Important User Information2
About the Controller3
General Safety3
Install the Controller4
Mount the Controller5
Ground the Controller5
Wire the Controller6
Make Communication Connections15
Reset Push Button17
Controller Tests18
Status Indicators19
Specifications20
Additional Resources24
2 GuardPLC 1800 Controllers
Important User Information
Solid-state equipment has operational characteristics differing from those of electromechanical equipment.
Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication
SGI-1.1
available from your local Rockwell Automation sales office or online at
http://www.rockwellautomation.com/literature/
equipment and hard-wired electromechanical devices. Because of this difference, and also because of the
wide variety of uses for solid-state equipment, all persons responsible for applying this equipment must
satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages
resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many
variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot
assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits,
equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell
Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can
cause an explosion in a hazardous environment, which may lead to personal
injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can
lead to personal injury or death, property damage, or economic loss.
Attentions help you identify a hazard, avoid a hazard and recognize the
consequences.
) describes some important differences between solid-state
SHOCK HAZARD: Labels may be on or inside the equipment, for example,
drive or motor, to alert people that dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example,
drive or motor, to alert people that surfaces may reach dangerous
temperatures.
IMPORTANT
Identifies information that is critical for successful application and understanding of
the product.
Rockwell Automation Publication 1753-IN002C-EN-P - June 2010
GuardPLC 1800 Controllers 3
About the Controller
The GuardPLC 1800 controller is a programmable electronic system featuring 24 digital inputs,
8 digital outputs, 2 counters, 8 analog inputs, and 4 connections for GuardPLC Ethernet
communication.
Ethernet Ports
(on top of controller)
Voltage
Supply
Connection
Ethernet Ports (on bottom of controller)
Digital
Outputs
General Safety
ATTENTION: Personnel responsible for the application of safety-related
programmable electronic systems (PES) shall be aware of the safety
requirements in the application of the system and shall be trained in using the
system.
Prevent Electrostatic Discharge
Digital Inputs
High
Speed
Counter
Analog Inputs
ATTENTION: This equipment is sensitive to electrostatic discharge, which can
cause internal damage and affect normal operation. Follow these guidelines
when you handle this equipment:
• Touch a grounded object to discharge static potential.
• Wear an approved wrist-strap grounding device.
• Do not touch connectors or pins on component boards.
• Do not touch circuit components inside the equipment.
• Use a static-safe workstation, if available.
• Store the equipment in appropriate static-safe packaging when not in use.
Rockwell Automation Publication 1753-IN002C-EN-P - June 2010
4 GuardPLC 1800 Controllers
Environment and Enclosure
ATTENTION: This equipment is intended for use in a Pollution Degree 2
industrial environment, in overvoltage Category II applications (as defined in
IEC publication 60664-1), at altitudes up to 2000 m (6562 ft) without derating.
This equipment is considered Group 1, Class A industrial equipment according
to IEC/CISPR 11. Without appropriate precautions, there may be difficulties
with electromagnetic compatibility in residential and other environments due
to conducted as well as radiated disturbances.
This equipment is supplied as open-type equipment. It must be mounted within
an enclosure that is suitably designed for those specific environmental
conditions that will be present and appropriately designed to prevent personal
injury resulting from accessibility to live parts. The enclosure must have
suitable flame-retardant properties to prevent or minimize the spread of flame,
complying with a flame spread rating of 5VA, V2, V1, V0 (or equivalent) if
non-metallic. The interior of the enclosure must be accessible only by the use
of a tool. Subsequent sections of this publication may contain additional
information regarding specific enclosure type ratings that are required to
comply with certain product safety certifications.
In addition to this publication, see:
• Industrial Automation Wiring and Grounding Guidelines, Rockwell
Automation publication 1770-4.1
• NEMA 250 and IEC 60529, as applicable, for explanations of the degrees of
protection provided by different types of enclosure.
, for additional installation requirements.
Install the Controller
Follow these steps to install the GuardPLC 1600 controller.
1. Mount the controller to a DIN rail.
2. Ground the controller.
3. Wire the controller.
4. Make communication connections.
This publication describes these steps in detail.
Rockwell Automation Publication 1753-IN002C-EN-P - June 2010
Mount the Controller
GuardPLC 1800 Controllers 5
IMPORTANT
For effective cooling, mount the controller following these guidelines
• Mount the controller horizontally.
• Provide a gap of at least 100 mm (3.94 in.) above and below the controller.
