Rockwell Automation 1794-IA8, 1794-IA8I, 1794-IA16 User Manual

Installation Instructions
FLEX I/O ac Digital Input Modules
Cat. Nos. 1794-IA8, -IA8K, IA8I, -IA16
(Modules with a K in the last position of the catalog number are conformally coated to meet noxious gas requireme nts of ISA / AN SI-71.040 1985 Class G3 Environment.)
Important User Information
Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.ab.com/manuals/gi) describes some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc. is prohibited.
Throughout this manual we use notes to make you aware of safety considerations.
WARNING
IMPORTANT
ATTENTION
ATTENTION
Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
Identifies information that is critical for successful application and understanding of the product.
Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you:
identify a hazard
avoid a hazard
recognize the consequence
Environment and Enclosure
This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes up to 2000 meters without derating.
This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR Publication 11. Without appropriate precautions, there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance.
This equipment is supplied as "open type" equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.
See NEMA Standards publication 250 and IEC publication 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosure. Also, see the appropriate sections in this publication, as well as the Allen-Bradley publication 1770-4.1 ("Industrial Automation Wiring and Grounding Guidelines"), for additional installation requirements pertaining to this equipment.
WARNING
WARNING
ATTENTION
ATTENTION
When you insert or remove the module while backplane power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
If you connect or disconnect wiring while the field side power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding..
FLEX I/O is grounded through the DIN rail to chassis ground. Use zinc plated yellow-chromate steel DIN rail to assure proper grounding. The use of other DIN rail materials (e.g. aluminum, plastic, etc.) that can corrode, oxidize, or are poor conductors, can result in improper or intermittent grounding.
Preventing Electrostatic Discharge
This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment:
Touch a grounded object to discharge potential static.
Wear an approved grounding wriststrap.
Do not touch connectors or pins on component boards.
Do not touch circuit components inside the equipment.
If available, use a static-safe workstation.
The following input modules are North American Hazardous Location approved: 1794-IA8, -IA8K, -IA8I and 1794-IA16.
.
The following information applies when operating this equipment in hazardous locations:
Products marked “CL I, DIV 2, GP A, B, C, D” are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Lo cations and nonhazardous loc ations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the mos t adverse temperatur e code (lowest “T” number) may be used to help determine the overall temperature code of the sys tem. Combinations of e quipment in your system are subject to i nvestigation by the loca l Authority Having Jurisdiction at the t ime of installation.
WARNING
EXPLOSION HAZARD
Do not discon nect equipment unless power has been removed or the area is known to be n onhazardous.
Do not disconnect connections to this equipment un less power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using scr ews, sliding latches, thre aded connectors, or other means provided with this product.
Substituti on of components ma y impair suitability f or Class I, Division 2.
If this product contains batteries, they must only be changed in an area known to be nonhazar dous.
Informations sur l’utilisation de cet équipement en environnements dangereux :
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu’à une utilisation en environnements de Classe I Division 2 Grou pes A, B, C, D dangere ux et non dangereux. Chaque produit est livré avec des mar quages sur sa plaque d’identificati on qui indiquent le code de température pour les environnemen ts dangereux. Lorsq ue plusieurs produits s ont combinés dans un syst ème, le code de température le plus défavorable (c ode de température le p lus faible) peut être utilisé pour dé terminer le code de tem pérature global du système. Les c ombinaisons d’équipeme nts dans le système sont sujettes à inspe ction par les autorités local es qualifiées au moment de l’ installation.
AVERTISSEMENT
RISQUE D’EXPLOSION
Couper le cou rant ou s’assurer que l’environnement est classé non dangereux avant de débrancher l'équipement .
Couper le cou rant ou s'assurer que l’environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tou s les connecteurs externes reli és à cet équipement à l'aide de vis , loquets coulissants, connecteurs filetés ou autres moyens fournis avec c e produit.
La substitut ion de composants peut rendre cet é quipement inadapté à une utilisation en en vironnement de Classe I, Division 2.
S’assurer que l’environnement est classé non da ngereux avant de change r les piles.
