Rockwell Automation 1791ES-IB16 User Manual

User Manual
Guard I/O EtherNet/IP Safety Modules
Catalog Numbers 1791ES-IB8XOBV4, 1791ES-IB16
Important User Information
IMPORTANT
Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/ important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
available from
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.
Identifies information that is critical for successful application and understanding of the product.
Allen-Bradley, Rockwell Software, Rockwell Automation, RSLogix, Log ix 5000, Studio 5000, Guard I/O, CompactBlock, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.

New and Updated Information

Summary of Changes

Change bars (as shown in this paragraph) show the areas in this manual that are different from previous editions and indicate the addition of revised information.
This table contains the changes made to this revision.
Top ic Pag e
Additional Resources 7
Studio 5000 Environment 7
Programming Requirements 14
Safety Data 91
Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013 3
Summary of Changes
Notes:
4 Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013

Table of Contents

Preface
About the Modules
Understand the Operation of Safety Functions
Studio 5000 Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
About the Specifications and Dimensions in This Manual . . . . . . . . . . . . . 8
Terminology. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Chapter 1
Before You Begin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Understand Suitability for Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Follow Precautions for Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Precautions to Mount, Wire, and Clean. . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
I/O Module Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
About Catalog Numbers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Programming Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
About CIP Safety in EtherNet/IP Safety Architectures. . . . . . . . . . . . . . 14
Identify Major Parts of the Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Chapter 2
Self-diagnostic Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Configuration Lock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
I/O Status Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Safety Inputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Using a Test Output with a Safety Input . . . . . . . . . . . . . . . . . . . . . . . 19
Set Dual-channel Mode and Discrepancy Time . . . . . . . . . . . . . . . . . 22
Dual-channels, Equivalent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Dual-channels, Complementary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Safety Input Fault Recovery. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Input Delays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Safety Outputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Safety Output with Test Pulse . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Dual-channel Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Safety Output Fault Recovery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Controlling Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Safety Precautions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Legislation and Standards. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Europe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
North America. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Japan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
EC Directives. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
EMC Directive. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Compliance with EC Directives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013 5
Table of Contents
Chapter 3
Install and Connect Your Modules
Wiring Examples
Configure the I/O Modules by Using the Logix Designer Application
Install the Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Connect the Ethernet Cable. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Set Network (IP) Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Connect I/O Power and I/O Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Chapter 4
Examples of Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Chapter 5
Use Help . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Add Modules to the I/O Configuration Tree . . . . . . . . . . . . . . . . . . . . . . . 47
Use the Module Properties and General Dialogs . . . . . . . . . . . . . . . . . . . . 49
Input Data Options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Input Status Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Output Data Options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Values and States of Tags . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Work with the Safety Dialog . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Configuration Ownership - Reset Ownership . . . . . . . . . . . . . . . . . . . 58
Configuration Signature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Work with the Input Configuration Dialog . . . . . . . . . . . . . . . . . . . . . . . . 60
Work with Test Output Configuration Dialog . . . . . . . . . . . . . . . . . . . . . 62
Work with the Output Configuration Dialog. . . . . . . . . . . . . . . . . . . . . . . 63
Save and Download the Module Configuration . . . . . . . . . . . . . . . . . . . . . 65
Interpret Module Indicators
Get Diagnostic Status from Modules by Using Explicit Messaging
Safety Data
Configuration Reference Information
Index
Chapter 6
Module Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Configuration Lock Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Appendix A
Work with 1791ES-IB8XOBV4 Modules . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Work with 1791ES-IB16 Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
I/O Data Supported by Each Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
I/O Assembly and Reference Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Explicit Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Appendix B
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Appendix C
Understand Parameter Groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
6 Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013

Preface

Read and understand this manual before using the described products. Consult your Rockwell Automation representative if you have any questions or comments. This manual describes how to use Guard I/O modules.

Studio 5000 Environment

The Studio 5000™ Engineering and Design Environment combines engineering and design elements into a common environment. The first element in the Studio 5000 environment is the Logix Designer application. The Logix Designer application is the rebranding of RSLogix™ 5000 software and will continue to be the product to program Logix5000™ controllers for discrete, process, batch, motion, safety, and drive-based solutions.
The Studio 5000 environment is the foundation for the future of Rockwell Automation® engineering design tools and capabilities. This environment is the one place for design engineers to develop all of the elements of their control system.

Additional Resources

Refer to the following as needed for additional help when setting up and using your modules. For specifications, refer to the relevant installation instructions.
Resource Description
CompactBlock Guard I/O EtherNet/IP Safety Modules Installation Instructions, publication 1791ES-IN001
GuardLogix 5570 Controllers User Manual, publication 1756-UM022
GuardLogix 5570 Controller Systems Safety Reference Manual, publication 1756-RM099
GuardLogix Controllers User Manual, publication 1756-UM020 Provides information on how to install, configure, program, and use GuardLogix 5560 and
GuardLogix Controller Systems Safety Reference Manual, publication 1756-RM093
Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013 7
Provides detailed specifications and information related to installation of Guard I/O modules.
Provides information on how to install, configure, program, and use GuardLogix 5570 controllers in Studio 5000 Logix Designer projects.
Provides information on safety application requirements for GuardLogix 5570 controllers in Studio 5000 Logix Designer projects.
5570 controllers in RSLogix 5000 projects.
Provides information on safety application requirements for GuardLogix 5560 and 5570 controllers in RSLogix 5000 projects.
Preface
Resource Description
GuardLogix Safety Application Instructions Safety Reference Manual, publication
1756-RM095
Ethernet Design Considerations Reference Manual, publication ENET-RM002 Describes the required media components and how to plan for and install these required
ODVA Media Planning and Installation Manual, publication 00148-BR00 the EtherNet/IP Library at ODVA.org
, available from
Provides reference information describing the GuardLogix Safety Application Instruction Set.
components.
Describes the required media components and how to plan for and install these required components.
You can view or download publications at
http://www.rockwellautomation.com/literature/
. To order paper copies of technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative.

About the Specifications and Dimensions in This Manual

Product specifications and accessories can change at any time based on improvements and other reasons. Consult with your Rockwell Automation representative to confirm actual specifications of purchased product. Dimensions and weights are nominal and are not for use for manufacturing purposes, even when tolerances are shown.

Terminology

Term Definition
Connection Logical communication channel for communication between nodes. Connections are maintained and controlled between masters and slaves.
EDS Acronym for electronic data sheet, a template that RSNetWorx software uses to display the configuration parameters, I/O data profile, and connection-type
support for a given I/O module. These are simple tex t files used by RSNetWorx software for you to identify products and commission them on a network.
L- Output +24V DC common.
M Sinking output common channel, output switches to the common voltage.
MTBF Acronym for mean time between failure, the average time between failure occurrences.
ODVA Acronym for Open DeviceNet Vendor Association, a nonprofit association of vendors established for the promotion of CIP networks.
P Sourcing output channel, output switches to the plus voltage.
PFD Acronym for probability of failure on demand, the average probability of a system to fail to perform its design function on demand.
PFH Acronym for probability of failure per hour, the probability of a system to have a dangerous failure occur per hour.
Proof test Periodic test per formed to detect failures in a safety-related system so that, if necessary, the system can be restored to an as-new condition or as close as
practical to this condition.
S+ Output +24V DC.
SNN Acronym for safety network number, which uniquely identifies a network across all networks in the safety system. You are responsible for assigning a
unique number for each safety network or safety sub-net within a system.
Standard Devices or portions of devices that do not par ticipate in the safety function.
Refer to the table for the meaning of common terms.
8 Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013
About the Modules
Top ic Pa ge
Before You Begin 9
Understand Suitability for Use 10
Follow Precautions for Use 10
Precautions to Mount, Wire, and Clean 11
I/O Module Overview 12
About Catalog Numbers 13
Programming Requirements 14
About CIP Safety in EtherNet/IP Safety Architectures 14
Identify Major Parts of the Module 14
Chapter 1

Before You Begin

This chapter includes important overview information and precautions for use of the Guard I/O modules that implement the EtherNet/IP safety protocol. Also included is an overview on how these I/O modules are used within a safety system.
Always observe the following when using a module, noting that in this manual we use safety administrator to mean a person qualified, authorized, and responsible to secure safety in the design, installation, operation, maintenance, and disposal of the machine.
Thoroughly read and understand this manual before installing and operating the module.
Keep this manual in a safe place where personnel can refer to it when necessary.
Use the module properly according to the installation environment, performance, and functions of the machine.
Verify that a safety administrator conducts a risk assessment on the machine and determines module suitability before installation.
Verify for CE LVD compliance, the external power supply that provides power to the modules is safety extra-low voltage (SELV) rated. Some Rockwell Automation Bulletin 1606 power supplies are SELV-compliant. Verify Bulletin 1606 Installation Instructions.
Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013 9
Chapter 1 About the Modules
Verify that the Guard I/O firmware version is correct prior to commissioning the safety system, noting that firmware information related to safety controllers is available at:
http://www.rockwellautomation.com/products/certification/

Understand Suitability for Use

Follow Precautions for Use

Rockwell Automation is not responsible for conformity with any standards, codes, or regulations that apply to the combination of the products in your application or use of the product.
Take all necessary steps to determine the suitability of the product for the systems, machine, and equipment with which it is used.
Know and observe all prohibitions of use applicable to this product.
Never use the products for an application involving serious risk to life or property without making sure that the system as a whole was designed to address the risks and that the Rockwell Automation product is properly rated and installed for the intended use within the overall equipment or system.
ATT EN TI ON :
Safety state of the inputs and outputs is defined as the off state.
Safety state of the module and its data is defined as the off state.
Use the Guard I/O module only in applications where the off state is the safety
state.
Serious injury can occur due to breakdown of safety outputs. Do not connect loads beyond the rated value to the safety outputs.
Serious injury can occur due to loss of required safety functions. Wire the module properly so that supplyy voltages or voltages for loads do not touch the safety outputs accidentally or inadvertently.
10 Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013
About the Modules Chapter 1
ATTENTION: Use a DC power supply satisfying the following requirements to prevent electric shock:
A DC power sup ply wi th dou ble or reinforced i nsulatio n, for examp le, according to IED/EN 60950 or EN 50178 or a transformer according to IEC/EN 61558
A DC supply satisfies requirement for class 2 circuits or limited voltage/current circuit stated in UL 508
Use an external power supply that is safety extra-low voltage (SELV) rated
Follow these precautions for safe use.
Wire conductors correctly and verify operation of the module before
placing the system into operation. Incorrect wiring can lead to loss of safety function.
Do not apply DC voltages exceeding the rated voltages to the module.
Apply properly specified voltages to the module inputs. Applying inappropriate voltages causes the module to fail to perform its specified function, which leads to loss of safety functions or damage to the module.
Never use test outputs as safety outputs. Test outputs are not safety outputs.
Note that after installation of the module, a safety administrator must confirm the installation and conduct trial operation and maintenance.
Do not disassemble, repair, or modify the module. This can result in loss of safety functions.
Use only appropriate components or devices complying with relevant safety standards corresponding to the required safety category and safety integrity level.
- Conformity to requirements of the safety category and safety
integrity level must be determined for the entire system.
- We recommend you consult a certification body regarding
assessment of conformity to the required safety integrity level or safety category.
Note that you must confirm compliance with the applicable standards for the entire system.
Disconnect the module from the power supply before wiring. Devices connected to the module can operate unexpectedly if wiring is performed while power is supplied.

Precautions to Mount, Wire, and Clean

Observe these precautions to prevent operation failure, malfunctions, or undesirable effects on product performance.
Follow these precautions when mounting modules.
Use DIN rail that is 35 mm (1.38 in.) wide to mount the module into the control panel.
Mount modules to DIN rail securely.
Leave at least 15 mm (0.6 in.) around the module to allow adequate
ventilation and room for wiring.
Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013 11
Chapter 1 About the Modules
Follow these instructions when wiring modules.
Do not place communication lines and I/O lines in the same wiring duct or track as high voltage lines.
Wire correctly after confirming the signal names of all terminals.
Follow torquing specifications as indicated in the installation instructions.
When cleaning modules, do not use the following:
Thinner
Benzene
Acetone

I/O Module Overview

The Guard I/O modules implement the CIP-safety protocol extensions over EtherNet/IP networks and provide various features for a safety system.
Use the modules to construct a safety-control network system that meets the requirements up to Safety Integrity Level 3 (SIL 3) as defined in IEC 61508, Functional Safety of Electrical, Electronic, and Programmable Electronic Safety-related Systems, and the requirements for Safety Category 4 of the EN 954-1 standard, Safety of machinery - Safety related parts of control systems.
Remote I/O communication for safety I/O data are performed through safety connections supporting CIP safety over an EtherNet/IP network, and data processing is performed in the safety controller.
The status and fault diagnostics of the I/O modules are monitored by a safety controller through a safety connection by using a new or existing EtherNet/IP network.
12 Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013
About the Modules Chapter 1
The following is a list of features common to Guard I/O modules:
CIP-safety and EtherNet/IP protocol conformance
Safety inputsSafety devices, such as emergency stop push buttons, gate switches, and
safety light curtains, can be connected.
– Dual-channel mode evaluates consistency between two input signals
(channels), which allows use of the module for Safety Category 3 and 4.
– The time of a logical discrepancy between two channels can be
monitored by using a discrepancy time setting.
– An external wiring short-circuit check is possible when inputs are wired
in combination with test outputs.
Independently adjustable on and off delay is available per channel.
Te st ou tp u ts Separate test outputs are provided for short circuit detection of a safety
input (or inputs).
Power (24V) can be supplied to devices, such as safety sensors.Test outputs can be configured as standard outputs.All Guard I/O modules have numerous test outputs, of which some can
be used for broken wire detection of a muting lamp.
Safety outputs Dual-channel mode evaluates consistency between two output signals
(channels).
– Safety outputs can be pulse tested to detect field wiring shorts to
24V DC and 0V DC.
I/O status data - In addition to I/O data, the module includes status data for monitoring I/O circuits.
Removable I/O connectors - I/O connectors support mechanical keying.

