Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety
Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1
your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/
important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference,
and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment
must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from
the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous
environment, which may lead to personal injury or death, property damage, or economic loss.
available from
) describes some
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death,
property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the
consequence
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that
dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that
surfaces may reach dangerous temperatures.
Identifies information that is critical for successful application and understanding of the product.
Allen-Bradley, Rockwell Software, Rockwell Automation, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Chapter 1
Installation & Wiring
Configure the EtherNet/IP
Communications Auxiliary
Rockwell Automation Publication 193-UM014B-EN-P - July 20115
6Rockwell Automation Publication 193-UM014B-EN-P - July 2011
Installation & Wiring
Chapter
1
Introduction
Overview
The purpose of this chapter is to provide the necessary instructions to successfully
install the Bulletin 193 Ethernet™/IP Communications Auxiliary and properly
connect it to an EtherNet/IP and DeviceNet™ network.
The Bulletin 193 EtherNet/IP Communications Auxiliary is an EtherNet/IP to
DeviceNet linking device. It provides a means for devices that primarily
communicate on a DeviceNet network (e.g., a Bulletin 193 or 592 E3 Plus
Overload Relay or a Bulletin 825-P Electronic Overload Relay) to communicate
to EtherNet/IP-based scanners. The EtherNet/IP Communications Auxiliary
allows up to six (6) DeviceNet-based devices to be scanned via Implicit Messaging
and can bridge explicit messaging for all nodes on a DeviceNet network. The
EtherNet/IP Communications Auxiliary uses an internal web server to configure
the module, the DeviceNet network, and DeviceNet-based devices that fully
support the Parameter Object.
SHOCK HAZARD: To prevent electrical shock, disconnect the EtherNet/
IP Communications Auxiliary from its power source before installing or
servicing. Install in suitable enclosure. Keep free from contaminants.
ATTENTION: The EtherNet/IP Communications Auxiliary contains ESD
(electrostatic discharge) sensitive parts and assemblies. Static control
precautions are required when installing, testing, servicing, or repairing
the EtherNet/IP Commuications Auxiliary. Component damage may result
if ESD control procedures are not followed. If you are not familiar with
static control procedures, refer to Rockwell Automation publication 8000-
4.5.2, “Guarding Against Electrostatic Damage”, or any other applicable
ESD protection handbook.
ATTENTION: The purpose of this document is to serve as a guide for
proper installation. The National Electrical Code (NEC) and any other
governing regional or local code will take precedence. Rockwell
Automation cannot assume responsibility for the compliance or proper
installation of the EtherNet/IP Communications Auxiliary or associated
equipment. A hazard of personal injury and/or equipment damage exists if
codes are ignored during installation.
Rockwell Automation Publication 193-UM014B-EN-P December 20117
Chapter 1
ATT ENTI ON: An incorrectly applied or installed EtherNet/IP
Communications Auxiliary can result in damage to the components or
reduction in product life. Wiring or application errors (e.g., supplying
incorrect or inadequate supply voltage or operating/storing in excessive
ambient temperatures) may result in malfunction of the product.
ATT ENTI ON: Only personnel familiar with the EtherNet/IP
Communications Auxiliary and associated machinery should plan to
install, set up, and maintain the system. Failure to comply may result in
personal injury and/or equipment damage.
ATT ENTI ON: This is a Class A product. In a domestic environment, this
product may cause radio interference in which case the user may be
required to take adequate measures.
ATT ENTI ON: To remain compliant with UL/CSA Certifications, the
DeviceNet power supply must meet NEC Class 2 Requirements.
8Rockwell Automation Publication 193-UM014B-EN-P December 2011
Chapter1
Features
Figure 1 - Features
Front View
Status
LEDs
Activity
LEDs
DeviceNet Network
DeviceNet Connector
Module
Ethernet/IP
Network
Front Port Link
Rear Port Link
Status LED
Side View
DIN
Rail Mounting
Top View
Ethernet Connectors
RJ-45
Rear View
Panel Mounting
Installation
Earth Ground Connector
The EtherNet/IP Communications Auxiliary may be DIN Rail or panel
mounted. To avoid overheating, the unit must be mounted vertically and
requires 37.4 mm (1-1/2 in.) of clearance at the top and bottom to allow proper
air flow. The temperature ratings for the unit will be derated if not mounted in
this manner.
Rockwell Automation Publication 193-UM014B-EN-P December 20119
Chapter 1
Front View
37.44 mm
(1-1/2 in.)
37.44 mm
(1-1/2 in.)
Figure 2 - Installation
Wiring
The EtherNet/IP Communications Auxiliary can accept all forms of DeviceNet
cable. However, DeviceNet shielded cable is recommended. The EtherNet/IP
Communications Auxiliary complies with the Open Device Vendors Association
(ODVA) DeviceNet compliance testing when the distance between end nodes is
100 m or less with 60 or fewer network drops.
Table 1 - Wire & Torque Specifications
WireTorque
1X
2X
1X
2X
1X
2X
24…12 AWG
24…16 AWG
5 lb.•in.
0.2…2.5 mm
0.25…1 mm
0.56 N•m
0.2…2.5 mm
0.2…1 mm
0.56 N•m
2
2
2
2
10Rockwell Automation Publication 193-UM014B-EN-P December 2011
Figure 3 - Wiring Diagram
5.85
(0.23)
105.0
(4.13)
100.5
(3.95)
98.0
(3.86)
110.0
(4.33)
Ø 4.50
(0.16)
87.0
(3.43)
31.3
(1.23)
Dimensions are shown in millimeters (inches).
DNET (Black)
24V -
CAN L (Blue)
Shield
CAN H (White)
DNET (Red)
24V +
Chapter1
Earth Ground
Dimensions
ATTENTION: Use a shielded DeviceNet cable to comply with CISPR 22
and CISPR 24.
Figure 4 - Dimension Diagram
Rockwell Automation Publication 193-UM014B-EN-P December 201111
Chapter 1
Network Design
The EtherNet/IP Communications Auxiliary is available as a single Ethernet port
(Cat. No. 193-DNENCAT) and dual Ethernet port (Cat. No.
193-DNENCATR) module that has RJ-45 ports to connect to Ethernet cable
CAT5 type or better . Rockwell Automation offers a wide variety of
Allen-Bradley Ethernet patch cables with its Bulletin 1585 line of Ethernet cables
(http://ab.rockwellautomation.com/Connection-Devices/RJ45-Network-
Media).
Both the 193-DNENCAT and 193-DNENCATR devices support a Star
Ethernet topology in which all Ethernet nodes wire back to a central Ethernet
switch, hub, or router as shown in Figure 5 on page 12
Figure 5 - Star Ethernet Topology
.
Rockwell Automation also offers a line of managed and unmanaged
Allen-Bradley Ethernet Switches with its Stratix™ family of Ethernet switches.
Refer to
The Cat. No. 193-DNENCATR Module also supports a Ring Ethernet topology
in which all Ethernet nodes are wired in series with one another until a complete
network ring is made as shown in Figure 6 on page 13
12Rockwell Automation Publication 193-UM014B-EN-P December 2011
.
Figure 6 - Ring Ethernet Topology
Chapter 1
The Cat. No. 193-DNENCATR Module supports Rockwell Automation’s
Device Level Ring (DLR) topology as a slave device in which the EtherNet/IP
network will still continue to communicate in the event that one of the network
chains is disrupted.
Rockwell Automation Publication 193-UM014B-EN-P December 201113
Chapter 1
14Rockwell Automation Publication 193-UM014B-EN-P December 2011
Chapter
2
Configure the EtherNet/IP Communications
Auxiliary
Introduction
Determining Network
Parameters
This chapter describes how to configure an EtherNet/IP Communications
Auxiliary to operate on an EtherNet/IP network.
When you first install an EtherNet/IP Communications Auxiliary, the module is
Dynamic Host Configuration Protocol (DHCP) enabled.
To operate an EtherNet/IP network, you must define these parameters.
Table 2 - EtherNet/IP Network Parameters
Network ParameterDescription
IP AddressThe IP address uniquely identifies the module. The IP address
is in the form xxx.xxx.xxx.xxx where each xxx is a number from
0...255. Do not use the following IP addresses, as these are
reserved values:
• 0.0.0.1...0.255.255.255
• 127.0.0.0...127.255.255.255
• 224.255.255.255...255.255.255.255
Subnet MaskSubnet addressing is an extension of the IP address scheme
that allows a site to use a single network ID for multiple
physical networks. Routing outside of the site continues by
dividing the IP address into a net ID and a host ID via the
class. Inside a site, the subnet mask is used to redivide the IP
address into a custom network ID portion and host ID portion.
NOTE: If you change the subnet mask of an alreadyconfigured module, you must cycle power to the module for
the change to take effect.
GatewayA gateway connects individual physical networks into a
system of networks. When a node needs to communicate
with a node on another network, a gateway transfers the data
between the two networks.
If DNS addressing is used or if the module is referenced via a host name in an
MSG instruction, the following parameters must be defined.
NOTE:Consult with your Ethernet network administrator to determine if these
parameters need to be specified.
Rockwell Automation Publication 193-UM014B-EN-P December 201115
Chapter 2
Table 3 - EtherNet/IP Network Parameters for DNS Addressing
Network ParameterDescription
Host NameA host name is part of a text address that identifies the
Domain NameA domain name is part of a text address that identifies the
Primary DNS Server AddressThis identifies any DNS servers used in the network. You must
Secondary DNS Server Address
module. The full text address of a module is:
host_name.domain_name.
domain in which the module resides. The full text address of a
module is: host_name.domain_name. The domain name has a
48-character limit.
have a DNS server configured if you specify an SMTP server
with a name. The DNS server converts the domain name or
host name to an IP address that can be used by the network.
For more information on DNS addressing, refer to page 23.