FLEX I/O is a trademark of Rockwell Automation DeviceNet is a trademark of ODVA, Inc. Publication 1794-IN102B-EN-P - June 2004
2
European Hazardous Location Approval
The following module is European Zone 2 approved: 1794-IA8K.
European Zone 2 Certification (The following applies when the product bears the EEx Marking)
This equipment is intended for use in potentially explosive atmospheres as defined by European Union Directive 94/9/EC.
The LCIE (Laboratoire Central des Industries Electriques) certifies that this equipment has been found to comply with the Essential Health and Safety Requirements relating to the design and construction of Categor y 3 equipment intended for use in potentially explosive atmospheres, given in Annex II to this Directive. The examination and test results are recorded in confidential report No. 28 682 010.
Compliance with the Essential Health and Safety Requirements has been assured by compliance with EN 50021.
IMPORTANT
Observe the following additional Zone 2 certification requirements.
This equipment is not resistant to sunlight or other sources of UV radiation.
The secondary of a current transformer shall not be open-circuited when applied in Class I, Zone 2 environments.
Equipment of lesser Enclosure Type Rating must be installed in an enclosure providing at least IP54 protection when applied in Class I, Zone 2 environments.
This equipment shall be used within its specified ratings defined by Allen-Bradley.
Provision shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 40% when applied in Class I, Zone 2 environments
Installing Your ac Digital Input Module
7
3
4
1
2
6
5
5. Press firmly and evenly to seat the module in the terminal base unit. The module is seated when the latching mechanism (7) is locked into the module.
Connecting Wiring for the 1794-IA8 and -IA8K
1. For 1794-TB2, -TB3, or -TB3S - Connect individual input wiring to even numbered terminals on the 0-15 row (A) as indicated in the table below . For 1794-TBN - Connect individual input wiring to numbered terminals on the 16-33 row (B) as indicated in the table below.
2. For 1794-TB2 - Connect the associated 120V ac power lead (L1) of the input device to the corresponding odd numbered terminals on the 0-15 row A for each input as indicated in the table below. (The odd numbered terminals on row A are internally connected to 120V ac L1.)
For 1794-TB3, or -TB3S - Connect the associated 120V ac power lead (L1) of the input device to the corresponding odd numbered terminals on the 34-51 row (C) or to the corresponding terminal on row (C) for each input as indicated in the table below. (The odd numbered terminals on row (A) and the terminals of row (C) are internally connected to 120V ac power L1.)
For 1794-TBN - Connect the associated 120V ac power lead (L1) of the input device to the corresponding odd numbered terminal on the 34-51 row (C) for each input as indicated in the table below. (The 120V ac power terminals of row (C) are internally connected together.)
3. Connect 120V ac power (L1) to terminal 34 on the 34-51 row (C).
4. Connect 120V ac common (L2) to terminal 16 on the 16-33 row (B).
5. If daisychaining power to the next terminal base, connect a jumper
from terminal 51 (+120V ac L1) on this base unit to terminal 34 on the next base unit
6. .If continuing ac common to the next base unit, connect a jumper from terminal 33 (120V common L2) on this base unit to terminal 16 on the next base unit.
The module mounts on a 1794 terminal base.
ATTENTION
During mounting of all devices, be sure that all debris (metal chips, wire strands, etc.) is kept from falling into the module. Debris that falls into the module could cause damage on power up.
1. Rotate the keyswitch (1) on the terminal base (2) clockwise to position 8 as required for this type of module.
2. Make certain the flexbus connector (3) is pushed all the way to the left to connect with the neighboring terminal base/adapter. You cannot install the module unless the connector is fully extended.
3. Make sure the pins on the bottom of the module are straight so they
will align properly with the connector in the terminal base.
WARNING
If you remove or insert the module while the backplane power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding..
4. Position the module (4) with its alignment bar (5) aligned with the groove (6) on the terminal base.
Publication 1794-IN102B-EN-P - June 2004
Wiring Connections for the 1794-IA8 and -IA8K
Input
Input 0 A-0
Input 1 A-2
Input 2 A-4
Input 3 A-6
Input 4 A-8
Input 5 A-10
Input 6 A-12
Input 7 A-14
A = Input terminals (Even numbe red terminals
0 thru 14) B = Common terminals C = Power terminals (C-34 and C-51 on - TB2; C-34
thru C-51 on -TB3 and -TB3S)
1 A-1, 3, 5, 7, 9, 11, 13 and 15 on the 1794-TB2, -TB3 and - TB3S are internally connected in the
module to 120V ac L1.
