2 GuardPLC 16-Digital Inputs and 8-Digital Outputs Module
Important User Information
Solid state equipment has operational characteristics differing from those of electromechanical equipment.
Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication
SGI-1.1 available from your local Rockwell Automation sales office or online at
http://www.ab.com/manuals/gi) describes some important differences between solid state equipment and
hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of
uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves
that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages
resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many
variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot
assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits,
equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell
Automation, Inc. is prohibited.
Throughout this manual, when necessary we use notes to make you aware of safety considerations.
WARNING
Identifies information about practices or circumstances that can cause an explosion in a
hazardous environment, which may lead to personal injury or death, property damage,
or economic loss.
IMPORTANT
ATTENTION
SHOCK HAZARD
BURN HAZARD
Identifies information that is critical for successful application and understanding of the
product.
Identifies information about practices or circumstances that can lead to personal injury
or death, property damage, or economic loss. Attentions help you:
• identify a hazard
• avoid a hazard
• recognize the consequence
Labels may be located on or inside the equipment (e.g., drive or motor) to alert people
that dangerous voltage may be present.
Labels may be located on or inside the equipment (e.g., drive or motor) to alert people
that surfaces may be dangerous temperatures.
Publication 1753-IN011A-EN-P - October 2005
GuardPLC 16-Digital Inputs and 8-Digital Outputs Module 3
Related Documentation
The table below provides a listing of publications that contain important
information about GuardPLC systems.
ForRead this documentPublication
number
Detailed information regarding the safety certification
of the GuardPLC System
Detailed information on installing, wiring, configuring,
operating, maintaining, and troubleshooting GuardPLC
systems
Detailed information on programming your GuardPLC
system using RSLogix Guard PLUS! software
Information on installing GuardPLC 1600 controllersGuardPLC 1600 Controller
Information on installing GuardPLC 1800 controllersGuardPLC 1800 Controller
Information on installing GuardPLC 1753-IB20XOB8
Digital Input/Output Modules
Information on installing GuardPLC 1753-IB16 Digital
Input Modules
Information on installing GuardPLC 1753-OB16 Digital
Output Modules
Information on installing GuardPLC 1753-IB8XOB8
Digital Input/Output Modules
Information on installing GuardPLC 1753-OW8 Relay
Output Modules
Information on installing GuardPLC 1753-IF8XOF4
Analog Input/Output Modules
Planning informationIndustrial Automation Wiring and
GuardPLC Controller Systems
Safety Reference Manual
GuardPLC Controller Systems User
Manual
Using RSLogix Guard PLUS!
Software with GuardPLC
Controllers Programming Manual
Installation Instructions
Installation Instructions
GuardPLC Digital Input/Output
Module
GuardPLC Digital Input Module
Installation Instructions
GuardPLC Digital Output Module
Installation Instructions
GuardPLC 8-Digital Inputs and
8-Digital Outputs Modules
Installation Instructions
GuardPLC Analog Input/Output
Module Installation Instructions
Grounding Guidelines
1753-RM002
1753-UM001
1753-PM001
1753-IN001
1753-IN002
1753-IN003
1753-IN004
1753-IN005
1753-IN010
1753-IN012
1753-IN013
1770-4.1
To view and download pdfs, go to Literature Library at
http://www.rockwellautomation.com/literature.
To order printed copies, contact your Allen-Bradley Distributor or Rockwell
Automation Sales Office.
Publication 1753-IN011A-EN-P - October 2005
4 GuardPLC 16-Digital Inputs and 8-Digital Outputs Module
Description
The 1753-IB16XOB8 digital input/output module is a distributed I/O module for
use with GuardPLC controllers. The module features 16 digital inputs, 8 two-pole (8
positive-switching and 8 negative-switching) digital outputs, and 2 pulsed outputs
as shown below.
Personnel responsible for the application of safety-related
Programmable Electronic Systems (PES) shall be aware of the
safety requirements in the application of the system and shall be
trained in using the system.
Publication 1753-IN011A-EN-P - October 2005
GuardPLC 16-Digital Inputs and 8-Digital Outputs Module 5
ATTENTION
Environment and Enclosure
This equipment is intended for use in a Pollution Degree 2 industrial environment, in
overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes up to
2000 meters without derating.
This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR
Publication 11. Without appropriate precautions, there may be potential difficulties ensuring
electromagnetic compatibility in other environments due to conducted as well as radiated
disturbance.
