Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines
for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 available from your local
Rockwell Automation sales office or online at http://literature.rockwellautomation.com
between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the
wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves
that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the
use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability
for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is
prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
) describes some important differences
WARNING
Identifies information about practices or circumstances that can cause an explosion in a
hazardous environment, which may lead to personal injury or death, property damage, or
economic loss.
IMPORTANT
ATTENTION
Identifies information that is critical for successful application and understanding of the product.
Identifies information about practices or circumstances that can lead to personal injury or death,
property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and
recognize the consequence
SHOCK HAZARD
Labels may be on or inside the equipment, for example, a drive or motor, to alert people that
dangerous voltage may be present.
BURN HAZARD
Labels may be on or inside the equipment, for example, a drive or motor, to alert people that
surfaces may reach dangerous temperatures.
Allen-Bradley, Rockwell Automation, Powermonitor, ControlLogix, PLC5, SLC, RSLinx and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Summary of Changes
Introduction
This release of this document contains new and updated information.
The information below summarizes the changes to this manual since
the last publication.
Revision bars in the margin identify updated information. Changes for
this version of the document include:
ChangePage
Added DH485 to the serial communication
protocol table.
Added section with information about
DH485.
Added that the Ethernet communication
port supports 10 or 100 Mbps data rate,
half-duplex, or full-duplex.
Added DH485 to the communication
command summary.
Added information about explicit messaging
instructions apply to Ethernet
communication and serial communication.
Added instructions to configure RSLinx
software driver configuration for DH485.
Added information for using the DH485
driver.
10
11
11
15
17
34
37
Added information for OPC tag browsing.39
Added information about a user configured
data table.
Added User Configured Table Results
Parameters table.
Added User Configured Table Results table. 45
Added element 5 to Analog Input
Configuration table
Updated elements 5 and 7 to Advanced
Configuration table.
Updated Serial RS-485 Port Configuration
table.
Updated Command table.61
Added element 10 to the Log Request table. 64
Updated Wiring Diagnostics Results table.68
Updated Unit Run Status Results table.80
3Publication 1408-UM001B-EN-P - May 20083
40
45
46
48
51
Summary of Changes
ChangePage
Added User Configurable Table Setup
92
Parameters table.
Added User Configured Table Setup table.92
Added Parameters for Configurable table.93
Use this document as a guide to set up communications with the 1408
Powermonitor 1000 unit using other applications and controllers. This
document is intended for advanced users. You should already be
familiar with data communications and programmable controller
messaging.
For further information on installing, wiring, connecting, applying
power, and configuring your 1408 power monitor, please refer to the
Powermonitor 1000 Installation Instructions.
You should have a basic understanding of electrical circuitry and
familiarity with relay logic. If you do not, obtain the proper training
before using this product.
This table lists documents that contain additional information
concerning Rockwell Automation Power and Energy Management
Solutions products.
For additional information, refer to these publications, that you can
download from http://literature.rockwellautomation.com
.
ResourceDescription
Powermonitor 1000 Unit Installation
Instructions, publication 1408-IN001
If you would like a manual, you can:
• download a free electronic version from the Internet at
http://literature.rockwellautomation.com
• purchase a printed manual by contacting your local
Allen-Bradley distributor or Rockwell Automation sales office.
This publication gives product description
and functionality.
7Publication 1408-UM001B-EN-P - May 20087
Preface Preface
8Publication 1408-UM001B-EN-P - May 2008
Powermonitor 1000 Overview
Chapter
1
Safety
Follow these advisories when using this product.
ATTENTION
ATTENTION
Only qualified personnel, following accepted safety procedures,
should install, wire, and service the power monitor and its
associated components. Before beginning any work, disconnect
all sources of power and verify that they are de-energized and
locked out. Failure to follow these instructions may result in
personal injury or death, property damage or economic loss.
Never open a current transformer (CT) secondary circuit with
primary current applied. Wiring between the CT’s and the
power monitor should include a shorting terminal block in the
CT secondary circuit. Shorting the secondary with primary
current present allows other connections to be removed if
needed. An open CT secondary with primary current applied
produces a hazardous voltage, which can lead to personal
injury, death, property damage or economic loss.
IMPORTANT
Introduction
9Publication 1408-UM001B-EN-P - May 20089
This manual covers advanced techniques for configuring setup
parameters and retrieving data from the power monitor using its
available communications. Typical applications include SCADA
applications using RSLinx Classic or OPC software to gather data from
the power monitor and applications using explicit messaging from
PLC controllers to retrieve data for control and information.
Please refer to the Powermonitor 1000 Installation Instructions,
publication 1408-IN001
• Product description and functionality
• Basic meter and communications setup using the LCD display,
HyperTerminal or the web interface
The power monitor is neither designed for, nor intended for, use
as a circuit protective device. Do not use this equipment in
place of a motor overload relay or circuit protective relay.
for the following information:
Chapter 1 Powermonitor 1000 Overview
What Can I Do Using Communication Networks?
When you use communication networks with the power monitor you
can do the following things.
• Configure analog input parameters such as PT/CT ratios
• Configure communications parameters such as IP address
• Read real-time power and energy data
• Read energy logs
Communication Overview
All Powermonitor 1000 units come standard with an RS-485 serial
communication port. Models with catalog numbers ending in -ENT are
equipped with an Ethernet 10BaseT communication port. This section
covers serial and Ethernet communication, the available protocols,
and what protocols to use for your application.
Serial Communication
The RS-485 serial communication port allows serial communication to
your power monitor. This port can be configured to communicate
using the protocols listed the Serial Communication Protocols table.
Serial Communication Protocols
ProtocolApplications
DF1 Half-duplex Slave The DF1 Half-duplex Slave protocol may be used for point-to-point or multi-drop
communication using a DF1 Polling Master driver for RSLinx software, or when using
explicit messages from Rockwell Automation controllers communicating via DF1
Half-duplex Master.
DF1 Full-duplex The DF1 Full-duplex protocol may be used only for point-to-point communication using a
RS-232 DF1 driver for RSLinx software, or when using explicit messages from Rockwell
Automation controllers communicating via DF1 Full-duplex.
Modbus RTU Slave The Modbus RTU Slave protocol may be used for point-to-point or multi-drop
communication with a client using the Modbus RTU Master protocol for PLC controller
communication.
Auto-senseWith auto-sense selected, the RS-485 port switches among the available serial
protocols based on the format of the packets the port receives.
DH485The DH485 protocol may be used for point-to-point or multi-drop communication using a
1747-PIC/AIC+ driver for RSLinx software, or when using explicit messages from
Allen-Bradley controllers or HMI (PanelView) terminals communicating via DH485.
TIP
When configuring serial communication, users should verify
that all serial devices wishing to communicate to the power
monitor have the same communication rate, and the same data
format.
10Publication 1408-UM001B-EN-P - May 2008
Powermonitor 1000 Overview Chapter 1
DH485 Protocol
DH485 is a token-passing protocol that allows messaging by up to
32 nodes on a serial network. The master is the node that owns the
token; only the master may transmit messages. When a node has
completed transmitting messages, it passes the token to the next node.
The power monitor does not initiate DH485 data messages. When
requested, it transmits reply messages to the initiator when it gets the
token, and then passes the token to its successor.
TIP
The DH485 protocol uses the same data table addressing as DF1
protocols. Please refer to the CSP file number column of
Powermonitor 1000 data tables.
The following configuration factors have a significant effect on
network performance and should be considered when you plan a
DH485 network.
• Number of Nodes - unnecessary nodes will slow the data
transfer rate. The maximum number of nodes on the network is
32. Fewer nodes are better.
• Node Addresses - best to start node addresses at 0 and assign in
sequential order. Controllers may not be node 0. Initiators such
as personal computers should be assigned the lowest numbered
addresses.
• Communication Rate - Higher is better. All devices must be at
the same communication rate.
• Maximum Node Address - should be set as low as possible to
reduce the time it takes to initialize the network.
Powermonitor 1000 units only support DH485 Local Link
messages and do not support the Send and Receive Data (SRD)
messages for DH485 non-token passing slave devices.
Ethernet Network Communication
The Ethernet network communication port allows communication
with your power monitor using a local-area-network (LAN). The
Ethernet port may also be used to view the power monitor’s internal
webpage. This Ethernet port uses a static IP address only, and can
simultaneously communicate using the protocols listed below. The
Ethernet communication port supports 10 or 100 Mbps data rate,
half-duplex, or full-duplex.
Publication 1408-UM001B-EN-P - May 200811
Chapter 1 Powermonitor 1000 Overview
EtherNet/IP Protocol
The power monitor supports the EtherNet/IP protocol for
communicating via Ethernet or EtherNet/IP drivers in RSLinx Classic
software, or when using explicit messages from Rockwell Automation
controllers communicating via Ethernet or EtherNet/IP network.
Modbus TCP Protocol
Modbus TCP protocol is also supported for communicating via
Modbus TCP for communication.
TIP
When configuring Ethernet communication, you should verify
that IP addresses do not conflict with the existing
infrastructure, and that subnet masks and gateways are
properly set.
12Publication 1408-UM001B-EN-P - May 2008
Chapter
2
Powermonitor 1000 Memory Organization
The power monitor memory is organized similarly to that of a PLC-5
or SLC 500 programmable controller. Data tables organize individual
data items of similar function. For example, the analog input setup
parameters are grouped in one data table, and voltage, current, and
frequency metering results in another.
Data Table Addressing
Appendix
Data tables may be addressed in several ways.
A provides a detailed list of the power monitor data tables.
• CSP addressing. This is also known as PLC-5 style or PCCC
addressing. Addresses are written in the form Axx:yy where A is
a letter describing the function of the data table, xx is the table
number, and yy is the element within, or offset into, the table.
For example, F23:0 is the CSP address of the first element in the
energy metering results table.
• CIP addressing. This is also known as DeviceNet addressing.
Addresses are of the form Object:Instance:Attribute. CIP
addressing allows addressing only a single element of an entire
data table. In CIP addressing, the energy metering results table
object 4 (Assembly object), instance 16 (energy results table)
and attribute 3 (data).
• Modbus RTU addressing. The data tables may be addressed by a
Modbus RTU master using Modbus register addressing. The
Modbus protocol supports four types of data: Discrete Input,
Coil, Input Register, and Holding Register. The power monitor
supports Input Registers (read-only) with addresses in the 30000
range and Holding Registers (read-write or write only) with
addresses in the 40000 range. Using the same example as above,
the energy results table has a Modbus address range of
30401…30438
Data Table Access
13Publication 1408-UM001B-EN-P - May 200813
Controllers and client applications may read or write single element,
multiple elements or complete tables as permitted by the addressing
selected.
Each data table’s read/write access is listed in Appendix
A.
Chapter 2 Powermonitor 1000 Memory Organization
The power monitor requires a valid password before it accepts a
write. There are two ways a password may be written.
• An entire table including a valid password may be written.
• A valid password may be written to the Single element password
write table which then enables single element writes until
30 minutes without a single element write elapses.
Data Table Data Format
The power monitor stores data in two basic formats.
• Integer, in which the 16-bit word may be represented by a
signed integer value or a bit field
• Floating-point, in the 32-bit IEEE 754 format
Modbus input registers and holding registers are 16 bits long. Floating
point values in the data tables are represented as big-Endian
two-register arrays in IEEE-754 floating point format. The Modbus
client application must be able to reassemble the two-word array into
a valid floating-point value.
An example Modbus address for a floating-point value is 40101-2.
Register 40101 holds the most significant bytes of the number and
40102 holds the lowest significant bytes.
14Publication 1408-UM001B-EN-P - May 2008
Chapter
Communications Command Summary
3
Serial DF1 Full-duplex,
DF1 Half-duplex Slave,
DH485
This section discusses data retrieval and parameter configuration using
explicit messaging from Rockwell Automation controllers. Explicit
messaging allows you to read and write from a controller to specific
data tables within the power monitor. With explicit messages, users
can read real-time power and energy values, configure analog input
parameters, configure communications parameters, and also read
energy logs.
In general, these instructions apply to Ethernet network
communication (Ethernet/IP protocol) and Serial communication
(DF1 half-duplex or full-duplex or DH485 protocols), provided that
the protocol is supported by the controller. If using serial
communication, the controller serial port must be correctly configured
for protocol, communication rate, or parity. Refer to the appropriate
controller user documentation for further details.
Explicit Message Setup –
Examples
Please refer to Appendix
descriptions of the power monitor data tables and their data access
privileges, and data types.
The power monitor allows PLC-5 Typed, SLC Typed, and CIP Generic
message requests.
This section gives examples on how to set-up explicit messaging.
A, Powermonitor 1000 Data Tables for
Read/Write Single or Multiple Elements
You can perform single or multiple element reads and writes to the
power monitor. Below is a table documenting the message type to use
for specific read/write type and communication scenarios.
17Publication 1408-UM001B-EN-P - May 200817
Chapter 4 Explicit Messaging
IMPORTANT
When performing a write to the power monitor, you must write
the password value to the password element of that specific
data table that you are writing to. This must be done in the
same message; therefore you must perform a multiple element
write. If you wish to perform only a single element write, you
must write the password value to the Single Element Password
Write table. This allows you to perform writes to any write
access data table for the next 30 minutes.
