FLEX I/O 5V dc TTL Digital Input and
Output Modules
1794-IG16, 1794-OG16
Important User Information
Solid state equipment has operational characteristics differing from those of
electromechanical equipment. Safety Guidelines for the Application, Installation and
Maintenance of Solid State Controls (Publication
Automation sales office or online at http://www.literature.rockwellautomation.com) describes
some important differences between solid state equipment and hard-wired electromechanical
devices. Because of this difference, and also because of the wide variety of uses for solid
state equipment, all persons responsible for applying this equipment must satisfy themselves
that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or
consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes.
Because of the many variables and requirements associated with any particular installation,
Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the
examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of
information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of
Rockwell Automation, Inc., is prohibited.
Throughout this manual we use notes to make you aware of safety considerations.
WARNING
IMPORTANT
ATTENTION
Identifies information about practices or circumstances that can cause an
explosion in a hazardous environment, which may lead to personal injury or
death, property damage, or economic loss.
Identifies information that is critical for successful application and understanding
of the product.
Identifies information about practices or circumstances that can lead to
personal injury or death, property damage, or economic loss. Attentions
help you:
• identify a hazard
• avoid a hazard
• recognize the consequence
ATTENTION
Environment and Enclosure
This equipment is intended for use in a Pollution Degree 2 industrial
environment, in overvoltage Category II applications (as defined in IEC
publication 60664-1), at altitudes up to 2000 meters (6562 ft) without
derating.
This equipment is considered Group 1, Class A industrial equipment
according to IEC/CISPR Publication 11. Without appropriate precautions,
there may be potential difficulties ensuring electromagnetic compatibility
in other environments due to conducted as well as radiated disturbance.
This equipment is supplied as open-type equipment. It must be mounted
within an enclosure that is suitably designed for those specific
environmental conditions that will be present and appropriately designed
to prevent personal injury resulting from accessibility to live parts. The
enclosure must have suitable flame-retardant properties to prevent or
minimize the spread of flame, complying with a flame spread rating of
5VA, V2, V1, V0 (or equivalent) if non-metallic. The interior of the
enclosure must be accessible only by the use of a tool. Subsequent
sections of this publication may contain additional information regarding
specific enclosure type ratings that are required to comply with certain
product safety certifications.
In addition to this publication, see:
• Industrial Automation Wiring and Grounding Guidelines, for
additional installation requirements, Allen-Bradley publication
1770-4.1.
• NEMA Standards publication 250 and IEC publication 60529, as
applicable, for explanations of the degrees of protection provided by
different types of enclosure.
SGI-1.1 available from your local Rockwell
ATTENTION
ATTENTION
WARNING
WARNING
FLEX I/O is grounded through the DIN rail to chassis ground. Use zinc
plated yellow-chromate steel DIN rail to assure proper grounding. The use
of other DIN rail materials (for example, aluminum or plastic) that can
corrode, oxidize, or are poor conductors, can result in improper or
intermittent grounding. Secure DIN rail to mounting surface approximately
every 200 mm (7.8 in.) and use end-anchors appropriately.
Preventing Electrostatic Discharge
This equipment is sensitive to electrostatic discharge, which can cause
internal damage and affect normal operation. Follow these guidelines
when you handle this equipment:
• Touch a grounded object to discharge potential static.
• Wear an approved grounding wriststrap.
• Do not touch connectors or pins on component boards.
• Do not touch circuit components inside the equipment.
• If available, use a static-safe workstation.
• Store the equipment in appropriate static-safe packaging when not
in use.
If you insert or remove the module while backplane power is on, an
electrical arc can occur. This could cause an explosion in hazardous location
installations. Be sure that power is removed or the area is nonhazardous
before proceeding.
Do not connect directly to line voltage. Line voltage must be supplied by a
suitable, approved isolating transformer or power supply having short circuit
capacity not exceeding 100 VA maximum or equivalent.
North American Hazardous Location Approval
The following modules are North American Hazardous Location approved:
1794-IG16, 1794-OG16.
The following information applies
when operating this equipment in
hazardous locations:
Products marked “CL I, DIV 2, GP A, B, C, D”
are suitable for use in Class I Division 2
Groups A, B, C, D, Hazardous Locations and
nonhazardous locations only. Each product is
supplied with markings on the rating
nameplate indicating the hazardous location
temperature code. When combining
products within a system, the most adverse
temperature code (lowest “T” number) may
be used to help determine the overall
temperature code of the system.
Combinations of equipment in your system
are subject to investigation by the local
Authority Having Jurisdiction at the time of
installation.
WARNING
EXPLOSION HAZARD
• Do not disconnect equipment unless
power has been removed or the area
is known to be nonhazardous.
• Do not disconnect connections to
this equipment unless power has been
removed or the area is known to be
nonhazardous. Secure any external
connections that mate to this
equipment by using screws, sliding
latches, threaded connectors, or other
means provided with this product.