This equipment is supplied as "open type" equipment. It must be mounted within an
enclosure that is suitably designed for those specific environmental conditions that will be
present and appropriately designed to prevent personal injury resulting from accessibility to
live parts. The interior of the enclosure must be accessible only by the use of a tool.
Subsequent sections of this publication may contain additional information regarding
specific enclosure type ratings that are required to comply with certain product safety
certifications.
See NEMA Standards publication 250 and IEC publication 60529, as applicable, for
explanations of the degrees of protection provided by different types of enclosure. Also, see
the appropriate sections in this publication, as well as the Allen-Bradley publication 1770-4.1
("Industrial Automation Wiring and Grounding Guidelines"), for additional installation
requirements pertaining to this equipment.
Preventing Electrostatic Discharge
ATTENTION
This equipment is sensitive to electrostatic discharge, which can
cause internal damage and affect normal operation. Follow these
guidelines when you handle the module:
• Touch a grounded object to discharge static potential.
• Wear an approved wrist-strap grounding device.
• Do not touch connectors or pins on component boards.
• Do not touch circuit components inside the equipment.
• If available, use a static-safe workstation.
• When not in use, store the equipment in appropriate static
safe packaging.
Publication 1753-IN011A-EN-P - October 2005
6 GuardPLC 16-Digital Inputs and 8-Digital Outputs Module
Mount the Module
IMPORTANT
The module cannot be panel-mounted. Mount the module to a DIN rail by
following the four steps below.
1. Hook the top slot over the DIN rail.
2. Insert a flathead screwdriver into the
gap between the housing and the latch
and pull the latch downward.
3. Hold the latch down as you push the
housing back onto the DIN rail.
4. Release the latch to lock the device
onto the rail.
TIP
For effective cooling:
• Mount the module horizontally.
• Provide a gap of at least 100 mm (3.94 in.) above and below
the module.
• Select a location where air flows freely or use an additional
fan.
• Do not mount the module over a heating device.
(3)
(2)
Latch
To remove the module from the DIN rail, insert a flathead
screwdriver into the gap between the housing and the latch
and pull the latch downward as you lift the module off of the
rail.
(1) Top Slot
DIN Rail
IP Address Label
A transparent label shipped with the module can be used to note the IP address
and system ID (SRS).
IMPORTANT
Publication 1753-IN011A-EN-P - October 2005
If you attach the label to the module, make sure you do not cover
any of the ventilation slots.
GuardPLC 16-Digital Inputs and 8-Digital Outputs Module 7
Wire the Module
The following sections describe how to wire the module.
Ground the Module
You must also provide an acceptable grounding path for each device in your
application. For more information on proper grounding guidelines, refer to the
Industrial Automation Wiring and Grounding Guidelines, publication number
1770-4.1.
The module is functionally grounded through its DIN rail connection. A protective
earth ground connection is required and is provided through a separate grounding
screw, located on the upper left of the housing and marked with the grounding
symbol .
ATTENTION
This product is grounded through the DIN rail to chassis ground.
Use zinc plated yellow-chromate steel DIN rail to assure proper
grounding. The use of other DIN rail materials (e.g. aluminum,
plastic, etc.) that can corrode, oxidize, or are poor conductors,
can result in improper or intermittent grounding.
Connections for Safety-Related Communications
Ethernet Switch
The module has two 10/100BaseT, RJ-45 connectors to provide communications via
GuardPLC Ethernet to GuardPLC controllers, and with the programming software.
The connectors are located on the bottom side on the left. The connectors and the
module are connected together by an internal Ethernet switch. The switches are
auto-detect. Either cross-over or straight-through shielded Ethernet cabling can be
used.
Star or line configurations are available. Make sure that a network loop is not
generated. Data packets must only be able to reach a node via a single path.
MAC Address
The Media Access Control (MAC) Address of the module can be found on the label
positioned over both lower RJ-45 connections.
Publication 1753-IN011A-EN-P - October 2005
8 GuardPLC 16-Digital Inputs and 8-Digital Outputs Module
Connect the Voltage Supply
The 24V dc voltage supply must feature galvanic isolation (in accordance with
EN 60950 or UL 1950) since inputs and outputs are not electrically isolated from the
processor. In order to comply with CE Low Voltage Directives (LVD), you must use
either a NEC Class 2, a Safety Extra Low Voltage (SELV) or a Protected Extra Low
Voltage (PELV) power supply to power this adapter. An SELV supply can’t exceed
30V rms, 42.4V peak or 60V dc under normal conditions and under single fault
conditions. A PELV supply has the same rating and is connected to protected earth.
