Solid state equipment has operational characteristics differing from those of electromechanical
equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State
Controls (Publication
http://literature.rockwellautomation.com) describes some important differences between solid state
equipment and hard-wired electromechanical devices. Because of this difference, and also because
of the wide variety of uses for solid state equipment, all persons responsible for applying this
equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential
damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of
the many variables and requirements associated with any particular installation, Rockwell
Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and
diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information,
circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of
Rockwell Automation, Inc., is prohibited.
Throughout this manual we use notes to make you aware of safety considerations.
WARNING
ATTENTION
IMPORTANT
ATTENTION
WARNING
WARNING
SGI-1.1 available from your local Rockwell Automation sales office or online at
Identifies information about practices or circumstances that can cause an
explosion in a hazardous environment, which may lead to personal injury or
death, property damage, or economic loss.
Identifies information about practices or circumstances that can lead to
personal injury or death, property damage, or economic loss. Attentions help
you:
• identify a hazard
• avoid a hazard
• recognize the consequence
Identifies information that is critical for successful application and
understanding of the product.
Environment and Enclosure
This equipment is intended for use in a Pollution Degree 2 industrial
environment, in overvoltage Category II applications (as defined in IEC
60664-1), at altitudes up to 2000 m (6562 ft) without derating.
This equipment is considered Group 1, Class A industrial equipment according
to IEC/CISPR 11. Without appropriate precautions, there may be difficulties
with electromagnetic compatibility in residential and other environments due
to conducted and radiated disturbances.
This equipment is supplied as open-type equipment. It must be mounted within
an enclosure that is suitably designed for those specific environmental
conditions that will be present and appropriately designed to prevent personal
injury resulting from accessibility to live parts. The enclosure must have
suitable flame-retardant properties to prevent or minimize the spread of flame,
complying with a flame spread rating of 5VA, V2, V1, V0 (or equivalent) if
non-metallic. The interior of the enclosure must be accessible only by the use
of a tool. Subsequent sections of this publication may contain additional
information regarding specific enclosure type ratings that are required to
comply with certain product safety certifications.
In addition to this publication, see:
• Industrial Automation Wiring and Grounding Guidelines, for additional
• NEMA Standards 250 and IEC 60529, as applicable, for explanations of
.
the degrees of protection provided by different types of enclosure.
If you insert or remove the module while backplane power is on, an electrical
arc can occur. This could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
If you connect or disconnect wiring while the field side power is on, an
electrical arc can occur. This could cause an explosion in hazardous location
installations. Be sure that power is removed or the area is nonhazardous
before proceeding.
European Hazardous Location Approval
ATTENTION
ATTENTION
FLEX I/O is grounded through the DIN rail to chassis ground. Use zinc plated
yellow-chromate steel DIN rail to assure proper grounding. The use of other DIN
rail materials (for example, aluminum or plastic) that can corrode, oxidize, or are
poor conductors, can result in improper or intermittent grounding. Secure DIN
rail to mounting surface approximately every 200 mm (7.8 in.) and use
end-anchors appropriately.
Prevent Electrostatic Discharge
This equipment is sensitive to electrostatic discharge, which can cause internal
damage and affect normal operation. Follow these guidelines when you handle
this equipment:
• Touch a grounded object to discharge potential static.
• Wear an approved grounding wriststrap.
• Do not touch connectors or pins on component boards.
• Do not touch circuit components inside the equipment.
• Use a static-safe workstation, if available.
• Store the equipment in appropriate static-safe packaging when not in
use.
ATTENTION
ATTENTION
ATTENTION
European Zone 2 Certification (The following applies when the product bears the Ex
or EEx Marking)
This equipment is intended for use in potentially explosive atmospheres as defined by European
Union Directive 94/9/EC and has been found to comply with the Essential Health and Safety
Requirements relating to the design and construction of Category 3 equipment intended for use
in potentially explosive atmospheres, given in Annex II to this Directive.
Compliance with the Essential Health and Safety Requirements has been assured by compliance
with EN 60079-15 and EN 60079-0.