• Select a location where air flows freely or use an additional fan.
• Do not mount the controller over a heating device.
The controller cannot be panel-mounted. Mount the controller to a DIN rail by following these
steps.
1. Hook the top slot over the DIN rail.
2. Insert a flathead screwdriver into the gap
between the housing and the latch and pull
the latch downward.
3. Hold the latch down as you push the housing
back onto the DIN rail.
4. Release the latch to lock the device onto the
rail.
TIP
To remove the controller from the DIN rail, insert a flathead screwdriver
into the gap between the housing and the latch and pull the latch
downward as you lift the controller off of the rail.
(3)
(2)
(1) Top Slot
DIN Rail
Latch
Ground the Controller
The controller is functionally grounded through its DIN rail connection. A protective earth
ground connection is required and is provided through a separate grounding screw on the upper
left of the housing and marked with the grounding symbol .
You must also provide an acceptable grounding path for each device in your application. For
more information on proper grounding guidelines, refer to the Industrial Automation Wiring
and Grounding Guidelines, publication 1770-4.1
ATTENTION: This product is grounded through the DIN rail to chassis ground.
Use zinc-plated yellow-chromate steel DIN rail to assure proper grounding. The
use of other DIN rail materials (for example, aluminum or plastic) that can
corrode, oxidize, or are poor conductors, can result in improper or intermittent
grounding. Secure DIN rail to mounting surface approximately every 200 mm
(7.8 in.) and use end-anchors appropriately.
Rockwell Automation Publication 1753-IN002C-EN-P - June 2010
.
6 GuardPLC 1800 Controllers
Wire the Controller
The following section describe how to connect the voltage supply and wire the controller’s
digital inputs and outputs.
Connect the Voltage Supply
The 24V DC voltage supply must feature galvanic isolation (in accordance with
EN 60950 or UL 1950) since inputs and outputs are not electrically isolated from the processor.
To comply with CE Low Voltage Directives (LVD) and UL restrictions, you must use either a
Safety Extra Low Voltage (SELV), or a Protected Extra Low Voltage (PELV) power supply to
power this controller. A SELV supply cannot exceed 30V rms, 42.4V peak, or 60V DC under
normal conditions and under single-fault conditions. A PELV supply has the same rating and is
connected to protected earth.
IMPORTANT
IMPORTANT
The supply voltage is connected via a 4-pin connector that accommodates wire sizes up to
2
(14 AWG). You need to connect only one wire to L+ and one wire to L-. Both L+ and
2.5 mm
L- terminals are internally connected, so you can daisy-chain 24V DC power from the
GuardPLC controller to other devices in the panel by using the remaining terminal.
Protect the controller with a slow-blowing fuse.
The GuardPLC 1800 controller can draw up to 9 A. The controller needs 1 A to
operate. Up to 8 A can be used to source voltage power for inputs and
outputs connected to the controller.
ATTENTION: Do not reverse the L+ and L- terminals or damage to the
controller will result. There is no reverse polarity protection.
Rockwell Automation Publication 1753-IN002C-EN-P - June 2010
GuardPLC 1800 Controllers 7
Safety-Related Digital Inputs
The controller has 24 digital inputs whose status is indicated via status indicators when the
controller is in RUN mode.
LS+ is a voltage source that provides 24V DC for a group of eight dry contact inputs. There are
three groups on the GuardPLC 1800 controller.
COM
24V DC
Power
+
Supply
(—)4(—)
3
L-L-L+ L+
24V DC
RS-485
Connection of Voltage Supply to Input Device
If devices require 24V DC to operate and use the same power source as the controller, then wire
the outputs of the device directly to inputs on the controller.
COM
24V DC
Power
+
Supply
123456
1234
1L-
Light Curtain
(or any Safety Input)
COM
+
78910
56
345 678
11 12 13 14 15 16
11 12 13 14
10789
L-DO2
(2A)(2A)
17 18 19 20
15 16
1LS+L-DI2 3 4 5 6 7 8
2017 18 19
(—)4(—)
3
L-L-L+ L+
24V DC
RS-485
123456
1234
1L-
3456 78
56
78910
(2A)(2A)
10789
L-DO2
11 12 13 14 15 16
15 16
11 12 13 14
1LS+L-DI2 3 4 5 6 7 8
17 18 19 20
2017 18 19
Connection of Voltage Supply to Input Device
Devices with their own dedicated power supply can also be connected. Connect the reference
pole of the external power supply to the L- reference pole of the input.
