Rockwell Automation 1771-OND User Manual

Installation Instructions
AC (24V) Output Module
Cat. No. 1771-OND Series B

To The Installer

Preinstallation Considerations

European Union Directive Compliance

This document provides information on:
important pre-installation considerations
power supply requirements
installing the module
setting the fault mode
replacing the fuses
module specifications
This module must be used with a 1771-A1B thru -A4B or later I/O chassis. If you are using a 1771-ASB remote I/O adapter you may use any combination of I/O modules. Otherwise, make sure no other output module or single card block transfer module is placed in the same I/O group.
If this product has the CE mark it is approved for installation within the European Union and EEA regions. It has been designed and tested to meet the following directives.
EMC Directive
This product is tested to meet Council Directive 89/336/EEC Electromagnetic Compatibility (EMC) and the following standards, in whole or in part, documented in a technical construction file:
EN 50081-2EMC – Generic Emission Standard, Part 2 –
Industrial Environment
EN 50082-2EMC – Generic Immunity Standard, Part 2 –
Industrial Environment
This product is intended for use in an industrial environment.
Publication 17715.41 - May 1996
AC (24V) Output Module2
Low Voltage Directive
This product is tested to meet Council Directive 73/23/EEC Low Voltage, by applying the safety requirements of EN 61131–2 Programmable Controllers, Part 2 – Equipment Requirements and Tests.
For specific information required by EN 61131-2, see the appropriate sections in this publication, as well as the following Allen-Bradley publications:
Industrial Automation Wiring and Grounding Guidelines For
Noise Immunity, publication 1770-4.1
Guidelines for Handling Lithium Batteries, publication AG-5.4
Automation Systems Catalog, publication B111

Power Requirements

Initial Handling

Your module receives its power through the 1771 I/O chassis backplane from the chassis power supply. The module requires 700mA from the output of this supply. Add this to the requirements of all other modules in the I/O chassis to prevent overloading the chassis backplane and/or backplane power supply.
The ac output module is shipped in a static-shielded bag to guard against electrostatic discharge damage. Observe the following precautions when handling the module.
Electrostatic Discharge Damage
ATTENTION: Under some conditions, electrostatic discharge can degrade performance or damage the
!
module. Observe the following precautions to guard against electrostatic damage.
Wear an approved wrist strap grounding device, or touch a
grounded object to discharge yourself before handling the module.
Do not touch the backplane connector or connector pins.
If you configure or replace internal components, do not touch
other circuit components inside the module. If available, use a static-free work station.
When not in use, keep the module in a static-shielded bag.
Publication
17715.41 - May 1996
AC (24V) Output Module 3

