Rockwell Automation 1792-IB2XOB2EB User Manual

Installation Instructions
 
Cat. No. 1792-IB2XOB2E Series B
To: See page:
Install
the ArmorBlock Module Connect the Wiring to the ArmorBlock Module Communicate with Y Configure Y
Manager Configuration T Configure Y
Manager Configuration T Reset Faults 25
Configure Y
For this reference information
Default Configuration Status indicators Troubleshooting 32 Specifications 34
our ArmorBlock Module
our ArmorBlock Module Of
ool
our ArmorBlock Module Online Using the DeviceNet
ool
our ArmorBlock Module with EDS Files
fline Using the DeviceNet
3
8 10 11
17
27
See page:
14 32
This 1792 ArmorBlock I/O block module (Cat. No. 1792-IB2XOB2E) contains I/O circuits, a built-in power supply, and a built-in DeviceNet I/O adapter. Because of its sealed housing, this 1792 I/O block requires no enclosure. It is compatible with PLC or SLC programmable controllers using DeviceNet scanners. The I/O values are accessible from the PLC or SLC programmable controller data table.
This ArmorBlock module has no switches to set. You set module parameters using the DeviceNet Manager Software (cat. no. 1787-MGR) or similar configuration tool.
ArmorBlock is a trademark of Allen-Bradley Co. Inc.
Publication 1792-5.5 – October 1996
ArmorBlock 2 Input/2 Output Module2
European Union Directive Compliance
If this product is installed within the European Union or EEA regions and has the CE mark, the following regulations apply.
EMC Directive
This apparatus is tested to meet Council Directive 89/336/EEC Electromagnetic Compatibility (EMC) using a technical construction file and the following standards, in whole or in part:
EN 50081-2 EMC – Generic Emission Standard, Part 2 –
Industrial Environment
EN 50082-2 EMC – Generic Immunity Standard, Part 2 –
Industrial Environment
The product described in this manual is intended for use in an industrial environment.
Low Voltage Directive
This apparatus is also designed to meet Council Directive 73/23/EEC Low Voltage, by applying the safety requirements of EN 61131–2 Programmable Controllers, Part 2 – Equipment Requirements and Tests.
For specific information that the above norm requires, see the appropriate sections in this manual, as well as the following Allen-Bradley publications:
Industrial Automation Wiring and Grounding Guidelines,
publication 1770-4.1
Automation Systems Catalog, publication B111
Publication 1792-5.5 – October 1996
ArmorBlock 2 Input/2 Output Module
Install Your ArmorBlock Module
Installation of the ArmorBlock module consists of:
setting the node address in the ArmorBlock module
mounting the ArmorBlock module
connecting the wiring
communicating with your module
configuring the parameters
Set the Node Address
Each ArmorBlock comes with its internal program set for node address
63. To set the node address, you need the following:
host computer with DeviceNet Manager Software (or similar
configuration software tool)
1770-KFD RS-232 module (or similar interface)
suitable cables to connect the 1770-KFD to your module and to
connect the 1770-KFD to your host computer
3
Set the node address to meet your system requirements as follows:
1. Set up a system (as shown below) to communicate with your
ArmorBlock module.
Power
from 9V DC Power-Supply Adapter
1770-KFD
RS-232 module
open style connector to sealed mini-female cable
host computer with the DeviceNet Manager software
power supply
Publication 1792-5.5 – October 1996
ArmorBlock 2 Input/2 Output Module4
2. Using DeviceNet Manager Software, go online using the “Setup
Online Connection” selection on the utility pulldown menu.
3. The DeviceNet Driver selection screen appears.
Select the driver for your application and click on .
4. The Driver configuration screen lets you:
set the data rate
set the interface adapter node address
select the interface adapter serial port
set interface adapter baud rate
Click on to go online.
Publication 1792-5.5 – October 1996
ArmorBlock 2 Input/2 Output Module
5
5. The bar at the bottom of the screen will tell you when you go online.
6. At the utility pulldown, select “Node Commissioning.”
7. You can set the node address on the “Device Configuration – Node
Commissioning” screen. Note that the node address “out of the box” setting is 63. Set the desired node address per your system requirements.
Set new node address here.
You can also set the data rate on this screen, if required. However, your module is shipped with the “autobaud” parameter enabled. This assures that the module will be at the correct data rate for any network to which it is connected. To change the data rate, you must first disable autobaud on the parameter screen, then return to the “Device Configuration – Node Commissioning” screen and enter the new data rate.
8. Click on
to apply the new node settings.
9. Repeat the above procedure to set the node addresses of any
additional ArmorBlock modules you want to install.