Light Curtain
(or any Safety Input)
24V DC
Power
Supply
COM
+
(—)4(—)
3
L-L-L+ L+
24V DC
RS-485
24V DC
Power
Supply
COM
+
123456
1234
1L-
COM
+
78910
56
345 678
11 12 13 14 15 16
11 12 13 14
10789
L-DO2
(2A)(2A)
17 18 19 20
15 16
1LS+L-DI2 3 4 5 6 7 8
2017 18 19
Connection of Devices with Dedicated Power Supplies
Rockwell Automation Publication 1753-IN002C-EN-P - June 2010
8 GuardPLC 1800 Controllers
The safe state of an input is indicated by a 0 signal being passed to the user program logic. If the
test routines detect a fault in the digital inputs, a 0 signal is processed in the user program for the
defective channel. When a fault occurs, the inputs are switched off (0).
Follow the closed-circuit principle for external wiring when connecting sensors. To create a safe
state in the event of a fault, the input signals revert to the de-energized state (0). The FAULT
status indicator activates.
Digital Input Terminals
11 12 13 14 15 16
11 12 13 14
1LS+L-DI2 3 4 5 6 7 8
Terminals accommodate wires up to 1.5 mm2 (16 AWG). See the terminal torque specifications
on page 21. Digital inputs are connected to these terminals.
LS+, not L+, should be used for short-circuit protection. Each LS+ features individual
short-circuit and EMC protection that make it important to use LS+ for only its eight related
inputs.
Line Control
The short-circuit and line break monitoring system, such as E-stop inputs, cannot be configured
for the GuardPLC 1800 controller. This is due to the fact that the 24 discrete inputs are actually
analog inputs with a resolution of one bit.
Safety-Related Analog Inputs
The controller has 8 analog inputs with transmitter supplies for the unipolar measurement of
voltages from 0…10V, referenced to L-. A 10 KΩ shunt is used for single-ended voltage signals.
With a 500 Ω shunt resistor, currents from 0…20 mA can also be measured.
The feeder lines should be no more than 300 m (984 ft) in length. Use shielded, twisted-pair
cables, with the shields connected at both ends, for each measurement input.
Unused analog inputs must be short-circuited. Place wire jumpers into any inputs that are not
used.
AI
T1 I1 L- T2 I2 L-
41 42 43 44 45 46
Wire Jumper
Rockwell Automation Publication 1753-IN002C-EN-P - June 2010
41T1Transmitter supply 1
42I1Analog input 1
43L-Reference pole
44T2Transmitter supply 2
45I2Analog input 2
46L-Reference pole
47T3Transmitter supply 3
48I3Analog input 3
49L-Reference pole
50T4Transmitter supply 4
51I4Analog input 4
52L-Reference pole
53T5Transmitter supply 5
54I5Analog input 5
55L-Reference pole
56T6Transmitter supply 6
57I6Analog input 6
58L-Reference pole
+
COM
Power Source
-
+
Rockwell Automation Publication 1753-IN002C-EN-P - June 2010
12 GuardPLC 1800 Controllers
47 48 49 50 51524142434445 46535
Terminal Number DesignationFunction
59T7Transmitter supply 7
60I7Analog input 7
61L-Reference pole
62T8Transmitter supply 8
63I8Analog input 8
64L-Reference pole
Connecting the I/O Circuits
The I/O circuits are connected to the front plate of the controller using pluggable terminals. For
controls with analog inputs, shielded cabling is fed in from below so that the shielding can be
connected to the shield contact plate using a clip. Remove about 2 cm (0.78 in.) of the outer
cable insulation so that the mesh is exposed at the point where the cable is clipped to the plate.
Position the clip over the uninsulated cable shielding and push it into the slots of the shield
contact plate until it fits firmly in place, as shown below.
Mesh
IMPORTANT
Shielded Cable
Make sure that the mesh comes in direct contact with the shield contact plate.
Cable Clip
If the mesh does not touch the plate, the cable is not grounded.
Safety-related Digital Outputs
The controller has eight digital outputs (DO1…DO8) whose status is indicated via status
indicators.
An output is in a safe state when it is de-energized. When a fault occurs, all outputs are switched
off.
Outputs 1…3 and 5…7 can have a load of 0.5 A at an ambient temperature of 60 °C (140 °F).
