Catalog Numbers 1794-IB16D, 1794-OB16D
User Manual
Important User Information
WARNING
IMPORTANT
ATTENTION
SHOCK HAZARD
BURN HAZARD
Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application,
Installation and Maintenance of Solid State Controls (publication SGI-1.1
http://literature.rockwellautomation.com
) describes some important differences between solid state equipment and hard-wired electromechanical
devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this
equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this
equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated
with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and
diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this
manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
available from your local Rockwell Automation sales office or online at
Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may
lead to personal injury or death, property damage, or economic loss.
Identifies information that is critical for successful application and understanding of the product.
Identifies information about practices or circumstances that can lead to: personal injury or death, property damage, or
economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
Labels may be on or inside the equipment, such as a drive or motor, to alert people that dangerous voltage may be present.
Labels may be on or inside the equipment, such as a drive or motor, to alert people that surfaces may reach dangerous
temperatures.
Allen-Bradley, Rockwell Automation, FLEX I/O, RSLogix, RSLinx, RSLogix 5000 and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
This manual provides information on installation, setting, and reading your
diagnostics on the 1794-IB16D and the 1794-OB16D Diagnostic modules.
For information onSee Chapter
1794 Diagnostic Modules1
Specific Diagnostic Module2 or 3
Using Diagnostic Modules in a Remote I/O System4
Using Diagnostic Modules in a DeviceNet System5
Using Diagnostic Modules in a ControlNet System6
Using Diagnostic Modules in an EtherNet /IP System7
Using the Indicators for TroubleshootingAppendix A
Simplified Schematics for all 1794 Digital ModulesAppendix B
Obey the following warnings and cautions when installing or using these
modules.
Environment and Enclosure
This equipment is intended for use in a Pollution Degree 2 industrial
environment, in overvoltage Category II applications (as defined in IEC
publication 60664-1), at altitudes up to 2000 meters without derating.
This equipment is considered Group 1, Class A industrial equipment
according to IEC/CISPR Publication 11. Without appropriate
precautions, there may be potential difficulties ensuring
electromagnetic compatibility in other environments due to conducted
as well as radiated disturbance.
This equipment is supplied as open-type equipment. It must be
mounted within an enclosure that is suitably designed for those
specific environmental conditions that will be present and
appropriately designed to prevent personal injury resulting from
accessibility to live parts. The interior of the enclosure must be
accessible only by the use of a tool. Subsequent sections of this
publication may contain additional information regarding specific
enclosure type ratings that are required to comply with certain
product safety certifications.
See NEMA Standards publication 250 and IEC publication 60529, as
applicable, for explanations of the degrees of protection provided by
different types of enclosure. Also, see the appropriate sections in this
publication, as well as Industrial Automation Wiring and Grounding
Guidelines, Allen-Bradley publication 1770-4.1, for additional
installation requirements pertaining to this equipment.
5Publication 1794-UM065B-EN-E - July 2006
6 Preface
WARNING
ATTENTION
ATTENTION
ATTENTION
When you insert or remove the module while backplane power is on,
an electrical arc can occur. This could cause an explosion in
hazardous location installations. Be sure that power is removed or the
area is nonhazardous before proceeding.
FLEX I/O is grounded through the DIN rail to chassis ground. Use zinc
plated yellow-chromate steel DIN rail to assure proper grounding. The
use of other DIN rail materials (such as aluminum or plastic) that can
corrode, oxidize, or are poor conductors, can result in improper or
intermittent grounding.
Prevent Electrostatic Discharge
This equipment is sensitive to electrostatic discharge, which can
cause internal damage and affect normal operation. Follow these
guidelines when you handle this equipment:
• Touch a grounded object to discharge potential static.
• Wear an approved grounding wriststrap.
• Do not touch connectors or pins on component boards.
• Do not touch circuit components inside the equipment.
• If available, use a static-safe workstation.
During mounting of all devices, be sure that all debris (such as metal
chips or wire strands) is kept from falling into the module. Debris that
falls into the module could cause damage on power up.
Publication 1794-UM065B-EN-E - July 2006
Preface 7
WARNING
AVERTISSEMENT
North American Hazardous Location Approval
The 1794-IB16D and 1794-OB16D diagnostic modules are North American
Hazardous Location approved.
