Rockwell Automation 1606-XLS960 DC User Manual [en, de, es, fr, it]

1 EN 1606-XLS960 Instruction Manual DC Power Supply 2 DE 1606-XLS960 Bedienungsanleitung DC Stromversorgung 3 FR 1606-XLS960 Manual d'instructions DC Alimentation d'Énergie 4 ES 1606-XLS960 Manual de instrucciones DC Fuente De Alimentación 5 IT 1606-XLS960 Manuale di Istruzione DC Gruppo di alimentazione 6 PT 1606-XLS960 Manual de Instruções DC Fonte De Alimentação
1606-XLS960
Read this first! English 1
Before operating this unit please read this manual thoroughly and retain this manual for future reference! This device may only be installed and put into operation by qualified personnel. If damage or malfunction should occur during operation, immediately turn power off and send unit to the factory for inspection. The unit does not contain serviceable parts. The tripping of an internal fuse (if included) is caused by an internal defect. The information presented in this document is believed to be accurate and reliable and may change without notice. For any clarifications the English translation will be used.
Intended Use: This power supply is designed for installation in an enclosure and is intended for general use such as in industrial control, office, communication, and instrumentation equipment. Do not use this device in equipment, where malfunction may cause severe personal injury or threaten human life.
WARNING
Risk of electrical shock, fire, personal injury or death.
1) Do not use the power supply without proper grounding (Protective Earth).
2) Turn power off before working on the device. Protect against inadvertent re-powering.
3) Make sure that the wiring is correct by following all local and national codes.
4) Do not modify or repair the unit.
5) Do not open the unit as high voltages are present inside.
6) Use caution to prevent any foreign objects from entering the housing.
7) Do not use in wet locations or in areas where moisture or condensation can be expected.
8) Do not touch during power-on, and immediately after power-off. Hot surfaces may cause burns.
Vor Inbetriebnahme lesen! Deutsch 2
Bitte lesen Sie diese Warnungen und Hinweise sorgfältig durch, bevor Sie das Gerät in Betrieb nehmen. Bewahren Sie die Anleitung zum Nachlesen auf. Das Gerät darf nur durch fachkundiges und qualifiziertes Personal installiert werden. Bei Funktionsstörungen oder Beschädigungen schalten Sie sofort die Versorgungsspannung ab und senden das Gerät zur Überprüfung ins Werk. Das Gerät beinhaltet keine Servicebauteile. Interne Sicherungen (falls vorhanden) lösen nur bei Gerätedefekt aus. Die angegebenen Daten dienen allein der Produktbeschreibung und sind nicht als zugesicherte Eigenschaften im Rechtssinne aufzufassen. Im Zweifelsfall gilt der englische Text. Bestimmungsgemäßer Gebrauch: Diese Stromversorgung ist für den Einbau in ein Gehäuse konzipiert und zur Verwendung für allgemeine elektronische Geräte, wie z.B. Industriesteuerungen, Bürogeräte, Kommunikationsgeräte oder Messgeräte geeignet. Benutzen Sie dieses Gerät nicht in Steuerungsanlagen, in denen eine Funktionsstörung zu schweren Verletzungen führen oder Lebensgefahr bedeuten kann.
WARNUNG
Missachtung nachfolgender Punkte kann einen elektrischen Schlag, Brände, schwere Unfälle oder Tod zur Folge haben.
1) Betreiben Sie die Stromversorgung nie ohne Schutzleiter.
2) Schalten Sie die Eingangsspannung vor Installations-, Wartungs- oder Änderungsarbeiten ab und sichern Sie diese gegen unbeabsichtigtes Wiedereinschalten.
3) Sorgen Sie für eine ordnungsgemäße und fachgerechte Verdrahtung .
4) Führen Sie keine Änderungen oder Reparaturversuche am Gerät durch.
5) Gerät niemals öffnen. Im Inneren befinden sich gefährliche Spannungen.
6) Verhindern Sie das Eindringen von Fremdkörpern, wie z.B. Büroklammern und Metallteilen.
7) Betreiben Sie das Gerät nicht in feuchter Umgebung oder in einer Umgebung, bei der mit Betauung oder Kondensation zu rechnen ist.
8) Gehäuse nicht während des Betriebes oder kurz nach dem Abschalten berühren. Heiße Oberflächen können Verletzungen verursachen.
CAUTION
Reduction of output current may be necessary when:
1) Minimum installation clearance can not be met.
2) Altitude is higher than 2000m.
3) Device is used above +60°C ambient.
4) Mounting orientation is other than output and input terminal located at the bottom of the unit.
5) Airflow for convection cooling is obstructed.
VORSICHT
Rücknahme der Ausgangsleistung kann erforderlich sein:
1) wenn die minimalen Einbauabstände nicht eingehalten werden kön nen.
2) bei Aufstellhöhen über 2000m.
3) Betrieb bei Umgebungstemperaturen über +60°C.
4) bei Einbaulagen abweichend von der Standardeinbaulage (Eingang und Ausgang an der Unterseite des Gerätes).
