2. Configure the module's parameters.
3. In addition to the IP address, subnet mask, and gateway address, configure
a host name for the module, domain name, and primary/secondary DNS server addresses.
Rockwell Automation Publication 193-UM014B-EN-P December 2011 23
Chapter 2
embedded in the module OR
the Allen-Bradley EDS file download website.
Download the EDS File
Embedded in the Module
The EDS file for the EtherNet/IP Communications Auxiliary is embedded within the module. After the IP address for the module has been configured, connect the module to same Ethernet network as a personal computer. Using a web browser on the personal computer, a user can download the EDS file using a web browser by following these steps:
1. Type the IP address of the EtherNet/IP Communications Auxiliary on the address line of the web browser.
2. Select EDS File link
3. Click Save to save the EDS file to the personal computer.
24 Rockwell Automation Publication 193-UM014B-EN-P December 2011
Chapter 2
From the EDS File Download Site
The EDS file for the EtherNet/IP Communications Auxiliary can also be downloaded from the Allen-Bradley EDS File download site. Using a web browser on the personal computer that is connected to the internet, a user can download the EDS file by following these steps:
1. Ty p e http://www.ab.com/networks/eds browser.
2. Select EtherNet/IP as the network type, then click Search.
3. Locate the EDS file for the EtherNet/IP Communications Auxiliary and
download it to the personal computer.
on the address line of the web
Register the EDS File
After the EDS file has been downloaded, a user will need to register the EDS file with the software that configures the EtherNet/IP network. The following example lists the steps needed to register an EDS file with Rockwell Automation’s RSLinx Classic software.
Rockwell Automation Publication 193-UM014B-EN-P December 2011 25
Chapter 2
1. Start the EDS Hardware Installation Tool located at Start>Programs> Rockwell Software>RSLinx Tools.
2. Click Add to register a new device.
3. Click the “Register a single file” radio button, then browse to the location
where the EDS file is located. Click Next.
26 Rockwell Automation Publication 193-UM014B-EN-P December 2011
4. Click Next to accept the installation test results.
Chapter 2
Rockwell Automation Publication 193-UM014B-EN-P December 2011 27
Chapter 2
5. Click Next to accept the graphic image.
6. Click Next to register the device.
28 Rockwell Automation Publication 193-UM014B-EN-P December 2011
7. Click Finish to successfully register the module.
Chapter 2
Rockwell Automation Publication 193-UM014B-EN-P December 2011 29
Chapter 2
30 Rockwell Automation Publication 193-UM014B-EN-P December 2011

Configure the DeviceNet Network

Chapter
3

Introduction

Configuration

The purpose of this chapter is to assist in configuring the DeviceNet Network with the EtherNet/IP Communications Auxiliary. A DeviceNet network can be configured using the internal web interface from the EtherNet/IP Communications Auxiliary.
1. From the web page, navigate to Scan List>Configuration>Advanced.
2. If desired, change the baud rate using the DeviceNet Baud Rate pull-down
menu. The default value of 125K for the DeviceNet network.
NOTE: Autobaud is not supported with this product.
Rockwell Automation Publication 193-UM014B-EN-P December 2011 31
Chapter 3
3. Type the size of the Scan List I/O Entry in the field.
The entry size determines the number of input and output bytes that the EtherNet/IP Communications Auxiliary will scan from each of the scanned devices. The maximum Scan List I/O Entry Size supported is 50 bytes with the default value being 8 bytes.
NOTE: Auto Device Replacement (ADR) is discussed in Chapter 6, Automatic Device
Recovery or Replace.
4. If necessary, adjust DNet IO Request Packet Interval (RPI) and DNet IO Inhibit.
DNet IO RPI determines the time it takes for data to be requested; DNet IO Inhibit is the time used on DeviceNet Change of State (COS) I/O. Both of these parameters are measured in milliseconds.
NOTE: Electronic keying is implemented on all scan list entries. Electronic keys are
captured when a scan list is configured form the EtherNet/IP Communications Auxiliary webpage. The proper setting of the electronic keying becomes more important with ADR functions and replacing units in the network.
5. Navigate to Scan List>Configuration>Scan List to change the DeviceNet node address of the EtherNet/IP Communcations Auxiliary.
32 Rockwell Automation Publication 193-UM014B-EN-P December 2011
Chapter 3
6. Change the DeviceNet network address to the appropriate node address, then click Save.
NOTE: Typically, DeviceNet scanners have the node address of 0.
7. Click OK to finish changing the scanner DeviceNet network address.
Rockwell Automation Publication 193-UM014B-EN-P December 2011 33
Chapter 3
34 Rockwell Automation Publication 193-UM014B-EN-P December 2011
Chapter

Add Devices to the DeviceNet Network

4

Introduction

DeviceNet Node Addressing

In this chapter, you will be able to assign an address to each DeviceNet module and configure the DeviceNet scanner to scan up to six modules.
Each module being added to the DeviceNet network must have a unique network mode address. A unique network node address can be created by using hardware devices (e.g., DIP and Selector Switches) or by the Node Commissioning tool from the internal web interface of the EtherNet/IP Communications Auxiliary.
The following chart shows the recommended node addresses.
Table 5 - Recommended Node Addresses
Assign this Device:
Scanner 0 For multiple scanners, assign the lowest addresses in
Any Device on the Network (except the scanner)
Computer Interface to the Network
New DeviceNet Module
This Node Address: Notes:
sequence (0, 1...).
1...61 Give the lower addresses to devices with 15 bytes or
more of input or output data.
Gaps between addresses are acceptable and have no
effect on system performance. If the final layout of the system is not certain at this time, leave gaps between addresses to allow flexibility as the system is developed.
62 If a computer is connected directly to the DeviceNet
network, use address 62 for the computer. The reason for this is that many computer interface devices use 63 as the default address.
The 1784-U2DN device can connect a computer directly
to a DeviceNet network.
63 To avoid conflict, always leave address 63 open. This is
due to the following: – most DeviceNet devices have a factory preset
address of 63.
– leaving address 63 open allows for configuration of a
new device.
– the auto-address recovery feature requires address
63 to be open.
Some devices do not have switches or push buttons to
set the address. Therefore, the device must first be connected to the network then software (e.g., RSNetworx for DeviceNet) must be used to change the address.
If another device is already using address 63, an address
conflict will occur and communication will not occur with the newly connected device.
Rockwell Automation Publication 193-UM014B-EN-P December 2011 35
Chapter 4
IMPORTANT
IMPORTANT
Node Address Basics
Verify the node address assigned to the new device.
Prevent duplicate node address assignments.
When connecting new DeviceNet modules with the Node
Commissioning tool from the EtherNet/IP Communications Auxiliary web interface, place one new DeviceNet module on the network at a time. Refer to “New DeviceNet Module” in Tab le 5 on pag e 35
– If DIP or selector switches on hardware will be used, set the network
node address for the device before connecting it to the network.
Leave node address 63 open.
For more information about setting the node address for DeviceNet devices, refer to the Rockwell Automation Literature Library at:
www.rockwellautomation.com/literature
.

