Rockwell Automation 150-SM3 User Manual

SMC-50 I/O Option Module Installation Instructions
(Cat 150-SM3; 150-SM4)
WARNING: To prevent electrical shock, disconnect from power source before installing or servicing. Install in a suitable enclosure. Keep free from contaminants.
25U6
IND. CONT. EQ.
N223
1
90°
2
0.45 Nm (4 lb-in)
Port Compatibility
7 8 9
ok ok ok
3
4
PN-164120 DIR 10000152878 (Version 01)
Publication 150-IN052B-EN-E
Printed in U.S.A.
5
90°
0.2 - 2.5 mm
(#24 - #14 AWG)
NOTE: When installed in Control Module port number 7 the orientation of the module is rotated 180°.
PN-164120 DIR 10000152878 (Version 01)
Publication 150-IN052B-EN-E
2
7.0 mm
(0.27 in)
0.8 Nm
(7 lb-in)
A1
A2
A3
A4
A5
A7A6
A8
A9
(2)
A10
A11
A12
Field Wiring Terminal Identification
L1
NOTE: For control wiring details refer to the SMC-50 User Manual
A1 A2 A3 A4 A5 A6 A7 A8
InA1
InA3 InA4
InA2
120 / 240V AC
Inputs
150-SM4 Input and Output Specifications
Nominal Operating Voltage Operating Voltage Range On-state Current, Minimum
Control Circuit:
150-SM4
Optional Inputs:
Terminals A1 and A2
On-state Voltage, Minimum Off-state Voltage, Maximum Off-state Current, Maximum Inrush Current Max Input Delay Time Rated Insulation Voltage Rated Impulse Voltage Dielectric Withstand
L2 L2 L2 L2
L1 L1 L1
A9
In
COM
AuxA1
AuxA2 AuxA3
Relay Outputs
UL/CSA/NEMA IEC
120/240V AC 85 to 264V AC @ 47 to 63 Hz
9.7 mA @ 47 Hz, 9.7 mA @ 62.4 Hz
74.5V AC @ 47 Hz, 55.9V AC @ 62.4 Hz
68.8V AC @ 47 Hz, 53.6V AC @ 62.4 Hz
9.0 mA @ 47 Hz, 9.3 mA @ 62.4 Hz
3.64 A On-to-Off: 30 mS, Off-to-On: 25 mS
1600V AC 2000V
A10
A11
A12
NC
NA 240V NA 3000V
Nominal Operating Voltage Operating Voltage Range On-state Current, Minimum
Control Circuit:
150-SM4
Optional Inputs:
Terminals A3 and A4
On-state Voltage, Minimum Off-state Voltage, Maximum Off-state Current, Maximum
(1)
Inrush Current Max Input Delay Time (Maximum) Rated Insulation Voltage Rated Impulse Voltage Dielectric Withstand
(1) Meets IEC Type 2 specification per IEC 60947-1 for 240V AC only
Specification
Type of Output Electromagnetic Relay Contact Number of Contacts 1 Type of Contact Programmable: Normally Open (N.O.) or
Control Circuit:
150-SM4
Optional Outputs:
Terminals A6 thru A11
Rated Operational Current (Inductive) 3A @ 120V AC, 1.5A @ 240V AC Rated Operational Current (Resistive) 8A @ 250V AC, 5A @ 30V DC Rated Thermal Current (Ith) 5A (AC) Max. Make / Break 3600VA Make, 360VA Break UL Utilization Ratings AC-15, B300 (AC Pilot Duty: NEMA) Output De
lay Time (max) On-to-Off: 25 mS; Off-to-On 30 mS Relay Life (electrical-Inductive Load cos ø = 0.4) Relay Life (mechanical) 10 million operations
UL/CSA/NEMA IEC
120/240V AC 85 to 264V AC @ 47 to 63 Hz
5.1 mA @ 47 Hz, 5.0 mA @ 62.4 Hz
74.5V AC @ 47 Hz, 55.8V AC @ 62.4 Hz
68.6V AC @ 47 Hz, 53.5V AC @ 62.4 Hz
4.7 mA @ 47 Hz, 4.8 mA @ 62.4 Hz
3.64 A On-to-Off: 30 mS, Off-to-On: 25 mS
NA 240V NA 3000V
1600V AC 2000V
Normally Closed (N.C.)