5) bei behinderter Luftzirkulation.
siaçnarF !noisnet suos esim tnava eril A 3
Merci de lire ces instructions de montage et d'entretien avant de mettre l'alimentation sous tension. Conservez ce manuel qui vous sera toujours utile. Cette alimentation doit être installée par du personnel qualifié et compétent. Le déclenchement du fusible i nterne traduit très probablement un défaut au niveau de l'appareil. Si un défaut quelconque app araît en cours de fonctionnement, débrancher au plus vite l'alimentation. Dans ce deux cas de figure, il convient de faire contrôler l'alimentation en usine! Les données indiquées dans ce document servent uniquement à donn er une description du produit et n'ont aucune valeur juridique. En cas de divergences, le texte anglais fait foi.
Utilisation: Cet appareil est conçu pour être installé dans une armoire et pour tous les équipements électroniques, tel que l'équipement industriel de commande, l'équipement de bureau, le matériel de communication et les instruments de mesures. N'utilisez pas cet appareil sur des installations dans lesquels un problème de fonctionnement de l'alimentation pourrait causer des blessures graves ou menacer la vie humaine.
AVERTISSEMENT ATTENTION
Prendre en compte les points suivants, afin d'éviter toute détérioration électrique, incendie, dommage aux personnes ou mort.
1) ne jamais faire fonctionner l'alimentation sans raccordement à la terre !
2) débrancher l'installation avant toute intervention sur l'alimentation (ou démontage) et s'assurer qu'il n'y a pas risque de redémarrage.
3) s'assurer que le câblage a été fait selon les prescriptions
4) ne pas effectuer de réparations ou modifications sur l'alimentation
5) ne pas ouvrir l'appareil. Des tensions importantes passent à l'intérieur.
6) veiller à ce qu'aucun objet ne rentre en contact avec l'intérieur de l'alimentation (trombones, pièces métalliques)
7) ne pas faire fonctionner l'appareil dans un environnement humide ou à l'extérieur, non protégé. Ne pas utiliser l'appareil dans un environnement où il peut y avoir de la condensation.
8) ne pas toucher le carter pendant le fonctionnement ou après la mise sous tension. Surface chaude risquant d’entraîner des blessures.
Des limitations de puissance de sortie peuvent apparaître si :
1) les distances d'installation mini. ne peuvent être observées
2) installation à une altitude > 2000 m
3) pour des fonctionnements en charge et avec une température ambiante > 60°C
4) pour des positions de montage différentes de la préconisation standard (entrée en sortie dessous)
5) lorsque la circulation d'air est gênée
1606-XLS960: Power Supply Instruction Manual 1606-XLS960: Bedienungsanleitung für Stromversorgung
Lea primero! Español 4
Conserve este manual como referencia para futuras consultas. La fuente de alimentación solo puede ser instalada y puesta en funcionamiento por personal cuali ficado. Por favor lea detenidamente este manual antes de conectar la fuente de alimentación. Cuando se funde un fusible interno, existe gran prob abilidad de un fallo interno en el equipo.Si se produce un fallo o mal funcionamiento durante la operación, desconecte inmediatamente la tensión de alimentación. En ambos casos, el equipo debe ser inspeccionado en fábrica. La información presentada en este documento es exacta y fiable en cuanto a la descripción del producto y puede cambiar sin aviso. En casa de duda, prevalece el texto inglés.
Uso apropiado: Este equipo ha sido diseñado para su instalación en un ambiente cerrado y ha sido concebido para uso general en instalaciones de control industrial, oficinas, comunicaciones y equipos de instrumentación. No emplee esta unidad en equipos, donde un mal funcionamiento puede ocasionar lesiones graves o riesgo mortal.
ADVERTENCIA
Riesgo de descarga eléctrica, incendio, accidente grave o muerte.
1) No conectar nunca la unidad sin conexión de puesta a tierra.
2) Desconectar la tensión de red antes de trabajar en la fuente de alimentación. Evite una posible reconexión involuntaria.
3) Asegurarse de que el cableado es correcto de acuerdo a los códigos locales y nacionales.
4) No realizar ninguna modificación o reparación de la unidad.
5) No abrir nunca la unidad. En el interior existe riesgo de altas tensiones.
6) Evitar la introducción en la carcasa de objetos extraños.
7) No usar el equipo en ambientes húmedos. No operar el equipo en ambientes donde se espere la formación de rocío o condensación.
8) No tocar durante el funcionamiento ni inmediatamente después del apagado. El calor de la superficie puede causar quemaduras graves
ATENCIÓN
La deriva en la tensión de salida se produce:
1) cuando no pueden mantenerse las distancias mínimas de montaje.
2) en caso de que el montaje se realice en altitudes superiores a los 2000 m.
3) en caso de funcionamiento a plena carga y temperaturas ambientales superiores a +60ºC.
4) En caso de posiciones de montaje diferentes a la posición de montaje estándar (terminales abajo).
5) en caso de que la circulación de aire para la refrigeración por conducción esté obstruida.
Puede encontrar más detalles del caso de deriva en este manual.