Set the Node Address

Using the Hardware Mechanism
Many DeviceNet devices feature a hardware mechanism to set the network node address (e.g., a rotary switch or a push wheel switch). Use the following procedure to set the node address.
Ensure each device’s node address set by the hardware mechanism matches the node address used in the DeviceNet network. Note that if the network node address is set higher than 63, the Ethernet /IP Communications Auxiliary Node Commissioning tool can be used instead of the hardware mechanism.
In order for the node address change to take effect, cycle the module’s power.
1. Usi ng Tab le 5 o n pa ge 3 5 new device.
as a guide, select a node address to apply to the
36 Rockwell Automation Publication 193-UM014B-EN-P December 2011
Chapter 4
2. Change the node address using the appropriate mechanism for the new device.
Mechanism Procedure
Rotary Switch Turn the rotary switch dials to the desired node address value.
2
0
PGM
MSD
Push Wheel Switch
2
4
0
8
6
LSD
Usually, a small, flathead screwdriver is needed to turn the dials.
4
Once the device is powered up, the rotary switch settings are recognized. If the set node address value needs to be changed,
6
power down the device, turn the dials to the desired setting, then power up the device again.
Turn the push wheel to the desired node address value.
Using the DeviceNet Node Commissioning Tool
A device’s network node address can be set using the Node Commissioning Tool on the EtherNet/IP Communications Auxiliary web page. This tool uses the Network Who to view the DeviceNet modules on the network.
Refer to the following guidelines when using the Network Commissioning tool.
Only use this tool with an online DeviceNet network.
Only use this tool when adding new devices to the network if :the new device does not feature a hardware mechanism to set the node
address or
– the new device’s node address is set higher than 63.
NOTE: If the new device features a hardware mechanism and the node address
is set at 63 or lower, the Network Commissioning tool does not change the device’s node address.
Each time a new device is added to the DeviceNet network, the procedures beginning on page 38
To avoid conflict with duplicate node addresses, due largely in part to modules having a factory node setting of 63, configure a module to the online DeviceNet network one a time.
Record the node address for each device that is set by the Node Commissioning Tool.
must be performed.
Complete the following steps to set a device’s node address using the Node Commissioning Tool on the EtherNet/IP Communications Auxiliary web page.
Rockwell Automation Publication 193-UM014B-EN-P December 2011 37
Chapter 4
1. From the EtherNet/IP Communications Auxiliary web page, navigate to Scan List>Configuration>Node Commissioning.
2. Select the device where node address needs to be assigned. Once selected, the Current Settings aand New Settings areas are populated.
3. Double-click the “Node address” field’s value. The value will be highlighted in blue.
38 Rockwell Automation Publication 193-UM014B-EN-P December 2011
Chapter 4
4. Using the keypad on the PC keyboard, change the network node address to the desired value. Ensure the desired value is not duplicating any other device’s node address, then click the Apply button.
5. The following window will appear confirming a successful node address value change. Click OK.
6. Verify the node address was changed to the desired value in the “New settings” section of the page. Note that the “Current settings” area will still display the old node address unitl the device is selected again from the Network Who list.
7. Repeat steps 1 through 6 until all new or additional devices are added to the DeviceNetwork.
Rockwell Automation Publication 193-UM014B-EN-P December 2011 39
Chapter 4

Add DeviceNet Modules to the Scan List

After each DeviceNet device has been assigned a unique node address, up to six DeviceNet devices can be added to the EtherNnet/IP Communications Auxiliary DeviceNet scan list. The EtherNet/IP Communications Auxiliary provide two methods to configure the scan list, Simple and User-Defined.
Simple
1. From the EtherNet/IP Communications Auxiliary web page, navigate to Scan List>Configuration>Scan List. The EtherNet/IP Communications Auxiliary will read the available DeviceNet modules on the DeviceNet network.
2. Click Config. The lowest six DeviceNet node addresses will populate into the Scan List field on the right.
40 Rockwell Automation Publication 193-UM014B-EN-P December 2011
Chapter 4
3. Click OK to complete the configuration.
The DeviceNet scanner on the EtherNet/IP Communications Auxiliary will begin scanning the DeviceNet devices.
User-Defined
If there are more than six DeviceNet devices on the network, the user can select up to six DeviceNet devices to scan. Follow the steps below to select specific DeviceNet devices for the scan list.
1. From the EtherNet/IP Communications Auxiliary web page, navigate to Scan List>Configuration>Scan List. The EtherNet/IP Communications Auxiliary will read the available DeviceNet modules on the DeviceNet network.
2. Select the DeviceNet device in the Network Who screen to be added to the Scan List. The >> button becomes highlighted.
Rockwell Automation Publication 193-UM014B-EN-P December 2011 41
Chapter 4
3. Click >> to move the selected device into the Scan List.
4. Repeat steps 2 and 3 to add five additional DeviceNet devices.
5. Click Save at the bottom right of the screen.
6. Click OK to complete the scan list configuration.
42 Rockwell Automation Publication 193-UM014B-EN-P December 2011

View & Configure Parameters

Chapter
5

Introduction

View & Edit

In this chapter, you will be able to view and configure parameters for a DeviceNet device that supports the full implementation of the Parameter Object.
The EtherNet/IP Commuications Auxiliary is able to view and configure parameters for a DeviceNet device that supports the full implementation of the Parameter Object. Users can use the web interface to view and edit parameters for a DeviceNet Module in the scan list.
Follow the steps below to view and edit parameters using the web interface of the EtherNet/IP Commuications Auxiliary.
1. Navigate to Scan List>Configuration, then select the DeviceNet device folder to view or edit its parameters. The selected DeviceNet device folder will expand.
Rockwell Automation Publication 193-UM014B-EN-P December 2011 43
Chapter 5
2. Click on the Identity folder. The Identity tab will appear, providing information about the selected device.
3. Click on the Parameter folder. Subfields for this folder will appear.
44 Rockwell Automation Publication 193-UM014B-EN-P December 2011
Chapter 5
TIP
4. Select a parameter group. A list of up to 15 parameters will be displayed. If more than 15 parameters are available, select the page number or use the navigation arrows to view the additional parameter screens.
To increase the update rate of the data being displayed on the screen, lower the value in the “Seconds before refresh:” field.
5. Select a parameter group that contains programmable parameters, then click the Edit button. The value options will appear.
Rockwell Automation Publication 193-UM014B-EN-P December 2011 45
Chapter 5
6. Click the down arrow on the pull-down boxes to adjust fixed values and/or enter numerical values in the fields without an arrow to adjust the values.
7. Click Apply once all parameter edits have been completed. The EtherNet/ IP Communications Auxiliary will download the new parameter values to the device. A confirmation window will appear.
8. Click OK.
9. Continue editing the remaining parameters, if desired.
NOTE:
46 Rockwell Automation Publication 193-UM014B-EN-P December 2011
If a DeviceNet module does not support the parameter object, the following window will appear:
Chapter
IMPORTANT

Automatic Device Recovery or Replace

6

Introduction

Setting ADR

In this chapter, using the Automatic Device Recovery or Replace (ADR) will be explained. The use of this feature reduces downtime if a device needs to be replaced.
With ADR, there is no need for software tools to get a replacement device configured and online. The EtherNet/IP Communications Auxiliary automatically configures the replacement device if the device was listed in the scan list and the appropriate electronic keying was selected.
Not all DeviceNet devices support ADR.
1. Navigate to Scan List>Configuration>Advanced.
2. Select the appropriate electronic keying for your DeviceNet network
application.
Rockwell Automation Publication 193-UM014B-EN-P December 2011 47
Chapter 6
By default, the Device Type, Vendor, and Product Code will be enabled. Electronic keying will define how closely a replacement device must match a failed device before the EtherNet/IP Auxiliary reconfigures a module. If the new module does not match the criteria of one of the checked boxes, the ADR will not function and an ADR error will appear.
3. Once the scan list and DeviceNet module programmable parameters have been configured, click Upload ADR Data.
The EtherNet/IP Communications Auxiliary will upload and store the configuration data from the modules in the scan list and a confirmation message will appear,
4. Select Enable from the Auto Device Replace pull-down menu. This will enable the ADR.
48 Rockwell Automation Publication 193-UM014B-EN-P December 2011
Chapter 6
5. Click Save, then cycle power on the EtherNet/IP Communications Auxiliary.
An ADR download is performed immediately before an I/O connection is allocated by the DeviceNet master.
If the download is unsuccessful, an “ADR Error” for the appropriate node will be reported in the corresponding “Scan List Entry Status Word”. If the electronic keys for the device at a given node address do not match the saved electronic keys, no ADR download will take place, an I/O connection will not be allocated, and a “Keying Mismatch” will be reported in the corresponding “Scan List Entry Status Word”.
A warning list will appear after enabling the ADR and a change has been made to the scan list.
AAR (Auto Address Recovery) is also supported by the EtherNet/IP Communications Auxiliary. When the EtherNet/IP Communications Auxiliary detects a node is missing from the scan list and a module matching the electonic
Rockwell Automation Publication 193-UM014B-EN-P December 2011 49
Chapter 6
key is detected on node 63, the EtherNet/IP Communications Auxiliary will attempt to change the module’s network node address to that of the missing scan list node number. When successful, the EtherNet/IP Communications Auxiliary will download the ADR information to the module.
50 Rockwell Automation Publication 193-UM014B-EN-P December 2011
Chapter