Outputs 4 and 8 can each have a load of 1 A at an ambient temperature of 60 °C (140 °F), or up
to 2 A at an ambient temperature of 50 °C (122 °F).
With an overload, one or all of the outputs are turned off. When the overload is eliminated, the
outputs are activated again according to the specified value.
Although the external line of an output is not monitored, a short-circuit will be indicated.
Rockwell Automation Publication 1753-IN002C-EN-P - June 2010
Digital Output Terminals
123456
GuardPLC 1800 Controllers 13
78910
1234
1L-L-DO2
56
345 678
(2A)(2A)
10789
Terminals accommodate wires up to 1.5 mm2 (16 AWG). See the terminal torque specifications
on page 21. Digital outputs are connected to these terminals.
Terminal Number DesignationFunctionCurrent
1L-Reference pole—
21Digital output 10.5 A
32Digital output 20.5 A
43Digital output 30.5 A
54Digital output 4 (for increased load)2.0 A
65Digital output 50.5 A
76Digital output 60.5 A
87Digital output 70.5 A
98Digital output 8 (for increased load)2.0 A
10L-Reference pole—
For connection of a load, the reference pole L- of the concerned channel group must be used
(2-pole connection). Although L- at terminals 1 and 6, 7 and 12 is connected internally to L- on
he power supply input, it is strictly recommended to use 1 and 6 for outputs 1…4 only and 7 and
12 for outputs 5…8 only. EMC testing was performed in this manner.
Rockwell Automation Publication 1753-IN002C-EN-P - June 2010
14 GuardPLC 1800 Controllers
636465 66 67 68717269 70
net
Example: Connecting Actuators to the Outputs
DO 2
…
DO 1
DO 7
DO 8L-L-
TIP
Inductive loads can be connected without a protection diode on the load.
However, Rockwell Automation strongly recommends that a protection diode be
fitted directly to the load to suppress any interference voltage. A 1N4004 diode
is recommended.
High-speed Counter Connections
The controller features two independent high-speed counters. Both counters are 24-bit, are
configured for either 5V or 24V DC, and have a maximum input frequency of 100 KHz.
The counters can be used as a counter or as a decoder for 3-bit Gray Code inputs. As a counter,
input A is the counter input, input B is the counter direction input, and input Z is used for a
reset.
The counter inputs must be connected using shielded, twisted-pair cables for each measurement
input. The shields must be connected at both ends. The input lines should be no more than
500 m (1640 ft) in length. All L- connections are internally connected on the controller.
Cables are clipped to the shield contact plate when connecting counter inputs. Remove about
2 cm (0.78 in.) of the outer cable insulation so that the mesh is exposed at the point where the
cable is clipped to the plate.
Mesh
Shield
Contact Plate
IMPORTANT
Rockwell Automation Publication 1753-IN002C-EN-P - June 2010
Cable Clip
Make sure that the mesh comes in direct contact with the shield contact plate.
If the mesh does not touch the plate, the cable is not grounded.
GuardPLC 1800 Controllers 15
High-speed Counter Terminals
HSC
A1 B1 Z1 L- A2 B2 Z2 L-
65 66 67 6871 7269 70
Terminals accommodate wires up to 1.5 mm2 (16 AWG). Counters are connected to these
terminals.
Terminal Number DesignationCounter FunctionGray Code Function
For more information on GuardPLC system wiring and counter
configuration, see the GuardPLC Controller Systems User Manual,
publication 1753-UM001.
Make Communication Connections
The controller supports separate connections for safety and nonsafety-related communication.
Connections for Safety-related Communication
The controller has four 10/100BaseT, RJ45 connectors to provide communication via
GuardPLC Ethernet protocol to distributed I/O and other GuardPLC controllers, OLE for
Process Control (OPC) servers, and with the programming software. Connectors 1 and 2 are on
the bottom side on the left. Connectors 3 and 4 are on the top side on the left. All four
connectors and the GuardPLC processor are connected together by an internal Ethernet switch.
The switches are auto-detect. Either crossover or straight-through Ethernet cabling can be used.
Star or line configurations are available. Make sure that a network loop is not generated. Data
packets must be able to reach a node only via a single path.
Rockwell Automation Publication 1753-IN002C-EN-P - June 2010
16 GuardPLC 1800 Controllers
OPC Server
The GuardPLC 1800 controller is an OPC client. An OPC server, catalog number 1753-OPC,
is available from Rockwell Automation and lets computer applications read and write data to and
from the GuardPLC controller.