WARNING
Personnel responsible for the application of safety-related programmable
electronic systems (PES) shall be aware of the safety requirements in the
application of the system and shall be trained in using the system.
To comply with the CE Low Voltage Directive (LVD), all connections to this
equipment must be powered from a source compliant with the following:
Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV).
Do not remove or replace a Terminal Base unit while power is applied.
Interruption of the backplane can result in unintentional operation or machine
motion.
Observe the following additional Zone 2 certification requirements.
• This equipment is not resistant to sunlight or other sources of UV
radiation.
• This equipment must be installed in an enclosure providing at least IP54
protection when applied in Zone 2 environments.
• This equipment shall be used within its specified ratings defined by
Allen-Bradley.
• Provision shall be made to prevent the rated voltage from being
exceeded by transient disturbances of more than 40% when applied in
Zone 2 environments.
• Secure any external connections that mate to this equipment by using
screws, sliding latches, threaded connectors, or other means provided
with this product.
• Do not disconnect equipment unless power has been removed or the
area is known to be nonhazardous.
Publication 1794-IN129B-EN-P - April 2009
Page 2
2
North American Hazardous Location Approval
The following adapters are North American Hazardous Location approved:
1794-IF4IXT, 1794-OF4IXT, 1794-IF2XOF2IXT
The following information applies when
operating this equipment in hazardous
locations:
Products marked “CL I, DIV 2, GP A, B, C, D” are
suitable for use in Class I Division 2 Groups A, B, C,
D, Hazardous Locations and nonhazardous locations
only. Each product is supplied with markings on the
rating nameplate indicating the hazardous location
temperature code. When combining prod ucts
within a system, the most adverse temperature
code (lowest “T” number) may be used to help
determine the overall temperature co de of the
system. Combinations of equipment in your system
are subject to investigation by the local Authority
Having Jurisdiction at the time of installation.
WARNING
EXPLOSION HAZARD
• Do not disconnect equipment
unless power has been
removed or the area is known
to be nonhazardous.
• Do not disconnect
connections to this
equipment unless power has
been removed or the area is
known to be nonhazardous.
Secure any external
connections that mate to this
equipment by using screws,
sliding latches, threaded
connectors, or other means
provided with this product.
• Substitution of components
may impair suitability for
Class I, Division 2.
• If this product contains
batteries, they must only be
changed in an area known to
be nonhazardous.
Informations sur l’utilisation de cet équipement
en environnements dangereux :
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne
conviennent qu’à une utilisation en environnements
de Classe I Division 2 Groupes A, B, C, D dang ereux et
non dangereux. Chaque produit est livré avec des
marquages sur sa plaque d’identification qui indiquent
le code de température pour les environnemen ts
dangereux. Lorsque plusieurs prod uits sont combinés
dans un système, le code de température le plus
défavorable (code de température le plus faib le) peut
être utilisé pour déterminer le code de température
global du système. Les combinaisons d’équipements
dans le système sont sujettes à inspection par les
autorités locales qualifiées au moment de
l’installation.
AVERTISSEMENT
RISQUE D’EXPLOSION
• Couper le courant ou s’assurer
que l’environnement est classé
non dangereux avant de
débrancher l'équipement.
• Couper le courant ou s'assurer
que l’environnement est classé
non dangereux avant de
débrancher les connecteurs.
Fixer tous les connecteurs
externes reliés à cet
équipement à l'aide de vis,
loquets coulissants,
connecteurs filetés ou autres
moyens fournis avec ce
produit.
• La substitution de composants
peut rendre cet équipement
inadapté à une utilisation en
environnement de Classe I,
Division 2.
• S’assurer que l’environnement
est classé non dangereux
avant de changer les piles.
Install Your Analog Input Module
7
3
1
4. Position the module (4) with its alignment bar (5) aligned with the
groove (6) on the terminal base.
5. Press firmly and evenly to seat the module in the terminal base
unit. The module is seated when the latching mechanism (7) is
locked into the module.
Connect individual input/output wiring to numbered terminals on
the 0-15 row (A) as indicated in the Wire Connections table.
Use Belden 8761 cable for signal wiring.