About Catalog Numbers

Catalog Number Description Enclosure Type
1791ES-IB16 Safety input module Meets IP20 16 16
1791ES-IB8XOBV4 Safety I/O module with solid state outputs 8 8 4 bipolar pairs
(1) Broken wires can be detected on the muting outputs.
See the table for a listing of the types of Guard I/O modules.
Rating
Safety Inputs Test Outputs
Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013 13
(1)
Safety Outputs
Solid State
Chapter 1 About the Modules
EtherNet/IP Network
ControlNet Network
DeviceNet Network
DeviceNet Network
EtherNet
EtherNet
RSLogix Software RSView Software
Control Net Network
DeviceNet Network
DeviceNet Network
Standard Communication
Safety Communication

Programming Requirements Use the minimum software versions listed here.

Cat. No. Studio 5000 Environment
1791ES-IB16 21 16
1791ES-IB8XOBV4 21 16
(1) This version or later.
Versio n
(1)
RSLogix 5000 Software Version (EtherNet/IP Network)
(1)

About CIP Safety in EtherNet/IP Safety Architectures

Use Guard I/O modules in EtherNet/IP safety architectures as shown in the figure. The Guard I/O family is a set of I/O modules that when connected to an EtherNet/IP safety network are suitable for applications up to SIL3, as defined in the IEC 61508 standard, and Safety Category 4, as defined in the EN 954-1 standard.
Figure 1 - Safety Interlocking and Control via CIP Safety
Safety controllers control the safety outputs. Safety or standard controllers can control the standard outputs.

Identify Major Parts of the Module

14 Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013
See the figure for module identification. For pin-out information, refer to the relevant installation instructions.
Figure 2 - Major Module Parts
I/O Connectors
I/O Connectors
Power Connector
LED Status Indicators
IP Address Switch
EtherNet IP Address Label
EtherNet Connecto r
Network Activity Indicator
About the Modules Chapter 1
Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013 15
Chapter 1 About the Modules
Notes:
16 Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013
Chapter 2
Output Off
Input
Inputs to Network Off
EtherNet/IP Network
Safety Status
44076
Understand the Operation of Safety Functions
Top ic Pa ge
Self-diagnostic Functions 18
Configuration Lock 18
I/O Status Data 18
Safety Inputs 18
Safety Outputs 27
Controlling D evices 28
Safety Precautions 29
Legislation and Standards 29
EC Directives 31
Read this chapter for information related to the safety functions of the modules. Also included is a brief overview on international standards and directives that you must be familiar with.
The following status is the safety state of the Guard I/O modules:
Safety outputs: off
Safety input data to network: off
Figure 3 - Safety Status
The module is designed for use in applications where the safety state is the off state.
Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013 17
Chapter 2 Understand the Operation of Safety Functions

Self-diagnostic Functions

Configuration Lock

I/O Status Data

Self-diagnostics are performed when the power is turned on and periodically during operation. If a fatal internal module error occurs, the red module status (MS) indicator is illuminated, and the safety outputs and input data and status to the network turn off.
After configuration data has been downloaded and verified, the configuration data within the module can be protected.
For GuardLogix systems, the LED indicator is not used. Reference information about safety signatures in the GuardLogix Controller Systems Safety Reference Manual, publication 1756-RM093
In addition to I/O data, the module provides status data for monitoring the I/O circuits. The status data includes the following data, which can be read by the controllers. Note that 1 = ON/Normal and 0 = OFF/Fault/Alarm.
Individual Point Input Status
Combined Input Status
Individual Point Output Status
Combined Output Status
Individual Test Output Status
Individual Output Readback (actual ON/OFF state of the outputs)
.

Safety Inputs

Status data indicate whether each safety input, safety output, or test output is normal (normal status: ON, faulted status: OFF). For fatal errors, communication connections can be broken, so the status data cannot be read.
Combined status is provided by an AND of the status of all safety inputs or all safety outputs. When all inputs or outputs are normal the respective combined status is ON. When one or more of them has an error the respective combined status is OFF. This is known as the combined safety input status or combined safety output status.
Read this section for information about safety inputs and their associated test outputs. A safety input can be used with test outputs. Safety inputs are used to monitor safety input devices.
18 Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013

Using a Test Output with a Safety Input

I8 I9 T8 T9 I10 I11 T10 T11M I12 I13 T12 T13 I14 I15 T14 T15M
I0 I1 T0 T1 I2 I3 T2 T3M I4 I5 T4 T5 I6 I7 T6 T7M
IN+ IN-
24V DC
24V DC Output with Test Pulse
External Contact
Safety Input
44295
OUT
On
Off
Typ ic al 500 μs
Typ ic al 150 ms
A test output can be used in combination with a safety input for short circuit detection. Configure the test output as a pulse test source and associate it to a specific safety input.
The test output can also be used as a power supply to source 24V DC for an external input circuit.
Figure 4 - Example Use of a 1791ES-IB16 Module
Understand the Operation of Safety Functions Chapter 2
Table 1 - Typical Pulse Width and Period
Attribute 1791ES-IB8XOBV4 1791ES-IB16
Pulse width 500 μs 500 μs
Period 150 ms 150 ms
Figure 5 - Test Pulse in a Cycle
Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013 19
Chapter 2 Understand the Operation of Safety Functions
T0
IN0
T1
IN1
IN+
IN-
External
Short-circuit Between Input Signal Lines and Power
Supply (Positive Side)
External Contact
Short-circuit Between Input Signal Lines
44079
When the external input contact is closed, a test pulse is output from the test output terminal to diagnose the field wiring and input circuitry. By using this function, short-circuits between input signal lines and the power supply (positive side), and short-circuits between input signal lines can be detected.
Figure 6 - Short-circuit Between Input Signal Lines
24V
24V
0V
20 Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013
Understand the Operation of Safety Functions Chapter 2
24V
0V
T0
Input Terminal 0
External Device
Faul t De tected
Remote I/O Data
ON
OFF
ON
OFF
ON
OFF
ON
OFF
24V
0V
ON
OFF
T0
Safety Input Status 0
Fault Detection
Remote I/O Data
ON
OFF
ON
OFF
ON
OFF
Safety Input Status 0
Safety Input 0
Safety Input 0
Input Terminal 0
Normal Operation
External Device
If an error is detected, safety input data and safety input status turns off.
Figure 7 - Normal Operation and Fault Detection (not to scale)
Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013 21
Chapter 2 Understand the Operation of Safety Functions
IMPORTANT
IMPORTANT

Set Dual-channel Mode and Discrepancy Time

To support redundant channel safety devices, the consistency between signals on two channels can be evaluated. Either equivalent or complementary can be selected. This function monitors the time during which there is a discrepancy between the two channels.
If the length of the discrepancy exceeds the configured discrepancy time (0…65,530 ms in increments of 10 ms), the safety input data and the individual-safety input status turns off for both channels.
The dual-channel function is used with two consecutive inputs that are paired together, starting at an even input number, such as inputs 0 and 1, 2 and 3, and so on.
Do not set the discrepancy time longer than necessary. The purpose of the discrepancy time is to allow for normal differences between contact switching when demands are placed on safety inputs. For this testing to operate correctly, only a single demand on the safety input is expected during the discrepancy time. If the discrepancy time is set too high, and multiple demands occur during this time, then both safety input channels will fault.
22 Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013
The following table shows the relation between input terminal states and controller input data and status.
Table 2 - Terminal Input Status and Controller I/O Data
Understand the Operation of Safety Functions Chapter 2
Dual-channel Mode Input Terminal Controller Input Data and Status Dual- channel
IN0 IN1 Safety
Dual-channels, Equivalent OFF OFF OFF OFF ON ON OFF Normal
OFF ON OFF OFF OFF OFF OFF Fault
ON OFF OFF OFF OFF OFF OFF Fault
ON ON ON ON ON ON ON Normal
Dual-channels, Complementary
OFF OFF OFF ON OFF OFF OFF Fault
OFF ON OFF ON ON ON OFF Normal
ON OFF ON OFF ON ON ON Normal
ON ON OFF ON OFF OFF OFF Fault
Input 0 Data
Safety Input 1 Data
Safety Input 0 Status
Safety Input 1 Status
Resultant Data
Dual-channel Resultant Status

Dual-channels, Equivalent

In Equivalent mode, both inputs of a pair must typically be in the same (equivalent) state. When a transition occurs in one channel of the pair, prior to the transition of the second channel of the pair, a discrepancy occurs. If the second channel transitions to the appropriate state prior to the discrepancy time elapsing, the inputs are considered equivalent. If the second transition does not occur before the discrepancy time elapses, the channels will fault. In the fault state the input and status for both channels are set low (off). When configured as an equivalent dual pair, the data bits for both channels will always be sent to the controller as equivalent, both high or both low.
Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013 23
Chapter 2 Understand the Operation of Safety Functions
ON
OFF
IN0
Safety Input 0
IN1
Fault Detec ted
Discrepancy Time
Remote I/O Data
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
IN0
Safety Input Status 0, 1
IN1
Fault Detection
Remote I/O Data
ON
OFF
ON
OFF
ON
OFF
Discrepancy Time
Safety Input Status 0, 1
Safety Input 1
Safety Input 1
Safety Input 0
Normal Operation
Figure 8 - Equivalent, Normal Operation and Fault Detection (not to scale)

Dual-channels, Complementary

In Complementary mode, the inputs of a pair must typically be in the opposite (complementary) state. When a transition occurs in one channel of the pair prior to the transition of the second channel of the pair, a discrepancy occurs. If the second channel transitions to the appropriate state prior to the discrepancy time elapsing, the inputs are considered complementary.
If the second transition does not occur before the discrepancy time elapses, the channels will fault. The fault state of complementary inputs is the even numbered input turned off and the odd numbered input turned on. Note that if faulted,
24 Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013
Understand the Operation of Safety Functions Chapter 2
ON
OFF
IN0
Safety Input 0
IN1
Faul t De tected
Discrepancy Time
Remote I/O Data
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
IN0
Safety Input Status 0, 1
IN1
Fault Detection
Remote I/O Data
ON
OFF
ON
OFF
ON
OFF
Discrepancy Time
Safety Input Status 0, 1
Safety Input 1
Safety Input 1
Safety Input 0
Normal Operation
both channel status bits are set low. When configured as a complementary dual channel pair, the data bits for both channels will always be sent to the controller in complementary, or opposite states.
Figure 9 - Complementary, Normal Operation and Fault Detection (not to scale)
Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013 25
Chapter 2 Understand the Operation of Safety Functions
44094
On-delay
ON OFF
ON OFF
Input Signal
Remote I/O Data Safety Input
44094
44095
Remote I/O Data Safety Input
Off-delay
Input Signal
ON OFF
ON OFF

Safety Input Fault Recovery

If an error is detected, the safety input data remains in the off state. The procedure for activating the safety input data again is as follows.
1. Remove the cause of the error.
2. Place the safety input (or safety inputs) into the safety state.
The safety input status turns on (fault cleared) after the input-error latch time has elapsed. The I/O indicator (red) turns off. The input data can now be controlled.

Input Delays

On-delay - An input signal is treated as logic 0 during the on-delay time (0…126 ms, in increments of 6 ms) after the input contact’s rising edge. The input only turns on if the input contact remains on after the on-delay time has elapsed. This helps prevent rapid changes of the input data due to contact bounce.
Figure 10 - On-delay
Input
ON
OFF
ON
OFF
ON-delay
Input Signal
Remote I/O Data Safety
Off-delay - An input signal is treated as logic 1 during the off-delay time (0…126 ms, in increments of 6 ms) after the input contact’s falling edge. The input only turns off if the input contact remains off after the off delay time has elapsed. This helps prevent rapid changes of the input data due to contact bounce.
Figure 11 - Off-delay
Input Signal
Remote I/O Data Safety Input
OFF
ON
OFF
OFF-delay
26 Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013
Understand the Operation of Safety Functions Chapter 2
IMPORTANT
44096
OUT
On
Off
Typ ic al 700 μs
Typ ic al 600 ms

Safety Outputs

Read this section for information about safety outputs.