Message Type
Read/Write TypeCommunicationRead/Write Message Type
Single ElementSerialSLC Typed
Single ElementEthernetPLC5 Typed or SLC Typed
Multiple ElementSerialSLC Typed
Multiple ElementEthernet
(1)
The CIP Generic message type is only available for RSLogix5000 software. All elements in the data table are written to or read back.
PLC5 Typed or SLC Typed or CIP Generic
(1)
RSLogix5000 – Message Configuration using PLC5 or SLC Typed
Read/Write
This is an example of how to set up a message instruction to read or
write single or multiple elements from a power monitor using PLC5 or
SLC Typed messages. This setup applies to ControlLogix and
CompactLogix programmable logic controllers.
18Publication 1408-UM001B-EN-P - May 2008
Explicit Messaging Chapter 4
Follow these steps to configure a message.
1. Choose the appropriate parameters in the Message
Configuration window.
ParameterChoice
Message typeSelect the appropriate message type according to Message Type
page 18
.
Source ElementRead: Refer to Appendix
address of the specific data table address you’re reading. If you are
performing a multiple element read, this should be the first element in
the array of elements you’re reading back.
Write: This is the controller tag in which to store the data being
written to the power monitor.
Number of
Elements
Destination
Element
This is the number of elements being read or written to. If you are
performing a single element read or write, then this value should be 1.
If you are performing a multiple element read or write, then this should
be the number of elements after the source element that you wish to
read or write.
Read: This is the controller tag in which to store the data being read.
Write: Refer to Appendix
address of the specific data table address you’re writing to.
A – Powermonitor 1000 Data Tables for the
A – Powermonitor 1000 Data Tables for the
on
2. Click the Communication tab to select the communication type,
either Ethernet or Serial.
Publication 1408-UM001B-EN-P - May 200819
Chapter 4 Explicit Messaging
3. Choose the communication type and then set the path and
communication method.
Communication TypePathMethod
Ethernet<Backplane (always 1), Slot of Ethernet
Module, Port (always 2 for Ethernet), power
monitor IP Address>
Serial Communications<Port, Power Monitor Serial Node Address>CIP
CIP
4. Click OK to complete the message setup.
RSLogix5000 Software – Message Setup Using CIP Generic
The following example shows how to set up your message instruction
to read or write to a data table in the power monitor using a CIP
Generic message type for RSLogix5000 software. This setup applies to
ControlLogix and CompactLogix programmable logic controllers. The
CIP Generic message type does not support single element reads or
writes. In this example, we are reading the Voltage, Amps, and
Frequency data table from the power monitor.
20Publication 1408-UM001B-EN-P - May 2008
Explicit Messaging Chapter 4
Follow these steps to configure a message.
1. Choose the appropriate parameters in the Message
Configuration window.
ParameterChoice
Message TypeChoose message type CIP Generic.
Service TypeRead: Select service type Get Attribute Single
Write: Select service type Set Attribute Single
InstanceRefer to Appendix
requesting to read. In this example, the power monitor’s Voltage, Amp,
and Frequency data table is instance 14.
Class4
Attribute3
DestinationGet Attribute Single - This is the controller tag in which to store the
data being read.
Source ElementSet Attribute Single - Refer to Appendix
specific data table address you’re writing to.
Source LengthSet Attribute Single - This is the number of elements of the source
element, to be written to the power monitor.
A for the CIP Instance of the data table you are
A for the address of the
Publication 1408-UM001B-EN-P - May 200821
Chapter 4 Explicit Messaging
2. Click theCommunicationtab and enter the path and method.
PathMethod
<Backplane (always 1), Slot of Ethernet Module, Port (always 2 for
Ethernet), Power Monitor IP Address>
CIP
3. Click OK to complete message setup.
22Publication 1408-UM001B-EN-P - May 2008
Explicit Messaging Chapter 4
RSLogix500 Software - Message Setup Using PLC5 or SLC Typed
Read/Write
The following is an example of how to set up your message
instruction to read or write single or multiple elements to a power
monitor using Peer-To-Peer PLC5 or CPU 500 Typed messages in
RSLogix500 software. This setup applies to SLC and MicroLogix
programmable logic controllers.
Follow these steps to configure a message.
1. Set your MSG instruction.
ParameterChoice
Read/WriteSelect Read or Write
Target DeviceSelect the appropriate message type according to Message Type
page 18
.
Local/RemoteSelect Local
Control BlockSelect an available Integer word. In this example, we used N7:0.
2. Click Setup Screen at the bottom of the message instruction.
The message configuration window for either Ethernet network
or Serial communication appears.
on
Publication 1408-UM001B-EN-P - May 200823
Chapter 4 Explicit Messaging
3. Choose the appropriate parameters in the Message
Configuration window.
Ethernet Network Communication
Serial Communication
Communication
ParameterChoice
Ty pe
EthernetData Table Address (This
Controller)
Size in ElementsThis is the number of elements being
Channel1
Data Table Address
(Target Device)
MultiHopYes
Read: This is the controller tag in
which to store the data being read
Write: This is the controller tag that
stores the value to be written to the
power monitor.
read or written to. If you are
performing a single element read or
write, then this value should be 1. If
you are performing a multiple element
read or write, then this should be the
number of elements after the source
element that you wish to read or
write.
Refer to Appendix
A for the address of
the specific data value you’re reading
or writing to.
24Publication 1408-UM001B-EN-P - May 2008
Explicit Messaging Chapter 4
Communication
Ty pe
SerialData Table Address (This
ParameterChoice
Controller)
Size in ElementsThis is the number of elements being
Channel0
Data Table Address (Target
Device)
Local NodeThis is the serial node address of your
Read: This is the controller tag in
which to store the data being read
Write: This is the controller tag that
stores the value to be written to the
power monitor.
read or written to. If you are
performing a single element read or
write, then this value should be 1. If
you are performing a multiple element
read or write, then this should be the
number of elements after the source
element that you wish to read or
write.
Refer to Appendix
the specific data value you’re reading
or writing to.
power monitor.
A for the address of
Message setup is complete for Serial communication.
4. Click the MultiHop tab if configuring Ethernet communications.
5. Enter the IP Address of the power monitor in the To Address
box.
Message setup is complete.
Publication 1408-UM001B-EN-P - May 200825
Chapter 4 Explicit Messaging
RSLogix5 Software - Message Setup using PLC5 or SLC Typed
Read/Write
The following is an example of how to set up your message
instruction to read or write single or multiple elements to a power
monitor using PLC5 or SLC Typed messages in RSLogix5. This setup
applies to PLC5 programmable logic controllers.
Follow these steps to configure a message.
1. Choose an available message data block in your message
instruction.
In this example, we used MG9:0.
2. Click Setup Screen at the bottom of the message instruction.
The message configuration window for either Ethernet network
or Serial communcation appears.
26Publication 1408-UM001B-EN-P - May 2008
Explicit Messaging Chapter 4
3. Choose the appropriate parameters in the Message
Configuration window.
Ethernet Network Communication
Serial Communication
Communication TypeParameterChoice
EthernetCommunication CommandSelect the appropriate message type according to
Message Type
on page 18.
Data Table Address (This Controller)Read: This is the controller tag in which to store the data
being read.
Write: This is the controller tag that stores the value to be
written to the power monitor.
Size in ElementsThis is the number of elements being read or written to. If
you are performing a single element read or write, then
this value should be 1. If you are performing a multiple
element read or write, then this should be the number of
elements after the source element that you wish to read or
write.
Port Number2
Data Table Address (Target Device)Refer to Appendix
A for the address of the specific data
value you’re reading or writing to.
MultiHopYes
Publication 1408-UM001B-EN-P - May 200827
Chapter 4 Explicit Messaging
Communication TypeParameterChoice
SerialCommunication CommandSelect the appropriate message type according to
Message Type
Data Table AddressRead: This is the controller tag in which to store the data
being read.
Write: This is the controller tag that stores the value to be
written to the power monitor.
Size in ElementsThis is the number of elements being read or written to. If
you are performing a single element read or write, then
this value should be 1. If you are performing a multiple
element read or write, then this should be the number of
elements after the source element that you wish to read or
write.
Port Number0
Data Table Address (Target Device)Refer to Appendix
value you’re reading or writing to.
Local Station AddressThis is the serial node address of your power monitor.
Local / RemoteLocal
on page 18.
A for the address of the specific data
Message setup is complete for Serial communication.
4. Click the MultiHop tab if configuring Ethernet communication.
5. Enter the IP Address of the power monitor in the first row of the
To Address column.
Message setup is complete.
28Publication 1408-UM001B-EN-P - May 2008
Explicit Messaging Chapter 4
Reading Logs
You can perform explicit messages to read data from log records in
the power monitor.
For information on setting up explicit messages to the power monitor,
please refer to Explicit Message Setup – Examples
The following logs can be read into a controller depending on the
logs supported by your power monitor.
• Unit Status Log
• Min/Max Log
• Energy Log
• Load Factor Log
• Time of Use Log kWh
• Time of Use Log kVAR
• Time of Use Log kVA
Please refer to Appendix
log you are requesting.
A for the data table address of the specific
on page 17.
Log Data Table Methodology
The log data tables only hold one record instance for a specific log.
Successive reads of the data table return a successive record instance
for that log. By writing to specific configuration elements in the Log
Request Table data table, you can configure the log to return in a
forward or reverse direction. You can also configure the log to return
a specific record for all logs except the Unit Status Log, and Energy
Log.
Refer to
Log Request Table on page 64 for more information.
Publication 1408-UM001B-EN-P - May 200829
Chapter 4 Explicit Messaging
Example 1: Read the 5th Log Record in the Load Factor Log
This example explains how to configure the Log Request Table to
read the 5
1. Create a write message to write the following values to the Log
Element Item NameValue
0Selected Log4
1Chronology of Auto Return Data0
2Mix/Max Record to be Returned0
3Number of Unit Status Records0
4Number of Energy Log Records0
5Number of Time of Use Log Records0
6Number of Load Factor Log Records0
7Load Factor or TOU Record to be Returned5
th
log record in the Load Factor Log.
Request Table.
2. Create a read message to read the values in the Load Factor Log
table.
30Publication 1408-UM001B-EN-P - May 2008
Explicit Messaging Chapter 4
Example 2: Read Min/Max Log for Average Current
This example explains how to configure the Log Request Table to
read the Min/Max log for Average Current.
Refer to
Min/Max Parameter List on page 84 for the specific record to
return.
In this example, Average Current is record 4.
1. Create a write message to write the following values to the Log
Request Table.
Element Item NameValue
0Selected Log2
1Chronology of Auto Return Data0
2Mix/Max Record to be Returned4
3Number of Unit Status Records0
4Number of Energy Log Records0
5Number of Time of Use Log Records0
6Number of Load Factor Log Records0
7Load Factor or TOU Record to be Returned0
2. Create a read message to read the values in the Min/Max Log
table.
Publication 1408-UM001B-EN-P - May 200831
Chapter 4 Explicit Messaging
32Publication 1408-UM001B-EN-P - May 2008
Chapter
SCADA Applications
This section covers RSLinx driver setup, and OPC setup using the
RSLinx OPC Server.
5
RSLinx Classic Drivers
Configuration
The Powermonitor 1000 unit EDS file should be installed on the
computer running RSLinx software before configuring drivers. RSLinx
software supports DF1 Half-duplex, DF1 Full-duplex, and EtherNet/IP
network communication.
Configure DF1 Half-duplex Slave
You need to use a RS232 to RS485 converter like the 1761-NET-AIC or
B&B Electronics Converter – Model 485SD9TB.
1. Create a DF1 Polling Master Driver in RSLinx software.
2. Verify that the communication rate in the Port Configuration tab
is the same as the communication rate set for your power
monitor.
3. Set the Error Checking Mode in the DF1 Protocol Settings tab to
CRC.
4. Set the Destination Station Out-of-List Strategy in the Polling
Strategies tab to Allow Msgs to Stns that are not in lists.
5. Perform an RSWho to verify that RSLinx software is
communicating to the power monitor.
RSLinx software driver configuration is complete.
33Publication 1408-UM001B-EN-P - May 200833
Chapter 5 SCADA Applications
Configure DF1 Full-duplex
You need to use a RS232 to RS485 converter, like the 1761-NET-AIC or
B&B Electronics Converter – Model 485SD9TB.
1. Create a RS232 DF1 devices driver in RSLinx software.
2. Perform an Auto-configure.
3. Verify connections if Auto-configure fails.
4. Perform an RSWho to verify that RSLinx software is
communicating to the power monitor.
RSLinx software driver configuration is complete.
Configure RSLinx Software Driver Configuration for DH485
You need to use an RS232 to RS485 converter like the 1761-NET-AIC
converter or B&B Electronics Converter - Model 485SD9TB.
1. Open the RSLinx Launch Control Panel.
2. Start RSLinx software to run as normal application, not as
service.
3. Create a 1747-PIC/AIC+ Driver in RSLinx software.
4. Verify that the communication rate is the same as the
communication rate set for your power monitor.
