Rockwell Automation 1791R-XXXX User Manual

Installation Instructions
Compact
Block
Distributed I/O on
Remote I/O
(Cat. No. 1791R-16B0, -0B16P, -8B8P, -4B4P, -8V8P)
1791R CompactBlock™ I/O modules are stand-alone 24V dc Block I/O products that communicate via a Remote I/O link. Each Remote I/O node consists of either one base module or one base module and one expansion module. Any expansion module can be coupled with any base module. CompactBlock 1791R consists of only base modules. The expansion modules are part of the CompactBlock 1791D family of products.
CompactBlock Remote I/O modules must be installed in a secondary enclosure. Base modules are equipped with 8 to 16 points.
CompactBlock Remote I/O provides both sinking and sourcing inputs and outputs. Sinking inputs are 24V dc NEMA Type 3 compatible. Self-protected 24V dc outputs can provide up to 0.5 amp each.

Important User Information

Because of the variety of uses for the products described in this publication, those responsible for the application and use of these products must satisfy themselves that all necessary steps have been taken to assure that each application and use meets all performance and safety requirements, including any applicable laws, regulations, codes and standards. In no event will Allen-Bradley be responsible or liable for indirect or consequential damage resulting from the use or application of these products.
Publication 1791R-IN001A-EN-P - February 2002
2 CompactBlock Distributed I/O on Remote I/O
WARNING
!
ATTENTION
!
Any illustrations, charts, sample programs, and layout examples shown in this publication are intended solely for purposes of example. Since there are many variables and requirements associated with any particular installation, Allen-Bradley does not assume responsibility or liability (to include intellectual property liability) for actual use based upon the examples shown in this publication.
Allen-Bradley publication SGI-1.1, Safety Guidelines for the
Application, Installation and Maintenance of Solid-State Control
(available from your local Allen-Bradley office), describes some important differences between solid-state equipment and electromechanical devices that should be taken into consideration when applying products such as those described in this publication.
Reproduction of the contents of this copyrighted publication, in whole or part, without written permission of Rockwell Automation, is prohibited.
Throughout this publication, notes may be used to make you aware of safety considerations. The following annotations and their accompanying statements help you to identify a potential hazard, avoid a potential hazard, and recognize the consequences of a
potential hazard:
Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
Publication 1791R-IN001A-EN-P - February 2002
Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss.
CompactBlock Distributed I/O on Remote I/O 3
IMPORTANT
ATTENTION
!
Identifies information that is critical for successful application and understanding of the product.
Environment and Enclosure
This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes up to 2000 meters without derating.
This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR Publication 11. Without appropriate precautions, there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance.
This equipment is supplied as "enclosed" equipment. It should not require additional system enclosure when used in locations consistent with the enclosure type ratings stated in the Specifications section of this publication. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings, beyond what this product provides, that are required to comply with certain product safety certifications.
NOTE: See NEMA Standards publication 250 and IEC publication 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosure. Also, see the appropriate sections in this publication, as well as the Allen-Bradley publication 1770-4.1 ("Industrial Automation Wiring and Grounding Guidelines"), for additional installation requirements pertaining to this equipment.
Publication 1791R-IN001A-EN-P - February 2002
4 CompactBlock Distributed I/O on Remote I/O
ATTENTION
!

Installing CompactBlock I/O

Follow these steps, to install the 1791R I/O module:
1. Set the Node Address on the Base Module.
2. Mount the Block(s).
3. Connect the Input/Output Wires to the Block.
4. Connect the RIO Cable.
5. Select termination for the module.
6. Connect power to the module.
7. Remove the terminal block.
8. Insert the terminal block.
9. Communicate with the 1791R Module.
These steps are explained in detail in the following procedures.
Preventing Electrostatic Discharge
This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment:
Publication 1791R-IN001A-EN-P - February 2002
Touch a grounded object to discharge
potential static.
Wear an approved grounding wriststrap.
Do not touch connectors or pins on
component boards.
Do not touch circuit components inside the
equipment.
If available, use a static-safe workstation.
When not in use, store the equipment in
appropriate static-safe packaging.
CompactBlock Distributed I/O on Remote I/O 5
IMPORTANT
Vi