MAC Address
The media access control (MAC) address of the controller can be found on the label positioned
over both lower RJ45 connections.
Connections for Nonsafety-Related Communication
Three 9-pin D-shell connectors on the front of the controller provide the following
communication options.
DesignationFunction
COMM1 (RS-485)Modbus Slave (1753-L32BBB-M)
COMM2TBD
COMM3 (RS-485)GuardPLC ASCII Protocol
The pin assignments of the D-shell connector are listed in this table.
Profibus-DP-Slave (1753-L32BBB-P)
ConnectionSignalFunction
1——
2RP5V, decoupled with diodes
3RxD/TxD-AReceive/transmit data A
4CNTR-AControl signal A
5DGNDData reference potential
6VP5V, positive pole of supply voltage
7——
8RxD/TxD-BReceive/transmit data B
9CNTR-BControl signal B
IP Address and System ID (SRS)
A transparent label provided with the controller can be used to note the IP Address and system
ID (SRS). The default value for the IP Address is 192.168.0.99. The default SRS is 60000.
IMPORTANT
Rockwell Automation Publication 1753-IN002C-EN-P - June 2010
If you attach the label to the controller, make sure you do not cover any of the
ventilation slots.
GuardPLC 1800 Controllers 17
Reset Push Button
The controller is equipped with a reset push button. Reset via the push button is necessary under
the following conditions.
• You forget the password to go online via the programming software.
• You are unable to determine the IP address and SRS of the controller.
The push button is accessible through a small round hole at the top of the housing,
approximately 4…5 cm (1.6…2.0 in.) from the left rim and recessed approximately 9.5 mm
(0.375 in.).
IMPORTANT
To reset, press and hold the push button for 20 seconds while rebooting the device by cycling
power. Pressing the Reset push button during operation has no affect.
With activation of the reset button:
Activate the reset push button using an insulated pin to prevent short-circuits.
• all accounts are deleted except for the default account.
• IP Address and System ID (SRS) are set to their default values.
The next time you cycle power, these settings will be restored to the last values stored into
nonvolatile memory. This means that either the settings prior to the reset will be restored, or if
any settings were changed after the reset, those new settings will still be in effect.
Rockwell Automation Publication 1753-IN002C-EN-P - June 2010
18 GuardPLC 1800 Controllers
Controller Tests
In addition to the tests for safety, the controller tests the supply voltage and controller
temperature.
Supply Voltage Tests
The supply voltage (24V DC) is monitored and the alarm and system shutdown are controlled
according to the voltage levels listed below.
Voltage LevelSystem Condition
19.3 to 28.8V Normal
< 19.3VAlarm state 1 (internal variables are written)
< 15.4VAlarm state 2 (prepares for shutdown)
< 13.0VSwitched off
Temperature Tests
The temperature of the controller is automatically and continuously monitored. The alarm is
triggered by the temperature conditions described in the table below.
Operating TemperatureAlarm
< 60 °C (140 °F)None (normal)
60…70 °C (140…158 °F)Warning on
> 70 °C (158 °F)Main alarm on
return to 64… 54 °C (147.2…129.2 °F)Main alarm off, warning on
return to < 54 °C (129.2 °F)None (return to normal)
Rockwell Automation Publication 1753-IN002C-EN-P - June 2010
GuardPLC 1800 Controllers 19
Status Indicators
IndicatorStateDescription
24V DCOn24V DC operating voltage present.
OffNo operating voltage.
RUNOnThis is the normal status of the controller.
Flashing The controller is in STOP mode and is not executing a routine.
OffThe controller is in ERROR_STOP mode (see ERROR).
ERROROn
OffNo errors are detected.
PROGressOnThe upload of a new controller configuration is in progress.
Flashing The upload of a new operating system into the nonvolatile ROM is in progress.
OffNo upload of controller configuration or operating system in progress.
FORCEOnThe controller is executing a routine (RUN) and FORCE mode is activated by the user.
Flashing The controller is in STOP mode, but Forcing has been initiated and will be activated
OffForcing is OFF.
FAULTOn
Flashing An error has occurred during a nonvolatile ROM write cycle.
OffNone of the above errors has occurred.
OSLFlashing Emergency Operating System Loader is active.
BLFlashing Boot Loader unable to load operating system or unable to start COMM operating
Controller status can be interrogated through the programming software. For more information, see the
GuardPLC Controller System User Manual, publication 1753-UM001
A routine, which has been loaded into the controller, is executed.
