Rockwell Automation 1408-EMxx User Manual

User Manual
(Catalog Numbers
1408-TR1A-485, 1408-TR2A-485, 1408­EM1A-485, 1408-EM2A-485, 1408­EM3A-485, 1408-TR1A-ENT, 1408­TR2A-ENT, 1408-EM1A-ENT, 1408­EM2A-ENT, 1408-EM3A-ENT
)

Important User Information

Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://literature.rockwellautomation.com between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
) describes some important differences
WARNING
Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
IMPORTANT
ATTENTION
Identifies information that is critical for successful application and understanding of the product.
Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence
SHOCK HAZARD
Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.
BURN HAZARD
Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.
Allen-Bradley, Rockwell Automation, Powermonitor, ControlLogix, PLC5, SLC, RSLinx and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.

Summary of Changes

Introduction

This release of this document contains new and updated information. The information below summarizes the changes to this manual since the last publication.
Revision bars in the margin identify updated information. Changes for this version of the document include:
Change Page
Added DH485 to the serial communication protocol table.
Added section with information about DH485.
Added that the Ethernet communication port supports 10 or 100 Mbps data rate, half-duplex, or full-duplex.
Added DH485 to the communication command summary.
Added information about explicit messaging instructions apply to Ethernet communication and serial communication.
Added instructions to configure RSLinx software driver configuration for DH485.
Added information for using the DH485 driver.
10
11
11
15
17
34
37
Added information for OPC tag browsing. 39 Added information about a user configured
data table. Added User Configured Table Results
Parameters table. Added User Configured Table Results table. 45 Added element 5 to Analog Input
Configuration table Updated elements 5 and 7 to Advanced
Configuration table. Updated Serial RS-485 Port Configuration
table. Updated Command table. 61 Added element 10 to the Log Request table. 64 Updated Wiring Diagnostics Results table. 68 Updated Unit Run Status Results table. 80
3Publication 1408-UM001B-EN-P - May 2008 3
40
45
46
48
51
Summary of Changes
Change Page
Added User Configurable Table Setup
92
Parameters table. Added User Configured Table Setup table. 92 Added Parameters for Configurable table. 93
4 Publication 1408-UM001B-EN-P - May 2008
Powermonitor 1000 Overview
Powermonitor 1000 Memory Organization
Communications Command Summary

Table of Contents

Preface
Before You Begin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Who Should Use This Manual . . . . . . . . . . . . . . . . . . . . . . . . 7
Additional Resources. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Chapter 1
Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Communication Overview . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Chapter 2
Data Table Addressing . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Data Table Access. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Data Table Data Format . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Chapter 3
Serial DF1 Full-duplex, DF1 Half-duplex Slave, DH485 . . . . 15
Optional EtherNet/IP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Modbus RTU Serial and Optional Modbus/TCP Ethernet . . . 16
Explicit Messaging
SCADA Applications
Powermonitor 1000 Data Tables
Chapter 4
Explicit Message Setup – Examples . . . . . . . . . . . . . . . . . . . 17
Reading Logs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Chapter 5
RSLinx Drivers Configuration . . . . . . . . . . . . . . . . . . . . . . . . 33
RSLinx Software OPC Server Setup. . . . . . . . . . . . . . . . . . . . 35
Appendix A
Summary of Data Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Data Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Index
5Publication 1408-UM001B-EN-P - May 2008 5
Table of Contents
6 Publication 1408-UM001B-EN-P - May 2008

Preface

Before You Begin

Who Should Use This Manual

Additional Resources

Use this document as a guide to set up communications with the 1408 Powermonitor 1000 unit using other applications and controllers. This document is intended for advanced users. You should already be familiar with data communications and programmable controller messaging.
For further information on installing, wiring, connecting, applying power, and configuring your 1408 power monitor, please refer to the Powermonitor 1000 Installation Instructions.
You should have a basic understanding of electrical circuitry and familiarity with relay logic. If you do not, obtain the proper training before using this product.
This table lists documents that contain additional information concerning Rockwell Automation Power and Energy Management Solutions products.
For additional information, refer to these publications, that you can download from http://literature.rockwellautomation.com
.
Resource Description
Powermonitor 1000 Unit Installation Instructions, publication 1408-IN001
If you would like a manual, you can:
download a free electronic version from the Internet at
http://literature.rockwellautomation.com
purchase a printed manual by contacting your local
Allen-Bradley distributor or Rockwell Automation sales office.
This publication gives product description and functionality.
7Publication 1408-UM001B-EN-P - May 2008 7
Preface Preface
8 Publication 1408-UM001B-EN-P - May 2008
Powermonitor 1000 Overview
Chapter
1