Set the Node Address on the Base Module

The node address for network connection is set using two 8-bit DIP switches. To set the node address, lift the door containing the status LEDs on the top left side of the module. The switches are read at module power up only. The rack address setting and the starting
quarter setting are described below.
It is important to monitor the rack fault bit. When installing a system for the first time, it is possible to mistakenly put devices with duplicate rack addresses on the same network. Blocks with duplicate addresses may in certain instances cause outputs to toggle on/off until the duplicate address error is corrected.
ew when looking into module.
DIP Switch Settings
The 1791R DIP switches are described in the table below.
DIP Switch No. Description Starting Quarter
SW1
8
7
6
5
4
3
ON
2
1
1 Starting Quarter
2 Starting Quarter
8
7
6
5
4
3
ON
SW1-2 SW1-2
2
1
Module
Group
0 0 0 (1st)
0 1 2 (2nd)
1 0 4 (3rd)
1 1 6 (4th)
Publication 1791R-IN001A-EN-P - February 2002
6 CompactBlock Distributed I/O on Remote I/O
DIP Switch No. Description
3 Rack Address
4 Rack Address
SW1
5 Rack Address
6 Rack Address
See table below.
7 Rack Address
8 Rack Address
Rack Address (6 bit): Position in scanner data mapping. Starting Quarter: Position in Rack Address with 1/4 rack size data.
Rack addresses are listed in the table below.
1747-SN Rack Number
Rack 0 Rack 1 Rack 1 Not Valid Rack 0 Rack 0 0 0 0 0 0 0
Rack 1 Rack 2 Rack 2 Rack 1 Rack 1 Rack 1 0 0 0 0 0 1
Rack 2 Rack 3 Rack 3 Rack 2 Rack 2 Rack 2 0 0 0 0 1 0
Rack 3 Rack 4 Rack 4 Rack 3 Rack 3 Rack 3 0 0 0 0 1 1
1771-SN Rack Number
Rack 5 Rack 5 Rack 4 Rack 4 Rack 4 0 0 0 1 0 0
Rack 6 Rack 6 Rack 5 Rack 5 Rack 5 0 0 0 1 0 1
Rack 7 Rack 7 Rack 6 Rack 6 Rack 6 0 0 0 1 1 0
PLC-2 Rack Number
PLC-5 Rack Number
Rack 7 Rack 7 Rack 7 0 0 0 1 1 1
Rack 10 Rack 10 Rack 10 0 0 1 0 0 0
Rack 11 Rack 11 Rack 11 0 0 1 0 0 1
Rack 12 Rack 12 Rack 12 0 0 1 0 1 0
Rack 13 Rack 13 Rack 13 0 0 1 0 1 1
Rack 14 Rack 14 Rack 14 0 0 1 1 0 0
Rack 15 Rack 15 Rack 15 0 0 1 1 0 1
Rack 16 Rack 16 Rack 16 0 0 1 1 1 0
Rack 17 Rack 17 Rack 17 0 0 1 1 1 1
PLC5/250 Rack Number
PLC-3 Rack Number
SW1 Switch Position
876543
Publication 1791R-IN001A-EN-P - February 2002
CompactBlock Distributed I/O on Remote I/O 7
1747-SN Rack Number
1771-SN Rack Number
PLC-2 Rack Number
PLC-5 Rack Number
Rack 20 Rack 20 Rack 20 0 1 0 0 0 0
Rack 21 Rack 21 Rack 21 0 1 0 0 0 1
Rack 22 Rack 22 Rack 22 0 1 0 0 1 0
Rack 23 Rack 23 Rack 23 0 1 0 0 1 1
Rack 24 Rack 24 Rack 24 0 1 0 1 0 0
Rack 25 Rack 25 Rack 25 0 1 0 1 0 1
Rack 26 Rack 26 Rack 26 0 1 0 1 1 0
Rack 27 Rack 27 Rack 27 0 1 0 1 1 1
PLC5/250 Rack Number
Rack 30 Rack 30 011000
Rack 31 Rack 31 011001
Rack 32 Rack 32 011010
Rack 33 Rack 33 011011
Rack 34 Rack 34 011100
Rack 35 Rack 35 011101
Rack 36 Rack 36 011110
Rack 37 Rack 37 011111
PLC-3 Rack Number
Rack 40 100000
Rack 41 100001
Rack 42 100010
Rack 43 100011
Rack 44 100100
Rack 45 100101
Rack 46 100110
Rack 47 100111
Rack 50 101000
Rack 51 101001
Rack 52 101010
Rack 53 101011
Rack 54 101100
Rack 55 101101
SW1 Switch Position
876543
Publication 1791R-IN001A-EN-P - February 2002
8 CompactBlock Distributed I/O on Remote I/O
1747-SN Rack Number
Rack address 77 is an illegal configuration.
PLC-5/11 processors can scan rack 03.
1771-SN Rack Number
PLC-2 Rack Number
PLC-5 Rack Number
PLC5/250 Rack Number
PLC5/15 and PLC-5/20 processors can scan racks 01-03. PLC5/25 and PLC-5/30 processors can scan racks 01-07. PLC5/40 and PLC-5/40L processors can scan racks 01-17. PLC5/60 and PLC-5/60L processors can scan racks 01-27. PLC5/250 processors can scan racks 00-37.
PLC-3 Rack Number
Rack 56 101110
Rack 57 101111
Rack 60 110000
Rack 61 110001
Rack 62 110010
Rack 63 110011
Rack 64 110100
Rack 65 110101
Rack 66 110110
Rack 67 110111
Rack 70 111000
Rack 71 111001
Rack 72 111010
Rack 73 111011
Rack 74 111100
Rack 75 111101
Rack 76 111110
Not Valid111111
SW1 Switch Position
876543
Publication 1791R-IN001A-EN-P - February 2002
CompactBlock Distributed I/O on Remote I/O 9
WARNING
!
DIP
Switch
SW2
No. Description ON OFF
1Comm Rate
2Comm Rate
3 N/A
4 Hold Last State Hold Last State Output Reset
5 Processor
Restart/Lockout
6 Last I/O Last Rack Not Last Rack
7 Filter Speed Setting
8 Filter Speed Setting
00=57.6K 01=115.2K 10=230.4K 11=230.4K
Lockout Restart
00=2ms 10=4ms 01=8ms 11=16ms

Mount the Block(s)

The base and expansion modules mount to a panel or DIN rail which must be grounded before installing the module(s).
Base Module Mounting
Install the CompactBlock base module on a panel or DIN rail.
When used in a Class I, Division 2, hazardous location, this equipment must be mounted in a suitable enclosure with proper wiring method that complies with the governing electrical codes.
Panel Mounting
1. Place the module against the panel where you want to mount it.
2. Drill holes in the panel that are aligned with mounting holes on the module.
Publication 1791R-IN001A-EN-P - February 2002
Loading...
+ 19 hidden pages