The following information applies when
operating this equipment in hazardous
locations:
Products marked “CL I, DIV 2, GP A, B, C, D”
are suitable for use in Class I Division 2
Groups A, B, C, D, Hazardous Locations and
nonhazardous locations only. Each product is
supplied with markings on the rating
nameplate indicating the hazardous location
temperature code. When combining products
within a system, the most adverse
temperature code (lowest “T” number) may be
used to help determine the overall
temperature code of the system. Combinations
of equipment in your system are subject to
investigation by the local Authority Having
Jurisdiction at the time of installation.
EXPLOSION HAZARD
•Do not disconnect
equipment unless power
has been removed or the
area is known to be
nonhazardous.
•Do not disconnect
connections to this
equipment unless power
has been removed or the
area is known to be
nonhazardous. Secure any
external connections that
mate to this equipment by
using screws, sliding
latches, threaded
connectors, or other means
provided with this product.
•Substitution of
components may impair
suitability for Class I,
Division 2.
•If this product contains
batteries, they must only be
changed in an area known
to be nonhazardous.
Informations sur l’utilisation de cet
équipement en environnements dangereux :
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne
conviennent qu’à une utilisation en environnements
de Classe I Division 2 Groupes A, B, C, D dangereux
et non dangereux. Chaque produit est livré avec des
marquages sur sa plaque d’identification qui
indiquent le code de température pour les
environnements dangereux. Lorsque plusieurs
produits sont combinés dans un système, le code
de température le plus défavorable (code de
température le plus faible) peut être utilisé pour
déterminer le code de température global du
système. Les combinaisons d’équipements dans le
système sont sujettes à inspection par les autorités
locales qualifiées au moment de l’installation.
RISQUE D’EXPLOSION
•Couper le courant ou s’assurer
que l’environnement est classé
non dangereux avant de
débrancher l'équipement.
•Couper le courant ou s'assurer
que l’environnement est classé
non dangereux avant de
débrancher les connecteurs. Fixer
tous les connecteurs externes
reliés à cet équipement à l'aide
de vis, loquets coulissants,
connecteurs filetés ou autres
moyens fournis avec ce produit.
•La substitution de composants
peut rendre cet équipement
inadapté à une utilisation en
environnement de Classe I,
Division 2.
•S’assurer que l’environnement
est classé non dangereux avant
de changer les piles.
Spring Clamp Terminal Base Unit
Temperature Terminal Base Unit
Spring Clamp Temperature Base Unit
Terminal Base Unit
Spring Clamp Terminal Base Unit
Cage Clamp Terminal Base Unit
Spring Clamp Terminal Base Unit
Terminal Base Unit
Fused Terminal Base Unit
Conformally Coated Terminal Base Unit
Conformally Coated Terminal Base Unit
Conformally Coated Fused Terminal
Base Unit
User Manual
1794-TB37DS,
-TB62DS,
D-Shell Terminal Base Units and
Distribution Boards
1794-IN107
TB37EXD4VM8,
-TB37EXD4CM8,
-TB62EXD4X15
1794–CE1, –CE3
1794–NM1
Extender Cables1794–5.12
Mounting Kit1794–5.13
1794–PS1324V dcPower Supply 1794-IN069
1794–PS324V dcPower Supply
FLEX Ex
1797–IBN16See note16 NAMUR Digital Input Module1797-5.7
1797–OB4DSee note4 NI, Ex Source Digital Output Module1797-5.6
1797–IE8, -IE8HSee note8 Input Module1797-5.5
1797–IE8NFSee note8 Selectable Filter Analog Input Module 1797-5.31
1797–OE8, -OE8HSee noteAnalog 8 Output Module 1797-5.3
1797–IRT8See note8 Thermocouple/RTD Input Module1797-5.4
1797–IJ2See note2 Channel Frequency Input Module1797-5.9
1797–TB3
1797–TB3S
Cage Clamp Terminal Base
Spring Clamp Terminal Base
1797-5.1
1797-5.2
Publication 1794-UM065B-EN-E - July 2006
Preface 11
Catalog
Number
1797–BICSee noteI.S. Bus Isolator1797-5.13
1797–CECSee noteFLEX Ex Bus Connector1797-5.13
Note: Intrinsically Safe Voltage
VoltageDescriptionPublications
Installation
Instructions
For more information on DeviceNet modules in Logix5000 systems, see
publication DNET-UM004
, DeviceNet Modules in Logix5000 Systems.
For more information on ControlNet modules in Logix5000 systems, see
publication CNET-UM001
, ControlNet Modules in Logix5000 Systems.