Leggere prima questa parte! Italiano 5
Prima di collegare il sistema di alimentazione elettrica si prega di leggere attentamente le seguenti avvertenze. Conservare le istruzioni per la consultazione futura. Il sistema di alimentazione elettrica deve essere installato solo da personale competente e qualificato. In caso di intervento del fusibile interno, molto probabilmente l'apparecchio è guasto. Se durante il funzionamento si verificano anomalie o guasti, scollegare immediatamente la tensione di alimentazione. In entrambi i casi è necessario far controllare l'apparecchio dal produttore! I dati sono indicati solo a scopo descrittivo del prodotto e non vanno considerati come caratteristiche garantite dell'apparecchio.In caso di differenze o problemi è valido il testo inglese Uso previsto: Questo apparecchio è previsto per il montaggio in un rack per moduli elettronici, ad esempio per controllori industriali, apparecchiature per ufficio, unità di comunicazione o apparecchi di misura. Non utilizzare questo apparecchio in apparati o impianti dove il malfunzionamento può causare danni alla persona o pericolo di vita.
AVVERTENZA
Il mancato rispetto delle seguenti norme può provocare folgorazione elettrica, incendi, gravi incidenti e perfino la morte.
1) Non far funzionare in nessun caso il sistema di alimentazione elettrica senza conduttore di protezione!
2) Prima di eseguire interventi di installazione, di manutenzione o di modifica scollegare la tensione di rete ed adottare tutti i provvedimenti necessari per impedirne il ricollegamento non intenzionale.
3) Assicurare un cablaggio regolare e corretto.
4) Non tentare di modificare o di riparare da soli l'apparecchio.
5) Non aprire l'apparecchio. Al suo interno sono applicate tensioni elettriche pericolose.
6) Impedire la penetrazione di corpi estranei nell'appar ecc hio, ad ese mpio ferm ag li o altri ogg etti metallici.
7) Non far funzionare l'apparecchio in un ambiente umido. Non far funzionare l'apparecchio in un ambiente soggetto alla formazione di condensa o di rugiada.
8) Non toccare quando acceso e subito dopo lo spegnimento. La superficie calda può causare scottature.
ATTENZIONE
È necessario ridurre la potenza di uscita se:
1) non è possibile rispettare le distanze minime di montaggio;
2) l'apparecchio viene installato in un luogo di altitudine maggiore di 2000 m;
3) il funzionamento è a pieno carico a temperatura ambiente maggiore di +60°C;
4) la posizione di montaggio differisce da quella standard (ingresso, uscita in basso)
5) è ostacolata la libera circolazione dell'aria.
Leia primeiro! Portuguès 6
Recomendamos a leitura cuidadosa das seguintes advertências e observações, antes de colocar em funcionamento a fonte de alimentação. Guarde as Instruções para futura consulta, em casos de dúvida. A fonte de alimentação deverá ser instalada apenas por profissionais da área, tecnicamente qualificados. Se o fusível interno se fundir, é grande a possibilidade de existir um defeito no aparelho. Se por acaso, durante a utilização ocorrer algum defeito de funcionamento ou dano, desligue imediatamente a tensão de alimentação. Em ambos os casos, será necessária uma verificação na Fábrica! Os dados mencionados têm como finalidade somen te a descrição do produto, e não devem ser interpr eta dos como propriedades garantidas no sentido jurídico. Em caso de duvidas aplica-se o texto em inglês.
Utilize: Este aparelho foi concebido para ser montado dentro de invólucros, caixas ou armários para aparelhos eletrônicos em geral, como, por exemplo, comandos de instalações industriais, aparelhos para escritórios, aparelhos de comunicação ou instrumentos de medida e quadros eléctricos. Não utilize este aparelho em instalações, nos quais um defeito de funcionamento poderá causar danos graves ou significar risco de morte.
ATENÇÃO
A não observância ou o incumprimento dos pontos a seguir mencionados, poderá causar uma descarga elétrica, incêndios, acidentes graves ou morte.
1) Não use a fonte de alimentação sem o condutor de proteção terra!
2) Antes de trabalhos de instalação, manutenção ou modificação, desligue a tensão de alimentação, protegendo-a contra uma nova ligação involuntária.
3) As ligações devem ser efectuadas apenas por profissionais competentes.
4) Não efectue nenhuma modificação ou tentativa de reparação no aparelho. Quando necessário contacte o seu distribuidor.
5) Não abra o aparelho mesmo quando desligado. No seu interior existem condensadores que podem estar carregados electricamente.
6) Proteger a fonte de alimentação contra a introdução inadvertida de corpos metálicos, como por ex., clipes ou outras peças de metal.
7) Não usar o aparelho em ambientes húmidos. Não usar o aparelho em ambientes propensos a condensações.
8) Não tocar enquanto estiver em funcionamento, nem após a desligar. A superficie poderá estar quente e provocar lesões.
CUIDADO
Será necessário reduzir a potência de saída nos seguintes casos:
1) Quando não forem observadas as distâncias mínimas de montagem.
2) Quando instaladas a altitudes superiores a 2000m.
3) Existencia de temperatur a ambiente superior a +60ºC, em plena carga do aparelho.
4) Montagem invertida do aparelho (Entrada, saída em baixo).
5) Montagem em ambiente sem ventilação.