Safety Output with Test Pulse

When the safety output is on, the safety output can be test pulsed, as shown in the figure and table.
Attribute 1791ES-IB8XOBV4
Pulse width 700 μs
Period 600 ms
By using this function, short-circuits between output signal lines and the power supply (positive side) and short-circuits between output signal lines can be detected. If an error is detected, the safety output data and individual-safety output status turns off.
Figure 12 - Test Pulse in a Cycle
To prevent the test pulse from causing the connected device to malfunction, pay careful attention to the input response time of the device.
Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013 27
Chapter 2 Understand the Operation of Safety Functions
ON
OFF
OUT0
Safety Output Status 0, 1
OUT0
OUT1
OUT1
Safety Output Status 0, 1
Fault Detection
Error Detected
Remote I/O Data
Remote I/O Data
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Normal Oper ation

Dual-channel Setting

When the data of both channels is in the on state, and neither channel has a fault, the outputs are turned on. The status is normal. If a fault is detected on one channel, the safety output data and individual safety output status turn off for both channels.
Figure 13 - Dual-channel Setting (not to scale)

Safety Output Fault Recovery

If a fault is detected, the safety outputs are switched off and remain in the off state. The procedure for activating the safety output data again is as follows.

Controlling Devices

28 Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013
1. Remove the cause of the error.
2. Place the safety output (or safety outputs) into the safety state.
The safety output status turns on (fault cleared) when the output-error latch time has elapsed. The I/O indicator (red) turns off. The output data can now be controlled.
See the table for information about controlling devices.
ATTENTION: Use appropriate devices as indicated in the Controlling Device Requirements table. Serious injury can occur due to loss of safety functions.
Understand the Operation of Safety Functions Chapter 2
Table 3 - Controlling Device Requirements
Device Requirement Allen-Bradley Bulletin Safety Components
Emergency stop switches Use approved devices with direct opening mechanisms complying with IEC/EN
Door interlocking switches, limit switches
Safety sensors Use approved devices complying with the relevant product standards,
Relays with forcibly- guided contacts, contactors
Other devices Evaluate whether devices used are appropriate to satisfy the requirements of
60947-5-1.
Use approved devices with direct opening mechanisms complying with IEC/EN 60947-5-1 and capable of switching microloads of 24V DC 5 mA.
regulations, and rules in the country where used.
Use approved devices with forcibly-guided contacts complying with EN 50205. For feedback purposes, use devices with contacts capable of switching micro loads of 24V DC 5 mA.
safety category levels.
Bulletin 800F, 800T
Bulletin 440K, 440G, 440H for interlock switch Bulletin 440P, 802T for limit switch
Any Guardmaster product
Bulletin 700S, 100S

Safety Precautions

ATTENTION: As serious injury can occur due to loss of required safety function,
follow these safety precautions:
Do not use test outputs of the modules as safety outputs.
Do not use EtherNet/IP standard I/O data or explicit message data as
safety data.
Do not use LED indicators on the I/O modules for safety operations.
Do not connect loads beyond the rated value to the safety outputs.
Wire the Guard I/O modules properly so that 24V DC line does not touch
the safety outputs accidentally or unintentionally.
Clear previous configuration data before connecting devices to the network.
Set suitable IP addresses before connecting devices to the network.
Perform testing to confirm that all of the device configuration data and
operation is correct before starting system operation.
When replacing a device, configure the replacement device suitably and confirm that it operates correctly.
When installing or replacing modules, clear any previous configuration before connecting input or output power to the device.

Legislation and Standards

Read this section to familiarize yourself with related legislation and standards information. Relevant international standards include the following:
IEC 61508 (SIL 1-3)
IEC 61131-2
IEC 60204-1
IEC 61000-6-2
IEC 61000-6-4
The modules received the following certification from ODVA, when product is marked.
Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013 29
Chapter 2 Understand the Operation of Safety Functions
EtherNet/IP Conformance
EtherNet/IP Safety Conformance

Europe

In Europe, the modules are subject to the European Union (EU) Machinery Directive Annex IV, B, Safety Components, items 1 and 2. The type approval of TUV-Rheinland addresses compliance to applicable requirements of the following directives and standards:
EU legislation Machinery Directive 98/37/EC Low-voltage Directive 73/23/EEC EMC Directive 89/336/EEC
European standards EN 61508 (SIL1-3)EN 954-1 (Category 4, 3, 2, 1, B)EN 61131-2EN 418EN 60204-1IEC 61000-6-2IEC 61000-6-4

North America

In North America, the TUV-Rheinland type approval includes Guard I/O compliance to the relevant standards and related information including the following:
U.S. standards - ANSI RIA15.06, ANSI B11.19, NFPA 79
The modules are UL-certified functionally safe and carry the NRGF label,
when product is marked.
The modules received UL Listing to standards of U.S. and Canada including the following, when product is marked.

Japan

In Japan, type test requirements are provided in Article 44 of the Industrial Safety and Health Law. These requirements apply to complete systems and cannot be applied to a module by itself. Accordingly, to use the module in Japan as a safety device for press machine or shearing tool pursuant to Article 42 of the above­mentioned law, it is necessary to apply for testing of the entire system.
30 Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013
Understand the Operation of Safety Functions Chapter 2

EC Directives

These products conform to the EMC Directive and Low-voltage Directive. For additional information, refer to the relevant installation instructions.

EMC Directive

Rockwell Automation devices that comply with EC directives also conform to the related EMC standards so that they can more easily be built into other devices or the overall machine. The actual products have been checked for conformity to EMC standards. Whether they conform to the standards in the system used by the customer, however, must be confirmed by the customer.
EMC-related performance of Rockwell Automation devices that comply with EC directives vary depending on the configuration, wiring, and other conditions of the equipment or control panel in which the Rockwell Automation devices are installed. The customer must, therefore, perform the final check to confirm that devices and the overall machine conform to EMC standards.

Compliance with EC Directives

EtherNet/IP products that comply with EC directives must be installed as follows:
All Type IP20 EtherNet/IP units must be installed within control panels.
Use reinforced insulation or double insulation for the DC power supplies
used for the communication power supply, internal- circuit power supply, and the I/O power supplies.
EtherNet/IP products that comply with EC directives also conform to the Common Emission Standard (EN 50081-2). Radiated emission characteristics (10-m regulations) can vary depending on the configuration of the control panel used, other devices connected to the control panel, wiring, and other conditions. You must confirm that the overall machine or equipment complies with EC directives.
Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013 31
Chapter 2 Understand the Operation of Safety Functions
Notes:
32 Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013
Install and Connect Your Modules
Top ic Pa ge
Install the Module 34
Connect the Ethernet Cable 35
Set Network (IP) Address 35
Connect I/O Power and I/O Cables 36
ATT EN TI ON : You can configure Test Outputs to be used as standard outputs. You can connect actuators to Test Output points that are expecting a Standard configuration.
Test Output points configured as Pulse Test or Power Supply become active whenever you apply input power to the module. These configured functions are independent of the I/O connections to the module.
Chapter 3
ATT EN TI ON : If a module with Test Outputs configured as Pulse Test or Power Supply is incorrectly installed in an application where actuators are connected to these Test Output points, the actuators are activated when input power is applied.
To prevent this possibility, follow these procedures.
When installing a module, be sure that the module is correctly configured for the application or in the out-of-box condition before applying input power.
When replacing a module, be sure that the module is correctly configured for the application or in the out-of-box condition before applying input power.
Reset modules to their out-of-box condition when removing them from an application.
Be sure that all modules in replacement stock are in their out-of-box condition.
Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013 33
Chapter 3 Install and Connect Your Modules
IMPORTANT

Install the Module

Follow these instructions when installing a module.
Use the module in an environment that is within the general specifications.
Use the module in an enclosure rated IP54 (IEC60529) or higher.
Use DIN rail that is 35 mm (1.38 in.) wide to mount the module in
the control panel.
Always use an end plate on each end of the module to secure it.
Place other heat sources an appropriate distance away from the
module to maintain ambient temperatures around the module below specified maximums.
A 1791ES module can be installed either horizontally or vertically.
34 Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013
Figure 14 - Required Spacing
Wiring D uct
15 mm (0.6 in.) Min
35 mm (1.38 in.) DIN Rail
Use horizontal or vertical mounting.
End Plate
Wiring Duc t
15 mm (0.6 in.) Min
44407
End Plate
Install and Connect Your Modules Chapter 3
Use DIN rail that is 35 mm (1.38 in.) wide to install the module in the control panel. See the figure that shows required spacing.

Connect the Ethernet Cable

See the Ethernet Design Considerations Reference Manual, publication
ENET-RM002
, for information about Ethernet cable.

Set Network (IP) Address

The module ships with the rotary switches set to 999 and DHCP enabled.
Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013 35
Chapter 3 Install and Connect Your Modules
4
2
6
8
0
X100
X1
X10
4
2
6
8
0
4
2
6
8
0
This example shows the switches set at 163 with a network address being 192.168.1.163.
IMPORTANT
To set the network address, you can:
adjust the switches on the front of the module.
use a Dynamic Host Configuration Protocol (DHCP) server, such as
Rockwell Automation BootP/DHCP Server Utility.
retrieve the IP address from nonvolatile memory.
The module reads the switches first to determine if the switches are set to a valid number. You set the network address by adjusting the three switches on the front of the module. Use a small-blade screwdriver to rotate the switches. Line up the small notch on the switch with the number setting you wish to use. Valid settings range from 001…254.
When the switches are set to a valid number, the module’s IP address is
192.168.1.xxx (where xxx represents the number set on the switches). The module’s subnet mask is 255.255.255.0 and the gateway address is set to 0.0.0.0. When the module is reading the network address set on the switches, the module does not have a host name assigned to it or use any Domain Name System.
If the switches are set to an invalid number (such as 000 or a value greater than
254), the module checks to see if DHCP is enabled. If DHCP is enabled, the module asks for an address from a DHCP server. The DHCP server also assigns other transport control protocol (TCP) parameters.

Connect I/O Power and I/O Cables

If DHCP is not enabled, the module uses the IP address (along with other TCP configurable parameters) stored in nonvolatile memory.
Figure 15 - Example Network Address
See installation instructions for specifications on wire type and size.
Note that I/O connectors are detachable.
Tighten the screws on the I/O connector to the specified torque settings
as shown in the installation instructions.
Because the I/O connector has a structure that helps prevent incorrect wiring, make connections at the specified locations corresponding to the terminal numbers.
36 Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013
Wiring Examples
I0 I1 T0 T1
44275
I0 I1 T0 T1
44276
24V DC
Top ic Pa ge
Examples of Wiring 39
Read this chapter for information about wiring and safety categories. See the tables that show input device connection methods and their safety categories.
Table 4 - Input Device Connection Methods and Safety Categories
Connected Device Test Pulse from
Tes t Ou tpu t
Reset Switch No Connect the switch
Connection Schematic Diagram Safety
between I0 and T0. T0 must be configured as 24V power supply.
Chapter 4
Category
N/A
Connect the switch between 24V DC and I0
Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013 37
N/A
Chapter 4 Wiring Example s
I0 I1 T0 T1
44277
I0 I1 T0 T1
44278
I0 I1 T0 T1
24V DC
44279
OSSD2
OSSD1
44280
Table 4 - Input Device Connection Methods and Safety Categories (continued)
Connected Device Test Pulse from
Tes t Ou tpu t
Emergency stop switch
Yes Connect the switches
Door monitor
Connection Schematic Diagram Safety
between I0 and T0, and I1 and T1
Category
4
No Connect the switches
between T0 and I0 and I1, noting that T0 is configured for 24V power supply.
Connect the switches between 24V DC and I0 and I1.
Light Curtain Yes Connect the OSSD1 and
OSSD2 to I0 and I1, respec tively. Connect the 24V power supply commons.
3
3 or 4 based on light curtain being used
In - I0I1T0T1
38 Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013
24V DC COM
OSSD1
OSSD2
Wiring E xample s Chapter 4
In + In -
FE I0 I1 T0 T1 I2 I3 T2 T3M
S2
PS1
S1
44281
PS1: User 24V DC power supply S1: Emergency Stop Switch
(Positive Opening Mechanism)