For more information on EtherNet/IP modules in Logix5000 systems, see
publication ENET-UM001
, EtherNet/IP Modules in Logix5000 Systems.
User Manual
Publication 1794-UM065B-EN-E - July 2006
12 Preface
Notes:
Publication 1794-UM065B-EN-E - July 2006
Chapter
1
1794 FLEX I/O Diagnostic Digital Modules
Overview
Introduction
General Description
In this chapter, you will learn about the diagnostic input module, cat. no.
1794-IB16D, and the diagnostic output module, cat. no. 1794-OB16D.
TopicSee Page
General Description13
Install Your Digital Input or Output Module16
This chapter contains an overview of the FLEX I/O diagnostic digital
modules, the 1794-IB16D input module and 1794-OB16D output module.
You can use the FLEX I/O diagnostic modules to help diagnose problems
with input and output field devices, I/O wiring and the user power supply.
Additionally, these modules can reduce installation start-up time and help
minimize time to find and fix failures.
This chapter explains how to use the FLEX I/O diagnostic modules to help
detect the following types of faults:
• Open input or output field devices
• Open input or output wiring
• Shorted output field devices
• Shorted input or output wiring
• Reversed polarity of user supply wiring
• Open user supply wiring or failed user supply (using one diagnostic
input channel)
13Publication 1794-UM061A-EN-P - July 2006
14 1794 FLEX I/O Diagnostic Digital Modules Overview
Network Compatibility
You can use the diagnostic modules with ControlNet, DeviceNet,
EtherNet/IP, or remote I/O networks.
Network1794-IB16D1794-OB16D
Remote I/OCompatible with 1794-ASB
DeviceNetNo limitations or constraints.
ControlNetDirect connection only.Direct or rack connections.
EtherNet/IPDirect connection only.Direct or rack connections.
Usage Limitations
series E (or higher) and
1794-ASB2 series D (or higher)
remote I/O adapters.
Compatible with 1794-ASB
series D (or higher) and
1794-ASB2 series C (or higher)
remote I/O adapters.
1794-IB16D Diagnostic Input Module Compatibility
The 1794-IB16D diagnostic input module interfaces to sensing devices and
detects whether they are on or off. The diagnostic input module converts dc
signals from user devices to the appropriate logic level for use in the
FLEX I/O system. Typical input devices include these types of switches.
• Proximity switches
• Limit switches
• Photoelectric switches
• Selector switches
•Float switches
• Pushbutton switches
When designing a system using a FLEX I/O diagnostic input module, you
must consider:
• the voltage necessary for your application.
• current leakage through the input devices.
• the amount of current consumed by the input devices.
• whether the application requires sinking or sourcing devices.
Publication 1794-UM061A-EN-P - July 2006
1794 FLEX I/O Diagnostic Digital Modules Overview 15
Capabilities of the 1794-IB16D include:
• 61131-2 Type 3 compatible sinking inputs.
• interface with PNP sourcing sensors.
• 10-31.2V dc operating range.
• provides up to 50 mA to power an attached sensor.
• detects for an open wire condition down to 50 μA.
You need a dummy resistor to mask the channel diagnostic function for each
unused sensor port. Used sensor ports must have a 50 μA minimum current
draw with the input field device in both the on- and off-state.
1794-OB16D Diagnostic Output Module Compatibility
You can use FLEX I/O diagnostic output modules to drive a variety of output
devices. Typical output devices include the following.
•Relays
• Solenoids
• Contactors
• Indicators
• Small motor starters
When you design a system using FLEX I/O diagnostic output modules, you
must consider:
• The output must supply the necessary surge and continuous current for
the output device being used.
• When sizing output loads, check the documentation supplied with the
output device for the surge and continuous current needed to operate
the device.
Capabilities of the 1794-OB16D diagnostic output module include:
• sourcing style outputs for loads connected to common.
• 10-31.2V dc operating range.
• provides continuous current of 0.5 A maximum (8 A per module),
2.0 mA minimum per output.
• capable of 2 A surge for 50 ms, repeatable every 2 s.
• protection from short circuit and overload.
You need a dummy resistor to mask the channel diagnostic function for each
unused output channel.
Publication 1794-UM061A-EN-P - July 2006
16 1794 FLEX I/O Diagnostic Digital Modules Overview
Install Your Digital Input or
Output Module
To install a digital diagnostic module, follow these steps:
✓Installation Step
❑ 1.Mount the terminal base unit
See installation instructions 1794-IN096
❑ 2.Install the module in the terminal base unit
See installation instructions 1794-IN096
❑ 3.Connect the wiring to the terminal base unit
See installation instructions 1794-IN096
.
