Rockwell Automation 1794-IJ2XT User Manual

Installation Instructions
FLEX I/O 2 Input Frequency Module
Cat. No. 1794-IJ2, 1794-IJ2K, and 1794-IJ2XT
(Modules with a K in the last position of the catalog number are conformally coated to meet noxious gas requirements of ISA/ANSI-71.040 1985 Class G3 Environment.)
Important User Information
Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 online at http://literature.rockwellautomation.com between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc. is prohibited.
Throughout this manual we use notes to make you aware of safety considerations.
WARNING
IMPORTANT
ATTENTION
ATTENTION
available from your local Rockwell Automation sales office or
Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
Identifies information that is critical for successful application and understanding of the product.
Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you:
identify a hazard
avoid a hazard
recognize the consequence
Environment and Enclosure
This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes up to 2000 meters (6562 ft) without derating. This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR Publication 11. Without appropriate precautions, there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance. This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame spread rating of 5VA, V2, V1, V0 (or equivalent) if non-metallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications. In addition to this publication, see:
Industrial Automation Wiring and Grounding Guidelines, for additional installation requirements, Allen-Bradley publication 1770-4.1
NEMA Standards publication 250 and IEC publication 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosure.
) describes some important differences
.
WARNING
WARNING
ATTENTION
ATTENTION
ATTENTION
ATTENTION
ATTENTION
If you insert or remove the module while backplane power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
If you connect or disconnect wiring while the field-side power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
Personnel responsible for the application of safety-related Programmable Electronic Systems (PES) shall be aware of the safety requirements in the application of the system and shall be trained in using the system.
Do not remove or replace a Terminal Base unit while power is applied. Interruption of the backplane can result in unintentional operation or machine motion.
FLEX I/O is grounded through the DIN rail to chassis ground. Use zinc plated yellow-chromate steel DIN rail to assure proper grounding. The use of other DIN rail materials (for example, aluminum or plastic) that can corrode, oxidize, or are poor conductors, can result in improper or intermittent grounding. Secure DIN rail to mounting surface approximately every 200 mm (7.8 in.) and use end-anchors appropriately.
Preventing Electrostatic Discharge
This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment:
Touch a grounded object to discharge potential static.
Wear an approved grounding wriststrap.
Do not touch connectors or pins on component boards.
Do not touch circuit components inside the equipment.
Use a static-safe workstation, if available.
Store the equipment in appropriate static-safe packaging when not in
use.
To reduce susceptibility to noise, power analog modules and digital modules from separate power supplies. Do not exceed a total length of 9.8 ft (3m) for dc power cabling.
The following frequency input modules are European Zone 2 approved: 1794-IJ2, 1794-IJ2K, and 1794-IJ2XT
European Zone 2 Certification (The following applies when the product bears the Ex or EEx Marking)
This equipment is intended for use in potentially explosive atmospheres as defined by European Union Directive 94/9/EC and has been found to comply with the Essential Health and Safety Requirements relating to the design and construction of Category 3 equipment intended for use in potentially explosive atmospheres, given in Annex II to this Directive. Compliance with the Essential Health and Safety Requirements has been assured by compliance with EN 60079-15 and EN 60079-0.
Publication 1794-IN049D-EN-P - January 2009
2
WARNING
ATTENTION
Observe the following additional Zone 2 certification requirements.
This equipment is not resistant to sunlight or other sources of UV radiation.
This equipment must be installed in an enclosure providing at least IP54 protection when applied in Zone 2 environments.
This equipment shall be used within its specified ratings defined by Allen-Bradley.
Provision shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 40% when applied in Zone 2 environments.
Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.
Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.
To comply with the CE Low Voltage Directive (LVD), all connections to this equipment must be powered from a source compliant with the following:
Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV).
North American Hazardous Location Approval
The following frequency input modules are North American Hazardous Location approved: 1794-IJ2, 1794-IJ2K, and 1794-IJ2XT.
The following information applies when operating this equipment in hazardous loca tions:
Products marked “CL I, DIV 2, GP A, B, C, D” are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest “T” number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation.
WARNING
EXPLOSION HAZARD
• Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.
• Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.
• Substitution of components may impair suitability for Class I, Division 2.
• If this product contains batteries, they must only be changed in an area known to be nonhazardous.
