Rockwell Automation 1753-L28BBB-MP User Manual

Page 1
Installation Instructions
GuardPLC 1600 Controllers
Catalog Numbers 1753-L28BBB-M, 1753-L28BBB-P
Top ic Pa ge
Important User Information 2 About the GuardPLC 1600 Controller 3 General Safety 3 Install the Controller 4 Mount the Controller 5 Ground the Controller 5 Wire the Controller 6 Make Communication Connections 12 Reset Push Button 14 Controller Tests 15 Status Indicators 16 Specifications 17 Additional Resources 20
Page 2
2

Important User Information

Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication
SGI-1.1
available from your local Rockwell Automation sales office or online at
http://www.rockwellautomation.com/literature/
equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
ATTENTION: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard and recognize the consequences.
) describes some important differences between solid-state
SHOCK HAZARD: Labels may be on or inside the equipment, for example, drive or motor, to alert people that dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, drive or motor, to alert people that surfaces may reach dangerous temperatures.
IMPORTANT
Identifies information that is critical for successful application and understanding of the product.
Rockwell Automation Publication 1753-IN001C-EN-P - June 2010
Page 3
3

About the GuardPLC 1600 Controller

The GuardPLC 1600 controller is a programmable electronic system featuring 20 digital inputs, 8 digital outputs, and 4 connections for GuardPLC Ethernet communication.
Ethernet Ports (on top of controller)
Voltage Supply
Connection
Ethernet Ports (on bottom of controller)

General Safety

ATTENTION: Personnel responsible for the application of safety-related
programmable electronic systems (PES) shall be aware of the safety requirements in the application of the system and shall be trained in using the system.

Prevent Electrostatic Discharge

ATTENTION: This equipment is sensitive to electrostatic discharge, which can
cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment:
Touch a grounded object to discharge static potential.
Wear an approved wrist-strap grounding device.
Do not touch connectors or pins on component boards.
Do not touch circuit components inside the equipment.
Use a static-safe workstation, if available.
Store the equipment in appropriate static-safe packaging when not in use.
Digital Outputs
Digital Inputs
Rockwell Automation Publication 1753-IN001C-EN-P - June 2010
Page 4
4

Environment and Enclosure

ATTENTION: This equipment is intended for use in a Pollution Degree 2
industrial environment, in overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes up to 2000 m (6562 ft) without derating.
This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR 11. Without appropriate precautions, there may be difficulties with electromagnetic compatibility in residential and other environments due to conducted as well as radiated disturbances.
This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame spread rating of 5VA, V2, V1, V0 (or equivalent) if non-metallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.
In addition to this publication, see:
Industrial Automation Wiring and Grounding Guidelines, Rockwell
Automation publication 1770-4.1
NEMA 250 and IEC 60529, as applicable, for explanations of the degrees of
protection provided by different types of enclosure.
, for additional installation requirements.

Install the Controller

Follow these steps to install the GuardPLC 1600 controller.
1. Mount the controller to a DIN rail.
2. Ground the controller.
3. Wire the controller.
4. Make communication connections.
This publication describes these steps in detail.
Rockwell Automation Publication 1753-IN001C-EN-P - June 2010
Page 5

Mount the Controller

5
IMPORTANT
For effective cooling, mount the controller following these guidelines.
Mount the controller horizontally.
Provide a gap of at least 100 mm (3.94 in.) above and below the controller.
Select a location where air flows freely or use an additional fan.
Do not mount the controller over a heating device.
The controller cannot be panel-mounted. Mount the controller to a DIN rail by following these steps.
1. Hook the top slot over the DIN rail.
2. Insert a flathead screwdriver into the gap
between the housing and the latch and pull the latch downward.
3. Hold the latch down as you push the housing back onto the DIN rail.
4. Release the latch to lock the device onto the rail.
TIP
To remove the controller from the DIN rail, insert a flathead screwdriver into the gap between the housing and the latch and pull the latch downward as you lift the controller off of the rail.
(3)
(2)
(1) Top Slot
DIN Rail
Latch

Ground the Controller

The controller is functionally grounded through its DIN rail connection. A protective earth-ground connection is required and is provided through a separate grounding screw on the
upper left of the housing and marked with the grounding symbol .
You must also provide an acceptable grounding path for each device in your application. For more information on proper grounding guidelines, refer to the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1
ATTENTION: This product is grounded through the DIN rail to chassis ground. Use zinc-plated yellow-chromate steel DIN rail to assure proper grounding. The use of other DIN rail materials (for example, aluminum or plastic) that can corrode, oxidize, or are poor conductors, can result in improper or intermittent grounding. Secure the DIN rail to the mounting surface approximately every 200 mm (7.8 in.) and use end-anchors appropriately.
Rockwell Automation Publication 1753-IN001C-EN-P - June 2010
.
Page 6
6

Wire the Controller

The following sections describe how to connect the voltage supply and wire the controller’s digital inputs and outputs.