1794-TBN - Connect individual input/output wiring to even
numbered terminals on the 16-33 row (B) as indicated in the
following table.
Use Belden 8761 cable for signal wiring.
ATTENTION
2. 1794-TB2, -TB3, -TB3S, -TB3T, -TB3TS - Connect each channel
3. Connect any signal wiring shields to functional ground as near as
4. Connect the +V DC power to terminal 34 on the 34-51 row (C) and
ATTENTION
Connect only one current or one voltage signal per channel. Do not connect
both current and voltage on one channel.
signal return to numbered terminals on 0-15 row (A) as indicated
in the following table. Use Belden 8761 cable for signal wiring.
1794-TBN - Connect each channel signal return to odd numbered
terminals on row (C) as indicated in the following table.
possible to the module.
1794-TB3T or -TB3TS only: Connect cable shield to terminate
C-39 through C-46 (earth ground).
-V common/return to terminal 16 on the B row.
To reduce susceptibility to noise, power analog modules and digital modules
from separate power supplies.
2
6
4
ATTENTION
The module mounts on a 1794 terminal base.
1. Rotate the keyswitch (1) on the terminal base (2) clockwise to
2. Make certain the flexbus connector (3) is pushed all the way to the
3. Make sure the pins on the bottom of the module are straight so
During mounting of all devices, be sure that all debris (such as metal chips, or
wire strands) is kept from falling into the module. Debris that falls into the
module could cause damage on
power up.
Keep a minimum of 25 mm (1 in.) of space on the top and bottom of the
module, for adequate ventilation between equipment.
position 3 as required for 1794-IF4IXT, position 4 for 1794-OF4IXT,
and position 5 for 1794-IF2XOF2IXT.
left to connect with the neighboring terminal base/adapter.
You cannot install the module unless the connector is fully
extended.
they will align properly with the connector in the terminal base.
5
5. If daisychaining +V power to the next terminal base, connect a
jumper from terminal 51 (+V DC) on this base unit to terminal 34
on the next base unit.
6. If continuing DC common (-V) to the next base unit, connect a
jumper from terminal 33 (common) on this base unit to terminal 16
on the next base unit.
Wire Connections for 1794-IF4IXT, 1794-OF4IXT, 1794-IF2XOF2IXT Modules
1794-TB2, -TB3, -TB3S - Terminals B-16 through B-33 are internally
connected in the terminal base unit.
1794-TBN - Terminals B-16 and B-33 are internally connected in the
terminal base unit.
1794-TB3T, -TB3TS - Terminals 16, 17, 19, 21, 23, 25, 27, 29, 31 and 33 are
internally connected in the terminal base unit.
1794-TB3, -TB3S - Terminals 34 through 51 are internally connected in the
terminal base unit.
1794-TB3T, -TB3TS - Terminals 34, 35, 50 and 51 are internally connected
in the terminal base unit.
1794-TBN, -TB2 - Terminals 34 and 51 are internally connected in the
terminal base unit.
1794-TB3T, -TB3TS - Terminals 39 through 46 are internally connected to
chassis ground.
Label
Markings
1794-TB2, -TB3, -TB3S, -TB3T,
-TB3TS
Terminal Shield (1794-TB3T,
-TB3TS
1794-TBN
Terminal
7. 1794-TB2, -TB3, and -TB3S - Connect wiring shields to functional
earth ground as near as possible to the module.