5. Set the node address and maximum node address of RSLinx
Driver.
6. Perform an RSWho to verify that RSLinx software is
communicating to the power monitor.
7. Restart RSLinx software to run as service.
34Publication 1408-UM001B-EN-P - May 2008
SCADA Applications Chapter 5
Configure EtherNet/IP Network Using Ethernet Devices Driver
1. Create an Ethernet devices driver in RSLinx software.
2. Add the IP address of the power monitor to the driver station
mapping.
3. Perform an RSWho to verify that RSLinx software is
communicating to the power monitor.
RSLinx software driver configuration is complete.
Configure EtherNet/IP Network Using Ethernet/IP Driver
1. Create an Ethernet/IPdriver in RSLinx software.
RSLinx Classic Software
OPC Server Setup
2. Make selections to browse the local or remote subnet as
appropriate.
3. Perform an RSWho to verify that RSLinx software is
communicating to the power monitor.
RSLinx software driver configuration is complete.
IMPORTANT
You can setup RSLinx software as an OPC Server to serve data from a
power monitor to an OPC 2.0 compliant application. You must first
setup an RSLinx driver to communicate to the power monitor. You can
then create an OPC topic to serve data to your SCADA application.
The power monitor makes a connection to either the RSLinx
Ethernet Devices driver or the Ethernet/IP driver on a single
computer but not both simultaneously.
Setup OPC Topic
Follow these steps to setup a DDE/OPC topic in RSLinx software for
the power monitor.
1. Open RSLinx software.
Publication 1408-UM001B-EN-P - May 200835
Chapter 5 SCADA Applications
2. From the DDE/OPC menu, choose Topic Configuration.
This configuration window appears.
3. Click New.
This creates a topic in the left hand pane.
4. Name the topic pertinent to your application.
36Publication 1408-UM001B-EN-P - May 2008
SCADA Applications Chapter 5
5. In the right hand pane, under the Data Source tab, browse to
your power monitor.
You may use a serial or Ethernet network driver.
TIP
When using a DH485 driver, change the connection type to
local addressing mode in the Advanced Communication tab.
This is especially important when several topics use the DH485
driver.
6. Make sure that the topic is highlighted in the left pane, and that
the power monitor is also highlighted in the right pane, then
click Apply.
7. Click the Data Collection tab.
Publication 1408-UM001B-EN-P - May 200837
Chapter 5 SCADA Applications
8. From the Processor Type menu, choose SLC 500 or SLC 503+.
9. Click Done.
OPC Topic configuration is complete.
You can now use the RSLinx OPC Server, and the topic just created, to
serve data to your application.
OPC item addresses are of the format [OPC Topic Name]Address,Ln,C1
where Address is the power monitor data address (example: F21:7).
Optional argument Ln is the length of the array requested in elements.
If the Ln argument is used, C1 (number of array columns) must also
be specified.
38Publication 1408-UM001B-EN-P - May 2008
SCADA Applications Chapter 5
Browse OPC Tags
The power monitor supports OPC tag browsing. The example uses
the RSI OPC Test Client to illustrate tag browsing.
1. Open the RSI Test Client and connect to the RSLinx Classic OPC
Server.
2. Add a group, then add an item. Browse to the OPC topic and
then to the table and element in the Online tags.
Publication 1408-UM001B-EN-P - May 200839
Chapter 5 SCADA Applications
In this example, the User Configured Read Instance F9, element
8, in the OPC topic EM3_LAB is selected.
3. Click OK and start viewing data.
User-configured Data Table
The 1408-EM3 model provides a user configured data table. You may
select the 16 floating-point parameters that comprise this table. Your
application may read this table as connected input instance 1, or as
CSP file F9 using explicit messaging.
Setup
You must use serial or Ethernet network communication to set up and
read the user configured data table.
To set up the user configured table, using explicit messaging, write a
new configuration to the User Configured Table Setup table.
See page 92
of the setup table. Pages 93…96
parameters.
for the content, default parameters and addressing details
list the available selections for the
40Publication 1408-UM001B-EN-P - May 2008
SCADA Applications Chapter 5
Reading the User Configured Table as Connected Instance 1
The following example illustrates the steps required to set up an I/O
connection between a Logix controller and the user configured
Instance 1. The example uses a CompactLogix controller and
RSLogix 5000 software.
Follow these steps to configure the connection.
1. Open an offline project in RSLogix 5000 software.
2. Open the Ethernet network interface and select the Ethernet
network.
3. Add a new module and choose Generic Ethernet Module from
the Communications group.
4. Configure the properties of the new module and click OK.
ParameterChoice
NameYour choice of name
Comm FormatInput Data - REAL
IP AddressThe IP address of your power monitor
InputAssembly Instance 1; Size 16 (32-bit)
OutputAssembly Instance 2
ConfigurationAssembly Instance 3; Size 0
Open Module PropertiesLeave checked
Publication 1408-UM001B-EN-P - May 200841
Chapter 5 SCADA Applications
5. On the connection tab, enter the desired Requested Packet
Interval (RPI).
Do not enter an RPI less than 50 mS.
6. Click OK, then Save and download the offline project into the
controller.
The data from the user configured table is read into the controller tag
[Module Name]:I.Data without any further logic programming, at the
selected RPI rate.
A power monitor connected instance may be owned by only one
controller. An error results if you attempt to establish a connection
with more than one controller. You may use explicit messaging to
read the F9 table from any number of controllers.
42Publication 1408-UM001B-EN-P - May 2008
Powermonitor 1000 Data Tables
Appendix
A
Summary of Data Tables
Summary of Powermonitor 1000 Data Tables for all Communication Protocols
Name of data tableData
Access
User Configured Table ResultsRF9131601…31632 16•45
Analog Input ConfigurationRWF10340001…400147•••••46
Advanced ConfigurationRWF11440101…40144 22•••••47
The Summary of Powermonitor 1000 Data Tables for all
Communication Protocols table summarizes all data tables available
and their general attributes
The rest of the tables detail each specific data table and its associated
elements, such as Modbus address, default value, ranges, and
description.
IMPORTANT
CSP
File No.
CIPModbus
The lock symbol designates that the parameter that is
marked will not be able to be written when the hardware lock
terminals are connected together.
No of
Addressing
Elements
TR1
TR2
EM1
EM2
EM3
Refer to
Page
RS485 ConfigurationRWN12540201…402099•••••51
Ethernet ConfigurationRWN13640301…40323 23•••••52
Time Zone Information54
Date and Time ConfigurationRWN14740401…404088•••••57
Log ConfigurationRWN15840501…40512 12•••58
CommandWF16940601…4064422•••••61
Log RequestRWN171040701…4071111•••••64
Controller InterfaceWN181140801…408088••66
Discrete ResultRN191230001…300066•••••67
Wiring Diagnostics ResultsRF201330101…30142 21•••••68
Volts, Amps and Frequency
Results
Power ResultsRF221530301…30334 17•••71
Energy ResultsRF231630401…30438 19•••72
Publication 1408-UM001B-EN-P - May 200843
RF211430201…30232 16•••70
Appendix A Powermonitor 1000 Data Tables
Summary of Powermonitor 1000 Data Tables for all Communication Protocols
Name of data tableData
Access
CSP
File No.
CIPModbus
Addressing
No of
Elements
TR1
TR2
EM1
EM2
Refer to
Page
EM3
Demand ResultsRF241730501…30518 9••73
Unit Status Log ResultsRN251830601…3061313•••••74
Unit Status Log Code76
Energy Log ResultsRF261930701…30742 21•••78
Write Error Status Results RN272030801…30803 3•••••79
Unit Run Status ResultsRN282130901…30925 25•••••80
Min/Max Log ResultsRF292231001…31022 11•••83
Min/Max Parameter List•••84
Load Factor Log Results RF302331101…31128 14••85
Time of Use Log Results- Real
RF312431201…31224 12•••87
Energy and Demand
Time of Use Log Results -
RF322531301…31324 12••88
Reactive Energy and Demand
Time of Use Log Results -
RF332631401…31424 12••89
Apparent Energy and Demand
Catalog Number and WINRN342731501…31519 19•••••90
Single Element Password WriteWN3528409011•••••91
User Configurable Table SetupR/WN362941001…41017 17•92
Parameters for Configurable
Table
93
44Publication 1408-UM001B-EN-P - May 2008
Powermonitor 1000 Data Tables Appendix A
Data Tables
User Configured Table Results
Element No. Modbus
Address
031601-2User selected Parameter #1Parameters previously setup during a write to User Configured Table
131603-4User selected Parameter #2
231605-6User selected Parameter #3
331607-8User selected Parameter #4
431609-10User selected Parameter #5
531611-12User selected Parameter #6
Element NameDescription
User Configured Table Results Parameters
CSP File No.F9
CIP Instance1
Applies toEM3 only
No. of Elements16
No. of Words32
Data TypeFloat
Data AccessRead Only
CSP File No.F10
CIP Instance3
Applies toAll models
No. of Elements7
No. of Words14
Data TypeFloat
Data AccessRead/Write
Element
No.
Modbus
Address
Element NameDefault
Value
RangeDescription
040001-2Password00…9999When writing the complete table this parameter allows the
input data to be accepted. When writing a single parameter
the separate password table should be used. Returns -1 on a
read.
140003-4Voltage Mode20…4Should match the external electrical system and how it is
wired to the Powermonitor’s voltage and current input
terminals. Refer to the installation manual wiring diagrams.
0 = Direct Delta
1 = Open Delta
2 = Wye
3 = Single Phase
4 = Demo
240005-6PT Primary4801.00…
50,000
The first value of the PT ratio (xxx:xxx) indicating the nominal
voltage present at the high-end of the transformer. If no
transformer is used (for direct connect of up to 347V L-N or
600V L-L), set the PT ratio to any valid 1:1 ratio (for example
480:480).
340007-8PT Secondary4801.00…
600.00
The second value of the PT ratio (xxx:xxx) indicating the
nominal voltage present at the low-end of the transformer.
440009-10CT Primary55.00…
50,000
The first value of the CT ratio (xxx:5) indicating the nominal
current present at the high-end (primary side) of the
transformer.
Example: PRI = 1000. Setting = 1000:5.
5 A is the nominal secondary current of the CT.
540011-12System PF Setting20…20 = Leading -97…89
1 = High -85…98
2 = Low -52…-95
640013-14Reserved00Reserved for future use.
46Publication 1408-UM001B-EN-P - May 2008
Advanced Configuration
Powermonitor 1000 Data Tables Appendix A
Advanced Configuration Parameters
CSP File No.F11
CIP Instance4
No. of Elements22
No. of Words44
Data TypeFloat
Data AccessRead/Write
Element
No.
Modbus
Address
Range
Element
Name
Default
Value
Range
Description
TR1
TR2
EM1
EM2
EM3
040101-2Password00…9999•••••When writing the complete table this
parameter allows the input data to be
accepted. When writing a single
parameter the separate password table
should be used. Returns -1 on a read.
140103-4New
Password
00…9999•••••This becomes the new password when the
proper the configuration password entry
has been made and this parameter is
greater than (-1).
240105-5Metering
Result
Averaging
10…1•••••The metering results for volts, amps,
power and frequency is averaged over 8
cycles of data to provide a steady output
reading.
0 = Off
1 = On
340107-8Log Status
Input
Changes
00…1•••••0 = Disable recording of status input
changes into the status log.
1 = Enable recording of status input
changes into the status log.
440109-10Use Daylight
Savings
00…1•••••0 = Disable Daylight Savings
1 = Enable Daylight Savings
Correction
Publication 1408-UM001B-EN-P - May 200847
Appendix A Powermonitor 1000 Data Tables
Advanced Configuration
Element
No.
Modbus
Address
Element
Name
Range
540111-12Daylight
Savings
Month/Week
/Day Start
640113-14Hour of Day
Start
740115-16Return from
Daylight
Savings
Month/Week
/Day
Default
Range
Description
Value
TR1
TR2
EM1
EM2
EM3
030201
March,
2nd,
10101…
120507
•••••This is the day that the power monitor will
add an hour to the time. This feature also
looks at Ethernet SNTP offset and corrects
for Daylight Savings.
Sunday
Example: 040107 = April/1st week/Sunday
Month Settings:
01 = January…12 = December
Week Settings:
01 = 1st week…05 = Last Week
Day of the Week Settings:
01 = Sunday…07 = Saturday
20…23•••••The hour of day the daylight savings
adjustment should be made to add an
hour.
110101
November,
1st,
Sunday
10101…
120507
•••••This is the day that the power monitor will
subtract an hour from the time. This
feature also looks at Ethernet SNTP offset
and corrects for the return from Daylight
Savings.
840117-18Hour of Day
End
940119-20KYZ Solid
State Output
Parameter
1040121-22KYZ Solid
State Output
Scale
Month Settings:
01 = January…12 = December
Week Settings:
01 = 1st week…05 = Last Week
Day of the Week Settings:
01 = Sunday…07 = Saturday
20…23•••••The hour of day the daylight savings
adjustment should be made to subtract an
hour.
00…5•••The parameter selected will pulse the KYZ
output at a rate that equals the parameter
value divided by KYZ scale.
scale is the output pulse rate. Example:
Wh is selected for the parameter and
1,000 is the scale value. The output is
pulsed every kWh.