Examples of Wiring

Read this section for examples of wiring by application. See catalog number details for appropriate module.
Figure 16 - Emergency Stop Switch Dual-channel Inputs with Manual Reset
Controller Configuration Parameter Name Configuration Setting
Safety Input 0 Safety Input 0 Channel Mode Test Pulse from Test Output
Safety Input 0 Test Source Test Output 0
Dual-channel Safety Input 0/1 Mode Dual-channel Equivalent
Dual-channel Safety Input 0/1 Discrepancy Time 100 ms (application dependent)
Safety Input 1 Safety Input 1 Channel Mode Test Pulse from Test Output
Safety Input 1 Test Source Test Output 1
Safety Input 2 Safety Input 2 Channel Mode Used as standard input
Safety Input 2 Test Source Not Used
Dual-channel Safety Input 2/3 Mode Single Channel
Test Output 0 Test Output 0 Mode Pulse Test Output
Test Output 1 Test Output 1 Mode Pulse Test Output
Test Output 2 Test Output 2 Mode Power Supply Output
This example shows wiring and controller configuration when using the Guard I/O module. If used in combination with the programs in a safety controller, this wiring is Safety Category 4 in accordance with EN 954-1 wiring requirements.
Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013 39
Chapter 4 Wiring Example s
Figure 17 - Two-hand Monitor
S11
I0 I2
FE
I1 I3
T1
S12
IN+ IN- T0
T2
T1
T1 T3
-
+
E1
31803-M
Controller Configuration Parameter Name Configuration Setting
Safety Input 0 Safety Input 0 Channel Mode Test Pulse from Test Output
Safety Input 0 Test Source Test Output 0
Dual Channel Safety Input 0/1 Mode Dual Channel Complementary
Dual Channel Safety Input 0/1 Discrepancy Time 100 ms (application dependent)
Safety Input 1 Safety Input 1 Channel Mode Test Pulse from Test Output
Safety Input 1 Test Source Test Output 1
Safety Input 2 Safety Input 2 Channel Mode Test Pulse from Test Output
Safety Input 2 Test Source Test Output 0
Dual Channel Safety Input 2/3 Mode Dual Channel Complementary
Dual Channel Safety Input 2/3 Discrepancy Time 100 ms (application dependent)
Safety Input 3 Safety Input 3 Channel Mode Test Pulse from Test Output
Safety Input 3 Test Source Test Output 1
Test Output 0 Test Output 0 Mode Pulse Test Output
Test Output 1 Test Output 1 Mode Pulse Test Output
This example shows wiring and controller configuration when using the Guard I/O module. If used in combination with the programs of a safety controller, the wiring is Category 4 in accordance with EN 954-1 wiring requirements.
40 Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013
Figure 18 - Mode Select Switch
In + In -
T3M
PS1
FE I0 I1 T0 T1 I2 I3 T2 T7MI4 I5 T4 T5 I6 I7 T6
S1
S2
S3
S4
S5
44283
PS1: User 24V DC power supply S1-S5: Switch
Wiring E xample s Chapter 4
Controller Configuration Parameter Name Configuration Setting
Safety Input 0 Safety Input 0 Channel Mode Safety Input
Safety Input 1 Safety Input 1 Channel Mode Safety Input
Safety Input 2 Safety Input 2 Channel Mode Safety Input
Safety Input 3 Safety Input 3 Channel Mode Safety Input
Safety Input 4 Safety Input 4 Channel Mode Safety Input
Safety Input 0 Test Source None
Dual Channel Safety Input 0/1 Mode Single Channel
Safety Input 1 Test Source None
Safety Input 2 Test Source None
Dual Channel Safety Input 2/3 Mode Single Channel
Safety Input 3 Test Source None
Safety Input 4 Test Source None
Dual Channel Safety Input 4/5 Mode Single Channel
Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013 41
Chapter 4 Wiring Example s
In + In -
FE I0 I1 T0 T1 I2 I3 T2 T3M
PS1
L1
44284
PS1: User 24V DC power supply L1: External Muting Lamp
Figure 19 - Muting Lamp Output
Controller Configuration Parameter Name Configuration Setting
Test Output 3 Test Output 3 Mode Muting Lamp Output
42 Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013
Figure 20 - Limit Switch Dual-channel Inputs and a Manual Reset
44285
PS1: User 24V DC power supply S!: Safety Limit Switch
(Positive Opening Mechanism)
S2: Safety Limited Switch
Close
Safety Guard
PS1
In + In -
FE I0 I1 T0 T1 I2 I3 T2 T3M
S1
(N.C.)
Wiring E xample s Chapter 4
S2
(N.O.)
Controller Configuration Parameter Name Configuration Setting
Safety Input 0 Safety Input 0 Channel Mode Test Pulse from Test Output
Safety Input 0 Test Source Test Output 0
Dual-channel Safety Input 0/1 Mode Dual-channel Equivalent
Dual-channel Safety Input 0/1 Discrepancy Time 1000 ms (application dependent)
Safety Input 1 Safety Input 1 Channel Mode Test Pulse from Test Output
Safety Input 1 Test Source Test Output 1
Safety Input 2 Safety Input 2 Channel Mode Used as Standard Input
Safety Input 2 Test Source Not Used
Dual-channel Safety Input 2/3 Mode Single Channel
Test Output 0 Test Output 0 Mode Pulse Test Output
Test Output 1 Test Output 1 Mode Pulse Test Output
Test Output 2 Test Output 2 Mode Power Supply Output
S3
This example shows wiring and controller configuration when using the Guard I/O module with limit switch dual-channel inputs and a manual reset. If used in combination with the programs of a safety controller, the wiring is Category 4 in accordance with EN 954-1 wiring requirements.
Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013 43
Chapter 4 Wiring Example s
Controller Configuration Parameter Name Configuration Setting
Safety Input 1 Safety Input 1 Channel Mode Standard Input
Safety Input 1 Test Source None
Dual-channel Safety Input 0/1 Mode Single Channel
Test Pulse 0 Test Output 0 Mode 1 Standard Output
44287
PS1: User 24V DC power supply L1: Lamp S1: Switch
Figure 21 - Guard I/O module with limit switch dual-channel inputs and a manual reset
S1
PS1
In + In -
FE I0 I1 T0 T1 I2 I3 T2 T3M
L1
44 Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013
Figure 22 - Dual-load Bipolar Outputs
IMPORTANT
In + In -
FE I0 I1 T0 T1 I2 I3 T2 T3M
PS1
FE
O0
P
O1
M
L- S+
O2
P
O3
M
L- S+
Out+Out
-
PS2
K2
K1
K1
K2
M
k2K1
44288
PS1, PS2: User 24V DC power supply (A single power supply can be used for both input and output power)
In order for the bipolar safety outputs to work correctly, you must connect the devices that are being controlled as shown in this figure. Connection of devices directly to 24V DC, 0V DC, or Ground is strictly prohibited.
Wiring E xample s Chapter 4
Controller Configuration Parameter Name Configuration Setting
Safety Input 0 Safety Input 0 Channel Mode Test Pulse from Test Output
Safety Input 0 Test Source Test Output 0
Dual-channel Safety Input 0/1 Mode Single Channel
Test Output 0 Test Output 0 Mode Pulse Test Output
Safety Output 0 Safety Output 0 Channel Mode Safety Pulse Test
Safety Output 1 Safety Output 1 Channel Mode Safety Pulse Test
The example shows wiring and configuration when using the Guard I/O module with solid state outputs in Dual-channel mode.
Note that all safety outputs of this Guard I/O module are permanently configured for use as Dual-channel mode only. When used in combination with the programs of the safety controller, this circuit configuration is Safety Category 4 in accordance with EN 954-1 requirements.
Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013 45
Chapter 4 Wiring Example s
Notes:
46 Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013
Chapter 5
Configure the I/O Modules by Using the Logix Designer Application
Top ic Pa ge
Use Help 47
Add Modules to the I/O Configuration Tree 47
Use the Module Properties and General Dialogs 49
Work with the Safety Dialog 60
Work with the Input Configuration Dialog 62
Work with Test Output Configuration Dialog 62
Work with the Output Configuration Dialog 63
Save and Download the Module Configuration 65

Use Help

Add Modules to the I/O Configuration Tree

At the bottom of a dialog box, choose Help for information about how to complete entries in the dialog box. At the bottom of a warning dialog box, choose Help to get information about that specific error.
To add a module to the I/O configuration tree, follow these guidelines.
Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013 47
Chapter 5 Configure the I/O Modules by Using the Logix Designer Application
1. From the I/O Configuration tree, right-click the EtherNet Bridge module, as shown in the figure, and choose New Module.
The Select Module dialog box is displayed with a list that includes Safety.
48 Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013
Configure the I/O Modules by Using the Logix Designer Application Chapter 5
A list of safety modules appears here.
2. From the Select Module dialog box, choose the + next to Safety to see a list of safety modules

Use the Module Properties and General Dialogs

3. From the Select Module dialog box, choose the appropriate module, such as 1791ES-IB16, and OK at the bottom of the dialog box.
To use the Module Properties and General dialogs to configure a module, follow these guidelines.
1. From the I/O configuration tree, double-click the module, such as the 1791ES-IB8XOBV4 module, to see the Module Properties dialog box.
2. From the Module Properties dialog box, complete entries for the General dialog box.
a. For Name, type a unique name. b. For IP Address, enter the IP address of the Guard I/O module.
Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013 49
Chapter 5 Configure the I/O Modules by Using the Logix Designer Application
c. For Description, if desired, type a description.
For a detailed explanation of the safety network number (SNN), see the GuardLogix Controller Systems Safety Reference Manual listed in the Additional Resources on page 7 default provided by the Logix Designer application.
d. Click Change to see the Module Definition dialog box.
, noting that in most cases, you use the
e. From the Module Definition dialog box, select values to configure what
data and status tags to generate implicitly for the safety module, noting that you can configure Input Data, Input Status, and Output Data.

Input Data Options

Choose from these options:
Safety - Selecting Safety creates these tags for the target module:
RunMode: Module modeConnectionFaulted: Communication statusSafety Data: Safety inputs from module
50 Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013
Configure the I/O Modules by Using the Logix Designer Application Chapter 5
IMPORTANT
Safety-Readback - This selection is not available for input-only safety modules. Selecting Safety-Readback creates both safety and readback tags, with readback indicating the presence of 24V on the output terminal.

Input Status Options

Choose from these options.
Status data is not SIL 3 data. Do not use status data to directly control a SIL 3 safety output.
None - No status tags, only data for the inputs
Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013 51
Chapter 5 Configure the I/O Modules by Using the Logix Designer Application
Point Status-Muting - A muting status tag for test output T3/T7 with point status for each input and output point
Combined Status-Muting A single BOOL tag represents an AND of the status bits for all the
input points. For example, if any input channel has a fault, this bit goes
(1)
LO.
– A single BOOL tag represents an AND of the status bits for all the
output points.
(1)
– A muting status tag for test output T3/T7
(1) When using combined status, use explicit messaging to read individual point status for diagnostic purposes.
52 Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013
Configure the I/O Modules by Using the Logix Designer Application Chapter 5
IMPORTANT
.

Output Data Options

Choose from these options.
The standard outputs on the module must not be used for safety purposes.
None - Selecting None results in an input only connection to the module. Inputs and status are read, but no outputs are written.
Safety - Selecting Safety creates these safety tags and enables these outputs for use in the safety task.
Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013 53
Chapter 5 Configure the I/O Modules by Using the Logix Designer Application
Test - Selecting Test creates these tags and enables the test outputs on the module. These outputs are standard outputs and must not be used for safety purposes.
Combined - Selecting Combined creates these tags and enables all module outputs - safety and test.
54 Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013

Values and States of Tags

IMPORTANT
This table shows the values and states of the tags.
Table 5 - Values and States of Tags
Data Description
Input data Safety Input Data
SAFETY
Combined S afety In put Status SAFETY
Individual Safety Input Status SAFETY
Combined Safety Output Status SAFETY
Individual Safety O utput Status SAFETY
Muting Lamp Status SAFETY
Output Readback STANDARD
Individual Test Output Status STANDARD
Indicates the ON/OFF status of each input circuit.
· ON: 1 OFF: 0
An AND of the status of all input circuits.
· All circuits are normal: 1
· An error was detected in one or more input circuits: 0
Indicates the status of each input circuit.
· Normal: 1 Fault (Alarm): 0
An AND of the status of all safety output circuits.
· All circuits are normal: 1
· An error has been detected in one or more output circuits: 0
Indicates the status of each safety output circuit.
· Normal: 1 Fault (Alarm): 0
Indicates the status when circuit T3 is configured as the muting lamp output.
· Normal: 1 Fault (Alarm): 0
Monitors the presence of 24V on the output circuit. Readback is ON (1) if 24V is on output terminal.
· ON: 1 OFF: 0
Indicates the status of each of the test output circuits.
· Normal: 1 Fault (Alarm): 0
Configure the I/O Modules by Using the Logix Designer Application Chapter 5
Output data Safety Output Data
SAFETY
Standard Output Data STANDARD
Controls the safety output.
ON: 1 OFF: 0
Controls the test output when Test Output mode is set to a standard output.
ON: 1 OFF: 0
Safety denotes information the controller can use in safety-related functions. Standard denotes additional information that must not be relied on for safety functions.
Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013 55
Chapter 5 Configure the I/O Modules by Using the Logix Designer Application

Work with the Safety Dialog

Read this for information about how to complete entries when you choose the Safety tab.
1. From the Module Properties dialog box, choose the Safety tab to see the Safety dialog box.
2. Configure Requested Packet Interval (RPI) and Configure Connection Reaction Time Limit (CRTL) by following step 3.
56 Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013
Configure the I/O Modules by Using the Logix Designer Application Chapter 5
IMPORTANT
We suggest that you keep the Time-out Multiplier and Network Delay Multiplier at their default values of 2 and 200.
See GuardLogix Controllers User Manual, listed in the Additional
Resources on page 7, for more
information about the CRTL.
3. From the Safety dialog box, choose Advanced to see the Advanced Connection Reaction Time Limit Configuration dialog box.
Make sure that input RPI is set to match the need. The smallest input RPI allowed is 6 ms. Selecting small RPI's consumes network bandwidth and can cause nuisance trips because other devices can't get access to the network.
As an example, a safety input module with only ESTOP switches connected to it generally can work well with settings of 50…100 ms. An input module with a light curtain guarding a hazard can need the fastest response that is possible.
Selecting appropriate RPI's will result in a system with maximum (best) performance.
Analyze each safety channel to determine what is appropriate. The default timeout multiplier of 2 and network delay multiplier of 200 will create an input connection reaction time limit of four times the RPI and an output connection reaction limit of three times the RPI. Changes to these parameters must be approved by a safety administrator.
Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013 57
Chapter 5 Configure the I/O Modules by Using the Logix Designer Application
Connect ion Faul ted
A connection status tag exists for every connection.
If the RPI and CRTL for the network are set appropriately, then this status tag must always remain HI. Monitor all connection status bits to verify that they are not going LO intermittently due to timeouts.