IMPORTANT
The supply voltage is connected via a 4-pin connector. See page 22 for the
appropriate wire size. You only need to connect one wire to L+ and one wire to L-.
Both L+ and L- terminals are internally connected, so you can daisy-chain 24V dc
power from the module to other devices in the panel using the remaining terminal.
ATTENTION
Protect the module with a 12 A slow-blow fuse.
Do not reverse the L+ and L- terminals or damage to the module
will result. There is no reverse polarity protection.
Publication 1753-IN011A-EN-P - October 2005
GuardPLC 16-Digital Inputs and 8-Digital Outputs Module 9
Safety-Related Digital Inputs
The module has 16 digital inputs whose status is indicated via LED indicators when
the controller or module is in the RUN mode. Refer to page 4 for location of digital
inputs and LED indicators.
LS+ is a voltage source that provides 24V dc for a group of four inputs.
If devices require 24V dc to operate and use the same power source as the
GuardPLC, wire the outputs of the device directly to inputs on the GuardPLC.
COM
24V dc
Power
+
Supply
25 26 27 28 29 30 3231
2222
1111
PO PULSE TEST
1753-IB16XOB8
16 DC Inputs
8 DC Outputs
LS+ LS+13 14 15 16 L-L-
63 64 65 66 67 68 69 70 71 72
24 V DC
RUN
ERROR
PROG
FORCE
FAULT
OSL
BL
GuardPLC Ethernet
10/100 BaseT
(—)2(—)
1
L-L- L+ L+
24V DC
DO +-
1
2
3
4
5
6
7
8
DI
LS+ LS+ 1 2 3 4 L-L-
33 34 35 36 37 38 39 40 41 42
123456 87
S+
S+ S+ S+ S- S- S- S-
91011121314 1615
1- 1+ 2- 2+ 3- 3+ 4+4- 5- 5+ 6- 6+ 7- 7+ 8+8-
DODO
DIDIDI
LS+ LS+5 6 7 8 L-L-
43 44 45 46 47 48 49 50 51 52
LS+ LS+ 9 10 11 12 L-L-
53 54 55 56 57 58 59 60 61 62
17 18 19 20 21 22 2423
Connection of voltage supply
to input device
Light Curtain
(or any Safety Input Device)
COM
+
Publication 1753-IN011A-EN-P - October 2005
10 GuardPLC 16-Digital Inputs and 8-Digital Outputs Module
Devices with their own dedicated power supply can also be connected instead of
contacts. Connect the reference pole of the signal source to the L- reference pole of
the input.
COM
24V dc
Power
+
Supply
25 26 27 28 29 30 3231
2222
1111
PO PULSE TEST
1753-IB16XOB8
16 DC Inputs
8 DC Outputs
LS+ LS+13 14 15 16 L-L-
63 64 65 66 67 68 69 70 71 72
L-L-L+ L+
24V DC
DO +-
PROG
FORCE
FAULT
RUN
OSL
BL
1
2
3
4
5
6
7
8
DI
LS+ LS+ 1 2 3 4 L-L-
33 34 35 36 37 38 39 40 41 42
24 V DC
ERROR
GuardPLC Ethernet
10/100 BaseT
(—)2(—)
1
Connection of devices with dedicated
power supplies
Light Curtain
(or any Safety Input Device)
123456 87
S+
S+ S+ S+ S- S- S- S-
LS+ LS+5 6 7 8 L-L-
43 44 45 46 47 48 49 50 51 52
COM
+
DIDI
LS+ LS+ 9 10 11 12 L-L-
53 54 55 56 57 58 59 60 61 62
24V dc
Power
+
Supply
17 18 19 20 21 22 2423
91011121314 1615
1- 1+ 2- 2+ 3- 3+ 4+4- 5- 5+ 6- 6+ 7- 7+ 8+8-
DODO
COM
The safety state of an input is indicated by a 0 signal being passed to the user
program logic. If the test routines detect a fault in the digital inputs, a 0-signal is
processed in the user program for the defective channel. When a fault occurs, the
inputs are switched off (0) and the fault LED indicator is activated.
