Because of the variety of uses for the products described in this
publication, those responsible for the application and use of this control
equipment must satisfy themselves that all necessary steps have been taken
to assure that each application and use meets all performance and safety
requirements, including any applicable laws, regulations, codes and
standards.
The illustrations, charts, sample programs and layout examples shown in
this guide are intended solely for example. Since there are many variables
and requirements associated with any particular installation, Allen-Bradley
does not assume responsibility or liability (to include intellectual property
liability) for actual use based upon the examples shown in this publication.
Allen-Bradley publication SGI–1.1, “Safety Guidelines For The
Application, Installation and Maintenance of Solid State Control”
(available from your local Allen-Bradley office) describes some important
differences between solid-state equipment and electromechanical devices
which should be taken into consideration when applying products such as
those described in this publication.
Reproduction of the contents of this copyrighted publication, in whole or
in part, without written permission of Allen–Bradley Company, Inc. is
prohibited.
Throughout this manual we make notes to alert you to possible injury to
people or damage to equipment under specific circumstances.
ATTENTION: Identifies information about practices or
circumstances that can lead to personal injury or death, property
damage or economic loss.
Attention helps you:
- Identify a hazard
- Avoid the hazard
- recognize the consequences
Important: Identifies information that is critical for successful application
and understanding of the product.
Important: We recommend you frequently backup your application
programs on appropriate storage medium to avoid possible data loss.
Summary of Changes
Summary of Changes
Summary of Changes
This release of the publication contains new and updated information from
the last release.
New Information
This release includes information on new block I/O modules now
available. This information was not included in the previous release of
this publication. The modules are:
1791-NDV – 24V dc Analog Block I/O (voltage outputs)
1791-NDC – 24V dc Analog Block I/O (current outputs)
Updated Information
Generally, change bars (as shown to the right of this paragraph) are used to
show new or significantly revised copy. Certain additions, such as adding
octal numbering or corrected typographical errors, are not shown by
change bars.
Programming Your Analog Block I/O Module 61. . . . . . . . . . .
Chapter
Block Transfer Programming 61
PLC3 Program Example 62
PLC5 and PLC-5/250 Program Example 63
Sample Programs for Analog Block 64
PLC3 Family Processors 64
PLC5 Family Processors 65
This manual shows you how to use your block I/O with an Allen-Bradley
programmable controller. It helps you:
install your module
program your module
troubleshoot your module
You must be able to program and operate an Allen-Bradley programmable
controller (PLC) to make efficient use of block I/O modules.
We assume that you know how to do this in this manual. If you do not,
refer to the appropriate PLC programming and operations manual before
you attempt to program this module.
In this manual, we refer to:
the block I/O module as the “block” or the “module”
the programmable controller as the “controller” or “processor”
This manual is divided into eight chapters. The following chart shows each
chapter with its corresponding title and brief overview of the topics
covered in that chapter.
ChapterTitleTopics Covered
1Introducing Block I/O
2Installing Block I/O
3
4
5
6
7Module CalibrationHow to calibrate analog block I/O
8Troubleshooting
Appendix A SpecificationsSpecifications for the block I/O modules
Configuring Your Block I/O for PLC
Family Programmable Controllers
Analog Block Applications using Block
Transfers
Analog Block Applications using Discrete
Transfers
Programming Your Analog Block I/O
Module
Description of the modules, including general and
hardware features
Module power requirements, location, and wiring
information
How to set the configuration switches and address
the block I/O
How to use block transfer programming with your
block I/O
How to use discrete transfer with your block I/O
Programming examples for analog block I/O and
PLC family controllers
How to use the indicators to troubleshoot your block
I/O module
P-1
Preface
Using This Manual
Block
I/O Products Covered
by this Publication
Related Publications
This publication covers the following analog block I/O products:
1791N4V2120V ac42analog - 4 input, 2 voltage output
1791N4C2120V ac42analog - 4 input, 2 current output
1791NDV24V dc42analog - 4 input, 2 voltage output
1791NDC24V dc42analog - 4 input, 2 current output
For a list of publications with information on Allen-Bradley products,
consult our publication index (SD499).
