Important User Information2
About the Module3
General Safety3
Install the Module4
Mount the Module5
Ground the Module5
Wire the Module6
Make Connections for Safety-related
Communication
Reset Push Button10
Status Indicators11
Specifications12
Additional Resources14
10
Page 2
2 GuardPLC Digital Input Module
Important User Information
Solid-state equipment has operational characteristics differing from those of electromechanical equipment.
Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication
SGI-1.1
available from your local Rockwell Automation sales office or online at
http://www.rockwellautomation.com/literature/
equipment and hard-wired electromechanical devices. Because of this difference, and also because of the
wide variety of uses for solid-state equipment, all persons responsible for applying this equipment must
satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages
resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many
variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot
assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits,
equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell
Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can
cause an explosion in a hazardous environment, which may lead to personal
injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can
lead to personal injury or death, property damage, or economic loss.
Attentions help you identify a hazard, avoid a hazard and recognize the
consequences.
) describes some important differences between solid-state
SHOCK HAZARD: Labels may be on or inside the equipment, for example,
drive or motor, to alert people that dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example,
drive or motor, to alert people that surfaces may reach dangerous
temperatures.
IMPORTANT
Identifies information that is critical for successful application and
understanding of the product.
Rockwell Automation Publication 1753-IN004C-EN-P - June 2010
Page 3
GuardPLC Digital Input Module 3
About the Module
The 1753-IB16 digital input module is a 16-channel input module for use with
GuardPLC controllers.
Voltage Supply Connection
Digital Inputs
Ethernet Ports
(on bottom of controller)
Digital Inputs
General Safety
ATTENTION: Personnel responsible for the application of safety-related
programmable electronic systems (PES) shall be aware of the safety
requirements in the application of the system and shall be trained in using the
system.
Preventing Electrostatic Discharge
ATTENTION: This equipment is sensitive to electrostatic discharge, which can
cause internal damage and affect normal operation. Follow these guidelines
when you handle this equipment:
• Touch a grounded object to discharge static potential.
• Wear an approved wrist-strap grounding device.
• Do not touch connectors or pins on component boards.
• Do not touch circuit components inside the equipment.
• Use a static-safe workstation, if available.
• Store the equipment in appropriate static-safe packaging when not in use.
Pulsed Outputs
Rockwell Automation Publication 1753-IN004C-EN-P - June 2010
Page 4
4 GuardPLC Digital Input Module
Environment and Enclosure
ATTENTION: This equipment is intended for use in a Pollution Degree 2
industrial environment, in overvoltage Category II applications (as defined in
IEC publication 60664-1), at altitudes up to 2000 m (6562 ft) without derating.
This equipment is considered Group 1, Class A industrial equipment according
to IEC/CISPR 11. Without appropriate precautions, there may be difficulties
with electromagnetic compatibility in residential and other environments due
to conducted as well as radiated disturbances.
This equipment is supplied as open-type equipment. It must be mounted within
an enclosure that is suitably designed for those specific environmental
conditions that will be present and appropriately designed to prevent personal
injury resulting from accessibility to live parts. The enclosure must have
suitable flame-retardant properties to prevent or minimize the spread of flame,
complying with a flame spread rating of 5VA, V2, V1, V0 (or equivalent) if
non-metallic. The interior of the enclosure must be accessible only by the use
of a tool. Subsequent sections of this publication may contain additional
information regarding specific enclosure type ratings that are required to
comply with certain product safety certifications.
In addition to this publication, see:
• Industrial Automation Wiring and Grounding Guidelines, Rockwell
Automation publication 1770-4.1
• NEMA 250 and IEC 60529, as applicable, for explanations of the degrees of
protection provided by different types of enclosure.
, for additional installation requirements.
Install the Module
Follow these steps to install the module.
1. Mount the module to a DIN rail.
2. Ground the module.
3. Wire the module.
4. Make connections for safety-related communication.
This publication describes these steps in detail.
Rockwell Automation Publication 1753-IN004C-EN-P - June 2010
Page 5
Mount the Module
GuardPLC Digital Input Module 5
IMPORTANT
For effective cooling, mount the module following these guidelines.