Automation Controller Communications

7

Introduction

Ethernet Messaging

I/O Messaging

This chapter describes and gives examples of how each type of EtherNet/IP messaging, I/O messaging and Explicit messaging, is used.
The EtherNet/IP Communications Auxiliary supports two types of EtherNet/IP messaging.
I/O Messaging — Used for deterministic EtherNet/IP communications with ControlLogix™, CompactLogix™, SoftLogix™, and EtherNet/IP scanners. Its primary use is to read and write I/O data for control purposes.
Logic Explicit Messaging — Used for non-deterministic communications in which the data is not critical for control. Logic explicit messages have a lower priority compared to I/O messages and are used to read and write non-critical data.
RS Logix 5000™ software is used to configure I/O messaging between an automation controller and an EtherNet/IP Communications Auxiliary on an EtherNet/IP network.
The following example provides the steps necessary to configure a Logix controller for I/O messaging.
ControlLogix Configuration with Add-On Profiles
An Add-On Profile is available for the EtherNet/IP Communications Auxiliary and can be used with RSLogix 5000 version 17 and higher. The profile can be downloaded from:
http://support.rockwellautomation.com/controlflash/LogixProfiler.asp
An existing project can be used or a new project can be created to configure EtherNet/IP I/O Messaging. To create a new project, perform the following steps.
Rockwell Automation Publication 193-UM014B-EN-P December 2011 51
Chapter 7
1. Select File>New from the RSLogix 5000.
2. Select the controller type, chassis type, slot number, and project path.
Then, enter a name for the controller and click OK.
3. Right-click the I/O Configuration folder, then select New Module. The Select Module Type window will appear.
52 Rockwell Automation Publication 193-UM014B-EN-P December 2011
4. Select the desired EtherNet/IP scanner module, then click OK.
Chapter 7
5. Enter the desired communication settings, then click Finish.
EtherNet/IP Network Configuration with Add-On Profiles
After the controller configuration, the EtherNet/IP Communications Auxiliary has to be added to the I/O configuration.
Rockwell Automation Publication 193-UM014B-EN-P December 2011 53
Chapter 7
1. Place the program in offline mode.
2. Right-click on the EtherNet/IP scanner within the I/O Configuration
folder, then select New Module to open the Select Module Type window.
3. Select the appropriate device (either 193-DNENCAT or 193­DNENECATR, then click OK.
54 Rockwell Automation Publication 193-UM014B-EN-P December 2011
Chapter 7
4. Enter a name for the EtherNet/IP Communications Auxiliary. The name will create tags in RSLogix 5000 that can be used to read and write data from DeviceNet modules being scanned by the EtherNet/IP Communications Auxiliary.
5. Enter the IP address of the EtherNet/IP Communications Auxiliary.
6. Select Change to select a motor protection device with predefined tag
names for Data Mapping. For non-motor protection devices, select Generic.
NOTE: Predefined tag names exist for the E3 Plus EC1, EC2, EC3, EC4, and EC-5
models and the 825-P Overload Relay.
7. Select the appropriate data format, then click OK.
Rockwell Automation Publication 193-UM014B-EN-P December 2011 55
Chapter 7
8. Click OK at the next window to have RSLogix 5000 create the predefined tags. The EtherNet/IP Communications Auxiliary will now show as a module in the I/O Configuration folder.
Accessing Module Data with Add-On Profiles
With both the Logix controller and EtherNet/IP network configured, the Logix controller can exchange data with the EtherNet/IP Communication Auxiliary.
1. Open the Controller Tags window.
2. Select the Monitor Tags tab.
In the above example, the predefined input and output tags were generated for each of the six scanned devices. To control the output relays for the scanned device, use the output tags. For diagnostic informaton from the device, use the input tags.
56 Rockwell Automation Publication 193-UM014B-EN-P December 2011
Chapter 7
ControlLogix Generic Configuration
An existing project can be used or a new project can be created to configure EtherNet/IP I/O Messaging. To create a new project, perform the following steps.
1. Select File>New from the RSLogix 5000.
2. Select the controller type, chassis type, slot number, and project path.
Then, enter a name for the controller and click OK.
3. Right-click the I/O Configuration folder, then select New Module. The Select Module Type window will appear.
Rockwell Automation Publication 193-UM014B-EN-P December 2011 57
Chapter 7
4. Select the desired EtherNet/IP scanner module, then click OK.
5. Enter the desired communication settings, then click Finish.
EtherNet/IP Generic Module Configuration
Once the Logix controller has been configured, the EtherNet/IP Communications Auxiliary must be added to the I/O configuration.
58 Rockwell Automation Publication 193-UM014B-EN-P December 2011
Chapter 7
1. Place the program in offline mode.
2. Right-click on the EtherNet/IP scanner within the I/O Configuration
folder, then select New Module to open the Select Module Type window.
3. Select Generic Ethernet Module, then click OK.
Rockwell Automation Publication 193-UM014B-EN-P December 2011 59
Chapter 7
4. Enter a name for the EtherNet/IP Communications Auxiliary. The name will create a tag in RSLogix 5000 that can be used to read and write data from the devices being scanned by the EtherNet/IP Communication Auxiliary.
5. Select Data-INT for the Comm Format. The Data-INT format wil l represent the data from the EtherNet/IP Communications Auxiliary as a field of 16-bit values.
6. Set the Connection Parameters. I/O data is accessed using Input Instance 101 and Output Instance 100. The size of the input connection and the output connection shall correspond to the size of the chosen instance. The configuration assembly instance is 102.
NOTE: In this example, configuration data is not used. Thus, the data size is set to 0
60 Rockwell Automation Publication 193-UM014B-EN-P December 2011
Chapter 7
7. Type the IP address of the EtherNet/IP Communications Auxiliary.
8. Type the value for the time between each scan of the module. The
recommended RPI time is 250 ms. Ensure that the Inhibit Module is not checked.
9. Click OK to add the EtherNet/IP Communications Auxiliary to the I/O Configuration in RSLogix 5000.
Accessing Generic Module Data
With both the ControlLogix controller and the EtherNet/IP network configured, the ControlLogix controller can exchange data with the EtherNet/IP Communications Auxiliary.
1. Go online, then switch the controller to Remote Run mode.
Rockwell Automation Publication 193-UM014B-EN-P December 2011 61
Chapter 7
2. Open the Controller Tags window.
3. Select the Monitor Tags tab.
An array of input and output tags were generated for each of the six scanned devices. To control the output relays for the scanned device, use the output tags; to obtain diagnostic information from the scanned device, use the input tags.
The format of output data is shown in the table to follow.
Table 6 - Output Assembly — Instance 100
Byte Size Contents
Scan List I/O Size Data to be delivered to the first scan list entry. Scan List I/O Size Data to be delivered to the second scan list entry. Scan List I/O Size Data to be delivered to the third scan list entry. Scan List I/O Size Data to be delivered to the fourth scan list entry. Scan List I/O Size Data to be delivered to the fifthscan list entry. Scan List I/O Size Data to be delivered to the sixth scan list entry.
The format of the input data is shown in the table to follow.
Table 7 - Input Assembly — Instance 101
Byte Size Contents
4 bytes Logix Status Word 2 bytes DeviceNet Scanner Status (Parameter 1) See Table 9 on page 73 2 bytes Scan List Entry 1 Status Word (Parameter 2) See Table 10 on page 74 2 bytes Scan List Entry 2 Status Word (Parameter 3) See Table 11 on page 74 2 bytes Scan List Entry 3 Status Word (Parameter 4) See Table 12 on page 74 2 bytes Scan List Entry 4 Status Word (Parameter 5) See Table 13 on page 75 2 bytes Scan List Entry 5 Status Word (Parameter 6) See Table 14 on page 75 2 bytes Scan List Entry 6 Status Word (Parameter 7) See Table 15 on page 75 Scan List I/O Size Produced I/O data from the first scan list entry. Scan List I/O Size Produced I/O data from the second scan list entry. Scan List I/O Size Produced I/O data from the third scan list entry.
62 Rockwell Automation Publication 193-UM014B-EN-P December 2011
Byte Size Contents
Scan List I/O Size Produced I/O data from the fourth scan list entry. Scan List I/O Size Produced I/O data from the fifth scan list entry. Scan List I/O Size Produced I/O data from the sixth scan list entry. 2 bytes Data Link 1 Data 2 bytes Data Link 2 Data 2 bytes
: : 2 bytes Data Link 48 Data
Data Link 3 Data : :
Chapter 7