P-2
Introducing Block I/O
y
Chapter
1
Chapter
Objectives
General Description
In this chapter, you will learn what analog block I/O is, its features, and
how it functions.
Block I/O consists of small, self-contained remote I/O devices complete
with power supply, programmable controller interface, input/output
connections and signal conditioning circuitry. Table 1.A is a list of block
I/O modules covered in this publication.
The analog blocks communicate via block transfer or discrete transfer with
any Allen-Bradley programmable controller that connects to the remote
I/O network. The analog blocks communicate with SLC family controllers
using discrete transfer.
Each analog block has four independent inputs, which can be configured as
either all voltage inputs or all current inputs. The block contains a 24V dc
current limited voltage source for accommodating loop-powered current
transducer inputs.
1771SN subI/O scanner or
1772SD and SD2 remote I/O scanners
Block attaches directly to controller
1-1
Chapter 1
Introducing Block I/O
Analog block outputs are configured at the factory for either a current
output or a voltage output. Outputs are not user-configurable.
Figure 1.1 shows the physical features of the block I/O.
Figure 1.1
Features of the Analog Block I/O Modules (1791N4V2 shown)
Major
1791N4V2
ANALOG
POWER
COMM
FAULT
BLOCK
Indicators
1
Removable
Terminal Strip for
Input, Output, Remote
I/O and Power
Connections
Switch
Assemblies
Equipment
Grounding
Stud
30
2 mounting holes
for 1/4inch screws
12631I
Terminal Strip - Remote I/O link, power and input/output connections are
made to the removable terminal strip for easy connection of wiring.
Switch Assembly - The modules contain two switch assemblies. Use these
assemblies to make the following settings:
I/O rack number
starting I/O group
communication rate
last I/O group
last state
transfer type
processor restart/lockout
1-2
Status Indicators - Indicators display the status of module power,
communication and fault. Use these indicators to help in troubleshooting.
Chapter 1
Introducing Block I/O
How
Block I/O Fits in a
PLC System
Programmable
Controller
or Scanner
Block I/O is a complete I/O interface that includes the functionality of the
I/O rack, adapter, power supply, and I/O module in a single unit. Connect
sensors and actuators to the module and use the remote I/O cable to
connect the block I/O to your programmable controller.
Connect the block I/O to your remote I/O link as you would any other
device. Input and output data is scanned asynchronously and transferred
back and forth between the block and the programmable controller using
either block transfer or discrete transfer. When using block transfer
(Figure 1.2), the block looks like a 1/4 I/O rack to the processor (two
words of input image table memory and two words of output image table
memory). Block transfer provides the most efficient use of your data table
image memory, and allows access to all implemented user functions of
the block.
Figure 1.2
I/O Connection in a PLC System using block transfer
Block
Block I/O each block
1/4
is 1/4 I/O rack
1/4
1/4
+
Blocks are daisychained to
a programmable controller or
a scanner
1/4
+
+
= 1 I/O Rack
10828I
1-3
Chapter 1
Introducing Block I/O
Discrete transfer (Figure 1.3) is intended to be used with controllers which
do not have block transfer capability. However, discrete transfer can be
used with any PLC family controller. When using discrete transfer, the
block looks like a 1/2 I/O rack to the controller (four words of input image
table memory and four words of output image table memory). Note that
certain alarms and user scaling features are not available when using
discrete transfer.
Figure 1.3
I/O Connection in an SLC System using discrete transfer
Block
Block I/O each block
1747SN Remote I/O
Scanner Module
1/2
is 1/2 I/O rack
1/2
Inputs
Simplified Schematic
Channel 0 Input
inV0
inI0
249Ω
RET in0
GND in0
20MΩ
20MΩ
Analog Input
1
Common
+
= 1 I/O Rack
Blocks are daisychained to
a scanner
A simplified schematic of the input circuit of one input channel is
shown below.