Installing Your Module

In this section we tell you how to set the fault mode selection plug, key your I/O chassis, install your module and make your wiring connections.
Fault Mode Selection
You may select one of two output-failure configurations (last state or reset) by positioning a configuration plug on the bottom edge of the printed circuit board. This configuration plug is independent of the last state switch on the I/O chassis backplane.
To set the fault mode selection, proceed as follows:
1. Locate the fault mode selection plug at the bottom edge of the
module circuit board (Figure 1).
Figure 1
Mode Selection Plug
Fault
LS RESET
Bottom edge of circuit board
Fault Mode Selection Plug
(shown in last state position)
10673-I
2. Using your finger, slide the plug off the two posts.,
3. Carefully position the plug on two of the three posts that
correspond to your requirement.
Keying Your I/O Chassis
Use the plastic keying bands, shipped with each I/O chassis, to key the I/O slots to accept only this type of module.
The module circuit board is slotted in two places on the rear edge. The position of the keying bands on the backplane connector must correspond to these slots to allow insertion of the module. You can key any connector in an I/O chassis to receive this module except for the left-most connector reserved for adapter or processor modules. Place keying bands between the following numbers labeled on the backplane connector:
Between 20 and 22
Between 32 and 34
You can change the position of these keys if system redesign and rewiring makes insertion of a different module necessary.
Publication
17715.41 - May 1996
AC (24V) Output Module4
Installing the Output Module
To install the ac output module in your 1771 I/O chassis, follow the steps listed below.
ATTENTION: Remove power from the 1771 I/O chassis backplane and wiring arm before removing or
!
installing the module.
Failure to remove power from the backplane or field
wiring arm could cause module damage, degradation of performance, or injury.
Failure to remove power from the backplane could
cause injury or equipment damage due to possible unexpected operation.
1. Turn off power to the I/O chassis.
2. Place the module in the plastic tracks on the top and bottom of the
slot that guides the module into position.
3. Do not force the module into its backplane connector. Apply firm,
even pressure on the module to seat it properly.
4. Snap the chassis latch over the top of the module to secure its
position.
5. Connect the wiring arm to the module.
6. Make wiring connections to the field wiring arm as indicated in
Figure 2.
Publication
17715.41 - May 1996
AC (24V) Output Module 5
Connecting Wiring to the Output Module
Connections to the output module are made to the field wiring arm (cat. no. 1771-WH) shipped with the module. An optional fused wiring arm is available (cat. no. 1771-WHF) which provides individual fusing for each circuit. Attach the wiring arm to the pivot bar on the bottom of the I/O chassis. The wiring arm pivots upward and connects with the module so you can install or remove the module without disconnecting the wires.
You must supply ac (L1) at terminals A through D on the wiring arm. You need four ac connections to accommodate the total required surge rating on the module without overstressing any single connection on the field wiring arm. Jumper all ac (L1) connections together to prevent module damage.
Figure 2 Connection
Diagram
Terminal A Terminal B Terminal C
Terminal D
Output 00 Output 01 Output 02 Output 03 Output 04 Output 05
Output 06 Output 07 Output 10 Output 11 Output 12 Output 13 Output 14 Output 15 Output 16 Output 17
Terminal E
A
B C D 00 01
02 03 04
05 06 07 10 11 12 13 14 15
16 17
E
(Actual wiring runs in this direction.)
L1
24V ac
Output
Device
L2
ac Low
10674I
Publication
17715.41 - May 1996
AC (24V) Output Module6
Important: You can use an AC (24V) Output Module (cat. no.
1771-OND) to directly drive terminals on an AC (24V) Input Module (cat. no. 1771-IND) (Figure 3). You can also use a 1771-OND Output module to drive an AC (24V) Input Module (cat. no. 1771-IN) but you must connect a 250 ohm, 5W resistor between the output terminal and L2 (common) as shown in Figure 3. Use
the same ac power source to power both modules to ensure proper phasing and prevent module damage.
Figure 3
an Input Module with an Output Module
Driving
AC (24V)
Output Module
(Cat. No. 1771OND)
L1
24V ac High
AC (24V)
Input Module
(Cat. No. 1771IND)
AC (24V)
Output Module
(Cat. No. 1771OND)
AC (24V)
Input Module
(Cat. No. 1771IN)
L1
24V ac High
250 ohm 5W
resistor
Publication
ac Low
Note: 1771OND output voltage range is 1060V ac. However, the onstate voltage range of the 1771IND is 1929V ac.
17715.41 - May 1996
L2
L2
L2
ac Low
Note: 1771OND output voltage range is 1060V ac. However, the onstate voltage range of the 1771IN is 1228V ac.
AC (24V) Output Module 7

Interpreting the Status Indicators

The front panel of your module contains one green, module active indicator, and 16 red status indicators (Figure 4). The 1771-OND performs diagnostics in a handshaking mode when first powered up. Upon successful completion of the diagnostics, the green module active indicator lights. It turns off if a fault occurs in the data paths or the opto-isolators.
The red status indicators are provided for system logic side indication of individual inputs. When a red indicator lights, voltage is present on the terminal. The module transfers this information to the backplane for the processor to read.
Figure 4
Indicators
Status
Module Active Indicator (green)
ACTIVE 00
10
01
11
02
12
03
13
04
14
05
15
06
16
07
17
00 to 17 Status Indicators (red)
10676I
Publication
17715.41 - May 1996
AC (24V) Output Module8

Replacing the Fuse

The module’s output circuitry is protected from overload or shorts by a fuse. You can replace the fuse as outlined below.
1. Turn off all power to the I/O chassis and all output device power
to the field wiring arm.
ATTENTION: Remove power from the 1771 I/O chassis backplane and wiring arm before removing or
!
installing the module.
Failure to remove power from the backplane or field
wiring arm could cause module damage, degradation of performance, or injury.
Failure to remove power from the backplane could
cause injury or equipment damage due to possible unexpected operation.
2. Pivot the wiring arm away from the module and remove the
module from the chassis.
3. Replace the blown fuse with a 10A, 250V rectifier fuse (1/4 x
1-1/4 inch), Littelfuse part number 322010.
4. Replace the module in the chassis and attach the field wiring arm.
Publication
17715.41 - May 1996
AC (24V) Output Module 9