Connect the Voltage Supply

The 24V DC voltage supply must feature galvanic isolation (in accordance with EN 60950 or UL 1950) since inputs and outputs are not electrically isolated from the processor. To comply with CE Low Voltage Directives (LVD) and UL restrictions, you must use either a Safety Extra Low Voltage (SELV), or a Protected Extra Low Voltage (PELV) power supply to power this controller. A SELV supply cannot exceed 30V rms, 42.4V peak, or 60V DC under normal conditions and under single-fault conditions. A PELV supply has the same rating and is connected to protected earth.
IMPORTANT
IMPORTANT
The supply voltage is connected via a 4-pin connector that accommodates wire sizes up to
2.5 mm2 (14 AWG). You need to connect only one wire to L+ and one wire to L-. Both L+ and L- terminals are internally connected, so you can daisy-chain 24V DC power from the GuardPLC controller to other devices in the panel by using the remaining terminal.
Protect the controller with a slow-blowing fuse.
The GuardPLC 1600 controller can draw up to 8 A. The controller needs 0.5 A to operate. Up to 7.5 A can be used to source voltage power for inputs and outputs connected to the controller.
ATTENTION: Do not reverse the L+ and L- terminals or damage to the controller will result. There is no reverse polarity protection.
Rockwell Automation Publication 1753-IN001C-EN-P - June 2010
Page 7
7