2 C-1, 3, 5, 7, 9, 11, 13 and 15 on the 1794-TBN are internally connected in the module to
120V ac L1.
1794-TB2,-TB3, -TB3S 1794-TBN Input
Ter mi nal
120V ac Supply
A-11/C-35
A-31/C-36
A-51/C-37
A-71/C-38
A-91/C-39
A-111/C-40
A-131/C-41
A-151/C-42
Input Te rm in al
B-0
B-2
B-4
B-6
B-8
B-10
B-12
B-14
B = Even numbered Input terminals 0-14, ac common terminals 16 and 33 C = Power terminals C-34 and C-51, and odd numbered input terminals 1 thru 1 5
120V ac Supply
2
C-1
2
C-3
2
C-5
2
C-7
2
C-9
2
C-11
2
C-13
2
C-15
3
Inputs
)
Even Numbered I/O Terminals 0 thru 14
n)
L L U
1794-TB2, -TB3 and -TB3S Terminal Base Wiring for 1794-IA8, IA8K and -IA16
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33
16
L2
35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51
34
L1
Connect 120V ac L1 power to terminal C-34 Connect 120V ac common L2 to terminal B-16 Use B-33 and C-51 for daisychaining to the next terminal base unit (Terminals C-35 thru C-50 not available on the 1794-TB2.)
Commons
Voltage
A
B
L2
C
L1
(1794-TB3 shown
1794-TBN Terminal Base Wiring for 1794-IA8, IA8K and -IA16
L2
16
34
L1
1 = 120V ac - Connect to terminal C-34 2 = 120V ac common - Connect to terminal B-16
se B-33 and C-51 for daisychaining to the next terminal base unit
4
2
0
1
6789101112
3
5
Odd Numbered I/O Terminals 1 thru 15
L2
14
33
15
B
51
C
L1
(1794-TBN show
13
Connecting Wiring for the 1794-IA16
1. For 1794-TB3, or -TB3S - Connect individual input wiring to numbered terminals on the 0-15 row (A) as indicated in the table below . For 1794-TBN - Connect individual input wiring to even numbered terminals on the 16-33 row (B), and to the odd numbered terminals on the 34-51 row (C) as indicated in the table below.
2. For 1794-TB3, or -TB3S - Connect the associated 120V ac power lead (L1) of the input device to the corresponding terminals on the 34-51 row (C) for each input as indicated in the table below. (The 120V power terminals of row (C) are internally connected together.)
For 1794-TBN - An external terminal strip is needed to distribute 120V ac power (L1) to each device.
Terminal Base Wiring for 1794-IA16
Input Channel
Input 0 A-0 B-0 C-35 Input 1 A-1 C-1 C-36 Input 2 A-2 B-2 C-37 Input 3 A-3 C-3 C-38 Input 4 A-4 B-4 C-39 Input 5 A-5 C-5 C-40 Input 6 A-6 B-6 C-41 Input 7 A-7 C-7 C-42 Input 8 A-8 B-8 C-43 Input 9 A-9 C-9 C-44 Input 10 A-10 B-10 C-45 Input 11 A-11 C-11 C-46 Input 12 A-12 B-12 C-47 Input 13 A-13 C-13 C-48 Input 14 A-14 B-14 C-49 Input 15 A-15 C-15 C-50 120V ac L1 Power terminals C-34 thru C-51 (C-34 and C-51 on -TBN) are
120V ac L2 Common terminals B-16 thru B-33 (B-16 and B-33 for -TBN) are
1
When using the 1794-TBN, an external terminal strip is needed to connect the 120V ac power
connections.
