Because of the variety of uses for the products described in this publication,
those responsible for the application and use of this control equipment must
satisfy themselves that all necessary steps have been taken to assure that
each application and use meets all performance and safety requirements,
including any applicable laws, regulations, codes and standards.
The illustrations, charts, sample programs and layout examples shown in
this guide are intended solely for purposes of example. Since there are many
variables and requirements associated with any particular installation,
Allen-Bradley does not assume responsibility or liability (to include
intellectual property liability) for actual use based upon the examples shown
in this publication.
Allen-Bradley publication SGI-1.1, Safety Guidelines for the Application, Installation and Maintenance of Solid-State Control (available from your
local Allen-Bradley office), describes some important differences between
solid-state equipment and electromechanical devices that should be taken
into consideration when applying products such as those described in this
publication.
Reproduction of the contents of this copyrighted publication, in whole or
part, without written permission of Rockwell Automation, is prohibited.
Throughout this manual we use notes to make you aware of safety
considerations:
Identifies information about practices or circumstances
that can lead to personal injury or death, property damage
or economic loss
Attention statements help you to:
• identify a hazard
• avoid a hazard
• recognize the consequences
Identifies information that is critical for successful
application and understanding of the product.
SMC-Flex, SMC PLUS, SMC Dialog Plus, SMB, and STC are trademarks of Rockwell
Automation. ControlNet is a trademark of ControlNet International, Ltd. DeviceNet and the
DeviceNet logo are trademarks of the Open Device Vendors Association (ODVA). Ethernet is a
registered trademark of Digital Equipment Corporation, Intel, and Xerox Corporation. Modbus is
a trademark or registered trademark of Schneider Automation Inc. Profibus is a registered
trademark of Profibus International.
European Communities (EC)
Directive Compliance
If this product has the CE mark it is approved for installation within the
European Union and EEA regions. It has been designed and tested to meet
the following directives.
EMC Directive
This product is tested to meet the Council Directive 89/336/EC
Electromagnetic Compatibility (EMC) per EN/IEC 60947-4-2.
This product is intended for use in an industrial environment.
Low Voltage Directive
This product is tested to meet Council Directive 73/23/EEC Low Voltage,
per EN/IEC 60947-4-2.
This equipment is classified as open equipment and must be mounted in an
enclosure during operation to provide safety protection.
Notes
Table of Contents
Chapter 1
Product Overview
Other Related Documents ........................................................................... 1-1
Renewal Part Cross Reference ....................................................................F-1
Product Overview
Chapter1
Other Related Documents•Quick Start — Publication 150-QS001_
•Renewal Part Instructions — 41053-277-01(5…85 A)
41053-328-01(108…135 A)
41053-228-01(201…480 A)
41053-367-01(625…1250 A)
•Selection Guide — Publication 150-SG009_
•Application Guide — Publication 150-AT002_
①
-EN-P
①
-EN-P
①
-EN-P
DescriptionThe SMC™-Flex controller offers a full range of starting modes as
standard:
•Soft Start with Selectable Kickstart
•Current Limit with Selectable Kickstart
•Dual Ramp Start with Selectable Kickstart
•Full Voltage Start
•Preset Slow Speed
•Linear Speed Acceleration with Selectable Kickstart (requires
Tach feedback)
•Soft Stop
Other features that offer further user benefit include:
•Expanded protective features
•Metering
•I/O
•Communication capability
Innovative starting and stopping options provide enhanced
performance:
•Pump Control
•Braking Control
•Smart Motor Braking (SMB™)
•Accu-Stop™
•Slow Speed with Braking
These modes, features, and options are further described in this
chapter.
➀Latest revision
1-2Product Overview
Percent Voltage
100%
Initial
Torque
Time in Seconds
Start
Run
Ramp Time
Current Limit
OperationThe SMC-Flex controller can operate standard squirrel-cage
induction motors rated 1…1250 A or Star-delta (wye-delta) type
motors rated 1.8…1600 A; up to 690V AC, 50/60 Hz. Depending
upon the controller type ordered, the control power input can range
from 100…240V AC to 24V AC/DC. Please verify voltage on
product, before applying power.