Safety-related Digital Inputs

The controller has 20 digital inputs whose status is indicated via status indicators when the controller is in RUN mode.
LS+ is a voltage source that provides 24V DC for a group of four dry contact inputs. There are five groups on the GuardPLC 1600 controller.
COM
24V DC Power
+
Supply
(—)4(—)
3
L-L- L+ L+
24V DC
RS-485
L-L- L+ L+
PROFIBUS
MODBUS
24V DC
COMM1
COMM2 COMM3
GuardPLC Ethernet
10/100 BaseT
(—)4(—)
3
Connection of Voltage Supply to
Input Device
If devices require 24V DC to operate and use the same power source as the controller, then wire the outputs of the device directly to inputs on the controller.
COM
24V DC Power
+
Supply
(—)4(—)
3
L-L- L+ L+
24V DC
RS-485
L-L- L+ L+
MODBUS
PROFIBUS
24V DC
COMM1
COMM2 COMM3
GuardPLC Ethernet
10/100 BaseT
(—)4(—)
3
Connection of Voltage Supply to
Input Device
123456
1234
1L-
24 V DC
RUN
ERROR
PROG
FORCE
FAULT
1LS+- L-D1234
OSL
BL
13 14 15 16 17 18
1LS+- LS+ LS+ LS+ LS+L-D1234
13 14 1516 17 18
13 14 15 16 23 24
123456
1234
1L-
24 V DC
RUN
ERROR
PROG
FORCE
FAULT
1LS+- L-D1234
OSL
BL
13 14 15 16 17 18
1LS+- LS+ LS+ LS+ LS+L-D1234
13 14 1516 17 18
13 14 15 16 23 24
789101112
78910
56
L-DO 2
34
(2A)
56
L-DO 2
34
(2A)
11 12
5L- L-DO 6
7 8
(2A)
5L-D1678
9L-D11011 12
19 20 2122 23 24
25 26 2728 29 30
19 20 2122 23 2413 14 1516 23 24 25 26 2728 29 30 31 3233 34 35 36 37 38 39 40 41 42
789101112
78910
11 12
5L- L-DO 6
7 8
(2A)
5L-D1678
9L-D11011 12
19 20 2122 23 24
25 26 2728 29 30
19 20 2122 23 2413 14 1516 23 24 25 26 2728 29 30 31 32 33 34 35 36 37 38 39 40 41 42
31 32 3334 35 36
13 L-D11415 16
13 L-D11415 16
31 32 3334 35 36
1753-L28BBBM
20 DC Inputs 8 DC Outputs
1753-L28BBBM
20 DC Inputs 8 DC Outputs
17 L-D11819 20
37 38 3940 41 42
17 L-D11819 20
37 38 3940 41 42
COM
+
Light Curtain
(or any Safety Input)
Rockwell Automation Publication 1753-IN001C-EN-P - June 2010
Page 8
8
Devices with their own dedicated power supply can also be connected. Connect the reference pole of the external power supply to the L- reference pole of the input.
COM
24V DC
Power
+
Supply
(—)4(—)
3
L-L- L+ L+
24V DC
RS-485
L-L- L+ L+
MODBUS
PROFIBUS
24V DC
COMM1
COMM2 COMM3
GuardPLC Ethernet
10/100 BaseT
(—)4(—)
3
Connection of Devices with Dedicated Power Supplies
123456
1234
1L-
24 V DC
RUN
ERROR
PROG
FORCE
FAULT
OSL
BL
34
1LS+- L-D1234
13 14 15 16 17 18
1LS+- LS+ LS+ LS+ LS+L-D1234
13 14 15 16 17 18
13 14 15 16 23 24
(or any Safety Input)
789101112
78910
56
L-DO 2
(2A)
11 12
5L- L-DO 6
7 8
(2A)
5L-D1678
9L-D11011 12
25 26 27 28 29 30
13 L-D11415 16
31 32 33 34 35 36
19 20 21 22 23 24
19 20 21 22 23 2413 14 15 16 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42
COMCOM
+
+
Light Curtain
1753-L28BBBM
20 DC Inputs 8 DC Outputs
37 38 39 40 41 42
24V DC
Power Supply
17 L-D11819 20
The safe state of an input is indicated by a 0 signal being passed to the user program logic. If the test routines detect a fault in the digital inputs, a 0 signal is processed in the user program for the defective channel. When a fault occurs, the inputs are switched off (0).
Follow the closed-circuit principle for external wiring when connecting sensors. To create a safe state in the event of a fault, the input signals revert to the de-energized state (0). The FAULT status indicator activates.
TIP
For more information on input wiring, see the GuardPLC Controller Systems User Manual, publication number 1753-UM001.
Digital Input Terminals
DI
1LS+- LS+LS+LS+LS+L-
234
13 14 15 16 17 18
Rockwell Automation Publication 1753-IN001C-EN-P - June 2010
DI
5L-
678
19 20 21 22 23 24
DI
9L-
10 11 12
25 26 27 28 29 30
DI
19 20 21 22 23 2413 14 15 16 17 18 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42
13 L-
14 15 16
31 32 33 34 35 36
DI
17 L-
18 19 20
37 38 39 40 41 42
Page 9
9
Terminals accommodate wires up to 1.5 mm on page 17
Terminal Number Designation Function
13 LS+ Sensor supply for inputs 1…4 14 1 Digital input 1 15 2 Digital input 2 16 3 Digital input 3 17 4 Digital input 4 18 L- Reference pole 19 LS+ Sensor supply for inputs 5…8 20 5 Digital input 5 21 6 Digital input 6 22 7 Digital input 7 23 8 Digital input 8 24 L- Reference pole 25 LS+ Sensor supply for inputs 9 …12 26 9 Digital input 9 27 10 Digital input 10 28 11 Digital input 11 29 12 Digital input 12 30 L- Reference pole 31 LS+ Sensor supply for inputs 13…16 32 13 Digital input13 33 14 Digital input 14 34 15 Digital input 15 35 16 Digital input 16 36 L- Reference pole 37 LS+ Sensor supply for inputs 17…20 38 17 Digital input 17 39 18 Digital input 18 40 19 Digital input 19 41 20 Digital input 20 42 L- Reference pole
. Digital inputs are connected to these terminals.
2
(16 AWG). See the terminal torque specifications
LS+, not L+, should be used for short-circuit protection. Each LS+ features individual short-circuit and EMC protection that make it important to use LS+ for only its four related inputs.
Rockwell Automation Publication 1753-IN001C-EN-P - June 2010
Page 10
10

