Rockwell Automation 1794-IB8, 1794-IB16, 1794-IB16K, 1794-IB32 User Manual

Installation Instructions
WARNING
IMPORTANT
ATTENTION
ATTENTION
ATTENTION
ATTENTION
WARNING
FLEX I/O Digital Input Modules
Cat. Nos. 1794-IB8, -IB16, -IB16K, and -IB32
(Modules with a K in the last position of the catalog number are conformally coated to meet noxious gas requirements of ISA/ANSI-71.040 1985 Class G3 Environment.)
Important User Information
Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication Automation sales office or online at http://www.literature.rockwellautomation.com) describes some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams. No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual. Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc. is prohibited. Throughout this manual we use notes to make you aware of safety considerations.
Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
Identifies information that is critical for successful application and understanding of the product.
Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you:
identify a hazard
avoid a hazard
recognize the consequence
SGI-1.1 available from your local Rockwell
Prevent Electrostatic Discharge
This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment:
Touch a grounded object to discharge potential static.
Wear an approved grounding wriststrap.
Do not touch connectors or pins on component boards.
Do not touch circuit components inside the equipment.
Use a static-safe workstation, if available.
Store the equipment in appropriate static-safe packaging when not
in use.

European Hazardous Location Approval

-IB16K.
European Zone 2 Certification (The following applies when the product bears the Ex Marking)
This equipment is intended for use in potentially explosive atmospheres as defined by European Union Directive 94/9/EC and has been found to comply with the Essential Health and Safety Requirements relating to the design and construction of Category 3 equipment intended for use in potentially explosive atmospheres, given in Annex II to this Directive. Compliance with the Essential Health and Safety Requirements has been assured by compliance with EN
60079-15 and EN 60079-0.
Observe the following additional Zone 2 certification requirements.
This equipment is not resistant to sunlight or other sources of UV
radiation.
This equipment must be installed in an enclosure providing at least
IP54 protection when applied in Zone 2 environments.
This equipment shall be used within its specified ratings defined
by Allen-Bradley.
Provision shall be made to prevent the rated voltage from being
exceeded by transient disturbances of more than 40% when applied in Zone 2 environments
This equipment must be used only with ATEX certified backplanes.
Secure any external connections that mate to this equipment by
using screws, sliding latches, threaded connectors, or other means provided with this product.
Do not disconnect equipment unless power has been removed or
the area is known to be nonhazardous.
Environment and Enclosure
This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating.
This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR 11. Without appropriate precautions, there may be difficulties with electromagnetic compatibility in residential and other environments due to conducted and radiated disturbances.
This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame spread rating of 5VA, V2, V1, V0 (or equivalent) if non-metallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.
In addition to this publication, see:
Industrial Automation Wiring and Grounding Guidelines,
Allen-Bradley publication requirements.
NEMA Standards 250 and IEC 60529, as applicable, for explanations
of the degrees of protection provided by different types of enclosure.
This product is grounded through the DIN rail to chassis ground. Use zinc plated yellow-chromate steel DIN rail to assure proper grounding. The use of other DIN rail materials (for example aluminum or plastic) that can corrode, oxidize, or are poor conductors, can result in improper or intermittent grounding. Secure DIN rail to mounting surface approximately every 200 mm (7.8 in.) and use end-anchors appropriately.
1770-4.1, for additional installation
Publication 1794-IN093C-EN-P - December 2009
2
WARNING
AVERTISSEMENT
ATTENTION
ATTENTION
WARNING