Modes of Operation (Standard)Soft Start
This mode has the most general application. The motor is given an
initial torque setting, which is user-adjustable from 0…90% of locked
rotor torque. From the initial torque level, the output voltage to the
motor is steplessly increased during the acceleration ramp time. The
acceleration ramp time is user-adjustable from 0…30 seconds. If the
SMC-Flex controller senses that the motor has reached the up-tospeed condition during the voltage ramp operation, the internal
bypass contactor will be pulled in.
Figure 1.1 Soft Start
①
➀Kickstart is also available with Soft Start.
Product Overview1-3
S
t
un
00%
que
ge
)
S
t
p
C
t
p
S
t
600%
50%
C
t
)
Selectable Kickstart
This feature provides a boost at startup to break away loads that
require a pulse of high torque to get started. This is intended to
provide a pulse of current that is selectable from 0…90% of locked
rotor torque. Selectable kickstart is user-adjustable from
0.0…2.0 seconds.
Figure 1.2 Selectable Kickstart
Percent
Volta
1
Initial
Tor
electable Kickstar
oast-to-res
Soft Sto
tar
Current Limit Start
R
Time (seconds
➀
Soft Sto
This starting mode provides a true current limit start; it is used when
limiting maximum starting current is necessary. The Current Limit
level is user-adjustable from 50…600% of the motor full load ampere
rating; and the current limit time is user-adjustable from 0…30
seconds. If the SMC-Flex controller senses that the motor has reached
the up-to-speed condition during the current limit starting mode, the
internal bypass contactor will be pulled in.
Figure 1.3 Current Limit Start
Percent Full
urren
Load
tar
Time (seconds
➀Kickstart is also available with Current Limit Start.
1-4Product Overview
Ramp #2
Ramp #1
Time in Seconds
Percent Voltage
100%
Initial
Torque #2
Initial
Torque #1
Start #1
Start #2
Run #1
Run #2
Current Limit 2
Current Limit 1
100%
Percent Voltage
Time in Seconds
Dual Ramp Start
➀
This starting mode is useful on applications that have varying loads
(and therefore varying starting torque requirements). Dual Ramp Start
allows the user to select between two separate start profiles with
separately adjustable ramp times and initial torque settings.
Figure 1.4 Dual Ramp Start
➀Dual Ramp Start is available only with the standard controller.
Full Voltage Start
This starting mode is used for applications requiring across-the-line
starting. The output voltage to the motor will reach full voltage within
1/4 second.
Figure 1.5 Full Voltage Start
Product Overview1-5
S
t
un
00%
peed
)
gh
w
w
gh
d
se
ATTENTION
!
Preset Slow Speed
This option can be used in applications that require a slow speed jog
for general purpose positioning. Preset Slow Speed provides either
7% of base speed (low) or 15% of base speed (high) settings in the
forward direction. Reverse can also be programmed and offers 10%
of base speed (low) and 20% of base speed (high) settings.
Figure 1.6 Preset Slow Speed
1
Motor
S
Forwar
15% - Hi
7% - Lo
10% - Lo
20% - Hi
Time (seconds
Rever
tar
R
Slow speed running is not intended for continuous
operation due to reduced motor cooling.
1-6Product Overview
S
t
00%
peed
)
un
Stop
ATTENTION
!
Linear Speed Acceleration
➀
The SMC-Flex has the ability to control the motor speed during
starting and stopping maneuvers. A tach input (0…5V DC) is
required to perform this start mode. The start time is selectable from
0…30 seconds and determines the time the motor will ramp from 0
speed to full speed. Kickstart is available with this option.
Figure 1.7 Linear Speed Acceleration
Percent
S
1
tar
R
Time (seconds
➀Kickstart is also available with Linear Speed Acceleration.
Linear Stop is not intended to be used as an
emergency stop. Refer to the applicable standards
for emergency stop requirements.
The Linear Stop does not need to be set up even if the linear start has
been programmed. The Linear Stop can not brake the motor/load and
reduce the stopping time.
Product Overview1-7
S
t
un
00%
que
ge
)
S
t
p
C
t
p
ATTENTION
!
Soft Stop
This option can be used in applications that require an extended stop
time. The voltage ramp down time is user-adjustable from
0…120 seconds and is adjusted independently from the starting time.
The load will stop when the output voltage drops to a point where the
load torque is greater than the developed motor torque.
