Rockwell Automation 1793-OB16 User Manual

Installation Instructions
FLEX Integra 16 Protected Source Output Module
(Cat. No. 1793-OB16P and -OB16PS)
Module Installation
This module mounts on a DIN rail. It connects to an adapter or another FLEX I/O or Integra module. Note: If using this module with FLEX I/O modules, do not mount between FLEX I/O modules. Mount Integra modules to the right of the FLEX I/O modules. To mount this module:
1. Remove the cover plug (if used) in the male connector of the unit to which you are connecting this module.
2. Position the module on the 35 x 7.5mm DIN rail A (A-B pt. no. 199-DR1).
3. Rotate the module onto the DIN rail with the top of the rail hooked under the lip on the rear of the module.
A
A
30869-M
FLEX I/O and FLEX Integra are trademarks of Rockwell Automation Publication 1793-5.9 - December 1999
2 FLEX Integra 16 Protected Source Output Module
30870-M
30871-M
30872-M
4. Press down to lock the module on the DIN rail.
If the module does not lock in place, use a screwdriver of similar device to move the locking tab down, press the module flush with the DIN rail and release the locking tab to lock the module in place.
5. Firmly push the module into the adjacent module/terminal base until the units lock together.
6. Repeat the above steps to install the next module.
7. To remove an Integra module, you must work from the right side and
remove one module at a time. To disengage a module from its neighbor, place a common flat-bladed screwdriver between the 2 modules and turn 1/4 turn to separate the modules.
8. Then slide the module away from its left neighbor, and release the locking lever to remove the module from the DIN rail.
Publication 1793-5.9 - December 1999
FLEX Integra 16 Protected Source Output Module 3
ATTENTION: Do not remove this module under power. Removing this module under power will break the
!
electrical backplane (flexbus) connections. This can cause personal injury or property damage by:
• sending an erroneous signal to your system's field devices causing unintended machine motion
• causing an explosion in a hazardous environment
• breaking communication to modules beyond this module
European Union Directive Compliance
If this product has the CE mark it is approved for installation within the European Union and EEA regions. It has been designed and tested to meet the following directives.
EMC Directive
This product is tested to meet Council Directive 89/336/EEC Electromagnetic Compatibility (EMC) and the following standards, in whole or in part, documented in a technical construction file:
• EN 50081-2 EMC - Generic Emission Standard, Part 2 - Industrial Environment
• EN 50082-2 EMC - Generic Immunity Standard, Part 2 - Industrial Environment
This product is intended for use in an industrial environment.
Low Voltage Directive
This product is tested to meet Council Directive 73/23/EEC Low Voltage, by applying the safety requirements of EN 61131-2 Programmable Controllers, Part 2 - Equipment Requirements and Tests.
For specific information required by EN 61131-2, see the appropriate sections in this publication, as well as the following Allen-Bradley publications:
• Industrial Automation Wiring and Grounding Guidelines For Noise Immunity, publication 1770-4.1
• Automation Systems Catalog, publication B111
This equipment is classified as open equipment and must be mounted in an enclosure during operation to provide safety protection.
Publication 1793-5.9 - December 1999
4 FLEX Integra 16 Protected Source Output Module
A
B
01 23 45678 9101112131415COM
COM
VVCOM COM
41817
0 12345 6789101112131415
A
B
41815
VV
COM
COM
COM
COM
Wiring
This module is available with 2 styles of terminations: 1793-OB16P ­screw-cage and 1793-OB16PS - spring-clamp. Refer to the wiring figure below.
1793-OB16P
1793-OB16PS
Where: COM = common, V = +24V dc power, 0 thru 15 = outputs
1. Connect individual sensor signal output leads to terminals 0 through
15 on row A (channels 0 thru 15 respectively).
2. Connect the associated sensor common lead to a COM terminal on
row (B).
3. Connect +24V dc voltage to V terminal on row B.
4. Connect 24V dc common to terminal COM on row A.
5. If daisy-chaining + 24V dc from this module to the next Integra
module, connect a jumper from terminal V to terminal 8 on the next 8 point Integra module or terminal V on the next 16 point Integra module.
6. If daisy-chaining 24V dc common from this module to the next FLEX
Integra module, connect a jumper from terminal COM on this module to terminal 0 on the next 8 point Integra module, or to terminal COM on the next 16 point Integra module.
.