48Publication 1408-UM001B-EN-P - May 2008
Advanced Configuration
Powermonitor 1000 Data Tables Appendix A
Element
No.
Modbus
Address
Element
Name
Range
1140123-24KYZ Pulse
Duration
Setting
1240125-26Status Input
1 Input Scale
1340127-28Status Input
2 Input Scale
1440129-30Demand
Source
Default
Range
Description
Value
TR1
TR2
EM1
EM2
EM3
250 ms0 or
50…1000
•••Set as 50…1000 to indicate the duration
of the pulse in milliseconds, or set to 0 for
KYZ-style transition output. (Toggle)
The value for delay is rounded off to the
nearest 10ms internally during this
function.
11…
1,000,000
•••When a status pulse is received the count
is increased by the scale factor. Input
pulse * input scale added to total status
count.
11…
1,000,000
•••When a status pulse is received the count
is increased by the scale factor. Input
pulse * input scale added to total status
count.
00…3••When item Demand Broadcast Master
Select of the ethernet table is set to
master a selection of 0 through 2 sets the
type of master input. In this case item 3 is
ignored. When the Demand Broadcast
Master Select of the ethernet table is set
to slave then any of these inputs can set
the end of the demand period. Selections
of 0 through 2 can be selected for RS485
units.
Selection 3 can only be programmed when
the Ethernet option is installed.
15 min0…99••Specifies the desired period for demand
calculations. When set to 0 there are no
projected demand calculations. If the
internal timer is selected a setting of 0
turns the demand function off.
11…15••Specifies the number of demand periods
to average for demand measurement.
Publication 1408-UM001B-EN-P - May 200849
Appendix A Powermonitor 1000 Data Tables
Advanced Configuration
Element
No.
Modbus
Address
Element
Name
Range
1740135-36Forced
Demand
Sync Delay
1840137-38Unit Error
Action
1940139-40Software
Error Log Full
Action
Default
Range
Description
Value
TR1
TR2
EM1
EM2
EM3
10 s0…900 s••When the power monitor is configured for
external demand control the unit delays
for xxx seconds after the expected control
pulse has not been received. The demand
period starts over and a record is recorded
in the status log.
0 = Wait forever
1…900 = Wait this many seconds before
starting a new demand period.
This setting becomes active when the
demand interval is set from -1…-99
minutes.
10…1•••••This parameter determines the action
when a unit error occurs.
0 = Halt on error and make status LED
solid red
1 = Reset power monitor hardware.
10…1•••••This parameter determines the action
when a firmware failure is detected and
the error log is full.
0 = Halt on error and wait for clear log
command, also make status LED solid red
1 = Perform a firmware reset.
2040141-42Reserved00•••••Reserved for future use.
2140143-44Reserved00•••••Reserved for future use.
50Publication 1408-UM001B-EN-P - May 2008
Serial RS-485 Port Configuration
Powermonitor 1000 Data Tables Appendix A
Serial RS-485 Port Configuration Parameters
CSP File No.N12
CIP Instance5
Applies toAll models
No. of Elements9
No. of Words9
Data TypeInteger
Data AccessRead/Write
Element
No.
Modbus
Address
Element NameDefault
Value
RangeDescription
040201Password00…9999When writing the complete table this parameter allows the input
data to be accepted. When writing a single parameter the separate
password table should be used. Returns -1 on a read.
140202Protocol Setting10…3The protocol selection for communications.
0 = DF1 Half Duplex Slave
1 = DF1 Full Duplex
2 = Modbus RTU Slave
3 = Auto Sense
4 = DH485
240203Serial Delay2
(10 ms)
1…15The setting times 5 = milliseconds that the unit waits before
responding to a communication request. Useful for consistent
communications and slow devices.
340204Baud Rate50…6The serial communications baud rate.
During production the Device ID is printed on the nameplate. This ID
then becomes the default address for DF1 and Modbus.
(DH485)
Publication 1408-UM001B-EN-P - May 200851
Appendix A Powermonitor 1000 Data Tables
Serial RS-485 Port Configuration
Element
No.
540206Data Format00…2
Modbus
Address
Element NameDefault
Value
RangeDescription
Parity, number of data bits, number of stop bits
(2 for
DH485)
0 = No parity, 8 data bits, 1 stop bit
1 = Odd parity, 8 data bits, 1 stop bit
2 = Even parity, 8 data bits, 1 stop bit
640207Inter Character
Timeout
00…
6553
Specifies the minimum delay between characters that indicates the
end of a message packet for Modbus protocol. 0 = 3.5 character
times in default. The unit is ms.
840208Maximum Node
31…31Specifies the maximum node address on a DH485 network.
Address
940209Reserved00Reserved for future use.
Ethernet Configuration Parameters
CSP File No.N13
CIP Instance6
No. of Elements23
No. of Words23
Data TypeInteger
Data AccessRead/Write
Ethernet Configuration
Element
No.
Modbus
Address
Element NameDefault
Value
Range
TR1
TR2
EM1
EM2
Description
EM3
040301Password00…9999•••••When writing the complete table this
parameter allows the input data to be
accepted. When writing a single
parameter the separate password table
should be used. Returns -1 on a read.
140302IP Address Byte a
1920…255•••••The 1st Octet of the Static IP Address.
(aaa.xxx.xxx.xxx)
240303IP Address Byte b
1680…255•••••The 2nd Octet of the Static IP Address.
(xxx.bbb.xxx.xxx)
340304IP Address Byte c
2540…255•••••The 3rd Octet of the Static IP Address.
(xxx.xxx.ccc.xxx)
440305IP Address Byte d
Unit ID0…255•••••The 4th Octet of the Static IP Address.
(xxx.xxx.ddd.xxx)
52Publication 1408-UM001B-EN-P - May 2008
Ethernet Configuration
Powermonitor 1000 Data Tables Appendix A
Element
No.
Modbus
Address
Element NameDefault
Value
Range
TR1
TR2
EM1
EM2
Description
EM3
540306Subnet Mask Byte a 2550…255•••••Specifies the subnet mask to apply to
the IP address.
640307Subnet Mask Byte b 2550…255•••••Specifies the subnet mask to apply to
the IP address.
740308Subnet Mask Byte c 00…255•••••Specifies the subnet mask to apply to
the IP address.
840309Subnet Mask Byte d 00…255•••••Specifies the subnet mask to apply to
the IP address.
940310Gateway IP Address
Byte a
1040311Gateway IP Address
Byte b
1140312Gateway IP Address
Byte c
1240313Gateway IP Address
Byte d
1280…255•••••IP address of the gateway to other
subnets for wide area networking.
10…255•••••IP address of the gateway to other
subnets for wide area networking.
10…255•••••IP address of the gateway to other
subnets for wide area networking.
10…255•••••¸ IP address of the gateway to other
subnets for wide area networking.
1340314SNTP Mode Select00…2•••••This mode selects the mode of the SNTP
function or to disable the SNTP function.
0 = Disable
1 = Unicast - The SNTP address points to
a unicast server.
2 = Anycast Mode - The SNTP address is
a broadcast address of an anycast
group.
1440315SNTP Update
Interval
3001…32766•••••Indicates how often the time is updated
from the SNTP Server. The unit is
minute.
1540316Time Zone Select70…32•••••The time zone table has detailed time
zone information.
1640317Time Server IP
Address Byte a
00…255•••••The internal clock is set after each Time
set interval has expired. The Time server
IP address is the SNTP time server
where the request is handled.
1740318Time Server IP
Address Byte b
00…255•••••The internal clock is set after each Time
set interval has expired. The Time server
IP address is the SNTP time server
where the request is handled.
1840319Time Server IP
Address Byte c
00…255•••••The internal clock is set after each Time
set interval has expired. The Time server
IP address is the SNTP time server
where the request is handled.
Publication 1408-UM001B-EN-P - May 200853
Appendix A Powermonitor 1000 Data Tables
Ethernet Configuration
Element
No.
1940320Time Server IP
Modbus
Address
Element NameDefault
Value
00…255•••••The internal clock is set after each Time
Address Byte d
Range
TR1
TR2
EM1
Description
EM2
EM3
set interval has expired. The Time server
IP address is the SNTP time server
where the request is handled.
2040321Demand Broadcast
Master Select
00…1••When configured as a Master the power
monitor broadcasts an end of demand
interval broadcast to the UDP port
number configured.
0 = Slave
1 = Master control
2140322Broadcast Port
Number
300300…400••When configured as a Master and
External Demand Source or Ethernet
Demand Broadcast the port number is
the listening or broadcast port for the
UDP message.
2240323Reserved00••••• Reserved for future use.
Time Zone Information
ValueOffset from GMTTime Zone NameAreas in Time Zone
0GMT-12:00Dateline Standard TimeEniwetok, Kwajalein
1GMT-11:00Samoa Standard TimeMidway Island, Samoa
2GMT-10:00Hawaiian Standard TimeHawaii
3GMT-09:00Alaskan Standard TimeAlaska
4GMT-08:00Pacific Standard TimePacific Time (US & Canada,; Tijuana)
5GMT-07:00Mountain Standard TimeMountain Time (US & Canada)
US Mountain Standard TimeArizona
6GMT-06:00Canada Central Standard TimeSaskatchewan
Central America Standard TimeCentral America
Central Standard TimeCentral Time (US & Canada)
Mexico Standard TimeMexico City
7GMT-05:00Eastern Standard TimeEastern Time (US & Canada)
SA Pacific Standard TimeBogota, Lima, Quito
US Eastern Standard TimeIndiana (East)
8GMT-04:00Atlantic Standard TimeAtlantic Time (Canada)
Pacific SA Standard TimeSantiago
SA Western Standard TimeCaracas, La Paz
9GMT-03:30Newfoundland Standard TimeNewfoundland
54Publication 1408-UM001B-EN-P - May 2008
Powermonitor 1000 Data Tables Appendix A
Time Zone Information
ValueOffset from GMTTime Zone NameAreas in Time Zone
10GMT-03:00E. South America Standard TimeBrasilia
Greenland Standard TimeGreenland
SA Eastern Standard TimeBuenos Aires, Georgetown
11GMT-02:00Mid-Atlantic Standard TimeMid-Atlantic
12GMT-01:00Azores Standard TimeAzores
Cape Verde Standard TimeCape Verde Is.
13GMTStandard TimeGreenwich Mean Time: Dublin, Edinburgh, Lisbon, London
Greenwich Standard TimeCasablanca, Monrovia
14GMT+01:00Central Europe Standard TimeBelgrade, Bratislava, Budapest, Ljubljana, Prague
Central European Standard TimeSarajevo, Skopje, Sofija, Vilnius, Warsaw, Zagreb
Romance Standard TimeBrussels, Copenhagen, Madrid, Paris
W. Central Africa Standard TimeWest Central Africa
W. Europe Standard TimeAmsterdam, Berlin, Bern, Rome, Stockholm, Vienna
15GMT+02:00E. Europe Standard TimeBucharest
Egypt Standard TimeCairo
FLE Standard TimeHelsinki, Riga, Tallinn
GTB Standard TimeAthens, Istanbul, Minsk
Israel Standard TimeJerusalem
South Africa Standard TimeHarare, Pretoria
16GMT+03:00Arab Standard TimeKuwait, Riyadh
Arabic Standard TimeBaghdad
E. Africa Standard TimeNairobi
Russian Standard TimeMoscow, St. Petersburg, Volgograd
17GMT+03:30Iran Standard TimeTehran
18GMT+04:00Arabian Standard TimeAbu Dhabi, Muscat
Caucasus Standard TimeBaku, Tbilisi, Yerevan
19GMT+04:30Afghanistan Standard TimeKabul
20GMT+05:00Ekaterinburg Standard TimeEkaterinburg
West Asia Standard TimeIslamabad, Karachi, Tashkent
21GMT+05:30India Standard TimeCalcutta, Chennai, Mumbai, New Delhi
22GMT+05:45Nepal Standard TimeKathmandu
23GMT+06:00Central Asia Standard TimeAstana, Dhaka
N. Central Asia Standard TimeAlmaty, Novosibirsk
Sri Lanka Standard TimeSri Jayawardenepura
24GMT+06:30Myanmar Standard TimeRangoon
Publication 1408-UM001B-EN-P - May 200855
Appendix A Powermonitor 1000 Data Tables
Time Zone Information
ValueOffset from GMTTime Zone NameAreas in Time Zone
25GMT+07:00North Asia Standard TimeKrasnoyarsk
SE Asia Standard TimeBangkok, Hanoi, Jakarta
26GMT+08:00China Standard TimeBeijing, Chongqing, Hong Kong, Urumqi
North Asia East Standard TimeIrkutsk, Ulaan Bataar
Singapore Standard TimeKuala Lumpur, Singapore
Taipei Standard TimeTaipei
W. Australia Standard TimePerth
27GMT+09:00Korea Standard TimeSeoul
Tokyo Standard TimeOsaka, Sapporo, Tokyo
Yakutsk Standard TimeYakutsk
28GMT+09:30AUS Central Standard TimeDarwin
Cen. Australia Standard TimeAdelaide
29GMT+10:00AUS Eastern Standard TimeCanberra, Melbourne, Sydney
E. Australia Standard TimeBrisbane
Tasmania Standard TimeHobart
Vladivostok Standard TimeVladivostok
West Pacific Standard TimeGuam, Port Moresby
30GMT+11:00Central Pacific Standard TimeMagadan, Solomon Is., New Caledonia
31GMT+12:00Fiji Standard TimeFiji, Kamchatka, Marshall Is.