Setting the IP Network
Address
An EtherNet/IP Communications Auxiliary ships with DHCP enabled. You can
set the network Internet Protocol (IP) address by using:
• the EtherNet/IP node address selection switches,
• a Bootstrap Protocol (BOOTP)/Dynamic Host Configuration Protocol
(DHCP) server (e.g., the Rockwell Automation BOOTP-DHCP Server
Utility, which is included with Rockwell Software’s RSLinx™ Classic
software), OR
• a web browser and MAC scanner software.
EtherNet/IP Node Address Selection Switches
The EtherNet/IP Communications Auxiliary comes with three node address
selection switches that allow the user to select the last octet for the IP address
192.168.1.xxx.
16Rockwell Automation Publication 193-UM014B-EN-P December 2011
Figure 7 - Last Octet Selection
EXAMPLE
IMPORTANT
When the top dial is set to 1, the middle dial is set to 2, and the bottom
dial is set to 3, the resulting IP address is: 192.168.1.123.
Chapter2
x 100 Digit
x 10 Digit
x 1 Digit
Assign Network
Parameters via the BOOTP/
DHCP Utility
When the node address selection switches are set to a value greater than 255, the
IP address is set to DHCP Enabled or programmed for a static IP address.
By default, the EtherNet/IP Communications Auxiliary is DHCP Enabled. The
BOOTP/DHCP utility is a standalone program that is located in the BOOTPDHCP Server folder accessed from the Start menu.
Beforestarting the BOOTP/DHCP utility: Make sure you have the
hardware MAC ID of the module, which is printed on the front of the
EtherNet/IP Communications Auxiliary. The MAC ID has a format
similar to: 00-0b-db-14-55-35.
This utility recognizes DHCP-enabled devices and provides an interface to
configure a static IP address for each device.
To assign network parameters via the BOOTP/DHCP utility, perform this
procedure:
1. Execute the BOOTP/DHCP software.
2. Choose Tool >Network Settings.
Rockwell Automation Publication 193-UM014B-EN-P December 201117
Chapter 2
3. If appropriate for the network, type the subnet mask, gateway address,
primary/secondary server addresses, and domain name in their respective
fields.
4. Click OK.
The Request History panel displays the hardware addresses of modules
issuing BOOTP or DHCP requests.
5. Double-click the MAC address of the module to be configured.
NOTE: The MAC address is printed on the front of the EtherNet/IP Communications
Auxiliary. The format of the hardware address resembles:
00-0b-db-14-55-35
18Rockwell Automation Publication 193-UM014B-EN-P December 2011
The New Entry window appears with the module’s Ethernet Address
(MAC).
6. Type the IP address, host name, and a module description.
7. Click OK.
Chapter 2
Assign Network
Parameters Via a Web
Browser & MAC Scanner
Software
8. Cycle power to the module by removing and reapplying the DeviceNet
connector.
9. To permanently assign this configuration to the module: Select the module
in the Relation List panel and click Disable BOOTP/DHCP.
When module power is cycled, it uses the assigned configuration and does
not issue a DHCP request.
If you do not click Disable BOOTP/DHCP, on a power cycle, the module
clears the current IP configuration and will again begin sending DHCP
requests.
In the event that a user does not have access to a DHCP software utility, a user
can assign network parameters via a web browser (e.g., Microsoft® Internet
Explorer) and Media Access Control (MAC) scanner software (e.g., MAC
Scanner from Colasoft® - http://www.colasoft.com/
configure the module using this method.
1. Locate and identify the MAC ID printed on the label of the EtherNet/IP
Communications Auxiliary. This address has a format that is similar to:
00-0b-db-14-55-35
). Follow these steps to
2. Connect the EtherNet/IP Communications Auxiliary to the same wide
area network (WAN) as your personal computer.
3. Initiate the MAC scanner software.
Rockwell Automation Publication 193-UM014B-EN-P December 201119
Chapter 2
4. Select the appropriate subnet to scan for available MAC addresses.
5. Scan the Subnet for all available MAC addresses.
6. Identify the IP address assigned to the MAC ID of the EtherNet/IP
Communications Auxiliary. The IP address will have a format that is
similar to 192.168.0.100.
7. Open a web browser and type the IP address on the address line to view the
internal web server of the EtherNet/IP Communications Auxiliary.
8. Select Administration Settings>Network Configuration to change the IP
address of the EtherNet/IP Communications Auxiliary to a static IP
address.
20Rockwell Automation Publication 193-UM014B-EN-P December 2011
Chapter2
9. The module will prompt the user for a User Name and Password. Type
“Administrator” as the user name, leave the password field blank, then click
OK.
10. Assign the appropriate network settings per the recommendation of the
network administrator for the network that this module will be
communicating on and click Apply.
11. Remove and reapply the DeviceNet connector to allow the
communications changes to take affect.
Rockwell Automation Publication 193-UM014B-EN-P December 201121
Chapter 2
Other Factors to Consider When Assigning Network Parameters
There are other factors to consider when assigning networks parameters, which
include the:
• network isolation from or integration into the plant/enterprise network.
• network size.
For large networks, even isolated networks, it might be more convenient
and safer to use a BOOTP/DHCP server rather than RSLinx software.
The BOOTP/DHCP server also limits the possibility of assigning
duplicate IP addresses.
• company policies and procedures associated with plant floor network
installation and maintenance.
• level of involvement by information technology personnel in plant floor
network installation and maintenance.
• type of training offered to control engineers and maintenance personnel.
If the Rockwell Automation BOOTP or DHCP server is used in an uplinked
subnet where an enterprise DHCP server exists, a module may get an address
from the enterprise server before the Rockwell Automation utility even sees the
module. In this case, disconnect the uplink to set the address and configure the
module to retain its static address before reconnecting to the uplink. This is not a
problem if you have node names configured in the module and leave DHCP
enabled.
ATT ENTI ON: The EtherNet/IP Communications Auxiliary must be
assigned a fixed network address. The IP address of this module must not
be dynamically provided. Failure to observe this precaution may result in
unintended machine motion or loss of process control.
Duplicate IP Address
Detection
When you change the IP address or connect the module to an EtherNet/IP
network, the module checks to make sure that the IP address assigned to this
module does not match the address of any other network device. If the module
determines that another device on the network with a matching IP address, the
EtherNet/IP port of the module goes into conflict mode where the Network
Status LED indicator is solid red.
To resolve this conflict, use the instructions below to change the IP address of the
module. Then, cycle power to the module or reset the modules by disconnecting
and then reconnecting the Ethernet cable.
Two modules could possibly detect a conflict simultaneously. If this occurs,
perform this procedure.
1. Remove the module with the incorrect IP address and correct its conflict.
2. Cycle power or disconnect the Ethernet cable from the second module and
reconnect it.
22Rockwell Automation Publication 193-UM014B-EN-P December 2011
Chapter2
Behavior of Modules With Duplicate IP Addresses
Devices in conflict over an IP address behave differently depending on whether
connections have been established to either of the modules and whether both
modules support duplicate IP address detection.
Table 4 - Device Conflict over Duplicate IP Addresses
Ifthen
both modules support duplicate IP
address detection,
both modules support duplicate IP
address detection and are started at
roughly the same time,
one module supports duplicate IP address
detection and a second module does not,
the first started module uses and retains its IP address.
The other module will detect a conflict, give up the IP
address and enter conflict mode.
one of the modules surrenders the IP address and enters
conflict mode.
the second module generally keeps its IP address,
regardless of which module first obtains the IP address.
The module that supports duplicate IP address detection
will detect the conflict and give up the IP address.
DNS Addressing
To further qualify a module’s address, use DNS addressing to specify a host name
for a module, which also includes specifying a domain name and DNS servers.
DNS addressing makes it possible to set up similar network structures and IP
address sequences under different domains.
DNS addressing is only necessary if you refer to the module by host name, such as
in path descriptions in MSG instructions.
To use DNS addressing, perform this procedure.
Electronic Data Sheet (EDS)
File Installation
Before the EtherNet/IP Communications Auxiliary is configured to
communicate on an EtherNet/IP network, it must be registered to the software
that configures the network (e.g., Rockwell Automation RSLinx Classic and
RSNetWorx for EtherNet/IP software). A user registers the module by installing
an EDS file. The EDS file for the EtherNet/IP Communications Auxiliary can
be obtained from one of two locations:
1. Assign a host name to the module.
NOTE: Contact the network administrator ro have a host name assigned. Valid host
names should be IEC-1131-3 compliant.
2. Configure the module's parameters.
3. In addition to the IP address, subnet mask, and gateway address, configure
a host name for the module, domain name, and primary/secondary DNS
server addresses.
Rockwell Automation Publication 193-UM014B-EN-P December 201123
Chapter 2
• embedded in the module OR
• the Allen-Bradley EDS file download website.
Download the EDS File
Embedded in the Module
The EDS file for the EtherNet/IP Communications Auxiliary is embedded
within the module. After the IP address for the module has been configured,
connect the module to same Ethernet network as a personal computer. Using a
web browser on the personal computer, a user can download the EDS file using a
web browser by following these steps:
1. Type the IP address of the EtherNet/IP Communications Auxiliary on the
address line of the web browser.
2. Select EDS File link
3. Click Save to save the EDS file to the personal computer.
24Rockwell Automation Publication 193-UM014B-EN-P December 2011
Chapter2
From the EDS File Download Site
The EDS file for the EtherNet/IP Communications Auxiliary can also be
downloaded from the Allen-Bradley EDS File download site. Using a web
browser on the personal computer that is connected to the internet, a user can
download the EDS file by following these steps:
1. Ty p e http://www.ab.com/networks/eds
browser.
2. Select EtherNet/IP as the network type, then click Search.
3. Locate the EDS file for the EtherNet/IP Communications Auxiliary and
download it to the personal computer.
on the address line of the web
Register the EDS File
After the EDS file has been downloaded, a user will need to register the EDS file
with the software that configures the EtherNet/IP network. The following
example lists the steps needed to register an EDS file with Rockwell Automation’s
RSLinx Classic software.
