Rockwell Automation 1792-OB8PLP User Manual

Installation Instructions

Cat. No. 1792-OB8PLP
This 1792 ArmorBlock I/O block module (Cat. No. 1792-OB8PLP) contains I/O circuits, a built-in power supply, and a built-in DeviceNet I/O adapter. Because of its sealed housing, this 1792 I/O block requires no enclosure. It is compatible with PLC or SLC programmable controllers using DeviceNet scanners. The I/O values are accessible from the PLC or SLC programmable controller data table.
This ArmorBlock-LP module has no switches to set. You set module parameters using the DeviceNet Manager Software (cat. no. 1787-MGR) or similar configuration tool.

Contents

This box contains:
1 ArmorBlock–LP module
Package containing 10 write-on indicator tabs, and 7 micro caps
1 DeviceNet right-hand aluminum T-port tap (part number 97042401)
Installation Instructions
DeviceNet is a trademark of Open DeviceNet V
DeviceNetManager is a trademark of Rockwell Automation
endor Association, Inc.
Publication
1792-5.7 – December 1997
ArmorBlock-LP 8 Output Module2

European Union Directive Compliance

If this product is installed within the European Union or EEA regions and has the CE mark, the following regulations apply.

EMC Directive

This apparatus is tested to meet Council Directive 89/336/EEC Electromagnetic Compatibility (EMC) using a technical construction file and the following standards, in whole or in part:
EN 50081-2 EMC – Generic Emission Standard, Part 2 –
Industrial Environment
EN 50082-2 EMC – Generic Immunity Standard, Part 2 –
Industrial Environment
The product described in this manual is intended for use in an industrial environment.

Low Voltage Directive

This apparatus is also designed to meet Council Directive 73/23/EEC Low Voltage, by applying the safety requirements of EN 61131–2 Programmable Controllers, Part 2 – Equipment Requirements and Tests.
For specific information that the above norm requires, see the appropriate sections in this manual, as well as the following Allen-Bradley publications:
Industrial Automation Wiring and Grounding Guidelines, publication
1770-4.1
Automation Systems Catalog, publication B111
Publication
1792-5.7 – December 1997
ArmorBlock-LP 8 Output Module 3
M

Install Your ArmorBlock-LP Module

Installation of the ArmorBlock-LP module consists of:
setting the node address and communication rate in the ArmorBlock
module
mounting the ArmorBlock module
connecting the wiring
communicating with your module

Set the Node Address

Each ArmorBlock-LP comes with its internal program set for node address 63 and a communication rate of 125K bps. To set the node address and communication rate, you need the following:
host computer with DeviceNet Manager Software (or similar
configuration software tool)
1770-KFD RS-232 module (or similar interface)
suitable cables to connect the 1770-KFD to your module and to
connect the 1770-KFD to your host computer
Set up a system (as shown below) to communicate with your ArmorBlock module to set the node address and communication rate to meet your system requirements.
Power from 9V dc power supply adapter
1770-KFD
RS-232 module
Host computer with
DeviceNetManager
software
Power Supply
Open style connector
to sealed mini–connector
Publication
1792-5.7 – December 1997
30195–
ArmorBlock-LP 8 Output Module4

Mount the ArmorBlock Module

Mount the block module directly to the machine or device. Complete mounting dimensions are shown below.

Mounting Dimensions

1.8
1.5
(45)
(38)
0.63 (16)
0.8
(20.1)
2.4
(60)
1.4
(36)
A A
OUT OUT
inches
(millimeters)
Use 3 #8 (4mm) screws to mount block
8
7
(27)
1.1
A A
(172.1)
6
5
(27)
6.8
1.1
4.2
(107)
2
A A
A A
34
1.1
(27)
1
1.25 (32)
1.0
(25.5)
6.0
(152)
1.3
(33)
2.0
(51)
0.18 (4.5)
1.5
(39)
30199–M
Publication
1792-5.7 – December 1997
ArmorBlock-LP 8 Output Module 5

Connect the Wiring to the ArmorBlock Module

This module uses quick disconnect, screw-on style connectors for:
I/O output wiring
the DeviceNet connector
the output power connector
Eight
5-pin Output Micro-connectors
Output Power
3-pin Mini-connector
OUT OUT
8
A A
7
6
A A
5-pin DeviceNet Mini-connector
A A
5
34
2
A A
1
30197–M
Seven micro caps are included with your module. Use these caps to cover and seal unused ports. Pinout diagrams for the connectors are shown below.
ATTENTION: Make sure all connectors are securely tightened to properly seal the connections against leaks and
!
maintain IP67 requirements.