Publication 1792-5.5 – October 1996
ArmorBlock 2 Input/2 Output Module6
Mount the ArmorBlock Module
Mount the block module directly to the machine or device. Complete mounting dimensions are shown below. Note that the block dimensions allow direct connection of a T-port tap (cat. no. 1485P-P1N5-j) to the DeviceNet connector. (Refer to publication 1485-6.7.1 for cabling details.)
The ArmorBlock module has a sloping top and a gap at the rear to allow water or other liquids to run off during washdowns. The flow through the gap prevents buildup of debris under the block.
Preferred mounting position is with the microconnectors pointing down. However, the block can be mounted in any orientation.
Publication 1792-5.5 – October 1996
Mounting Dimensions
.
1.90
(48.3)
3.055 (77.6)
Inches
(Millimeters)
2.63
(66.7)
2.5
(63.5)
ADDRESS
NODE
ArmorBlock 2 Input/2 Output Module
25
7
7
(184.2)
ARMORBLOCK
MOD/NET
INPUT
STATUS
FAULT
TE RA
DATA
1792-IB2XOB2E
I/O
4
mounting holes
for #10 screws
6.24
(158.5)
Block dimensions allow T
-port tap
connection directly onto connector
For washdown installations, or excessively moist areas, mount block with micro connectors down.
7.74
(196.6)
Direction
of liquid flow
Publication 1792-5.5 – October 1996
ArmorBlock 2 Input/2 Output Module8
Connect the Wiring to the ArmorBlock Module
The block module uses quick disconnect, screw-on style connectors for:
I/O input wiring
I/O output wiring
power wiring for I/O outputs
the DeviceNet connector
DeviceNet
mini connector
2 micro connectors for output wiring
0101
Output power
mini connector
2 micro connectors for input wiring
4 micro plugs – these seal unused ports
Micro plugs are included with your module. Use these plugs to cover and seal unused ports.
Pinout diagrams for these connectors are shown below.
ATTENTION: All connectors must be securely tightened to properly seal the connections against leaks
!
Publication 1792-5.5 – October 1996
and maintain NEMA 4X and 6P requirements.
ArmorBlock 2 Input/2 Output Module
Connecting the Input Wiring
Connect input wiring to the micro connectors which screw into mating connectors on the side of the block.
Make connections as shown below.
I/O Input Micro Connector
9
4
1
3
2
(View into socket)
Pin 1 = Sensor Source Voltage Positive Pin 2 = Not used Pin 3 = Negative/Return Pin 4 = Signal
Connecting the Output Wiring
Connect individual output wiring to micro connectors which screw into mating connectors on the side of the block. Make connections as shown below.
I/O Output Micro Connector
4
1
3
2
(View into socket)
Connect the output power wiring to the 3-pin mini connector on the end of the block.
Important: The
Output Power Mini Connector
outputs use electronic overcurrent fault protection. Make certain
your output power supply can handle overcurrent events.
Pin 1 = Not used Pin 2 = Not used Pin 3 = Negative Pin 4 = Output
1
23
(View into pins)
Pin 1 = Not used Pin 2 = Positive Pin 3 = Negative
Publication 1792-5.5 – October 1996
ArmorBlock 2 Input/2 Output Module10
Connecting the DeviceNet Wiring
Connect DeviceNet wiring to the 5-pin mini connector on the end of the block. Connections are shown below.
DeviceNet Mini Connector
Pin 1 = Drain (Bare)
1
2
3
(View into pins)
5
4
Pin 2 = V+ (Red) Pin 3 = V– (Black) Pin 4 = CAN–HI (White) Pin 5 CAN–LO (Blue)
Note: Colors are DeviceNet standard
Communicate with Your ArmorBlock Module
This ArmorBlock module acts as a slave in a master/slave environment. It is both a “polled device” and a “change of state device.”
When configured as a polled device, a master initiates communication by sending its polled I/O message to the ArmorBlock module. The 2 input/2 output module scans the inputs and fault bits producing a response, and consumes the message, updates outputs, and produces a response that reflects their status.
When configured as a “change of state” device, productions occur when an input changes, or an output fault occurs. If neither has occurred within the “expected packet rate,” a heartbeat production occurs. This heartbeat production tells the scanner module that the ArmorBlock module is alive and ready to communicate.