1794-TB2, 1794-TB3, 1794-TB3S, 1794-TB3T and 1794-TB3TS Terminal Base
Wiring
Word 0Analog Value Channel 0
Word 1Analog Value Channel 1
Word 2Analog Value Channel 2
Word 3Analog Value Channel 3
Word 4Real Time Sample
Word 5PU FP CF 0 Reserved0 0 0 0 0 BD DN 0
Word 60 0 0 0 0 0 0 0 V3 V2 V1 V0 U3 U2 U1 U0
Where :
PU = Power up inconfigured
FP = Field power off
CF = In configuration mode
BD = Bad calibration
DN = Calibration accepted
U = Underrange for specified channel
V = Overrange for specified channel
Word 2Read Back Channel 2
Word 3Read Back Channel 3
Word 4PU FP CF 0 Reserved0 0 0 0 0 BD DN 0
Word 50 0 0 0 P3 P2 P1 P0 0 0 0 0 W3 W2 W1 W0
1794-IF2XOF2XT
Word 0Analog value for Input channel 0
Word 1Analog value for Input channel 1
Word 2Read Back Output channel 0
Word 3Read Back Output channel 1
Word 40 Real Time Sample
Word 5PU FP CF 0 Reserved0 0 0 0 0 BD DN 0
Word 60 0 0 0 P1 P0 0 0 0 0 V1 V0 W1 W0 U1 U0
Where :
PU = Power up inconfigured
FP = Field power off
CF = In configuration mode
BD = Bad calibration
DN = Calibration accepted
P0 thru P3 = Output holding in response to Q0 thru Q3
W0 thru W3 = Wire off current loop status for channels 0 thru 3 respectively
Word 0EN 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Word 1Channel 3 FilterChannel 2 FilterChannel 1 FilterChannel 0 Filter
Word 2Ch 3 ConfigurationCh 2 ConfigurationCh 1 ConfigurationCh 0 Configuration
Word 30 Real Time Sample Interval
Word 4IC 1 TR IT 0 0 0 0 RV QK CK GO Channel Number
Word 5Reserved
Where :
EN = Inable bit (not used on input module)
IC = Initiate Configuration bit
TR = Transparent bit
IT = Interrupt toggle bit
RV = Revert to default bit
QK = Quick calibration
CK = Calibration clock
GO = Gain Offset select
Word 0EN S1 S0 0 0 0 0 0 0 0 0 0 0 0 0 0
Word 1Output Data Channel 0
Word 2Output Data Channel 1
Word 3Output Data Channel 2
Word 4Output Data Channel 3
Word 5Ch 3 ConfigurationCh 2 ConfigurationCh 1 ConfigurationCh 0 Configuration
Word 6IC 1 TR IT Q3 Q2 Q1 Q0 RV QK CK GO Channel Number
1794-IF2XOF2XT
Word 0EN S1 S0 0 0 0 0 0 0 0 0 0 0 0 0 0
Word 1Analog Output Data - Channel 0
Word 2Analog Output Data - Channel 1
Word 30 0 0 0 0 0 0 0 Input Channel 1 Filter Input Channel 0 Filter
Words 4Output Channel 1
Configuration
Word 50 Real Time Sample Programmed Interval
Word 6IC 1 TR IT Q1 Q0 0 0 RV QK CK GO Channel Number
Where :
EN = Inable output - 0 = output follows S1/S0; 1 = output enabled
S1/S0 = Safe state source
IC = Initiate Configuration bit
TR = Transparent bit
IT = Interrupt toggle bit
Q0 thru Q3 = Requests for outputs to hold
RV = Revert to default bit
QK = Quick calibration
CK = Calibration clock
GO = Gain Offset select
Output Channel 0
Configuration
Input Channel 1
Configuration
Input Channel 0
Configuration
Publication 1794-IN129B-EN-P - April 2009
Page 4
4
Configure Your Input Channels 1794-IF4IXT,
1794-IF2XOF2XT)
Input Channel Configuration
03 02 01 00 Set these bits for channel 0
07 06 05 04 Set these bits for channel 1
11 10 09 08 Set these bits for channel 2
15 14 13 12 Set these bits for channel 3
Input Update Rate for Real Time Sample Interval = 0 (1794-IF4IXT,
1794-IF2XOF2XT)
Configuration Bits
MSD LS D
00014…20 mA7.5 ms5.0 ms
0010±10V2.5 ms2.5 ms
0011±5V2.5 ms2.5 ms
01000…20 mA7.5 ms5.0 ms
01014…20 mA7.5 ms5.0 ms
01100…10V5.0 ms5.0 ms
0111±10V5.0 ms5.0 ms
10000…20 mA2.5 ms2.5 ms
10014…20 mA7.5 ms5.0 ms
10100…10V2.5 ms2.5 ms
10110…5V2.5 ms2.5 ms
1100±20 mA2.5 ms2.5 ms
11014…20 mA7.5 ms5.0 ms
1110±10V2.5 ms2.5 ms
1111±5V2.5 ms2.5 ms
(1)
When IT = 1, the channel update rate for all channels is determined by the slowest channel.