© 2013 by
Business
Phone 440 646 5800
www.ab.com
Rockwell Automation CH-5001 Aarau, Switzerland Fax +41 62 837 2202
Allen-Bradley Company, LCC
Industrial Components
1201 South Second Street
Milwaukee, WI 53204-2496
USA
1606-XLS960: Power Supply Instruction Manual 1606-XLS960: Bedienungsanleitung für Stromversorgung
Technical Data 1) Technische Daten
1)
XLS960E XLS960EE XLS960F XLS960FE
gnunnapssgnagsuA egatloV tuptuO nom. DC 24-28V DC 24-28V DC 48-54V DC 48-54V Factory Setting at Full Load Werkseinstellung bei Nennlast “Single-Use”, typ. 24.1V 24.1V 48.0V 48.0V Output Current continuous Ausgangsstrom dauernd nom. 40A (24V)
Output Current short-term (4s)
14)
Ausgangsstrom kurzzeitig (4s)
14)
nom. 60A (24V)
34.3A (28V)
51.5A (28V)
40A (24V)
34.3A (28V) 60A (24V)
51.5A (28V)
20A (48V)
17.8A (54V) 30A (48V)
26.7A (54V)
20A (48V)
17.8A (54V) 30A (48V)
26.7A (54V)
short-term (25ms) A55 A55A011A011 )sm52( gitiezzruk
Output Power continuous Ausgangsleistung dauernd nom. 960W 960W 960W 960W Output Power short-term (4s) Output Ripple & Noise Voltage AC Input Voltage AC Eingangsspannung nom. AC 100-240V
Input Frequency Eingangsfrequenz nom. AC Input Current 3) AC Eingangsstrom Power Factor
3)
14)
Ausgangsleistung kurzzeitig (4s)
13)
Ausgangswelligkeit
13)
3)
3)
rotkafsgnutsieL
14)
nom. 1440W 1440W 1440W 1440W max. 100mVpp 100mVpp 150mVpp 150mVpp
50-60Hz
-15%/+10% ±6%
15)
AC 200-240V
-15%/+10% ±6%
50-60Hz
AC 100-240V
-15%/+10%
50-60Hz
15)
AC 200-240V
±6%
-15%/+10%
50-60Hz
±6%
typ. 8.6A / 4.5A - / 4.6A 8.6A / 4.5A - / 4.6A typ. 0.99 / 0.99 - / 0.96 0.99 / 0.99 - / 0.96
Allowed Voltage L or N to Earth Erlaubte Spannung L oder N zu Erde max. 300Vac 300Vac 300Vac 300Vac PFC Norm EN 61000-3-2 Class A PFC Norm EN 61000-3-2 Klasse A - Yes / Ja Yes / Ja Yes / Ja Yes / Ja DC Input Voltage DC Eingangsspannung nom. - - - - Input Inrush Current Hold-up Time Efficiency Power Losses
3) 4)
Einschaltspitzenstrom
3)
3)
3)
3)
tiezreffuP
3) 4)
3)
dargsgnukriW
3)
gnutsieltsulreV
typ. 16A / 9A peak - / 14A peak 16A / 9A peak - / 14A peak typ. 27ms / 27ms - / 30ms 27ms / 27ms - / 30ms typ. 93.6% / 94.6% - / 94.6% 93.9% / 95.0% - / 95.0% typ. 65.6W / 54.8W - / 54.8W 62.4W / 50.5W - / 50.5W
Operational Temperature Range Betriebstemperaturbereich nom. -25°C - +70°C -25°C - +70°C -25°C - +70°C -25°C - +70°C
eL gnitareD tuptuO istungsrücknahme +60°C to +70°C 24W/°C 24W/°C 24W/°C 24W/°C
Storage Temperature Range Lagertemperaturbereich nom. -40°C - +85°C -40°C - +85°C -40°C - +85°C -40°C - +85°C Humidity
5)
5)
ethcueF
IEC 60068-2-30 5 - 95% r.H. 5 - 95% r.H. 5 - 95% r.H. 5 - 95% r.H.
negniwhcS noitarbiV IEC 60068-2-6 1g 1g 1g 1g
nekcohcS kcohS IEC 60068-2-27 15g 6ms,
Degree of Pollution Verschmutzungsgrad IEC 62103 2 Degree of Protection Schutzart EN 60529 IP20 IP20 IP20 IP20 Class of Protection Schutzklasse IEC 61140 I
10g 11ms
5)
6)
15g 6ms,
10g 11ms
15g 6ms,
10g 11ms
5)
2
6)
I
25) 2
I6) I
15g 6ms,
10g 11ms
Over-temperature Protection Übertemperaturschutz OTP Yes / Ja Yes / Ja Yes / Ja Yes / Ja Output Over-voltage Protection Überspannungsschutz am Ausgang OVP, max. 32Vdc 32Vdc 60Vdc 60Vdc Return Voltage Resistance 8) Rückspeisefestigkeit Leakage Current
IT-mains
Parallel Use Serial Use
7)
TN/TT-mains
11)
12)
PE- Ableitstrom 7)TN/TT-Netze
IT-Netze
Dimensions9)(WxHxD) Abmessungen
8)
11)
rabtlahcslellaraP
12)
rabtlahcsneireS
9)
(BxHxT) nom. 125x124x127mm 125x124x127mm 125x124x127mm 125x124x127mm
max. 35Vdc 35Vdc 63Vdc 63Vdc max.
max.