• Mount the module horizontally.
• Provide a gap of at least 100 mm (3.94 in.) above and below the module.
• Select a location where air flows freely or use an additional fan.
• Do not mount the module over a heating device.
The module cannot be panel-mounted. Mount the module to a DIN rail by following these
steps.
1. Hook the top slot over the DIN rail.
2. Insert a flathead screwdriver into the gap
between the housing and the latch and pull
the latch downward.
3. Hold the latch down as you push the housing
back onto the DIN rail.
4. Release the latch to lock the module onto the
rail.
TIP
To remove the module from the DIN rail, insert a flathead screwdriver into
the gap between the housing and the latch and pull the latch downward as
you lift the module off of the rail.
(3)
(2)
(1) Top Slot
DIN Rail
Latch
Ground the Module
The module is functionally grounded through its DIN rail connection. A protective earth
ground connection is required and is provided through a separate grounding screw on the upper
left of the housing and marked with the grounding symbol .
You must also provide an acceptable grounding path for each device in your application. For
more information on proper grounding guidelines, refer to the Industrial Automation Wiring
and Grounding Guidelines, publication 1770-4.1
ATTENTION: This product is grounded through the DIN rail to chassis ground.
Use zinc-plated yellow-chromate steel DIN rail to assure proper grounding. The
use of other DIN rail materials (for example, aluminum or plastic) that can
corrode, oxidize, or are poor conductors, can result in improper or intermittent
grounding. Secure DIN rail to mounting surface approximately every 200 mm
(7.8 in.) and use end-anchors appropriately.
Rockwell Automation Publication 1753-IN004C-EN-P - June 2010
.
Page 6
6 GuardPLC Digital Input Module
Wire the Module
The following sections describe how to connect the voltage supply and connect the inputs and
outputs.
Connect the Voltage Supply
To comply with CE Low Voltage Directives (LVD) and UL restrictions, you must use either a
Safety Extra Low Voltage (SELV), or a Protected Extra Low Voltage (PELV) power supply to
power this module. A SELV supply cannot exceed 30V rms, 42.4V peak, or 60V DC under
normal conditions and under single-fault conditions. A PELV supply has the same rating and is
connected to protected earth.
IMPORTANT
Protect the module with a 4 A slow-blow fuse.
The supply voltage is connected via a 4-pin connector that accommodates wire sizes up to
2
(14 AWG). You need to connect only one wire to L+ and one wire to L-. Both L+ and
2.5 mm
L- terminals are internally connected, so you can daisy-chain 24V DC power from the module to
other devices in the panel by using the remaining terminal.
ATTENTION: Do not reverse the L+ and L- terminals or damage to the module
will result. There is no reverse polarity protection.
Safety-related Digital Inputs
The module has 16 digital inputs (DI1…DI16) and 4 pulsed test-sources (PO1…PO4) whose
status is indicated via status indicators.
LS+ is a voltage source that provides 24V DC for a group of four dry contact inputs. There are
four groups on the module.
COM
24V DC
Power
+
Supply
789101112
789101112
5L-
D1
L-L-L+ L+
24V DC
123456
123456
1LS+ LS+LS+L-D1234
Connection of Voltage Supply to Input Device
13 14 15 16 17 18
13 14 15 16 17 18
6789L-
10 11 12
D1
Rockwell Automation Publication 1753-IN004C-EN-P - June 2010
Page 7
GuardPLC Digital Input Module 7
If devices require 24V DC to operate and use the same power source as the module, then wire the
outputs of the device directly to inputs on the module.
Light Curtain
(or any Safety Input)
24V DC
Power
Supply
COM
+
COM
+
L-L-L+ L+
24V DC
123456
123456
1LS+ LS+LS+L-D1234
789101112
789101112
5L-
D1
13 14 15 16 17 18
13 14 15 16 17 18
6789L-
10 11 12
D1
Connection of Voltage Supply to Input Device
Devices with their own dedicated power supply can also be connected. Connect the reference
pole of the external power supply to the L- reference pole of the input.