Figure 1.8 Soft Stop
Percent
Volta
1
Initial
Tor
electable Kickstar
oast-to-res
Soft Sto
tar
R
Time (seconds
Soft Sto
Soft Stop is not intended to be used as an emergency
stop. Refer to the applicable standards for
emergency stop requirements.
1-8Product Overview
100%
Motor Speed
Time in Seconds
Pump Start
Ramp Time
Run
Pump Stop
Stop Time
ATTENTION
!
ATTENTION
!
Control OptionsThe SMC-Flex controller offers the control options described below.
Important: The options listed in this section are mutually exclusive
and must be specified when ordering. An existing
controller may be upgraded to another control option by
replacing the control module. Consult your local
Allen-Bradley distributor.
Modes of Operation
(Pump Control)
Pump Control Option
This option reduces surges during the starting and stopping of a
centrifugal pump by smoothly accelerating and decelerating the
motor. The microprocessor analyzes the motor variables and
generates commands that control the motor and reduce the possibility
of surges occurring in the system.
The starting time is programmable from 0…30 seconds, and the
stopping time is programmable from 0…120 seconds.
Figure 1.9 Pump Control Option
➀
➀Kickstart is also available with Pump Control.
Pump stopping is not intended to be used as an
emergency stop. Refer to the applicable standard for
emergency stop requirements.
Pump stopping may cause motor heating depending
on the mechanical dynamics of the pumping system.
Therefore, select the lowest stopping time setting
that will satisfactorily stop the pump.
Product Overview1-9
100%
Motor Speed
Smart Motor
Braking
Coast-to-Rest
Time in Seconds
Automatic Zero
Speed Shut-Off
Start
Run
Brake
Stop
Time
ATTENTION
!
Modes of Operation
(Braking Control)
SMB™ Smart Motor Braking Option
This option can be used in applications that require reduced stopping
times. The SMC-Flex controller incorporates a microprocessor-based
system that applies braking current to a motor without any additional
equipment. This option offers a user-adjustable braking current
setting from 0% to 400% of the motor’s full load current rating.
Further, it provides automatic shut-off at zero speed detection.
Figure 1.10 SMB Smart Motor Braking Option
Note: All braking current settings in the range of 1…100% will
provide 100% braking current to the motor.
SMB Smart Motor Braking is not intended to be used
as an emergency stop. Refer to applicable standards
for emergency stop requirements.
1-10Product Overview
ATTENTION
!
Accu-Stop™ Option
This option combines the benefits of the SMB Smart Motor Braking
and Preset Slow Speed options. For general purpose positioning, the
Accu-Stop option provides a brake from full speed to the preset slow
speed setting, then brakes to stop.
Figure 1.11 Accu-Stop Option
Accu-Stop and Slow Speed with Braking are not
intended to be used as an emergency stop. Refer to
applicable standards for emergency stop
requirements.
Slow Speed with Braking Option
The Slow Speed with Braking option provides a jog speed for process
set-up and braking-to-stop at the end of the cycle.
Figure 1.12 Slow Speed with Braking Option
Product Overview1-11
Protection and DiagnosticsThe SMC-Flex controller provides the protective and diagnostic
features described below.
Overload
The SMC-Flex controller meets applicable requirements as a motor
overload protective device. Thermal memory provides added
protection and is maintained even when control power is removed.
The built-in overload controls the value stored in Parameter 12, Motor
Thermal Usage; an Overload Fault will occur when this value reaches
100%. The programming parameters below provide application
flexibility and easy setup.
ParameterRange
Overload ClassOff, 10, 15, 20, 30
Overload ResetManual – Auto
Motor FLC
Service Factor
Notes: (1) The factory default setting for Overload Class, which is
10, enables overload protection. The motor’s full load
current rating must be programmed to properly set
overload protection.
(2) Automatic reset of an overload fault requires the start
input to be cycled in a 2-wire control scheme.
1.0
…2200 A
0.01…1.99
The trip rating is 117% of the programmed FLC.
Figure 1.13 and Figure 1.14 provide the overload trip curves for the
available trip classes.
Underload
➀
Utilizing the underload protection of the SMC-Flex controller, motor
operation can be halted if a sudden drop in current is sensed.
The SMC-Flex controller provides an adjustable underload trip
setting from 0…99% of the programmed motor full load current
rating. Trip delay time can be adjusted from 0…99 seconds.