0.71mA / 1.18mA
1.73mA / 2.82mA
- / 0.75mA
- / 1.74mA
0.71mA / 1.18mA
1.73mA / 2.82mA
- / 0.75mA
- / 1.74mA
- Yes / Ja Yes / Ja Yes / Ja Yes / Ja
- Yes / Ja Yes / Ja Yes / Ja Yes / Ja
thciweG thgieW max. 1900g, 4.2lb 1800g, 4lb 1900g, 4.2lb 1800g, 4lb
5)
6)
1) All parameters are specified at 230Vac input voltage, nominal output current, “Single Use” setting, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
3) At 120Vac / 230Vac
4) Input inrush current is electronically limited, temperature independent and is valid for mains interruptions > 1s
5) Do not energize while condensation is present.
6) PE connection required (Ground).
7) Leakage current at 132Vac, 60Hz / 264Vac, 50Hz
8) Loads such as decelerating motors and inductors can feed voltage back to the output of the power supply. The figure represents the maximum allowed feed back voltage
9) Depth without DIN-rail.
11) Set jumper on the front to “Parallel Use”. A fuse (or diode) on the output is required if more than three units are paralleled.
12) Use only power supplies of the same type. The total output voltage should not be >150Vdc.
13) 50-Ohm measurement, bandwidth 20MHz
14) BonusPower automatically reduced to the continuous output power level
15) An output current derating might be necessary at input voltages below 90Vac, see figure 5
®
: The short-term power is available for 4s. After this, the output power will be
1) Alle Werte gelten bei 230Vac Eingangsspannung, Nennausgangsstrom, „Single-Use“ Modus, 25°C Umgebung und nach einer Aufwärmzeit von 5 Minuten, falls nichts anderes angegeben.
3) bei 120Vac / 230Vac
4) Der Einschaltstromstoß ist elektronisch begrenzt, temperaturunabhängig und gilt für Netzunterbrechungen > 1s
5) Nicht betreiben, solange das Gerät Kondensation aufweist.
6) PE Verbindung erforderlich.
7) Ableitstrom bei 132Vac, 60Hz / 264Vac, 50Hz
8) Bremsende Motoren oder Induktivitäten können Spannung zum Ausgang des Netzteils rückspeisen. Der Wert gibt die max. zulässige Rückspeisespannung an.
9) Tiefe ohne DIN-Schiene
11) Steckbrücke an der Front des Gerätes auf „Parallel Use“ umstellen. Bei mehr als drei Geräten wird eine Sicherung oder eine Diode zur Entkopplung benötigt.
12) Nur für gleiche Geräte bis zu einer Gesamtspannung von 150Vdc
13) 50-Ohm Messung, Bandbreite 20MHz
14) BonusPower®: Wird dir Kurzzeitleistung für länger als 4s entnommen, reduziert sich die maximal entnehmbare Ausgangsleistung auf die Dauerleistung
15) Unterhalb 90Vac kann ei ne Lei stu ng sr ücknah me erforderlich sein. Siehe Bild 5
1606-XLS960: Power Supply Instruction Manual
A
1606-XLS960: Bedienungsanleitung für Stromversorgung
Installation
Use DIN-rails according to EN 60715 with a height of 7.5 or 15mm. Mounting orientation must be output and input terminals on the bottom. For other orientations see datasheet. Do not obstruct air flow as the unit is convection cooled. Ventilation grid must be kept free of any obstructions. The following installation clearances must be kept when power supplies are permanently fully loaded:
Left / right: 5mm (15mm in case the adjacent device is a heat source) 40mm on top, 20mm on the bottom of the unit.
CE Marking
CE mark is in conformance with EMC directive 2004/108/EC, the low-voltage directive (LVD) 2006/95/EC and the RoHS directive 2011/65/EU.
EMC Immunity: EN 61000-6-1, EN 61000-6-2 EMC Emission EN 61000-6-3, EN 61000-6-4, FCC Part 15 Class B
Input Fuses
Internal input fuse included, not user accessible. The unit is tested and approved for branch circuits up to 32A. An external protection is only required if the supplying branch has an ampacity greater than this, however, in some countries local regulations might apply. Check local codes and requirements. If an external fuse is necessary or utilized, minimum requirements need to be considered to avoid nuisance tripping of the circuit breaker. 1606-XLS960E, 1606-XLS960F: Use a minimum value of 16A B- or C-Characteristic breaker 1606-XLS960EE, 1606-XLS960FE: Use a min. value of 10A B- or 8A C-Characteristic breaker
Isolation and Dielectric Strength (see Fig. 4)
The output voltage is floating and separated from the input according to SELV (IEC/EN 60950-1) and PELV (EN 60204-1, EN 50178; IEC 62103, IEC 60364-4-41) requirements. Type and factory tests are conducted by the manufacturer. Field tests may be conducted in the field using the appropriate test equipment which applies the voltage with a slow ramp (2s up and 2s down). Connect all phase-terminals together as well as all output poles before the test is conducted. When testing, set the cut-off current settings to the value in the table below.