New Zealand Standard TimeAuckland, Wellington
32GMT+13:00Tonga Standard TimeNuku'alofa
56Publication 1408-UM001B-EN-P - May 2008
Date and Time Configuration
Powermonitor 1000 Data Tables Appendix A
Date and Time Configuration Parameters
CSP File No.N14
CIP Instance7
Applies toAll models
No. of Elements8
No. of Words8
Data TypeInteger
Data AccessRead/Write
Element
No.
Modbus
Address
Element NameDefault
Value
RangeDescription
040401Password00…9999When writing the complete table this parameter allows the
input data to be accepted. When writing a single parameter the
separate password table should be used. Returns -1 on a read.
140402Date: Year20052001…
The range is from 2001… 2100. A write sets the current year.
2100
240403Date: Month11…12A write sets the current month.
A read returns current month.
1=January, 2=February,…12=December
340404Date: Day11…31A write sets the current day of the month.
A reads returns the current day of the month.
The internal real-time clock adjusts the date for leap-year.
440405Time: Hour00…23A write sets the current hour.
A read returns the current hour.
0=12am, 1=1am,…23=11pm
The internal real-time clock does not adjust for daylight savings
time.
540406Time: Minute00…59A write sets the current minutes.
A read returns the current minutes.
640407Time: Seconds00…59A write sets the current seconds.
A read returns the current seconds.
740408Time: Hundredths00…99Set this element to 0 for writes. Returns hundredths of a second
on read.
Publication 1408-UM001B-EN-P - May 200857
Appendix A Powermonitor 1000 Data Tables
Log Configuration
Log Configuration Parameters
CSP File No.N15
CIP Instance8
No. of Elements12
No. of Words12
Data TypeInteger
Data AccessRead/Write
Element
No.
Modbus
Address
Element Name Default
Value
Range
040501Password00…
9999
140502Energy Log
15 min-1…60•••Selects how often a record is logged
Interval
240503Energy Log
10…1•••This parameter set the action of the log
Mode
340504Time of Use Log
310…31•••Automatically stores the current record
Auto Log
Setting
Description
TR1
TR2
EM1
EM2
EM3
•••When writing the complete table this
parameter allows the input data to be
accepted. When writing a single
parameter the separate password table
should be used. Returns -1 on a read.
(minutes). A value of 0 disables periodic
logging of records. A value of –1 causes
logging of records to be synchronized to
the end of the demand interval.
once is has filled to capacity. Setting the
option to 0 allows the log to fill but stops
at the end. Option 1 lets the log fill and
then oldest records are deleted and
replaced with new records.
0 = Fill and Stop
1 = Overwrite, When the log is filled new
records replace the oldest records.
for the month replacing the oldest record
if the log is full. The log holds 12 months
plus the current record.
0 = Disables the auto clear feature.
1 = Store and clear the table on the 1st
day of each month.
2 = 2nd Day
3 = 3rd day
…
29…31 = Store and clear table at the
last day of the month.
58Publication 1408-UM001B-EN-P - May 2008
Log Configuration
Powermonitor 1000 Data Tables Appendix A
Element
No.
Modbus
Address
Element Name Default
Value
Range
TR1
TR2
EM1
EM2
Description
EM3
440505Off Peak Days650…127•••This bit map field selects the off peak
days. OFF-PEAK days have only one rate
for billing.
Bit0= Sunday
Bit1= Monday
Bit2= Tuesday
Bit3= Wednesday
Bit4= Thursday
Bit5= Friday
Bit6= Saturday
Saturday and Sunday are default Off
Peak days.
540506MID Peak AM
Hours
17920…
4095
•••This bit map selects any AM hours that
are designated as MID Peak. Example:
The hours from 8 AM to 11AM is
designated as bit 8 through bit 10 =
1792d.
Bit0= 12 AM…1 AM
Bit1= 1 AM…2 AM
Bit2= 2 AM…3 AM
…
…
Bit11= 11AM…12 AM
Default is 8 AM…11 AM
640507MID Peak PM
Hours
1200…
4095
•••This bit map selects any PM hours that
are designated as MID Peak. Example:
The hours from 3 PM to 7 PM is
designated as bit 3 through bit 6 = 120d.
average, and load factor results as a
record in the non-volatile load factor log
and resets the log at the specified day of
the month.
0 = Disables the auto clear feature.
1 = Store and clear the table on the 1st
day of each month.
2 = 2nd Day
3 = 3rd day
…
29…31 = Store and clear table at the
last day of the month.
1040511Reserved00•••••Reserved for future use.
1140512Reserved00•••••Reserved for future use.
Command Table Parameters
CSP File No.F16
CIP Instance9
No. of Elements22
No. of Words44
Data TypeFloat
Data AccessWrite
60Publication 1408-UM001B-EN-P - May 2008
Command Table
Powermonitor 1000 Data Tables Appendix A
Element
No.
Modbus
Address
Element Name Default
Value
Range
TR1
TR2
EM1
EM2
Description
EM3
040601-2Password00…9999•••••When writing the complete table this
parameter allows the input data to be
accepted. When writing a single
parameter the separate password table
should be used. Returns -1 on a read.
140603-4Command Word 100…32•••••These commands can be sent to the
power monitor. When using the optional
elements the command table must be
sent complete with all elements present.
If the single password table is used to
gain access to configuration items then
the command can be sent alone without
optional settings. The command options
are:
0 = No Action
1 = Set kWh Register
2 = Set kVARh Register
3 = Set kVAh Register
4 = Clear All Energy Registers
5 = Set Status 1 Count
6 = Set Status 2 Count
7 = Clear Energy Log
8 = Force KYZ Output On
9 = Force KYZ Output Off
10 = Remove Force from KYZ
11 = Restore Factory Defaults
12 = Perform Wiring Diagnostics
13 = Reset power monitor System
14…32 = Reserved
If a command is received that is not
supported by your catalog number the
command will be ignored.
240605-6Command Word 200…32•••••0 = No Action
1 = Clear Min/Max Records
2 = Store and clear current Load Factor
Record
3 = Clear Load Factor Log
4 = Store and clear current TOU Record
5 = Clear TOU Log
6 = Clear Error Log command
7 = Troubleshooting Mode Enable
8…32 = Reserved.
If a command is received that is not
supported by your catalog number the
command will be ignored.
Publication 1408-UM001B-EN-P - May 200861
Appendix A Powermonitor 1000 Data Tables
Command Table
Element
No.
Modbus
Address
Element Name Default
340607-8Clear Single
Min/Max
Records
440609-10Status 1 Count x
M Register Set
Value
540611-12Status 1 Count
X 1 Register Set
Value
640613-14Status 2 Count x
M Register Set
Value
740615-16Status 2 Count
X 1 Register Set
Value
840617-18GWh Fwd
Register Set
Value
940619-20kWh Fwd
Register Set
Value
1040621-22GWh Rev
Register Set
Value
1140623-24kWh Rev
Register Set
Value
1240625-26GVARh Fwd
Register Set
Value
1340627-28kVARh Fwd
Register Set
Value
1440629-30GVARh Rev
Register Set
Value
Range
Value
00…35
0…31
0…19
00…
9,999,999
00…
999,999
00…
9,999,999
00…
999,999
00…
9,999,999
00…
999,999
00…
9,999,999
00…
999,999
00…
9,999,999
00…
999,999
00…
9,999,999
Description
TR1
TR2
EM1
EM2
EM3
•••When setting the Min/Max Clear bit this
value can be sent to specify a single
parameter. If clearing all values this is
not required.
EM3 = 0…35
TR2 = 0…31
TR1 = 0…19
0=Clear All Parameters
1= Clear the 1st Min/Max Record
2= Clear the 2nd Min/Max Record
…
35=Clear the 35th Min/Max Record
•••Status 1 Count Register Start Value x
1,000,000
•••Status 1 Count Register Start Value x 1
•••Status 2 Count Register Start Value x
1,000,000
•••Status 2 Count Register Start Value x 1
•••Sets the GWh Fwd Register to the
desired Value
•••Sets the kWh Fwd Register to the
desired Value
•••Sets the GWh Rev Register to the
desired Value
•Sets the kWh Rev Register to the
desired Value
••Sets the GVARh Fwd Register to the
desired Value
••Sets the kVARh Fwd Register to the
desired Value
••
Sets the GVARh Rev Register to the
desired Value
62Publication 1408-UM001B-EN-P - May 2008
Command Table
Powermonitor 1000 Data Tables Appendix A
Element
No.
Modbus
Address
Element Name Default
1540631-32kVARh Rev
Register Set
Range
Value
00…
999,999
TR1
TR2
EM1
EM2
••Sets the kVARh Rev Register to the
Description
EM3
desired Value
Value
1640633-34GVAh Register
Set Value
1740635-36kVAh Register
Set Value
1840637-38Troubleshooting
Password
00…
9,999,999
00…
999,999
••Sets the GVAh Register to the desired
Value
••Sets the kVAh Register to the desired
Value
00••••Password for Troubleshooting Mode
provided by the password generator
program.
1940639-40Reserved00•••••Reserved for future use.
2040641-42Reserved00•••••Reserved for future use.
2140643-44Reserved00•••••Reserved for future use.
Publication 1408-UM001B-EN-P - May 200863
Appendix A Powermonitor 1000 Data Tables
Log Request Table
Log Request Table Parameters
CSP File No.N17
CIP Instance10
No. of Elements11
No. of Words11
Data TypeInteger
Data AccessRead/Write
Element
No.
Modbus
Address
Element Name Default
Value
Range
TR1
TR2
EM1
EM2
Description
EM3
040701Selected Log00…5•••••Selects the log that information is
returned from. Once a single request
has been made the auto return feature
will bring back successive records
each time the log is read. Some logs
support individual record requests.
1 = Unit Status Log
2 = Min/Max Log
3 = Energy Log
4 = Load Factor Log
5 = Time of Use Log kWh
6 = Time of Use Log kVAR
7 = Time of Use Log kVA
If your catalog number does not
support the requested log item the
power monitor will ignore the request.
140702Chronology of
Auto Return
Data
10…1•••••The date chronology of the returned
records.
0 = Reverse direction
1 = Forward direction
240703The Min/Max
record to be
returned
00…35
0…31
0…15
•••Selects the Min/Max record number
to be returned. See the table for
Min/Max record list.
0 = Use incremental return and the
chronology selected.
EM3 = 1…35
TR2 = 1…31
TR1 = 1…15
340704Number of Unit
Status Records
-1…50•••••On a read of this table the value of this
parameter is the number of Unit
Status Records available. This log is
only returned using the incremental
return method.
64Publication 1408-UM001B-EN-P - May 2008
Log Request Table
Powermonitor 1000 Data Tables Appendix A
Element
No.
Modbus
Address
Element Name Default
440705Number of
Energy Log
Records
540706Number of Time
of Use Log
Records
640707Number of Load
Factor Log
Records
740708Load Factor or
TOU Record to
be Returned.
Range
Value
-0…
17,280
TR1
TR2
EM1
EM2
•••On a read of this table the value of this
Description
EM3
parameter is the number of Energy Log
Records available.
-1…13•••On a read of this table the value of this
parameter is the number of Time of
Use Log Records available. One is the
current record being updated before
logging.
-1…13••On a read of this table the value of this
parameter is the number of Load
Factor Log Records available. One is
the current record being updated
before logging.
-0…13•••••Selects the Load Factor or TOU record
number to be returned.
0 = Use incremental return and the
chronology selected
1 through 13 selects an individual
record.
840709Reserved-0•••••Reserved for future use.
940710Reserved-0•••••Reserved for future use.
1040711Reserved-0•••••Reserved for future use.
Publication 1408-UM001B-EN-P - May 200865
Appendix A Powermonitor 1000 Data Tables
Controller Interface Table
Controller Interface Table Parameters
CSP File No.N18
CIP Instance11
Applies toEM2, EM3 only
No. of Elements8
No. of Words8
Data TypeInteger
Data AccessWrite
Element
No.
Modbus
Address
Element Name Default
Value
RangeDescription
040801Password00…9999When writing the complete table this parameter allows the input
data to be accepted. When writing a single parameter the separate
password table should be used. Returns -1 on a read.
140802Controller
Command Word
00…1Bit 0 = When this bit is written to the power monitor it signals the
end of the demand period. The power monitor resets the bit to 0 and
sends the end of demand broadcast to all of the slaves configured for
the master/slave demand system. The power monitor must be
configured as a Master for external demand pulse input.
Bit 1…15 = Reserved
240803Reserved00Reserved for future use.
340804Reserved00Reserved for future use.
440805Reserved00Reserved for future use.
540806Reserved00Reserved for future use.
640807Reserved00Reserved for future use.