Informations sur l’utilisation de cet équipement en environnements dangereux :
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu’à une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livré avec des marquages sur sa plaque d’identification qui indiquent le code de température pour les environnements dangereux. Lorsque plusieurs produits sont combinés dans un système, le code de température le plus défavorable (code de température le plus faible) peut être utilisé pour déterminer le code de température global du système. Les combinaisons d’équipements dans le système sont sujettes à inspection par les autorités locales qualifiées au moment de l’installation.
AVERTISSEMENT
RISQUE D’EXPLOSION
• Couper le courant ou s’assurer que l’environnement est classé non dangereux avant de débrancher l'équipement.
• Couper le courant ou s'assurer que l’environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes reliés à cet équipement à l'aide de vis, loquets coulissants, connecteurs filetés ou autres moyens fournis avec ce produit.
• La substitution de composants peut rendre cet équipement inadapté à une utilisation en environnement de Classe I, Division 2.
• S’assurer que l’environnement est classé non dangereux avant de changer les piles.
Installing Your Frequency Input Module
7
3
1
2
6
1. Rotate the keyswitch (1) on the terminal base (2) clockwise to position 1 as required for this type of module.
2. Make certain the flexbus connector (3) is pushed all the way to the left to connect with the neighboring termbase/adapter. You
cannot install the module unless the connector is fully extended.
3. Make sure the pins on the bottom of the module are straight so
they will align properly with the connector in the terminal base.
WARNING
If you remove or insert the module while the backplane power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
4. Position the module (4) with its alignment bar (5) aligned with the groove (6) on the terminal base.
5. Press firmly and evenly to seat the module in the terminal base unit. The module is seated when the latching mechanism (7) is locked into the module.
Connecting Wiring for the 1794-TB3G, and -TB3GS
ATTENTION
ATTENTION
Connect wiring as shown here.
To reduce susceptibility to noise, power analog modules and digital modules from separate power supplies. Do not exceed a length of 3 m (9.8 ft) for DC power cabling.
Do not daisy chain power or ground from this terminal base unit to any AC or
DC digital module terminal base units.
Wiring Connections for the Frequency Input Module using the 1794-TB3G or -TB3GS Terminal Base Unit
Wiring Connections for the 1794-TB3G and -TB3GS
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
3V 6V 24V
16
Chassis Ground
+V COM
24V dc Supply In
+24V dc = Terminals C-34 and C-50 COM = C-35 and C-51 Chassis Ground = Terminals B-16, B-33, C-38, C-40 thru 45, and C-47 NC = No connection
For daisy-chaining: Supply in - C-34 (+) and C-35 (-)
RET 50
500/50
F 24V
24V
500/50
PWR
mV
mV
SEL
SEL
Channel 0 Frequency Input
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33
NC NC
RET 50
500/50
mV
RET
Channel 0 Gate Input
35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51
34
NC
Channel 0 Output Supply
SEL
Chassis
Sply0 Sply0
Ground
RET
mV SEL
Chassis Grounds for Shields
PWR
G 24V
PWR
PWR
24V PWR
F
mV SEL Channel 1 Frequency Input
GOUT 0 OUT 0
Channel 1 Gate Input
mV SEL
RET50
500/50
mV
mV
SEL
SEL
Sply1 Sply1
Channel 1 Output Supply
24V PWR
Chassis Ground
Supply out - C-50 (+) and C-51 (-)
A
3V6VRET50
Chassis
OUT 1 OUT 1
Ground
RET
+V COM
NC
RET
24V dc Supply Out
(1794-TB3G shown)
B
C
4
ATTENTION
During mounting of all devices, be sure that all debris (metal chips, wire strands, etc.) is kept from falling into the module. Debris that falls into the module could cause damage on power up.
5
The module mounts on a 1794-TB3G or -TB3GS terminal base.
Publication 1794-IN049D-EN-P - January 2009
Output Alarm Connections
Channel 0 Terminals
Sply + Sply
RET
Out + Out
1
RET
Channel 1 Terminals
Sply + Sply
RET
1
Out + Out
RET
Supply C-37 C-39 C-46 C-48 Output B-17 B-18 B-31 B-32 1 Connect cable shields to GND connections.