Logic Explicit Messaging

CompactLogix, ControlLogix, and SoftLogix controllers can read and write specific information to and from DeviceNet modules on the same DeviceNet network through the EtherNet/IP Communications Auxiliary using Explicit Messaging.
The following steps configure a ControlLogix explicit message using the MSG instruction to read diagnostic parameters from an E3 Plus Model and EC5 Overload Relay.
1. In an interger array named MSG_Read_Request, define the number of attributes to read and list the specific attribute numbers.
The MSG instruction will return in an integer array with the first integer representing the following information:
number of attributes
first attribute number being returned
first attribute number data status
first attribute data…
last attribute number being returned
last attribute number data status
last attribute data
Rockwell Automation Publication 193-UM014B-EN-P December 2011 63
Chapter 7
In the screen capture below, the user-defined structure listing the integers is being returned in this example.
64 Rockwell Automation Publication 193-UM014B-EN-P December 2011
Chapter 7
2. Set up the MSG instruction in the Configuration tab to read the list of attributes (Parameters Group) by configuring the following fields:
Message Type: CIP Generic
Service Type: Custom
Service Code: 0x03 (hex)
Class: 0x375 (hex)
Instance: 1 (dec)
Attribute: 0x00 (hex)
Source Element: MSG_Read_Request [0]
Source Length: 14 (bytes)
Destination: MSG_Read_Data
3. Set up the communications path in the Communications tab to read the data from the E3 Plus Overload Relay located at Node 6 by configuring the communication path as “MotorStarter, 3, 6”.
NOTE: Motor Starter — the name of the EtherNet/IP Communications Auxiliary
3 — the port number of the DeviceNet Scanner of the EtherNet/IP Communications Auxiliary.
6 — the node address of the E3 Plus Overload Relay.
Rockwell Automation Publication 193-UM014B-EN-P December 2011 65
Chapter 7
4. Click OK. When finished, the MSG instruction will read the 25 parameters from the E3 Overload Relay and place the results into MSG_Read_Data as shown below.
66 Rockwell Automation Publication 193-UM014B-EN-P December 2011

E-mail/Text

Chapter
8

Introduction

E-mail Notifications

This chapter describes e-mail notifications and how to configure an EtherNet/IP Communications Auxiliary to send e-mail messages and text notifications for different communication events.
Events
Several communication events can trigger e-mail notifications. These events are fault conditions for the DeviceNet scan list and EtherNet/IP Communications Auxiliary.
Fault Conditions for the DeviceNet Scan List
Minor Recoverable Major Unrecoverable Wrong Data Size Slave Init Error Minor Unrecoverable Connection Timeout No Such Device I/O Data Overflow Major Recoverable Keying Mismatch Frag/Idle Error Automatic Device
Replacement Error
Acknowledge Timeout
Fault Conditions for the EtherNet/IP Communications Auxiliary
On Line Global ADR Error In Idle Mode Duplicate Mac Error Illegal Scan List Data No Scanner Messages Hardware Error Data Link Error No Network Messages Transmit Failure Bus Off Error Non Volatile Storage Error
E-mail Contents
The subject and body contents in the e-mail message wil be created from the:
type of trip or warning that is detected,
device name,
device description,
device location, and
contact information.
Rockwell Automation Publication 193-UM014B-EN-P December 2011 67
Chapter 8
EXAMPLE
E-mail Subject:
193-DNENCATR Comms Aux has detected a fault
E-mail Body:
Fault Status: Device Name: 193-DNENCATR Comms Aux Device Description: Motor Starters Device Location: Bay 6-U29 Contact Info: Contact Person contactperson@thecontact.com
The first word in the e-mail subject is the device name. If a device name is not configured, then the product name attribute from the identity object will be used.
E-mail Configuration
To be able to send an e-mail, the IP address ot the hostname of a Simple Mail Transfer Protocol (SMTP) server must be configured and notifications must be selected. Follow these steps to configure an e-mail notification.
1. In the web browser, type the IP address of the EtherNet/IP Communications Auxiliary in the address bar, then press the enter key on the keyboard.
2. Select Administrative Settings E-Mail Configuration. A login window will appear.
68 Rockwell Automation Publication 193-UM014B-EN-P December 2011
Chapter 8
3. Log in with the username “Adminstrator”, leave the password field blank, and click OK.
NOTE: If desired, a password can be set within the Administrative Settings tab.
4. Type the information into the e-mail notification fields as stated below.
E-mail Recipient The e-mail address of the person who will receive the notifications. E-Mail Sender The e-mail address from which the notification will be sent. SMTP Server Consult with the network administrator for the SMTP server address. SMTP Username Consult with the network administrator for the SMTP username. SMTP Password Consult with the network administrator for the SMTP password. SMTP Port Consult with the network administrator which SMTP port number to
use. Port 25 is the most common SMTP port.
5. Check the desired notification time, fault conditions, and local conditions to be included in notification e-mails to the recipient. These can be changed after the initial configurations.
6. ClickApply Changes to save the configuration.
Configure Device Identity
The properties of the Device Identity populate the notification e-mail subject and e-mail body. To configure the Device Identity, perform the following steps.
1. Select Administrative Settings>Device Identity.
Rockwell Automation Publication 193-UM014B-EN-P December 2011 69
Chapter 8
2. Type the Device Identity information into the fields as described below.
Device Name The name of the EtherNet/IP Communications Auxiliary. Device Description The description of the EtherNet/IP Communications Auxiliary. Device Location The location of the EtherNet/IP Communications Auxiliary. Contact Information The contact information for the EtherNet/IP Communications
Auxiliary.
Device X Name The name of the DeviceNet device being scanned. Device X Description The description of the DeviceNet device being scanned.
3. Click Apply Changes to save the configuration.
Text Notifications
The EtherNet/IP Communications Auxiliary can send a text message to a wireless phone be e-mailing the wireless phone’s service provider. The format for the text message is provided by the service provider and looks similar to the example formats below.
AT& T™ 10-digit wireless phone number@txt.att.net Sprint® 10-digit wireless phone number@messaging.sprint.pcs.com
70 Rockwell Automation Publication 193-UM014B-EN-P December 2011
Chapter 8
EXAMPLE
Multiple e-mail addresses can be entered into the E-mail Recipient field, separating each e-mail address with a semicolon (;). The E-mail Recipient field is limited to 255 characters.
An EtherNet/IP Communications Auxiliary sending an e-mail and text message when a Communications Timeout event occurs:

Limitations

Based on the functionality of the EtherNet/IP Communications Auxiliary, there are some limitations on when the e-mails can be triggered.
If two events occur at the same time, an e-mail will only be sent for the most significant error.
If the device has been configured to send an e-mail for a lower prioritized event and this event occurs at the same time as a higher prioritized event for which the device has not been programmed to send an e-mail, an e-mail will not be sent for either event.
The Clear e-mail will only be sent when all events have been cleared and an event e-mail has previously been sent.
Rockwell Automation Publication 193-UM014B-EN-P December 2011 71
Chapter 8
72 Rockwell Automation Publication 193-UM014B-EN-P December 2011