Connecting the Output Wiring

Connect output wiring to the micro-connectors which screw into mating connectors on the front of the block.
I/O Output Micro-Connector
34
5
1
2
Pin 1 = No connection Pin 2 = Not used Pin 3 = Negative/Return Pin 4 = Signal A
(View into socket)
Pin 5 = Ground
Publication
1792-5.7 – December 1997
ArmorBlock-LP 8 Output Module6

Connecting the Output Power Wiring

Connect output power wiring to the 3-pin mini-connector on the end of the block.
Important:
your output power supply can handle overcurrent events.
Output Power Mini-Connector
The outputs use electronic overcurrent fault protection. Make certain
3
1
(View into pins)
2
Pin 1 = Chassis ground Pin 2 = +24V dc Pin 3 = Negative/Return

Connecting the DeviceNet Wiring

Connect DeviceNet wiring to the 5-pin mini-connector on the end of the block. Connections are shown below.
DeviceNet Mini-Connector
3
4
5
(View into pins)
Pin 1 = Drain (Bare) Pin 2 = V+ (Red)
2
Pin 3 = V– (Black)
1
Pin 4 = CAN–HI (White) Pin 5 CAN–LO (Blue)
Note:
Colors are
DeviceNet standard
Publication
1792-5.7 – December 1997
ArmorBlock-LP 8 Output Module 7

Communicate with Your ArmorBlock Module

This ArmorBlock module’s I/O is exchanged with the master through a poll, bit strobe or change of state connection.
When set for Polled, Bit Strobe, or change of state, the module consumes and produces as follows:
Type of I/O Connections Consumes Produces
Polled 1 Bytes Bit Strobe Change of State
0 Bytes 0 Bytes
1 Byte 1 Byte 1 Byte
Polled device – a master initiates communication by sending its polled I/O message to the ArmorBlock module. The 8 output module consumes the message, updates outputs, and produces a response that reflects the status of its output faults.
Change of state device – productions occur when a fault condition changes. If no fault condition occurs within the “expected packet rate,” a heartbeat production occurs. This heartbeat production tells the scanner module that the ArmorBlock module is alive and ready to communicate.
Bit Strobe device – a master initiates communication by sending its bit strobe I/O message. All bit strobed devices then respond. The 8 output module consumes the message, and produces a response that reflects the status of output faults.
Publication
1792-5.7 – December 1997
ArmorBlock-LP 8 Output Module8
Produces
Refer to the table below for the word/bit definitions.
Bit 07 06 05 04 03 02 01 00
Consumes O8A O7A O6A O5A O4A O3A O2A O1A
Produces Reser
Where: O = Output
OF = Output fault status
Word Bit Description
OF Reserved
ved
Consumes 00–07 Output bits – when the bit is set (1), the output is on. Bit 00
Produces
corresponds to output 1A, bit 01 corresponds to output 2A, bit 02 to output 3A, bit 03 output 4A, bit 04 corresponds to output 5A, bit 05
to output 6A, bit 06 to output 7A, and bit 07 to output 8A. 00–05 Reserved 06 OF = output fault status bit – indicates presence of field power and
overload condition. 07 Reserved