Type Test (60s) 2500Vac 3000Vac 500Vac 500Vac Factory Test (5s) 2500Vac 2500Vac 500Vac 500Vac Field Test (5s) 2000Vac 2000Vac 500Vac 500Vac Cut-off current setting >20mA >20mA >40mA >1mA
PLUS
Hiccup
The output current is electronically controlled. During an overcurrent situation, the output voltage will be reduced after a defined time. If the voltage falls below 20V for the 24V units and 40V for the 48V units, the unit switches to the Hiccup by a restart attempt after 17s for 2s. This cycle is repeated as long as the overload or short circuit exists. If the overload or short circuit has been cleared, the device will operate normally.
Overload Characteristic (see Fig. 1and 2)
A B C D
PLUS
mode. In this mode, the output switches off followed
Installation
Geeignet für DIN-Schienen entsprechend EN 60715 mit einer Höhe von 7,5 oder 15mm. Der Einbau hat so zu erfolgen, dass sich die Eingangs- und Ausgangsklemmen unten befinden. Für andere Einbaulagen siehe Datenblatt. Luftzirkulation nicht behindern! Das Gerät ist für Konvektionskühlung ausgelegt. Es ist für ungehinderte Luftzirkulatio n zu sorgen. Folgende Einbauabstände sind bei dauerhafter Volllast einzuhalten:
Links / rechts: 5mm (15mm bei benachbarten Wärmequellen) Oben: 40mm, unten 20mm vom Gerät.
CE Kennzeichnung
Das CE Zeichen ist angebracht und erklärt die Erfüllung der EMV Richtlinie 2004/108/EG, der Niederspannungsrichtlinie 2006/95/EG und der RoHS Richtlinie 2011/65/EU.
Störfestigkeit: EN 61000-6-1, EN 61000-6-2 Störaussendung: EN 61000-6-3, EN 61000-6-4, FCC Part 15 Klasse B
Sicherungen am Eingang
Das Gerät besitzt eine eingebaute Eingangssicherung, die nicht anwenderzugänglich ist. Das Gerät ist geprüft und zugelassen zum Anschluss an Stromkreisen bis max. 32A. Ein zusätzlicher externer Schutz ist nur erforderlich, wenn der Speisestromkreis mit einem höheren Wert abgesichert ist oder nationale Richtlinien es vorschreiben. Um ein fehlerhaftes Auslösen externer Schutzelemente zu vermeiden folgende Minimalwerte nicht unterschreiten: 1606-XLS960E, 1606-XLS960F: 16A B- oder C-Charakteristik 1606-XLS960EE, 1606-XLS960FE: 10A B- oder 8A C-Charakteristik
Galvanische Trennung und Isolationsfestigkeit (siehe Bild 4)
Die Ausgangsspannung hat keinen Bezug zur Erde oder Schutzleiter und ist zum Eingang nach den SELV (IEC/EN 60950-1) und PELV (EN 60204-1, EN 50178, IEC 62103, IEC 60364-4-41) Standards getrennt. Typ- und Stückprüfungen werden beim Hersteller durchgeführt. Wieder­holungsprüfungen dürfen mittels geeigneten Prüfgenerators mit langsam (2s) ansteigenden und abfallenden Spannungsrampen in der Anwendung erfolgen. Vor den Tests sind alle Phasen wie auch alle Ausgangspole miteinander zu verbinden. Während der Tests darf die Strom-
bschaltschwelle nicht kleiner als der in der Liste angegebene Wert sein.
Typprüfung (60s) 2500Vac 3000Vac 500Vac 500Vac Stückprüfung (5s) 2500Vac 2500Vac 500Vac 500Vac Wiederholungsprüfung (5s) 2000Vac 2000Vac 500Vac 500Vac Strom- Abschaltschwelle >20mA >20mA >40mA >1mA
PLUS
Hiccup
Der Ausgangsstrom ist elektronisch überwacht. Während einer Überstromsituation wird nach einer bestimmten Zeit die Ausgangsspannung reduziert. Fällt die Spannung unter 20V bei 24V Geräten oder 40V bei 48V Geräten schaltet das Gerät in den Hiccup das Gerät ab und macht nach 17s einen Startversuch mit einer Dauer von 2s. Der Vorgang wiederholt sich solange, bis die Überlast oder der Kurzschluss entfernt ist. Nach entfernen der Überlast oder des Kurzschlusses schaltet das Gerät wieder in den Normalbetrieb.
Überlastverhalten (siehe Bilder 1 und 2)
A B C D
PLUS
Modus. In diesen Modus schaltet
Output Characteristic /Ausgangskennlinie, typ.
Output Voltage
28V
56V
24V
48V
20V
40V
16V
32V
12V
24V
8V
16V
4V
8V
0V
0V
24V
48V
Unit
Unit
Fig. 1/ Bild 1
Hiccup
mode
0 50% 100%
Adjustment range
Continuously
A
B
available Short-term (4s)
B
available
A
PLUS
150% 200% 250%
Output Current
PLUS
Hiccup
Overload and Short-Circuit Behavior / Hiccup
Output Current
Normal
operation
I
SC
0
2s
24V units: 65A
ISC:
48V units: 35A
17s
Fig. 2/ Bild 2
Short -circuit
2s
PLUS
Überlast- und Kurzschlussverhalten, typ.