Analog Multiplexer
ATTENTION: The 249 ohm
input current shunt is rated at
0.25 Watts. Do not exceed this
power rating or apply more
than 6V across the resistor
Channel 0
Channel 1
Channel 2
Channel 3
Instrumentation
Amplifier
+
-
Analog Input
1
Common
10828I
A/D
12501-I
1-4
Inputs have selectable input ranges as shown below.
ApplicationInput RangeResolution
voltage+10V14 Bits
voltage or current+5V14 Bits
voltage0 to 10V14 Bits
voltage or current0 to 5V14 Bits
Chapter 1
Introducing Block I/O
Voltage Input
Voltage inputs can be either single-ended or differential. In the voltage
mode, a signal applied between inV0 and the combination of RET in0
shorted to GND in0 provides a single-ended input mode. A signal applied
between inV0 and RET in0 provides a differential input mode. The four
terminals for ground are internally connected together to form the analog
input common. In either input mode (single-ended or differential) the
common mode voltage between any input terminal and analog input
common cannot exceed 11V or unreliable operation will occur. The figures
below show examples of differential input mode and single-ended input
mode.
10V
Differential Input ModeSingleended Input Mode
inV0
inI0
(no connection)
RET in0
GND in0
10VinV0
Current Input
When using the 0–5V or +5V range, an internal precision 249Ω shunt is
provided on each input. Input current is measured when the I
terminals are connected together. To get the proper input voltages, you
must indicate that the current shunt is connected when you configure the
module at powerup. A +24V power supply is provided for two-wire
current transducers.
I
5V
Current Input
inV0
inI0
RETin0
inI0
(no connection)
RETin0
GNDin0
and V
IN
IN
GNDin0
Each range setting has a margin of 2.5% to allow for compensation of
system or calibration inaccuracies.
1-5
Chapter 1
Introducing Block I/O
This is illustrated using the +10V scale below:
14 Bits
Resolution
Margin
13.96 Bits
Margin
Input Signal
I1I2I3I4I5
Nominal Range
In the above scale, input signals 1 thru 5 produce corresponding internal
analog to digital converter (ADC) binary counts. A full scale (FS) voltage
input produces an internal count of 16383 (input signal 1), while a bottom
scale (BS) voltage input produces an internal count of 0000 (input 5).
During calibration, the module’s representation of the counts are adjusted
so a voltage of nominal full scale (NFS) will produce a count shown as
input signal 2 while the nominal bottom scale voltage (NBS) produces a
count shown as input signal 4. For each range scale, the input voltage
which produces the ADC count of input signals 1 thru 5 in the above scale
are shown below:
The input data represented at the module is always the internal ADC binary
counts scaled by values set in the maximum (S
) and minimum (S
max
min
)
scaler value using a two point scaling method. The input voltage which
produces input signal 2 (V
signal 4 (V
Scaling
Input Signal
Voltage
) is equal to S
nbs
Smax
I1I2I3I4I5
Vnfs
) is always equal to S
nfs
as shown below:
min
, and voltage of input
max
Smin
Vnbs
Chapter 1
Introducing Block I/O
The following equation shows how the module interprets the input data:
Module
where:
data = M x Vin + B
– S
(S
M =
B =
(V
(S
max
nfs
min
– V
x V
(V
min
nbs
nfs
nfs
)
) – (S
)
– V
nbs
max
)
x V
nbs
)
You can choose one of three scaling methods:
binary counts (module sets scalers)
default scaling (module sets scalers)
user scaling (you set scalers)
User scaling is not available when you select discrete transfer mode.