Configuration Ownership - Reset Ownership

The connection between the owner and the Guard I/O module is based on the following:
Guard I/O EtherNet IP address
Guard I/O safety network number
GuardLogix slot number
GuardLogix safety network number
Path from GuardLogix controller to Guard I/O module
Configuration signature
If any of these change, the connection between the GuardLogix controller and the Guard I/O module is lost, and the yellow yield in the project tree appears. Reset ownership to reestablish the connection by using this procedure.
1. Open the safety I/O module properties.
2. Choose the Safety tab.
3. From the dialog box, choose Reset ownership.
58 Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013
Configure the I/O Modules by Using the Logix Designer Application Chapter 5

Configuration Signature

The configuration signature is created by the Logix Designer application and verified by the safety module. The configuration signature provides SIL 3 integrity of the configuration of a Guard I/O module.
When a GuardLogix controller first connects to an unconfigured Guard I/ O module, the complete configuration is downloaded to the I/O module.
Any time the GuardLogix controller attempts to connect to a Guard I/O module, if the configuration signatures are the same, then the configuration does not need to be downloaded, because they already match.
Any time the GuardLogix controller attempts to connect to a Guard I/O module and the signatures do not match, the module checks the IP address and safety network number. If these are all correct, the controller will attempt to configure the module.
Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013 59
Chapter 5 Configure the I/O Modules by Using the Logix Designer Application

Work with the Input Configuration Dialog

See the table that shows typical safety input parameters, referring to Chapter 2 for related information.
Table 6 - Typical Safety Input Parameters
Parameter Name Value Description
Input Point Operation Type Single Channel Inputs are treated as single channel.
Dual-channel Equivalent Inputs are treated as a dual-channel pair. The channels must match (be equal) within the discrepancy
Dual-channel Complementary Inputs are treated as a dual-channel pair. The channels must disagree (be opposite) within the
Input Point Mode Not Used The input is disabled. It remains logic 0 if 24V is applied to the input terminal.
Safety Test Pulse Pulse testing is performed on this input circuit. A test source on the 1791ES module must be used as
Safety A safety input is connected but there is no requirement for the 1791ES module to perform a pulse test
Standard A standard device, such as a reset switch, is connected. This point cannot be used in dual channel
Safety Input Test Source None If pulse testing is being performed on an input point, then the test source that is sourcing the 24V for
Tes t Out pu t 0
Tes t Out pu t 1
Tes t Out pu t 2
Tes t Out pu t 3
Test Output 4…15
Input Delay Time Off -> On
Input Delay Time On -> Off
Safety Input Error Latch Time 0…65,530 ms (in increments
(1) There are eight test outputs on 1791ES-IB8XOBV4 modules.
0…126 ms (in increments of 6ms)
0…126 ms (in increments of 6ms)
of 10 ms)
(1)
time or a fault is generated.
discrepancy time or a fault is generated.
the 24V source for this circuit. The test source is configured by using the test source pulldown. The pulse test will detec t shorts to 24V and channel-to -channel shorts to other inputs.
on this c ircuit. An example is a safety device that performs its own pulse tests on the input wires, such as a light curtain.
operation.
the input circuit must be selected. If the incorrect test source is entered, the result is pulse test failures on that input circuit.
Filter time is for OFF to ON transition. Input must be high after input delay has elapsed before it is set logic 1.
Filter time is ON to OFF transition. Input must be low after input delay has elapsed before it is set logic
0.
Default is 1000 ms. The purpose for latching input errors is to make sure that intermittent faults that can only exist for a few milliseconds are latched long enough to be read by the controller. The amount of time to latch the error must be based on the RPI, the safety task watchdog, and other application­specific variables.
60 Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013
Configure the I/O Modules by Using the Logix Designer Application Chapter 5
Follow this procedure to complete entries from the Input Configuration dialog box that you see when, from the top of the Module Properties dialog box, choose Input Configuration.
1. For Point Operation Type, choose one of these values and a value for Discrepancy Time if set to Equivalent or Complementary:
Single
Inputs are treated as single channels. Note that in many cases, dual­channel safety inputs are configured as two individual single channels. This does not affect pulse testing because it is handled on an individual channel basis.
(1)
Equivalent
Inputs are treated as a dual-channel pair. The channels must match within the discrepancy time or an error is generated.
Complementary
(1)
Inputs are treated as a dual-channel pair. They must be in opposite states within the discrepancy time or an error is generated.
(1) Be aware that configuring discrepancy time on safety I/O modules masks input inconsistent faults from the GuardLogix safety
instructions. Status can be read by GuardLogix to obtain this fault information.
Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013 61
Chapter 5 Configure the I/O Modules by Using the Logix Designer Application
2. For Point Mode, choose one of these values for each point, referring to the Safety Input Parameters table for additional information:
Not Used - Safety input channel is disabled
Safety Pulse Test - Safety input is configured for pulse test operation
Safety - The safety input is used with a safety field device
Standard - Safety input has a standard field device wired to it
3. Complete entries, noting the following:
For each safety input on the module, you can define if the input will be
pulse tested. If the inputs is pulse tested, select which test source to use.
Off -> On and On -> Off delay times can be configured per channel
with each channel specifically tuned to match the characteristics of the field device for maximum performance.
Input Error Latch Time is the time the module holds an error to make
sure the controller can detect it. This provides you more reliable diagnostics and enhances the chances that a nuisance error is detected.
4. Click OK at the bottom of the dialog box or a tab at the top of the dialog box.

Work with Test Output Configuration Dialog

Table 7 - Configuring Test Outputs
Parameter Name Value Description Default
Test Output Mode Not Used The test output is disabled. Not Used
Standard The output point is enabled for use by the GuardLogix controller.
Pulse Test The test output is being used as a pulse test source.
Power Supply A constant 24V is placed on the output terminal. It can be used to provide power to a field device.
Muting Lamp Output (Terminal T3/T7 only)
Read this for information about how to work with the Test Output Configuration dialog box, referring to the table that provides information on configuring test outputs.
An indicator lamp is connected to the output. Whe n this lamp is energized, a burned-out bulb, broken wire, or short to GND error condition can be detected. Typically, the lamp is an indicator used in light curtain applications.
62 Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013
Configure the I/O Modules by Using the Logix Designer Application Chapter 5
Complete entries on the Test Output dialog box, referring to the figure.

Work with the Output Configuration Dialog

Read this for a guideline on how to configure safety outputs by using the information in the table and completing the entries referring to the figure.
Table 8 - Guidelines for Configuring Safety Outputs
Parameter Name Value Description Default
Point Operation Type Dual The 1791ES module treats the outputs as a pair. It always sets them HI to LO as a matched pair.
Point Mode Not Used The output is disabled. Not Used
Safety The output point is enabled, and it does not perform a pulse test on the output.
Safety Pulse Test The output point is enabled and performs a pulse test on the output.
Output Error Latch Time
0…65,530 ms (in increments of 10 ms)
Safety logic must set both of these outputs ON or OFF at the same time or the module will declare a channel fault.
When the output is energized, the output pulses LO briefly. The pulse test detects if 24V remains on the output terminal during t his LO pulse due to a short to 24V or if the output is shorted to another output te rminal.
The purpose for latching output errors is to make sure that intermittent faults that can only exist for a few milliseconds are latched long enough to be read by the controller. The amount of time to latch the errors is based on the RPI, the safety task watchdog, and other application-specific variables.
Dual-channel
1000 ms
Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013 63
Chapter 5 Configure the I/O Modules by Using the Logix Designer Application
Follow this procedure to complete entries from the Output Configuration dialog box.
1. For Point Operation, all safety outputs are Dual mode only.
The Guard I/O module always sets them high or low as a pair.
You must always match the two outputs as a pair in software as well.
2. For Point Mode, select Not Used, Safety, or Safety Pulse Test, referring to
the Safety Output Parameters table for additional information.
3. Select a value for Output Error Latch Time. Output Error Latch Time is the time the module holds an error to make sure the controller can detect it. This provides you more reliable diagnostics and enhances the changes that a nuisance error is detected.
4. Click Apply from the bottom of the dialog box.
64 Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013
Configure the I/O Modules by Using the Logix Designer Application Chapter 5

Save and Download the Module Configuration

We recommend that after a module is configured you save your work.
If after downloading the program the MS and NS LED indicators on the Guard I/O module are not both solid green, this can be due to loss of ownership. The ownership is based on the following:
Guard I/O EtherNet IP address
Guard I/O safety network number
GuardLogix slot number
GuardLogix safety network number
Path from GuardLogix controller to Guard I/O module
Configuration signature
If any of these change, the connection between the GuardLogix controller and the Guard I/O module is lost, and the yellow yield in the project tree appears. Reset ownership to reestablish the connection by using this procedure.
1. Open the safety I/O module properties.
2. Choose the Safety tab.
3. From the dialog box, choose Reset ownership.
Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013 65
Chapter 5 Configure the I/O Modules by Using the Logix Designer Application
Notes:
66 Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013
Interpret Module Indicators
24V DC Input Power Indicator
Module Status Indicator
Configuration Lock Indicator
24V DC Output Power Indicator (1791ES-IB8XOBV4 modules only)
I0…I15 - Safety Input Status Indicator T0…T15 - Test Output Status indicator 00…07 - Safety Output Status Indicator (1791ES-IB8XOBV4 module)
Network Status Indicator
Network Activity Indicator
Top ic Pa ge
Module Indicators 67
Configuration Lock Indicator 69
Chapter 6

Module Indicators

See the figure and tables for information on how to interpret LED module indicators.
Figure 23 - Module Indicators
Table 9 - 24V DC Input Power Indicator
State Status Description Recommended Action
Off No power No power is applied. Apply power to this section.
Solid green Normal operation The applied voltage is within specifications. None.
Solid yellow Input power out of specification The input power is out of specification. Check your connectors, wiring, and voltages.
Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013 67
Chapter 6 Interpret Module Indicators
Table 10 - 24V DC Output Power Indicator
State Status Description Recommended Action
Off No power No power is applied. Apply power to this section.
Solid green Normal operation The applied voltage is within specifications. None.
Solid yellow Output power out of specification The output power is out of specification. Check your connectors, wiring, and voltages.
Table 11 - Module Status Indicator
State Status Description Recommended Action
Off No power No power is applied to the power connector. Apply power to this connector.
Solid green Normal operation The module is operating normally. None.
Solid red Unrecoverable fault The module detected an unrecoverable fault. Cycle power to the module. If problem persists,
Flashing red and green
Flashing green Idle Idle, waiting for connection from scanner. Establish connection.
Flashing red Recoverable fault The module has detected a recoverable fault. Cycle power to the module or reset the module.
Module is unconfigured Module needs commissioning due to missing, incomplete, or
incorrect configuration.
Device in self test The module is performing its power-cycle diagnostic tests. Wait for the module to complete its power-cycle
User-initiated firmware update in progress User-initiated firmware update is in progress. Wait for firmware update to complete.
replace the module.
Reconfigure the module. For additional information, inspect Network Status indicator.
diagnostics.
Table 12 - Network Status Indicator
State Status Description Recommended Action
Off Module not online The module does not have an IP address. Verify your network is working properly.
Flashing green Module online with no connections in
Solid green Module online with connections in
Flashing red One or more I/O connections in timed-out
Solid red Critical link failure The module detected an error that prevents it from communicating on the
Flashing red and green
established state
established state
state
User-initiated firmware update User-initiated firmware update is in progress. Wait for firmware update to complete.
Self test The module is performing its power-cycle diagnostic test. Wait for the module to complete its power-
The module has acquired an IP address, but no connections are established. Verify your network and module
The module is operating normally. None.
The module detected a recoverable network fault. Verify your network and module
network, such as duplicate IP address has been detected.
configuration.
configuration.
Cycle power to the module. Check network IP addressing.
cycle diagnostics.
68 Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013
Interpret Module Indicators Chapter 6
Table 13 - Network Activity Indicator
State Status Recommended Action
Off No link established Establish link.
Flashing Green Transmit or receive activity None.
Steady Green Link established None.
Table 14 - Safety Input Status Indicator
State Status Description Recommended Action
Off Safety input off The safety input is off or the channel is configured for not used. Turn the safety input on or reconfigure the
Solid yellow Safety input on The safety input is on. None.
Solid red Fault detected A fault in the external wiring or input circuit detected. Check configuration, field wiring, and devices. If no
Flashing red Partner fault detected A fault in the partner input circuit of a dual-input configuration
detected.
channel, if desired.
problem found, replace module.
Check the field wiring and verify your configuration for the partner circuit. If no problem found, replace module.
Table 15 - Test Output Status Indicator
State Status Description Recommended Action
Off Test output off The test output is off or the channel is configured for not used. Turn the test output on or reconfigure the channel, if
Solid yellow Output on Output is on. None.
Solid red Fault detected A fault in the external wiring or input circuit detected. Check field wiring. If no problem found, replace
desired.
module. For outputs configured for muting could indicate undercurrent or burned-out lamp.
Table 16 - Safety Output Status Indicator (1791ES-IB8XOBV4 only)
State Status Description Recommended Action
Off Safety output off The safety output is off or the channel is configured for not used. Turn the safety output on or reconfigure the channel, if
Solid yellow Safety output on The safety output is on. None.
Solid red Fault detected A fault in the output circuit was detected. Check the circuit wiring and end device. If no problem
Both tags in a dual channel circuit do not have the same value. Make sure logic is driving tag values to the same state
Flashing red Partner fault detected A fault in the partner output circuit of a dual output configuration