Publication 1753-IN011A-EN-P - October 2005
GuardPLC 16-Digital Inputs and 8-Digital Outputs Module 11
The sensor supplies, LS+, supply a default current of 40 mA that is buffered for 20
ms in case of a power failure. If a higher current is needed, two unbuffered
supplies of 1 A can be switched on using the DI Supply [xx] system signal in the
application program. This supply feeds the neighboring input channel group. The
status of this supply is read and the supply is switched off if an overcurrent
condition occurs. This supply is protected by a current limiting device. The
following illustration shows two digital input supplies for four different input
groups.
L+ not bufferedL+ buffered
Current
limiting
1 A
LS+
53
LS+
54
LS+
63
Current
limiting
40 mA
LS+
64
Current
limiting
40 mA
LS+
33
L+ not bufferedL+ buffered
LS+
43
Current
limiting
40 mA
LS+
44
Current
limiting
1 A
LS+
34
Current
limiting
40 mA
Follow the closed-circuit principle for external wiring when connecting sensors. To
create a safe state in the event of a fault, the input signals revert to the de-energized
state (0). Although the external line is not monitored, a wire break is interpreted as
a safe 0-signal. Unused inputs must not be terminated.
TIP
For more information on input wiring, see the GuardPLC
System User Manual, publication number 1753-UM001.
Publication 1753-IN011A-EN-P - October 2005
12 GuardPLC 16-Digital Inputs and 8-Digital Outputs Module
See page 22 for the appropriate wire size. Digital inputs are connected to the
following terminals:
Terminal Number Designat ionFunction
33LS+Sensor supply for inputs 1 to 4, 40 mAbuffered/1 A non-buffered
34LS+Sensor supply for inputs 1 to 4, 40 mAbuffered/1 A non-buffered
351Digital input 1
362Digital input 2
373Digital input 3
384Digital input 4
39L-Reference pole
40L-Reference pole
41GroundShield
42GroundShield
43LS+Sensor supply for inputs 5 to 8, 40 mA buffered/1 A non-buffered
44LS+Sensor supply for inputs 5 to 8, 40 mA buffered/1 A non-buffered
455Digital input 5
466Digital input 6
477Digital input 7
488Digital input 8
49L-Reference pole
50L-Reference pole
51GroundShield
52GroundShield
53LS+Sensor supply for inputs 9 to 12, 40 mA buffered/1 A non-buffered
54LS+Sensor supply for inputs 9 to 12, 40 mA buffered/1 A non-buffered
559Digital input 9
5610Digital input 10
Publication 1753-IN011A-EN-P - October 2005
GuardPLC 16-Digital Inputs and 8-Digital Outputs Module 13
Terminal Number Designat ionFunction
5711Digital input 11
5812Digital input 12
59L-Reference pole
60L-Reference pole
61GroundShield
62GroundShield
63LS+Sensor supply for inputs 13 to 16, 40 mA buffered/1 A non-buffered
64LS+Sensor supply for inputs 13 to 16, 40 mA buffered/1 A non-buffered
6513Digital input 13
6614Digital input 14
6715Digital input 15
6816Digital input 16
69L-Reference pole
70L-Reference pole
71GroundShield
72GroundShield
Surge on Digital Inputs
An EN 61000-4.5 surge impulse can be read as a short duration HI signal. To avoid
an error:
• install shielded input lines to prevent effects of surges in the system, or
• implement software filtering in the user program. A signal must be present
for at least two cycles before it is used by the rest of the logic in the user
program.
Line Control
Line control is a short-circuit and line break monitoring system (for example, E-Stop
inputs) which can be configured for the GuardPLC system.
IMPORTANT
For information on how to configure inputs and outputs for line
control, see the GuardPLC System User Manual, publication
number 1753-UM001.
Publication 1753-IN011A-EN-P - October 2005
14 GuardPLC 16-Digital Inputs and 8-Digital Outputs Module
Pulse Test Sources
ATTENTION
Pulse test sources must not be used as safety-related outputs.
The example shows 2 pulse test sources connected to the digital inputs (DI) of the
same system. As a result, the connections to the digital inputs (DI) are monitored
for line control.
PO 1 2
Emergency OFF 1Emergency OFF 2
DI 1 2DI 3 4
When line control detects any of the following faults, inputs are set to 0, a fault
code is generated, and the FAULT LED indicator is on.
• short-circuit between two parallel connections
• reversal of two connections
• earth fault on one of the lines (only with earthed reference pole)
• line break or opening of the contacts (e.g., when one of the E-stop off
switches is pressed in the example above), the FAULT LED indicator is on
and the fault code is generated.