Light Curtain
(or any Safety Input)
COMCOM
24V DC
Power
+
24V DC
Power
Supply
COM
+
+
789101112
789101112
5L-
6789L-
D1
L-L-L+ L+
24V DC
123456
123456
1LS+ LS+LS+L-D1234
Supply
13 14 15 16 17 18
13 14 15 16 17 18
10 11 12
D1
Connection of Devices with Dedicated Power Supplies
The safe state of an input is indicated by a 0 signal being passed to the user program. If the test
routines detect a fault in the digital inputs, a 0 signal is processed in the user program for the
defective channel. When a fault occurs, the inputs are switched off (0) and the FAULT indicator
is activated.
Follow the closed-circuit principle for external wiring when connecting sensors. To create a safe
state in the event of a fault, the input signals revert to the de-energized state (0). Although the
external line is not monitored, a wire break is interpreted as a safe (0) signal.
Rockwell Automation Publication 1753-IN004C-EN-P - June 2010
Page 8
8 GuardPLC Digital Input Module
Digital Input Terminals
DI
1LS+-LS+LS+LS+L-
234
DI
5L-
678
DI
9L-
10 11 12
DI
13L-
14 15 16
123456
1 2 3 4 5 67 8 9 1011 12131415161718192021222324
789101112
13 14 15 16 17 18
19 20 21 22 23 24
Terminals accommodate wires up to 1.5 mm2 (16 AWG). See the terminal torque specifications
on page 12
Terminal Number DesignationFunction
1LS+Sensor supply for inputs 1…4
21Digital input 1
32Digital input 2
43Digital input 3
54Digital input 4
6L-Reference pole
7LS+Sensor supply for inputs 5…8
85Digital input 5
96Digital input 6
107Digital input 7
118Digital input 8
12L-Reference pole
13LS+Sensor supply for inputs 9…12
149Digital input 9
1510Digital input 10
1611Digital input 11
1712Digital input 12
18L-Reference pole
19LS+Sensor supply for inputs 13…16
2013Digital input13
2114Digital input 14
2215Digital input 15
2316Digital input 16
24L-Reference pole
. Digital inputs (DI) are connected to the following terminals.
LS+, not L+, should be used for short-circuit protection. Each LS+ features individual
short-circuit and EMC protection that make it important to use LS+ for only its four related
inputs.
Rockwell Automation Publication 1753-IN004C-EN-P - June 2010
Page 9
GuardPLC Digital Input Module 9
Line Control
Line control is a short-circuit and line-break monitoring system, for example, E-stop inputs that
are configured for the 1753-IB16 system.
For line control, the device has four digital pulse test sources (PO) connected to the following
terminals.
Terminal Number DesignationFunction
25L-Reference pole
261Pulsed source 1
272Pulsed source 2
283Pulsed source 3
294Pulsed source 4
30L-Reference pole
The example below shows two pulse test sources connected to the digital inputs (DI) of the same
system. As a result, the connections to the digital inputs (DI) are monitored.
.
PO 1 2
Emergency OFF 1
DI 1 2DI 3 4
Emergency OFF 2
Inputs are set to 0, a fault code is generated, and the FAULT status indicator is on when:
• a short-circuit occurs between two parallel connections.
• two connections are reversed.
• earth fault occurs on one of the lines (only with earthed reference pole).
• a line breaks or one of the contacts opens (that is, when one of the E-stop off switches is
pressed in the example above).
IMPORTANT
For information on how to configure inputs and pulse test sources for line
control, see the GuardPLC Controller Systems User Manual, publication
1753-UM001.
Rockwell Automation Publication 1753-IN004C-EN-P - June 2010
Page 10
10 GuardPLC Digital Input Module
Make Connections for Safety-related Communication
The module has two 10/100BaseT, RJ45 connectors on the bottom of the unit, that provide
communication to the GuardPLC controller via GuardPLC Ethernet protocol. Because this is
an Ethernet switch, you can daisy-chain connections from the GuardPLC module to other
distributed I/O modules. The switch is auto-detect. Either crossover or straight-through cabling
can be used. Star or line configurations are available. Make sure that a network loop is not
generated. Data packets must be able to reach a node only via a single path.
The media access control (MAC) address of the module can be found on the label positioned
over both lower RJ45 connections.