3
Types of Inputs
Frequency 24V DC IEC 1+ Proximity 24V DC Contact Switch
500 mV AC Magnetic Pickup A-7 A-5 A-3 A-8 A-10 A-12 50 mV AC Magnetic Pickup
6V AC Vortex A-2 A-1 A-3 A-13 A-14 A-12 3V AC Vortex A-2 A-0 A-3 A-13 A-15 A-12 Gate
24V DC IEC 1+ Proximity 24V DC Contact Switch
500 mV DC Magnetic Pickup B-24 B-22 B-20 B-25 B-27 B-29 50 mV DC Magnetic Pickup
1 As defined by standard IEC 1131-2. 2 RET not used on 2-wire devices. 3 Add external resistor from 24V to F (A-6) or G (A-9) for wire-off detection (0.4 mA). 4 Add jumper between 50 mV and RET (frequency - channe l 0 = A-4 to A-3; channel 1 = A-11 to A-12)
(gate - channel 0 = B-21 to B-20; channel 1 = B-28 to B-29). 5 Connect cable shields to GND terminals. 6 All 4 RET terminals (ch0 and 1, Freq. and Gate) are internally connected together.
Channel 0 Terminals5Channel 1 Terminals
Power Input
1,2
A-7 A-6 A-3 A-8 A- 9 A-12
3
A-7 A-6 A-3 A-8 A- 9 A-12
4
A-7 A-5 A-3 A-8 A-10 A-1 2
1,2
B-24 B-23 B-20 B-25 B-26 B-29
3
B-24 B-23 B-20 B-25 B-26 B-29
4
B-24 B-22 B-20 B-25 B-27 B-29
RET
6
Power Input
5
RET6GND
5
Resolution and Accuracy
+1Hz or +0.1Hz (depending on frequency range bit setting), or + accuracy specification listed below, whichever is greater.
Resolution % is defined as:
% Resolution =
count frequency X minimum frequency sample time
Accuracy % is defined as:
% Accuracy =
Min. Freq. Sample Time (ms)
2+0.02% +0.0225% +0.0425 +0.1-1.4 +1-14 0.01% 4+0.01% +0.0225% +0.0325 +0.1-1.1 +1-11 0.005% 5+0.008% +0.022 5% +0.0305 +0.1-1.0 +1-10 0.004% 10 +0.004% +0.022 5% +0.0265 +0.1-0.9 +1-9 0.002% 20 + 50 +0.0008% +0.0225% +0.0233 +0.1-0.8 +1-8 0.0004% 100 +0.0004% +0.0225% +0.0229 +0.1-0.8 +1-8 0.0002% 200 +0.0002% +0.0225% +0.0227 +0.1-0.7 +1-7 0.0001% 500 +0.00008% +0. 0225% +0.02258 +0. 1-0.7 +1 -7 0.0000 4% 1000 +0.00004% +0. 0225% +0.02254 +0. 1-0.7 +1 -7 0.0000 2%
100 1 -
Accuracy
Sampling Accuracy
0.002% +0.022 5% +0.0245 +0.1-0.8 +1-8 0.001%
Tim e Base Accuracy
100
minimum frequency sample time
minimum frequency sample time
2
Worst Case Total Accuracy
2
+
Deviation in Hz Due to Total Accuracy
1.0-3276.7 Freq. Range (in Hz)
1
count frequency
1-32767 Freq. Range (in Hz)
Resolution
Input Map
Bit⇒15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
WordRead
0 Frequency 0…32,767 or 0.0…3,276.7 Channel 0 1
% Full Scale 0.03,276.7% Channel 0 or Acceleration -32,76832,767 Channel 0
2
Frequency 032,767 or 0.03,276.7 Channel 1
3
% Full Scale 0.03,276.7% Channel 1 or Acceleration -32,76832,767 Channel 1
4 R R Direction
5 Reserved Diagnostic Status
Ch 0
GS
F/A Ch 0
Ch 0
Channel 0
WO
MPA
R R Directio
Ch 0
Ch 0
n Ch 1
Reserved Diagnostic Status
GS Ch 1
Channel 1 6 Reserved Where:
GS = Gate state F/A = Frequency/Accel alarm WO = Wire-off alarm MPA = Missing pulse alarm R = Reserved
Output Map
Dec.15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Oct. 17 16 15 14 13 12 11 10 7 6 5 4 3 2 1 0
0 CF SSM FR
1 Maximum Frequency 0 - 32.767 or 0.0 - 3,276.7 - or -
Absolute Value of Acceleration - 0 to 32767 Channel 0