740808Reserved00Reserved for future use.
66Publication 1408-UM001B-EN-P - May 2008
Discrete Results
Powermonitor 1000 Data Tables Appendix A
Discrete Results Parameters
CSP File No.N19
CIP Instance12
Applies toAll models
No. of Elements6
No. of Words6
Data TypeInteger
Data AccessRead
Element
No.
Modbus
Address
Element NameRangeDescription
030001Status Input States0…3Indicates the current states of the status input.
Bit 0 = Status 1 activated
Bit 1 = Status 2 activated
Bit 2…15 = Reserved
130002Output Word0…15Bit 0 = KYZ relay actuated
Bit 1 = KYZ output forced on
Bit 2 = KYZ output forced off
Bit 3 = External demand pulse timeout
Bit 4 = Terminal Locked
Bit 5…15 = Reserved
230003Reserved0Reserved for future use.
330004Reserved0Reserved for future use.
430005Reserved0Reserved for future use.
530006Reserved0Reserved for future use.
Publication 1408-UM001B-EN-P - May 200867
Appendix A Powermonitor 1000 Data Tables
Wiring Diagnostics Results
Wiring Diagnostics Results Parameters
CSP File No.F20
CIP Instance13
No. of Elements21
No. of Words42
Data TypeFloat
Data AccessRead
Element
No.
Modbus
Address
Element NameUnitsRange
TR1
TR2
EM1
EM2
Description
EM3
030101-2Wiring Status0…5•••••This is the overall status of the
wiring diagnostic test.
0 = Pass
1 = Failed
2 = Input Level Low
3 = Disabled
4 = Waiting Command
5 = Out of range
130103-4Voltage Input
Missing
-1…123•••••Reports on all three phases.
-1 = Test not run.
0 = Test passed.
1 = Phase 1 missing
2 = Phase 2 missing
3 = Phase 3 missing
12 = Phase 1 and 2 missing
13 = Phase 1 and 3 missing
23 = Phase 2 and 3 missing
123 = All phases missing
230105-6Voltage Input
Inverted
-1…123•••••Reports on all three phases.
-1 = Test not run.
0 = Test passed.
1 = Phase 1 inverted
2 = Phase 2 inverted
3 = Phase 3 inverted
12 = Phase 1 and 2 inverted
13 = Phase 1 and 3 inverted
23 = Phase 2 and 3 inverted
123 = All phases inverted
68Publication 1408-UM001B-EN-P - May 2008
Wiring Diagnostics Results
Powermonitor 1000 Data Tables Appendix A
Element
No.
330107-8Current Input
Modbus
Address
Element NameUnitsRange
-1…123•••••Reports on all three phases.
Missing
Description
TR1
TR2
EM1
EM2
EM3
-1 = Test not run.
0 = Test passed.
1 = Phase 1 missing
2 = Phase 2 missing
3 = Phase 3 missing
12 = Phase 1 and 2 missing
13 = Phase 1 and 3 missing
23 = Phase 2 and 3 missing
123 = All phases missing
430109-10Current Input
Inverted
-1…123•••••Reports on all three phases.
-1 = Test not run.
0 = Test passed.
1 = Phase 1 inverted
2 = Phase 2 inverted
3 = Phase 3 inverted
12 = Phase 1 and 2 inverted
13 = Phase 1 and 3 inverted
23 = Phase 2 and 3 inverted
123 = All phases inverted
530111-12Voltage Rotation-1…132•••••Reports on all three phases. The
reported sequence represents
each phase. Example: 123 =
Phase 1 then phase 2 then phase
3
-1 = Test not run
4 = Invalid rotation
1…132 designating phase and
rotation.
630113-14Current Rotation-1…321•••••Reports on all three phases. The
reported sequence represents
each phase. Example: 123 =
Phase 1 then phase 2 then phase
3
-1 = Test not run
4 = Invalid rotation
1…321 designating phase and
rotation.
730115-16Voltage Phase 1
Angle
Degrees0…359.99•••Shows the present phase angle
of this channel. Should always be
0 degrees for voltage phase 1.
830117-18Voltage Phase 1
Magnitude
Volts0…9,999,999•••Shows the present magnitude of
this phase.
930119-20Voltage Phase 2
Angle
1030121-22Voltage Phase 2
Magnitude
1130123-24Voltage Phase 3
Angle
Publication 1408-UM001B-EN-P - May 200869
Degrees0…359.99•••Shows the present phase angle
of this channel.
Volts0…9,999,999•••Shows the present magnitude of
this phase.
Degrees0…359.99•••Shows the present phase angle
of this channel.
Appendix A Powermonitor 1000 Data Tables
Wiring Diagnostics Results
Element
No.
1230125-26Voltage Phase 3
1330127-28Current Phase 1
1430129-30Current Phase 1
1530131-32Current Phase 2
1630133-34Current Phase 2
1730135-36Current Phase 3
1830137-38Current Phase 3
1930139-40Degrees out of
Modbus
Address
Element NameUnitsRange
Volts0…9,999,999•••Shows the present magnitude of
Magnitude
Degrees0…359.99•••Shows the present phase angle
Angle
Amperes0…9,999,999•••Shows the present magnitude of
Magnitude
Degrees0…359.99•••Shows the present phase angle
Angle
Amperes0…9,999,999•••Shows the present magnitude of
Magnitude
Degrees0…359.99•••Shows the present phase angle
Angle
Amperes0…9,999,999•••Shows the present magnitude of
Magnitude
0…360•••••When Status = 5, how many
range
Description
TR1
TR2
EM1
EM2
EM3
this phase.
of this channel.
this phase.
of this channel.
this phase.
of this channel.
this phase.
degrees out of range.
2030141-42Reserved0•••••Reserved for future use
Volts, Amps, Frequency Results Parameters
CSP File No.F21
CIP Instance14
No. of Elements16
No. of Words32
Data TypeFloat
Data AccessRead
Volts, Amps, Frequency Results
Element
No.
Modbus
Address
Element NameRange
TR1
TR2
EM1
EM2
Description
EM3
030201-2L1 Current0.000…9,999,999•••Phase 1 scaled RMS Current
130203-4L2 Current0.000…9,999,999•••Phase 2 scaled RMS Current
230205-6L3 Current0.000…9,999,999•••Phase 3 scaled RMS Current
330207-8Average Current0.000…9,999,999•••Average RMS Current
430209-10L1-N Volts0.000…9,999,999•••Phase 1 scaled RMS Voltage
530211-12L2-N Volts0.000…9,999,999•••Phase 2 scaled RMS Voltage
70Publication 1408-UM001B-EN-P - May 2008
Volts, Amps, Frequency Results
Powermonitor 1000 Data Tables Appendix A
Element
No.
Modbus
Address
Element NameRange
TR1
TR2
EM1
EM2
Description
EM3
630213-14L3-N Volts0.000…9,999,999•••Phase 3 scaled RMS Voltage
730215-16Average L-N Volts0.000…9,999,999•••Averaged RMS Voltage
830217-18L1-L2 Volts0.000…9,999,999•••Line 1 to Line 2 Volts
930219-20L2-L3 Volts0.000…9,999,999•••Line 2 to Line 3 Volts
1030221-22L3-L1 Volts0.000…9,999,999•••Line 3 to Line 1 Volts
1130223-24Average L-L Volts0.000…9,999,999•••Average Line to Line Volts
1230225-26Frequency40.0 Hz…70.0 Hz•••Last frequency reading.
1330227-28Percent Current
Unbalance
1430229-30Percent Voltage
Unbalance
0.0…100.0•••Percent maximum deviation from
Ave. / Ave.
0.0…100.0•••Percent Maximum deviation from
Ave. / Ave.
1530231-32Metering Iteration0…9,999,999•••Increments by 1 for each new
metering calculation.
Power Results Parameters
Power Results
Element
No.
Modbus
Address
Element NameRange
030301-2L1 True Power
Factor
130303-4L2 True Power
Factor
230305-6L3 True Power
Factor
330307-83 Phase True
Power Factor
CSP File No.F22
CIP Instance15
No. of Elements17
No. of Words34
Data TypeFloat
Data AccessRead
630313-14L3 kWatts+/- 0.000…9,999,999••Line 3 kWatts
730315-16Total kWatts+/- 0.000…9,999,999••Total kWatts
830317-18L1 kVAR+/- 0.000…9,999,999••Line 1 kVAR
930319-20L2 kVAR+/- 0.000…9,999,999••Line 2 kVAR
1030321-22L3 kVAR+/- 0.000…9,999,999••Line 3 kVAR
1130323-24Total kVAR+/- 0.000…9,999,999••Total kVAR
1230325-26L1 kVA0.000…9,999,999••Line 1 kVA
1330327-28L2 kVA0.000…9,999,999••Line 2 kVA
1430329-30L3 kVA0.000…9,999,999••Line 3 kVA
1530331-32Total kVA0.000…9,999,999••Total kVA
1630333-34Metering Iteration0…9,999,999••Increments by 1 for each new
Modbus
Address
Element NameRange
IMPORTANT
TR1
TR2
EM1
EM2
Only total power values are returned in delta wiring modes.
Description
EM3
metering calculation.
Zeroes are returned for individual phase values.
Energy Results Parameters
CSP File No.F23
CIP Instance16
No. of Elements19
No. of Words38
Data TypeFloat
Data AccessRead
Energy Results
Element
No.
030401-2Status 1 Count xM0…9,999,999•••Status 1 Count times 1,000,000
130403-4Status 1 Count x10…999,999•••Status 1 count times 1
230405-6Status 2 Count xM0…9,999,999•••Status 2 Count times 1,000,000
330407-8Status 2 Count x10…999,999•••Status 2 count times 1
CSP File No.F24
CIP Instance17
No. of Elements9
No. of Words18
Data TypeFloat
Data AccessRead
Demand Results
Element
No.
Modbus
Address
Element NameRange
TR1
TR2
EM1
EM2
Description
EM3
030501-2kWatt Demand+/- 0.000…9,999,999••The average real power during the
last demand period.
130503-4kVAR Demand+/- 0.000…9,999,999••The average reactive power during
the last demand period.
230505-6kVA Demand 0.000…9,999,999••The average apparent power during
the last demand period.
Publication 1408-UM001B-EN-P - May 200873
Appendix A Powermonitor 1000 Data Tables
Demand Results
Element
No.
Modbus
Address
Element NameRange
TR1
TR2
EM1
EM2
Description
EM3
330507-8Demand PF-100.0…+100.0••The average demand for PF during
the last demand period.
430509-10Projected kWatt
Demand
530511-12Projected kVAR
Demand
630513-14Projected kVA
Demand
730515-16Elapsed Demand
Period Time
+/- 0.000…9,999,999••The projected total real power for
the current period.
+/- 0.000…9,999,999••The projected total reactive power
for the current period.
0.000…9,999,999••The projected total apparent power
for the current period.
0.00…99.99••The amount of time that has
elapsed during the current period.
830517-18Metering Iteration 0…9,999,999••Increments by 1 for each new
metering calculation.
Unit Status Log Results Parameters
CSP File No.N25
CIP Instance18
Applies toAll models
No. of Elements13
No. of Words13
Data TypeInteger
Data AccessRead
Unit Status Log Results
Element
No.
030601Status Record Internal
Modbus
Address
Element NameRangeDescription
1…50Used to verify record sequence when returning multiple
Identifier
records.
130602Timestamp Year of record -The year when the record was recorded.
230603Timestamp Month/Day-The month and day when the record was recorded.
330604Timestamp Hour/Minute-The hour and minute when the record was recorded.
430605Timestamp
-The seconds and hundredths when the record was recorded.
Seconds/Hundredths
530606Status Event Type0…512Indicates the type of status event that has occurred.
630607General Code0…4096Indicates general information about the status event.
730608Information Code0…256Indicates specific information about the status event.
74Publication 1408-UM001B-EN-P - May 2008
Unit Status Log Results
Powermonitor 1000 Data Tables Appendix A
Element
No.
Modbus
Address
Element NameRangeDescription
830609Reserved0Reserved for future use.
930610Reserved0Reserved for future use.
1030611Reserved0Reserved for future use.
1130612Reserved0Reserved for future use.
1230613Reserved0Reserved for future use.
Watchdog Timer32Watchdog Time Out1
Metering64Metering Status Failed1
Boot Code Checksum2
Application Code Checksum4
Calibration Data CRC8
No Calibration Data16
Wrong Application FRN32
Invalid Model Type64
WIN Mismatch128
Missing Upgrade Block256
SPI Interface Failed2
Real Time Clock not Set2
LCD Interface128LCD Interface Failure1
Serial Communications256Serial Communication Port Failed1
Ethernet Communications512Ethernet Communications Port Failed1
Factory Defaults Restored4
Energy Register Set8Wh Register1
Terminal Locked16
Terminal Unlocked32
Log Cleared or Set4Min/Max Log Cleared1
Energy Log Cleared2
LoadFactor Log Cleared4
TOU Log Cleared8
KYZ Forced8KYZ Forced On1
KYZ Forced Off2
Status Input Activated16Status Input 11
Status Input 22
All Status Input4
VARh Register2
VAh Register4
All Energy Registers Cleared8
Status Input 22
Status Input Deactivated32Status Input 11
Status Input 22
Energy Register Rollover64Wh Register1
VARh Register2
VAh Register4
Status Input 1 Register8
Status Input 2 Register16
Device Power Up128
Device Power Down256
Missed External Demand
512
Sync
Publication 1408-UM001B-EN-P - May 200877
Appendix A Powermonitor 1000 Data Tables
Energy Log Results
Energy Log Results Parameters
CSP File No.F26
CIP Instance19
No. of Elements21
No. of Words42
Data TypeFloat
Data AccessRead
Element
No.