Troubleshooting

If a problem occurs, follow the procedure listed below.
Modules with Internal Fuses Only
1. Turn off all power to the I/O chassis and all output device power
to the field wiring arm.
ATTENTION: Remove power from the 1771 I/O chassis backplane and wiring arm before removing or
!
installing the module.
Failure to remove power from the backplane or field
wiring arm could cause module damage, degradation of performance, or injury.
Failure to remove power from the backplane could
cause injury or equipment damage due to possible unexpected operation.
2. Pivot the wiring arm away from the module and remove the
module from the chassis.
3. Replace the blown fuse with a 10A, 250V rectifier fuse (1/4 x
1-1/4 inch), Littelfuse part number 322010.
4. Replace the module in the chassis and attach the field wiring arm.
5. Turn OFF all outputs to the module.
6. Turn ON power to the I/O chassis only.
7. Check that the red status indicators on the front of the module
(Figure 4) are off (no outputs on). Make sure the red fuse blown indicator is off.
8. Turn on output device power to the field wiring arm.
9. Start with bit 00 and turn on individual outputs one at a time.
Turn off the previous output before turning on the next output.
10.If the red fuse blown indicator turns on, note which output is
faulty and trace the output wiring to the faulty device.
After correcting the fault problem, return to step 1 and begin again. If you cannot locate a faulty output, return to step 9 and turn on 2 or more outputs at the same time. Total output current should not exceed 2A per output, or 8A total per module.
Publication
17715.41 - May 1996
AC (24V) Output Module10
Modules with External Fuses Only
1. Turn off all power to the I/O chassis and all output device power
to the field wiring arm.
2. Pivot the wiring arm away from the module.
3. Use a continuity checker (meter in low ohms setting) to check
fuses for an open (high resistance) reading.
4. Note if fuse is open and trace the output wiring back to the output
device.
5. Check the remaining fuses (refer to step 3).
6. After all faulty fuses are replaced and any wiring problems
solved, reposition the wiring arm on the module.
7. Turn off all outputs to the module.
8. Turn on power to the I/O chassis.
9. Check that the red status indicators on the front of the module are
off (no outputs on). Make sure the red fuse blown indicator is off.
10.Turn on output device power to the wiring arm.
11. Start with bit 00 and turn on individual outputs one at a time.
Turn off last output before turning on the next output.
12.If the red fuse blown indicator lights, note which output is faulty
and trace the output wiring to the faulty device.
After correcting the fault problem, return to step 1 and begin again. If you cannot locate a faulty output, return to step 8 and turn on 2 or more outputs at the same time. Total output current should not exceed 2A per output, or 8A per module.
Publication
17715.41 - May 1996
AC (24V) Output Module 11
CSA Hazardous Location Approval Approbation d'utilisation dans des emplacements dangereux par la
CSA certifies products for general use as well as for use in hazardous locations. Actual CSA certification is indicated by the product label as shown below, and not by statements in any user documentation.
Example of the CSA certification product label Exemple d'étiquette de certification d'un produit par la CSA
To comply with CSA certification for use in hazardous locations, the following information becomes a part of the product literature for CSAcertified AllenBradley industrial control products.
This equipment is suitable for use in Class I, Division 2,
Groups A, B, C, D, or nonhazardous locations only.
The products having the appropriate CSA markings (that is, Class
I Division 2, Groups A, B, C, D), are certified for use in other equipment where the suitability of combination (that is, application or use) is determined by the CSA or the local inspection office having jurisdiction.
Important: Due to the modular nature of a PLC control system, the product with the highest temperature rating determines the overall temperature code rating of a PLC control system in a Class I, Division 2 location. The temperature code rating is marked on the product label as shown.
CSA
La CSA certifie les produits d'utilisation générale aussi bien que ceux qui s'utilisent dans des emplacements dangereux. La certification CSA en vigueur est indiquée par l'étiquette du produit et non par des affirmations dans la documentation à l'usage des utilisateurs.
Pour satisfaire à la certification de la CSA dans des endroits dangereux, les informations suivantes font partie intégrante de la documentation des produits industriels de contrôle AllenBradley certifiés par la CSA.
Cet équipement convient à l'utilisation dans des emplacements de
Classe 1, Division 2, Groupes A, B, C, D, ou ne convient qu'à l'utilisation dans des endroits non dangereux.
Les produits portant le marquage approprié de la CSA (c'est à dire,
Classe 1, Division 2, Groupes A, B, C, D) sont certifiés à l'utilisation pour d'autres équipements où la convenance de combinaison (application ou utilisation) est déterminée par la CSA ou le bureau local d'inspection qualifié.
Important: Par suite de la nature modulaire du système de contrôle PLC), le produit ayant le taux le plus élevé de température détermine le taux d'ensemble du code de température du système de contrôle d'un PLC dans un emplacement de Classe 1, Division 2. Le taux du code de température est indiqué sur l'étiquette du produit.
Temperature code rating
Look for temperature code rating here
The following warnings apply to products having CSA certification for use in hazardous locations.
ATTENTION: Explosion hazard 
Substitution of components may impair suitability
!
for Class I, Division 2.
Do not replace components unless power has
been switched off or the area is known to be nonhazardous.
Do not disconnect equipment unless power has
been switched off or the area is known to be nonhazardous.
Do not disconnect connectors unless power has
been switched off or the area is known to be nonhazardous. Secure any usersupplied connectors that mate to external circuits on an AllenBradley product using screws, sliding latches, threaded connectors, or other means such that any connection can withstand a 15 Newton (3.4 lb.) separating force applied for a minimum of one minute.
Taux du code de température
Le taux du code de température est indiqué ici
Les avertissements suivants s'appliquent aux produits ayant la certification CSA pour leur utilisation dans des emplacements dangereux.
AVERTISSEMENT: Risque d'explosion 
La substitution de composants peut rendre ce matériel
!
inacceptable pour lesemplacements de Classe I, Division 2.
Couper le courant ou s'assurer quel'emplacement est
désigné non dangereux avant de remplacer lescomposants.
Avant de débrancher l'équipement, couper le courant
ou s'assurer que l'emplacement est désigné non dangereux.
Avant de débrancher les connecteurs, couper le
courant ou s'assurer que l'emplacement est reconnu non dangereux. Attacher tous connecteurs fournis par l'utilisateur et reliés aux circuits externes d'un appareil AllenBradley à l 'aide de vis, loquets coulissants, connecteurs filetés ou autres moyens permettant aux connexions de résister à une force de séparation de 15 newtons (3,4 lb.  1,5 kg) appliquée pendant au moins une minute.
CSA
logo is a registered trademark of the Canadian Standards Association.
Publication
17715.41 - May 1996
AC (24V) Output Module12