Configuration Lock Indicator

was detected.
Configuration lock indicator is not supported by the Logix Designer application.
desired.
found, replace module.
(off or on).
Check the circuit wiring and end device of t he partner. If no problem found, replace module.
Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013 69
Chapter 6 Interpret Module Indicators
Notes:
70 Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013
Appendix A
Get Diagnostic Status from Modules by Using Explicit Messaging
Top ic Pa ge
Work with 1791ES-IB8XOBV4 Modules 72
Work with 1791ES-IB16 Modules 77
I/O Data Supported by Each Module 81
I/O Assembly and Reference Data 83
Explicit Messages 88
This appendix provides information about how to use CIP Generic Message instructions (sometimes called explicit messaging ) to get diagnostic status information from the modules.
You can implicitly obtain individual point status of the Guard I/O module from the Module Definition dialog box by choosing Pt. Status from the Input Status pull-down menu.
Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013 71
Appendix A Get Diagnostic Status from Modules by Using Explicit Messaging
Another choice is to obtain overall status implicitly from the Module Definition di alo g box by choo sing Combined Status f rom the Input Status p ull-do wn menu.

Work with 1791ES-IB8XOBV4 Modules

If the Combined Status changes, use explicit messaging to obtain the point level status.
To work with 1791ES-IB8XOBV4 modules, follow this procedure.
1. In the Module Definition dialog box, from the Input Status pull-down menu, choose Combined Status.
72 Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013
Get Diagnostic Status from Modules by Using Explicit Messaging Appendix A
This creates a two-byte input assembly, as shown for the 1791ES­IB8XOBV4 module.
2. Use the CombinedInputStatus and CombinedOutputStatus bits to detect if one or more of the I/O points on the module have a fault.
If any input or output status bit goes to a value of 0 (0=error, 1=no
error), use the InputStatus and OutputStatus bits to condition your msg rungs as follows.
Note that the second rung can be used to read the status on mode
transition and once a fault is detected, continue reading until the fault is corrected.
Place these rungs in the standard task.
Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013 73
Appendix A Get Diagnostic Status from Modules by Using Explicit Messaging
Reference the figures below that show the MSG instruction parameters for reading Instance 852 from the 1791ES-IB8XOBV4 module.
354 (852) 1791ES-
IB8XOBV4
Safety and Standard
Instance 852 (354 Hex) is 5 bytes in length, so the Destination Tag MSGdata must be at least 5 bytes in length to hold this data. The size is DINT[2] or 8 bytes.
See the figure that shows the layout of Instance 852 (354 Hex).
0 Safet y Input
7
1Safety Input
7 S t a t u s
2Safety
Output 7 Status
3Safety
Output 7 Monitor
4 Reser ved Reserved Input
Safety Input 6Safety
Safety Input 6 Status
Safety Output 6 Status
Safety Output 6 Monitor
Input 5
Safety Input 5 Status
Safety Output 5 Status
Safety Output 5 Monitor
Power Error
(1)
Safety Input 4Safety
Safety Input 4 Status
Safety Output 4 Status
Safety Output 4 Monitor
Output Power
(1)
Error
Input 3
Safety Input 3 Status
Safety Output 3 Status
Safety Output 3 Monitor
Reserved Reser ved Muting
Safety Input 2Safety
Safety Input 2 Status
Safety Output 2 Status
Safety Output 2 Monitor
Input 1
Safety Input 1 Status
Safety Output 1 Status
Safety Output 1 Monitor
Lamp 7 Status
Safety Input 0
Safety Input 0 Status
Safety Output 0 Status
Safety Output 0 Monitor
Muting Lamp 3 Status
74 Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013
Get Diagnostic Status from Modules by Using Explicit Messaging Appendix A
From the top of the Message Configuration dialog box, choose the Communication tab. This dialog box requires the path to the module. Click Browse to browse to the module that the MSG will read.
From the top of the Message Configuration dialog box, choose Tag to see this dialog box.
Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013 75
Appendix A Get Diagnostic Status from Modules by Using Explicit Messaging
When the explicit message reads the data from the 1791ES-IB8XOBV4 module, the data appears in the MSGdata tags as shown.
The first 32 bits of the instance are in MSGdata[0].0…31, and the final 8 bits are in MSGdata[1].0…7. These 40 bits must be mapped according to Instance 852. An easy method to do this mapping is to create a user defined tag (UDT) for Instance 852. Once complete, it appears as follows.
76 Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013
Get Diagnostic Status from Modules by Using Explicit Messaging Appendix A

Work with 1791ES-IB16 Modules

To work with 1791ES-IB16 modules, follow this procedure.
1. In the Module Definition dialog box, from the Input Status pull-down menu, choose Combined Status.
This creates a three-byte input assembly, as shown, for the 1791ES-IB16 module.
Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013 77
Appendix A Get Diagnostic Status from Modules by Using Explicit Messaging
2. Use the CombinedInputStatus bit to detect if one or more of the I/O points on the module have a fault.
If any input status bits go to a value of 0 (0 = bad; 1 = good), use an
explicit message to determine which individual data points have faulted.
Note that you can use the second rung to read the status on mode
transition and once a fault is detected, continue reading until the fault is corrected.
Place these rungs in the standard task.
See the figures that show the MSG instruction parameters for reading Instance 869 from the 1791ES-IB16 module. See Appendix
C of this
manual for a layout of possible instances.
Instance 869 (365 Hex) is 7 bytes in length, so the Destination Tag IB16MSGdata must be at least 7 bytes in length to hold this data. The size is DINT[2] or 8 bytes.
78 Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013
Get Diagnostic Status from Modules by Using Explicit Messaging Appendix A
The layout of Instance 869 (365 Hex) is as follows.
365 1791ES-
IB16
Safety and Standard
0Safety Input 7Safety Input 6Safety
1Safety Input 15Safety Input 14Safety
2Safety Input
7 Status
3Safety Input
15 Status
4Safety
Output 7 Status
5Safety
Output 15 Status
6 Reserved Reserved Input
Safety Input 6 Status
Safety Input 14 Status
Safety Output 6 Status
Safety Output 14 Status
Input 5
Input 13
Safety Input 5 Status
Safety Input 13 Status
Safety Output 5 Status
Safety Output 13 Status
Power Err
or
From the top of the Message Configuration dialog box, choose the Communication tab. This dialog box requires the path to the module. Click Browse to browse to the module that the MSG will read.
Safety Input 4
Safety Input 12
Safety Input 4 Status
Safety Input 12 Status
Safety Output 4 Status
Safety Output 12 Status
Output Power
(1)
Error
Safety Input 3
Safety Input 11
Safety Input 3 Status
Safety Input 11 Status
Safety Output 3 Status
Safety Output 11 Status
Muting Lamp 15
(1)
Status
Safety Input 2
Safety Input 10
Safety Input 2 Status
Safety Input 10 Status
Safety Output 2 Status
Safety Output 10 Status
Muting Lamp 11 Status
Safety Input 1
Safety Input 9
Safety Input 1 Status
Safety Input 9 Status
Safety Output 1 Status
Safety Output 9 Status
Muting Lamp 7 Status
Safety Input 0
Safety Input 8
Safety Input 0 Status
Safety Input 8 Status
Safety Output 0 Status
Safety Output 8 Status
Muting Lamp 3 Status
Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013 79
Appendix A Get Diagnostic Status from Modules by Using Explicit Messaging
From the top of the Message Configuration dialog box, click Tag to see this dialog box.
When the explicit message reads the data from the 1791ES-IB16 module, the data appears in the MSGdata tags as shown.
80 Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013
Get Diagnostic Status from Modules by Using Explicit Messaging Appendix A
The first 32 bits of the instance are in IB16MSGdata[0].0…31, and the final 24 bits are in IB16MSGdata[1].0…23. Map these 56 bits according to Instance 869. An easy method to do this mapping is to create a user defined tag (UDT) for Instance 869. Once you complete this, it appears as follows.

I/O Data Supported by Each Module

See the table that shows a summary of default I/O data by module.
Table 17 -Default I/O Data
Safety Connection Assembly Instance (Hex)
1791ES-IB16 Safety 225 and 23
1791ES-IB8XOBV4 Safety 204 and 234
The tables show the I/O data supported by each module. Refer to I/O Assembly Data for data arrangements.
Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013 81
Appendix A Get Diagnostic Status from Modules by Using Explicit Messaging
For I/O data, safety connections for up to four items, including one output, can be allocated for the master unit. Also, standard connections for up to two items can be allocated for the master unit.
Table 18 - 1791ES-IB8XOBV4 Modules
Input Data Input Status Assembly Instance
Safety None 204
Safety - Readback Point Status - Muting 354
Output Data Assembly Instance
Safety 234
Tes t 2 2
Combined 2C4
None C7
(1) Default for output data.
(2) Default for input data.
(2)
Point Status - Muting 334
Combined Status - Muting 324
Point Status - Muting - Test Output 374
(1)
Table 19 - 1791ES-IB16 Modules
Input Data Input Status Assembly Instance
Safety None 205
Point Status - Muting 335
Point Status - Muting - Test Output 365
Combined Status - Muting 315
Point Status 225
Output Data Assembly Instance
Tes t 23
None C7
82 Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013
Get Diagnostic Status from Modules by Using Explicit Messaging Appendix A