➀Underload protection is disabled during slow speed and braking operations.
1-12Product Overview
Approximate trip time for 3-phase balanced
Approximate trip time for 3-phase balanced
1.0
10.0
100.0
1000.0
10000.0
1 10 2 3 9 8 7 6 5 4
0.1
1.0
10.0
100.0
1000.0
1 10 2 3 9 8 7 6 5 4
10.0
100.0
1000.0
10000.0
1
2 3 9 8 7 6 5 4
10.0
100.0
1000.0
10000.0
1 10 2 3 9 8 7 6 5 4
Approximate trip time for 3-phase balanced
condition from cold start.
Approximate trip time for 3-phase balanced
condition from hot start.
100%
0
1
10
100
1000
100000
Percent Full Load Current Setting
Class 10
Class 15
Class 20
Class 30
Auto Reset Times:
Class 10 = 90s
Class 15 = 135s
Class 20 = 180s
Class 30 = 270s
Class 10 Class 15 Class 20 Class 30
Figure 1.13 Overload Trip Curves
Approximate Trip Time (seconds)
Approximate Trip Time (seconds)
Approximate Trip Time (seconds)
1.0
Approximate Trip Time (seconds)
1.0
10
Multiples of FLC Multiples of FLC Multiples of FLC Multiples of FLC
condition from cold start.
condition from cold start.
Figure 1.14 Restart Trip Curves after Auto Reset
Seconds
1000%
Product Overview1-13
Undervoltage
➀
Utilizing the undervoltage protection of the SMC-Flex, motor
operation can be halted if a sudden drop in voltage is detected.
The SMC-Flex controller provides an adjustable undervoltage trip
setting from 0…99% of the programmed motor voltage. Trip delay
time can be adjusted from 0…99 seconds.
An alarm (pre-fault) indication level can be programmed to indicate
the unit is getting close to faulting. The alarm modification
information is displayed through the LCD, HIM, Communication (if
applicable) and alarm contact closing.
Overvoltage
➀
Utilizing the overvoltage protection of the SMC-Flex, motor
operation can be halted if a sudden increase in voltage is detected.
The SMC-Flex controller provides an adjustable overvoltage trip
setting from 0…199% of the programmed motor voltage. Trip delay
time can be adjusted from 0…99 seconds.
An alarm (pre-fault) indication level can be programmed to indicate
the unit is getting close to faulting. The alarm modification
information is displayed through the LCD, HIM, Communication (if
applicable) and alarm contact closing.
Unbalance
➀
The SMC-Flex is able to detect an unbalance in line voltages. Motor
operation can be halted if the unbalance is greater than the desired
range.
The SMC-Flex controller provides an adjustable unbalance setting
from 0…25% of the line voltages. Trip delay time can be adjusted
from 0…99 seconds.
An alarm (pre-fault) indication level can be programmed to indicate
the unit is getting close to faulting. The alarm modification
information is displayed through the LCD, HIM, Communication (if
applicable) and alarm contact closing.
➀Undervoltage, overvoltage, and voltage unbalance protection are disabled during braking operation.
1-14Product Overview
Stall
600%
Percent
Full
Load
Current
Time (seconds)
Programmed Start Time
100%
Running Jam
Percent
Full
Load
Current
Time (seconds)
User Programmed Trip Level
Stall Protection and Jam Detection
The SMC-Flex controller provides both stall protection and jam
detection for enhanced motor and system protection.
•Stall protection is user-adjustable from 0.0…10.0 seconds (in
addition to the ramp time programmed).
Figure 1.15 Stall Protection
•An alarm (pre-fault) indication level can be programmed to
indicate the unit is getting close to faulting. The alarm
modification information is displayed through the LCD, HIM,
Communication (if applicable) and alarm contact closing.
•Jam detection allows the user to determine the jam level (up to
1000% of the motor’s FLC rating) and the delay time (up to
99.0 seconds) for application flexibility.
Figure 1.16 Jam Detection
➀➁
➀Jam detection is disabled during slow speed and braking operation.
➁Unit will self-protect in a jam condition.
Product Overview1-15
Ground Fault
In isolated or high impedance-grounded systems, core-balanced
current sensors are typically used to detect low level ground faults
caused by insulation breakdowns or entry of foreign objects.