Binary Counts Scaling
Binary counts scaling mode activates when the module powers up. This
mode guarantees the maximum resolution. The module sets the scalers as
shown in the following table:
Scaler+/-10V0-10V+/-5V0-5V
S
max
S
min
819116383819116383
-81920-81920
Default Scaling
Default scaling mode scales inputs to the input stimulus in either millivolts
or microamps. The module sets the scalers as shown in the following
tables:
With Voltage Input Selected
Scaler+/-10V0-10V+/-5V0-5V
S
S
With Current Input Selected
Scaler+/-10V0-10V+/-5V0-5V
S
S
10,000mV10,000mV5000mV5000mV
max
-10,000mV0mV-5000mV0mV
min
max
min
N/AN/A20000uA20000uA
N/AN/A-20000uA0uA
1-7
Chapter 1
Introducing Block I/O
User Scaling
User scaling is available only when using the block transfer mode. This
mode allows you to define S
max
and S
in engineering units in the block
min
transfer write data table. The integer range is 32,767 to –32,768.
Important: If the range of user scaling values is set less than the range of
binary counts scaling values, input resolution is sacrificed.
Scaling Example
Using the +10V range scale, the following illustration shows five possible
input signals.
14 Bits
Resolution
Margin
13.96 Bits
Margin
Outputs
Input Signal
10.25100-10 -10.25
Nominal Range
The following table shows how the five signals will be scaled using each
of the three scaling methods. In the user scaling column, the S
to represent 5000 and the S
Input Value
Approx. +10.25V8395102505062
+10.000V8191100005000 (Smax)
0.000V0000000002500
-10.000V-8192-100000000 (Smin)
Approx. -10.25V-8396-10250-0062
Binary CountsDefaultUser
was set to represent 0.
min
Scaling Method
max
was set
The type of output your block I/O module has depends on its catalog
number:
1791-N4V2 and 1791-NDV have two +10V voltage outputs
1791-N4C2 and 1791-NDC have two 0-20mA current outputs
1-8
For any of the above modules, if your program tries to write a value which
is outside the output range, the output will be clamped at either the
maximum or minimum value. This condition will be indicated in the block
transfer read status word.
V
OUTS
Digital
Output
Opto
Isolation
Isolated Analog
Output Common
Chapter 1
Introducing Block I/O
V
oltage Outputs - 1791N4V2 and 1791NDV
A simplified schematic of a +10V output channel is shown below.
Precision
Operational
Amplifier
DAC
2
+
-
2
V
OUT
V
RET
Note: Schematic does not show overvoltage protection circuits.
The +10V output provides 14 bits of resolution and is capable of driving
loads as small as 1k ohm. The output sacrifices a small amount of the
resolution to provide a margin of 2.5% to allow for system or calibration
inaccuracies as shown below.
Resolution
Output Signal
Scaling
The digital data sent to the output is always scaled by the values set in the
maximum (S
scaling method. When digital data sent equals S
+10.000V and the digital data sent equals S
–10.000V. The following equations shows this relationship:
Isolated Analog
2
Output Common
14 Bits
13.96 Bits
Margin
10.25100-10 -10.25
Nominal Range
) and minimum (S
max
) scaler values using a two point
min
Isolated Analog
2
Output Common
, the output produces
max
, the output produces
min
12501-I
Margin
Vout
= M x Module Data + B
where:
M =
B =
(Smax – Smin)
10 x (Smax + Smin)
(Smax – Smin)
20V
1-9
Chapter 1
Introducing Block I/O
You can choose one of three scaling methods:
binary counts
default scaling
user scaling
User scaling is not available when you select discrete transfer mode.
The following table shows the output signals produced by various module
data values entered in each of the three scaling methods. In the user scaling
column, S
Output Signal
Approx. +10.25V8395102505062
was set to 5000 and S
max
Binary Counts
Scaling
was set to 0000.
min
Module Data
Default
Scaling
User
Scaling
+10V8191100005000 (Smax)
0.000V0000000002500
-10.00V-8192-100000000 (Smin)
Approx. -10.25V-8396-10250-0062
Current Outputs - 1791N4C2 and 1791NDC
A simplified schematic of a 0 to 20mA output channel is shown below.
I
OUTS
Digital
Output
Note: Schematic does not show overvoltage protection circuits.