Rockwell Automation Publication 193-UM014B-EN-P December 201125
Chapter 2
1. Start the EDS Hardware Installation Tool located at Start>Programs>
Rockwell Software>RSLinx Tools.
2. Click Add to register a new device.
3. Click the “Register a single file” radio button, then browse to the location
where the EDS file is located. Click Next.
26Rockwell Automation Publication 193-UM014B-EN-P December 2011
4. Click Next to accept the installation test results.
Chapter2
Rockwell Automation Publication 193-UM014B-EN-P December 201127
Chapter 2
5. Click Next to accept the graphic image.
6. Click Next to register the device.
28Rockwell Automation Publication 193-UM014B-EN-P December 2011
7. Click Finish to successfully register the module.
Chapter2
Rockwell Automation Publication 193-UM014B-EN-P December 201129
Chapter 2
30Rockwell Automation Publication 193-UM014B-EN-P December 2011
Configure the DeviceNet Network
Chapter
3
Introduction
Configuration
The purpose of this chapter is to assist in configuring the DeviceNet Network
with the EtherNet/IP Communications Auxiliary. A DeviceNet network can be
configured using the internal web interface from the EtherNet/IP
Communications Auxiliary.
1. From the web page, navigate to Scan List>Configuration>Advanced.
2. If desired, change the baud rate using the DeviceNet Baud Rate pull-down
menu. The default value of 125K for the DeviceNet network.
NOTE: Autobaud is not supported with this product.
Rockwell Automation Publication 193-UM014B-EN-P December 201131
Chapter 3
3. Type the size of the Scan List I/O Entry in the field.
The entry size determines the number of input and output bytes that the
EtherNet/IP Communications Auxiliary will scan from each of the
scanned devices. The maximum Scan List I/O Entry Size supported is 50
bytes with the default value being 8 bytes.
NOTE: Auto Device Replacement (ADR) is discussed in Chapter 6, Automatic Device
Recovery or Replace.
4. If necessary, adjust DNet IO Request Packet Interval (RPI) and DNet IO
Inhibit.
DNet IO RPI determines the time it takes for data to be requested; DNet
IO Inhibit is the time used on DeviceNet Change of State (COS) I/O.
Both of these parameters are measured in milliseconds.
NOTE: Electronic keying is implemented on all scan list entries. Electronic keys are
captured when a scan list is configured form the EtherNet/IP Communications
Auxiliary webpage. The proper setting of the electronic keying becomes more
important with ADR functions and replacing units in the network.
5. Navigate to Scan List>Configuration>Scan List to change the DeviceNet
node address of the EtherNet/IP Communcations Auxiliary.
32Rockwell Automation Publication 193-UM014B-EN-P December 2011
Chapter3
6. Change the DeviceNet network address to the appropriate node address,
then click Save.
NOTE: Typically, DeviceNet scanners have the node address of 0.
7. Click OK to finish changing the scanner DeviceNet network address.
Rockwell Automation Publication 193-UM014B-EN-P December 201133
Chapter 3
34Rockwell Automation Publication 193-UM014B-EN-P December 2011
Chapter
Add Devices to the DeviceNet Network
4
Introduction
DeviceNet Node
Addressing
In this chapter, you will be able to assign an address to each DeviceNet module
and configure the DeviceNet scanner to scan up to six modules.
Each module being added to the DeviceNet network must have a unique network
mode address. A unique network node address can be created by using hardware
devices (e.g., DIP and Selector Switches) or by the Node Commissioning tool
from the internal web interface of the EtherNet/IP Communications Auxiliary.
The following chart shows the recommended node addresses.
Table 5 - Recommended Node Addresses
Assign this
Device:
Scanner0• For multiple scanners, assign the lowest addresses in
Any Device on the
Network
(except the scanner)
Computer Interface
to the Network
New DeviceNet
Module
This
Node Address: Notes:
sequence (0, 1...).
1...61• Give the lower addresses to devices with 15 bytes or
more of input or output data.
• Gaps between addresses are acceptable and have no
effect on system performance. If the final layout of the
system is not certain at this time, leave gaps between
addresses to allow flexibility as the system is
developed.
62• If a computer is connected directly to the DeviceNet
network, use address 62 for the computer. The reason
for this is that many computer interface devices use 63
as the default address.
• The 1784-U2DN device can connect a computer directly
to a DeviceNet network.
63• To avoid conflict, always leave address 63 open. This is
due to the following:
– most DeviceNet devices have a factory preset
address of 63.
– leaving address 63 open allows for configuration of a
new device.
– the auto-address recovery feature requires address
63 to be open.
• Some devices do not have switches or push buttons to
set the address. Therefore, the device must first be
connected to the network then software (e.g.,
RSNetworx for DeviceNet) must be used to change the
address.
• If another device is already using address 63, an address
conflict will occur and communication will not occur
with the newly connected device.
Rockwell Automation Publication 193-UM014B-EN-P December 201135
Chapter 4
IMPORTANT
IMPORTANT
Node Address Basics
• Verify the node address assigned to the new device.
• Prevent duplicate node address assignments.
– When connecting new DeviceNet modules with the Node
Commissioning tool from the EtherNet/IP Communications Auxiliary
web interface, place one new DeviceNet module on the network at a
time. Refer to “New DeviceNet Module” in Tab le 5 on pag e 35
– If DIP or selector switches on hardware will be used, set the network
node address for the device before connecting it to the network.
• Leave node address 63 open.
For more information about setting the node address for DeviceNet devices, refer
to the Rockwell Automation Literature Library at:
www.rockwellautomation.com/literature
.
Set the Node Address
Using the Hardware Mechanism
Many DeviceNet devices feature a hardware mechanism to set the network node
address (e.g., a rotary switch or a push wheel switch). Use the following procedure
to set the node address.
Ensure each device’s node address set by the hardware mechanism
matches the node address used in the DeviceNet network. Note that if
the network node address is set higher than 63, the Ethernet /IP
Communications Auxiliary Node Commissioning tool can be used instead
of the hardware mechanism.
In order for the node address change to take effect, cycle the module’s
power.
1. Usi ng Tab le 5 o n pa ge 3 5
new device.
as a guide, select a node address to apply to the
36Rockwell Automation Publication 193-UM014B-EN-P December 2011
Chapter4
2. Change the node address using the appropriate mechanism for the new
device.
MechanismProcedure
Rotary SwitchTurn the rotary switch dials to the desired node address value.
2
0
PGM
MSD
Push Wheel Switch
2
4
0
8
6
LSD
Usually, a small, flathead screwdriver is needed to turn the dials.
4
Once the device is powered up, the rotary switch settings are
recognized. If the set node address value needs to be changed,
6
power down the device, turn the dials to the desired setting, then
power up the device again.
Turn the push wheel to the desired node address value.
Using the DeviceNet Node Commissioning Tool
A device’s network node address can be set using the Node Commissioning Tool
on the EtherNet/IP Communications Auxiliary web page. This tool uses the
Network Who to view the DeviceNet modules on the network.
Refer to the following guidelines when using the Network Commissioning tool.
• Only use this tool with an online DeviceNet network.
• Only use this tool when adding new devices to the network if :
– the new device does not feature a hardware mechanism to set the node
address or
– the new device’s node address is set higher than 63.
NOTE: If the new device features a hardware mechanism and the node address
is set at 63 or lower, the Network Commissioning tool does not change
the device’s node address.
• Each time a new device is added to the DeviceNet network, the procedures
beginning on page 38
• To avoid conflict with duplicate node addresses, due largely in part to
modules having a factory node setting of 63, configure a module to the
online DeviceNet network one a time.
• Record the node address for each device that is set by the Node
Commissioning Tool.
must be performed.
Complete the following steps to set a device’s node address using the Node
Commissioning Tool on the EtherNet/IP Communications Auxiliary web page.
Rockwell Automation Publication 193-UM014B-EN-P December 201137
Chapter 4
1. From the EtherNet/IP Communications Auxiliary web page, navigate to
Scan List>Configuration>Node Commissioning.
2. Select the device where node address needs to be assigned. Once selected,
the Current Settings aand New Settings areas are populated.
3. Double-click the “Node address” field’s value. The value will be
highlighted in blue.
38Rockwell Automation Publication 193-UM014B-EN-P December 2011
Chapter4
4. Using the keypad on the PC keyboard, change the network node address
to the desired value. Ensure the desired value is not duplicating any other
device’s node address, then click the Apply button.
5. The following window will appear confirming a successful node address
value change. Click OK.
6. Verify the node address was changed to the desired value in the “New
settings” section of the page. Note that the “Current settings” area will still
display the old node address unitl the device is selected again from the
Network Who list.
7. Repeat steps 1 through 6 until all new or additional devices are added to
the DeviceNetwork.
Rockwell Automation Publication 193-UM014B-EN-P December 201139
Chapter 4
Add DeviceNet Modules to
the Scan List
After each DeviceNet device has been assigned a unique node address, up to six
DeviceNet devices can be added to the EtherNnet/IP Communications Auxiliary
DeviceNet scan list. The EtherNet/IP Communications Auxiliary provide two
methods to configure the scan list, Simple and User-Defined.
Simple
1. From the EtherNet/IP Communications Auxiliary web page, navigate to
Scan List>Configuration>Scan List. The EtherNet/IP Communications
Auxiliary will read the available DeviceNet modules on the DeviceNet
network.
2. Click Config. The lowest six DeviceNet node addresses will populate into
the Scan List field on the right.
40Rockwell Automation Publication 193-UM014B-EN-P December 2011
Chapter4
3. Click OK to complete the configuration.
The DeviceNet scanner on the EtherNet/IP Communications Auxiliary
will begin scanning the DeviceNet devices.
User-Defined
If there are more than six DeviceNet devices on the network, the user can select
up to six DeviceNet devices to scan. Follow the steps below to select specific
DeviceNet devices for the scan list.