030701-2Internal Record
Modbus
Address
Element NameRange
TR1
TR2
EM1
•••
EM2
Description
EM3
Identifier.
130703-4Timestamp Year of
record
230705-6Timestamp
-•••The date and time when the
record was recorded.
-•••
Month/Day
330707-8Timestamp
-•••
Hour/Minute
430709-10Timestamp
-•••
Seconds/
Hundredths
530711-12Status 1 Count xM 0…9,999,999•••Status 1 Count times
1,000,000
630713-14Status 1 Count x10…999,999•••Status 1 count times 1
730715-16Status 2 Count xM 0…9,999,999•••Status 2 Count times
1,000,000
830717-18Status 2 Count x10…999,999•••Status 2 count times 1
930719-20GWh Net+/- 0…9,999,999•••Net gigawatt hours
1030721-22kWatth Net+/- 0.000…999,999•••Net kilowatt hours
1130723-24GVARH Net+/- 0…9,999,999••Net gigaVAR hours
1230725-26kVARh Net+/- 0.000…999,999••Net kiloVAR hours
1330727-28GVAh Net0…9,999,999••Net gigaVA hours
1430729-30kVAh Net0.000…999,999••Net kiloVA hours
1530731-32kWatt Demand+/- 0.000…9,999,999••The average real power during
the last demand period.
1630733-34kVAR Demand+/- 0.000…9,999,999••The average reactive power
during the last demand period.
78Publication 1408-UM001B-EN-P - May 2008
Energy Log Results
Powermonitor 1000 Data Tables Appendix A
Element
No.
Modbus
Address
Element NameRange
TR1
TR2
EM1
EM2
Description
EM3
1730735-36kVA Demand0.000…9,999,999••The average apparent power
during the last demand period.
1830737-38Demand PF-100.0…+100.0••The average demand for PF
during the last demand period.
1930739-40Reserved0••Reserved for future use.
2030741-42Reserved0••Reserved for future use.
Write Error Status Results Parameters
CSP File No.N27
CIP Instance20
Applies toAll Models
No. of Elements3
No. of Words3
Data TypeInteger
Data AccessRead
Write Error Status Results
Element
No.
030801Table Number or
Modbus
Address
Element NameRangeDescription
All Write Enabled TablesIndicates the last table that was written.
Instance
130802Offending ElementLength of current table - 1If the most recent write was successful this
returns a (-1). If the write was unsuccessful this
is the first rejected element in the table write.
230803Terminal Lock On0…1If a write was made to a table that has elements
that are locked this value is 1.
Publication 1408-UM001B-EN-P - May 200879
Appendix A Powermonitor 1000 Data Tables
Unit Run Status Results
Unit Run Status Results Parameters
CSP File No.N28
CIP Instance21
Applies toAll models
No. of Elements25
No. of Words25
Data TypeInteger
Data AccessRead
Element
No.
Modbus
Address
Element NameRangeDescription
030901Bulletin Number1408Always returns 1408
130902Series Letter0…8Indicates the unit hardware series letter, for
example.
0 = A
1 = B
.
.
8 = H
230903Catalog Device Type0…4The catalog number type of this device.
0 = TR1
1 = TR2
2 = EM1
3 = EM2
4 = EM3
330904Communication Type0…1The communication type of this device
0 = Serial only
1 = both serial and Ethernet
430905Application FRN-The current firmware revision
530906Boot Code FRN-The current boot code revision
630907Default Device ID1…247A semi-unique number assigned to a device at the
time it is manufactured. Used for out of the box
communications over DF1 and Ethernet.
730908Accuracy Class0…3Indicates the revenue metering accuracy class of
the power monitor as it is shipped from the
factory.
0 = No Class Designation
1 = Class 1
2 = Class 0.5
3 = Class 0.2
80Publication 1408-UM001B-EN-P - May 2008
Unit Run Status Results
Powermonitor 1000 Data Tables Appendix A
Element
No.
Modbus
Address
Element NameRangeDescription
830909Overall Status0…163830 indicates normal operation. Each bit indicates a
different fault condition.
Bit 0 = Flash Memory
Bit 1 = SRAM
Bit 2 = NVRAM
Bit 3 = SPI Interface
Bit 4 = Real Time Clock
Bit 5 = Watchdog Timer
Bit 6 = Metering
Bit 7 = LCD Interface
Bit 8 = Serial Communications
Bit 9 = Ethernet Communications
Bit 10 = Error Log Full
930910Flash Memory0…5110 indicates normal operation. Status bits are
Bit 0 = Overall status
Bit 1 = Boot code checksum
Bit 2 = Application code checksum
Bit 3 = Calibration data CRC
Bit 4 = No calibration data
Bit 5 = Wrong application FRN
Bit 6 = Invalid model type
Bit 7 = WIN mismatch
Bit 8 = missing upgrade block
1030911SRAM0…10 indicates normal operation.
Bit 0 = Read/write test
1130912NVRAM0…10 indicates normal operation.
Bit 0 = Read/write test
1230913SPI Interface0…10 indicates normal operation.
Bit 0 = SPI device not responding
1330914Real Time Clock0…30 indicates normal operation.
Bit 0 = RTC status
Bit 1 = Time Zone Set Failed
1430915Watchdog Timer0…10 indicates normal operation.
Bit 0 = Watchdog time out
1530916Metering0…10 indicates normal operation.
Bit 0 = Metering status
1630917LCD Interface0…10 indicates normal operation.
Bit 0 = LCD Interface status
1730918Serial Communications0…10 indicates normal operation.
Bit 0 = Serial Interface status
Publication 1408-UM001B-EN-P - May 200881
Appendix A Powermonitor 1000 Data Tables
Unit Run Status Results
Element
No.
Modbus
Address
Element NameRangeDescription
1830919Ethernet Communications0…5110 indicates normal operation.
Bit 0 = Ethernet Communications status
Bit 1 = SNTP Server timeout status
Bit 2 = Duplicate IP Address status
Bit 3 = Invalid IP/Netmask address
Bit 4 = Invalid gateway address
Bit 5 = Invalid SNTP time server address
Bit 6 = Modbus stack run status
Bit 7 = Demand broadcast thread run status
Bit 8 = SNTP thread run status
1930920Input Over Range0…30 indicates normal operation.
Bit 0 = Voltage Input over range
Bit 1 = Current Input over range
2030921Phase Loss Detection0…70 Indicates normal running condition.
Bit 0 = Loss of phase A
Bit 1 = Loss of phase B
Bit 2 = Loss of phase C
2130922Configuration Locked0…1Reports 1 if configuration lock is applied.
2230923Password Accepted0…11 indicates the password is verified and active
2330924Error Recorded0Is incremented by 1 when an internal error
happens
2430925Troubleshooting Times
Remaining
0…30Remaining times for troubleshooting mode.
82Publication 1408-UM001B-EN-P - May 2008
Min/Max Log Results
Powermonitor 1000 Data Tables Appendix A
Min/Max Log Results Parameters
CSP File No.F29
CIP Instance22
No. of Elements11
No. of Words22
Data TypeFloat
Data AccessRead
Element
No.
031001-2Parameter Being
Modbus
Address
Element NameRange
1…35•••Indicates the Parameter Number (See
Returned
131003-4MIN Value+/-
0.000…9,999
,999
231005-6MAX Value+/-
0.000…9,999
,999
331007-8Timestamp Year of
MIN
431009-10Timestamp
Month/Day of MIN
531011-12Timestamp
Hour/Minute of MIN
631013-14Timestamp Seconds/
Hundredths of MIN
731015-16Timestamp Year of
MAX
831017-18Timestamp
Month/Day of MAX
931019-20Timestamp
Hour/Minute of MAX
1031021-22Timestamp Seconds/
Hundredths of MAX
Description
TR1
TR2
EM1
EM2
EM3
Min/Max Parameter List).
•••The minimum value recorded for
parameter being returned since the
last clear command.
•••The maximum value recorded for
parameter being returned since the
last clear command.
CSP File No.F30
CIP Instance23
No. of Elements14
No. of Words28
Data TypeFloat
Data AccessRead
Load Factor Log Results
Element
No.
Modbus
Address
Element NameRange
Description
TR1
TR2
EM1
EM2
EM3
031101-2Record Number1…13••The record number of this data.
131103-4End Date
-••The date that this record was stored.
yy/mm/dd
231105-6Elapsed Time0.000…
9,999,999
••Amount of time (in hours) that has
elapsed since the last clear of the peak
and average values. Updated at the end
of each demand interval.
331107-8Peak Demand
kWatts
+/-
0.000…9,999,
999
••The largest magnitude demand for
kwatts that occurred over all of the
demand intervals since the last clear
command or auto-clear day.
431109-10Average Demand
kWatts
+/-
0.000…9,999,
999
••A running average of demand for
kwatts from the end of each demand
period since the last clear command or
auto-clear day.
531111-12Load Factor
kWatts
0…100%••Average Demand kW / Peak Demand
kW. This is a demand management
metric that indicates how ‘spiky’ (or
‘level’) a load is over a period of time
(usually 1 month). A value approaching
100% indicates a constant load.
Publication 1408-UM001B-EN-P - May 200885
Appendix A Powermonitor 1000 Data Tables
Load Factor Log Results
Element
No.
Modbus
Address
Element NameRange
631113-14Peak Demand
kVAR
+/- 0.000…
9,999,999
TR1
TR2
EM1
EM2
••The largest magnitude demand for
Description
EM3
kVAR that occurred over all of the
demand intervals since the last clear
command or auto-clear day.
731115-16Average Demand
kVAR
+/- 0.000…
9,999,999
••A running average of demand for kVAR
from the end of each demand period
since the last clear command or
auto-clear day.
831117-18Load Factor kVAR0…100%••Average Demand kVAR / Peak Demand
kVAR. This is a demand management
metric that indicates how ‘spiky’ (or
‘level’) a load is over a period of time
(usually 1 month). A value approaching
100% indicates a constant load.
931119-20Peak Demand kVA0.000…
9,999,999
••The largest magnitude demand for kVA
that occurred over all of the demand
intervals since the last clear command
or auto-clear day.
1031121-22Average Demand
kVA
0.000…
9,999,999
••A running average of demand for kVA
from the end of each demand period
since the last clear command or
auto-clear day.
1131123-24Load Factor kVA0…100%••Average Demand kVA / Peak Demand
kVA. This is a demand management
metric that indicates how ‘spiky’ (or
‘level’) a load is over a period of time
(usually 1 month). A value approaching
100% indicates a constant load.
1231125-26Reserved0••Reserved for Future Use
1331127-28Reserved0••Reserved for Future Use
86Publication 1408-UM001B-EN-P - May 2008
Time of Use Log Results - Real Energy and Demand Parameters
CSP File No.F31
CIP Instance24
No. of Elements12
No. of Words24
Data TypeFloat
Data AccessRead
Time of Use Log Results - Real Energy and Demand
Powermonitor 1000 Data Tables Appendix A
Element
No.
Modbus
Address
Element NameRange
TR1
TR2
EM1
EM2
Description
EM3
031201-2Record Number1…13•••The record number of the log. Record 0 is
always the current record before being
logged.
131203-4Time Stamp Start
-•••The Date this record was started.
Date (yy/mm/dd)
231205-6Time Stamp End
-•••The Date this record was ended.
Date (yy/mm/dd)
331207-8Off Peak GWh
Net
431209-10Off Peak kWh
Net
531211-12Off Peak kW
Demand
631213-14Mid Peak GWh
Net
731215-16Mid Peak kWh
Net
831217-18Mid Peak kW
Demand
931219-20On Peak GWh
Net
+/- 0…
9,999,999
+/- 0.000…
999,999
+/- 0.000…
9,999,999
+/- 0…
9,999,999
+/- 0.000…
999,999
+/- 0.000…
9,999,999
+/- 0.000…
9,999,999
•••Net Off Peak giga watt hours
•••Net Off Peak kilo watt hours
•••Off Peak Demand for kilo watts
•••Net Mid Peak giga watt hours
•••Net Mid Peak kilowatt hours
•••Mid Peak Demand for kilo watts
•••Net On Peak giga watt hours
1031221-22On Peak kWh Net +/- 0…
•••Net On Peak kilo watt hours
999,999
1131223-24On Peak kW
Demand
Publication 1408-UM001B-EN-P - May 200887
+/- 0.000…
9,999,999
••On Peak Demand for kilo watts
Appendix A Powermonitor 1000 Data Tables
Time of Use Log Results - Reactive Energy and Demand Parameters
CSP File No.F32
CIP Instance25
No. of Elements12
No. of Words24
Data TypeFloat
Data AccessRead
Time of Use Log Results - Reactive Energy and Demand
Element
No.