Publication 1753-IN011A-EN-P - October 2005
GuardPLC 16-Digital Inputs and 8-Digital Outputs Module 15
Pulsed Output Terminals
25 26 27 28 29 303231
11112222
All PO1 and PO2 terminals are internally connected. Therefore all PO1 and PO2
terminals pulse together.
Terminal Number DesignationFunction
251Pulsed output 1
261Pulsed output 1
271Pulsed output 1
281Pulsed output 1
292Pulsed output 2
302Pulsed output 2
312Pulsed output 2
322Pulsed output 2
Safety-Related Digital Outputs
The module has 8 output pairs whose status is indicated via LED indicators. The
digital outputs are not electrically isolated.
An output is in the safe state when it is de-energized. If a channel faults, the
affected outputs are switched off. If the module faults or loses ethernet
communications, all outputs are switched off.
An overload at an output causes the output to turn off. If the total current is greater
then 9 A, all outputs are turned off. When the overload is eliminated, the outputs
are activated according to their current software-driven state.
Publication 1753-IN011A-EN-P - October 2005
16 GuardPLC 16-Digital Inputs and 8-Digital Outputs Module
Actuator
The digital outputs can be configured as:
• 1-pole switch without line monitoring
• 2-pole switch with or without line monitoring
• 3-pole switch (2-pole with common reference).
Refer to the GuardPLC Controller Systems User Manual, publication number
1753-UM001 for more information.
1-pole Connection
For 1-pole applications, all 8 DO+ and all 8 DO- outputs are available, for a total of
16 outputs. If you are using a positive-switching output, connect the other side of
the output to S-. If you are using a negative-switching output, connect the other
side of the output to S+.
The DO+ outputs must be connected to the supply S- and the DO- outputs must be
connected to the supply S+.
Line monitoring with a 1-pole connection is not possible.
IMPORTANT
You must not connect the DO+ output directly to L- or connect
the DO- outputs directly to L+. You must use the S+ and Sterminals.
For 1-pole connection, Inductive loads can be connected without a protection
diode on the load because there is a protection diode located within the GuardPLC
device. However, Rockwell Automation recommends that you attach a protection
diode directly to the load to suppress any interference voltage. A 1N4004 diode is
recommended.
1753-IB16XOB8
S+
1+
1-
S-
2+
2-
Publication 1753-IN011A-EN-P - October 2005
GuardPLC 16-Digital Inputs and 8-Digital Outputs Module 17
Actuator
2-pole Connection
If the outputs are configured for 2-pole operation, 8 total outputs are available.
Each of the 8 outputs switch both L+ and L-. 2-pole outputs (without line
monitoring) are wired to both DO+ and DO- of a single channel, 2+ and 2- for
example.
DO 2+
DO 2-
IMPORTANT
ATTENTION
ATTENTION
The corresponding channels for the 2-pole connection must be
configured for 2-pole operation using the DO[xx].2-pole system
variable. Refer to the GuardPLC Controller Systems User Manual,
publication number 1753-UM001 for more information.
The DO+ output must be connected to the corresponding DOoutput of the same channel.
Inductive loads must be connected with a protection diode on the
load in 2-pole connection.
1753-IB16XOB8
Publication 1753-IN011A-EN-P - October 2005
18 GuardPLC 16-Digital Inputs and 8-Digital Outputs Module
Load
3-pole Connection With Line Monitoring
Two 2-pole channels can support dual channel devices with only a single reference
connection. If line monitoring is required, the channels must be configured in pairs,
using the DO[xx][xx].in pairs system parameter. There are four pairs allowed:
• channels 1 and 2,
• channels 3 and 4,
• channels 5 and 6,
• and channels 7 and 8.
Line monitoring is accomplished by switching off one channel while the second
channel is tested for wiring faults.
A detected line fault is reported by the module’s error codes.
1753-IB16XOB8
(drive, valve)
ATTENTION
Inductive loads must be connected with a protection diode on the
load in 3-pole connection.