North American Hazardous Location Approval

The following input modules are North American Hazardous Location approved: 1794-IB8, -IB16, -IB16K, and -IB32.
The following information applies when operating this equipment in hazardous locations:
Products marked “CL I, DIV 2, GP A, B, C, D” are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest “T” number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation.
EXPLOSION HAZARD
Do not disconnect equipment unless
power has been removed or the area is known to be nonhazardous.
Do not disconnect connections to this
equipment unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.
Substitution of components may
impair suitability for Class I, Di vision
2.
If this product contains batteries,
they must only be changed in an area known to be nonhazardous.
Informations sur l’utilisation de cet équipement en environnements dangereux:
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu’à une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livré avec des marquages sur sa plaque d’identification qui indiquent le code de température pour les environnements dangereux. Lorsque plusieurs produits sont combinés dans un système, le code de température le plus défavorable (code de température le plus faible) peut être utilisé pour déterminer le code de température global du système. Les combinaisons d’équipements dans le système sont sujettes à inspection par les autorités locales qualifiées au moment de l’installation.
RISQUE D’EXPLOSION
Couper le courant ou s’assurer que
l’environnement est classé non dangereux avant de débrancher l'équipement.
Couper le courant ou s'assurer que
l’environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes reliés à cet équipement à l'aide de vis, loquets coulissants, connecteurs filetés ou autres moyens fournis avec ce produit.
La substitution de composants peut
rendre cet équipement inadapté à une utilisation en environnement de Classe I, Division 2.
S’assurer que l’environnement est
classé non dangereux avant de changer les piles.
To comply with the CE Low Voltage Directive (LVD), this equipment must be powered from a source compliant with the following: Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV).

Compatibility

The following communication adapters are required to ensure compatibility with the 1794-IB32:
Remote I/O 1794-ASB series E or later
ControlNet 1794-ACN15 series C, firmware revision 4.1 or later
DeviceNet 1794-ADN Series B, firmware revision 2.4 or greater for out-of-box
Ethernet 1794-AENT series A, firmware revision 2.4 or later PROFIBUS 1794-APB series A, version 1.1 of the GSD file
ControlLogix Family RSLogix5000 programming software, version 11 or later
1794-ASB2 series D or later
1794-ACNR15 series C, firmware revision 4.1 or later
compatibility
(You can download the GSD file at www.ab.com/networks/gsd.)

Install Your Digital Input Module

7
3
1
2
6
4
5
The module mounts on a 1794 terminal base.
During mounting of all devices, be sure that all debris (such as metal chips and wire strands) is kept from falling into the module. Debris that falls into the module could cause damage on power up.
1. Rotate the keyswitch (1) on the terminal base (2) clockwise to position 2 as
required for this type of module.
2. Make certain the flexbus connector (3) is pushed all the way to the left to connect with the neighboring terminal base/adapter. You cannot
install the module unless the connector is fully extended.
3. Make sure the pins on the bottom of the module are straight so they will
align properly with the connector in the terminal base.
If you insert or remove the module while backplane power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
4. Position the module (4) with its alignment bar (5) aligned with the groove (6) on the terminal base.
5. Press firmly and evenly to seat the module in the terminal base unit. The module is seated when the latching mechanism (7) is locked into the module.

Connect Wiring for the 1794-IB8, -IB16, and -IB16K using a 1794-TB3 or -TB3S

1. Connect individual input wiring to numbered terminals on the 0…15 row (A) as indicated in the following table on the next page.
2. Connect the associated +V DC power lead of the input device to the corresponding terminal on the 34…51 row (C) for each input as indicated in the following table. (The +V power terminals of row (C) are internally connected together.)
3. Connect the associated input common (3-wire devices only) to the corresponding terminal on the 16…33 row (B) for each input as indicated in the following table. (Commons are internally connected together.)
4. Connect +V DC power to terminal 34 on the 34…51 row (C).
5. Connect DC common to terminal 16 on the 16…33 row (B).
6. If daisychaining power to the next terminal base, connect a jumper from
terminal 51 (+V DC) on this base unit to terminal 34 on the next base unit.
7. If continuing DC common to the next base unit, connect a jumper from terminal 33 (common) on this base unit to terminal 16 on the next base unit.
Publication 1794-IN093C-EN-P - December 2009
3
-V
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
16
35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51
34
Inputs
Commons
(1794-TB3 shown)
Connect V common to terminal B-16. Connect +V to terminal C-34.
Voltage In +V
Voltage Out +V
Voltage
A
B
C
Common
-V
Common
Use B-33 and C-51 to daisy-chain to the next terminal base unit.
= Sink input
= Common
= +V DC
0…15
16…33
34…51
A
B
C
A
B
C
2-Wire Device
(Sourcing Output)
3-Wire Device
(Sourcing Output)

Wiring Connections for 1794-IB8, -IB16, and -IB16K (use with 1794-TB3 or -TB3S Terminal Base Units)