Troubleshoot with the Indicators

The ArmorBlock I/O module has the following indicators:
Network status indicators (NS)
Module status indicator (MS)
Individual Output status indicators A1 through A8
Power Status indicators
module poweroutput voltageoutput status
Publication
1792-5.7 – December 1997
ArmorBlock-LP 8 Output Module 9
NS = Network Status Indicator
Output
Connector
U
= Output Power
S
Supply Status Indicator
U
L
8
OUT
A A
OUT
7
= Module Power Supply
6
A A
A A
5
34
MS = Module Status
Indicator
Status Indicator
Network
Status Indicator (NS)
Indication Status
Flashing Green Solid Green Flashing Red Solid Red
Module Status Indicator (MS)
Indication Status
OFF
Flashing Green/OFF Solid Green Flashing Red Solid Red
Output Short Circuit Indicator
Indication Status
OFF
Solid Red
Output I/O Status Indicator (1A thru 8A)
Indication Status
OFF Yellow
Module and Output Power Supply Status Indicators US and U
Indication Status
OFF Green
On-line, not connected Link OK, on-line connected At least 1 I/O connection is in the timed-out state Incorrect baud rate, or a duplicate Mac ID exists
No power
, or no network access
On-line but not connected On-line, link okay Recoverable fault Critical failure
No shorted outputs Shorted output
Output is of Output is on
Power supply is not functioning correctly Power Supply is operating
, connected
f
Output Short
Circuit Indicator
2
A A
1
A = Output
Status Indicators
30197–M
L
Publication
1792-5.7 – December 1997
ArmorBlock-LP 8 Output Module10

Specifications

8 Output Module – Cat. No. 1792-OB8PLP Output Power Supply Note: In order to comply with CE Low Voltage
Output Specifications
Outputs per Block 8 Sourcing Outputs – labeled 1A through 8A Output Voltage Range 19–30V dc On-state Current Maximum 2.0A per output at 60oC On-state Voltage Maximum 3.0V dc at rated current Module Current (all outputs
on) Off-state Leakage Current 1.5mA maximum per output Surge Current Maximum 4.0A for 10ms, repeatable every 2s Indicators Network Status – red/green
Communication Rate in Baud 125k, 250k, 500k software selectable
Specifications continued on next page.
Directives, you must use a Safety Extra Low Voltage (SELV) or a Protected Extra Low Voltage (PELV) power supply to power the outputs of this module.
12.0A per module
Module Status – red/green Output Status – Yellow Output Fault – Red Module Power Supply Status – green
Publication
1792-5.7 – December 1997
ArmorBlock-LP 8 Output Module 11
General Specifications
DeviceNet PowerVoltage
Current
Dimensions Inches
Millimeters
Environmental Conditions
Operational Temperature Storage Temperature Relative Humidity Shock Operating
Non-operating
Vibration
Conductors Refer to publication 1485-6.7.1 for information on
Enclosure Meets or exceeds IP67 Agency Certification
(when product is marked)
11.0 – 25.0V dc 100mA
6.8H X 2.4W X 2.0D
172.1H X 60W X 51D
0 to 60oC (32 to 140oF) –20 to 80oC (–4 to 176oF) up to 100% 30 g peak acceleration, 11(+ 50 g peak acceleration, 11(+ Tested 10 g @ 10–500Hz per IEC 68-2-6
cabling for your DeviceNet module.
CE marked for all applicable directives
1)ms pulse width
1)ms pulse width
This product has been tested at an Open DeviceNet Vendor Association, Inc. (ODVA) authorized independent test laboratory and found to comply with ODVA Conformance Test Software Version FT 1.3/1.1.
Publication
1792-5.7 – December 1997
ArmorBlock-LP 8 Output Module12
Worldwide representation.
Argentina • Colombia • Costa Rica • Croatia • Cyprus • Czech Republic • Denmark • Ecuador • Egypt • El Salvador Finland Indonesia • Mexico Puerto Rico • Qatar • Romania • Russia–CIS • Saudi Arabia • Singapore Africa, Republic • Spain • Sweden United Kingdom • United States • Uruguay • V
Allen-Bradley Headquarters, 1201 South Second Street, Milwaukee, WI 53204 USA, Tel: (1) 414 382-2000 Fax: (1) 414 382-4444
Publication
Australia • Austria • Bahrain • Belgium
France • Germany • Greece • Guatemala • Honduras • Hong Kong • Hungary • Iceland • India
Ireland • Israel • Italy • Jamaica •
Netherlands
1792-5.7 – Novembrr 1997
Publication
New
Zealand • Norway
Switzerland T
1792-5.7 – December 1997
Brazil
Bulgaria • Canada • Chile • China, PRC
Japan • Jordan • Korea • Kuwait • Lebanon
Pakistan
enezuela • Y
aiwan
Peru
Philippines
Thailand T
ugoslavia
Copyright
Poland • Portugal
Slovakia Slovenia
urkey • United Arab Emirates
1997 Allen-Bradley Company
Malaysia
South
PN955128–54
, Inc. Printed in USA
Loading...