1. From the EtherNet/IP Communications Auxiliary web page, navigate to
Scan List>Configuration>Scan List. The EtherNet/IP Communications
Auxiliary will read the available DeviceNet modules on the DeviceNet
network.
2. Select the DeviceNet device in the Network Who screen to be added to
the Scan List. The >> button becomes highlighted.
Rockwell Automation Publication 193-UM014B-EN-P December 201141
Chapter 4
3. Click >> to move the selected device into the Scan List.
4. Repeat steps 2 and 3 to add five additional DeviceNet devices.
5. Click Save at the bottom right of the screen.
6. Click OK to complete the scan list configuration.
42Rockwell Automation Publication 193-UM014B-EN-P December 2011
View & Configure Parameters
Chapter
5
Introduction
View & Edit
In this chapter, you will be able to view and configure parameters for a DeviceNet
device that supports the full implementation of the Parameter Object.
The EtherNet/IP Commuications Auxiliary is able to view and configure
parameters for a DeviceNet device that supports the full implementation of the
Parameter Object. Users can use the web interface to view and edit parameters for
a DeviceNet Module in the scan list.
Follow the steps below to view and edit parameters using the web interface of the
EtherNet/IP Commuications Auxiliary.
1. Navigate to Scan List>Configuration, then select the DeviceNet device
folder to view or edit its parameters. The selected DeviceNet device folder
will expand.
Rockwell Automation Publication 193-UM014B-EN-P December 201143
Chapter 5
2. Click on the Identity folder. The Identity tab will appear, providing
information about the selected device.
3. Click on the Parameter folder. Subfields for this folder will appear.
44Rockwell Automation Publication 193-UM014B-EN-P December 2011
Chapter5
TIP
4. Select a parameter group. A list of up to 15 parameters will be displayed. If
more than 15 parameters are available, select the page number or use the
navigation arrows to view the additional parameter screens.
To increase the update rate of the data being displayed on the
screen, lower the value in the “Seconds before refresh:” field.
5. Select a parameter group that contains programmable parameters, then
click the Edit button. The value options will appear.
Rockwell Automation Publication 193-UM014B-EN-P December 201145
Chapter 5
6. Click the down arrow on the pull-down boxes to adjust fixed values and/or
enter numerical values in the fields without an arrow to adjust the values.
7. Click Apply once all parameter edits have been completed. The EtherNet/
IP Communications Auxiliary will download the new parameter values to
the device. A confirmation window will appear.
8. Click OK.
9. Continue editing the remaining parameters, if desired.
NOTE:
46Rockwell Automation Publication 193-UM014B-EN-P December 2011
If a DeviceNet module does not support the parameter object, the following
window will appear:
Chapter
IMPORTANT
Automatic Device Recovery or Replace
6
Introduction
Setting ADR
In this chapter, using the Automatic Device Recovery or Replace (ADR) will be
explained. The use of this feature reduces downtime if a device needs to be
replaced.
With ADR, there is no need for software tools to get a replacement device
configured and online. The EtherNet/IP Communications Auxiliary
automatically configures the replacement device if the device was listed in the
scan list and the appropriate electronic keying was selected.
Not all DeviceNet devices support ADR.
1. Navigate to Scan List>Configuration>Advanced.
2. Select the appropriate electronic keying for your DeviceNet network
application.
Rockwell Automation Publication 193-UM014B-EN-P December 201147
Chapter 6
By default, the Device Type, Vendor, and Product Code will be enabled.
Electronic keying will define how closely a replacement device must match
a failed device before the EtherNet/IP Auxiliary reconfigures a module. If
the new module does not match the criteria of one of the checked boxes,
the ADR will not function and an ADR error will appear.
3. Once the scan list and DeviceNet module programmable parameters have
been configured, click Upload ADR Data.
The EtherNet/IP Communications Auxiliary will upload and store the
configuration data from the modules in the scan list and a confirmation
message will appear,
4. Select Enable from the Auto Device Replace pull-down menu. This will
enable the ADR.
48Rockwell Automation Publication 193-UM014B-EN-P December 2011
Chapter6
5. Click Save, then cycle power on the EtherNet/IP Communications
Auxiliary.
An ADR download is performed immediately before an I/O connection is
allocated by the DeviceNet master.
If the download is unsuccessful, an “ADR Error” for the appropriate node
will be reported in the corresponding “Scan List Entry Status Word”. If the
electronic keys for the device at a given node address do not match the
saved electronic keys, no ADR download will take place, an I/O
connection will not be allocated, and a “Keying Mismatch” will be
reported in the corresponding “Scan List Entry Status Word”.
A warning list will appear after enabling the ADR and a change has been
made to the scan list.
AAR (Auto Address Recovery) is also supported by the EtherNet/IP
Communications Auxiliary. When the EtherNet/IP Communications Auxiliary
detects a node is missing from the scan list and a module matching the electonic
Rockwell Automation Publication 193-UM014B-EN-P December 201149
Chapter 6
key is detected on node 63, the EtherNet/IP Communications Auxiliary will
attempt to change the module’s network node address to that of the missing scan
list node number. When successful, the EtherNet/IP Communications Auxiliary
will download the ADR information to the module.
50Rockwell Automation Publication 193-UM014B-EN-P December 2011
Chapter
Automation Controller Communications
7
Introduction
Ethernet Messaging
I/O Messaging
This chapter describes and gives examples of how each type of EtherNet/IP
messaging, I/O messaging and Explicit messaging, is used.
The EtherNet/IP Communications Auxiliary supports two types of EtherNet/IP
messaging.
• I/O Messaging — Used for deterministic EtherNet/IP communications
with ControlLogix™, CompactLogix™, SoftLogix™, and EtherNet/IP
scanners. Its primary use is to read and write I/O data for control purposes.
• Logic Explicit Messaging — Used for non-deterministic communications
in which the data is not critical for control. Logic explicit messages have a
lower priority compared to I/O messages and are used to read and write
non-critical data.
RS Logix 5000™ software is used to configure I/O messaging between an
automation controller and an EtherNet/IP Communications Auxiliary on an
EtherNet/IP network.
The following example provides the steps necessary to configure a Logix
controller for I/O messaging.
ControlLogix Configuration with Add-On Profiles
An Add-On Profile is available for the EtherNet/IP Communications Auxiliary
and can be used with RSLogix 5000 version 17 and higher. The profile can be
downloaded from:
An existing project can be used or a new project can be created to configure
EtherNet/IP I/O Messaging. To create a new project, perform the following
steps.
Rockwell Automation Publication 193-UM014B-EN-P December 201151
Chapter 7
1. Select File>New from the RSLogix 5000.
2. Select the controller type, chassis type, slot number, and project path.
Then, enter a name for the controller and click OK.
3. Right-click the I/O Configuration folder, then select New Module. The
Select Module Type window will appear.
52Rockwell Automation Publication 193-UM014B-EN-P December 2011
4. Select the desired EtherNet/IP scanner module, then click OK.
Chapter7
5. Enter the desired communication settings, then click Finish.
EtherNet/IP Network Configuration with Add-On Profiles
After the controller configuration, the EtherNet/IP Communications Auxiliary
has to be added to the I/O configuration.
Rockwell Automation Publication 193-UM014B-EN-P December 201153
Chapter 7
1. Place the program in offline mode.
2. Right-click on the EtherNet/IP scanner within the I/O Configuration
folder, then select New Module to open the Select Module Type window.
3. Select the appropriate device (either 193-DNENCAT or 193DNENECATR, then click OK.
54Rockwell Automation Publication 193-UM014B-EN-P December 2011
Chapter7
4. Enter a name for the EtherNet/IP Communications Auxiliary. The name
will create tags in RSLogix 5000 that can be used to read and write data
from DeviceNet modules being scanned by the EtherNet/IP
Communications Auxiliary.
5. Enter the IP address of the EtherNet/IP Communications Auxiliary.
6. Select Change to select a motor protection device with predefined tag
names for Data Mapping. For non-motor protection devices, select
Generic.
NOTE: Predefined tag names exist for the E3 Plus EC1, EC2, EC3, EC4, and EC-5
models and the 825-P Overload Relay.
7. Select the appropriate data format, then click OK.
Rockwell Automation Publication 193-UM014B-EN-P December 201155
Chapter 7
8. Click OK at the next window to have RSLogix 5000 create the predefined
tags. The EtherNet/IP Communications Auxiliary will now show as a
module in the I/O Configuration folder.
Accessing Module Data with Add-On Profiles
With both the Logix controller and EtherNet/IP network configured, the Logix
controller can exchange data with the EtherNet/IP Communication Auxiliary.
1. Open the Controller Tags window.
2. Select the Monitor Tags tab.
In the above example, the predefined input and output tags were generated for
each of the six scanned devices. To control the output relays for the scanned
device, use the output tags. For diagnostic informaton from the device, use the
input tags.
56Rockwell Automation Publication 193-UM014B-EN-P December 2011
Chapter7
ControlLogix Generic Configuration
An existing project can be used or a new project can be created to configure
EtherNet/IP I/O Messaging. To create a new project, perform the following
steps.
1. Select File>New from the RSLogix 5000.
2. Select the controller type, chassis type, slot number, and project path.
Then, enter a name for the controller and click OK.
3. Right-click the I/O Configuration folder, then select New Module. The
Select Module Type window will appear.
Rockwell Automation Publication 193-UM014B-EN-P December 201157
Chapter 7
4. Select the desired EtherNet/IP scanner module, then click OK.
5. Enter the desired communication settings, then click Finish.
EtherNet/IP Generic Module Configuration
Once the Logix controller has been configured, the EtherNet/IP
Communications Auxiliary must be added to the I/O configuration.
58Rockwell Automation Publication 193-UM014B-EN-P December 2011
Chapter7
1. Place the program in offline mode.
2. Right-click on the EtherNet/IP scanner within the I/O Configuration
folder, then select New Module to open the Select Module Type window.