Modbus
Address
Element Name Range
TR1
TR2
EM1
EM2
Description
EM3
031301-2Record Number1…13•••The record number of the log. Record 0 is
always the current record before being
logged.
131303-4Time Stamp
-•••The Date this record was started.
Start Date
(yy/mm/dd)
231305-6Time Stamp End
-•••The Date this record was ended.
Date
(yy/mm/dd)
331307-8Off Peak GVARH
Net
431309-10Off Peak kVARh
Net
531311-12Off Peak kVAR
Demand
631313-14Mid Peak
GVARH Net
731315-16Mid Peak kVARh
Net
831317-18Mid Peak kVAR
Demand
+/- 0…
9,999,999
+/- 0.000…
999,999
+/- 0.000…
9,999,999
+/- 0…
9,999,999
+/- 0.000…
999,999
+/- 0.000…
9,999,999
•••Net Off peak giga VAR hours
•••Net Off Peak kilo VAR hours
•••Off Peak Demand for kilo VAR
•••Net Mid Peak giga VAR hours
•••Net Mid Peak kilo VAR hours
•••Mid Peak Demand for kilo VAR
931319-20On Peak GVARH
Net
1031321-22On Peak kVARh
Net
1131323-24On Peak kVAR
Demand
88Publication 1408-UM001B-EN-P - May 2008
+/- 0.000…
9,999,999
+/- 0…
999,999
+/- 0.000…
9,999,999
•••Net On Peak giga VAR hours
•••Net On Peak kilo VAR hours
••On Peak Demand for kilo VAR
Time of Use Log Results - Apparent Energy and Demand Parameters
CSP File No.F33
CIP Instance26
No. of Elements12
No. of Words24
Data TypeFloat
Data AccessRead
Time of Use Log Results - Apparent Energy and Demand
Powermonitor 1000 Data Tables Appendix A
Element
No.
Modbus
Address
Element NameRange
TR1
TR2
EM1
EM2
Description
EM3
031401-2Record Number1…13•••The record number of the log. Record 0 is
always the current record before being
logged.
131403-4Time Stamp Start
-•••The Date this record was started.
Date (yy/mm/dd)
231405-6Time Stamp End
-•••The Date this record was ended.
Date (yy/mm/dd)
331407-8Off Peak GVAh
Net
431409-10Off Peak kVAh
Net
531411-12Off Peak kVA
Demand
631413-14Mid Peak GVAh
Net
731415-16Mid Peak kVAh
Net
831417-18Mid Peak kVA
Demand
931419-20On Peak GVAh
Net
+/- 0…
9,999,999
+/- 0.000…
999,999
+/- 0.000…
9,999,999
+/- 0…
9,999,999
+/- 0.000…
999,999
+/- 0.000…
9,999,999
+/- 0.000…
9,999,999
•••Net Off peak giga VA hours
•••Net Off Peak kilo VA hours
•••Off Peak Demand for kilo VA
•••Net Mid Peak giga VA hours
•••Net Mid Peak kilo VA hours
•••Mid Peak Demand for kilo VA
•••Net On Peak giga VA hours
1031421-22On Peak kVAh
Net
1131423-24On Peak kVA
Demand
Publication 1408-UM001B-EN-P - May 200889
+/- 0…
999,999
+/- 0.000…
9,999,999
•••Net On Peak kilo VA hours
••On Peak Demand for kilo VA
Appendix A Powermonitor 1000 Data Tables
Catalog Number and WIN
Catalog Number and WIN Parameters
CSP File No.N34
CIP Instance27
Applies toAll models
No. of Elements19
No. of Words19
Data TypeInteger
Data AccessRead
Element
No.
Modbus
Address
Element NameRangeDescription
031501Catalog # text char pair #1 0…32767Contains the product number (example: 1408-EM3A-485A, but with
131502Catalog # text char pair #2
231503Catalog # text char pair #3
331504Catalog # text char pair #4
out the dashes). A read of this table returns the catalog # as 4
integers: each integer contains a character pair. For each character
pair, character 1=integer/256 and character 2 = remainder of
integer/256.
431505Catalog # text char pair #4
531506Catalog # text char pair #4
631507Reserved0Reserved for future use.
731508Hardware Series0…25Indicates the product series letter.
For example, 0=A, 1=B,
831509WIN # text char pair #10…32767Contains the product WIN(Warranty Identification Number). This is
931510WIN # text char pair #2
1031511WIN# text char pair #3
the same alpha-numeric string that can be found on the master
module label (example: 21AW0AT5HO). 5 integers each contains two
characters as displayed by the Catalog parameter method.
1131512WIN# text char pair #4
1231513WIN# text char pair #5
1331514Reserved0Reserved for future use.
1431515Reserved0Reserved for future use.
1531516Original Model 0
…10This number represents the catalog number type.
0 = TR1
1 = TR2
2 = EM1
3 = EM2
4 = EM3
5 through 10 = Reserved
90Publication 1408-UM001B-EN-P - May 2008
Catalog Number and WIN
Powermonitor 1000 Data Tables Appendix A
Element
No.
Modbus
Address
Element NameRangeDescription
1631517Current Model0…10The current model of the product. This can be the same as the
original model (if no upgrades have been performed).
1731518Reserved0Reserved for future use.
1831519Reserved0Reserved for future use.
Single Element Password Write Parameters
CSP File No.N35
CIP Instance28
Applies toAll models
No. of Elements1
No. of Words1
Data TypeInteger
Data AccessWrite
Single Element Password Write
Element
No.
Modbus
Address
Element
Name
RangeDescription
040901Password0…9999A write of this table allows any configuration parameter to be written as a single
element or poke. The password stays active for 30 minutes and resets to another 30
minutes when a single element is configured.
Publication 1408-UM001B-EN-P - May 200891
Appendix A Powermonitor 1000 Data Tables
User Configured Table Setup
User Configurable Table Setup Parameters
CSP File No.N36
CIP Instance29
Applies toEM3 only
No. of Elements17
No. of Words17
Data TypeInteger
Data AccessRead/Write
Element
No.
Modbus
Address
Element NameDefault ValueRangeDescription
041001Password00…9999Required for configuration,
returns -1.
141002Selection for Parameter #129 (L1 Current)0…110
241003Selection for Parameter #230 (L2 Current)
341004Selection for Parameter #331 (L3 Current)
441005Selection for Parameter #437 (L1-L2 Voltage)
541006Selection for Parameter #538 (L2-L3 Voltage)
641007Selection for Parameter #639 (L3-L1 Voltage)
741008Selection for Parameter #741 (Frequency)
841009Selection for Parameter #852 (Total Real Power)
941010Selection for Parameter #956 (Total Reactive Power)
1041011Selection for Parameter #1060 (Total Apparent Power)
1141012Selection for Parameter #1148 (3 Phase True Power Factor)
1241013Selection for Parameter #1270 (Real Energy Net (kWh))
1341014Selection for Parameter #1362 (Status 1 Count x1)
1441015Selection for Parameter #1464 (Status 2 Count x1)
1541016Selection for Parameter #1579 (Real Power Demand)
1641017Selection for Parameter #168 (Status Input States)
92Publication 1408-UM001B-EN-P - May 2008
Parameters for Configurable Table
Parameter No. Parameter NameDescription
0NoneNo Parameter.
Powermonitor 1000 Data Tables Appendix A
1Date: YearRefer to Date and Time Configuration
2Date: Month
3Date: Day
4Time: Hour
5Time: Minute
6Time: Seconds
7Time: Hundredths
8Status Input StatesRefer to Discrete Results
table.
30L2 Current
31L3 Current
32Average Current
33L1-N Volts
Publication 1408-UM001B-EN-P - May 200893
Appendix A Powermonitor 1000 Data Tables
Parameters for Configurable Table
Parameter No. Parameter NameDescription
34L2-N VoltsRefer to Volts, Amps, Frequency Results table.
35L3-N Volts
36Average L-N Volts
37L1-L2 Volts
38L2-L3 Volts
39L3-L1 Volts
40Average L-L Volts
41Frequency
42Percent Current Unbalance
43Percent Voltage Unbalance
44Metering Iteration
45L1 True Power FactorRefer to Power Results
table.
46L2 True Power Factor
47L3 True Power Factor
483 Phase True Power Factor
49L1 kWatts
50L2 kWatts
51L3 kWatts
52Total kWatts
53L1 kVAR
54L2 kVAR
55L3 kVAR
56Total kVAR
57L1 kVA
58L2 kVA
59L3 kVA
60Total kVA
61Status 1 Count xMRefer to Energy Results
62Status 1 Count x1
63Status 2 Count xM
64Status 2 Count x1
65GWh Fwd
66kWatth Fwd
table.
67GWh Rev.
68kWatth Rev.
69GWh Net
94Publication 1408-UM001B-EN-P - May 2008
Parameters for Configurable Table
Parameter No. Parameter NameDescription
70kWatth NetRefer to Energy Results table.
71GVARH Fwd
72kVARh Fwd
73GVARH Rev.
74kVARh Rev.
75GVARH Net
76kVARh Net
77GVAh Net
78kVAh
79kWatt DemandRefer to Demand Results
table.
80kVAR Demand
81kVA Demand
82Demand PF
Powermonitor 1000 Data Tables Appendix A
83Projected kWatt Demand
84Projected kVAR Demand
85Projected kVA Demand
86Elapsed Demand Period Time
87Bulletin NumberRefer to Unit Run Status Results
88Series Letter
89Catalog Device Type
90Communication Type
91Application FRN
92Boot Code FRN
93Default Device ID
94Accuracy Class
95Overall Status
96Flash Memory
97SRAM
98NVRAM
99SPI Interface
100Real Time Clock
101Watchdog Timer
102Metering
106Input Over RangeRefer to Unit Run Status Results table.
107Phase Loss Detection
108Terminal Locked
109Password Accepted
110Error Recorded
96Publication 1408-UM001B-EN-P - May 2008
Index
A
additional resources 7
advanced configuration
analog input configuration
47
45, 46, 92
B
before you begin 7
C
catalog number and WIN 90
command table
communications command summary
61
15
15
DH485
Modbus RTU serial
optional EtherNet/IP
optional Modbus/TCP Ethernet
serial DF1 full-duplex slave
serial DF1 half-duplex slave
communications overview
16
15
16
15
15
10
ethernet
serial
controller interface table
11
10
66
D
data and time configuration 57
data table
access
13
addressing
data format
data tables
advanced configuration
analog input configuration
catalog number and WIN
command table
controller interface table
data and time configuration
demand results
discrete results
energy log results
energy results
ethernet configuration
load factor log results
log configuration
log request table
min/max log results
min/max parameter list
power results
serial RS-485 configuration
13
14
43
47
45, 46, 92
90
61
66
577367
78
72
52
855864
83
84
71
51
single element password write
time of use log results apparent energy
and demand
time of use log results reactive energy
and demand
time of use log results real energy and
demand
unit run status results
unit status log results
volts, amps, frequency results
wiring diagnostics results
write error status results
demand results
discrete results
73
67
89
88
87
80
74
68
79
E
energy log results 78
energy results
ethernet communications
EtherNet/IP protocol
Modbus TCP Protocol
ethernet configuration
explicit messaging
read write single or multiple elements
RSLogix5 message setup PLC5 or SLC
safety 9
SCADA applications
serial communications
serial RS-485 port configuration
single element password write
33
10
51
91
35
T
time of use log results apparent energy
and demand
time of use log results reactive energy
and demand
time of use log results real energy and
demand
time zone information
89
88
87
54
U
unit run status results 80
unit status log results
using communications
74
10
V
volts, amps, frequency results 70
W
wiring diagnostics results 68
write error status results
79
98Publication 1408-UM001B-EN-P - May 2008
Rockwell Automation
Support
Rockwell Automation provides technical information on the Web to assist
you in using its products. At http://support.rockwellautomation.com
find technical manuals, a knowledge base of FAQs, technical and application
notes, sample code and links to software service packs, and a MySupport
feature that you can customize to make the best use of these tools.
For an additional level of technical phone support for installation,
configuration, and troubleshooting, we offer TechConnect support programs.
For more information, contact your local distributor or Rockwell Automation
representative, or visit http://support.rockwellautomation.com
, you can
.
Installation Assistance
If you experience a problem within the first 24 hours of installation, please
review the information that's contained in this manual. You can also contact a
special Customer Support number for initial help in getting your product up
and running.
United States1.440.646.3434
Monday – Friday, 8am – 5pm EST
Outside United
States
Please contact your local Rockwell Automation representative for any
technical support issues.
New Product Satisfaction Return
Rockwell Automation tests all of its products to ensure that they are fully
operational when shipped from the manufacturing facility. However, if your
product is not functioning and needs to be returned, follow these
procedures.
United StatesContact your distributor. You must provide a Customer Support case
number (call the phone number above to obtain one) to your distributor
in order to complete the return process.
Outside United
States
Please contact your local Rockwell Automation representative for the
return procedure.
Publication 1408-UM001B-EN-P - May 2008 100PN 40055-250-02(1)