Safety

Follow these advisories when using this product.
ATTENTION
ATTENTION
Only qualified personnel, following accepted safety procedures, should install, wire, and service the power monitor and its associated components. Before beginning any work, disconnect all sources of power and verify that they are de-energized and locked out. Failure to follow these instructions may result in personal injury or death, property damage or economic loss.
Never open a current transformer (CT) secondary circuit with primary current applied. Wiring between the CT’s and the power monitor should include a shorting terminal block in the CT secondary circuit. Shorting the secondary with primary current present allows other connections to be removed if needed. An open CT secondary with primary current applied produces a hazardous voltage, which can lead to personal injury, death, property damage or economic loss.
IMPORTANT

Introduction

9Publication 1408-UM001B-EN-P - May 2008 9
This manual covers advanced techniques for configuring setup parameters and retrieving data from the power monitor using its available communications. Typical applications include SCADA applications using RSLinx Classic or OPC software to gather data from the power monitor and applications using explicit messaging from PLC controllers to retrieve data for control and information.
Please refer to the Powermonitor 1000 Installation Instructions, publication 1408-IN001
Product description and functionality
Basic meter and communications setup using the LCD display,
HyperTerminal or the web interface
The power monitor is neither designed for, nor intended for, use as a circuit protective device. Do not use this equipment in place of a motor overload relay or circuit protective relay.
for the following information:
Chapter 1 Powermonitor 1000 Overview
What Can I Do Using Communication Networks?
When you use communication networks with the power monitor you can do the following things.
Configure analog input parameters such as PT/CT ratios
Configure communications parameters such as IP address
Read real-time power and energy data
Read energy logs

Communication Overview

All Powermonitor 1000 units come standard with an RS-485 serial communication port. Models with catalog numbers ending in -ENT are equipped with an Ethernet 10BaseT communication port. This section covers serial and Ethernet communication, the available protocols, and what protocols to use for your application.
Serial Communication
The RS-485 serial communication port allows serial communication to your power monitor. This port can be configured to communicate using the protocols listed the Serial Communication Protocols table.
Serial Communication Protocols
Protocol Applications
DF1 Half-duplex Slave The DF1 Half-duplex Slave protocol may be used for point-to-point or multi-drop
communication using a DF1 Polling Master driver for RSLinx software, or when using explicit messages from Rockwell Automation controllers communicating via DF1 Half-duplex Master.
DF1 Full-duplex The DF1 Full-duplex protocol may be used only for point-to-point communication using a
RS-232 DF1 driver for RSLinx software, or when using explicit messages from Rockwell Automation controllers communicating via DF1 Full-duplex.
Modbus RTU Slave The Modbus RTU Slave protocol may be used for point-to-point or multi-drop
communication with a client using the Modbus RTU Master protocol for PLC controller communication.
Auto-sense With auto-sense selected, the RS-485 port switches among the available serial
protocols based on the format of the packets the port receives.
DH485 The DH485 protocol may be used for point-to-point or multi-drop communication using a
1747-PIC/AIC+ driver for RSLinx software, or when using explicit messages from Allen-Bradley controllers or HMI (PanelView) terminals communicating via DH485.
TIP
When configuring serial communication, users should verify that all serial devices wishing to communicate to the power monitor have the same communication rate, and the same data format.
10 Publication 1408-UM001B-EN-P - May 2008
Powermonitor 1000 Overview Chapter 1
DH485 Protocol
DH485 is a token-passing protocol that allows messaging by up to 32 nodes on a serial network. The master is the node that owns the token; only the master may transmit messages. When a node has completed transmitting messages, it passes the token to the next node.
The power monitor does not initiate DH485 data messages. When requested, it transmits reply messages to the initiator when it gets the token, and then passes the token to its successor.
TIP
The DH485 protocol uses the same data table addressing as DF1 protocols. Please refer to the CSP file number column of Powermonitor 1000 data tables.
The following configuration factors have a significant effect on network performance and should be considered when you plan a DH485 network.
Number of Nodes - unnecessary nodes will slow the data
transfer rate. The maximum number of nodes on the network is
32. Fewer nodes are better.
Node Addresses - best to start node addresses at 0 and assign in
sequential order. Controllers may not be node 0. Initiators such as personal computers should be assigned the lowest numbered addresses.
Communication Rate - Higher is better. All devices must be at
the same communication rate.
Maximum Node Address - should be set as low as possible to
reduce the time it takes to initialize the network.
Powermonitor 1000 units only support DH485 Local Link messages and do not support the Send and Receive Data (SRD) messages for DH485 non-token passing slave devices.
Ethernet Network Communication
The Ethernet network communication port allows communication with your power monitor using a local-area-network (LAN). The Ethernet port may also be used to view the power monitor’s internal webpage. This Ethernet port uses a static IP address only, and can simultaneously communicate using the protocols listed below. The Ethernet communication port supports 10 or 100 Mbps data rate, half-duplex, or full-duplex.
Publication 1408-UM001B-EN-P - May 2008 11
Chapter 1 Powermonitor 1000 Overview
EtherNet/IP Protocol
The power monitor supports the EtherNet/IP protocol for communicating via Ethernet or EtherNet/IP drivers in RSLinx Classic software, or when using explicit messages from Rockwell Automation controllers communicating via Ethernet or EtherNet/IP network.
Modbus TCP Protocol
Modbus TCP protocol is also supported for communicating via Modbus TCP for communication.
TIP
When configuring Ethernet communication, you should verify that IP addresses do not conflict with the existing infrastructure, and that subnet masks and gateways are properly set.
12 Publication 1408-UM001B-EN-P - May 2008
Chapter
2
Powermonitor 1000 Memory Organization
The power monitor memory is organized similarly to that of a PLC-5 or SLC 500 programmable controller. Data tables organize individual data items of similar function. For example, the analog input setup parameters are grouped in one data table, and voltage, current, and frequency metering results in another.