Line Control

Line control is a short-circuit and line-break monitoring system (that is, E-stop inputs) that can be configured for the GuardPLC 1600 system. Up to eight digital outputs (DO1 configured as pulsed outputs. The example below shows two pulse outputs connected to the digital inputs (DI) of the same system. As a result, the connections to the digital inputs (DI) are monitored.
DO 1 2
Emergency OFF 1 Emergency OFF 2
DO8) can be
DI 1 2
Inputs are set to 0, a fault code is generated, and the FAULT status indicator is on when:
DI 3 4
a short-circuit occurs between two parallel connections.
two connections are reversed.
earth fault occurs on one of the lines (only with earthed reference pole).
a line breaks or one of the contacts opens (that is, when one of the E-stop off switches is
pressed in the example above).
IMPORTANT
For information on how to configure inputs and outputs for line control, see the GuardPLC Controller Systems User Manual, publication 1753-UM001
.

Safety-related Digital Outputs

The controller has eight digital outputs (DO1…DO8) whose status is indicated via status indicators.
An output is in a safe state when it is de-energized. When a fault occurs, all outputs are switched off.
Outputs 1…3 and 5…7 can have a load of 0.5 A at an ambient temperature of 60 °C (140 °F). Outputs 4 and 8 can each have a load of 1 A at an ambient temperature of 60 °C (140 °F), or up to 2 A at an ambient temperature of 50 °C (122 °F).
With an overload, one or all of the outputs are turned off. When the overload is eliminated, the outputs are activated again according to the specified value.
Although the external line of an output is not monitored, a short-circuit will be indicated.
Rockwell Automation Publication 1753-IN001C-EN-P - June 2010
Page 11
11
Digital Output Terminals
123456
1234
56
1L- L-DO 2
34
(2A)
Terminals accommodate wires up to 1.5 mm2 (16 AWG). See the terminal torque specifications on page 17
. Digital outputs are connected to these terminals.
Terminal Number Designation Function Current
1 L- Reference pole — 2 1 Digital output 1 0.5 A 3 2 Digital output 2 0.5 A 4 3 Digital output 3 0.5 A 5 4 Digital output 4 (for increased load) 2.0 A 6 L- Reference pole — 7 L- Reference pole — 8 5 Digital output 5 0.5 A
9 6 Digital output 6 0.5 A 10 7 Digital output 7 0.5 A 11 8 Digital output 8 (for increased load) 2.0 A 12 L- Reference pole
789101112
78910
11 12
5L- L-DO 6
7 8
(2A)
For connection of a load, the reference pole L- of the corresponding channel group must be used (2-pole connection). Although L- at terminals 1 and 6 and at 7 and 12 is connected internally to L- on the power supply input, it is strictly recommended to use 1 and 6 for outputs 1…4 only and 7 and 12 for outputs 5… 8 only. EMC testing was performed in this manner.
Rockwell Automation Publication 1753-IN001C-EN-P - June 2010
Page 12
12
Example: Connecting Actuators to the Outputs
DO 1
DO 2
DO 3
DO 4L-L-
TIP
The digital outputs can be pulsed with the safety-related digital inputs of the same device. This enables short-circuit or line-break monitoring to be carried out (that is, emergency stop buttons to conform to Cat. 4 in EN954-1).
TIP
Inductive loads can be connected without a protection diode on the load. However, Rockwell Automation strongly recommends that a protection diode be fitted directly to the load to suppress any interference voltage. A 1N4004 diode is recommended.
ATTENTION: Pulse outputs may not be used as safety-related outputs.
For more information on output wiring, see the GuardPLC Controller Systems User Manual, publication 1753-UM001.

Make Communication Connections

The controller supports separate connections for safety and nonsafety-related communication.

Connections for Safety-related Communication

The controller has four 10/100BaseT, RJ45 connectors to provide communication via GuardPLC Ethernet protocol to distributed I/O and other GuardPLC controllers, OLE for Process Control (OPC) servers, and with the programming software. Connectors 1 and 2 are on the bottom side on the left. Connectors 3 and 4 are on the top side on the left. All four connectors and the GuardPLC processor are connected together by an internal Ethernet switch. The switches are auto-detect. Either crossover or straight-through Ethernet cabling can be used.
Star or line configurations are available. Make sure that a network loop is not generated. Data packets must be able to reach a node only via a single path.
Rockwell Automation Publication 1753-IN001C-EN-P - June 2010
Page 13
13
OPC Server
The GuardPLC 1600 controller is an OPC client. An OPC server, catalog number 1753-OPC, is available from Rockwell Automation and lets computer applications read and write data to and from the GuardPLC controller.
MAC Address
The media access control (MAC) address of the controller can be found on the label positioned over both lower RJ45 connections.