Detection of such ground faults can be used to interrupt the system to
prevent further damage, or to alert the appropriate personnel to
perform timely maintenance.
The SMC-Flex’s ground fault detection capabilities require the use of
external sensor. Installation of this sensor allows the option of
enabling Ground Fault Trip, Ground Fault Alarm, or both.
For the 5…480 Amp devices, the recommended sensor is a Cat. No.
825-CBCT core balance current transformer for 1…5 A corebalanced ground fault protection.
For the 625…1250 A devices, the recommended sensor is shown
below and provides 5…25 A core-balanced ground fault protection.
•Manufacturer:Allen-Bradley
•Description:600 Volt-Rated Current Transformer
•Catalog Number:1411-126-252
•Ratio:2500:5
Figure 1.17
1
2
1
BLACK
WHITE
SHIELD
SHIELD
BLACK
WHITE
➀Customer supplied.
➁Cat. No. 825-CBCT or Flex-Core Cat. No. 126-252
1
Note: When connecting the ground fault sensors, the secondary of
the CT should be shorted until the connection to the Flex
control module is completed.
1-16Product Overview
Ground Fault Trip
The SMC-Flex will trip with a ground fault indication if:
•No other fault currently exists
•Ground fault protection is enabled
•GF Inhibit Time has expired
•GF Current is equal to or greater than the GF Trip Level for a
time period greater than the GF Trip Delay
Parameter 75, Gnd Flt Inh Time, allows the installer to inhibit a
ground fault trip from occurring during the motor starting sequence
and is adjustable from 0…250 seconds.
Parameter 74, Gnd Flt Delay, allows the installer to define the time
period a ground fault condition must be present before a trip occurs. It
is adjustable from 0.1…250 seconds.
Parameter 73, Gnd Flt Level, allows the installer to define the ground
fault current at which the SMC-Flex will trip. It is adjustable from
1.0…5.0 A or 5.0…25 A, depending on the service size.
Important: The ground fault inhibit timer starts after the maximum
phase of load current transitions from 0 A to 30% of the
device’s minimum FLA Setting or the GF Current is
greater than or equal to 0.5 A. The SMC-Flex does not
begin monitoring for a ground fault condition until the
Gnd Flt Inh Time expires.
Ground Fault Alarm
The SMC-Flex will indicate a Ground Fault Alarm if:
•No warning currently exists
•Ground fault alarm is enabled
•GF Inhibit Time has expired
•GF Current is equal to or greater than the Gnd Flt A Lvl
Parameter 77, Gnd Flt A Lvl, allows the installer to define the ground
fault current at which the SMC-Flex will indicate a warning. It is
adjustable from 1.0…5.0 A or 5.0…25 A, depending on the service
size.
Parameter 78, Gnd Flt A Dly, allows the installer to define the time
period a ground fault alarm condition must be present before a trip
occurs. It is adjustable from 0…250 seconds.
Product Overview1-17
10
20
100
250
550
1330
4000
-20°CTNF-20K
0°CTNF- 5K
TNF+15K
TNF+ 5K
TNF
Thermistor/PTC Protection
The SMC-Flex provides terminals 23 and 24 for the connection of
positive temperature coefficient (PTC) thermistor sensors. PTC
sensors are commonly embedded in motor stator windings to monitor
the motor winding temperature. When the motor winding temperature
reaches the PTC sensor’s temperature rating, the PTC sensor’s
resistance transitions from a low to high value. Since PTC sensors
react to actual temperature, enhanced motor protection can be
provided to address such conditions as obstructed cooling and high
ambient temperatures.
The following table defines the SMC-Flex PTC thermistor input and
response ratings:
Table 1.A PTC Input Ratings
Response resistance3400 Ω ±150 Ω
Reset resistance1600 Ω ±100 Ω
Short-circuit Trip Resistance25 Ω ±10 Ω
Maximum Voltage at PTC Terminals (R
Maximum Voltage at PTC Terminals (R
Maximum Number of Sensors6
Maximum Cold Resistance of PTC Sensor Chain1500 Ω
Response Time800 ms
= 4kΩ)< 7.5V
PTC
= open)30V
PTC
The following figure illustrates the required PTC sensor
characteristics, per IEC-34-11-2.