• Substitution of components may
impair suitability for Class I,
Division 2.
• If this product contains batteries,
they must only be changed in an area
known to be nonhazardous.
Informations sur l’utilisation de cet
équipement en environnements dangereux :
Les produits marqués "CL I, DIV 2, GP A, B, C, D"
ne conviennent qu’à une utilisation en
environnements de Classe I Division 2 Groupes
A, B, C, D dangereux et non dangereux. Chaque
produit est livré avec des marquages sur sa
plaque d’identification qui indiquent le code de
température pour les environnements
dangereux. Lorsque plusieurs produits sont
combinés dans un système, le code de
température le plus défavorable (code de
température le plus faible) peut être utilisé pour
déterminer le code de température global du
système. Les combinaisons d’équipements dans
le système sont sujettes à inspection par les
autorités locales qualifiées au moment de
l’installation.
AVERTISSEMENT
RISQUE D’EXPLOSION
• Couper le courant ou s’assurer que
l’environnement est classé non dangereux
avant de débrancher l'équipement.
• Couper le courant ou s'assurer que
l’environnement est classé non dangereux
avant de débrancher les connecteurs.
Fixer tous les connecteurs externes reliés
à cet équipement à l'aide de vis, loquets
coulissants, connecteurs filetés ou autres
moyens fournis avec ce produit.
• La substitution de composants peut
rendre cet équipement inadapté à une
utilisation en environnement de Classe I,
Division 2.
• S’assurer que l’environnement est
classé non dangereux avant de changer
les piles.
Publication 1794-IN119A-EN-P - June 2008
2 FLEX I/O 5V dc TTL Digital Input and Output Modules
IMPORTANT
To comply with North American restrictions, all connected I/O must be
powered from a source compliant with the following:
Class 2
WARNING
If you connect or disconnect wiring while the field-side power is on, an
electrical arc can occur. This could cause an explosion in hazardous
location installations. Be sure that power is removed or the area is
nonhazardous before proceeding.
Do not remove or replace a Terminal Base unit when power is applied.
Interruption of the backplane can result in unintentional operation or
machine motion.
Connect Wiring for your Module
(using a 1794-TB3 or -TB3S Terminal Base)
1. Connect individual input or output wiring to numbered terminals on the
0-15 row (A) as indicated in Ta ble 1.
2. Connect the associated input and output devices as indicated in the wiring
diagrams.
3. Connect +V dc power to terminal 34 on the 34-51 row (C).
4. Connect dc common to terminal 16 on the 16-33 row (B).
5. If daisychaining power to the next terminal base, connect a jumper from
terminal 51 (+V dc) on this base unit to terminal 34 on the next base unit.
7
1
2
6
5
6. If continuing dc common to the next base unit, connect a jumper from
terminal 33 (common) on this base unit to terminal 16 on the next base
unit.
Table 1 Wiring Connections for 1794-IG16 and 1794-OG16
ChannelSignalPower TerminalCommon Terminal
0A-0C-35B-17
1A-1C-36B-18
2A-2C-37B-19
3A-3C-38B-20
4A-4C-39B-21
5A-5C-40B-22
6A-6C-41B-23
7A-7C-42B-24
8A-8C-43B-25
9A-9C-44B-26
10A-10C-45B-27
11A-11C-46B-28
12A-12C-47B-29
13A-13C-48B-30
14A-14C-49B-31
15A-15C-50B-32
+V DCC-34 thru C-51 are internally conn ected together.
CommonB-16 thru B-33 are internally conn ected together.
ATTENTION
During mounting of all devices, be sure that all debris (metal chips, wire
strands, etc.) is kept from falling into the module. Debris that falls into the
module could cause damage on power up.
1. Rotate the keyswitch (1) on the terminal base (2) clockwise to position 1 as
required for this type of module.
2. Make certain the flexbus connector (3) is pushed all the way to the left to
connect with the neighboring terminal base/adapter.
You cannot install the module unless the connector is fully extended.
3. Make sure the pins on the bottom of the module are straight so they will
align properly with the connector in the terminal base.
4. Position the module (4) with its alignment bar (5) aligned with the groove
(6) on the terminal base.
5. Press firmly and evenly to seat the module in the ter minal base unit. The
module is seated when the latching mechanism (7) is locked into the
module.
Capacitors shown must be 0.01µF and rated for 2000 Volts (minimum).
I/O cable length must be less than 10 meters.
Outputs
Commons
Voltage
A
B
-V
Common
Voltage
Out +V
(1794-TB3 shown)
A
-V
Common
(1794-TB3 shown)
C
B
Volt ag e
Out +V
C
Publication 1794-IN119A-EN-P - June 2008
IMPORTANT
To comply with the CE Low Voltage Directive (LVD), all connected I/O must
be powered from a source compliant with the following: Safety Extra Low
Voltage (SELV) or Protected Extra Low Voltage (PELV).