Connections for Nonsafety-related Communication

The three 9-pin D-shell connectors on the front of the controller provide the following communication options.
Designation Function
COMM1 (RS-485) Modbus Slave (1753-L28BBB-M)
COMM2 Not used COMM3 (RS-485) GuardPLC ASCII protocol
The pin assignments of the D-shell connector are listed in this table.
Profibus-DP-Slave (1753-L28BBB-P)
Connection Signal Function
1—— 2 RP 5V, decoupled with diodes 3 RxD/TxD-A Receive/transmit data A 4 CNTR-A Control signal A 5 DGND Data reference potential 6 VP 5V, positive pole of supply voltage 7—— 8 RxD/TxD-B Receive/transmit data B 9 CNTR-B Control signal B

IP Address and System ID (SRS)

A transparent label provided with the controller can be used to note the IP address and system ID (SRS). The default value for the IP address is 192.168.0.99. The default SRS is 60000.
IMPORTANT
If you attach the label to the controller, make sure you do not cover any of the ventilation slots.
Rockwell Automation Publication 1753-IN001C-EN-P - June 2010
Page 14
14

Reset Push Button

The controller is equipped with a reset push button. Reset via the push button is necessary under the following conditions.
You forget the password to go online via the programming software.
You are unable to determine the IP address and SRS of the controller.
The push button is accessible through a small round hole at the top of the housing, approximately 4…5 cm (1.6…2.0 in.) from the left rim and recessed approximately 9.5 mm (0.375 in.).
IMPORTANT
To reset, press and hold the push button for 20 seconds while rebooting the device by cycling power. Pressing the Reset push button during operation has no affect.
With activation of the reset button:
Activate the reset push button using an insulated pin to prevent short-circuits.
all accounts are deleted except for the default account.
IP Address and System ID (SRS) are set to their default values.
The next time you cycle power, these settings will be restored to the last values stored into nonvolatile memory. This means that either the settings prior to the reset will be restored, or if any settings were changed after the reset, those new settings will still be in effect.
Rockwell Automation Publication 1753-IN001C-EN-P - June 2010
Page 15
15

Controller Tests

In addition to the tests for safety, the controller tests the supply voltage and controller temperature.

Supply Voltage Tests

The supply voltage (24V DC) is monitored and the alarm and system shutdown are controlled according to the voltage levels listed below.
Voltage Level System Condition
19.3…28.8V Normal < 19.3V Alarm state 1 (internal variables are written) < 15.4V Alarm state 2 (prepares for shutdown) < 13.0V Switched off

Temperature Tests

The temperature of the controller is automatically and continuously monitored. The alarm is triggered by the temperature conditions described in this table.
Operating Temperature Alarm
< 60 °C (140 °F) None (normal) 60…70 °C (140…158 °F) Warning on > 70 °C (158 °F) Main alarm on Return to 64…54 °C (147.2…129.2 °F) Main alarm off, warning on Return to < 54 °C (129.2 °F) None (return to normal)
Rockwell Automation Publication 1753-IN001C-EN-P - June 2010
Page 16
16