Publication 1792-5.5 – October 1996
ArmorBlock 2 Input/2 Output Module
11
Bit
Produces IS Reserved OF1 OF0 I1 I0
Consumes Reserved O1 O0
Where: I = Input
IS = Sensor source voltage fault O = Output OF = Output fault
Word Bit Description
Produces
Consumes
00–01 Input bits – bit 00 corresponds to input 0, bit 01 to input 1. When the
02–03 Output fault bits – Shows fault status of each output. OS0
04–06 Reserved 07 Sensor source voltage fault bit – this bit is set (1) when the sensor
00–01 Output bits – Bit 00 corresponds to output 0, bit 01 corresponds to
02–07 Reserved
07 06 05 04 03 02 01 00
bit is set (1), the input is on.
corresponds to output 0, and OS1 corresponds to output 1. When the bit is set (1), the output is faulted.
source voltage is faulted.
output 1. 0 = output off; 1 = output on
Configure Your Armor Module Offline Using the DeviceNet Manager Configuration Tool
To configure your ArmorBlock module offline:
add the device to the network
set the parameters for the device
save the parameters to a file
Note: You cannot actually configure your device offline. You can set and save the parameters to a file for downloading to the device when you go online.
Publication 1792-5.5 – October 1996
ArmorBlock 2 Input/2 Output Module12
Adding a Device to the Network
Action Response
At
the network screen, click on the
“add device” button.
At the “add device to network” screen, click on “discrete I/O” in the device type box.
Then click on the desired ArmorBlock device.
Select the device node address for this device.
Click on the OK button when you have selected your device. Add more devices as necessary.
Publication 1792-5.5 – October 1996
ArmorBlock 2 Input/2 Output Module
13
Configure your Device Parameters
After adding the devices to the network, you must configure them. You have 2 choices:
highlight the device, and click on the button, or
double-click on the device to bring up the device configuration
screen.
For detailed device information on this device, click on .
Publication 1792-5.5 – October 1996
ArmorBlock 2 Input/2 Output Module14
Configuring the Parameters
Default settings for the 2 in/2 out module are:
autobaud when
of
f to on delay
on to of
f delay
fault state idle state reset faulted I/O reset sensor source voltage and faulted outputs
enabled, matches device baud rate to network baud
rate at powerup time from a valid input signal to recognition by the block
module time from input signal dropping below the valid level to
recognition by the block module defines output behavior during a communication fault defines output behavior during program mode
1. Double click on the parameter you want to change.
enable
no delay
no delay
reset outputs reset outputs nothing selected
The parameter screen appears.
Publication 1792-5.5 – October 1996
ArmorBlock 2 Input/2 Output Module
15
2. Click on the radio button to select a different setting. To save the
setting, click on
. To cancel any changes, click on
.
3. For help about a specific parameter, click on
. A screen
similar to this will appear. To continue, click on
4. Continue with any additional parameters you want set for your
block module. The 2 input/2 output module has the following additional parameters: off to on delay, on to off delay, idle state, fault state, and reset faulted I/O..
When you have completed each parameter selection, click on the
button. This returns you to the device configuration
screen. You can save these parameters to a file for downloading to the device
when online, or print them to a text file for hard copy use.
Publication 1792-5.5 – October 1996
ArmorBlock 2 Input/2 Output Module16
Saving to a File
1. To save those parameters to a file, click on the
button.
You see this screen.
2. Choose the file name, file type (.dcf), directory, and drive to which
you want to save the file.
3. Click on the
button to save.
Printing to a Text File
1. If you choose to save your changes to a text file, click on the
button.
A screen similar to the following will appear.
Publication 1792-5.5 – October 1996
ArmorBlock 2 Input/2 Output Module
2. Choose the file name, file type (.TXT), directory and drive to which
you want to save the file.
17
3. Click on the
hard copy for future reference.
button to save. Use this file to print out as
Online Help
Online help is available on all screens. Click on to bring up pertinent information concerning the device configuration you are selecting.
Additionally, help is available on each parameter screen by clicking on
.
Configure Your Armor Module Online Using the DeviceNet Manager Configuration Tool
The procedure for online configuration is similar to the offline configuration procedure previously described. You must:
establish the interface to the network
add the device to the network from the Add Device to Network
screen
access and configure the device parameters
Establish the Interface
1. Select the “set up online connection” at the Utilities pulldown menu.
Publication 1792-5.5 – October 1996
ArmorBlock 2 Input/2 Output Module18
2. The configuration screen for your selected driver appears. You can:
set the node address
set the data rate
select the interface adapter serial port
set the interface adapter baud rate
3. After setting the parameters, click on the button. The
system will automatically go online, as shown at the bottom of the screen.
Online
will also appear in the Network area.
Publication 1792-5.5 – October 1996
Add the Device to the Network
Action Response
At
the network screen, click on the
“add device” button.
At the “add device to network” screen, click on “discrete I/O” in the device type box.
ArmorBlock 2 Input/2 Output Module
19
Important: The
screen (from the Utilities pulldown menu). See page 3.
Then click on the desired ArmorBlock device.
Select the device node address for this device.