Opto
Isolation
Isolated Analog
Output Common
DAC
2
Isolated Analog
Output Common
High Side
Current
Monitor
2
+15V
-15V
I
OUT
I
RET
12505-I
1-10
The 0 to 20mA output provides 13 bits of resolution and is capable of
driving loads as large as 1k ohm.
Chapter 1
Introducing Block I/O
The output sacrifices a small amount of the resolution to provide a margin
of 2.5% to allow for system or calibration inaccuracies as shown below.
13 Bits
Resolution
Margin
12.9 Bits
Margin
Input Signal
20.520100.0 –0.5
Nominal Range
Scaling
The digital data sent to the output is always scaled by the values set in the
maximum (S
scaling method. When digital data sent equals S
20.000mA and the digital data sent equals S
0.000mA. The following equations shows this relationship:
Iout
where:
You can choose one of three scaling methods:
binary counts
default scaling
user scaling
) and minimum (S
max
= M x Module Data + B
M =
B =
(Smax – Smin)
20mA x (Smax + Smin)
(Smax – Smin)
min
20mA
) scaler values using a two point
, the output produces
max
, the output produces
min
User scaling is not available when you select discrete transfer mode.
The following table shows the output signals produced by various module
data values entered in each of the three scaling methods. In the user scaling
column, S
Output Signal
Nominally +20.5mA8395102505062
20.000mA8191100005000 (Smax)
0.000mA0000000002500 (Smin)
Nominally -0.5mA
1
The actual output can never go negative. However
compensation.
was set to 5000 and S
max
Binary Counts ScalingDefault ScalingUser Scaling
1
-0396-00050-2437
was set to 0000.
min
Module Data
, some of the output range is used to allow for zero of
In this chapter, you will learn how to mount the block, connect the remote
I/O link, connect the input and output wiring to the block, and terminate
the remote I/O link.
Before installation, you must determine the:
scanner/processor to use
number of blocks on your network
throughput requirements
total distance of the installation
transmission rate desired
external fuses required (if any)
Acceptable combinations are shown in Table 2.A.
Table 2.A
Acceptable
Combinations of Processor and Block I/O
Baud Rate
14 blocks with 150 ohm terminator
and discrete transfer
16 blocks/channel, 28 blocks/scanner
with 150 ohm terminator
57.6K10,000 cablefeet
115.2K5,000 cablefeet
57.6K10,000 cablefeet
115.2K5,000 cablefeet
Used
Maximum
Network Distance
PLC3 family
5 family
ny
1775S5, or SR5 module
PLC5VME (6008LTV)
PLC5/11
scanner module
16 blocks/channel, 64 blocks/scanner
with 150 ohm terminator. 128 blocks
with 2 scanners and 150 ohm
terminator.
32 blocks/channel, 64 blocks/scanner
with 82 ohm terminator. 128 blocks
with 2 scanners, 82 ohm terminator
and extended node addressing.