ATTENTION: Total current draw through the module’s (V) voltage terminals is limited to 10A. Separate power
!
Publication 1793-5.9 - December 1999
connections to the module may be required.
FLEX Integra 16 Protected Source Output Module 5
Wiring Connections
Channel Output Common Channel Output Common
00
11 99
2 2 10 10
3 3 11 11
4 4 12 12
5 5 13 13
6 6 14 14
7 7 15 15
+24V dc Power terminals V are internally connected together in the module.
24V dc common
Common terminals COM are internally connected together in the module.
connect to
corresponding
terminal on
row B
88
connect to
corresponding
terminal on row
Indicators
B
24 VDC SOURCE OUTPUT - PROTECTED
0 1 2 3 4 5 6 7 8 9 10 11 14 1512 13
AB
1793-OB16P
41813
A = Status indicators - 0 through 15 - shows status of individual outputs
B = Insertable label for writing individual input designations
Memory Mapping
Bit/
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Word
Read Reserved
Write O15O14O13O12O11010O9O8O7O6O5O4O3O2O1O
Where: O = Output
Important: Input and output wiring must be in accordance with Class I,
Division 2 wiring methods and in accordance with the authority having jurisdiction.
Publication 1793-5.9 - December 1999
0
6 FLEX Integra 16 Protected Source Output Module
CUS
LISTED
CL I, DIV 2
GP A,B,C,D
TEMP
LISTED
CL I, DIV 2
GP A,B,C,D
TEMP
C-UL and UL Hazardous Location Approval
C-UL and UL certifies products for general use as well as for use in hazardous locations. Actual
C-UL and UL certification is indicated by the product label as shown below, and not by
statements in any user documentation.
Example of the C-UL and UL certification product label
To comply with C-UL and UL certification for use in hazardous locations, the following information becomes a part of the product literature for this C-UL and UL-certified industrial constrol product.
Important: Due to the modular nature of a
This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D, or non-hazardous locations only.
The products having the appropriate C-UL and UL markings (that is, Class I, Division 2, Groups A, B, C, D) are certified for use in other equipment where the suitability of combination (that is, application or use) is determined by the C-UL and UL or the local inspection office having jurisdiction
Peripheral equipment must be suitable for the location in which it is used.
programmable control system, the product with the highest temperature rating determines the overall temperature code rating of a programmable control system in a Class I, Division 2, location. The temperature code rating is marked on the product label as shown.
Approbation d’utilisation dans des environnements dangereux par la C-UL and UL
La C-UL and UL certifie des produits pour une utilisation générale aussi bien que pour une utilisation en environnements dangereux. La certification C-UL and UL en vigueur est indiquée par l'étiquette produit et non par des indications dans la documentation utilisateur.
Exemple d'étiquette de certification d'un produit par la C-UL and UL
Importa nt: De par la nature modulaire des systèmes de
EPour satisfaire à la certification C-UL and UL en environnements dangereux, les informations suivantes font partie intégrante de la documentation des produits de commande industrielle certifiés.
Cet équipement ne convient qu’à une utilisation dans des environnements de Classe I, Division 2, Groupes A, B, C, D ou non dangereux.
Les produits portant le marquage C-UL and UL approprié (c'est-à-dire Classe I, Division 2, Groupes A, B, C, D) sont certifiés pour une utilisation avec d'autres équipements, les combinaisons d’applications et d’utilisation étant déterminées par la C-UL and UL ou le bureau local d'inspection.
L'équipement périphérique doit convenir à l'emplacement d'utilisation.
commande programmables, le produit ayant le code de température le plus élevé détermine le code de température global du système dans un environnement de Classe I, Division 2. Le code de température est indiqué sur l'étiquette produit.
7HPSHUDWXUHFRGHUDWLQJ &RGHGHWHPSpUDWXUH
CL I, DIV 2
GP A,B,C,D
TEMP
CUS
LISTED
The following warnings apply to products having C-UL and UL certification for use in hazardous locations.
Look for temperature code rating here.
CUS
LISTED
Les avertissements suivants s'appliquent aux produits ayant la certification C-UL and UL pour une utilisation dans des environnements dangereux.
CUS
CL I, DIV 2
GP A,B,C,D
TEMP
Le code de température est indiqué ici.
Publication 1793-5.9 - December 1999
FLEX Integra 16 Protected Source Output Module 7
C-UL and UL Hazardous Location Approval
WARNING: Explosion Hazard
Substitution of components may impair
suitability for Class I, Division 2.