2 Frequency Scaling Divisor 0-255 Channel 0 Frequency Scaling Multiplier 0-255
3WOF
G Ch 0
4 Maximum Frequency 0 - 32,767 or 0.0 - 3,276.7 - or -
Absolute Value of Acceleration - 0 to 32,767 Channel 1
5 Frequency Scaling Divisor 0-255 Channel 1 Frequency Scaling Multiplier 0-255
6WOF
G Ch 1
7 Reserved Where:CF = Communication Fault
SSM = Safe state mode FR = Frequency range MPM = Missing pulse multiplier LF = Local Fault mode F/AAS = Frequency/Accel alarm select WOFF = Wire-off fault frequency WOFG = Wire-off fault gate WOFM = Wire-off fault mode IGI = Invert gate input IFI = Invert frequency input ACT = Acceleration calculation time MPDM = Missing pulse delay multiplier R = Reserved
WOF F Ch 0
WOF F Ch 1
Ch 0
IGI Ch 0
IGI Ch 1
Number of pulses to terminate sampling 0-7 Ch 0
IFI
Minimum Frequency
Ch
Sample Time 0-15
0
Ch 0
IFI
Minimum Frequency
Ch
Sample Time 0-15
1
Ch 1
MPM 0-3 Ch 0
RLFFR
Ch 1
Channel 0 Init
ACT
St
0-3
Up
Ch 0
Ch 0
Channel 1 Init
ACT
St
0-3
Up
Ch 1
Ch 1
Number of pulses to terminate sampling 0-7 Ch 1
F/AA
MPDM
S Ch
0-3 Ch 0
0
F/AA
MPDM
S Ch
0-3 Ch 1
1
F/A Ch 1
WO Ch 1
MPA Ch 1
MPM 0-3 Ch 1
WOFM 0-3 Ch 0
WOFM 0-3 Ch 1
Publication 1794-IN049D-EN-P - January 2009
4
Status Indicators
A
llen
-
B
radley
FREQUENCY
INPUT 2 CHANNEL
FREQ GATE
F0F
0
=
Input indicator.
A B =
Insertable label for writing individual I/O assignments.
C =
Wire-Off Fault indicator.
D =
Output indicator.
E =
Power/status indicator - indicates power applied to module and status of module.
FREQ GATE
1F 1F
B
C DA
OUT0OUT
1794-IJ2
1
E
1
OK
1794-IJ2 shown
When an input indicator (yellow) is lighted, it indicates that a valid signal (active high or active low) is present at one of the Input terminals. When wire-off detection is enabled, and a wire-off fault is detected (24 V DC IEC 1+ input terminal only), a fault indicator (red) is blinked/flashed at a rate of 1Hz to signal a fault condition. A wire-off fault signal will also be sent to the backplane. A flashing red fault indication means a valid wire-off condition for a 24 V DC IEC 1+ Input or a 24 V DC contact switch input with a shunt resistor. When an output indicator is yellow, the logic is driving an output alarm On. After detecting a fault, the internal circuitry will set the output data to the appropriate safe state, as defined by the module data table. Safe state control may be adapter dependent. The input and output indicators are on the field side of the isolation path, and display the logic state of the actual microcontroller input and output. The status indicator initially powers up as solid green, indicating the power supply is operating and internal diagnostic tests are being performed. After a successful power up test, the indicator remains green. The indicator turns red in about 1.5 s if there is an internal diagnostics error. The module is operating correctly when the green OK indicator is on. A red OK indicator shows that the module is in a Faulted condition (internal error).