Configure Your Output Channels (1794-OF4IXT)
Configuration Bits
MSD LSD
00014…20 mASigned 2’s
0010
0011
01000…20 mASigned 2’s
01014…20 mA<0-10000>5.0 ms
01100…10V<0-10000>5.0 ms
0111
10000…20 mAbinary<0000-F3CF>2.5 ms
10014…20 mA<0000-F0F1>5.0 ms
10100…10V<0000-F9C2>2.5 ms
10110…5V<0000-F3CF?2.5 ms
11000…20 mAoffset binary<0618-F9E8>2.5 ms
11014…20 mA<8000-F878>5.0 ms
1110
1111
Input
Nominal
Ranges
Nominal
Range
±10V
±5V
±10V
±10V
±5V
Channel Update
(1)
Rate
RTSI = 0 and
No low pass filter
Data TypeOutput ValuesModule Update
complement
complement %
Channel Update Rate
RTSI and Filter = 0
IT bit = 1
Rate
<0000-7878>5.0 ms
<831F-7CE1>2.5 ms
<8618-79E8>2.5 ms
<0-10000>5.0 ms
<-10000-10000>5.0 ms
<031F-FCE1>2.5 ms
<0618-F9E8>2.5 ms
Set the Input Filters
Input Channel Configuration
03 02 01 00 Set these bits for channel 0
07 06 05 04 Set these bits for channel 1
11 10 09 08 Set these bits for channel 2
15 14 13 12 Set these bits for channel 3
Bit SettingsA/D Conversion RateLow Pass Filter
00001200 HzNo low pass
00011200 Hz100 ms low pass
00101200 Hz500 ms low pass
00111200 Hz1000 ms low pass
0100600 HzNo low pass
0101600 Hz100 ms low pass
0110600 Hz500 ms low pass
0111600 Hz1000 ms low pass
1000300 HzNo low pass
1001300 Hz100 ms low pass
1010300 Hz500 ms low pass
1011300 Hz1000 ms low pass
1100150 HzNo low pass
1101150 Hz100 ms low pass
1110150 Hz500 ms low pass
1111150 Hz1000 ms low pass
Power/status Indicator
The OK status indicator is bicolor red and green. The indicator flashes
green for any of the following 3 reasons:
1. The module configuration word is zero (for example, powerup
reset condition).
(1)
2. The 24V DC user power is off.
3. The module is in configuration mode.
The indicator displays red to indicate the module did not pass the initial
hardware test. Recycle power.
After powerup, if the status indicator is not flashing green or solid green,
recycle module power to verify a proper reset of the bus interface.
Specifications
General (Input)
AttributeValu e
Number of inputs4 isolated (1794-IF4IXT)
Resolution
Voltage
Current
Update rate2.5/5.0/7.5 ms all channels (see input update rate table)
Input current terminal4…20 mA (user configurable)
Input voltage terminal ±10V (user configurable)
Input Resistance
Voltage terminal
Current terminal
(1)
If 24V DC is removed fr om the module, input resistance = 10 kΩ
2 isolated (1794-IF2XOF2XT)
16 bits - unipolar; 15 bits plus sign - bipolar
0.156 mV/cnt unipolar; 0313 mV/cnt bipolar
0.320 μA/cnt unipolar; 0.640 μA/cnt bipolar
2.5/5.0 ms all channels (see input update rate table) (1794-OF4IXT)
0…20 mA (user configurable)
±20 mA (user configurable)
Update rate2.5/5.0/7.5 ms all channels (see input update rate table)
Normal mode rejection ratio
- voltage or current Terminal
Common mode rejection
ratio
Step response to 63% voltage or current terminal
(1794-IF4IXT,
1794-IF2XOF2XT)
Step response to 63% of full
scale (1794-OF4IXT,
1794-IF2XOF2XT)
Absolute accuracy
voltage terminal
current terminal
Accuracy drift with
temperature
Voltage terminal
Current terminal
Calibration requiredFactory calibrated. Can be calibrated in field when necessary
Maximum overload30V continuous or 32 mA continuous, one channel at a time.