Figure 1.18 PTC Sensor Characteristics per IEC-34-11-2
PTC Trip
The SMC-Flex will trip with a PTC indication if:
•No other fault currently exists
•PTC protection is enabled
1-18Product Overview
•The resistance across terminals 23 and 24 is either greater than
the relay’s response resistance or less than the short-circuit trip
resistance.
Excessive Starts/Hour
The SMC-Flex controller allows the user to program the allowed
number of starts per hour (up to 99). This helps eliminate motor stress
caused by repeated starting over a short time period.
Overtemperature
The SMC-Flex controller monitors the temperature of the SCRs and
Bypass by using internal thermistors. When the power poles’
maximum rated temperature is reached, the unit will shut down and
restart is inhibited.
An overtemperature condition can indicate inadequate ventilation,
high ambient temperature, overloading, or excessive cycling. After
the temperature is reduced to allowable levels, the fault can be
cleared.
Open Gate
An open gate fault indicates that improper SCR firing, typically
caused by an open SCR gate, has been detected on one of the power
poles. Before the controller shuts down, it will attempt to start the
motor a total of three times.
Line Faults
The SMC-Flex controller continually monitors line conditions for
abnormal factors. Pre-start protection includes:
•Line Fault (with phase indication)
– Line voltage loss
– Missing load connection
– Shorted SCR
Running protection includes:
•Line Fault (no phase indication)
– Line voltage loss
– Missing load connection
Phase Reversal
➀
protection can be toggled either On or Off.
➀Phase Reversal protection is functional only at pre-start.
MeteringPower monitoring parameters include:
•Three-phase current
•Three-phase voltage
•Power in kW
•Power usage in kWH
•Power factor
•Motor thermal capacity usage
•Elapsed time
Notes: (1) Voltage measurement is not available during the braking
operation of the SMB Smart Motor Braking, Accu-Stop,
and Slow Speed with Braking control options.
(2) The elapsed time and kWH values are automatically
saved to memory every 12 hours.
(3) Motor thermal capacity usage is determined by the built-
in electronic thermal overload. An overload fault occurs
when this value reaches 100%.
Product Overview1-19
I/OThe SMC-Flex has the ability to accept up to two (2) inputs and
four (4) outputs controlled over a network. The two inputs are
controlled at terminal 16 (Option Input #1), and terminal 15
(Option Input #2). For these two inputs, see Chapter 4 for the
parameter settings and see Chapter 7 for the bit identification.
By using these two terminals as inputs, the Stop Input will need to be
programmed to meet the desired stop functionality.
The four (4) outputs are Aux #1, Aux #2, Aux #3, and Aux #4. All
auxiliary contacts are programmable to the function found on
page 4-14. If programmed to Network or Network NC, they can be
controlled over a Network. Please see Table 7.H that defines the
Logic Command Word (Control).
1-20Product Overview
DPI
ATTENTION
!
Port 5 — DPI
Communications
Port 2
Ports 2 and 3 when two
HIMs are connected with
a splitter
CommunicationA serial interface port (DPI) is provided as standard, which allows
connection to the Bulletin 20-HIM LCD interface modules.
Figure 1.19 DPI Location
Two peripheral devices can be connected to the DPI.
The maximum output current through the DPI is
280 mA.
ProgrammingSetup is easy with the built-in keypad and three-line, sixteen character
backlit LCD. Parameters are organized in a three-level menu
structure, using a text format for straightforward programming.
Figure 1.20 Built-in Keypad and LCD
Product Overview1-21
11 12
13
14
15 16
17
18 19 20
21
23
24
25 26
27
28 29
30 31 32332234
Aux #3
Aux #2
Aux #4
Aux #1
SMC-Flex
Control Terminals
PTC
Input
TACH
Input
Ground
Fault
Stop
Input
Start
Input
Opt
Input #2
Opt
Input #1
Status IndicationFour programmable hard contact outputs are provided as standard. All
auxiliary contacts are programmable for the following states:
•Normal (N.O./N.C.)
•Up-to-Speed (N.O./N.C.)
•Alarm (N.O./N.C.)
•Fault (N.O./N.C.)
•Network Control (N.O./N.C.)
•External Bypass (N.O.)
Figure 1.21 Control Terminals
Network inputs can be obtained through proper programming of
Option Input #1 and Option Input #2.
1-22Product Overview
Notes
Loading...
+ 132 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.