Device Parameters

IMPORTANT
Chapter
9

Introduction

Parameter Programming

The EtherNet/IP Communications Auxiliary provides parameters to allow the user to view the status and configure the DeviceNet scanner with RSNetWorx for DeviceNet if the user does not want to use the internal web server of the EtherNet/IP Communications Auxiliary. The 14 available parameters are listed below.
Table 8 - Parameter List
1 Scanner Status 8 SL Entry Size 2 SL Entry 1 Status 9 Device Keys 3 SL Entry 2 Status 10 Scanlist Config 4 SL Entry 3 Status 11 ADR Record 5 SL Entry 4 Status 12 ADR Enable 6 SL Entry 5 Status 13 DNet IO RPI 7 SL Entry 6 Status 14 DNet IO Inhibit
Parameter setting changes to the EtherNet/IP Communications Auxiliary take effect immediately even during a “running” status.
Parameter Listing
The details for each of the 14 available parameters are listed below.
Table 9 - Parameter 1 — Scanner Status
Value
Description Access Rule Data Type Units
Provides the status of the
Devicenet scanner.
0 On Line 3 No Scanner Messages 6 Initializing 1 Illegal Scan List 4 Transmit Failure 7 Duplicate MAC Failure 2 No Network Messages 5 In Idle Mode 8 Bus Off
Rockwell Automation Publication 193-UM014B-EN-P December 2011 73
Get WORD 0 16383 0
Bit
Min. Max. Default
Chapter 9
Table 10 - Parameter 2 — SL Entry 1 Status
Value
Description Access Rule Data Type Units
Provides the status of the
first scan list entry in the
DeviceNet scanner.
0 On Line 4 No Such Device 8 Device Went Idle 1 Connection Timeout 5 Fragment Error 2 Keying Mismatch 6 Slave Initialization Error 3 Wrong Data Size 7 I/O Data Overflow 10 Acknoledgement Timeout
Get WORD 0 2047 0
Bit
Min. Max. Default
Automatic Device
9
Replacement Error
Table 11 - Parameter 3 — SL Entry 2 Status
Value
Description Access Rule Data Type Units
Provides the status of the
second scan list entry in the
DeviceNet scanner.
0 On Line 4 No Such Device 8 Device Went Idle 1 Connection Timeout 5 Fragment Error 2 Keying Mismatch 6 Slave Initialization Error 3 Wrong Data Size 7 I/O Data Overflow 10 Acknoledgement Timeout
Get WORD 0 2047 0
Bit
Min. Max. Default
Automatic Device
9
Replacement Error
Table 12 - Parameter 4 — SL Entry 3 Status
Value
Description Access Rule Data Type Units
Provides the status of the third scan list entry in the
DeviceNet scanner.
0 On Line 4 No Such Device 8 Device Went Idle 1 Connection Timeout 5 Fragment Error 2 Keying Mismatch 6 Slave Initialization Error 3 Wrong Data Size 7 I/O Data Overflow 10 Acknoledgement Timeout
Get WORD 0 2047 0
Bit
Min. Max. Default
Automatic Device
9
Replacement Error
74 Rockwell Automation Publication 193-UM014B-EN-P December 2011
Chapter 9
Table 13 - Parameter 5 — SL Entry 4 Status
Value
Description Access Rule Data Type Units
Provides the status of the
fourth scan list entry in the
DeviceNet scanner.
0 On Line 4 No Such Device 8 Device Went Idle 1 Connection Timeout 5 Fragment Error 2 Keying Mismatch 6 Slave Initialization Error 3 Wrong Data Size 7 I/O Data Overflow 10 Acknoledgement Timeout
Get WORD 0 2047 0
Bit
Min. Max. Default
Automatic Device
9
Replacement Error
Table 14 - Parameter 6 — SL Entry 5 Status
Value
Description Access Rule Data Type Units
Provides the status of the
fifth scan list entry in the
DeviceNet scanner.
0 On Line 4 No Such Device 8 Device Went Idle 1 Connection Timeout 5 Fragment Error 2 Keying Mismatch 6 Slave Initialization Error 3 Wrong Data Size 7 I/O Data Overflow 10 Acknoledgement Timeout
Get WORD 0 2047 0
Bit
Min. Max. Default
Automatic Device
9
Replacement Error
Table 15 - Parameter 7 — SL Entry 6 Status
Value
Description Access Rule Data Type Units
Provides the status of the sixth scan list entry in the
DeviceNet scanner.
0 On Line 4 No Such Device 8 Device Went Idle 1 Connection Timeout 5 Fragment Error 2 Keying Mismatch 6 Slave Initialization Error 3 Wrong Data Size 7 I/O Data Overflow 10 Acknoledgement Timeout
Get WORD 0 2047 0
Bit
Min. Max. Default
Automatic Device
9
Replacement Error
Rockwell Automation Publication 193-UM014B-EN-P December 2011 75
Chapter 9
Table 16 - Parameter 8 — SL Entry Size
Description Access Rule Data Type Units
Defines the number of bytes
to be scanned for I/O data
from each DeviceNet Device.
Get/Set USIN T Bytes 1 50 8
Min. Max. Default
Table 17 - Parameter 9 — Device Keys
Description Access Rule Data Type Units
Determines how electronic
keying will be performed.
0 Device Type 2 Product Code 4 Minor Revision 1 Vendor 3 Major Revision 5 Minor of Higher
Get/Set USIN T 0 63 7
Bit
Min. Max. Default
Value
Value
Table 18 - Parameter 10 — Scanlist Config
Description Access Rule Data Type Units
Triggers the building of a new
DeviceNet scan list.
0 = Ready
1 = Build Scan List
Get/Set BOOL 0 1 0
Table 19 - Parameter 11 — ADR Record
Description Access Rule Data Type Units
Triggers the recording of
configuration parameters from
devices in the DeviceNet scan list
to be used for Automatic Device
Replacement.
0 = Ready
1 = Record Parameters
Get/Set BOOL 0 1 0
Table 20 - Parameter 12 — ADR Enable
Description Access Rule Data Type Units
Enables Automatic Device
Replacement.
0 = Disable
1 = Enable
Get/Set BOOL 0 1 0
Value
Min. Max. Default
Value
Min. Max. Default
Value
Min. Max. Default
76 Rockwell Automation Publication 193-UM014B-EN-P December 2011
Table 21 - Parameter 13 — DNet IO RPI
Description Access Rule Data Type Units
Defines the requested packet
interval rate in milliseconds used
on DeviceNet Polled I/O
messaging.
Get/Set WORD ms 2 1000 75
Table 22 - Parameter 14 — DNet IO Inhibit
Description Access Rule Data Type Units
Defines the inhibit time in
milliseconds used on DeviceNet
Change of State (COS) I/O
messaging.
Get WORD ms 2 1000 1
Chapter 9
Value
Min. Max. Default
Value
Min. Max. Default
Rockwell Automation Publication 193-UM014B-EN-P December 2011 77
Chapter 9
78 Rockwell Automation Publication 193-UM014B-EN-P December 2011

Troubleshooting

Chapter
10

Introduction

EtherNet/IP Modules of Operation

The purpose of this chapter is to assist in troubleshooting the EtherNet/IP Communications Auxiliary.
SHOCK HAZARD: Servicing energized industrial control equipment can be hazardous. Electrical shock, burns, or unintential actuation of controlled industrial equipment may cause death or serious injury .For safety of maintenance personnel as well as others who may be exposed to electrical hazards assicated with maintenance activities, follow local safety related work practices (e.g., the NFPS 70W; Part II, Electrical Safety for Employee Workplaces, in the United States) when working on or near energized equipment. Maintenance personnel must be trained in the safety practices, procedures, and requirements that pertain to their respective job assignments. Do not work alone on energized equipment.
ATTENTION: Do not attempt to defeat or override fault circuits. The cause of a fault indication must be determined and corrected before attempting operation. Failure to correct a control system or mechanical malfunction may result in personal injury and/or equipment damage due to uncontrolled machine system operation.
The EtherNet/IP Communications Auxiliary has four EtherNet/IP modes of operation:
Power-Up Reset Mode,
Run Mode,
Recoverable Error Mode, and
Unrecoverable Error Mode.
Rockwell Automation Publication 193-UM014B-EN-P December 2011 79
Chapter 10
Power-Up Reset Mode
Figure 8 - Status LEDs
Module Status (MS) LED
Ethernet/IP Network Status (NS) LED
Front Port Link Activity LED
Rear Port Link Activity LED
DeviceNet Network Status (NS) LED
During the Power-Up Reset Mode, the following procedure occurs.
1. The various LEDs will cycle simultaneously.
Module Status (MS) LED will flash green for approximately 0.25 seconds, flash red for another 0.25 seconds, then remain a solid green.
EtherNet/IP Network Status (NS) LED will flash green for approximately 0.25 seconds, flash red for another 0.25 seconds, then not illuminate.
Device Network Status (NS) LED will flash green for approximately .25 seconds, flash red for another0 .25 seconds, then not illuminate.
The MS and both NS LEDs will then return to their standard illuminated state.
2. The EtherNet/IP Communications Auxiliary will perform a duplicate IP address check to verify that another module is not assigned to the same IP address. If a duplicate IP address is detected on the network, the EtherNet/ IP NS LED illuminates to a solid red, the MS LED flashes red, and the EtherNet/IP Communications Auxiliary enters the Recoverable Error Mode.
3. The EtherNet/IP Communications Auxiliary performs a duplicate MAC address check to verify that another module is not assigned to the same MAC address. If a duplicate MAC address is detected on the DeviceNet network, the DeviceNet NS LED illuminates a solid red, the MS LED flashes red, and the EtherNet/IP Communications Auxiliary enters the Recoverable Error Mode.
80 Rockwell Automation Publication 193-UM014B-EN-P December 2011
Chapter 10
4. If the power-up or reset is successful, the overload relay will enter into Run Mode.
Run Mode
In Run Mode, the EtherNet/IP Communications Auxiliary will:
operate as a slave device to a master device on an EtherNet/IP network.
operate as a master device and scan up to six slave devices on a DeviceNet
network.
accept messages from a master on the EtherNet/IP network.
send response messages, COS messages, or CYCLIC messages to a master.
support a Device Level Ring (DLR) for Caralog Number 193-
DNENCATR.
If a communication error is detected, the EtherNet/IP Communications Auxiliary will either enter the Recoverable Error Mode or Unrecoverable Error Mode.
Operating as a Slave Device to a Master Device
As stated, the EtherNet/IP Communications Auxiliary will operate as a slave device to a master device on an EtherNet/IP network in Run Mode. The EtherNet/IP NS LED will flash green if there are no network connections established with an EtherNet/IP network master. When one or more connections are in the “established’ state, the EtherNet/IP NS LED will illuminate a solid green. When one or more connections are in the “timed out” state, the EtherNet/IP NS will flash red.
Operating as a Master Device
As also stated, the EtherNet/IP Communications Auxiliary will also operate as a master device and scan up to six slave devices on a DeviceNet network in Run Mode. The DeviceNet NS LED will flash green if there are no connections established with a DeviceNet slave device. When one or more connections are in the “established” state, the DeviceNet NS LED will illumiate a solid green. When one or more connections are in the “timed out” state, the DeviceNet NS LED will flash red. If no slave devices are defined in the DeviceNet scan list, the MS LED will flash red.
Rockwell Automation Publication 193-UM014B-EN-P December 2011 81
Chapter 10
Recoverable Error Mode
In this mode, the EtherNet/IP Communications Auxiliary MS LED flashes red. The device will respond to messages that are specified in offline mode recovery message protocol.
Error Type Description LED State
Recoverable Duplicate IP address detected. Flashing Red
A device is not present on the DeviceNet scan list.
Unrecoverable Error Mode
In this mode, the EtherNet/IP Communications Auxiliary MS LED illuminates a solid red. The device continues in this state as long as the device is powered.
Error Type Description LED State
Unecoverable Power-up initialization failure. Solid Red
Data communication error.