Click on the OK button when you have selected your device. Add more devices as necessary.
node address can only be set at the “Node Commissioning”
Publication 1792-5.5 – October 1996
ArmorBlock 2 Input/2 Output Module20
4. Click once on the device you wish to configure on the project screen
and choose
.
The device configuration screen appears.
If you have Parameter Status is
Not previously modified default settings Default Values Modified parameters but have not saved them Modified Modified and saved parameter settings Current Clicked on “Load from File” File Values Clicked on “Load from Device” Device Values
Publication 1792-5.5 – October 1996
5. Load parameters.
If you want to load parameters Choose
From a file
You see this screen.
Choose the drive, file type, and directory to load the file from.
Select the file name so that it is highlighted and choose
Note: The product code, type and revision must be identical in order to load a file from one device to another.
From the selected device
ArmorBlock 2 Input/2 Output Module
21
From default settings
Publication 1792-5.5 – October 1996
ArmorBlock 2 Input/2 Output Module22
6. Modify the parameter.
If you want to Choose Modify a parameter
You
Click on the settings you wish to activate. T
o save these settings,
choose
T
o save these settings to the device,
choose
see a screen similar to this one.
o use default settings,
T choose
T
o cancel any changes,
choose
For help about a specific parameter parameter and then choose
You can view parameters online by clicking on
Any changes that occur for a parameter will be reflected on the screen.
Publication 1792-5.5 – October 1996
, click on the
ArmorBlock 2 Input/2 Output Module
7. Save parameters to a file, to the device, or print to a file.
If you want to Choose Save parameters
to a file
You
see this screen.
23
Select the drive, file type, directory would like to save and choose
, and file name to which you
Save parameters to the selected device
Print to a file
You
see this screen.
Select the drive, file type, directory would like to save and choose
, and file name to which you
8. To exit from the Enhanced Configuration screen,
click on
.
Publication 1792-5.5 – October 1996
ArmorBlock 2 Input/2 Output Module24
Monitoring
Parameters Online
You can monitor parameters at the Device Configuration screen or at the selected parameter screen.
The start monitor button on the Device Configuration screen allows you to monitor all of the parameters online. To monitor parameters:
Click on the button to start the monitor.
The monitor function starts after a few seconds.
1.The status line flashes “monitoring.”
2.The monitoring function is indicated by an asterisk moving down next to the parameters.
3.The monitor button changes to and only “modify parameter” and “stop monitoring” are active.
4.Click on the button to stop monitoring.
To monitor an individual parameter:
1. Select the parameter on the Device Configuration screen.
2. Highlight the parameter and click on “Modify Parameter.”
3. Click on “Start Monitor” on the individual parameter screen.
Publication 1792-5.5 – October 1996
ArmorBlock 2 Input/2 Output Module
Reset Faults
There are various ways to reset faults on an ArmorBlock module.
cycle power to the module by disconnecting, then reconnecting the
DeviceNet connector
use the Reset Faulted I/O feature on the parameter screen
use the explicit message program control feature
for output faults, remove and reconnect the output power connector
ATTENTION: If you reset a fault by removing and replacing the output power connector, outputs
!
(including the faulted output) will be on when power is reconnected.
25
Note: This
Reset Faults Online Using the Parameter Screen
To reset faults online, return to the network screen and proceed as follows:
module contains a circuit to protect the DeviceNet power supply from short circuits in an attached sensor or sensor cable. If you connect a sensor while the module is powered, the surge current produced by the sensor can cause the module to fault. This operation is normal. If this occurs, reset the module.
1.Click on the faulted device.
2.Then click on the Configure Device button.
Publication 1792-5.5 – October 1996
ArmorBlock 2 Input/2 Output Module26
The device configuration screen appears. Select the Reset Faulted I/O parameter.
After selecting the parameter, click on the modify parameter button.
The configuration screen for the selected parameter appears.
1.Click on the faulted output to reset.
2.Then click on the OK button to apply.
3.You will be returned to the configuration screen. Click on ”Save to Device” to apply the change.
Publication 1792-5.5 – October 1996
ArmorBlock 2 Input/2 Output Module
Header
Body
Reset Faults using Explicit Message Program Control
You can also reset inputs and outputs using the Explicit Message Program Control feature on the Scanner module master. Refer to the specific scanner publications for information on using this feature.