3. Select Generic Ethernet Module, then click OK.
Rockwell Automation Publication 193-UM014B-EN-P December 201159
Chapter 7
4. Enter a name for the EtherNet/IP Communications Auxiliary. The name
will create a tag in RSLogix 5000 that can be used to read and write data
from the devices being scanned by the EtherNet/IP Communication
Auxiliary.
5. Select Data-INT for the Comm Format. The Data-INT format wil l
represent the data from the EtherNet/IP Communications Auxiliary as a
field of 16-bit values.
6. Set the Connection Parameters. I/O data is accessed using Input Instance
101 and Output Instance 100. The size of the input connection and the
output connection shall correspond to the size of the chosen instance. The
configuration assembly instance is 102.
NOTE: In this example, configuration data is not used. Thus, the data size is set to 0
60Rockwell Automation Publication 193-UM014B-EN-P December 2011
Chapter 7
7. Type the IP address of the EtherNet/IP Communications Auxiliary.
8. Type the value for the time between each scan of the module. The
recommended RPI time is 250 ms. Ensure that the Inhibit Module is not
checked.
9. Click OK to add the EtherNet/IP Communications Auxiliary to the I/O
Configuration in RSLogix 5000.
Accessing Generic Module Data
With both the ControlLogix controller and the EtherNet/IP network
configured, the ControlLogix controller can exchange data with the EtherNet/IP
Communications Auxiliary.
1. Go online, then switch the controller to Remote Run mode.
Rockwell Automation Publication 193-UM014B-EN-P December 201161
Chapter 7
2. Open the Controller Tags window.
3. Select the Monitor Tags tab.
An array of input and output tags were generated for each of the six scanned
devices. To control the output relays for the scanned device, use the output tags;
to obtain diagnostic information from the scanned device, use the input tags.
The format of output data is shown in the table to follow.
Table 6 - Output Assembly — Instance 100
Byte SizeContents
Scan List I/O Size Data to be delivered to the first scan list entry.
Scan List I/O Size Data to be delivered to the second scan list entry.
Scan List I/O Size Data to be delivered to the third scan list entry.
Scan List I/O Size Data to be delivered to the fourth scan list entry.
Scan List I/O Size Data to be delivered to the fifthscan list entry.
Scan List I/O Size Data to be delivered to the sixth scan list entry.
The format of the input data is shown in the table to follow.
Table 7 - Input Assembly — Instance 101
Byte SizeContents
4 bytesLogix Status Word
2 bytesDeviceNet Scanner Status (Parameter 1) See Table 9 on page 73
2 bytesScan List Entry 1 Status Word (Parameter 2) See Table 10 on page 74
2 bytesScan List Entry 2 Status Word (Parameter 3) See Table 11 on page 74
2 bytesScan List Entry 3 Status Word (Parameter 4) See Table 12 on page 74
2 bytesScan List Entry 4 Status Word (Parameter 5) See Table 13 on page 75
2 bytesScan List Entry 5 Status Word (Parameter 6) See Table 14 on page 75
2 bytesScan List Entry 6 Status Word (Parameter 7) See Table 15 on page 75
Scan List I/O Size Produced I/O data from the first scan list entry.
Scan List I/O Size Produced I/O data from the second scan list entry.
Scan List I/O Size Produced I/O data from the third scan list entry.
62Rockwell Automation Publication 193-UM014B-EN-P December 2011
Byte SizeContents
Scan List I/O Size Produced I/O data from the fourth scan list entry.
Scan List I/O Size Produced I/O data from the fifth scan list entry.
Scan List I/O Size Produced I/O data from the sixth scan list entry.
2 bytesData Link 1 Data
2 bytesData Link 2 Data
2 bytes
: :
2 bytesData Link 48 Data
Data Link 3 Data
: :
Chapter7
Logic Explicit Messaging
CompactLogix, ControlLogix, and SoftLogix controllers can read and write
specific information to and from DeviceNet modules on the same DeviceNet
network through the EtherNet/IP Communications Auxiliary using Explicit
Messaging.
The following steps configure a ControlLogix explicit message using the MSG
instruction to read diagnostic parameters from an E3 Plus Model and EC5
Overload Relay.
1. In an interger array named MSG_Read_Request, define the number of
attributes to read and list the specific attribute numbers.
The MSG instruction will return in an integer array with the first integer
representing the following information:
• number of attributes
• first attribute number being returned
• first attribute number data status
• first attribute data…
• last attribute number being returned
• last attribute number data status
• last attribute data
Rockwell Automation Publication 193-UM014B-EN-P December 201163
Chapter 7
In the screen capture below, the user-defined structure listing the integers is
being returned in this example.
64Rockwell Automation Publication 193-UM014B-EN-P December 2011
Chapter7
2. Set up the MSG instruction in the Configuration tab to read the list of
attributes (Parameters Group) by configuring the following fields:
• Message Type: CIP Generic
• Service Type: Custom
• Service Code: 0x03 (hex)
• Class: 0x375 (hex)
• Instance: 1 (dec)
• Attribute: 0x00 (hex)
• Source Element: MSG_Read_Request [0]
• Source Length: 14 (bytes)
• Destination: MSG_Read_Data
3. Set up the communications path in the Communications tab to read the
data from the E3 Plus Overload Relay located at Node 6 by configuring the
communication path as “MotorStarter, 3, 6”.
NOTE: Motor Starter — the name of the EtherNet/IP Communications Auxiliary
3 — the port number of the DeviceNet Scanner of the EtherNet/IP
Communications Auxiliary.
6 — the node address of the E3 Plus Overload Relay.
Rockwell Automation Publication 193-UM014B-EN-P December 201165
Chapter 7
4. Click OK. When finished, the MSG instruction will read the 25
parameters from the E3 Overload Relay and place the results into
MSG_Read_Data as shown below.
66Rockwell Automation Publication 193-UM014B-EN-P December 2011
E-mail/Text
Chapter
8
Introduction
E-mail Notifications
This chapter describes e-mail notifications and how to configure an EtherNet/IP
Communications Auxiliary to send e-mail messages and text notifications for
different communication events.
Events
Several communication events can trigger e-mail notifications. These events are
fault conditions for the DeviceNet scan list and EtherNet/IP Communications
Auxiliary.
Fault Conditions for the DeviceNet Scan List
Minor RecoverableMajor UnrecoverableWrong Data Size Slave Init Error
Minor UnrecoverableConnection TimeoutNo Such DeviceI/O Data Overflow
Major RecoverableKeying MismatchFrag/Idle ErrorAutomatic Device
Replacement Error
Acknowledge Timeout
Fault Conditions for the EtherNet/IP Communications Auxiliary
On LineGlobal ADR ErrorIn Idle ModeDuplicate Mac Error
Illegal Scan List DataNo Scanner Messages Hardware ErrorData Link Error
No Network Messages Transmit FailureBus Off ErrorNon Volatile Storage Error
E-mail Contents
The subject and body contents in the e-mail message wil be created from the:
• type of trip or warning that is detected,
• device name,
• device description,
• device location, and
• contact information.
Rockwell Automation Publication 193-UM014B-EN-P December 201167
Chapter 8
EXAMPLE
E-mail Subject:
193-DNENCATR Comms Aux has detected a fault
E-mail Body:
Fault Status:
Device Name: 193-DNENCATR Comms Aux
Device Description: Motor Starters
Device Location: Bay 6-U29
Contact Info: Contact Person contactperson@thecontact.com
The first word in the e-mail subject is the device name. If a device name is not
configured, then the product name attribute from the identity object will be used.
E-mail Configuration
To be able to send an e-mail, the IP address ot the hostname of a Simple Mail
Transfer Protocol (SMTP) server must be configured and notifications must be
selected. Follow these steps to configure an e-mail notification.
1. In the web browser, type the IP address of the EtherNet/IP
Communications Auxiliary in the address bar, then press the enter key on
the keyboard.
2. Select Administrative Settings E-Mail Configuration. A login window will
appear.
68Rockwell Automation Publication 193-UM014B-EN-P December 2011
Chapter8
3. Log in with the username “Adminstrator”, leave the password field blank,
and click OK.
NOTE: If desired, a password can be set within the Administrative Settings tab.
4. Type the information into the e-mail notification fields as stated below.
E-mail Recipient The e-mail address of the person who will receive the notifications.
E-Mail SenderThe e-mail address from which the notification will be sent.
SMTP ServerConsult with the network administrator for the SMTP server address.
SMTP Username Consult with the network administrator for the SMTP username.
SMTP Password Consult with the network administrator for the SMTP password.
SMTP PortConsult with the network administrator which SMTP port number to
use. Port 25 is the most common SMTP port.
5. Check the desired notification time, fault conditions, and local conditions
to be included in notification e-mails to the recipient. These can be
changed after the initial configurations.
6. ClickApply Changes to save the configuration.
Configure Device Identity
The properties of the Device Identity populate the notification e-mail subject
and e-mail body. To configure the Device Identity, perform the following steps.
Rockwell Automation Publication 193-UM014B-EN-P December 201169
Chapter 8
2. Type the Device Identity information into the fields as described below.
Device NameThe name of the EtherNet/IP Communications Auxiliary.
Device DescriptionThe description of the EtherNet/IP Communications Auxiliary.
Device LocationThe location of the EtherNet/IP Communications Auxiliary.
Contact InformationThe contact information for the EtherNet/IP Communications
Auxiliary.
Device X NameThe name of the DeviceNet device being scanned.
Device X Description The description of the DeviceNet device being scanned.
3. Click Apply Changes to save the configuration.
Text Notifications
The EtherNet/IP Communications Auxiliary can send a text message to a
wireless phone be e-mailing the wireless phone’s service provider. The format for
the text message is provided by the service provider and looks similar to the
example formats below.