Do not replace components unless power has been switched off or the area is known to be non-hazardous.
Do not disconnect equipment unless power has been switched off or the area is known to be non-hazardous.
Do not disconnect connectors unless power has been switched off or the area is known to be non-hazardous. Secure any user-supplied connectors that mate to external circuits on this equipment by using screws, sliding latches, threaded connectors, or other means such that any connection can withstand a 15 Newton (3.4 lb.) separating force applied for a minimum of one minute.
Batteries must only be changed in an area known to be non-hazardous.
C-UL and UL logo is a registered trademark of the Underwriters Laboratories.
Approbation d’utilisation dans des environnements dangereux par la C-UL and UL
$9(57,66(0(175LVTXHGH[SORVLRQ
La substitution de composants peut rendre ce
matériel inadapté à une utilisation en environnement de Classe I, Division 2.
Couper le courant ou s'assurer que l’environnement est classé non dangereux avant de remplacer des composants.
Couper le courant ou s’assurer que l’environnement est classé non dangereux avant de débrancher l'équipement.
Couper le courant ou s'assurer que l’environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs fournis par l'utilisateur pour se brancher aux circuits externes de cet appareil à l 'aide de vis, loquets coulissants, connecteurs filetés ou autres, de sorte que les connexions résistent à une force de séparation de 15 Newtons (1,5 kg - 3,4 lb.) appliquée pendant au moins une minute.
S'assurer que l'environnement est classé non dangereux avant de changer les piles.
Le sigle C-UL and UL est une marque déposée de la Underwriters Laboratories.
Specifications - 16 Protected Output Module Cat. No. 1793-OB16P and -OB16PS
Module Type 16 digital output - sourcing, protected
1793-OB16P - screw-cage terminations 1793-OB16PS - spring-clamp terminations
Module Location DIN rail mounting
Number of Channels 16 (1 group of 16, nonisolated)
On-state Voltage 10V dc minimum
24V dc nominal
31.2V dc maximum
On-state Current 1mA minimum per channel
500mA maximum per channel
Surge Current 1.5A for 50ms, repeatable every 2s
Off-state Leakage 0.5mA maximum leakage
On-state Voltage Drop 0.5V dc maximum
Isolation Voltage 100% tested at 850V dc for 1s between user and
system. No isolation between individual channels
Publication 1793-5.9 - December 1999
8 FLEX Integra 16 Protected Source Output Module
Specifications - 16 Protected Output Module Cat. No. 1793-OB16P and -OB16PS
Delay Time Off to On
On to Off
0.5ms maximum
1.0ms maximum
Flexbus Current 80mA maximum
Power Dissipation 5W @ 31.2V dc
Thermal Dissipation 17 BTU/hr @ 31.2V dc
Indicators 16 yellow channel status indicators
Fusing Outputs are electronically protected
External dc Power Voltage
Current
Dimensions Inches
(Millimeters)
19.2-31.2V dc (5% ac ripple) 60mA
2.72H x 3.7D x 2.17W (69H x 94D x 80W)
Environmental Conditions
Operational Temperature Storage Temperature Relative Humidity Shock Operating
Nonoperating
Vibration
Conductors Wire Size
Category
o
C (32 to +131oF)
0 to +55
-40 to +85
o
C (-40 to +185oF) 5 to 95% noncondensing Tested to 30g peak acceleration, 11(+ Tested to 50g peak acceleration, 11(+
Tested 5g @ 10-500Hz per IEC68-2-6
2
12 gauge (4mm
wire rated @ 75
) to 18 gauge (0.75mm2) stranded
o
C minimum
3/64 in (1.2mm) maximum insulation
1
2
1)ms pulse width
1)ms pulse width
Screw Terminal Torque 5-7 lb-in (0.5-0.6Nm)
Agency Certification (when product is marked)
• C-UL listed
• C-UL Class I, Division 2 Groups A, B, C and D certified
• UL listed
• CE marked for all applicable directives
• C-Tick marked for all applicable acts
1 Use this categor y information for planning conductor routing as described in publication 1770-4.1, “Wiring a nd
Grounding Guidelines for Noise Immunity.”
Publication 1793-5.9 - December 1999 PN 957259-16
Supersedes publication 1793-5.9 - September 1999 © (1999) Rockwell International Corporation.Printed in USA