Input Terminal
1794-TB3, -TB3S
Input Terminal
1794-TBN
internally connected together. Connect 120V ac L1 to C-34
internally connected together. Connect 120V ac common L2 to terminal B-16
Connecting Wiring for the 1794-IA8I
1. For 1794-TB2, -TB3, or -TB3S - Connect individual input wiring to even numbered terminals on the 0-15 row (A) as indicated in the table below . For 1794-TBN - Connect individual input wiring to even numbered terminals 0-14 on the 16-33 row (B) as indicated in the table below.
2. For 1794-TB2, -TB3, or -TB3S - Connect the associated 120V ac common (L2) of the isolated supply to the corresponding odd numbered terminals on the 0-15 row A for each input as indicated in the table below. For 1794-TBN - Connect the associated 120V ac common lead (L2) of the isolated supply to the corresponding odd numbered terminal 1-15 on the 34-51 row (C) as indicated in the table below.
120V ac Supply (L1)
1
3. Connect 120V ac power (L1)to terminal 34 on the 34-51 row (C).
4. Connect 120V ac common (L2) to terminal 16 on the 16-33 row (B).
IMPORTANT
Individual isolated 120V ac L1 power leads must be run externally to each of the input devices.
5. If daisychaining power to the next terminal base, connect a jumper from terminal 51 (+120V ac L1) on this base unit to terminal 34 on the next base unit.
6. If continuing ac common to the next base unit, connect a jumper from terminal 33 (120V common L2) on this base unit to terminal 16 on the next base unit.
Publication 1794-IN102B-EN-P - June 2004
4
n)
C
C
Even Numbered I/O Terminals 0 thru 14
n) C L
)
Wiring Connections for the 1794-IA8I
1794-TB2, -TB3, -TB3S 1794-TBN
Input
Input Terminal
Input 0 A-0 A-1 B-0 C-1 Input 1 A-2 A-3 B-2 C-3 Input 2 A-4 A-5 B-4 C-5 Input 3 A-6 A-7 B-6 C-7 Input 4 A-8 A-9 B-8 C-9 Input 5 A-10 A-11 B-10 C-11 Input 6 A-12 A-13 B-12 C-13 Input 7 A-14 A-15 B-14 C-15
A = Even numbered terminals 0 thru 14 for cus tomer connections; corresponding odd numbered 120V ac common L2 terminals 1 thru 15 f or customer connections from isolat ed power supply.
120V ac L2 Common
Input Ter m in al
B = Even numbered term inals 0 thru 14 for customer connections; C = Odd numbered120V ac common L2 terminals 1 thru 15 for customer connections from isolat ed power supply.
120V ac L2 Common
1794-TB2, -TB3, or -TB3S Terminal Base Wiring for the 1794-IA8I
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33
16
35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51
34
onnect Inputs to even numbered terminals on row (A) onnect 120V ac common L2 to odd numbered terminals on row (A)
A
B
C
(1794-TB3 show
1794-TBN Terminal Base Wiring for 1794-IA8I
16
0
34
4
2
1
6789101112
3
5
Odd Numbered I/O Terminals 1 thru 15
onnect Inputs to even numbered terminals on row (B)
2 = 120V ac common - Connect to odd numbered terminals on row (C
14
33
13
15
B
51
C
(1794-TBN show
Configuring Your ac Input Module
Image Table Memory Map for the 1794-IA8, -IA8K and -IA8I .
Dec. 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Oct. 17 16 15 14 13 12 11 10 7 6 5 4 3 2 1 0
Read I7 I6 I5 I4 I3 I2 I1 I0
Write Not used - set to 0 Filter Time FT
Where I = Input
FT = Input filter time.
0-7
Setting the Input Filter Time
You can increase the input filter time (FT) for channels 00-07 (1794-IA8,
-IA8K, -IA8I) and channels 00-15 (1794-IA16) by setting the corresponding bits in the output image table (complementary word) for the module.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
O:010
FT = 12-15 FT = 0-11
1794-IA8, -IA8I
1794-IA16
Dec.
For example, to increase the off-to-on filter time to 12ms for all inputs at address rack 1, module group 0, set bits and program as shown below.
Write filter time on system startup.
I:000
00
765432 1 0
1794-IA8 1794-IA8I
76543
1794-IA16
FLL
Fill File Source Destination Length
0
1
21 0
1
010100
00
Write FT to complement of input module.