.
.
Publication 1794-UM061A-EN-P - July 2006
1794 FLEX I/O Diagnostic Digital Modules Overview 17
Terminals C-36, C-38, C-40, C-42, C-44, C-46, C-48 and C-50.
User power (+) Voltage: Terminals C-43, C-45, C-47 and C-49.
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
COM1 and COM2 are connected together in the module.
+V1 Terminals C-35, C-37, C-39, and C-41 are not used
1794-TB32 and 1794-TB32S Terminal Base Wiring for the 1794-IB16D
Wiring for 1794-IB16D (use with 1794-TB32 or 1794-TB32S Terminal Base Units)
InputInput
Term ina l
Sensor Power
Term in al
Common
IN 00A-0B-17-V common
IN 01A-1B-18
IN 02A-2B-19
IN 03A-3B-20
connected to
terminals 36, 38,
40, 42, 44, 46, 48,
and 50
IN 04A-4B-21
1
Supply
+V2 connected
to terminals 43,
45, 47, and 49
(+V1 terminals
35, 37, 39, and
41 are not used).
IN 05A-5B-22
IN 06A-6B-23
IN 07A-7B-24
IN 08A-8B-25
IN 09A-9B-26
IN 10A-10B-27
IN 11A-11B-28
IN 12A-12B-29
IN 13A-13B-30
IN 14A-14B-31
IN 15A-15B-32
+V2 dc
power
COM dc
Return
(1)
3-wire devices only. 2-wire devices use input and sensor power terminals; 3-wire
Power terminals 43, 45, 47, and 49 (power terminals are internally
connected together in the module)
Common terminals 36, 38, 40, 42, 44, 46, 48, and 50 (common terminals
COM 1 and COM 2 are internally connected together in the module)
devices use input, sensor power and common terminals.
Publication 1794-UM061A-EN-P - July 2006
18 1794 FLEX I/O Diagnostic Digital Modules Overview
1794-TB2, -TB3, and -TB3S Terminal Base Wiring for the 1794-OB16D
internally connected in the terminal base unit.
C-34…C-51 (1794-TB3, 1794-TB3S) (Power terminals
are internally connected in the terminal base unit.
CommonB-16…B-33 (Common terminals are internally
connected in the terminal base unit.
2
About the FLEX I/O Diagnostic Input Module
Introduction
About the 1794-IB16D
Diagnostic Input Module
In this chapter, you will learn about the diagnostic input module, cat. no.
1794-IB16D.
For Information AboutSee Page
About the 1794-IB16D Diagnostic Input Module19
Diagnostic Fault Detection21
Indicator Status Information2
Module Limitations24
Configure Your Diagnostic Input Module26
The 1794-IB16D diagnostic input module provides 16 points of 24V dc
sinking inputs with open-wire, short-circuit, and user supply reverse polarity
diagnostic features. Each input signal has an associated sensor power
connection. The module monitors current and voltage at each input channel
sensor power terminal.
The module detects:
• an open fault if the sensor-power current drops.
• a short fault if the sensor-power voltage goes low.
• a reverse-polarity fault if reverse voltage is applied to the user terminals.
Terminals C-36, C-38, C-40, C-42, C-44, C-46, C-48 and C-50.
User power (+) Voltage: Terminals C-43, C-45, C-47 and C-49
+V1 Terminals C-35, C-37, C-39 and C-41 are not used
NC
COM1 and COM2 are connected together in the module.
A
B
C
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Wiring Input Sensors
You must use a 1794-TB32 or 1794-TB32S terminal base unit with the
1794-IB16D diagnostic input module. See installation instructions
ldkg df;l 1794-IN096
for complete information.
Publication 1794-UM061A-EN-P - July 2006
Two-wire input devices connect to the input and sensor power terminals;
3-wire devices use input, sensor power and common terminals. You can wire
2-wire and 3-wire sensors to the FLEX I/O 1794-TB32 or 1794-TB32S
terminal base units.
Unused sensor-power ports or open-contact input devices must use a dummy
resistor to mask the diagnostic function. If these external resistors are not
used, the module’s fault indicator will light, along with the module’s error bits,
thus rendering fault detection of the remaining channels useless. The
recommended value of this dummy resistor is 20 kΩ (+
larger). Connect the resistor between sensor power and input signal or
10%), 1/8 Watt (or
between sensor power and common.