Publication 1753-IN011A-EN-P - October 2005
Digital Output Terminals
GuardPLC 16-Digital Inputs and 8-Digital Outputs Module 19
123456 87
S+
S+ S+ S+ S- S- S- S-
91011121314 1615
1- 1+ 2- 2+ 3- 3+4+4-5- 5+ 6- 6+ 7- 7+8+8DODO
17 18 19 20 21 222423
See page 22 for the appropriate wire size. Digital outputs are connected to the
following terminals:
Terminal Number DesignationFunction
1S+Reference pole for negative-switching digital outputs
2S+Reference pole for negative-switching digital outputs
3S+Reference pole for negative-switching digital outputs
4S+Reference pole for negative-switching digital outputs
5S-Reference pole for positive-switching digital outputs
6S-Reference pole for positive-switching digital outputs
7S-Reference pole for positive-switching digital outputs
8S-Reference pole for positive-switching digital outputs
91-Digital output 1, negative-switching
101+Digital output 1, positive-switching
112-Digital output 2, negative-switching
122+Digital output 2, positive-switching
133-Digital output 3, negative-switching
143+Digital output 3, positive-switching
154-Digital output 4, negative-switching
164+Digital output 4, positive-switching
175-Digital output 5, negative-switching
185+Digital output 5, positive-switching
196-Digital output 6, negative-switching
206+Digital output 6, positive-switching
217-Digital output 7, negative-switching
Publication 1753-IN011A-EN-P - October 2005
20 GuardPLC 16-Digital Inputs and 8-Digital Outputs Module
Terminal Number DesignationFunction
227+Digital output 7, positive-switching
238-Digital output 8, negative-switching
248+Digital output 8, positive-switching
Reset Pushbutton
You can use the reset button if you forget the password for connecting the
programming software. The pushbutton is accessible through a small round hole at
the top of the housing, approximately 4 to 5 cm (1.6 to 2.0 in.) from the left rim and
recessed approximately 9.5 mm (0.375 in.).
IMPORTANT
To reset, press and hold the pushbutton for 20 seconds while rebooting the device
by cycling power. Pressing the Reset pushbutton during operation has no affect.
With activation of the reset button:
• All accounts are deleted except for the default account.
• IP address and system ID (SRS) are set to default values.
At the next power cycle, these settings will be restored to the last values stored into
Flash. This means that either:
• the settings prior to the reset will be restored, or
• if any settings were changed after the reset, these new settings will still be in
effect.
Activate the reset pushbutton using an insulated pin to prevent
short-circuits.
Publication 1753-IN011A-EN-P - October 2005
GuardPLC 16-Digital Inputs and 8-Digital Outputs Module 21
Troubleshoot with LED Indicators
IndicatorStateCondition
24V dcOn24V dc operating voltage present.
OffNo operating voltage.
RUNOnThis is the normal status of the module.
Flashing The module is in STOP mode and is not executing a routine.
OffThe module is in ERROR_STOP (see ERROR).
ERROROn• A hardware error has been detected by the module. The module goes to
OffNo errors are detected.
PROGressOnThe upload of a new module configuration is in progress.
Flashing The upload of a new operating system into the Flash ROM is in progress.
OffNo upload of module configuration or operating system in progress.
FORCEOnThe module is executing a routine (RUN) and FORCE mode is activated by the user.
Flashing The module is in STOP, but Forcing has been initiated and will be activated when the
OffForcing is OFF.
FAULTOn• The routine (logic) has caused an error.
Flashing An error has occurred during a Flash ROM write cycle.
OffNone of the above errors has occurred.
OSLFlashing Emergency Operating System Loader is active.
BLFlashing Boot Loader unable to load operating system or unable to start COMM operating
Module status can be interrogated through the programming software. For more information, refer to the
GuardPLC System User Manual, publication number 1753-UM001.
A routine, which has been loaded into the module, is executed.
The module processes input and output signals, carries out communication and
performs hardware and software tests.
All system outputs are reset.
STOP mode can be triggered by setting the Emergency stop system variable to TRUE
in the routine, or by direct command from the programming software.
ERROR_STOP and the execution of the routine is halted. Hardware errors are
errors in the module, errors in one or more of the digital input and output
modules, or errors in the counters.
• A software error in the operating system has been detected by the module.
• The watchdog has reported an error due to exceeded cycle time.
All system outputs will be reset and the module ceases all hardware and software
tests. The module can only be restarted by a command from the programming
software.
module is started.
• The module configuration is faulty.
• The upload of a new operating system was not successful and the operating
system is corrupted.
One or more I/O errors have occurred.
system loader.