Status Indicators

Indicator State Description
24V DC On 24V DC operating voltage present.
Off No operating voltage.
RUN On This is the normal status of the controller.
Flashing The controller is in STOP mode and is not executing a routine.
Off The controller is in ERROR_STOP mode (see ERROR).
ERROR On
Off No errors are detected.
PROGress On The upload of a new controller configuration is in progress.
Flashing The upload of a new operating system into the nonvolatile ROM is in progress. Off No upload of controller configuration or operating system in progress.
FORCE On The controller is executing a routine (RUN) and FORCE mode is activated by the user.
Flashing The controller is in STOP mode, but forcing has been initiated and will be activated
Off Forcing is OFF.
FAULT On
Flashing An error has occurred during a nonvolatile ROM write cycle.
Off None of the above errors has occurred.
OSL Flashing Emergency Operating System Loader is active. BL Flashing Boot Loader unable to load operating system or unable to start COMM operating
Controller status can be interrogated through the programming software. For more information, see the GuardPLC Controller Systems User Manual, publication 1753-UM001
A routine, which has been loaded into the controller, is executed. The controller processes input and output signals, carries out communication, and performs hardware and software tests.
All system outputs are reset. STOP mode can be triggered by setting the Emergency stop system variable to TRUE in the routine, or by direct command from the programming software.
A hardware error has been detected by the controller. The controller goes to
ERROR_STOP mode and the execution of the routine is halted. Hardware errors are errors in the controller, errors in one or more of the digital input and output modules, or errors in the counters.
A software error in the operating system has been detected by the controller.
The watchdog has reported an error due to exceeded cycle time.
All system outputs will be reset and the controller ceases all hardware and software tests. The controller can only be restarted by a command from the programming software.
when the controller is started.
The routine (logic) has caused an error.
The controller configuration is faulty.
The upload of a new operating system was not successful and the operating
system is corrupted.
One or more I/O errors have occurred.
system loader.
.
Rockwell Automation Publication 1753-IN001C-EN-P - June 2010
Page 17
17
Communication via GuardPLC Ethernet protocol is indicated by two small status indicators integrated into all connecting sockets.
Indicator State Description
Green On Full-duplex operation
Flashing Collision Off Half-duplex operation, no collision
Yellow On Connection established
Flashing Interface activity
Additional nonsafety-related communication occurs on the field buses and is indicated by these status indicators.
Indicator Connection Description
Green COMM 1 RS-485 interface, field bus active
COMM 2 Unassigned COMM 3 Unassigned