#O:010
1
= 4 Octal or 4 Decimal
0
= 44 Octal or 36 Decimal
To increase the filter time, set the bits according to the table below.
Input Filter Time
Maximum
Bits Description
02 01 00 Filter Time -
05 04 03 Filter Time -
0 0 0 Filter Time 0
inputs 00-11
inputs 12-15
(Default)
Selected
Filter Tim e
256µs 8.4 26.4 8.4 26.4 7.5 26.5
Filter Time
1794-IA8, -IA8K
(ms)
Off to OnOn to
0 0 1 Filte r Tim e 1 51 2µs 8.6 26.6 8.6 26.6 8 27
0 1 0 Filte r Tim e 2 1m s 9 27 9 27 9 28
0 1 1 Filte r Tim e 3 2m s 10 28 10 28 10 29
1 0 0 Filte r Tim e 4 4m s 12 30 12 30 12 31
1 0 1 Filte r Tim e 5 8m s 16 34 16 34 16 35
1 1 0 Filte r Tim e 6 16 ms 24 42 24 42 24.5 44
1 1 1 Filte r Tim e 7 32 ms 40 58 40 58 42 60.5
Maximum
Filter Time
1794-IA8I
Off to
Off
On
(ms)
Maximum
Filter Time
1794-IA16
(ms)
On
Off to Off
On
to
to
On
Off
Image Table Memory Map for the 1794-IA16
Dec. 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Oct. 17 16 15 14 13 12 11 10 7 6 5 4 3 2 1 0
Read 1 I15I14I13I12I11I10I9 I8 I7 I6 I5 I4 I3 I2 I1 I0
Write 3 Not used - set to 0 Input Filter FT
Where I = Input
FT = Input filter time
12-15
Input Filter FT 0-11
Publication 1794-IN102B-EN-P - June 2004
Specifications
Specifications 1794-IA8, 1794-IA8K 1794-IA8I
Number of Inputs 8, (1 group of 8), nonisolated 8 isolated
Module Location Cat. No. 1794-TB2, -TB3, -TB3S and -TBN Terminal Base Units
On-state Voltage 65V ac minimum
On-state Current
Off-state Voltage 43V ac maximum
Off-state Current 2.9mA minimum
Input Impedance 10.6K ohms nominal
Nominal Input Current 12mA @ 120V ac, 6 0Hz
Isolation Voltage Tested at 2150V dc for 1s between
Input Filter Time Refer to Input F ilter Time ta ble
Flexbus Current 30mA @5V dc
Power Dissipation 4.5W maximum @ 132V ac
Thermal Dissipation Maximum 15.3 BTU/hr @ 132V ac
Specifications - Cat. No. 1794-IA16
Number of Inputs 16 (1 group of 16), nonisolated
Module Location Cat. No. 1794-TB3, -TB3S and -TBN Terminal Base Units
On-state Voltage 74V ac minimum
On-state Current1
Off-state Voltage 20V ac maximum
Off-state Current 2.9 mA minimum
Nominal Input Impedance 10K ohms
Nominal Input Current 12mA @ 120V ac, 60Hz
Isolation Voltage Tested at 2150V dc for 1s between u ser and system
Flexbus Current 20mA
Power Dissipation 6.4W maximum @ 132V ac
Thermal Dissipation Max imum 21.8 BTU/hr @ 132V ac
120V ac nominal 132V ac maximum
1
7.1mA minimum
user and system No isolation between individual channels
120V ac nominal 132V ac maximum
minimum nominal maximum
5.49mA @ 74V ac, 47Hz
12.06mA @ 120V ac, 60Hz
14.81mA @ 132V ac, 63Hz
No isolation between individual chann els
Tested at 2150V dc for 1s between user and system and between individual channels
5
General Specifications
Input Filter Time
Terminal Base Screw Torque
Dimensions (with module installed)
Indicators (field side indication, custome r device driven)
External ac power Supply voltage Voltage range
Keyswitch Position 8
Environmental Conditions
Enclosure Type Rating None (open-style)
Conductors Wire Size
Certifications (when product is marked)
1 Ac inputs compatible with proximity switches wit h leakage ratings of I 2 Input off-to-on filte r time is the time from a v alid input signal to recogn ition by the module. Input o n-to-off filter
3 You use this category information for planning conductor routing as described in Allen-Bradley
4 For the latest up-to- date information, see the Product Certificat ion link at www.ab.com for Declarations of
2
Off to On On to Off
Operating Temperature
Storage Temperature IEC 60068-2-1 (Test Ab, Un-packaged Non-oper ating Cold),
Relative Humidity IEC 60068-2-30 (Test Db, Un-packaged Non-operating
Vibration IEC60068-2-6 (Test Fc, Operating):
Shock IEC60068-2-27 (Test Ea, Unpackaged shock):
Emissions CISPR 11:
ESD Immunity IEC 61000-4-2:
Radiated RF Immunity IEC 61000-4-3:
EFT/B Immunity IEC 61000-4-4:
Surge Transient Immunity
Conducted RF Immunity
Category
time is time from the input signal droppin g below the valid level to recognition by the module.