(1)
Input
Input Terminal Voltage Terminal
Input 0 A-0 C-35 B-17 Input 1 A-1 C-36 B-18 Input 2 A-2 C-37 B-19 Input 3 A-3 C-38 B-20 Input 4 A-4 C-39 B-21 Input 5 A-5 C-40 B-22 Input 6 A-6 C-41 B-23 Input 7 A-7 C-42 B-24 Input 8 A-8 C-43 B-25 Input 9 A-9 C-44 B-26 Input 10 A-10 C-45 B-27 Input 11 A-11 C-46 B-28 Input 12 A-12 C-47 B-29 Input 13 A-13 C-48 B-30 Input 14 A-14 C-49 B-31 Input 15 A-15 C-50 B-32 +V DC C-34…C-51 Common B-16…B-33
(1)
1794-IB8: Inputs 0…7; 1794-IB16, -IB16K: Inputs 0…15.
(2)
3-wire devices use input, supply and common; 2-wire devices use input and supply.
Common Terminal
(2)
1794-TB3 and -TB3S Terminal Base Wiring for 1794-IB8, -IB16, and
-IB16K

Connect Wiring for the 1794-IB32 using a 1794-TB32 or -TB32S

1. Connect individual input wiring (IN0…IN15) to numbered terminals on the 0…15 row (A) as indicated in the following table.
2. Connect the associated power to the +V1 terminal (35, 37, 39, or 41) on the 34…51 row (C) as indicated in the following table.
3. Connect the associated common for IN0…IN15 to COM1 (terminal 36, 38, 40, or 42) on the 34…51 row (C) as indicated in the following table.
4. Connect individual input wiring (IN16…IN31) to numbered terminals on the 16…33 row (B) as indicated in the following table.
Do not connect to terminals 16 or 33.
5. Connect the associated power to the +V2 terminal (43, 45, 47, or 49) on
the 34…51 row (C) as indicated in the following table.
6. Connect the associated common for IN16…IN31 to COM2 (terminal 44, 46, 48, or 50) on the 34…51 row (C).
7. If continuing input wiring power for IN0…IN15 to the next terminal base, connect a jumper from terminal 41 (+V1) on this ter minal base unit to the power terminal on the next terminal base unit. (Refer to the installation instructions for the specific terminal base unit.
8. If continuing input wiring IN0…IN15 common to the next terminal base, connect a jumper from terminal 42 (COM1) on this terminal base unit to the common terminal on the next terminal base unit.
9. If continuing input wiring power for IN16…IN31 to the next terminal base, connect a jumper from terminal 49 (+V2) on this terminal base unit to the power terminal on the next terminal base unit. (Refer to the installation instructions for the specific terminal base unit.
10. If continuing input wiring IN16…IN31 common to the next terminal
base, connect a jumper from terminal 50 (COM2) on this terminal base unit to the common terminal on the next terminal base unit.

2- and 3-Wire Input Wiring for 1794-IB8, -IB16, and -IB16K

Wiring for 1794-IB32 (use with 1794-TB32 or -TB32S Terminal Base Unit)