70Rockwell Automation Publication 193-UM014B-EN-P December 2011
Chapter 8
EXAMPLE
Multiple e-mail addresses can be entered into the E-mail Recipient field,
separating each e-mail address with a semicolon (;). The E-mail Recipient field is
limited to 255 characters.
An EtherNet/IP Communications Auxiliary sending an e-mail and text
message when a Communications Timeout event occurs:
Limitations
Based on the functionality of the EtherNet/IP Communications Auxiliary, there
are some limitations on when the e-mails can be triggered.
• If two events occur at the same time, an e-mail will only be sent for the
most significant error.
• If the device has been configured to send an e-mail for a lower prioritized
event and this event occurs at the same time as a higher prioritized event
for which the device has not been programmed to send an e-mail, an e-mail
will not be sent for either event.
• The Clear e-mail will only be sent when all events have been cleared and an
event e-mail has previously been sent.
Rockwell Automation Publication 193-UM014B-EN-P December 201171
Chapter 8
72Rockwell Automation Publication 193-UM014B-EN-P December 2011
Device Parameters
IMPORTANT
Chapter
9
Introduction
Parameter Programming
The EtherNet/IP Communications Auxiliary provides parameters to allow the
user to view the status and configure the DeviceNet scanner with RSNetWorx for
DeviceNet if the user does not want to use the internal web server of the
EtherNet/IP Communications Auxiliary. The 14 available parameters are listed
below.
Parameter setting changes to the EtherNet/IP Communications Auxiliary
take effect immediately even during a “running” status.
Parameter Listing
The details for each of the 14 available parameters are listed below.
Table 9 - Parameter 1 — Scanner Status
Value
DescriptionAccess Rule Data TypeUnits
Provides the status of the
Devicenet scanner.
0 On Line3 No Scanner Messages6 Initializing
1 Illegal Scan List4 Transmit Failure7 Duplicate MAC Failure
2 No Network Messages5 In Idle Mode8 Bus Off
Rockwell Automation Publication 193-UM014B-EN-P December 201173
GetWORD—0163830
Bit
Min.Max. Default
Chapter 9
Table 10 - Parameter 2 — SL Entry 1 Status
Value
DescriptionAccess Rule Data Type Units
Provides the status of the
first scan list entry in the
DeviceNet scanner.
0 On Line4 No Such Device8Device Went Idle
1 Connection Timeout5 Fragment Error
2 Keying Mismatch6 Slave Initialization Error
3 Wrong Data Size7 I/O Data Overflow 10 Acknoledgement Timeout
GetWORD—020470
Bit
Min.Max. Default
Automatic Device
9
Replacement Error
Table 11 - Parameter 3 — SL Entry 2 Status
Value
DescriptionAccess Rule Data Type Units
Provides the status of the
second scan list entry in the
DeviceNet scanner.
0 On Line4 No Such Device8Device Went Idle
1 Connection Timeout5 Fragment Error
2 Keying Mismatch6 Slave Initialization Error
3 Wrong Data Size7 I/O Data Overflow 10 Acknoledgement Timeout
GetWORD—020470
Bit
Min.Max. Default
Automatic Device
9
Replacement Error
Table 12 - Parameter 4 — SL Entry 3 Status
Value
DescriptionAccess Rule Data Type Units
Provides the status of the
third scan list entry in the
DeviceNet scanner.
0 On Line4 No Such Device8Device Went Idle
1 Connection Timeout5 Fragment Error
2 Keying Mismatch6 Slave Initialization Error
3 Wrong Data Size7 I/O Data Overflow 10 Acknoledgement Timeout
GetWORD—020470
Bit
Min.Max. Default
Automatic Device
9
Replacement Error
74Rockwell Automation Publication 193-UM014B-EN-P December 2011
Chapter9
Table 13 - Parameter 5 — SL Entry 4 Status
Value
DescriptionAccess Rule Data Type Units
Provides the status of the
fourth scan list entry in the
DeviceNet scanner.
0 On Line4 No Such Device8Device Went Idle
1 Connection Timeout5 Fragment Error
2 Keying Mismatch6 Slave Initialization Error
3 Wrong Data Size7 I/O Data Overflow 10 Acknoledgement Timeout
GetWORD—020470
Bit
Min.Max. Default
Automatic Device
9
Replacement Error
Table 14 - Parameter 6 — SL Entry 5 Status
Value
DescriptionAccess Rule Data Type Units
Provides the status of the
fifth scan list entry in the
DeviceNet scanner.
0 On Line4 No Such Device8Device Went Idle
1 Connection Timeout5 Fragment Error
2 Keying Mismatch6 Slave Initialization Error
3 Wrong Data Size7 I/O Data Overflow 10 Acknoledgement Timeout
GetWORD—020470
Bit
Min.Max. Default
Automatic Device
9
Replacement Error
Table 15 - Parameter 7 — SL Entry 6 Status
Value
DescriptionAccess Rule Data Type Units
Provides the status of the
sixth scan list entry in the
DeviceNet scanner.
0 On Line4 No Such Device8Device Went Idle
1 Connection Timeout5 Fragment Error
2 Keying Mismatch6 Slave Initialization Error
3 Wrong Data Size7 I/O Data Overflow 10 Acknoledgement Timeout
GetWORD—020470
Bit
Min.Max. Default
Automatic Device
9
Replacement Error
Rockwell Automation Publication 193-UM014B-EN-P December 201175
Chapter 9
Table 16 - Parameter 8 — SL Entry Size
DescriptionAccess Rule Data Type Units
Defines the number of bytes
to be scanned for I/O data
from each DeviceNet Device.
Get/SetUSIN TBytes1508
Min.Max. Default
Table 17 - Parameter 9 — Device Keys
DescriptionAccess Rule Data TypeUnits
Determines how electronic
keying will be performed.
0 Device Type2 Product Code4 Minor Revision
1 Vendor3 Major Revision5 Minor of Higher
Get/SetUSIN T—0637
Bit
Min.Max. Default
Value
Value
Table 18 - Parameter 10 — Scanlist Config
DescriptionAccess Rule Data Type Units
Triggers the building of a new
DeviceNet scan list.
0 = Ready
1 = Build Scan List
Get/SetBOOL—010
Table 19 - Parameter 11 — ADR Record
DescriptionAccess Rule Data Type Units
Triggers the recording of
configuration parameters from
devices in the DeviceNet scan list
to be used for Automatic Device
Replacement.
0 = Ready
1 = Record Parameters
Get/SetBOOL—010
Table 20 - Parameter 12 — ADR Enable
DescriptionAccess Rule Data Type Units
Enables Automatic Device
Replacement.
0 = Disable
1 = Enable
Get/SetBOOL—010
Value
Min.Max. Default
Value
Min. Max. Default
Value
Min. Max. Default
76Rockwell Automation Publication 193-UM014B-EN-P December 2011
Table 21 - Parameter 13 — DNet IO RPI
DescriptionAccess Rule Data Type Units
Defines the requested packet
interval rate in milliseconds used
on DeviceNet Polled I/O
messaging.
Get/SetWORDms2100075
Table 22 - Parameter 14 — DNet IO Inhibit
DescriptionAccess Rule Data Type Units
Defines the inhibit time in
milliseconds used on DeviceNet
Change of State (COS) I/O
messaging.
GetWORDms210001
Chapter9
Value
Min. Max. Default
Value
Min. Max. Default
Rockwell Automation Publication 193-UM014B-EN-P December 201177
Chapter 9
78Rockwell Automation Publication 193-UM014B-EN-P December 2011
Troubleshooting
Chapter
10
Introduction
EtherNet/IP Modules of
Operation
The purpose of this chapter is to assist in troubleshooting the EtherNet/IP
Communications Auxiliary.
SHOCK HAZARD: Servicing energized industrial control equipment can
be hazardous. Electrical shock, burns, or unintential actuation of
controlled industrial equipment may cause death or serious injury .For
safety of maintenance personnel as well as others who may be exposed
to electrical hazards assicated with maintenance activities, follow local
safety related work practices (e.g., the NFPS 70W; Part II, Electrical Safety for Employee Workplaces, in the United States) when working on
or near energized equipment. Maintenance personnel must be trained in
the safety practices, procedures, and requirements that pertain to their
respective job assignments. Do not work alone on energized equipment.
ATTENTION: Do not attempt to defeat or override fault circuits. The
cause of a fault indication must be determined and corrected before
attempting operation. Failure to correct a control system or mechanical
malfunction may result in personal injury and/or equipment damage due
to uncontrolled machine system operation.
The EtherNet/IP Communications Auxiliary has four EtherNet/IP modes of
operation:
• Power-Up Reset Mode,
• Run Mode,
• Recoverable Error Mode, and
• Unrecoverable Error Mode.
Rockwell Automation Publication 193-UM014B-EN-P December 201179
Chapter 10
Power-Up Reset Mode
Figure 8 - Status LEDs
Module Status (MS) LED
Ethernet/IP Network Status (NS) LED
Front Port Link Activity LED
Rear Port Link Activity LED
DeviceNet Network Status (NS) LED
During the Power-Up Reset Mode, the following procedure occurs.
1. The various LEDs will cycle simultaneously.
• Module Status (MS) LED will flash green for approximately 0.25
seconds, flash red for another 0.25 seconds, then remain a solid green.
• EtherNet/IP Network Status (NS) LED will flash green for
approximately 0.25 seconds, flash red for another 0.25 seconds, then
not illuminate.
• Device Network Status (NS) LED will flash green for approximately
.25 seconds, flash red for another0 .25 seconds, then not illuminate.
The MS and both NS LEDs will then return to their standard illuminated
state.
2. The EtherNet/IP Communications Auxiliary will perform a duplicate IP
address check to verify that another module is not assigned to the same IP
address. If a duplicate IP address is detected on the network, the EtherNet/
IP NS LED illuminates to a solid red, the MS LED flashes red, and the
EtherNet/IP Communications Auxiliary enters the Recoverable Error
Mode.