Indicator Condition Operating Description
Input (0, 1)
(Freq, or Gate)
Fault (F)
(Freq, or Gate)
Output Alarm
(0, 1)
Status (OK) Off (Dark) 24V Power Turned Off, or 5V Logic Power Problem
Off (Dark) Input Turned Off, Input Not Used, or Wire Disconnected
On (Yellow) Input Turned On (Active High or Active Low if Inverted)
Off (Dark) Wire Connected, Normal Operation or Detection Disabled
On (Red Flashing)
Off (Dark) Output Alarm Turned Off
On (Yellow) Output Alarm Turned On (Logic Drive On)
Solid Green Module OK, Normal Operating Mode
Solid Red Module Fault, Outputs Disabled
Wire Disconnected, Fault Condition (for IEC 1+ Proximity switch or switch contacts with shunt resistor)
Diagnostics
The frequency input module returns diagnostics to the PLC processor in word 5 of the BTR file. These diagnostics give you information on the status or condition of the module.
BTR Word 5
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
word 5
See Table for diagnostics
44760
Input
Bit Definition
Word
Word 5 Bits
00 - 03
Specifications - Frequency Input Module, Cat. Nos. 1794-IJ2, 1794-IJ2K, and 1794-IJ2XT
Diagnostic Status - indciates the response from t he module; a normal or non-normal operating condition.
Bit 03020100
00000 = Normal Operation (No Failure) 00011 = Calibration Failure 00102 = Configuration Failure
00113 = Message Failure 01004 = Lead Break Detection Hardware Failure 01015 = Major Hardware Failure 01106 = EEPROM Failure 01117 = RAM Failure 10008 = ROM Failure 10019 = Calculation Failure
1010 - 1111 10 - 15 = Not used
A Minimum Frequency Sample Time value other than 0-9 was selected.
The actual Frequency is greater than 32,767 Hz or 3,276.7 Hz (overange). The scaled Frequency is greater than 32,767 Hz or 3,27 6.7 Hz (overange). The % Full Scale calculation (based on Maximum Frequency) is > 3,276.7%.
Input Specifications
Number of input channels
Number of inputs per channel
Input frequency Maximum - 1-32 kHz w/sine wave; 1-32 kHz w/square wave input Frequency value Maximum 32,767 or 3,276.7 (dependent on range) Input pulse width 20 μs Resolution/Accuracy Refer to Resolution/Accuracy table On-stage voltage, min 10V (24V IEC+1 proximity, encoder input or switch inputs) On-state voltage, nom
(selected by terminal base connections)
On-state voltage, max Limited to isolated 24V DC power supply maximum On-state current
minimum nominal
maximum Off-state current, min 1.5 mA into 24V DC IEC+ terminal Off-state voltage, max 5.0V DC on 24V DC IEC+1 terminal Wire-off detection 0.4 mA for proximity, encoder or contact switch with 50 kΩ shunt resistor Frequency input
impedance
Gate input impedance >5 KΩ for 50 mV Extended Magnetic Pickup
Output Specifications (meets IEC 1A 24V DC output specifications) Number of outputs 2 isolated Output voltage source Customer supplied Output voltage
minimum
nominal
maximum Off-state voltage, max 31.2V DC On-state current 1 mA per output minimum
Surge current 2 A for 50 ms, repeatable every 2 s Off-state leakage Less than 300 μA at 31.2V DC maximum
2
2 - Frequency and Gate (gate used to establish direction)
50 mV AC, 28V AC peak - Extended Magnetic Pickup 500 mV AC, 28V AC peak - Magnetic Pickup < 3V - Vortex Flowmeter low range > 6V - Vortex Flowmeter high range 24V DC IEC+1 proximity or encoder input 24V DC Contact Switch input
2.0 mA
9.0 mA
10.0 mA
>5 KΩ for 50 mV Extended Magnetic Pickup >5 KΩ for 500 mV Magnetic Pickup >10 KΩ for 3V Vortex Flowmeter low range >10 KΩ for 6V Vortex Flowmeter high range >2.5 KΩ for 24V DC IEC+1 proximity or encoder input >2.5 KΩ for 24V DC Contact Switch input
>5 KΩ for 500 mV Magnetic Pickup >2.5 KΩ for 24V DC IEC+1 proximity or encoder input >2.5 KΩ for 24V DC Contact Switch input
10V DC 24V DC
31.2V DC
1.0 A per channel sourced out of module maximum Current Limited - All outputs can be on simultaneously without derating
Publication 1794-IN049D-EN-P - January 2009
5