Publication 1753-IN011A-EN-P - October 2005
22 GuardPLC 16-Digital Inputs and 8-Digital Outputs Module
Specifications
Module
Response Time≥ 10 ms
Interface: GuardPLC
Ethernet
Operating Voltage24V dc, -15% to +20%, w
Current Consumptionmax. 10 A (with max. load)
Isolation VoltageNo isolation between circuits
Wiring Category
Wire Size
(1)
2 x RJ-45, 10/100BaseT (with 100 Mbps) with integrated switch
≤ 15%
ss
0.6 A @ 24V idle current
category 2 on communications ports, signal ports, and power ports
I/O – 16 AWG (1.5 mm
rated at 75 °C (167 °F) or greater with 3/64 inch (1.2 mm) insulation max.
2
) to 26 AWG (0.14 mm2) solid or stranded copper wire
Power – 14 AWG (2.5 mm
rated at 75 °C (167 °F) or greater with 3/64 inch (1.2 mm) insulation max.
Terminal Block Torque0.51 Nm (4.5 in-lb)
Fuse (external)12 A (slow blow)
Battery Backupnone
Digital Inputs
No. of Inputs16 (not electrically isolated)
On-stateVoltage: 15V to 30V dc
Off-stateVoltage: max. 5V dc
Switching Pointtypically 7.5V
Supply4 supplies @ 24V dc/40 mA short-circuit proof, buffered for 20 ms
Digital Outputs
No. of Outputs (L+)8 (not electrically isolated), reference pole SNo. of Outputs (L-)8 (not electrically isolated), reference pole S+
Output Voltage≥L+ minus 2V
Output Current (L+)
Output Current (L-)
Max. lamp load25 W
Max. inductive load500 mH
Minimum Load2 mA per channel
Internal Voltage Dropmax. 2.0V dc @ 2 A
Off-State Leakage Currentmax. 1 mA @ 2V
Overload ResponseShut down of the concerned output with cyclic reconnection
Current Consumption: ≥ 2 mA @ 15V
Current Consumption: max 1.5 mA (1.0 mA @ 5V)
2 supplies @ 24V dc/1 A short-circuit proof, non-buffered
Channels 2, 4, 5, and 7: 0.5 A @ 60°C (140°F)
Channels 1 and 8: 1 A @ 60 °C (140 °F); 2 A @ 40 °C (104 °C)
Channels 3 and 6: 1 A @ 60 °C (140 °F)
2
) to 22 AWG (0.34 mm2) solid or stranded copper wire
Publication 1753-IN011A-EN-P - October 2005
GuardPLC 16-Digital Inputs and 8-Digital Outputs Module 23
Total Output Currentmax. 8 A
Pulsed Outputs
No. of Outputs2 (not electrically isolated)
Output Voltage≥L+ minus 4V
Output Current (L+)Approx. 60 mA
Minimum Loadnone
Switching Time≤ 100 micro-seconds
Overload Response2 x ≥ 19.2V, short-circuit current 60 mA @ 24V
• IEC 60068-2-30 (Test Db, unpackaged non-operating damp heat)
EmissionsGroup 1, Class A
ESD Immunity6 kV contact discharges
8 kV air discharges
Radiated RF Immunity10V/m with 1kHz sine-wave 80% AM from 80 MHz to 2000 MHz
EFT/B Immunity±2 kV @ 5 kHz on power ports
±1 kV @ 5 kHz on signal ports
±1 kV @ 5 kHz on communication ports
Surge Transient Immunity±1 kV line-line (DM) and ±1 kV line-earth (CM) on DC power ports
±500V line-line (DM) and ±1 kV line-earth (CM) on signal ports
±1 kV line-earth (CM) on communication ports
Conducted RF Immunity10Vrms with 1 kHz sine-wave 80% AM from 150 kHz to 80 MHz
Enclosure Type Ratingmeets IP20
Mechanical Dimensions
Width205 mm (8.07 in.) including housing screws
Height114 mm (4.49 in.) including latch
Depth88 mm (3.46 in.) including grounding bolt
Weight1.3 kg (2.86 lb)
Publication 1753-IN011A-EN-P - October 2005
Certifications
(2)
(when product is marked)
c-UL-usUL Listed Industrial Control Equipment, certified for US and Canada
CEEuropean Union 89/336/EEC EMC Directive, compliant with:
AS/NZS CISPR 11; Industrial Emissions
TÜVTÜV Certified for Functional Safety
(1) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication number 1770-4.1.
(2) See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and other certification
details.
Allen-Bradley, Rockwell Automation, and GuardPLC are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Publication 1753-IN011A-EN-P - October 2005PN 40071-199-01(1)