A transparent label shipped with the module can be used to note the IP address and system
ID (SRS).
IMPORTANT
If you attach the label to the module, make sure you do not cover any of the
ventilation slots.
Reset Push Button
The module is equipped with a reset push button. Reset via the push button is necessary under
the following conditions.
• You forget the password to go online via the programming software.
• You are unable to determine the IP address and SRS of the controller.
The push button is accessible through a small round hole at the top of the housing,
approximately 4…5 cm (1.6…2.0 in.) from the left rim and recessed approximately 9.5 mm
(0.375 in.).
IMPORTANT
To reset, press and hold the push button for 20 seconds while rebooting the device by cycling
power. Pressing the Reset push button during operation has no affect.
With activation of the reset button:
• all accounts are deleted except for the default account.
• IP Address and System ID (SRS) are set to their default values.
The next time you cycle power, these settings will be restored to the last values stored into
nonvolatile memory. This means that either the settings prior to the reset will be restored, or if
any settings were changed after the reset, those new settings will still be in effect.
Activate the reset push button using an insulated pin to prevent short-circuits.
Rockwell Automation Publication 1753-IN004C-EN-P - June 2010
Page 11
GuardPLC Digital Input Module 11
Status Indicators
IndicatorStateDescriptin
24V DCOn24V DC operating voltage present.
OffNo operating voltage.
RUNOnThis is the normal status of the controller.
Flashing The controller is in STOP mode and is not executing a routine.
OffThe controller is in ERROR_STOP mode (see ERROR).
ERROROn
OffNo errors are detected.
PROGressOnThe upload of a new controller configuration is in progress.
Flashing The upload of a new operating system into the nonvolatile ROM is in progress.
OffNo upload of controller configuration or operating system in progress.
FORCEOnThe controller is executing a routine (RUN) and FORCE mode is activated by the user.
Flashing The controller is in STOP mode, but Forcing has been initiated, and will be activated
OffForcing is OFF.
FAULTOn
Flashing An error has occurred during a nonvolatile ROM write cycle.
OffNone of the above errors has occurred.
OSLFlashing Emergency Operating System Loader is active.
BLFlashing Boot Loader unable to load operating system or unable to start COMM operating
Module status can be interrogated through the programming software. For more information, refer to the
GuardPLC System User Manual, publication 1753-UM001
A routine, which has been loaded into the controller, is executed.
The controller processes input and output signals, carries out communication, and
performs hardware and software tests.
All system outputs are reset.
STOP mode can be triggered by setting the Emergency stop system variable to TRUE
in the routine, or by direct command from the programming software.
• A hardware error has been detected by the controller. The controller goes to
ERROR_STOP mode and the execution of the routine is halted. Hardware errors
are errors in the controller, errors in one or more of the digital input and output
modules, or errors in the counters.
• A software error in the operating system has been detected by the controller.
• The watchdog has reported an error due to exceeded cycle time.
All system outputs will be reset and the controller ceases all hardware and software
tests. The controller can only be restarted by a command from the programming
software.
when the controller is started.
• The routine (logic) has caused an error.
• The controller configuration is faulty.
• The upload of a new operating system was not successful and the operating
system is corrupted.
One or more I/O errors have occurred.
system loader.
.