On-state voltage drop 0.9V DC at 1 A Output control Outputs individually assignable to: Frequency, % Full Scale or Acceleration
Output switching time Triggered by frequency alarm or acceleration alarm
General Module location Cat. No. 1794-TB3G and -TB3GS Terminal Base Units External DC power
Voltage range Supply voltage Supply current
Isolated DC power
Voltage range Supply voltage Supply current Peak AC ripple
Dimensions (with module installed in base)
Isolation voltage 50V (continuous), Basic Insulation Type
Processing time <4 ms Flexbus current 30 mA at 5V DC Power dissipation 4.6W maximum at 31.2V DC Thermal dissipation Maximum 15.6 BTU/hr at 31.2V DC Indicators (field side
driven, logic side indication)
Keyswitch Position 1 Wire size Determined by installed terminal base
Wiring category
Wire type Shielded on signal ports Terminal screw torque Determined by installed terminal base Enclosure type rating None (open-style) North American temp
code IEC temp code T4
Alarm
Turn on: Less than 0.5 ms Turn off: Less than 1 ms
(Input for +5V logic and 24V DC/DC converters)
19.2…31.2V DC (includes 5% AC ripple) 24V DC nominal 220 mA @ 19.2V DC; 180 mA @ 24V DC; 140 mA @ 31.2V DC
(Output to sensors and encoders)
21.6…26.4V DC 24V DC nominal 0-60 mA maximum @ 24V DC (4 devices @ 15 mA = 60 mA) 100 mV maximum
94H x 94W x 69D mm (3.7H x 3.7W x 2.7D in.)
Type tested at 1365V AC for 60 s, between field side and system and individual channels
1 green/red power/status indicator 4 yellow status indicators (Freq 0, 1, Gate 0, 1) 4 red wire-off indicators (Freq 0, 1, Gate 0, 1) 2 yellow status indicators (Out 0, Out 1) - logic side
1
2 - on signal ports 3 - on power ports
T4A
Environmental
Operating temperature IEC 60068-2-1 (Test Ad, Operating Cold),
Non-operating temperature
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
Vibration IEC 60068-2-6 (Test Fc, Operating):
Operating shock IEC 60068-2-27 (Test Ea, Unpackaged Shock):
Non-operating shock IEC 60068-2-27 (Test Ea, Unpackaged Shock):
Emissions CISPR 11:
ESD immunity IEC 61000-4-2:
Radiated RF immunity IEC 61000-4-3:
EFT/B immunity IEC 61000-4-4:
IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock): 0…55 °C (32…131 °F) (1794-IJ2 and 1794-IJ2K)
-20…70 °C (-4…158 °F) (1794-IJ2XT) IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Non-operating Thermal Shock):
-40…85 °C (-40…185 °F)
5…95% noncondensing
5 g @ 10…500 Hz
30 g
50 g
Group 1, Class A (with appropriate enclosure)
4 kV contact discharges (1794-IJ2 and 1794-IJ2K) 6 kV contact discharges (1794-IJ2XT) 8 kV air discharges
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
±2 kV at 5 kHz on power ports ±2 kV at 5 kHz on shielded signal ports
Surge transient immunity
Conducted RF immunity
IEC 61000-4-5: ±2 kV line-earth(CM) on shielded signal ports
IEC 61000-4-6: 10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz on shielded signal ports
Certifications
Certifications (when product is
2
marked)
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL
CSA (1794-IJ2 and 1794-IJ2K)
CE European Union 2004/108/EC EMC Directive, compliant with:
C-Tick Australian Radiocommunications Act, compliant with:
Ex European Union 94/9/EC ATEX Directive, compliant with:
TÜV TÜV Certified for Functional Safety:
1 Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication
2 See the Product Certification link at http://www.ab.com for Declaration of Conformity, Certificates, and other certification details.
Valu e
File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.
CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
AS/NZS CISPR 11; Industrial Emissions
EN 60079-15; Potentially Explosive Atmospheres, Protection "n" (II 3 G Ex nA IIC T4 X) EN 60079-0; General Requirements (Zone 2)
up to and including SIL 2
1770-4.1.
Publication 1794-IN049D-EN-P - January 2009
Publication 1794-IN049D-EN-P - January 2009 6 PN-38821
Supersedes Publication 1794-IN049C-EN-P - June 2004 Copyright © 2009 Rockwell Automation, Inc. All rights reserved.
Loading...