I/O Assembly and Reference Data

See the tables for I/O assembly and reference data. The bits in the tag definitions of the Logix Designer application are different than those shown in the following section. The following defines the name associations for clarification with the programming software.
Table 20 - Bit Definitions and Logix Designer Tag Names
Bit Definitions Logix Designer Application Tag Name
Safety Input 0 Pt00Data
Safety Input 15 Pt15Data
Safety Input 0 Status Pt00InputStatus
Safety Input 15 Status Pt15InputStatus
Safety In Status InputStatus
Muting Lamp Status MutingStatus
Safety Output 0 Pt00Data
Safety Output 7 Pt07Data
Standard Output 0 Test00Data
Standard Output 15 Test15Data
Safety Output 0 Status Pt00OutputStatus
Safety Output 7 Status Pt07OutputStatus
Safety Out Status OutputStatus
Safety Output 0 Monitor Pt00Readback
Safety Output 7 Monitor Pt07Readback
Test Output 0 Status Pt00TestOutputStatus
Test Output 15 Status Pt15TestOutputStatus
Table 21 - Input Data
Instance Hex (Decimal)
204 (516) 1791ES-
205 (517) 1791ES-
224 (548) 1791ES-
Module Connection
IB8XOBV4
IB16
IB8XOBV4
Type
Safety and Standard
Safety and Standard
Safety and Standard
See these tables for reference data concerning input and output data.
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0Safety Input 7Safety Input 6Safety
0Safety Input 7Safety Input 6Safety
1Safety Input 15Safety Input 14Safety
0Safety Input 7Safety Input 6Safety
1Safety Input
7 Status
Safety Input 6 Status
Input 5
Input 5
Input 13
Input 5
Safety Input 5 Status
Safety Input 4Safety
Safety Input 4Safety
Safety Input 12Safety
Safety Input 4Safety
Safety Input 4 Status
Input 3
Input 3
Input 11
Input 3
Safety Input 3 Status
Safety Input 2Safety
Safety Input 2Safety
Safety Input 10Safety
Safety Input 2Safety
Safety Input 2 Status
Input 1
Input 1
Input 9
Input 1
Safety Input 1 Status
Safety Input 0
Safety Input 0
Safety Input 8
Safety Input 0
Safety Input 0 Status
Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013 83
Appendix A Get Diagnostic Status from Modules by Using Explicit Messaging
Table 21 - Input Data (continued)
Instance
Module Connection Hex (Decimal)
225 (549) 1791ES-
IB16
300 (768) 1791ES-
IB16
301 (769) 1791ES-
IB8XOBV4
315 (789) 1791ES-
IB16
324 (804) 1791ES-
IB8XOBV4
334 (820) 1791ES-
IB8XOBV4
335 (821) 1791ES-
IB16
Type
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Safety and Standard
0Safety Input 7Safety Input 6Safety
Input 5
1Safety Input 15Safety Input 14Safety
Input 13
2Safety Input
7 Status
3Safety Input
15 Status
Safety Input 6 Status
Safety Input 14 Status
Safety Input 5 Status
Safety Input 13 Status
Safety Input 4Safety
Input 3
Safety Input 12Safety
Input 11
Safety Input 4 Status
Safety Input 12 Status
Safety Input 3 Status
Safety Input 11 Status
Safety Input 2Safety
Input 1
Safety Input 10Safety
Input 9
Safety Input 2 Status
Safety Input 10 Status
Safety Input 1 Status
Safety Input 9 Status
Safety Input 0
Safety Input 8
Safety Input 0 Status
Safety Input 8 Status
Standard Only 0 Reserved Reserved Reserved Reser ved Reserved Reserved Reserved Input Power
Error
Standard Only 0 Reserved Reserved Reserved Reser ved Reserved Reserved Output
Power
Input Power Error
Error
Safety and Standard
Safety and Standard
Safety and Standard
Safety and Standard
0Safety Input
7
1Safety Input
15 Sta
tus
2Combined
Safety In Status
0Safety Input
7
1Combined
Safety In Status
0Safety Input
7
1Safety Input
7 Status
Safety Input 6Safety
Input 5
Safety Input 14 Status
Safety Input 13 Status
Reserved Input
Power Error
Safety Input 6Safety
Input 5
Combined Safety Out Status
Input Power Error
Safety Input 6Safety
Input 5
Safety Input 6 Status
Safety Input 5 Status
2 Reser ved Reserved Input
Power Error
0Safety Input 7Safety Input 6Safety
Input 5
1Safety Input 15Safety Input 14Safety
Input 13
2Safety Input
7 Status
3Safety Input
15 Status
Safety Input 6 Status
Safety Input 14 Status
Safety Input 5 Status
Safety Input 13 Status
4 Reser ved Reserved Input
Power Error
Safety Input 4Safety
Safety Input 12 Status
Reserved Muting
(1)
Safety Input 4Safety
Output Power
(1)
Error
Safety Input 4Safety
Safety Input 4 Status
Output Power
(1)
Error
Safety Input 4Safety
Safety Input 12Safety
Safety Input 4 Status
Safety Input 12 Status
Reserved Muting
(1)
Input 3
Safety Input 11 Status
Lamp 15 Status
Safety Input 10 Status
Muting Lamp 11 Status
Input 1
Safety Input 9 Status
Muting Lamp 7 Status
Safety Input 2Safety
Safety Input 2Safety
Input 3
Input 1
Reserved Reser ved Muting
(1)
Lamp 7 Status
Safety Input 2Safety
Input 3
Safety Input 3 Status
Safety Input 2 Status
Input 1
Safety Input 1 Status
Reserved Reser ved Muting
(1)
Lamp 7 Status
Safety Input 2Safety
Input 3
Input 1
Safety Input 10Safety
Input 11
Safety Input 3 Status
Safety Input 11 Status
Lamp 15 Status
Safety Input 2 Status
Safety Input 10 Status
Muting Lamp 11 Status
Input 9
Safety Input 1 Status
Safety Input 9 Status
Muting Lamp 7 Status
Safety Input 0
Safety Input 8 Status
Muting Lamp 3 Status
Safety Input 0
Muting Lamp 3 Status
Safety Input 0
Safety Input 0 Status
Muting Lamp 3 Status
Safety Input 0
Safety Input 8
Safety Input 0 Status
Safety Input 8 Status
Muting Lamp 3 Status
84 Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013
Table 21 - Input Data (continued)
Get Diagnostic Status from Modules by Using Explicit Messaging Appendix A
Instance
Module Connection Hex (Decimal)
344 (836) 1791ES-
IB8XOBV4
354 (852) 1791ES-
IB8XOBV4
364 (868) 1791ES-
IB8XOBV4
Type
Safety and Standard
Safety and Standard
Safety and Standard
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 Safet y Input
7
1Safety Input
7 St at us
2Safety
Output 7 Status
3 Reser ved Reserved Input
0 Safet y Input
7
1Safety Input
7 S t a t u s
2Safety
Output 7 Status
3Safety
Output 7 Monitor
4 Reser ved Reserved Input
0Safety Input
7 S t a t u s
1Safety
Output 7 Status
2 Test Output
7 Status
Safety Input 6Safety
Input 5
Safety Input 6 Status
Safety Output 6 Status
Safety Input 5 Status
Safety Output 5 Status
Power Error
Safety Input 6Safety
Input 5
Safety Input 6 Status
Safety Input 5 Status
Safety Output 6 Status
Safety Output 6 Monitor
Safety Output 5 Status
Safety Output 5 Monitor
Power Error
Safety Input 6 Status
Safety Input 5 Status
Safety Output 6 Status
Tes t O utp ut 6 Status
Safety Output 5 Status
Tes t O u tp ut 5 Status
Safety Input 4Safety
Safety Input 4 Status
Safety Output 4 Status
Output Power
(1)
Error
Safety Input 4Safety
Safety Input 4 Status
Safety Output 4 Status
Safety Output 4 Monitor
Output Power
(1)
Error
Safety Input 4 Status
Safety Output 4 Status
Tes t Out pu t 4 Status
Input 3
Safety Input 3 Status
Safety Output 3 Status
Reserved Reser ved Muting
(1)
Input 3
Safety Input 3 Status
Safety Output 3 Status
Safety Output 3 Monitor
Reserved Reser ved Muting
(1)
Safety Input 3 Status
Safety Output 3 Status
Tes t O u tp ut 3 Status
Safety Input 2Safety
Input 1
Safety Input 2 Status
Safety Output 2 Status
Safety Input 1 Status
Safety Output 1 Status
Lamp 7 Status
Safety Input 2Safety
Input 1
Safety Input 2 Status
Safety Input 1 Status
Safety Output 2 Status
Safety Output 2 Monitor
Safety Output 1 Status
Safety Output 1 Monitor
Lamp 7 Status
Safety Input 2 Status
Safety Input 1 Status
Safety Output 2 Status
Tes t O utp ut 2 Status
Safety Output 1 Status
Tes t Output 1
Safety Input 0
Safety Input 0 Status
Safety Output 0 Status
Muting Lamp 3 Status
Safety Input 0
Safety Input 0 Status
Safety Output 0 Status
Safety Output 0 Monitor
Muting Lamp 3 Status
Safety Input 0 Status
Safety Output 0 Status
Tes t O utp ut 0 Status
Status
3 Reser ved Reserved Input
Power Error
Output Power
(1)
Error
Reserved Reser ved Muting
(1)
Lamp 7 Status
Muting Lamp 3 Status
Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013 85
Appendix A Get Diagnostic Status from Modules by Using Explicit Messaging
Table 21 - Input Data (continued)
Instance
Module Connection Hex (Decimal)
365 (869) 1791ES-
IB16
374 (884) 1791ES-
IB8XOBV4
385 (901) 1791ES-
IB16
394 (916) 1791ES-
IB8XOBV4
Type
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Safety and Standard
0Safety Input 7Safety Input 6Safety
Input 5
1Safety Input 15Safety Input 14Safety
Input 13
2Safety Input
7 Status
3Safety Input
15 Status
4 Test Output
7 Status
Safety Input 6 Status
Safety Input 14 Status
Tes t O utp ut 6 Status
Safety Input 5 Status
Safety Input 13 Status
Tes t O u tp ut 5 Status
Safety Input 4Safety
Input 3
Safety Input 12Safety
Input 11
Safety Input 4 Status
Safety Input 12 Status
Tes t Out pu t 4 Status
Safety Input 3 Status
Safety Input 11 Status
Tes t O u tp ut 3 Status
Safety Input 2Safety
Input 1
Safety Input 10Safety
Input 9
Safety Input 2 Status
Safety Input 10 Status
Tes t O utp ut 2 Status
Safety Input 1 Status
Safety Input 9 Status
Tes t Output 1
Safety Input 0
Safety Input 8
Safety Input 0 Status
Safety Input 8 Status
Tes t O utp ut 0 Status
Status
5 Test Output
15 Status
Tes t O utp ut 14 Status
Tes t O u tp ut 13 Status
Tes t Out pu t 12 Status
Tes t O u tp ut 11 Status
Tes t O utp ut 10 Status
Tes t Output 9
Te
st Outp ut
8 Status
Status
Safety and Standard
6 Reser ved Reserved Input
Power Error
0 Safet y Input
7
1Safety Input
7 S t a t u s
Safety Input 6Safety
Input 5
Safety Input 6 Status
Safety Input 5 Status
2Safety
Output 7 Sta tus
3Safety
Output 7 Monitor
4 Test Output
7 Status
Safety Output 6 Status
Safety Output 6 Monitor
Tes t O utp ut 6 Status
Safety Output 5 Status
Safety Output 5 Monitor
Tes t O u tp ut 5 Status
(1)
Output Power Error
(1)
Muting Lamp 15 Status
Safety Input 4Safety
Input 3
Safety Input 4 Status
Safety Input 3 Status
Safety Output 4 Status
Safety Output 4 Monitor
Tes t Out pu t 4 Status
Safety Output 3 Status
Safety Output 3 Monitor
Tes t O u tp ut 3 Status
Muting Lamp 11 Status
Muting Lamp 7 Status
Safety Input 2Safety
Input 1
Safety Input 2 Status
Safety Input 1 Status
Safety Output 2 Status
Safety Output 2 Monitor
Tes t O utp ut 2 Status
Safety Output 1 Status
Safety Output 1 Monitor
Tes t Output 1
Muting Lamp 3 Status
Safety Input 0
Safety Input 0 Status
Safety Output 0 Status
Safety Output 0 Monitor
Tes t O utp ut 0 Status
Status
5 Reserved Reserved Input
Power Error
Output Power
(1)
Error
(1)
Reserved Reser ved Muting
Lamp 7 Status
Muting Lamp 3 Status
Standard Only 0 Reserved Reserved Reserved Reser ved Reserved Reserved Reserved Input Power
Error
1 Test Output
7 Status
Tes t O utp ut 6 Status
Tes t O u tp ut 5 Status
Tes t Out pu t 4 Status
Tes t O u tp ut 3 Status
Tes t O utp ut 2 Status
Tes t Output 1
Tes t O utp ut 0 Status
Status
2 Test Output
15 Status
Tes t O utp ut 14 Status
Tes t O u tp ut 13 Status
Tes t Out pu t 12 Status
Tes t O u tp ut 11 Status
Tes t O utp ut 10 Status
Tes t Output 9
Tes t O utp ut 8 Status
Status
Standard Only 0 Reserved Reserved Reserved Reser ved Reserved Reserved Output
Power
Input Power Error
Error
1 Test Output
7 Status
Tes t O utp ut 6 Status
Tes t O u tp ut 5 Status
Tes t Out pu t 4 Status
Tes t O u tp ut 3 Status
Tes t O utp ut 2 Status
Tes t Output 1
Tes t O utp ut 0 Status
Status
86 Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013
Table 21 - Input Data (continued)
Get Diagnostic Status from Modules by Using Explicit Messaging Appendix A
Instance Hex
Module Connection
Type
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
(Decimal)
3A4 (932) 1791ES-
Standard Only 0 Reserved Reserved Reserved Reser ved Reserved Reserved Output
IB8XOBV4
1Safety
2 Test Output
(1) This data is only diagnostic data and does not have safety integrity.
Table 22 - Output Data
Instance (hex)
22 (34) 1791ES-
23 (35) 1791ES-
234 (564) 1791ES-I
2C4 (708) 1791ES-
Module Connection
Type
Safety and
IB8XOBV4
Standard
Safety and
IB16
Standard
Safety Only 0 Safety
B8XOBV4
Safety Only 0 Safety
IB8XOBV4
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0Standard
0Standard
1Standard
1Standard
Output 7 Monitor
7 Status
Output 7
Output 7
Output 15
Output 7
Output 7
Output 7
(1)
Safety Output 6 Monitor
Tes t O utp ut 6 Status
Standard Output 6
Standard Output 6
Standard Output 14
Safety Output 6
Safety Output 6
Standard Output 6
Safety Output 5 Monitor
Tes t O u tp ut 5 Status
Standard Output 5
Standard Output 5
Standard Output 13
Safety Output 5
Safety Output 5
Standard Output 5
Safety Output 4 Monitor
Tes t Out pu t 4 Status
Safety Output 3 Monitor
Tes t O u tp ut 3 Status
Standard Output 4
Standard Output 4
Standard Output 12
Safety Output 4Safety
Safety Output 4Safety
Standard Output 4
Standard Output 3
Standard Output 3
Standard Output 11
Output 3
Output 3
Standard Output 3
Safety Output 2 Monitor
Tes t O utp ut 2 Status
Standard Output 2
Standard Output 2
Standard Output 10
Safety Output 2
Safety Output 2
Standard Output 2
Power Error
Safety Output 1 Monitor
Tes t Output 1 Status
Standard Output 1
Standard Output 1
Standard Output 9
Safety Output 1
Safety Output 1
Standard Output 1
Input Power Error
Safety Output 0 Monitor
Tes t O utp ut 0 Status
Standard Output 0
Standard Output 0
Standard Output 8
Safety Output 0
Safety Output 0
Standard Ou
tput 0
(1) Standard output signifies a Test Output configured as a standard output.
Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013 87
Appendix A Get Diagnostic Status from Modules by Using Explicit Messaging