About the FLEX I/O Diagnostic Input Module 21
.
.
User Power
Reverse
Voltage
Monitor
PTC
Shorted
Input
Monitor
Open Wire
Monitor
Input Circuit Indicator
+
-
Input
Sensor Power
Reverse
Short
Open
Input
Flexbus Interface
V+
Fault Indicator
Diagnostic Fault Detection
The module monitors current and voltage at each input channel sensor power
terminal, and monitors the user supply for reverse user supply voltage. The
figure below shows the location of these fault monitors in the 1794-IB16D
diagnostic input module.
Publication 1794-UM061A-EN-P - July 2006
22 About the FLEX I/O Diagnostic Input Module
Sensor Power Open and Short Circuit Detection
The sensor-power open-wire current monitor detects a fault condition if the
sensor-power current drops below 50 μA. Sensor-power shorts are protected
by the positive temperature coefficient (PTC) resistor in series with each
sensor power output (16 total). For overcurrents or shorts, the PTC resistor
heats up, the resistance increases and the sensor power output opens, similar to
a fuse opening. This shorted condition is monitored by the sensor power
voltage monitor. It detects a short if the sensor power voltage disappears.
When the short is removed, the PTC resistor cools down and the previously
shorted sensor-power port, sensor power is automatically restored and normal
operation continues.
The module’s embedded monitors detect open and short conditions.
Publication 1794-UM061A-EN-P - July 2006
When a fault is detected:
• the corresponding channel’s red indicator lights.
• the module’s red fault indicator lights.
• the module’s open, short or reverse error bit is set.
• the module error bit is set.
The input circuit is a conventional sinking style with an input voltage dropping
resistor. The yellow input indicator is in series with the input signal (field-side
indication). FLEX I/O system-side logic voltages are isolated from the user
power supply and input channels by optocouplers. This provides protection
against field side voltages and transients.
About the FLEX I/O Diagnostic Input Module 23
(1794-IB16D shown)
User Power Supply Reverse Voltage Detection
If the external user power supply is miswired (incorrect polarity), the module is
protected and reports a reverse user voltage fault. The reverse voltage
condition must be at least -10V to detect a fault. The module’s Fault indicator
turns red and the reverse fault bit is set. The module error bit is also set. When
the correct user power supply polarity is applied, the module Fault indicator is
off and the reverse fault bit is not set.
User Power Supply Loss Detection
The module does not check for presence of the external user power supply.
Detection can be accomplished by wiring an input channel to the user supply.
Any 24V dc input can be used. You can wire a 1794-IB16D diagnostic input
module or 1794-IB16 input module to monitor the user supply as shown
below:
Indicator Status
Information
The 1794-IB16D diagnostic input module has indicators that let you check the
module health and operational status. The following status can be checked
with the indicators.
• Channel I/O Status - This indicator displays the ON/OFF state of the
input channel, as well as channel wiring fault conditions:
– Off indicates the input channel is off with no faults.
– Yellow indicates the input channel is on with no faults.
– Red indicates either a channel sensor power open or short condition.
• Module Fault Status- This indictor turns red for any individual input
channel open, short or module reverse power conditions.
With no fault, the module fault status indicator turns off.
Publication 1794-UM061A-EN-P - July 2006
24 About the FLEX I/O Diagnostic Input Module
10
Ambient Temperature
(0°C)
Input
Voltage
(V)
Sensor
Power
Current
(mA)
Ambient Temperature (° C)
Module Limitations
Input Voltage Derating
You must derate the input voltage applied to each input channel, based on
operating ambient temperature, to keep module power dissipation within an
acceptable level.
31.2
30
26.4
25
20
15
10
5
0
20 30 40 50 55
Sensor-Power Derating
You must derate the allowable current from each channel sensor-power port
based on operating ambient temperature to keep module power dissipation to
an acceptable level.