Rockwell Automation Publication 1753-IN004C-EN-P - June 2010
Page 12
12 GuardPLC Digital Input Module
Specifications
Technical Specifications – 1753-IB16 Module
Attribute1753-IB16
Interfaces: GuardPLC
Ethernet
Operating voltage24V DC, -15…20%, w
Isolation voltage50V (continuous), Basic Insulation Type, I/O to Ethernet and Ethernet to DC
Wiring category
Wire size
Wire typeShielded on Ethernet
Terminal block torque0.51 N•m (4.5 lb•in)
Fuse (external)24V DC power: 10 A (time-lag)
Response time≥ 10 ms
Battery backupNone
Current consumption0.8 A max (with max load), 0.4 A idle current
Enclosure type ratingMeets IP20
Width, approx.152 mm (5.99 in.) including housing screws
Height, approx.114 mm (4.49 in.) including latch
Depth, approx.66 mm (2.60 in.) including grounding bolt
Weight, approx.0.7 kg (1.54 lb)
Digital Inputs
Number of inputs16 (not electrically isolated)
1 SignalVoltage: 15…30V DC, Current consumption: ≥ 2 mA @ 15V
0 SignalVoltage: 5V DC max, Current consumption:1.5 mA max (1 mA @ 5V)
Switching pointTypically 7.5V
Switching timeTypically 250 μs
Sensor supply4 x 19.2V / 40 mA @ 24V short-circuit proof
(1) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication 1770-4.1
(1)
2 x RJ45, 10/100BaseT (with 100 Mbit/s) with integrated switch
15% from a power supply with protective separation,
conforming to IEC 61131-2 requirements
power
Category 2 on communication ports, signal ports, and power ports
• I/O – 0.13…1.3 mm
75 °C (167 °F) or greater with 1.2 mm (3/64 in.) insulation max
• Power – 0.33…2.1 mm
at 75 °C (167 °F) or greater with 1.2 mm (3/64 in.) insulation max
ss
2
(26…16 AWG) solid or stranded copper wire rated at
2
(22…14 AWG) solid or stranded copper wire rated
• Ethernet – RJ45 connector according to IEC 60603-7, 2 or 4 pair Category
5e minimum cable according to TIA 568-B.1, or Category 5 cable according
to ISO/IEC 24702
.
Rockwell Automation Publication 1753-IN004C-EN-P - June 2010
(1) See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification
details.
(2) When used with specified firmware revisions.
Industrial Emissions
(2)
(Cat. 4) according to ISO 13849-1
: up to and including SIL 3 according to IEC 61508 and PLe
Additional Resources
The table below provides a listing of publications that contain important information about
GuardPLC systems.
ResourceDescription
GuardPLC Controller Systems Safety Reference
Manual, publication 1753-RM002
GuardPLC Controller Systems User Manual,
publication 1753-UM001
Using RSLogix Guard PLUS! Software with
GuardPLC Controllers Programming Manual,
publication 1753-PM001
Industrial Automation Wiring and Grounding
Guidelines, publication 1770-4.1
Detailed information regarding the safety certification of the
GuardPLC System
Detailed information on installing, wiring, configuring,
operating, maintaining, and troubleshooting GuardPLC
systems
Detailed information on programming your GuardPLC system
using RSLogix Guard PLUS! software
General guidelines for installing a Rockwell Automation
industrial system
You can view or download publications at http://www.rockwellautomation.com/literature
order paper copies of technical documentation, contact your local Rockwell Automation
distributor or sales representative.
Rockwell Automation Publication 1753-IN004C-EN-P - June 2010
. To
Page 15
GuardPLC Digital Input Module 15
Rockwell Automation Publication 1753-IN004C-EN-P - June 2010
Page 16
Rockwell Automation Support
Rockwell Automation provides technical information on the Web to assist you in using its products. At
http://www.rockwellautomation.com/support/
technical and application notes, sample code and links to software service packs, and a MySupport feature that
you can customize to make the best use of these tools.
For an additional level of technical phone support for installation, configuration and troubleshooting, we offer
TechConnect support programs. For more information, contact your local distributor or Rockwell Automation
representative, or visit http://www.rockwellautomation.com/support/
Installation Assistance
If you experience a problem within the first 24 hours of installation, please review the information that's
contained in this manual. You can also contact a special Customer Support number for initial help in getting your
product up and running.
Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the
manufacturing facility. However, if your product is not functioning and needs to be returned, follow these
procedures.
, you can find technical manuals, a knowledge base of FAQs,
.
at
, or contact
United States
Outside United States
Contact your distributor. You must provide a Customer Support case number (call the
phone number above to obtain one) to your distributor to complete the return process.
Please contact your local Rockwell Automation representative for the return
procedure.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to
improve this document, complete this form, publication RA-DU002
http://literature.rockwellautomation.com
Allen-Bradley, Rockwell Software, Rockwell Automation, and GuardPLC are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400
.
Rockwell Automation Publication 1753-IN004C-EN-P - June 2010PN-77079