Normal
operation
17s 17s
2s
t
1606-XLS960: Power Supply Instruction Manual
A
A
A
A
r
1606-XLS960: Bedienungsanleitung für Stromversorgung
Remote Control of Output Voltage (see Fig. 6)
The shut-down input can also be used to remotely adjust the output voltage. A control voltage applied on the shut-down input reduces the adjusted output voltage
Instructions:
1. Set the unit into “Single Use” mode
2. Set the output voltage adjustment to the maximum desired voltage.
3. Apply a control voltage to reduce the output voltage
DC-OK Relay Contact (see Fig. 3)
This feature monitors the output voltage, which is produced by the power supply, and is independent of a return voltage from a unit which is connected in parallel.
Contact closes when the output voltage is above 90% of the adjusted value. Contact opens when the output voltage is typ. below 90% of the adjusted value. Short dips will
be extended to a length of 250ms. Dips shorter than 1ms will be ignored.
Contact ratings: max.: 60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A, resistive load, min. current 1mA
Shut-down Input (see Fig. 7)
This feature allows a switch-off of the power supply with a control switch or an external voltage. The shut-down function has no safety feature included. The shut-dow n occurs immediately while the turn-on is delayed by 350ms. In a shut-down condition, the output voltage is <2V and the output power is <0.5W.
Single Use / Parallel Use Selector
This selector on the front of the unit enables a load sharing when power supplies are connected in parallel. The “Parallel Use” mode regulates the output voltage in such a manner that the voltage at no load is approx. 4% higher than at nominal load. If no jumper is plugged in, the unit is also in “Single Use”. Factory setting is “Single Use”. Instructions for parallel use: The output voltage shall be adjusted to the same value (±100mV) in “Single Use” at the same load condition on all units, or shall be left with the factory settings. Afterwards, the jumper on the front of the unit shall be moved from “Single Use” to “Parallel Use”
Externe Steuerung der Ausgangsspannung (siehe Bild 6)
Mithilfe einer externen Steuerspannung am Shut-down Eingang kann die eing estel lte
usgangsspannung in gewissen Grenzen reduziert werden. nleitung:
1. Gerät in „Single Use“ Modus stellen
2. Ausgangsspannung mittels Potentiometer auf den maximal gewünschten Wert einstellen
3. Steuerspannung am Shut-down Eingang anlegen um die Ausgangsspannung zu reduzieren
DC-OK Relais Kontakt (siehe Bild 3)
Diese Funktion überwacht die vom Gerät erzeugte Ausgangsspannung und lässt sich von einer rückwärts eingespeisten Spannung nicht beeinflussen (z.B.: bei Parallelschaltung)
Kontakt schließt, wenn die Ausgangsspannung typ. höher als 90% des eingestellten Wertes ist. Kontakt öffnet, wenn die Ausgangsspannung typ. kleiner als 90% des eingestellten Wertes ist.
Kurze Einbrüche werden auf 250ms verlängert. E i nbrüche kürzer 1ms werden ignoriert.
Kontakt Belastbarkeit: max.: 60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A, (R-Last), min. Strom 1mA
„Shut-down“ Eingang (siehe Bild 7)
bschaltung des Gerätes durch einen Signalschalter oder eine Fremdspannung. Die Abschaltung beinhaltet keine Sicherheitsfunktionen. Die Abschaltung erfolgt unverzögert, das Wiedereinschalten mit einer Verzögerung von ca. 350ms. Im abgeschaltetem Zustand ist die
usgangsspannung <2V und die Ausgangsleistung <0,5W.
„Single Use“ / „Parallel Use“ Steckbrücke
Diese Steckbrücke an der Frontseite des Geräts ermöglicht eine Lastaufteilung, wenn mehrere Geräte parallel geschaltet sind. In „Parallel Use“ Modus ist die Ausgangsspannung so geregelt, dass diese im Leerlauf um etwa 4% höher ist als bei Nennlast. Ein nicht eingesteckter Jumper bedeutet auch „Single Use“. Werkseinstellung ist „Single Use“.
Anleitung für Parallelbetrieb:
Die Ausgangsspannung aller Geräte bei gleicher Belastung in „Single Use“ auf ±100mV genau einstellen oder in Werkseinstellung belassen. Danach die Steckbrücke an der Front des Gerätes von „Single Use“ auf „Parallel Use“ umstecken.
Fig. 3 / Bild 3
DC-OK-Signal
V
=
90% V
V
OUT
ADJ
1ms
10%
<
>
1ms
250ms
ADJ
Input DC-ok
L N
Earth
open
Remote Control of Output Voltage / Externe Steuerung der Ausgangsspannung
Output Voltage
28V
56V
26V
52V
24V
48V
22V
44V
20V
40V
18V
36V
16V
32V
14V
28V
24V
48V
Unit
Unit
openclosed closed
Fig. 6 / Bild 6
Control Voltage
2V 4V 6V
Adjustment range
+
n.c.
8V 10V 12V
Control Voltage
15
Shut­down
16
Input
-
Fig. 4 / Bild 4
Insulation / Isolation, typ.