250,000 operations (3A @ 120V AC, 1.5A @ 240V AC)
NOTE: For additional information refer to the SMC-50 User manual (150-UM011x-EN-P) available from www.ab.com - Publications Library - Literature Library
PN-164120 DIR 10000152878 (Version 01)
Publication 150-IN052B-EN-E
(3)
Voltage
or Current
Load
+
Voltage
or Current
Load
+
-
-
+
Voltage
Transmitter
or
Voltage
Transmitter
+
-
or
-
B1
V / I
OUT
1+
Output #1
B2
V / I
OUT
1-
B3
V / I
OUT
2+
Output #2
B4
V / I
OUT
2-
B5
V
IN
1+
150-SM3 Input and Output Specifications
Specification
Control Circuit:
150-SM3
Optional Inputs:
Terminals B1 thru B4
Number of Inputs 2 differential inputs Normal Operating Input Ranges +/-10V, 0 to 10V, 0 to 5V, 1 to 5V, 0 to 20mA, 4 to 20mA Full Scale Operating Input Ranges +/-10.5V, 0 to 10.5V, -0.5 to 5.25V, 0.5 to 5.25V,
Input Resolution 16 bit (sample rate = 60Hz)
Data Refresh Rate: Filter dependent: 100mSec (sample rate = 60Hz)
Rated Working Voltage 24V dc / 17V ac Common Mode Voltage Range +/-10V dc / channel Input Impedance: 220K ohms: voltage mode
Input Channel Diagnostics Over and Under Range and Open Circuit Open Circuit Detection Time: Positive Full Scale Reading: within 3 seconds (max) Maximum Overload at Input Terminals Voltage: +/-24V dc continuous at 0.1mA
External Calibration Not required: auto-calibration performed by the module
Module Isolation to Control Board Yes (1000V ac) Removable Terminal Block Yes (150-SM3RTB as a spare replacement part) Cable Type: Belden 8760 (or equiv.) 0.750mm
Current
Transmitter
B6
I
IN
1+
Input #1
Current
Transmitter
B7
V / I
IN 1-
B8
V
IN
2+
B9
IN 2+
B10
I
V / I
B11 B12
NCNCControl IN 2-
Input #2
0 to 21mA, 3.5 to 21mA
13 bit (sample rate = 250Hz)
24mSec (sample rate = 250Hz)
249 ohms: current mode
Current: +/-30mA continuous at 7V dc
if required to meet specs.
100% shield with drain)
2
(18 AWG twisted pair
Ground
Control Circuit:
150-SM3
Optional Outputs:
Terminals B5 thru B10
PN-164120 DIR 10000152878 (Version 01)
Publication 150-IN052B-EN-E
Printed in U.S.A.
Number of Outputs 2 Single-ended Normal Operating Input Ranges +/-10V, 0 to 10V, 0 to 5V, 1 to 5V, 0 to 20mA, 4 to 20mA Full Scale Operating Input Ranges +/-10.5V, 0 to 10.5V, -0.5 to 5.25V, 0 to 21mA, 3.5 to 21mA
Output Resolution +/-10.5V, 0 to 10.5V, -0.5 to 5.25V,
0.5 to 5.25V, 0 to 21mA, 3.5 to 21mA Resistive Load on Current Output 0 to 750 ohms
Load Range on Voltage Output 1K ohm at 10V dc Max. Inductive Load (Current Outputs) 15mH Max. Capacitive Load (Voltage Outputs) 100uF Overall Accuracy Voltage Terminal: +/-0.5% full scale at 25° C
Accuracy Drift with Temperature +/-5 PPM / ° C
Output Impedance 15 ohms (typical) Open and Short-Circuit Protection Yes Maximum Short-Circuit Current 45mA Output Overvoltage Protection Yes
Specification
16 bit (15 plus sign bipolar)
Current Terminal: +/-0.35% full scale at 25° C