Input Signal Input Signal
IN 0 A-0 IN 16 B-17 IN 1 A-1 IN 17 B-18 IN 2 A-2 IN 18 B-19 IN 3 A-3 IN 19 B-20 IN 4 A-4 IN 20 B-21 IN 5 A-5 IN 21 B-22 IN 6 A-6 IN 22 B-23 IN 7 A-7 IN 23 B-24 IN 8 A-8 IN 24 B-25 IN 9 A-9 IN 25 B-26 IN 10 A-10 IN 26 B-27 IN 11 A-11 IN 27 B-28 IN 12 A-12 IN 28 B-29 IN 13 A-13 IN 29 B-30 IN 14 A-14 IN 30 B-31 IN 15 A-15 IN 31 B-32
+V1 DC power (inputs IN0…IN15)
COM1 DC Return (inputs IN0…IN15)
+V2 DC power (inputs IN16…IN31)
COM2 DC Return (inputs IN16…IN31)
(1)
(1)
2-wire input devices use signal and supply terminals; 3-wire devices use signal, return and supply terminals.
Power terminals 35, 37, 39, and 41 for IN0-IN15. +V1 connected to terminals 35, 37, 39, and 41
Common terminals 36, 38, 40, and 42 for IN0-IN15. V1 Return connected to terminals 36, 38, 40, and 42
Power terminals 43, 45, 47, and 49 for IN16-IN31. +V2 connected to terminals 43, 45, 47, and 49
Common terminals 44, 46, 48, and 50 for IN16-IN31. V2 Return connected to terminals 44, 46, 48, and 50
Publication 1794-IN093C-EN-P - December 2009
4
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
FT = 0…7 (1794-IB8) FT = 0…11 (1794-IB16)
1794-IB16
O:010
Dec.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
17 16 15 14 13 12 11 10 7 6 5 4 3 2 1 0
Oct.
FT = 12…15
FT = 0…31 1794-IB32
1
00
76543
FLL
I:000
00
Fill File Source Destination Length
#O:010
1
Write FT to complement of input module.
Write filter time on system startup.
76 54 32 1 0
0
1
0
= 4 Octal or 4 Decimal
21 0
= 44 Octal or 36 Decimal
010100
1794-IB8
1794-IB16
1
00
= 4 Octal or 4 Decimal
10 0
1794-IB32
09 08101112131415

1794-TB32 or -TB32S Terminal Base Wiring for the 1794-IB32

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33
16
NC
35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51
34
+V1 COM1 +V1 COM1 +V1 COM1 +V2 COM2 +V2 COM2 +V2 COM2 +V2 COM2 NC
NC
+V1 = Terminals 35, 37, 39, and 41 +V2 = Terminals 43, 45, 47, and 49 COM1 = Terminals 36, 38, 40, and 42 COM2 = Terminals 44, 46, 48, and 50 NC = No connections (terminals 16, 33, 34, and 51)
+V1 COM1
(1794-TB32 shown)
Inputs
NC
Inputs

Configure Your Input Module

Configure your input module by setting bits in the configuration word (write word).
Dec. 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Oct. 17 16 15 14 13 12 11 10 7 6 5 4 3 2 1 0
Read 1
I15 I14 I13 I12 I11 I10 I9 I8 I7 I6 I5 I4 I3 I2 I1 I0 (1794-IB16, 1794-IB32)
Read 1
Not used I7 I6 I5 I4 I3 I2 I1 I0 (1794-IB8)
Read 2
C = Counter Input value of input 15 (1794-IB16)
Read 2
I31 I30 I29 I28 I27 I26 I25 I24 I23 I22 I21 I20 I19 I18 I17 I16 (1794-IB32)
Write 1
Not used Input Filter (1794-IB8)
Write 1
Not used CF CR Not used Input Filter (1794-IB16)
Write 1
Not used Input Filter FT (1794-IB32)
Where I = Input
C = Counter value for input 15 FT = Input filter time CR = Counter reset CF = Counter fast - where 1 = fast input (raw data) , 0 = standard input filtered data
NOTE: C, CR and CF not available when used with a ny series 1794-ASB or 1794-ASB2 remote I/O adapter modules.
0…31
12…15
Not used
0…07 Input Filter
0…11

Set the Input Filter Time

To set the input filter time, set the associated bits in the output image table (complementary word) for the module.
For example, to increase the off-to-on filter time to 4 ms for all inputs at address rack 1, module group 0, (using 1794-IB32 as an example), set bits and program as shown below.
Refer to the following Input Filter time chart for other bit settings.

Input Filter Time

Bits Description - Filter Time Filter Time
02 01 00 Inputs 0…07 (1794-IB8) 1794-IB8, -IB16, -IB16K, -IB32 02 01 00 Inputs 0…11 (1794-IB16, -IB16K) 05 04 03 Inputs 12…15 (1794-IB16, -IB16K) 10 09 08 Inputs 0…31 (1794-IB32) Off to On/On to Off
0 0 0 Filter time 0 (default) 0.25 ms 0 0 1 Filter time 1 0.5 ms 0 1 0 Filter time 2 1 ms 0 1 1 Filter time 3 2 ms 1 0 0 Filter time 4 4 ms 1 0 1 Filter time 5 8 ms 1 1 0 Filter time 6 16 ms 1 1 1 Filter time 7 32 ms