The controller processes input and output signals, carries out communication, and
performs hardware and software tests.
All system outputs are reset.
STOP mode can be triggered by setting the Emergency stop system variable to TRUE
in the routine, or by direct command from the programming software.
• A hardware error has been detected by the controller. The controller goes to
ERROR_STOP mode and the execution of the routine is halted. Hardware errors
are errors in the controller, errors in one or more of the digital input and output
modules, or errors in the counters.
• A software error in the operating system has been detected by the controller.
• The watchdog has reported an error due to exceeded cycle time.
All system outputs will be reset and the controller ceases all hardware and software
tests. The controller can only be restarted by a command from the programming
software.
when the controller is started.
• The routine (logic) has caused an error.
• The controller configuration is faulty.
• The upload of a new operating system was not successful, and the operating
system is corrupted.
One or more I/O errors have occurred.
system loader.
.
Rockwell Automation Publication 1753-IN002C-EN-P - June 2010
20 GuardPLC 1800 Controllers
Communication via GuardPLC Ethernet is indicated by two small status indicators integrated
into all connecting sockets.
IndicatorStateDescription
GreenOnFull-duplex operation
Flashing Collision
OffHalf-duplex operation, no collision
YellowOnConnection established
Flashing Interface activity
Additional nonsafety-related communication occurs on the field buses and is indicated by the
status indicators.
Wire typeShielded on Ethernet, analog, and high-speed counter inputs
Terminal block torque0.51 N•m (4.5 lb•in)
Fuse (external)24V DC power: 10 A (time-lag)
Enclosure type ratingMeets IP20
Width, approx.257 mm (10.1 in.) including housing screws
Height, approx.114 mm (4.49 in.) including latch
Depth, approx.66 mm (2.60 in.) including grounding bolt
Weight, approx.1.2 kg (2.64 lb)
Digital Inputs
Number of inputs24 (not electrically isolated)
On stateVoltage: 15…30V DC
Off stateVoltage: 5V DC max
Input resistance< 7 kΩ
Overvoltage protection-10V, +35V
Line length, max300 m (9.8 ft)
Supply20V / 100 mA, short-circuit proof
Digital Outputs
Number of outputs8 (not electrically isolated)
Output voltage range≥ L+ minus 2V
Output currentChannels 1…3 and 5…7: 0.5 A @ 60 °C (140 °F)
Surge current per channel1 A for 10ms @ 1Hz (channels 1…3 and 5…7)
Current load, min2 mA per channel
Internal voltage drop2.0V DC max @ 2 A
Off-state leakage current1 mA max @ 2V
Total output current7 A max
Current consumption: approximately 3.5 mA @ 24V DC
Current consumption: approximately 4.5 mA @ 30V DC
Current consumption: 1.5 mA max (1 mA @ 5V DC)
Channels 4 and 8: 1A @ 60 °C (140 °F); 2A @ 50 °C (122 °C)
4 A for 10ms @ 1Hz (channels 4 and 8)
Rockwell Automation Publication 1753-IN002C-EN-P - June 2010
(1) See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification
details.
(2) When used with specified firmware revisions.
Industrial Emissions
(Cat. 4) according to ISO 13849-1
(2)
: up to and including SIL 3 according to IEC 61508 and PLe
Additional Resources
The table below provides a listing of publications that contain important information about
GuardPLC systems.
ResourceDescription
GuardPLC Controller Systems Safety Reference
Manual, publication 1753-RM002
GuardPLC Controller Systems User Manual,
publication 1753-UM001
Using RSLogix Guard PLUS! Software with
GuardPLC Controllers Programming Manual,
publication 1753-PM001
Industrial Automation Wiring and Grounding
Guidelines, publication 1770-4.1
You can view or download publications at http://www.rockwellautomation.com/literature
order paper copies of technical documentation, contact your local Rockwell Automation
distributor or sales representative.
Detailed information regarding the safety certification of the
GuardPLC System
Detailed information on installing, wiring, configuring,
operating, maintaining, and troubleshooting GuardPLC
systems
Detailed information on programming your GuardPLC system
using RSLogix Guard PLUS! software
General guidelines for installing a Rockwell Automation
industrial system
. To
Allen-Bradley, Rockwell Software, Rockwell Automation, and GuardPLC are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel : +90 (216) 5698400
Rockwell Automation Publication 1753-IN002C-EN-P - June 2010PN-77077