Indicators1 red/green power/status indicator
(1)
and 1794-TBN
2’s complement %
binary
offset binary
Digital to analog converter (1794-OF4IXT)
2.5/5.0 ms all channels (see input update rate table) (1794-OF4IXT)
-3 dB @ 12 Hz (300 Hz conversion rate)
-80 dB @ 50 Hz (300 Hz conversion rate)
-3 dB @ 6 Hz (150 Hz conversion rate)
-80 dB @ 60 Hz (150 Hz conversion rate)
-120 dB @ 50/60 Hz
1200 Hz conversion rate = 0.6 ms
600 Hz conversion rate = 06.7 ms
300 Hz conversion rate = 13.4 ms
150 Hz conversion rate = 26.7 ms
< 25 μs
0.1% Full Scale @ 25 °C
0.1% Full Scale @ 25 °C
0.0028% Full Scale/°C (1794-IF4IXT, 1794-IF2XOF2XT)
0.0012% Full Scale/°C (1794-OF4IXT)
0.0038% Full Scale/°C (1794-IF4IXT, 1794-IF2XOF2XT)
0.0025% Full Scale/°C (1794-OF4IXT)
General
AttributeValue
Isolation voltage120V (continuous), Basic Insulation Type, when used with 1794-TB2,
Flexbus current50 mA
Power dissipation2.0 W maximum @ 31.2V DC
Thermal dissipationMaximum 6.8 BTU/hr @ 31.2V DC
Keyswitch position3 (1794-IF4IXT)
External DC Power Supply
voltage
Voltage range
Supply current
Dimensions 46 mm x 94 mm x 75 mm (1.8 in. x 3.7 in. x 2.95 in.) with module
Wire sizeDetermined by installed terminal base
Wiring category
Wire type
Enclosure
Terminal screw torqueDetermined by installed terminal base
North American temp codeT4
IEC temp codeT4
(1)
(2)
(2)
Includes offset, gain, no nlinearity and repeatability error terms.
Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication 1770-4. 1.
1794-TB3, 1794-TB3S, 1794-TB3T, or 1794-TB3TS
250V (continuous), Basic Insulation Type, when used with 1794-TBN
Type tested at 1500V AC for 60 s and Routine tested at 2550V DC for
1
s, between channel to power, channel to system, and power to
system, and channel to channel
4 (1794-OF4IXT)
5 (1794-IF2XOF2XT)
24V DC nominal
19.2…31.2V DC (includes 5% AC ripple)
80 mA @ 24V DC (1794-IF4IXT)
210 mA @ 24V DC (1794-OF4IXT)
150 mA @ 24V DC (1794-IF2XOF2XT)
See the Product Certification link at http://w ww.ab.com for Declaration of Conformity, Certificates, and o ther
certification details.
IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz
3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
±2 kV at 5 kHz on power ports
±2 kV at 5 kHz on shielded signal ports
IEC 61000-4-5:
±1 kV line-line(DM) and ±2 kV line-earth(CM) on power ports
±2 kV line-earth(CM) on shielded signal ports
IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
(1)
UL Listed Industrial Control Equip ment, certified for US and Canada. See UL File
E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S.
and Canada. See UL File E194810.
European Union 2004/108/EC EMC Directive, compliant with:
EN 61326-1; Meas./Control/Lab., Industrial Requir ements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Z one A & B)
European Union 2006/95/EC LVD, compliant with:
EN 61131-2; Programmable Controllers (Clause 11)
Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
European Union 94/9/EC ATEX Directive, compliant with:
EN 60079-15; Potentially Explosive Atmo spheres,
Protection "n" (II 3 G Ex nA IIC T4 X)
EN 60079-0; General Requirements (Zone 2)
TÜV Certified for Functional Safety:
up to and including SIL 2
Publication 1794-IN129B-EN-P - April 2009 6 PN-46754