Specifications - 24V DC 8 Input Module, Cat. No. 1794-IB8

Specification
Number of inputs 8, nonisolated, sinking Module location 1794-T B3 or 1794-TB3S terminal base unit On-state voltage, min. 10V DC On-state voltage, nom. 24V DC On-state voltage, max. 31.2V DC On-state current, min. 2.0 mA On-state current, nom. 8.0 mA On-state current, max. 12.0 mA Off-state voltage, max. 5.0V DC Off-state current, max. 1.5 mA Input impedance 4.6K Ω Isolation voltage 50V (continuous), Basic Insulation Type, between field side and system
Flexbus current 20 mA at 5V DC Power dissipation 3.5W max. @ 31.2V DC Thermal dissipation Max. 11.9 BTU/hr @ 31.2V DC

Specifications - 24V DC 16 Input Module, Cat. Nos. 1794-IB16 and 1794-IB16K

Specification
Number of inputs 16 (1 group of 16), nonisolated, sinking Module location 1794-T B3 or 1794-TB3S terminal base unit Mounting Refer to the derating curve. On-state voltage, min. 10V DC On-state voltage, nom. 24V DC On-state voltage, max. 31.2V DC On-state current, min. 2.0 mA On-state current, nom. 8.0 mA On-state current, max. 12.0 mA Off-state voltage, max. 5.0V DC Off-state current, max. 1.5 mA Input impedance 4.6K Ω Isolation voltage 50V (continuous), Basic Insulation Type, between field side and system
Flexbus current 30 mA at 5V DC Power dissipation 6.1W max. @ 31.2V DC Thermal dissipation Max. 20.8 BTU/hr @ 31.2V DC
Description
No isolation between individual channels Type tested at 850V DC for 60 s
Description
No isolation between individual channels Type tested at 707V DC for 60 s
Publication 1794-IN093C-EN-P - December 2009
5

Specifications - 24V DC 32 Input Module, Cat. No. 1794-IB32

Specification
Number of inputs 32 (2 groups of 16), nonisolated with in groups, sinking Module location 1794-T B32 or 1794-TB32S terminal base unit On-state voltage, min. 19.2V DC On-state voltage, nom. 2 4V DC On-state voltage, max. 31.2V DC On-state current, min. 2.0 mA On-state current, nom. 4.1 mA at 24V DC On-state current, max. 6.0 mA Off-state voltage, max. 5.0V DC Off-state current, max. 1.5 mA Input impedance 6.0K Ω Isolation voltage 50V (continuous), Basic Insulation Type, between field side and system
Flexbus current 25 mA at 5V DC Power dissipation 6.0W max. @ 31.2V DC Thermal dissipation Max. 20.5 BTU/hr @ 31.2V DC
Description
No isolation between individual channels Routine tested at 2121V DC for 2 s

General Specifications

Specification
Input filter time
Terminal base screw torque Determined by installed terminal base. Dimensions (HxWxD, with
module installed) Indicators (field side indication,
customer device driven)
External DC power
North American temp code 1794-IB8 and -IB32: T3C; 1794-IB16 and -IB16K: T4A IEC temp code 1794-IB8: T 3; 1794-IB16 and -IB16K: T4
(1)
(1)
Off to On On to Off
Supply voltage, nom. Voltage range
Input off-to-on filter time is the time from a valid input signal to recognition by the module. Input on-to-off filter time is time from the input signal dr opping below the valid level to recognition by the module.
Description
0.25 ms, 0.5 ms, 1 ms, 2 ms, 4 ms, 8 ms, 16 ms, 32 ms
0.25 ms, 0.5 ms, 1 ms, 2 ms, 4 ms, 8 ms, 16 ms, 32 ms
0.25 ms default - Selectable using configuration word 3
94 x 94 x 69 mm (3.7 x 3.7 x 2.7 in.)
1794-IB8: 8 yellow status indicators 1794-IB16, -IB16K: 16 yellow status ind icators 1794-IB32: 32 yellow status indi cators
24V DC 1794-IB8, -IB16, -IB16K: 10…31.2V DC (includes 5% AC ripple) 1794-IB32: 19.2…31.2V DC (includes 5% AC rip ple)