Explicit Messages

Explicit messaging can also be used to read individual channel status for safety inputs, safety outputs, test outputs, and power status. Communication error
settings can also be configured and monitored for test outputs as well.
Table 23 - Reading the Cause of the Safety Input Error
Explicit Message
Safety Input Cause of Error (Fault) Information Read
Table 24 - Reading the Cause of the Safety Output Error
Explicit Message Service Function Command (hex) Response (hex)
Safety Output Cause of Error (Fault) Information
Service Function Command (hex) Response (hex)
Service
ClassIDInstance IDAttribute ID Data Size
Code
Get Attribute Single
Reads the cause for the status bit (1…n), specified by the Instance ID, turning OFF.
Get Attribute Single
Reads the cause for the status bit (1…n), specified by the Instance ID, turning OFF.
0E 3D 01…n 6E - 0: No error
Service Code
0E 3B 01…n 6E - 0: No error
ClassIDInstance ID Attribute ID Data Size
01: Configuration invalid 02: External test signal error 03:Internal input error 04: Di screpancy e rror 05: Error in the other dual channel input
01: Configuration invalid 02: Over current detected 03: Short circuit detected 04: Output ON error 05: Error in the other dual channel output 08: Output data error 09: Short circuit detected at safety output
Table 25 - Monitoring the Test Output Point
Explicit Message Ser vice Function Command (hex) Response (hex)
Tes t O utp ut Cause of Error (Fault) Information
Get Attribute Single
Reads the cause for the status bit (1…n), specified by the Instance ID, turning OFF.
Service Code
0E 09 01…n 76 - 0 = No error
ClassIDInstance ID Attribute ID Data
Size
01: Configuration invalid 02: Overload detected 05: Output ON error 06: Undercu rrent detected for muting lamp
88 Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013
Table 26 - Setting Hold/Clear for Communications Errors (Test Output)
Get Diagnostic Status from Modules by Using Explicit Messaging Appendix A
Explicit Message Service Function Command (hex) Response
Setting for Output State (Hold or Clear) after Communication Error
Setting for Output State (Hold or Clear) after Communication Error
Get Attribute Single
Set Attribute Single
Reads whether hold or clear is set as the output state after a communication error for a test output specified by the instance ID. The setting can be read for a specified number of points.
Sets whether hold or clear as the output status after a communication error for an output specified by the instance ID. Sets whether a test output must hold its state or clear (turn off) after a communication error.
Service Code
0E 09 01…08 05 - 1 byte
10 09 01…08 05 1 byte
Class ID
Instance ID
Attribute ID Data Size
00: Clear 01: Hold
(hex)
00: Clear 01: Hold
Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013 89
Appendix A Get Diagnostic Status from Modules by Using Explicit Messaging
Notes:
90 Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013
Appendix B
Safety Data
This appendix lists calculated values for probability of failure on demand (PFD), probability of failure per hour (PFH), and mean time between failure (MTTF). PFD and PFH calculations comply with IEC61508, edition 2, 2010.
Calculated values of probability of failure on demand and probability of failure per hour appear in the Ta b l e 2 7 system to comply with the SIL level required for application.
Users must be responsible for following the requirements of ISO 13849-1:2008, to assess performance levels in their safety system.
Within the proof test interval, every I/O module must be functionally tested by individually toggling each input point and verifying that it is detected by the controller.
and must be calculated for the devices within the
Additionally, each output point must be individually toggled by the controller and user-verified that the output point changes state.
For more information, refer to these publications.
Resource Description
GuardLogix 5570 Controller Systems Safety Reference Manual, publication 1756-RM099
GuardLogix Controller Systems Safety Reference Manual, publication 1756-RM093
Provides information on safety application requirements for GuardLogix 5570 controllers in Studio 5000 Logix Designer projects.
Provides information on safety application requirements for GuardLogix 5560 and 5570 controllers in RSLogix 5000 projects.
Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013 91
Appendix B Safety Data
Figure 25 - PFD versus Proof Test Interval 1791ES-IB8XOBV4
Figure 24 - PFD versus Proof Test Interval 1791ES-IB16
92 Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013
Table 27 - Calculated Values for Probability of Failure on Demand (PFD), Probability of Failure per Hour (PFH), and Mean Time To Failure (MTTF)
Cat. No. Proof Test Interval PFD
Yea r Ho ur
1791ES-IB16 1 8760 2.06E-06 4.98E-10 3.309E-06 34.48
2 17520 4.13E-06
5 43800 1.03E-05
10 87600 2.06E-05
1791ES-IB8XOBV4 1 8760 2.09E-06 5.04E-10 5.612E-06 20.33
2 17520 4.17E-06
5 43800 1.04E-05
10 87600 2.09E-05
(1/hour)
PFH (1/hour)
Spurious Trip Rate (STR)
MTTF (years)
Configuration Reference Information
IMPORTANT
Top ic Pa ge
Understand Parameter Groups 93
Appendix C

Understand Parameter Groups

The modules have these parameter groups: general parameters, safety input, test output, safety output.
See the tables for the settings in each parameter group. All parameters are set by using the Logix Designer application.
Table 28 - General Parameters
Parameter Name Value Description Default
Safety Output Error Latch Time 0…65,530 ms
Safety Input Error Latch Time 0…65,530 ms
Table 29 - Safety Input Parameters
Parameter Name Value Description
Input Point Operation Type Single Channel Use as single channel.
Input Point Mode Not Used External input device is not connected.
Safety Input Test Source Not Used The test output that is used with the input.
Input Delay Time Off -> On
Input Delay Time On -> Off
(in increments of 10 ms)
(in increments of 10 ms)
Dual-channel Equivalent Use as dual-channel. Normal when both channels are ON or OFF.
Dual-channel Complementary Use as dual-channel. Normal when one channel is ON and the other channel is OFF.
Safety Test Pulse Use with a contact output device and in combination with a test output. By using this setting, short-
Safety A solid-state output safety sensor is connected.
Standard A standard device, such as a reset switch, is connected.
Test Output 0 to n
0…126 ms (in increments of 6ms)
0…126 ms (in increments of 6ms)
Safety output errors are latched for this time. 1000 ms
Safety input or test output errors are latched for this time. 1000 ms
circuits between input signal lines and the power supply (positive side) and short-circuits between input signal lines can be detected.
n is dependent on the module catalog number.
Filter time for OFF to ON transition
Filter time for ON to OFF transition
When configuring a test output for Pulse Test mode, verify the corresponding safety input is configured for safety pulse test.
Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013 93
Appendix C Configuration Reference Information
Table 30 - Test Output Parameters
Parameter Name Value Description Default
Test Output Mode Not Used An external device is not connected. Not Used
Standard The output is connected to a standard device.
Pulse Test A contact output device is connected. Use in combination with a safety input.
Power Supply The power supply of a Safety Sensor is connected. The voltage supplied to I/O
Muting Lamp Output (Terminal T3 or T7 only)
Not Used An external output devices is not connected.
Safety When the output is ON, the test pulse is not output (remains ON).
Safety Pulse Test By using this function, short-circuits between output signal lines and the
Single Channel Use as single channel.
Dual-channel Use as dual-channel. When both channels are normal, outputs can be turned
power (V, G) is output from the test output terminal.
An indicator is connected and turned ON to detect broken lines in an external indicator.
power supply (positive side) and short-circuits between output signal lines can be detected.
ON.
Table 31 - Safety Output Parameters
Parameter Name Value Description Default
Output Point Mode Not Used An external output devices is not connected. Not Used
Safety When the output is ON, the test pulse is not output (remains ON).
Safety Pulse Test By using this function, short- circuits between output signal lines and the
Output Point Operation Type Single Channel Use as single channel. Dual-channel
Dual-channel Use as dual-channel. When both channels are normal, outputs can be turned
power supply (positive side) and short-circuits between output signal lines can be detected.
ON.
94 Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013
Table 32 - Safety and Standard Data
Data Description
Input data Safety Input Data Safety Indicates the ON/OFF status of each input circuit.
ON: 1
OFF: 0
Combined Safety Input Status Safety An AND of the status of all input circuits.
All circuits are normal: 1
An error was detected in one or more input circuits: 0
Individual Safety Input Status Safety Indicates the status of each input circuit.
Normal: 1
Faul t (Ala rm): 0
Combined Safety Output Status Safety An AND of the status of all safety output circuits.
All circuits are normal: 1
An error has been detected in one or more output circuits: 0
Individual Safety Output Status Safety Indicates the status of each safety output circuit.
Normal: 1
Faul t (Ala rm): 0
Muting Lamp Status Safety Indicates the status when circuit T3 is configured as the muting lamp output.
Normal: 1
Faul t (Ala rm): 0
Safety Output Monitor Standard Monitors the outputs of the safety output circuits.
ON: 1
OFF: 0
Individual Test Output Status Standard Indicates the status of each of the test output circuits.
Normal: 1
Faul t (Ala rm): 0
Configuration Reference Information Appendix C
Output data Safety Output Data Safet y Controls the safety output.
ON: 1
OFF: 0
Standard Output Data Standard Controls the test output when test output mode is set to a standard output.
ON: 1
OFF: 0
Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013 95
Appendix C Configuration Reference Information
Notes:
96 Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013

Index

A
about catalog numbers 13 additional resources administrator, safety architectures, safety
7
9
14
B
before you begin 9 BootP/DHCP
36
C
catalog numbers 13 certification cleaning common terms compliance with EC directive configuration
configure the module 47 conformity
controlling devices 28
29
12
8
reference information
10
codes regulations standards
10
10
93
31
G
get point status information 71
8
glossary Guardmaster product
29
H
help button 47
I
I/O
configuration tree module overview 12
input configuration dialog international standards IP address
36
47
60
29
J
Japan 30
L
legislation 29 limit switches Logix Designer application
29
7
D
dialog
49
General Input Configuration Output Configuration Safety 56 Test Output Configuration
DIN rail
11
directives discrepancy time door interlocking switches dual-load bipolar outputs dynamic host configuration protocol
30
60
63
62
22
29
45
E
EC directives 11 electronic data sheet EMC directives emergency stop switch
30
Europe
8
31
29, 39
F
fault recovery 26, 28 forcibly-guided contacts
29
36
M
mean time between failure 8, 91 model types module properties dialog mounting MTBF
muting lamp output wiring
13
49
11
See mean time between failure.
42
N
network (IP) address 35 node address setting North America
35
30
O
ODVA 8, 29 off-delay function on-delay function out-of-box condition output configuration dialog
26
26
33
63
P
parameter groups 93
Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013 97
Index
PFD
See probability of failure on demand.
PFH
See probability of failure per hour.
point status information precautions for use probability of failure on demand probability of failure per hour programming requirements publications, related
71
10
8
14
7
R
related publications 7
version
version
29
33
35
14
14
replace units replacement stock rotary switches RSLogix 5000 software
RSNetWorx for DeviceNet software
S
safety architectures 14 safety dialog safety functions
safety network number 8, 50 safety precautions self-diagnostics set network (IP) address SLogix 5000 software
SNN
standards Studio 5000 environment
56
safety input safety output
18
27
29
18
35
14
version
See safety network number.
30
7
14
version
W
wire the module 12 wiring examples
8
37
T
terminology 8 test output
configuration dialog
transport control protocol
62
36
U
understand the operation of safety functions
17
V
ventilation 11
98 Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013
Rockwell Automation Support
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400
Rockwell Automation provides technical information on the Web to assist you in using its products. At http://www.rockwellautomation.com/support code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools. You can also visit our Knowledgebase at http://www.rockwellautomation.com/knowledgebase information, support chat and forums, software updates, and to sign up for product notification updates.
, you can find technical manuals, technical and application notes, sample
for FAQs, technical
For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer
SM
Te c h C o n n e c t representative, or visit http://www.rockwellautomation.com/support/
support programs. For more information, contact your local distributor or Rockwell Automation
.
Installation Assistance
If you experience a problem within the first 24 hours of installation, review the information that is contained in this manual. You can contact Customer Support for initial help in getting your product up and running.
United States or Canada 1.440.646.3434
Outside United States or Canada Use the Wor ldwi de Lo cato r at http://www.rockwellautomation.com/rockwellautomation/support/overview.page, or contact your local
Rockwell Automation representative.
New Product Satisfaction Return
Rockwell Automation tests all of its products to help ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.
United States Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your
Outside United States Please contact your local Rockwell Automation representative for the return procedure.
distributor to complete the return process.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002
Publication 1791ES-UM001D-EN-P - May 2013
Supersedes Publication 1791ES-UM001C-EN-P - April 2009 Copyright © 2013 Rockwell Auto mation, Inc. All rights reserved. Pr inted in the U.S.A.
, available at http://www.rockwellautomation.com/literature/.
Loading...