The format for the reset explicit message transaction block must contain 6 words as shown below:
Word Input Fault Output Fault
27
Transaction
Transaction
Word 0TXID – CMD/ST W
ord 1
PORT – SIZE PORT – SIZE
W
ord 2
Service = 32 hex – MAC ID Service = 32 hex – MAC ID
W
ord 3
Class = 1D hex Class = 9
W
ord 4
Instance = 1
W
ord 5
Attribut Data = 0 Attribut Data = 0
ATUS
TXID – CMD/ST
Instance = n – where n = number of the output (1 or 2)
ATUS
Configure Your Armor Module Using EDS Files
Current versions of DeviceNet Manager software include ArmorBlock module support. If you are using a version of DeviceNet Manager software that does not include ArmorBlock module Electronic Data Sheets (EDS) files in its library, you can use the following information to create the file.
If you are using a configuration tool other than DeviceNet Manager, you can also use the following information to create the EDS file. (Note: This EDS file was current at the time of printing. Contact your nearest district office for information on later files.)
$ Electronic Data Sheet for Armor Block I/O (1792–IB2XOB2E) [File] DescText = ”1792–IB2XOB2E Armor Block I/O EDS File”; CreateDate = 04–18–96; CreateTime = 12:00:00; ModDate = 09–17–96; ModTime = 16:00:00; Revision = 2.1; $ EDS revision. [Device] VendCode = 1;
Publication 1792-5.5 – October 1996
ArmorBlock 2 Input/2 Output Module28
VendName = ”Allen–Bradley Company, Inc.”; ProdType = 7; ProdTypeStr = ”General Purpose Discrete I/O”; ProdCode = 1028; MajRev = 2; MinRev = 1; ProdName = ”Armor Block I/O 2 input / 2 output”; Catalog = ”1792–IB2XOB2E”; UCMM = 0; $ UCMM is not supported. [IO_Info] Default = 0x0001; $ The default I/O type is polled I/O. PollInfo = 0x0001, $ Polled I/O device. 1, $ Input1 entry is the default input connection. 1; $ Output1 entry is the default output connection. Input1 = 1, $ The size in bytes that this connection produces. 0, $ All bits of this connection are significant. 0x0001, $ Only Polled I/O is compatible. ”IB2XOB2E Production Data”, $ Name of Connection. 6, $ Path length. ”20 04 24 64 30 03”, $ Path to I/O Production Assembly.
”This connection contains input data at bits 0 and 1, output status at bits 2 and 3, and sensor source voltage status at bit 7.”;
Output1 = 1, $ The size in bytes that this connection consumes. 2, $ Only the two least significant bits of this
0x0001, $ Only Polled I/O is compatible. ”IB2XOB2E Consumption Data”, $ Name of Connection. 6, $ Path length. ”20 04 24 20 30 03”, $ Path to I/O Consumption Assembly.
”This connection contains data for two outputs.”;
$$$$$$$$$$ Help string $$$$$$$$$$$
$ connection are used.
$$$$$$$$$$ Help string $$$$$$$$$$$
[ParamClass] MaxInst = 11; $ 6 configurable and 5 read–only parameters. Descriptor = 0x09; $ Stub param instances in eeprom. CfgAssembly = 0x68; $ The config assembly is instance #104 of assy obj. [Params] $$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$ $$$$$$$$$$ Param1 = $ Disable Autobaud 0, $ reserved 6, $ Link Path Size ”20 03 24 01 30 64”, $ Link Path to disable autobaud attribute. 0x0002, $ No support for settable path, scaling, scaling links, or
4, $ Data Type – boolean 1, $ Data Size ”Autobaud”, $ Parameter Name ””, $ Units String
$$$$$$$$$$ Help string $$$$$$$$$$$
Publication 1792-5.5 – October 1996
$ real time update of value. Value is gettable and $ Settable. Enumerated strings are supported.
ArmorBlock 2 Input/2 Output Module
”Enable takes effect after next powerup. Disable is required to set fixed baud rate, no power cycle is required.”, 0,1,0, $ Min, Max, and Default values 1,1,1,0,0,0,0,0,0; $ Not Used $$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$ $$$$$$$$$$ Param2 = $ Input filter Off_to_On Delay selection 0, $ reserved 6, $ Link Path Size ”20 0F 24 02 30 01”, $ Link Path to param instance. The param instance
$ decodes the enumerated parameter into engineering $ units (micro seconds).