B
A
C
B
Output Shut-down
Option A: OFF: linked /
verbunden ON : open / offen
Output derating / Leistungsrücknahme
Fig. 5 / Bild 5
Allowed Output Powe
1440W
1200W
960W
D
+/-
-
Shut-
15
down Input
16
720W 480W 240W
*) only 1606-XLS960E, 1606-XLS960F
Shut-down Input / Eingang
short-term (4s)
continuous
0
-25 0 20 40
Fig. 7 / Bild 7
Option B: (open collector)
OFF: I > 0.3mA ON : I < 0.1mA
15
n.c.
16
I
Shut­down Input
Option C: (ext. voltage /
ext. Spannung) OFF: U < 1V ON : U = 4 -29V
U
-
90 to 276Vac
*)
or 170 to 276Vac
*)
85Vac
70°C
Ambient Temperature
n.c.
+
60
Shut-
15
down Input
16
-
1606-XLS960: Power Supply Instruction Manual
A
A
A
1606-XLS960: Bedienungsanleitung für Stromversorgung
Terminals and Wiring
Use appropriate copper cables that are designed for a minimum operating temperature of: 60°C for ambient temperatures up to 45°C, 75°C for ambient temperatures up to 60°C and 90°C for ambient temperatures up to 70°C.
Follow national installation codes and regulations! Ensure that all strands of a stranded wire enter the terminal connection! Ferrules are allowed.
Solid wire 0.5-6mm Stranded wire 0.5-4mm American wire gauge AWG 20-10 AWG 22-8 AWG 26-14 Max. wire diameter 2.8mm 5.2mm 1.5mm (including ferrules) Wire stripping length 7mm / 0.28inch 12mm / 0.5inch 7mm / 0.28inch Tightening torque 1Nm / 9lb.inch 2.3Nm / 20.5lb.inch Spring-clamp terminal
Input Output Signals
2 2
0.5-16mm
0.5-10mm
2 2
0.15-1.5mm
0.15-1.5mm
2 2n
Indicators, LEDs
Normal mode OFF ON Closed During BonusPower® OFF ON Closed Overload (Hiccup mode) flashing OFF Open Output short circuit flashing OFF Open Temperature Shut-down flashing OFF Open
ctive Shut-down input flashing OFF Open
1606-XLS960E, 1606-XLS960F; Functional Diagram / Funktionsschaltbild
L
N
Input Fuse Input Filter Inrush Limiter
Overload LED DC-OK LED DC-OK Contact
Fig. 8 / Bild 8
Output
Voltage
Regulator
Bridgeless
PFC
Converter
Power
Converter
Output
Filter
+ +
-
Single / Parallel
V
OUT
-
Overload LED
DC-ok
Temper-
ature Shut­down
Event Datalogger
Output Power
Manager
Output
Over-
Voltage
Protection
Output Voltage Monitor
DC ok Relay
Shut­down
LED
13 14 15 16
DC-ok Contact
Shut-down Input & Remote Control
Anschlussklemmen und Verdrahtung
Verwenden Sie geeignete Kupferkabel, die mindestens für: 60°C bei einer Umgebungstemperatur bis zu 45°C, 75°C bei einer Umgebungstemperatur bis zu 60°C und 90°C bei einer Umgebungstemperatur bis zu 70°C zugelassen sind.
Beachten Sie nationale Bestimmungen und Installationsvorschriften! Stellen Sie sicher, dass keine einzelnen Drähte von Litzen abstehen. Aderendhülsen sind erlaubt.
Starrdraht 0,5-6mm Litze 0,5-4mm AWG AWG 20-10 AWG 22-8 AWG 26-14 Max. Drahtdurchmesser 2,8mm 5,2mm 1,5mm (inklusive Aderendhülsen) Abisolierlänge 7mm / 0,28inch 12mm / 0,5inch 7mm / 0,28inch Anzugsdrehmoment 1Nm / 9lb.inch 2.3Nm / 20,5lb.inch Federkraftklemme
Eingang Ausgang Signale
2 2
0,5-16mm 0,5-10mm
2 2
0,15-1,5mm 0,15-1,5mm
2 2
Anzeigelampen
Normalbetrieb AUS EIN geschlossen Während BonusPower® AUS EIN geschlossen Überlast (Hiccup- Modus) blinken AUS offen
usgangskurzschluss blinken AUS offen
Temperaturabschaltung blinken AUS offen
ktiver „shut-down“ Eingang blinken AUS offen
PFC
Converter
Fig. 9 / Bild 9
Power
Converter
Output
Voltage
Regulator
Output
Filter
1606-XLS960EE, 1606-XLS960FE; Functional Diagram / Funktionsschaltbild
L N
Input Fuse Input Filter Input Rectifier Inrush Limiter
tcatnoC KO-CD DEL KO-CD DEL daolrevO
Single / Parallel
V
OUT
+ +
-
-
Overload LED
DC-ok
Temper-
ature Shut­down
Event Datalogger
Output Power
Manager
Output
Over-
Voltage
Protection
Output Voltage Monitor
DC ok Relay
Shut­down
LED
13
DC-ok Contact
14
Shut-down
15
Input & Remote Control
16
1606-XLS960E, 1606-XLS960F; Dimensions / Abmessungen
10000172266 (version 01) PU-384.010.38-10A
Fig. 10 / Bild 10
1606-XLS960EE, 1606-XLS960FE; Dimensions / Abmessungen
Fig. 11 / Bild 11