publication 177 0-4.1, Industrial Automat ion Wiring and Groundin g Guidelines.
Conformity, Certificates and other certification details. For notification of any additional release notes, refer to
www.ab.com/manuals/.
Refer to Input Filter Time chart for values.
7 pound-inches (0.8Nm) 9 pound-inches (1.0Nm) for 1794- TBN
3.7H x 3.7W x 2.7D inches 94H x 94W x 69D mm
1794-IA8, -IA8K - 8 yellow status indicators 1794-IA8I - 8 yellow status in dicators 1794-IA16 - 16 yellow status indicat ors
120V ac nominal 1794-IA8, -IA8K, -IA8I - 85 to 132V ac, 47-63 Hz 1794-IA16 - 74 to 132V ac, 47-63Hz
IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock): 0 to 55°C (32 to 131°F)
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat), IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal Shock): –40 to 85°C (–40 to 185°F)
Damp Heat): 5 to 95% non-condensing
5g @ 10-500Hz
Operating 30g Non-operating 50g
Group 1, Class A (with appropriate e nclosure)
4kV contact discharges 8kV air discharges
10V/m with 1kHz sine-wave 80%AM f rom 30MHz to 1000MHz 10V/m with 200Hz 50% Pulse 100% A M at 900Hz
±2kV at 5kHz on signal ports ±2kV at 5kHz on power ports
IEC 61000-4-5: ±1kV line-line(DM) and ±2kV line-earth(CM ) on signal ports ±1kV line-line(DM) and ±2kV line-earth(CM) on power ports
IEC 61000-4-6: 10Vrms with 1kHz sine-wave 80%AM from 150kHz to 80MHz
12-22AWG (2.5mm2-0.34mm2) stranded copper wire r ated at 75°C or higher 3/64 inch (1.2mm) insulation maximu m
3
2 UL UL Listed Industrial Control Equipm ent
4
CSA CSA certified for Class I, Division 2, Groups A, B, C and D
Hazardous locations
EEx5European Union 94/9/EEC ATEX Directive, compliant with:
EN 50021; Potentially Explosiv e Atmospheres, Protection “n” (European Zone 2) - (1794-IA8K only)
CE4 European Union 89/336/EEC EMC D irective, compliant with:
EN 61000-6-4; Industrial Emis sions EN 50082-2; Industrial Immun ity EN 61326; Meas./Control/Lab., Industria l Requirements
EN 61000-6-2; Industrial Immu nity European Union 73/23/EEC LVD Directive, comp liant with: EN 61131-2; Programmable Control lers
C-Tick4 - Australian Radiocommunications Act compliant with
AS/NZS CISPR 11, Industrial Emissions
< 2.5mA and Ion minimum = 5mA.
leak
Publication 1794-IN102B-EN-P - June 2004
Publication 1794-IN102B-EN-P - June 2004 6 PN 957867-39
Supersedes Publication 1794-IN102A -EN-P - March 2004 Copyright © 2004 Rockwell Automatio n, Inc. All rights reserved. Printed in the U.S.A.
Loading...