0x0002, $ No support for settable path, scaling, scaling links,
$ or real time update of value. Value is gettable and
$ Settable. Enumerated strings are supported. 2, $ Data Type – unsigned int 2, $ Data Size – (in bytes) ”Off–to–On Delay”, $ Parameter Name ”ms”, $ Units String
$$$$$$$$$$ Help string $$$$$$$$$$$ ”Signal must be present for this delay period before module detects the change.”, 0,4,0, $ Min, Max (max enumeration #), and Default values 1,1,1,0,0,0,0,0,0; $ Not Used $$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$ $$$$$$$$$$ Param3 = $ Input filter On_to_Off Delay selection 0, $ reserved 6, $ Link Path Size ”20 0F 24 03 30 01”, $ Link Path to param instance. The param instance decodes
$ the enumerated parameter into engineering units
$ (micro seconds). 0x0002, $ No support for settable path, scaling, scaling links,
$ or real time update of value. Value is gettable and
$ Settable. Enumerated strings are supported. 2, $ Data Type – unsigned int 2, $ Data Size – (in bytes) ”On–to–Off Delay”, $ Parameter Name ”ms”, $ Units String
$$$$$$$$$$ Help string $$$$$$$$$$$ ”Signal must be present for this delay period before module detects the change.”, 0,4,0, $ Min, Max (max enumeration #), and Default values 1,1,1,0,0,0,0,0,0; $ Not Used $$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$ $$$$$$$$$$ Param4 = $ Fault State selection 0, $ reserved 6, $ Link Path Size ”20 1E 24 01 30 07”, $ Link Path to DOG object’s fault state attribute. 0x0002, $ No support for settable path, scaling, scaling links,
$ or real time update of value. Value is gettable and
$ Settable. Enumerated strings are supported. 4, $ Data Type – boolean 1, $ Data Size ”Fault State”, $ Parameter Name ””, $ Units String
$$$$$$$$$$ Help string $$$$$$$$$$$
Publication 1792-5.5 – October 1996
29
ArmorBlock 2 Input/2 Output Module30
”Defines output behavior in the event of a communication fault.”, 0,1,0, $ Min, Max (max enumeration #), and Default values 1,1,1,0,0,0,0,0,0; $ Not Used $$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$ $$$$$$$$$$ Param5 = $ Idle State selection 0, $ reserved 6, $ Link Path Size ”20 1E 24 01 30 09”, $ Link Path to DOG object’s idle state attribute. 0x0002, $ No support for settable path, scaling, scaling links,
4, $ Data Type – boolean 1, $ Data Size ”Idle State”, $ Parameter Name ””, $ Units String
$$$$$$$$$$ Help string $$$$$$$$$$$ ”Defines output behavior during program mode.”, 0,1,0, $ Min, Max (max enumeration #), and Default values 1,1,1,0,0,0,0,0,0; $ Not Used $$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$ $$$$$$$$$$ Param6 = $ Reset Faulted I/O 0, $ reserved 6, $ Link Path Size ”20 0F 24 06 30 01”, $ Link Path to param instance. 0x0002, $ No support for settable path, scaling, scaling links,
8, $ Data Type – unsigned short int 1, $ Data Size – (in bytes) ”Reset Faulted I/O”, $ Parameter Name ””, $ Units String
$$$$$$$$$$ Help string $$$$$$$$$$$ ”This resets the voltage supplied to sensors or a faulted output. A reset will only be accepted if a fault exists.”, 0,3,0, $ Min, Max (max enumeration #), and Default values 1,1,1,0,0,0,0,0,0; $ Not Used $$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$ $$$$$$$$$$ Param7 = $ Input 1 value 0, $ reserved 6, $ Link Path Size ”20 08 24 01 30 03”, $ Link Path to Input 1 value attribute. 0x0030, $ No support for settable path, scaling, or scaling
8, $ Data Type – unsigned short int 1, $ Data Size – (in bytes) ”Input 1 Value”, $ Parameter Name ””, $ Units String
$$$$$$$$$$ Help string $$$$$$$$$$$ ”This parameter is the current value of Input 1.”, 0,1,0, $ Min, Max, and Default values 1,1,1,0,0,0,0,0,0; $ Not Used
$ or real time update of value. Value is gettable and $ Settable. Enumerated strings are supported.
$ or real time update of value. Value is gettable and $ Settable. Enumerated strings are supported.
$ links. $ Value is gettable only. Enumerated strings are not $ supported.