4 blocks with 150 ohm terminator
4 blocks with 150 ohm terminator
57.6K10,000 cablefeet
115.2K5,000 cablefeet
57.6K10,000 cablefeet
115.2K5,000 cablefeet
230.4K2,000 cablefeet
57.6K10,000 cablefeet
57.6K10,000 cablefeet
115.2K5,000 cablefeet
230.4K2,500 cablefeet
2-1
Chapter 2
terminator
16blocks/channel, 28blocksper
28 blocks/ch
16blocks/channel, 60blocksper
32 blocks/ch
16blocks/channel, 32blocksper
32 blocks/ch
16blocks/channel, 64blocksper
32 blocks/ch
16blocks/channel, 32blocksper
32 blocks/ch
Installing Block I/O
PLC5 family (continued)
PLC5/15
PLC5/20
PLC5/25
PLC5/30
PLC5/40
Maximum CapacityandWhen using
1
12 blocks with 150 ohm terminator57.6K10,000 cablefeet
Baud Rate
Used
Maximum
Network Distance
57.6K10,000 cablefeet
12 blocks with 82 ohm or 150 ohm
terminator
115.2K5,000 cablefeet
230.4K2,500 cablefeet
2
16 blocks with 150 ohm terminator,
28 blocks with 82 ohm terminator and
57.6K10,000 cablefeet
extended node addressing
16 blocks/channel, 28 blocks per
processor with 150 ohm terminator
57.6K10,000 cablefeet
115.2K5,000 cablefeet
57.6K10,000 cablefeet
annel, 28 blocks per
processor with 82 ohm terminator
115.2K5,000 cablefeet
and extended node addressing
230.4K2,500 cablefeet
16 blocks/channel, 60 blocks per
processor with 150 ohm terminator
57.6K10,000 cablefeet
115.2K5,000 cablefeet
57.6K10,000 cablefeet
annel, 60 blocks per
processor with 82 ohm terminator
115.2K5,000 cablefeet
and extended node addressing
230.4K2,500 cablefeet
PLC5/40L
PLC5/60
PLC5/60L
16 blocks/channel, 32 blocks per
processor with 150 ohm terminator
annel, 60 blocks per
processor with 82 ohm terminator
and extended node addressing
16 blocks/channel, 64 blocks per
processor with 150 ohm terminator
annel, 92 blocks per
processor with 82 ohm terminator
and extended node addressing
16 blocks/channel, 32 blocks per
processor with 150 ohm terminator
annel, 64 blocks per
processor with 82 ohm terminator
and extended node addressing
57.6K10,000 cablefeet
115.2K5,000 cablefeet
57.6K10,000 cablefeet
115.2K5,000 cablefeet
230.4K2,500 cablefeet
57.6K10,000 cablefeet
115.2K5,000 cablefeet
57.6K10,000 cablefeet
115.2K5,000 cablefeet
230.4K2,500 cablefeet
57.6K10,000 cablefeet
115.2K5,000 cablefeet
57.6K10,000 cablefeet
115.2K5,000 cablefeet
230.4K2,500 cablefeet
2-2
Chapter 2
a550Seoescae
32blocks/channel, 32
scanners) with 82 ohm terminator
8 block
3
Controller
Module(discretemodeonly)
Installing Block I/O
Maximum CapacityandWhen using
16 blocks/channel, 32
Baud Rate
Used
57.6K10,000 cablefeet
blocks/scanner, (128 blocks with 4
scanners) with 150 ohm terminator
PLC5 family (continued)
PLC5/250 requires
a 5150RS remote scanner
32 blocks/channel, 32
blocks/scanner, (128 blocks with 4
scanners) with 82 ohm terminator
and extended node addressing
PLC5/15 series A and PLC5/15 series B prior to revision H (B/H) can only address 3 blocks.
2
PLC5/25 revisions prior to A/D can only address 7 blocks.
3
Analog block is 1/2 rack in discrete transfer mode. If you combine analog block and discrete transfer on the same RIO link, the capacity ranges between 8 and 15 blocks.
Installing the Block I/O
Figure 2.1 shows the mounting dimensions for the block I/O module.
115.2K5,000 cablefeet
57.6K10,000 cablefeet
115.2K5,000 cablefeet
230.4K2,500 cablefeet
57.6K10,000 cablefeet
3
115.2K5,000 cablefeet
3
230.4K2,500 cablefeet
Mount the blocks vertically with a minimum of 2” between blocks. This air
gap is necessary to maintain proper cooling air flow through the block.
Maximum
Network Distance
Block
2.0 (50.8) air gap
on all 4 sides.
Operating temperature in
gap
below module must
air
not
exceed 60oC (140oF).
Figure 2.1
Mounting
Equipment
Grounding
Stud
CAUTION:
Dimensions for the Block I/O Modules (1791N4V2 shown)
2.710
1
(68.8)
1.71
(43.4)
ANALOG BLOCK
0
1
POWER
COMM
FAULT
1791N4V2
OUTPUT
INPUT
Inches
(Millimeters)
6.95H x 2.710W x 3.85D
(176.5H x 68.8W x 98D)
0
1
2
3
2 mounting holes
for 1/4inch screws
0.5
(12.7)
6.95
6.60
(176.5)
(167.6)
30
When tightening grounding stud nut, do not exceed 15 inlbs.