Troubleshooting Procedures

The following table identifies possible causes and corrective actions when troubleshooting EtherNet/IP related failures using the status LEDs.
Table 23 - Troubleshooting Procedures
Status LED Color State Possible Cause Corrective Action
EtherNet/IP Network Status (NS)
None
Green, Red, Not Illuminated
Green Flashing
Green Solid
Red Flashing
Red Solid
Flashing (once)
The EtherNet/IP Communications Auxiliary is not receiving power.
Normal This is a normal power-up
The EtherNet/IP Communications Auxiliary is online, but with no connections established.
Normal operating state and the EtherNet/IP Communications Auxiliary is allocated to a master.
One or more EtherNet/IP connections timed out.
Diagnostics test failed on power-up/reset. An internal fault exists.
Duplicate EtherNet/IP module address exists. Two modules cannot have the same address.
A fatal communication error occurred.
Check the DeviceNet cable connections and verify that 24V DC exists between the red and black terminals.
sequence.
Check the EtherNet/IP master and its scan list for correct scanner configuraton.
No action is required.
Reset the EtherNet/IP master device.
Cycle power to the unit. If the fault still exists, replace the unit.
Change the IP address to a valid setting and reset the device.
Check Ethernet media for proper installation.
82 Rockwell Automation Publication 193-UM014B-EN-P December 2011
Chapter 10
Status LED Color State Possible Cause Corrective Action
DeviceNet Network Status (NS)
Module Status
Link Link (front) Link (back)
None
Green, Red, Not Illuminated
Green Flashing
Green Solid
Red Flashing
Red Solid
None
Green, Red, Not Illuminated
Green Flashing
Green Solid
Red Flashing
Red Solid
None
Green Flashing
Green Solid
Flashing (once)
Flashing (once)
The EtherNet/IP Communications Auxiliary is not receiving power.
Normal This is a normal power-up
The EtherNet/IP Communications Auxiliary is not configured to scan any DeviceNet slave devices.
Normal operating state and the EtherNet/IP Communications Auxiliary is scanning DeviceNet slave devices.
One or more DeviceNet connections timed out.
Diagnostics test failed on power-up/reset. An internal fault exists.
Duplicate DeviceNet module address exists. Two modules cannot have the same address.
A fatal communication error occurred.
The EtherNet/IP Communications Auxiliary is not receiving power.
Normal This is a normal power-up
The EtherNet/IP Communications Auxiliary is proper;y scanning DeviceNet slave devices, but it is not being scanned by the EtherNet/IP master.
Normal operating state, the EtherNet/IP Communications Auxiliary is scanning DeviceNet slave devices, and is allocated to its master.
One or more DeviceNet or EtherNet/IP connections timed out.
The EtherNet/IP Communications Auxiliary is not configured to scan any DeviceNet slave devices.
Diagnostics test failed on power-up/reset.
The EtherNet/IP Communications Auxiliary is
ot properly conne
n Ethernet network.
The Ethernet network is properly connected.
Communications are occurring on the Ethernet network.
cted to an
Check the DeviceNet cable connections and verify that 24V DC exists between the red and black terminals.
sequence.
Check the DeviceNet scan list for the correct scanner configuration.
No action is required.
Reset the EtherNet/IP Communications Auxiliary.
Cycle power to the unit. If the fault still exists, replace the unit.
Change the MAC address to a valid setting and reset the device.
Check DeviceNet media for proper installation.
Check the DeviceNet cable connections and verify that 24V DC exists between the red and black terminals.
sequence.
Check the Ethernet scan list for the correct scanner configuration.
No action is required.
Reset the EtherNet/IP Communications Auxiliary.
Check the DeviceNet scan list for correct scanner configuration.
Cycle power to the device. If the fault still exists, replace the device.
Check the Ethernet cabling to make sure it is properly installed.
No action is required.
No action is required.
Rockwell Automation Publication 193-UM014B-EN-P December 2011 83
Chapter 10
84 Rockwell Automation Publication 193-UM014B-EN-P December 2011

Specifications

Appendix
A
Specifications
Table 24 - Ratings
Terminal Ratings
Terminal Screw M3 Wire Cross Section See wiring diagram section Torque 0.56…0.79 N•m (5…7 lb.•in.) Degree of Protection IP20
Power Supply Ratings
Rated Supply Voltage U Rated Operating Range U Rated Supply Current I Maximum Surge Current at Power-Up 6.4 A Maximum Power Consumption 2.1 W
Environmental Ratings
Ambient Temperature T Storage Operating (Open) (Enclosed)
Humidity Operating Damp Heat - Steady State Damp Heat - Cyclic
Cooling Method Natural Convection Vibration (per IEC 68-2-6) 3 G Shock (per IEC 68-2-27) 30 G Maximum Altitude 2000 m Pollution Environment Pollution Degree 2 Terminal Marking EN 50012 Degree of Protection IP20
s
e
e
amb
24V DC 24V -15%, +10% DC 100 mA at 24V DC
-40…+85 °C (-40…+185 °F)
-20…+60 °C (-4…+140 °F)
-20…+40 °C (-4…+104 °F)
5…95% non-condensing per IEC 68-2-3 per IEC 68-2-30
Rockwell Automation Publication 193-UM014B-EN-P December 2011 85
Appendix A
Table 25 - Electromagnetic Compatibility
Electromagnetic Compatibility
Electrostatic Discharge Immunity Test Level
Performance Criteria RF Immunity
Test Level
Performance Criteria Electrical Fast Transient/Burst Immunity
Test Level
Performance Criteria Surge Immunity
Test Level Performance Criteria
Radiated Emissions Class A Conducted Emissions Class A
8 kV Air Discharge 4 kV Contact Discharge
B➊➋
10V/m: 80 MHz…1 GHz 3V/m: 1.4 GHz…2 GHz 1V/m: 2.0 GHz…2.7 GHz
B➊➋
2 kV (Power Protective Earth) 1 kV (control bus cable)
B➊➋
1 kV L-L (bus cable) B➊➋
Performance Criteria B requires the DUT (device under test) not to experience degradation or loss of performance.Environment 2 - Heavy Industrial.
WARNING: This is a class A product. In domestic environment, this product may cause radio interference, in which case the user may be required to take adequate measures.
Table 26 - Ethernet IP Communcations
EtherNet/IP Communications
Total Connections Supported TCP CIP
Total CIP Unconnected Messages Supported 128 CIP Class 1 Connection Consumed 1 Packet Rates (packets/second)
I/O HIM/MSG
Media Support Twisted Pair Fiber
Speed Duplex (Half/Full) 10/100 Duplicate IP Detection Yes
150 47
500 500
Yes No
86 Rockwell Automation Publication 193-UM014B-EN-P December 2011
Table 27 - Standards & Certifications
Standards and Certifications
UL 508 CSA 22.2, No. 14 EN 60947-4-1
Appendix A
Rockwell Automation Publication 193-UM014B-EN-P December 2011 87
Appendix A
88 Rockwell Automation Publication 193-UM014B-EN-P December 2011
Appendix
EtherNet/IP & DeviceNet Information
B