Publication 1792-5.5 – October 1996
ArmorBlock 2 Input/2 Output Module
$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$ $$$$$$$$$$ Param8 = $ Input 2 value 0, $ reserved 6, $ Link Path Size ”20 08 24 02 30 03”, $ Link Path to Input 2 value attribute. 0x0030, $ No support for settable path, scaling, or scaling
$ links. $ Value is gettable only. Enumerated strings are not
$ supported. 8, $ Data Type – unsigned short int 1, $ Data Size – (in bytes) ”Input 2 Value”, $ Parameter Name ””, $ Units String
$$$$$$$$$$ Help string $$$$$$$$$$$ ”This parameter is the current value of Input 2.”, 0,1,0, $ Min, Max, and Default values 1,1,1,0,0,0,0,0,0; $ Not Used $$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$ $$$$$$$$$$ Param9 = $ Input status 0, $ reserved 6, $ Link Path Size ”20 1D 24 01 30 05”, $ Link Path to Dicrete Input Group status attribute. 0x0032, $ No support for settable path, scaling, or scaling
$ links. $ Value is gettable only. Enumerated strings are
$supported. 8, $ Data Type – unsigned short int 1, $ Data Size – (in bytes) ”Input Status”, $ Parameter Name ””, $ Units String
$$$$$$$$$$ Help string $$$$$$$$$$$ ”This parameter is the current status of all inputs.”, 0,1,0, $ Min, Max, and Default values 1,1,1,0,0,0,0,0,0; $ Not Used $$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$ $$$$$$$$$$ Param10 = $ Output 1 status 0, $ reserved 6, $ Link Path Size ”20 09 24 01 30 04”, $ Link Path to Output 1 status attribute. 0x0032, $ No support for settable path, scaling, or scaling
$ links.
$ Value is gettable only. Enumerated strings are
$supported. 8, $ Data Type – unsigned short int 1, $ Data Size – (in bytes) ”Output 1 Status”, $ Parameter Name ””, $ Units String
$$$$$$$$$$ Help string $$$$$$$$$$$ ”This parameter is the current status of Output 1.”, 0,1,0, $ Min, Max, and Default values 1,1,1,0,0,0,0,0,0; $ Not Used $$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$ $$$$$$$$$$ Param11 = $ Output 2 status
Publication 1792-5.5 – October 1996
31
ArmorBlock 2 Input/2 Output Module32
0, $ reserved 6, $ Link Path Size ”20 09 24 02 30 04”, $ Link Path to Output 2 status attribute. 0x0032, $ No support for settable path, scaling, or scaling
$ links. $ Value is gettable only. Enumerated strings are
$ supported. 8, $ Data Type – unsigned short int 1, $ Data Size – (in bytes) ”Output 2 Status”, $ Parameter Name ””, $ Units String
$$$$$$$$$$ Help string $$$$$$$$$$$ ”This parameter is the current status of Output 2.”, 0,1,0, $ Min, Max, and Default values 1,1,1,0,0,0,0,0,0; $ Not Used [Groups] Group1=”Configuration”,5,1,2,3,4,5; Group2=”I/O”,6,6,7,8,9,10,11; [EnumPar] Param1=”Enable”,”Disable”; Param2=”0 ms”,”2 ms”,”4 ms”,”8 ms”,”16 ms”; Param3=”0 ms”,”2 ms”,”4 ms”,”8 ms”,”16 ms”; Param4=”Reset Outputs”,”Hold Last State”; Param5=”Reset Outputs”,”Hold Last State”; Param6=”Nothing Selected”,”Output #1”,”Output #2”,”Sensor Source Voltage”; Param9=”Healthy”,”Faulted”; Param10=”Healthy”,”Faulted”; Param11=”Healthy”,”Faulted”;
Troubleshoot with the Indicators
The ArmorBlock I/O module has 3 types of indicators:
Mod/Net status indicator
Input fault indicator
individual I/O status indicators
Mod/Net Status Indicator
MOD/NET
STATUS
TE RA
ADDRESS
DATA
NODE
Input I/O Status Indicators
Publication 1792-5.5 – October 1996
Input Fault Indicator
INPUT FAULT
ARMORBLOCK
1792-IB2XOB2E
I/O
Output I/O Status Indicators
ArmorBlock 2 Input/2 Output Module
33
Note: This module contains a circuit to protect the DeviceNet power supply from short circuits
in an attached sensor or sensor cable. If you connect a sensor while the module is powered, the surge current produced by the sensor can cause the module to fault. This operation is normal. If this occurs, reset the module (page 25).
Mod/Net
Status Indicator
Indication Status
No
power
OFF
Flashing Green/OFF Solid Green Flashing Red Solid Red Green to Red to Of
1
This only occurs when Autobaud is disabled, and the module is set to an incorrect baud rate.
Input
Fault Indicator
f
, or no network access, or incorrect baud rate On-line but not connected On-line, link okay Recoverable fault Critical failure, or duplicate node address present
At powerup only – The module is autobauding
, connected
1
Indication Status
Sensor
OFF
Solid Red
Input
I/O Status Indicator
source voltage operating correctly
1 or more Sensor source voltage shorts
Indication Status
OFF No Yellow V
Output
I/O Status Indicator
valid input signal present
alid input signal present
Indication Status
OFF Output is off Yellow Red (see note) Note: A faulted output may cause adjacent outputs to fault.