Environmental Specifications

Specification
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold),
Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold),
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
Vibration IEC 60068-2-6 (Test Fc, Operating):
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock):
Shock, non-operating IEC 60068-2-27 (Test Ea, Unpackaged Shock):
Emissions CISPR 11:
ESD immunity IEC 61000-4-2:
Radiated RF immunity IEC 61000-4-3:
EFT/B immunity IEC 61000-4 -4:
Surge transient immunity IEC 61000-4-5:
Conducted RF immunity IEC 61000-4-6:
Enclosure type rating None (open-style) Wire size D etermined by installed terminal base.
Wiring category
(1)
(1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1
Description
IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock): 0…55 °C (32…131 °F)
IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Non-operating Thermal Shock): –40…85 °C (–40…185 °F)
5…95% non-condensing
5 g @ 10…500 Hz
30 g
50 g
Group 1, Class A (with appropriate enclosure)
4 kV contact discharges 8 kV air discharges
10V/m with 1 kHz sine-wave 80% AM from 80…2 000 MHz (all) 10V/m with 200 Hz 50% pulse 100% AM at 900 MHz (all) 10V/m with 200 Hz 50% pulse 100% AM at 1890 MHz (1794-IB8, -IB16, and -IB16K) 1V/m with 1 kHz sine-wave 80% AM from 2000 …2700 MHz (1794-IB8) 3V/m with 1 kHz sin e-wave 80% AM from 2000…2700 MHz (1794-IB16,
-IB16K, and -IB32)
±2kV at 5 kHz on signal ports
±1kV line-line (DM) and ±2kV line-earth (CM) on signal ports
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
2 - on signal ports
.

Certifications

Certifications (when product
(1)
is marked)
c-UL-us UL Listed Industrial Control Equipment, certi fied for US and Canada. See
CSA (for 1794-IB8, -IB16, and -IB16K)
CE European Union 2004/108/EC EMC Dire ctive, compliant with:
C-Tick Australian Radiocommunications Act compliant with:
Ex (for 1794-IB8, -IB16, and -IB16K)
TÜV (for 1794-IB16)
(1)
See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates and other certification details.
Description
UL File E65584. UL Listed for Class I, Division 2, Group A, B, C, D Haza rdous Locations, certified for US and Canada. See UL File 19481 0.
CSA Certified Process Control Equipment. See CSA File LR5468 9C. CSA Certified Process Control Equipment for Class I , Division 2, Group A, B, C, D Hazardous Locations. See CSA File LR69960C.
EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
AS/NZS CISPR 11; Industrial Emissions
European Union 94/9/EC ATEX Directive, compliant with:
EN 60079-15; Potentially Explosive Atmosphe res, Protection “n” EN 60079-0; General Requirement s II 3 G Ex nA IIC T3 X (1794-IB8) II 3 G Ex nA IIC T4 X (1794-IB16, -IB16K)
TÜV Certified for Functional Safety:
up to and including SIL 2
Publication 1794-IN093C-EN-P - December 2009

Derating Chart for the 1794-IB16 and -IB16K

31.2
30
28.5
27.5
25
V
in
On-State
Voltage
(V DC)
20
15
10
0
10 20 30 40 50 55 60
Temperature
(max.)
Normal
Ambient Temperature
Other
The area within the curve represents the safe operating range for the module under various conditions of user supplied 24V DC supply voltages and ambient temperature.
= Normal mounting safe operating range, (includes ).
= Other mounting positions (including inverted horizontal) safe operating range
Normal Mounting – Horizontal
Other Mounting (including Vertical, and Inverted Horizontal Mounting)
Voltage
(max.)
Voltage
(max.)
3732
o
C
Temperature
(max.)
Normal
Other
31.2 37 32 29.0 51 45
30.5 41 36 28.5 48
30.0 45 39 28.0 55 51
29.5 48 42 27.5 55
Publication 1794-IN093C-EN-P - December 2009 6 PN-64734
Supersedes Publication 1794-IN093B-EN-P - May 2 004 Copyright © 2009 Rockwell Automation, Inc. All rights reserved.
Loading...