3. The EtherNet/IP Communications Auxiliary performs a duplicate MAC
address check to verify that another module is not assigned to the same
MAC address. If a duplicate MAC address is detected on the DeviceNet
network, the DeviceNet NS LED illuminates a solid red, the MS LED
flashes red, and the EtherNet/IP Communications Auxiliary enters the
Recoverable Error Mode.
80Rockwell Automation Publication 193-UM014B-EN-P December 2011
Chapter10
4. If the power-up or reset is successful, the overload relay will enter into Run
Mode.
Run Mode
In Run Mode, the EtherNet/IP Communications Auxiliary will:
• operate as a slave device to a master device on an EtherNet/IP network.
• operate as a master device and scan up to six slave devices on a DeviceNet
network.
• accept messages from a master on the EtherNet/IP network.
• send response messages, COS messages, or CYCLIC messages to a master.
• support a Device Level Ring (DLR) for Caralog Number 193-
DNENCATR.
If a communication error is detected, the EtherNet/IP Communications
Auxiliary will either enter the Recoverable Error Mode or Unrecoverable Error
Mode.
Operating as a Slave Device to a Master Device
As stated, the EtherNet/IP Communications Auxiliary will operate as a slave
device to a master device on an EtherNet/IP network in Run Mode. The
EtherNet/IP NS LED will flash green if there are no network connections
established with an EtherNet/IP network master. When one or more
connections are in the “established’ state, the EtherNet/IP NS LED will
illuminate a solid green. When one or more connections are in the “timed out”
state, the EtherNet/IP NS will flash red.
Operating as a Master Device
As also stated, the EtherNet/IP Communications Auxiliary will also operate as a
master device and scan up to six slave devices on a DeviceNet network in Run
Mode. The DeviceNet NS LED will flash green if there are no connections
established with a DeviceNet slave device. When one or more connections are in
the “established” state, the DeviceNet NS LED will illumiate a solid green. When
one or more connections are in the “timed out” state, the DeviceNet NS LED will
flash red. If no slave devices are defined in the DeviceNet scan list, the MS LED
will flash red.
Rockwell Automation Publication 193-UM014B-EN-P December 201181
Chapter 10
Recoverable Error Mode
In this mode, the EtherNet/IP Communications Auxiliary MS LED flashes red.
The device will respond to messages that are specified in offline mode recovery
message protocol.
Error TypeDescriptionLED State
RecoverableDuplicate IP address detected. Flashing Red
A device is not present on the DeviceNet scan list.
Unrecoverable Error Mode
In this mode, the EtherNet/IP Communications Auxiliary MS LED illuminates a
solid red. The device continues in this state as long as the device is powered.
Error TypeDescriptionLED State
Unecoverable Power-up initialization failure. Solid Red
Data communication error.
Troubleshooting
Procedures
The following table identifies possible causes and corrective actions when
troubleshooting EtherNet/IP related failures using the status LEDs.
Table 23 - Troubleshooting Procedures
Status LEDColorStatePossible CauseCorrective Action
EtherNet/IP
Network Status
(NS)
None—
Green, Red,
Not Illuminated
GreenFlashing
GreenSolid
RedFlashing
RedSolid
Flashing
(once)
The EtherNet/IP
Communications Auxiliary is
not receiving power.
NormalThis is a normal power-up
The EtherNet/IP
Communications Auxiliary is
online, but with no
connections established.
Normal operating state and
the EtherNet/IP
Communications Auxiliary is
allocated to a master.
One or more EtherNet/IP
connections timed out.
Diagnostics test failed on
power-up/reset. An internal
fault exists.
Duplicate EtherNet/IP module
address exists. Two modules
cannot have the same address.
A fatal communication error
occurred.
Check the DeviceNet cable
connections and verify that
24V DC exists between the red
and black terminals.
sequence.
Check the EtherNet/IP master
and its scan list for correct
scanner configuraton.
No action is required.
Reset the EtherNet/IP master
device.
Cycle power to the unit. If the
fault still exists, replace the
unit.
Change the IP address to a
valid setting and reset the
device.
Check Ethernet media for
proper installation.
82Rockwell Automation Publication 193-UM014B-EN-P December 2011
Chapter10
Status LEDColorStatePossible CauseCorrective Action
DeviceNet
Network Status
(NS)
Module Status
Link
Link (front)
Link (back)
None—
Green, Red,
Not Illuminated
GreenFlashing
GreenSolid
RedFlashing
RedSolid
None—
Green, Red,
Not Illuminated
GreenFlashing
GreenSolid
RedFlashing
RedSolid
None—
GreenFlashing
GreenSolid
Flashing
(once)
Flashing
(once)
The EtherNet/IP
Communications Auxiliary is
not receiving power.
NormalThis is a normal power-up
The EtherNet/IP
Communications Auxiliary is
not configured to scan any
DeviceNet slave devices.
Normal operating state and
the EtherNet/IP
Communications Auxiliary is
scanning DeviceNet slave
devices.
One or more DeviceNet
connections timed out.
Diagnostics test failed on
power-up/reset. An internal
fault exists.
Duplicate DeviceNet module
address exists. Two modules
cannot have the same address.
A fatal communication error
occurred.
The EtherNet/IP
Communications Auxiliary is
not receiving power.
NormalThis is a normal power-up
The EtherNet/IP
Communications Auxiliary is
proper;y scanning DeviceNet
slave devices, but it is not
being scanned by the
EtherNet/IP master.
Normal operating state, the
EtherNet/IP Communications
Auxiliary is scanning
DeviceNet slave devices, and
is allocated to its master.
One or more DeviceNet or
EtherNet/IP connections timed
out.
The EtherNet/IP
Communications Auxiliary is
not configured to scan any
DeviceNet slave devices.
Diagnostics test failed on
power-up/reset.
The EtherNet/IP
Communications Auxiliary is
ot properly conne
n
Ethernet network.
The Ethernet network is
properly connected.
Communications are occurring
on the Ethernet network.
cted to an
Check the DeviceNet cable
connections and verify that
24V DC exists between the red
and black terminals.
sequence.
Check the DeviceNet scan list
for the correct scanner
configuration.
No action is required.
Reset the EtherNet/IP
Communications Auxiliary.
Cycle power to the unit. If the
fault still exists, replace the
unit.
Change the MAC address to a
valid setting and reset the
device.
Check DeviceNet media for
proper installation.
Check the DeviceNet cable
connections and verify that
24V DC exists between the red
and black terminals.
sequence.
Check the Ethernet scan list
for the correct scanner
configuration.
No action is required.
Reset the EtherNet/IP
Communications Auxiliary.
Check the DeviceNet scan list
for correct scanner
configuration.
Cycle power to the device. If
the fault still exists, replace
the device.
Check the Ethernet cabling to
make sure it is properly
installed.
No action is required.
No action is required.
Rockwell Automation Publication 193-UM014B-EN-P December 201183
Chapter 10
84Rockwell Automation Publication 193-UM014B-EN-P December 2011
2 kV (Power Protective Earth)
1 kV (control bus cable)
B➊➋
1 kV L-L (bus cable)
B➊➋
➊ Performance Criteria B requires the DUT (device under test) not to experience degradation or loss of performance.
➋ Environment 2 - Heavy Industrial.
WARNING: This is a class A product. In domestic environment, this
product may cause radio interference, in which case the user may be
required to take adequate measures.
Table 26 - Ethernet IP Communcations
EtherNet/IP Communications
Total Connections Supported
TCP
CIP
Total CIP Unconnected Messages Supported128
CIP Class 1 Connection Consumed1
Packet Rates (packets/second)
I/O
HIM/MSG
Media Support
Twisted Pair
Fiber
Speed Duplex (Half/Full)10/100
Duplicate IP DetectionYes
150
47
500
500
Yes
No
86Rockwell Automation Publication 193-UM014B-EN-P December 2011
Table 27 - Standards & Certifications
Standards and Certifications
UL 508
CSA 22.2, No. 14
EN 60947-4-1
Appendix A
Rockwell Automation Publication 193-UM014B-EN-P December 201187
Appendix A
88Rockwell Automation Publication 193-UM014B-EN-P December 2011
Appendix
EtherNet/IP & DeviceNet Information
B
Electronic Data Sheet (EDS)
Files
Common Industrial Protocol
(CIP) Objects
EDS files are specially formatted ASCII files that provide all of the information
necessary for a configuration tool (e.g., RSNetWorx for EtherNet/IP) to access
and alter the parameters of a device. The EDS file contains all the parameter
information of a device: number of parameters, groupings, parameter name, min,
max, and default values, units, data format and scaling. The EDS file for the
EtherNet/IP Communications Auxiliary is available from the Internet at
www.ab.com/networks/eds/index.html
EtherNet/IP Communications Auxiliary’s internal web page.
Identity Object instances contain the following instance attributes.
Table 30 - Identity Object Instance Attributes
Attribute ID Access Rule Name Data TypeValue
1GetVendor IDUINT
2Get Device TypeUINT12
3GetProduct CodeUINT220 for 193-DNENCAT
221 for 193-DNENCATR
4Get Major Revision USINT1
Minor Revision USINT1
5GetStatusWORDBit 0: Owned, shall be set when
at least one connection i configured
Bit 2: Configured
Bit 8: Minor Recoverable fault
BIt 9: Minor Unrecoverable fault
Bit 10: Major Recoverable fault
Bit 11: Major Unrecoverable fault
6GetSerial NumberUDINTUnique number assigned for
each device
7GetProduct NameSHORT_STRING Product name
8Get StateUSINT3=Operational
The following common services are implemented for the Identity Object.
Table 31 - Identity Object Common Services
Implemented for:
Service Code
0x01NoYesGet Attribute All
0x0EYesYesGet Attribute Single
0x05NoYesReset
Service NameClassInstance
Message Router Object — CLASS CODE 0x02
No class or instance attributes are supported. The message router object exists
only to route explicit messages to other objects.