Publication 1794-UM061A-EN-P - July 2006
About the FLEX I/O Diagnostic Input Module 25
User Power +
PTC Resistor
Off-Wire
Current Monitor
Fault if:
1 < 50 μA
Sensor Power
Sensor
Input
Vsensor = (Ext Pwr) - 2.2V
Overcurrent causes PTC to open
Voltage Drop = 2.2V maximum
24V dc External
User Power Supply
User Power
-
Unused Sensor Power Ports
You must connect dummy resistors to unused Sensor Power ports to mask the
diagnostic function. If external resistors are not used, the module's sensing
circuitry will not detect the intended voltage or current and not report that a
fault exists. The module’s fault and open-channel indicators light, and the
module’s open and module error bits are set, thus rendering fault detection of
the remaining channels useless. The recommended value of this dummy
resistor is 20 KΩ (+
10%), 1/8 W (or larger).
Open Contact Mechanical Switches and Relays
The module's sensing circuitry must detect a minimum current level to
conclude that an open circuit does not exist. Electronic input field devices
typically have sufficient leakage current to satisfy the minimum requirement.
However, hard contacts have no leakage current, so you must add dummy
resistors in parallel to the hard contacts to supply the minimum current needed
for the module to sense that an open circuit does not exist. The
recommended resistor value is 20 kΩ (+
the dummy resistor at the field device also allows for monitoring of field
wiring conditions. Connect the resistor between sensor power and input signal,
or between sensor power and common.
10%), 1/8 W (or larger). Placement of
Sensor Power Internal Voltage Drop
The modules sensor power circuit exhibits an internal voltage drop. This
voltage drop can be as large as 2.2V for all operating conditions. You must
subtract 2.2V from the value of your external user power supply to determine
the voltage applied to power attached sensors. Make sure this voltage meets
sensor requirements. Consult the data sheet for your sensor to determine what
voltage is necessary.
Read 1I 15I 14I 13I 12I 11I 10I 9I 8I 7I 6I 5I 4I 3I 2I 1I 0
Read 2Not usedRead Diagnostics Status
Write 1 Not usedInput Filter FT 0-15Not used
Where:I = Input
FT = Input filter time
Diagnostic status;
Bit 00 = module error;
Bit 01 = external power reverse polarity error;
Bit 02 = sensor power short error;
Bit 03 = sensor power open wire error
The configuration and input filter selection table are shown below.
Data Table & Input Filter Time Selection
The inputs are read in Word 1. Bit 00 is the first input and decimal bit 15 is the
last input.
Diagnostic status is read from Word 2:
Bit 00: Module Error Bit
Bit 01: External Power Reverse Polarity Error Bit
Bit 02: Sensor Power Short Error Bit
Bit 03: Sensor Power Open Wire Error Bit
Input Filter Times
Input filter times are configurable on a module basis. Both off-to-on and
on-to-off times are set by write Word 3. The default filter time is 0.25 ms.
BitsDescriptionFilter Time
100908Filter time for inputs 0
thru 15
000Filter time 0 (default)0.25 ms
001Filter time 10.5 ms
010Filter time 21 ms
011Filter time 32 ms
100Filter time 44 ms
101Filter time 58 ms
110Filter time 616 ms
111Filter time 732 ms
Off-to-On/
On-to-Off
Publication 1794-UM061A-EN-P - July 2006
Chapter
3
About the FLEX I/O Diagnostic Output Module
Introduction
About the 1794-OB16D
Diagnostic Output Module
In this chapter, you will learn about the diagnostic output module, cat. no.
1794-OB16D.
For Information AboutSee Page
About the 1794-OB16D Diagnostic Output Module27
Diagnostic Fault Detection29
Module Protection Functions30
Module Limitations32
Configure Your Output Diagnostic Module32
The 1794-OB16D diagnostic output module provides sixteen 24V dc sourcing
outputs with open-wire, short-circuit, and user supply reverse polarity
diagnostic features. The module monitors current and voltage at each output
channel.
The module detects:
• an open fault if no current is present at the output terminal.
• a short fault if no voltage is present at the output terminal.
• a reverse-polarity fault if reverse voltage is applied.
When an open or short fault is detected:
• the corresponding channels red indicator is illuminated.
• the module’s red fault indicator is illuminated.
• the module’s open or short error bit is set.
• the module error bit is set.
When a user supply reverse-polarity fault is detected:
You can use the 1794-OB16D diagnostic module with the 1794-TB2,
1794-TB3, or 1794-TB3S terminal base units.
User power can be wired to the (+) voltage and common terminals directly, or
power can be daisychained from the FLEX I/O terminal base units on the
DIN rail. Output channels are not isolated from one another. All 16 channels
share a common return (group isolation from FLEX I/O system-side logic
voltages).
Publication 1794-UM061A-EN-P - July 2006
Loading...
+ 102 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.