Output is on Output is faulted
Publication 1792-5.5 – October 1996
ArmorBlock 2 Input/2 Output Module34
Specifications
2 Input/2 Output Module – 1792-IB2XOB2E/B
Input Specifications
Inputs per Block 2 sinking On-state Voltage Range 10–30V dc On-state Current Maximum
Minimum Off-state Voltage Maximum 5V dc Off-state Current Minimum 1.5mA Transition Voltage 5–10V dc Transition Current 1.5–3.0mA Input Impedance Maximum 5K ohms Input Signal Delay Off to On
On to Off Sensor Source Voltage
Current
Output Specifications
6.0mA @ 30V dc
2.0mA @ 10V dc
0ms, 2ms, 4ms, 8ms, 16ms 0ms, 2ms, 4ms, 8ms, 16ms
10–25V dc 50mA per point, 0.1A total per module
Outputs per Block 2 sourcing Output Voltage Range 19 – 30V dc On-state Voltage Maximum 0.25V dc @ rated current On-state Current Maximum 2.0A per output @ 70oC Module Current (all outputs on)
Maximum Off-state Leakage Current
Maximum 1.5mA per output Surge Current (per output)
Maximum 4.0A for 10ms, repeatable every 2s
Specifications continued on next page
Publication 1792-5.5 – October 1996
4.0A per module
1
ArmorBlock 2 Input/2 Output Module
2 Input/2 Output Module – 1792-IB2XOB2E/B
General Specifications
Indicators Mod/Net Status – red/green
Input Fault – red I/O Status – yellow/red (customer field side driven)
DeviceNet Power Voltage
Current
Surge Current at Power Up Less than 10A for 5ms Dimensions Inches
Millimeters
Connectors 1792-IB2XOB2EA/B – Aluminum connectors
Power Dissipation Maximum 1.9 Watts Thermal Dissipation Maximum 6.9 BTU/hr Isolation Voltage 500V ac – outputs to DeviceNet
Specifications continued on next page
11.0 – 25.0V dc 100mA (no powered sensors) 200mA (full sensor load)
2.6H X 7.7W X 3.06D 66H X 195W X 77.7D
1792-IB2XOB2ES/B – Stainless Steel Connectors
500V ac – outputs to inputs
35
Publication 1792-5.5 – October 1996
ArmorBlock 2 Input/2 Output Module36
2 Input/2 Output Module – 1792-IB2XOB2E/B
Environmental Conditions
Operational Temperature Storage Temperature Relative Humidity Shock Operating
Non-operating
Vibration
Conductors Refer to publication 1485-6.7.1 for information on
Enclosure Meets or exceeds NEMA 4X and 6P, IP67
Agency Certification (when product or packaging is marked)
1
Minimum wire size is 20 gauge.
This
product has been tested at an Open DeviceNet V
Inc. (ODV
A) authorized independent test laboratory and found to comply
with ODVA Conformance Test Software V
–25 to 70oC (–13 to 158oF) –40 to 85
o
C (–40 to 185oF) up to 100% 30 g peak acceleration, 11(+ 50 g peak acceleration, 11(+
1)ms pulse width
1)ms pulse width
Tested 10 g @ 10–500Hz per IEC 68-2-6
cabling for your DeviceNet module.
o
1200psi, 140
F hosedown
CSA certified
CSA Class I, Division 2, Groups A, B, C, D
certified
UL listed
CE marked for all applicable directives
endor Association,
ersion FT 1.2/1.0.
Worldwide representation.
Argentina • Colombia • Costa Rica • Croatia • Cyprus • Czech Republic • Denmark • Ecuador • Egypt • El Salvador Finland Indonesia • Mexico Puerto Rico • Qatar • Romania • Russia–CIS • Saudi Arabia • Singapore Africa, Republic • Spain • Sweden United Kingdom • United States • Uruguay • V
Allen-Bradley Headquarters, 1201 South Second Street, Milwaukee, WI 53204 USA, Tel: (1) 414 382-2000 Fax: (1) 414 382-4444
Publication
Publication 1792-5.5 – October 1996
Supersedes
Australia • Austria • Bahrain • Belgium
France • Germany • Greece • Guatemala • Honduras • Hong Kong • Hungary • Iceland • India
Ireland • Israel • Italy • Jamaica •
Netherlands
1792-5.5 – October 1996
1792-5.5 – December 1995
New
Zealand • Norway
Switzerland T
Brazil
Bulgaria • Canada • Chile • China, PRC
Japan • Jordan • Korea • Kuwait • Lebanon
Pakistan
enezuela • Y
Peru
Philippines
aiwan
Thailand T ugoslavia
Copyright 1996 Allen-Bradley Company
Poland • Portugal
Slovakia Slovenia
urkey • United Arab Emirates
Malaysia
South
PN955126–06
, Inc. Printed in USA
Loading...