90Rockwell Automation Publication 193-UM014B-EN-P December 2011
AppendixB
DeviceNet Object — CLASS CODE 0x03
The following class attributes will be supported for the DeviceNet Object.
Table 32 - DeviceNet Object Class Attributes
Attribute IDAccess RuleNameData Type Value
1GetRevisionUINT2
A single instance of the DeviceNet Object will be supported by the following
attributes.
Table 33 - Single Instance of the DeviceNet Object
Identifies which
nodes are online
on the local
network based on
the node address.
The following services will be implemented for the DeviceNet Object.
Table 34 - DeviceNet Object Common Services
Implemented for:
Service Code
0x0EYesYesGet Attribute Single
0x10NoYesSet Attribute Single
Service NameClassInstance
Assembly Object — CLASS CODE 0x04
The following class attributes are supported for the Assembly Object.
Table 35 - Assembly Object Class Attributes
Attribute ID Access Rule NameData Type Value
2GetMax. Instance UINT120
Instance Attributes
Instances/Connection points implements the following data attributes.
Rockwell Automation Publication 193-UM014B-EN-P December 201191
Appendix B
Table 36 - Instance Attributes
# Access Name TypeValue Description
3 Get/Set DataArray of UINT —Data produced/consumed by the module
Output Assemblies
The following output assembly instances are implemented.
Table 37 - Instance 100
Byte SizeContents
Scan List I/O SizeData to be delivered to the first scan list entry.
Scan List I/O SizeData to be delivered to the second scan list entry.
Scan List I/O SizeData to be delivered to the third scan list entry.
Scan List I/O SizeData to be delivered to the fourth scan list entry.
Scan List I/O SizeData to be delivered to the fifth scan list entry.
Scan List I/O SizeData to be delivered to the sixth scan list entry.
Input Assemblies
Table 38 - Instance 101
Byte SizeContents
4 BytesLogix Status Word
2 BytesDeviceNet Scanner Status (Parameter 1) See Table 9 on page 73
2 BytesScan List Entry 1 Status Word (Parameter 2) See Table 10 on page 74
2 BytesScan List Entry 2 Status Word (Parameter 3) See Table 11 on page 74
2 BytesScan List Entry 3 Status Word (Parameter 4) See Table 12 on page 74
2 BytesScan List Entry 4 Status Word (Parameter 5) See Table 13 on page 75
2 BytesScan List Entry 5 Status Word (Parameter 6) See Table 14 on page 75
2 BytesScan List Entry 6 Status Word (Parameter 7) See Table 15 on page 75
Scan List I/O SizeData to be delivered to the first scan list entry.
Scan List I/O SizeData to be delivered to the second scan list entry.
Scan List I/O SizeData to be delivered to the third scan list entry.
Scan List I/O SizeData to be delivered to the fourth scan list entry.
Scan List I/O SizeData to be delivered to the fifth scan list entry.
Scan List I/O SizeData to be delivered to the sixth scan list entry.
2 BytesDataLink 1 Data
2 BytesDataLink 2 Data
2 Bytes
: : : :
2 BytesData Link 48 Data
DataLink 3 Data
: : : :
92Rockwell Automation Publication 193-UM014B-EN-P December 2011
AppendixB
Table 39 - Instance 103 ➊
Byte SizeContents
4 Bytes Logix Status Word
4 Bytes DeviceNet Scanner Status (Parameter 1) See Table 9 on page 73
4 Bytes Scan List Entry 1 Status Word (Parameter 2) See Table 10 on page 74
4 Bytes Scan List Entry 2 Status Word (Parameter 3) See Table 11 on page 74
4 Bytes Scan List Entry 3 Status Word (Parameter 4) See Table 12 on page 74
4 Bytes Scan List Entry 4 Status Word (Parameter 5) See Table 13 on page 75
4 Bytes Scan List Entry 5 Status Word (Parameter 6) See Table 14 on page 75
4 Bytes Scan List Entry 6 Status Word (Parameter 7) See Table 15 on page 75
Scan List I/O Size Data to be delivered to the first scan list entry.
Scan List I/O Size Data to be delivered to the second scan list entry.
Scan List I/O Size Data to be delivered to the third scan list entry.
Scan List I/O Size Data to be delivered to the fourth scan list entry.
Scan List I/O Size Data to be delivered to the fifth scan list entry.
Scan List I/O Size Data to be delivered to the sixth scan list entry.
2 BytesDataLink 1 Data
2 Bytes DataLink 2 Data
2 Bytes DataLink 3 Data
: : : : : : : :
2 Bytes Data Link 48 Data
➊Available with firmware v 2.00 and higher.
Rockwell Automation Publication 193-UM014B-EN-P December 201193
Appendix B
Configuration Assembly
Table 40 - Instance 102 (Revision 1)
Byte SizeContents
2 BytesRevision = 1
2 Bytes ScanList I/O Size
2 Bytes Data Link Update Interval (ms)
1 Byte Data Link 1 Node
2 Bytes Data Link 1 Parameter
1 Byte Data Link 2 Node
2 Bytes Data Link 2 Parameter
1 Byte Data Link 3 Node
2 Bytes Data Link 3 Parameter
1 Byte Data Link 4 Node
2 Bytes Data Link 4 Parameter
1 Byte Data Link 5 Node
2 Bytes Data Link 5 Parameter
1 Byte Data Link 6 Node
2 Bytes Data Link 6 Parameter
: : : :: : : :
1 Byte Data Link 48 Node
2 Bytes Data Link 48 Parameter
94Rockwell Automation Publication 193-UM014B-EN-P December 2011
Table 41 - Instance 102 (Revision 2)➊
Byte SizeContents
2 BytesRevision = 2
2 Bytes ScanList I/O Size
2 Bytes Data Link Update Interval (ms)
2 Bytes Reserved
2 BytesData Link 1 Node
2 Bytes Data Link 1 Parameter
2 BytesData Link 2 Node
2 Bytes Data Link 2 Parameter
2 BytesData Link 3 Node
2 Bytes Data Link 3 Parameter
2 BytesData Link 4 Node
2 Bytes Data Link 4 Parameter
2 BytesData Link 5 Node
2 Bytes Data Link 5 Parameter
2 BytesData Link 6 Node
2 Bytes Data Link 6 Parameter
AppendixB
: : : :: : : :
2 BytesData Link 48 Node
2 Bytes Data Link 48 Parameter
➊Available with firmware v 2.00 and higher.
The following services are implemented for the Assembly Object.
Table 42 - Ethernet Object Common Services
Implemented for:
Service Code
0x0EYesYesYesGet Attribute Single
0x10NoYesNoSet Attribute Single
Service NameClass Instance Consuming Instance Producing
Connection Manager Object — CLASS CODE 0x06
No class or instance attributes are supported.
The following common service are implemented for the Connection Manager
Object.
Rockwell Automation Publication 193-UM014B-EN-P December 201195
Appendix B
Table 43 - Connection Manager Object Common Services
Implemented for:
Service NameInstance
YesForward Open
YesForward Close
YesUnconnected Send
Parameter Object — CLASS CODE 0x0F
The following class attributes are supported for the Parameter Object.
Table 44 - Parameter Object Class Attributes
Attribute ID Access Rule NameData Type Value
1GetRevisionUINT0x0001
2GetMax InstanceUINT0x0029
8GetParameter Class Descriptor WORD0x000B
The following instance attributes are implemented for all parameter attributes.
Table 45 - Parameter Object Instance Attributes
Attribute ID Access Rule NameData Type Value
1Get/SetValueSpecified in Descriptor
2GetLink Path SizeUSINT
3GetLink PathPacked EPATH:Path to specified
4GetDescriptorWORD
5GetData TypeEPATH
6GetData SizeUSINT
7GetParameter Name
String
8GetUnits StringSHORT_STRING
9GetHelp StringSHORT_STRING
10GetMinimum ValueSpecified in Descriptor
11 Get Maximum ValueSpecified in Descriptor
12GetDefault ValueSpecified in Descriptor
13GetScaling Multiplier UINT
14GetScaling DivisorUINT
15GetScaling BaseUINT
16GetScaling OffsetINT
17 Get Multiplier LinkUINT
SHORT_STRING
N/A
object attribute
Parameter
Dependent
96Rockwell Automation Publication 193-UM014B-EN-P December 2011
Rockwell Automation Publication 193-UM014B-EN-P December 201199
Service NameClass Instance
Appendix B
TCP/IP Interface Object — CLASS CODE 0xF5
The TCP/IP object supports the following class.
Table 56 - TCP/IP Object Class
Attribute ID Access Rule NameData Type Value
1GetRevision UINT3
For single port devices, one instance of the TCP/IP interface object is supported.
For dual port devices, two instances of the TCP/IP interface object are
supported.
Table 57 - TCP/IP Object Class Instances
Attribute ID Access Rule NameData TypeValue
1GetStatusDWORD
2GetConfiguration
Capability
3Get/SetConfiguration
Control
4GetPhysical
Link Object
5Get/SetInterface
Configuration
6Get/SetHost NameSTRING
8Get/SetTTL ValueUSINTTime to live value for EtherNet/IP
9Get/SetMulticast
Config
DWORD0x00000014
DWORD0=Configuration from NVS
Struct of:
UINT
Padded
EPATH
Struct of:
UDINT
UDINT
UDINT
UDINT
UDINT
STRING
Struct of:
USINT
USINT
UINT
UDINT
2=Configuration from DHCP
For a single port device: 2 words
20 F6 24 01 (ENet Link Object Inst 1)
For dual port device: NULL
IP Address
Network Mask
Gateway Address
Primary DNS
Secondary DNS
Default domain name for not fully
qualified host names
multicast packets
Allocation Control
Reserved
Number of multicast addresses to
allocate (1-4)
Multicast starting address
The following common services are implemented for the TCP/IP interface
object.
100Rockwell Automation Publication 193-UM014B-EN-P December 2011
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.