Specifications

Outputs per Module 16
Module Location 17711A1B thru A4B or later I/O chassis; 1771AM1, AM2
Output Voltage Range 10 to 60V ac @ 47  63Hz
Output Current Rating 2A per output  not to exceed 8A per module
Surge Current (maximum) 25A per output for 100ms, repeatable every 1 second
25A per module for 100ms, repeatable every 1 second
Minimum Load Current 50mA per output @ 24V ac, 60Hz
On State Voltage Drop (max.) 1.6V at 2A
Off State Leakage Current (max.) 3mA per output @ 24V ac
Signal Delay Off to On
On to Off
1.0ms;
8.3 to 9.1ms @ 60Hz
Power Dissipation 16.5 Watts (max.), 3.7 Watts (min.)
Thermal Dissipation 56.2 BTU/hr (max.), 12.6 BTU/hr (min.)
Backplane Current 700mA @ 5V dc +5%
Isolation Voltage Tested at 1500V ac (rms) for 1s
Environmental Conditions
Operational Temperature Storage Temperature Relative Humidity
Conductors Wire Size
Category
0o to 60oC (32o to 140oF)
o
40
to 85oC (40o to 185oF)
5 to 95% (without condensation)
14 gauge (2mm2) stranded maximum
3/64 inch (1.2mm) insulation maximum
1
1
Keying Between 20 and 22
Between 32 and 34
Fuse 10A, 250V rectifier fuse (1/4 x 11/4 inch), Littelfuse PN 322010
Field Wiring Arm Standard
Optional
Catalog Number 1771WH
Catalog Number 1771WHF (fused)
Wiring Arm Screw Torque 79 inchpounds
Agency Certification (when product or packaging is marked)
CSA certified
CSA Class I, Division 2, Groups A, B, C, D certified
UL listed
CE marked for all applicable directives
1
Refer
to publication 17704.1, Programmable Controller Wiring and Grounding Guidelines.
AllenBradley, a Rockwell Automation Business, has been helping its customers improve productivity and quality for more than 90 years. We design, manufacture and support a broad range of automation products worldwide. They include logic processors, power and motion control devices, operator interfaces, sensors and a variety of software. Rockwell is one of the world's leading technology companies.
Worldwide representation.
Argentina Denmark • Ecuador Ireland Philippines Sweden
AllenBradley Headquarters, 1201 South Second Street, Milwaukee, WI 53204 USA, Tel: (1) 414 3822000 Fax: (1) 414 3824444
Publication
Australia • Austria • Bahrain
Israel Italy Jamaica
Switzerland • T
17715.41 - May 1996
Publication
Egypt El Salvador Finland France
Poland • Portugal • Puerto Rico • Qatar • Romania • Russia-CIS • Saudi Arabia • Singapore
aiwan
17715.41 - May 1996
Belgium Brazil
Japan • Jordan • Korea • Kuwait • Lebanon
Thailand T
urkey • United Arab Emirates • United Kingdom • United States • Uruguay
Bulgaria • Canada
Germany • Greece • Guatemala • Honduras • Hong Kong • Hungary
Chile
China, PRC • Colombia
Malaysia Mexico
Costa Rica
Netherlands
New Zealand •
Slovakia Slovenia
Croatia • Cyprus
Norway
South Africa, Republic
V
enezuela
Copyright
1995 AllenBradley Company
Iceland
Yugoslavia
Czech Republic
India • Indonesia
Pakistan
Peru
Spain
PN955124-34
, Inc. Printed in USA
Loading...