2-3
Chapter 2
Installing Block I/O
Connecting Wiring
Figure 2.2
Mounting
1. Hook top of slot over DIN rail.
2. While pressing block against rail,
pull down on locking lever.
3. When block is flush against rail,
push up on locking lever to
secure block to rail.
on a DIN Rail
Block
DIN Rail
AB pt. no. 199DR1
DIN 462773
EN 50022
(3.4 x 7.5mm)
Locking Lever
12382I
Make wiring connections to the removable terminal block which plugs into
the front of the block.
Figure 2.3
Removing
ATTENTION: The terminal block is not keyed to prevent
incorrect insertion. If you remove the terminal block, make
certain that it is inserted with the lower row of screws on the
outside of the block with number 1 at the top of the
terminal strip.
the T
erminal Block
To remove the terminal strip,
unscrew the two captive screws
and pull the terminal strip out.
2-4
12383I
Chapter 2
Installing Block I/O
Figure 2.4
Terminal
Block Pin Numbering
Refer to the following table for wiring schematics and connecting wiring
lists for the analog block modules.
Power Supply VoltageInputFor Schematic refer to:For wiring refer to:
120V ac
24V dc
120V ac
24V dc
120V ac
24V dc
Wiring Connections for the Analog Block with
Wiring Connections for the Analog Block with
Voltage Inputs
Wiring Connections for the Analog Block with
Wiring Connections for the Analog Block with
Current Input and CustomerSupplied Loop Power
Wiring Connections for the Analog Block with
Wiring Connections for the Analog Block with
Current Input and BlockSupplied Loop Power
Figure 2.5, page 26Table 2.B, page 29
Figure 2.6, page 26Table 2.C, page 210
Figure 2.7, page 27Table 2.D, page 211
Figure 2.8, page 27Table 2.E, page 212
Figure 2.9, page 28Table 2.D, page 211
Figure 2.10, page 28Table 2.E, page 212
2-5
Chapter 2
Installing Block I/O
RIO
Figure 2.5
Connections for the 120V ac Analog Block with V
Wiring
GND
NOT
USED
BLU
CLR
RET
in0
GND
in0
RET
in1
GND
in1
RET
in2
GND
in2
RET
in3
GND
in3
RET
out0
RET
out1
NOT
USED
30
NOT
USED
SHD
in
in I0
in V1
in I1
in V2
in I2
in V3
in I3
+24
Vdc
out0
out1
1
L1
N
V0
L1
Voltage Input
+
User Analog
Input Device
-
User +24VUser GND
Output
+
User Analog
Output Device
-
oltage Inputs
L2/N
Analog signals must be within the 10V
common mode voltage range which is
referenced to the analog input common
(GND). Typically, this is accomplished by
connecting to user ground. If an input
channel floats outside of this range,
invalid input readings will result.
RIO
Figure 2.6
Connections for the 24V dc Analog Block with V
Wiring
GND
NOT
USED
BLU
CLR
RET
in0
GND
in0
RET
in1
GND
in1
RET
in2
GND
in2
RET
in3
GND
in3
RET
out0
RET
out1
NOT
USED
30
RET
+24
NOT
USED
SHD
in
in I0
in V1
in I1
in V2
in I2
in V3
in I3
+24
Vdc
out0
out1
1
+24
V0
+
+24V dc
Supply
Voltage Input
+
User Analog
Input Device
-
User +24VUser GND
Output
+
User Analog
Output Device
-
oltage Input
-
Analog signals must be within the 10V
common mode voltage range which is
referenced to the analog input common
(GND). Typically, this is accomplished by
connecting to user ground. If an input
channel floats outside of this range,
invalid input readings will result.
2-6
Loading...
+ 56 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.