Electronic Data Sheet (EDS) Files

Common Industrial Protocol (CIP) Objects

EDS files are specially formatted ASCII files that provide all of the information necessary for a configuration tool (e.g., RSNetWorx for EtherNet/IP) to access and alter the parameters of a device. The EDS file contains all the parameter information of a device: number of parameters, groupings, parameter name, min, max, and default values, units, data format and scaling. The EDS file for the EtherNet/IP Communications Auxiliary is available from the Internet at
www.ab.com/networks/eds/index.html
EtherNet/IP Communications Auxiliary’s internal web page.
The following CIP object classes are supported.
Table 28 - CIP Object Classes
. It can also be obtained from the
Class Object EtherNet/IP DeviceNet
0x01 Identity X X 0x02 Message Router X X 0x03 DeviceNet X 0x04 Assembly X X 0x05 Connection X 0x06 Connection Manager X 0x0F Parameter X X 0x47 Device Level Ring Object X 0x48 Q05 Object X 0xA1 Non-Volatile Storage Object X X 0xF4 Port Object X X 0xF5 TCP/IP Interface X 0xF6 Ethernet Link X
Identity Object — CLASS CODE 0x01
The following class attributes are supported for the Identity Object.
Rockwell Automation Publication 193-UM014B-EN-P December 2011 89
Appendix B
Table 29 - Identity Object Class Attributes
Attribute ID Access Rule Name Data Type Value
1 Get Revision UINT 0x0001 2 Get Max. Instance UINT 0x00011
Identity Object instances contain the following instance attributes.
Table 30 - Identity Object Instance Attributes
Attribute ID Access Rule Name Data Type Value
1 Get Vendor ID UINT 2 Get Device Type UINT 12 3 Get Product Code UINT 220 for 193-DNENCAT
221 for 193-DNENCATR
4 Get Major Revision USINT 1
Minor Revision USINT 1
5 Get Status WORD Bit 0: Owned, shall be set when
at least one connection i configured Bit 2: Configured Bit 8: Minor Recoverable fault BIt 9: Minor Unrecoverable fault Bit 10: Major Recoverable fault Bit 11: Major Unrecoverable fault
6 Get Serial Number UDINT Unique number assigned for
each device 7 Get Product Name SHORT_STRING Product name 8 Get State USINT 3=Operational
The following common services are implemented for the Identity Object.
Table 31 - Identity Object Common Services
Implemented for:
Service Code
0x01 No Yes Get Attribute All 0x0E Yes Yes Get Attribute Single 0x05 No Yes Reset
Service NameClass Instance
Message Router Object — CLASS CODE 0x02
No class or instance attributes are supported. The message router object exists only to route explicit messages to other objects.
90 Rockwell Automation Publication 193-UM014B-EN-P December 2011
Appendix B
DeviceNet Object — CLASS CODE 0x03
The following class attributes will be supported for the DeviceNet Object.
Table 32 - DeviceNet Object Class Attributes
Attribute ID Access Rule Name Data Type Value
1 Get Revision UINT 2
A single instance of the DeviceNet Object will be supported by the following attributes.
Table 33 - Single Instance of the DeviceNet Object
Attribute ID Access Rule Name Data Type Value
1 Get/Set Node Address USINT 0-63 2 Get/Set Baud Rate USINT 0=125K
1=250K 2=500K
13 Get Active Node
Tab le
Array of BOOL [64]
Identifies which nodes are online on the local network based on the node address.
The following services will be implemented for the DeviceNet Object.
Table 34 - DeviceNet Object Common Services
Implemented for:
Service Code
0x0E Yes Yes Get Attribute Single 0x10 No Yes Set Attribute Single
Service NameClass Instance
Assembly Object — CLASS CODE 0x04
The following class attributes are supported for the Assembly Object.
Table 35 - Assembly Object Class Attributes
Attribute ID Access Rule Name Data Type Value
2 Get Max. Instance UINT 120
Instance Attributes
Instances/Connection points implements the following data attributes.
Rockwell Automation Publication 193-UM014B-EN-P December 2011 91
Appendix B
Table 36 - Instance Attributes
# Access Name Type Value Description
3 Get/Set Data Array of UINT — Data produced/consumed by the module
Output Assemblies
The following output assembly instances are implemented.
Table 37 - Instance 100
Byte Size Contents
Scan List I/O Size Data to be delivered to the first scan list entry. Scan List I/O Size Data to be delivered to the second scan list entry. Scan List I/O Size Data to be delivered to the third scan list entry. Scan List I/O Size Data to be delivered to the fourth scan list entry. Scan List I/O Size Data to be delivered to the fifth scan list entry. Scan List I/O Size Data to be delivered to the sixth scan list entry.
Input Assemblies
Table 38 - Instance 101
Byte Size Contents
4 Bytes Logix Status Word 2 Bytes DeviceNet Scanner Status (Parameter 1) See Table 9 on page 73 2 Bytes Scan List Entry 1 Status Word (Parameter 2) See Table 10 on page 74 2 Bytes Scan List Entry 2 Status Word (Parameter 3) See Table 11 on page 74 2 Bytes Scan List Entry 3 Status Word (Parameter 4) See Table 12 on page 74 2 Bytes Scan List Entry 4 Status Word (Parameter 5) See Table 13 on page 75 2 Bytes Scan List Entry 5 Status Word (Parameter 6) See Table 14 on page 75 2 Bytes Scan List Entry 6 Status Word (Parameter 7) See Table 15 on page 75 Scan List I/O Size Data to be delivered to the first scan list entry. Scan List I/O Size Data to be delivered to the second scan list entry. Scan List I/O Size Data to be delivered to the third scan list entry. Scan List I/O Size Data to be delivered to the fourth scan list entry. Scan List I/O Size Data to be delivered to the fifth scan list entry. Scan List I/O Size Data to be delivered to the sixth scan list entry. 2 Bytes DataLink 1 Data 2 Bytes DataLink 2 Data 2 Bytes
: : : : 2 Bytes Data Link 48 Data
DataLink 3 Data : : : :
92 Rockwell Automation Publication 193-UM014B-EN-P December 2011
Appendix B
Table 39 - Instance 103
Byte Size Contents
4 Bytes Logix Status Word 4 Bytes DeviceNet Scanner Status (Parameter 1) See Table 9 on page 73 4 Bytes Scan List Entry 1 Status Word (Parameter 2) See Table 10 on page 74 4 Bytes Scan List Entry 2 Status Word (Parameter 3) See Table 11 on page 74 4 Bytes Scan List Entry 3 Status Word (Parameter 4) See Table 12 on page 74 4 Bytes Scan List Entry 4 Status Word (Parameter 5) See Table 13 on page 75 4 Bytes Scan List Entry 5 Status Word (Parameter 6) See Table 14 on page 75 4 Bytes Scan List Entry 6 Status Word (Parameter 7) See Table 15 on page 75 Scan List I/O Size Data to be delivered to the first scan list entry. Scan List I/O Size Data to be delivered to the second scan list entry. Scan List I/O Size Data to be delivered to the third scan list entry. Scan List I/O Size Data to be delivered to the fourth scan list entry. Scan List I/O Size Data to be delivered to the fifth scan list entry. Scan List I/O Size Data to be delivered to the sixth scan list entry. 2 Bytes DataLink 1 Data 2 Bytes DataLink 2 Data 2 Bytes DataLink 3 Data : : : : : : : : 2 Bytes Data Link 48 Data
Available with firmware v 2.00 and higher.
Rockwell Automation Publication 193-UM014B-EN-P December 2011 93
Appendix B
Configuration Assembly
Table 40 - Instance 102 (Revision 1)
Byte Size Contents
2 Bytes Revision = 1 2 Bytes ScanList I/O Size 2 Bytes Data Link Update Interval (ms) 1 Byte Data Link 1 Node 2 Bytes Data Link 1 Parameter 1 Byte Data Link 2 Node 2 Bytes Data Link 2 Parameter 1 Byte Data Link 3 Node 2 Bytes Data Link 3 Parameter 1 Byte Data Link 4 Node 2 Bytes Data Link 4 Parameter 1 Byte Data Link 5 Node 2 Bytes Data Link 5 Parameter 1 Byte Data Link 6 Node 2 Bytes Data Link 6 Parameter
: : : : : : : :
1 Byte Data Link 48 Node 2 Bytes Data Link 48 Parameter
94 Rockwell Automation Publication 193-UM014B-EN-P December 2011