Specifications

Technical Specifications – GuardPLC 1600 Controllers
Attribute 1753-L28BBB-M, 1753-L28BBB-P
User Memory 250 KB max user program memory
250 KB max application data memory Watchdog, min 10 ms Safety time, min 20 ms Current consumption 8 A max (with max load)
Operating voltage 24V DC, -15% to 20%, w
Isolation voltage 50V (continuous), Basic Insulation Type, I/O to Ethernet and Ethernet to DC
Wiring category Wire size I/O – 0.13…1.3 mm
Wire type Shielded on Ethernet Terminal block torque 0.51 N•m (4.5 lb•in)
(1)
0.5 A idle current
≤ 15% (from a power supply with protective
separation conforming to IEC 61131-2 requirements)
power
Category 2 on communication ports, signal ports, and power ports
75 °C (167 °F) or greater with 1.2 mm (3/64 in.) insulation max
Power – 0.33…2.1 mm
at 75 °C (167 °F) or greater with 1.2 mm (3/64 in.) insulation max
Ethernet – RJ45 connector according to IEC 60603-7, 2-pair or 4-pair
Category 5e minimum cable according to TIA 568-B.1, or Category 5 cable according to ISO/IEC 24702
Comm: 9-pin D-sub
ss
2
(26…16 AWG) solid or stranded copper wire rated at
2
(22…14 AWG) solid or stranded copper wire rated
Rockwell Automation Publication 1753-IN001C-EN-P - June 2010
Page 18
18
Technical Specifications – GuardPLC 1600 Controllers
Attribute 1753-L28BBB-M, 1753-L28BBB-P
Fuse (external) 24V DC power: 10 A (time-lag) Enclosure type rating Meets IP20 Width, approx. 257 mm (10.1 in.) Height, approx. 114 mm (4.49 in.) including latch Depth, approx. 66 mm (2.60 in.) including grounding bolt Weight 1.2 kg (2.64 lb)
Digital Inputs
Number of inputs 20 (not electrically isolated) On-state Voltage: 15…30V DC
Current consumption: 2 mA @ 15V
7.5 mA @ 30V
Off-state Voltage: 5V DC max
Switching point typically 7.5V Supply 5 x 20V / 100 mA @ 24V short-circuit proof
Digital Outputs
Number of outputs 8 (not electrically isolated) Output voltage range 18.4…26.8V Output current Channels 1…3 and 5…7: 0.5 A @ 60 °C (140 °F)
Surge current per channel 1 A for 10ms @ 1Hz (Channels 1…3 and 5…7)
Current load, min 2 mA per channel On-state voltage drop 2.0V DC max @ 2 A Off-state leakage current 1 mA max @ 2V
(1) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication 1770-4.1
Current consumption: 1.5 mA max (1 mA @ 5V)
Channels 4 and 8: 1 A @ 60 °C (140 °F); 2 A @ 50 °C (122 °C)
4 A for 10ms @ 1Hz (Channels 4 and 8)
.
Rockwell Automation Publication 1753-IN001C-EN-P - June 2010
Page 19
Environmental Specifications – GuardPLC 1600 Controllers
Attribute 1753-L28BBB-M, 1753-L28BBB-P
Temperature, nonoperating
IEC 60068-2-1 (Test Ab, Unpackaged
nonoperating cold)
IEC 60068-2-2 (Test Bb, Unpackaged nonoperating
dry heat)
IEC 60068-2-14 (Test Na, Unpackaged
nonoperating thermal shock)
Temperature, operating
IEC 60068-2-1 (Test Ad, operating cold)
IEC 60068-2-2 (Test Bd, operating dry heat)
IEC 60068-2-14 (Test Nb, operating thermal
shock) Temperature, surrounding air 60 °C (140 °F) Vibration
IEC 60068-2-6 (Test Fc, operating) Shock, operating
-40…85 °C (-40…185 °F)
0…60 °C (32…140 °F)
1 g @ 10…150 Hz
15 g
IEC 60068-2-27 (Test Ea, unpackaged shock)
Relative humidity
10…95% noncondensing
IEC 60068-2-30 (Test Db, unpackaged damp heat)
Emissions CISPR 11: Group 1, Class A ESD Immunity
IEC 61000-4-2
Radiated RF Immunity
IEC 61000-4-3
6 kV contact discharges
8 kV air discharges
10V/m with 1kHz sine-wave 80% AM from 80
MHz…2000 MHz
1 V/m with 1 kHz sine-wave 80% AM from
2000…2700 MHz
EFT/B Immunity
IEC 61000-4-4
±2 kV @ 5 kHz on DC power ports
±1 kV @ 5 kHz on signal ports
±1 kV @ 5 kHz on communication ports
Surge Transient Immunity
IEC 61000-4-5
±500V line-line (DM) and ±500V line-earth (CM) on
DC power ports
±1 kV line-earth (CM) on signal ports
±1 kV line-earth (CM) on communication ports
Conducted RF Immunity
IEC 61000-4-6
Damped Oscillatory Wave Immunity
IEC 61000-4-12
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
±1 kV line-earth (CM) on signal ports
±1 kV line-earth (CM) on power ports
19
Rockwell Automation Publication 1753-IN001C-EN-P - June 2010
Page 20
Certifications
Certification (when product is marked)
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL
CE European Union 2004/108/EC EMC Directive, compliant with:
1753-L28BBB-M, 1753-L28BBB-P
(1)
File E65584.
EN 61326-1 Meas./Control/Lab., Industrial Requirements
EN 61000-6.2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11;
Functional Safety Certified by TÜV
(1) See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification
details.
(2) When used with specified firmware revisions.
Industrial Emissions
(Cat. 4) according to ISO 13849-1
(2)
: up to and including SIL 3 according to IEC 61508 and PLe

Additional Resources

The table below provides a listing of publications that contain important information about GuardPLC systems.
Resource Description
GuardPLC Controller Systems Safety Reference Manual, publication 1753-RM002
GuardPLC Controller Systems User Manual, publication 1753-UM001
Using RSLogix Guard PLUS! Software with GuardPLC Controllers Programming Manual, publication 1753-PM001
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1
You can view or download publications at http://www.rockwellautomation.com/literature order paper copies of technical documentation, contact your local Rockwell Automation distributor or sales representative.
Detailed information regarding the safety certification of the GuardPLC System
Detailed information on installing, wiring, configuring, operating, maintaining, and troubleshooting GuardPLC systems
Detailed information on programming your GuardPLC system using RSLogix Guard PLUS! software
General guidelines for installing a Rockwell Automation industrial system
. To
Allen-Bradley, Rockwell Software, Rockwell Automation, and GuardPLC are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel : +90 (216) 5698400
Rockwell Automation Publication 1753-IN001C-EN-P - June 2010 PN-77076
Supersedes Publication 1753-IN001B-EN-P - March 2004 Copyright © 2010 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.
Loading...