Ground Your Module
Use shielded communication cable (Belden #8761). The Belden cable has two signal
wires (black and clear), one drain wire, and a foil shield. The drain wire and foil
shield must be grounded at one end of the cable.
Foil Shield
Black Wire
Insulation
Drain Wire
Clear Wire
IMPORTANT
Do not ground the drain wire and foil shield at both ends of the cable.
Configure Your Input Module
You configure your input module by setting bits in the configuration word (word 3).
FLEX I/O 5V dc TTL Digital Input and Output Modules 3
Specifications - 1794-IG16 Flex I/O 5V dc TTL Digital Input Module
SpecificationDescription
Number of I/O channels16, nonisolated
Module locationCat. No. 1794-TB3, -TB3S
On-state voltage-0.2V dc...0.8V dc typical
Input current3.7mA nominal @ 5V dc
Off-state voltage2.0...5.5V dc typical
Off-state current4.1mA maximum
Input impedance1.4K ohms minimum
Isolation voltage50V (continuous), Basic Insulation Type, between field side and syste m
Flexbus current40mA
Power dissipation1.4W maximum @ 5.5V dc
Thermal dissipation4.78 BTU/hr @ 5.5V dc
Indicators (field side indication,
customer device driven)
Input filter time
(1)
(1)
Off to On
On to Off
Input off-to-on filter time is the time from a valid input signal to recognition by the module.
Input on-to-off filter t ime is time from the input signal dropping below the valid level to recognition by the module.
IMPORTANT
TTL inputs are inverted
(-0.2…0.8V dc=logic low voltage=1=on
2.0…5.5V dc=logic high voltage=0=off).
Use a NOT instruction in the ladder program to convert to traditional
true=High logic.
Specifications - 1794-OG16 Flex I/O 5V dc TTL Digital Output Module
SpecificationDescription
Number of I/O channels16, nonisolated
Module locationCat. No. 1794-TB3, -TB3S
On-state voltage0V dc...0.4V dc
Output current rating24mA maximum per channel
Off-state voltage4.5V...5.5V dc typical
On-state current0.15mA minimum per channel
Off-state leakage0.1mA maximum
Isolation voltage50V (continuous), Basic Insulation Type, between field side and syste m
(1)
Output signal delay
(Resistive load)
Flexbus current80mA
Power dissipation0.8W maximum @ 5.5V dc
Thermal dissipation3.41 BTU/hr maximum @ 5.5V dc
Pilot duty ratingNot rated
Indicators (field side indication,
customer device driven)
(1)
The time from the receipt of an on or off command to the output actually turning on or off.
IMPORTANT
TTL outputs are inverted
(On=1=logic low voltage=0…0.4V dc;
Off=0=logic high voltage=4.5…5.5V dc).
Use a NOT instruction in the ladder program to convert to traditional
true=High logic.
4.1mA maximum @ 5V dc
1.5K ohms typical
Type tested at 707V dc for 60 s, between field side and system
No isolation between individual channels
16 yellow status indicators
0.25ms, 0.5ms, 1ms, 2ms, 4ms, 8ms, 16ms, 32ms
0.25ms, 0.5ms, 1ms, 2ms, 4ms, 8ms, 16ms, 32ms
24mA maximum per channel
Type tested at 707V dc for 60 s, between field side and system
No isolation between individual channels
Off to On - 0.25ms maximum
On to Off - 0.5ms maximu m
16 yellow status indicators
Publication 1794-IN119A-EN-P - June 2008
General Specifications - 1794-IG16, 1794-OG16
SpecificationDescription
Terminal base screw torqueDetermined by installed terminal base
Dimensions (with module installed)
H x W x D
External dc power supply voltage 5V dc nominal
External dc power voltage range 4.5...5.5V dc
External dc power supply current 1794-IG16 - 210mA max @ 5V dc
North American temp codeT4A
Keyswitch position1
Enclosure type ratingNone (open-style)
Wire typeShielded (Power and I/O)
Wire sizeDetermined by installed terminal base
Wiring category
(1)
(1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication 1770-4.1
10V/m with 1 kHz sine-wave 80% AM fro m 80...2000 MHz
10V/m with 200 Hz 50% Pulse 100% A M at 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz
1V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz
±2k V at 5kHz on power ports
±2k V at 5kHz on signal ports
±2 kV line-earth(CM) on power ports
10V rms with 1 kHz sine-wave 80% AM from 150 kH z…80 MHz
Certifications
Certifications (when product is marked)
c-UL-usUL Listed Industrial Control Equipme nt, certified for US and Canada.
CEEuropean Union 2004/108/EC EMC Di rective, compliant with:
See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and othe r certification
details.
See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations,
certified for U.S. and Canada. See UL File E19 4810.
EN 61326; Meas./Control/Lab., Industria l Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clau se 8, Zone A & B)
AS/NZS CISPR 11; Industrial Emissions
(1)
Publication 1794-IN119A-EN-P - June 2008 4PN-24535