Table 41 - Instance 102 (Revision 2)
Byte Size Contents
2 Bytes Revision = 2 2 Bytes ScanList I/O Size 2 Bytes Data Link Update Interval (ms) 2 Bytes Reserved 2 Bytes Data Link 1 Node 2 Bytes Data Link 1 Parameter 2 Bytes Data Link 2 Node 2 Bytes Data Link 2 Parameter 2 Bytes Data Link 3 Node 2 Bytes Data Link 3 Parameter 2 Bytes Data Link 4 Node 2 Bytes Data Link 4 Parameter 2 Bytes Data Link 5 Node 2 Bytes Data Link 5 Parameter 2 Bytes Data Link 6 Node 2 Bytes Data Link 6 Parameter
Appendix B
: : : : : : : :
2 Bytes Data Link 48 Node 2 Bytes Data Link 48 Parameter
Available with firmware v 2.00 and higher.
The following services are implemented for the Assembly Object.
Table 42 - Ethernet Object Common Services
Implemented for:
Service Code
0x0E Yes Yes Yes Get Attribute Single 0x10 No Yes No Set Attribute Single
Service NameClass Instance Consuming Instance Producing
Connection Manager Object — CLASS CODE 0x06
No class or instance attributes are supported.
The following common service are implemented for the Connection Manager Object.
Rockwell Automation Publication 193-UM014B-EN-P December 2011 95
Appendix B
Table 43 - Connection Manager Object Common Services
Implemented for:
Service NameInstance
Yes Forward Open Yes Forward Close Yes Unconnected Send
Parameter Object — CLASS CODE 0x0F
The following class attributes are supported for the Parameter Object.
Table 44 - Parameter Object Class Attributes
Attribute ID Access Rule Name Data Type Value
1 Get Revision UINT 0x0001 2 Get Max Instance UINT 0x0029 8 Get Parameter Class Descriptor WORD 0x000B
The following instance attributes are implemented for all parameter attributes.
Table 45 - Parameter Object Instance Attributes
Attribute ID Access Rule Name Data Type Value
1 Get/Set Value Specified in Descriptor 2 Get Link Path Size USINT 3 Get Link Path Packed EPATH: Path to specified
4 Get Descriptor WORD 5 Get Data Type EPATH 6 Get Data Size USINT 7 Get Parameter Name
String 8 Get Units String SHORT_STRING 9 Get Help String SHORT_STRING 10 Get Minimum Value Specified in Descriptor 11 Get Maximum Value Specified in Descriptor 12 Get Default Value Specified in Descriptor 13 Get Scaling Multiplier UINT 14 Get Scaling Divisor UINT 15 Get Scaling Base UINT 16 Get Scaling Offset INT 17 Get Multiplier Link UINT
SHORT_STRING
N/A
object attribute
Parameter Dependent
96 Rockwell Automation Publication 193-UM014B-EN-P December 2011
Appendix B
Attribute ID Access Rule Name Data Type Value
18 Get Divisor Link UINT 19 Get Base Link UINT 20 Get Offset Link UINT 21 Get Decimal Precision USINT Parameter Dependent
The following commons services are implemented for the Parameter Object.
Table 46 - Parameter Object Common Services
Implemented for:
Service Code
0x01 No Yes Get Attribute All 0x0E Yes Yes Get Attribute Single 0x10 No Yes Set Attribute Single 0x4B No Yes Get Enum String
Service NameClass Instance
Device Level Ring (DLR) Object — CLASS CODE 0x47
No class attributes will be supported for the DLR object. A single instance (Instance 1) will be supported.
Table 47 - DLR Object Single Instance
Attributes ID Access Rule Name Data Type Value
1 Get Network Topology USINT
2 Get Network Status USINT
10 Get
12 Get Capability Flags DWORD 0x00000002
Active Supervisor
Address
Structure of UDINT; array of 6 USINT
The following common services will be implemented for the DLR object.
Table 48 - DLR Object Common Services
Implemented for:
Service Code
0x01 No Yes Get_Attributes_All 0x0E No Yes Get_Attribute_Single
Service NameClass Instance
0=Linear 1=Ring
0=Normal 1=Ring Fault 2=Unexpected Loop Detect 3=Partial Network Fault 4=Rapid Fault/Restore Cycle
Ring Supervisor
Rockwell Automation Publication 193-UM014B-EN-P December 2011 97
Appendix B
QoS Object — CLASS CODE 0x48
The following class attributes will be supported for the QoS object.
Table 49 - QoS Object Class Attributes
Attribute ID Access Rule Name Data Type Value
1 Get Revision UINT 1
A single instance (Instance 1) will be supported.
Table 50 - QoS Object Instance
Attribute ID Access Rule Name Data Type Value
1 Set 802: 1Q Tag Enable USINT 0=Disable (default)
1=Enable 4 Set DSCP Urgent USINT Default=55 5 Set DSCP Schedule USINT Default=47 6 Set DSCP High USINT Default=43 7 Set DSCP Low USINT Default=31 8 Set DSCP Explicit USINT Default=27
The following common services will be implemented for the QoS object.
Table 51 - QoS Object Common Services
Implemented for:
Service Code
0x0E Yes Yes Get_Attribute_Single 0x10 No Yes Set_Attribute_Single
Service NameClass Instance
Non-Volatile Storage Object — CLASS CODE 0xA1
The following instances of the Non-Volatile Storage object will be supported.
Table 52 - Non-Volatile Storage Object Instances
NVS Object Instance Entity to be Updated
1 EtherNet/IP Module Application Code 2 EtherNet/IP Module Boot Code 3 EtherNet/IP Module FPGA Image
98 Rockwell Automation Publication 193-UM014B-EN-P December 2011
Appendix B
Port Object — CLASS CODE 0x0F4
The Port object supports the following class attributes.
Table 53 - Port Object Class Attributes
Attribute ID Access Rule Name Data Type Value
1 Get Revision UINT 1 2 Get Max. Instance UINT 2 3 Get Num. Instances UINT 2 8 Get Entry Port UINT 1
Port Instance Info Array of
Structure of
9Get
Port Type UINT Port Number UINT
Two instances of the Port object will be supported. Instance 1 will represent the EtherNet/IP port and Instance 2 will represent the DeviceNet port.
1
Table 54 - Port Object Instances
Attribute ID Access Rule Name Data Type Value
1 Get Port Type UINT Inst 1=4; Inst 2=5 2 Get Port Number UINT
Link Object Struct of
3Get
4 Get Port Name Short String Inst 1=”Port A”;
5 Get Port Type Name Short String Inst 1=”EtherNet/IP”;
7 Get Node Address Padded EPATH
8Get
Path Length UINT Link Path Padded EPATH
Port Node Range Struct of Min. Node Number UINT Max. Node Number UINT
Inst 2=”Port B”
Inst 2=”DeviceNet”
This attribute is implemented for Inst 2 only.
The following services will be implemented.
Table 55 - Port Object Services
Implemented for:
Service Code
0x01 Yes Yes Get_Attributes_All 0x0E Yes Yes Get_Attribute_Single
Rockwell Automation Publication 193-UM014B-EN-P December 2011 99
Service NameClass Instance
Appendix B
TCP/IP Interface Object — CLASS CODE 0xF5
The TCP/IP object supports the following class.
Table 56 - TCP/IP Object Class
Attribute ID Access Rule Name Data Type Value
1 Get Revision UINT 3
For single port devices, one instance of the TCP/IP interface object is supported. For dual port devices, two instances of the TCP/IP interface object are supported.
Table 57 - TCP/IP Object Class Instances
Attribute ID Access Rule Name Data Type Value
1 Get Status DWORD 2 Get Configuration
Capability
3 Get/Set Configuration
Control
4 Get Physical
Link Object
5 Get/Set Interface
Configuration
6 Get/Set Host Name STRING 8 Get/Set TTL Value USINT Time to live value for EtherNet/IP
9 Get/Set Multicast
Config
DWORD 0x00000014
DWORD 0=Configuration from NVS
Struct of:
UINT
Padded EPATH
Struct of: UDINT UDINT UDINT UDINT UDINT STRING
Struct of: USINT USINT UINT
UDINT
2=Configuration from DHCP
For a single port device: 2 words 20 F6 24 01 (ENet Link Object Inst 1) For dual port device: NULL
IP Address Network Mask Gateway Address Primary DNS Secondary DNS Default domain name for not fully
qualified host names
multicast packets
Allocation Control Reserved Number of multicast addresses to allocate (1-4) Multicast starting address
The following common services are implemented for the TCP/IP interface object.
100 Rockwell Automation Publication 193-UM014B-EN-P December 2011
Loading...