Data Table Addressing

Appendix
Data tables may be addressed in several ways.
A provides a detailed list of the power monitor data tables.
CSP addressing. This is also known as PLC-5 style or PCCC
addressing. Addresses are written in the form Axx:yy where A is a letter describing the function of the data table, xx is the table number, and yy is the element within, or offset into, the table. For example, F23:0 is the CSP address of the first element in the energy metering results table.
CIP addressing. This is also known as DeviceNet addressing.
Addresses are of the form Object:Instance:Attribute. CIP addressing allows addressing only a single element of an entire data table. In CIP addressing, the energy metering results table object 4 (Assembly object), instance 16 (energy results table) and attribute 3 (data).
Modbus RTU addressing. The data tables may be addressed by a
Modbus RTU master using Modbus register addressing. The Modbus protocol supports four types of data: Discrete Input, Coil, Input Register, and Holding Register. The power monitor supports Input Registers (read-only) with addresses in the 30000 range and Holding Registers (read-write or write only) with addresses in the 40000 range. Using the same example as above, the energy results table has a Modbus address range of 30401…30438

Data Table Access

13Publication 1408-UM001B-EN-P - May 2008 13
Controllers and client applications may read or write single element, multiple elements or complete tables as permitted by the addressing selected.
Each data table’s read/write access is listed in Appendix
A.
Chapter 2 Powermonitor 1000 Memory Organization
The power monitor requires a valid password before it accepts a write. There are two ways a password may be written.
An entire table including a valid password may be written.
A valid password may be written to the Single element password
write table which then enables single element writes until 30 minutes without a single element write elapses.

Data Table Data Format

The power monitor stores data in two basic formats.
Integer, in which the 16-bit word may be represented by a
signed integer value or a bit field
Floating-point, in the 32-bit IEEE 754 format
Modbus input registers and holding registers are 16 bits long. Floating point values in the data tables are represented as big-Endian two-register arrays in IEEE-754 floating point format. The Modbus client application must be able to reassemble the two-word array into a valid floating-point value.
An example Modbus address for a floating-point value is 40101-2. Register 40101 holds the most significant bytes of the number and 40102 holds the lowest significant bytes.
14 Publication 1408-UM001B-EN-P - May 2008
Chapter
Communications Command Summary
3

Serial DF1 Full-duplex, DF1 Half-duplex Slave, DH485

Optional EtherNet/IP

PCCC Protected Logical Read w/ 2 Address Fields (CMD = 0x0F,
FUNC = 0xA1)
PCCC Protected Logical Write w/ 2 Address Fields (CMD = 0x0F,
FUNC = 0xA9)
PCCC Protected Logical Read w/ 3 Address Fields (CMD = 0x0F,
FUNC = 0xA2)
PCCC Protected Logical Write w/ 3 Address Fields (CMD = 0x0F,
FUNC = 0xAA)
PCCC Protected Logical Write w/ 4 Address Fields (CMD = 0x0F,
FUNC = 0xAB)
PCCC Status Diagnostics (CMD = 0x06, FUNC = 0x03)
CIP Generic Assembly Object (Class 04), Get & Set Attribute
Single for Attribute 3 (data)
CIP Generic Assembly Object (Class 04), Get Attribute Single for
Attribute 4 (size)
PCCC PLC5 Word Range Write Function (CMD = 0x0F, FUNC =
0x00)
PCCC PLC5 Word Range Read Function (CMD = 0x0F, FUNC =
0x01)
PCCC PLC5 Typed Write Function (CMD = 0x0F, FUNC = 0x67)
PCCC PLC5 Typed Read Function (CMD = 0x0F, FUNC = 0x68)
PCCC Protected Logical Read Function w/2 Address Fields (CMD
= 0x0F, FUNC = 0xA1)
PCCC Protected Logical Write Function w/2 Address Fields
(CMD = 0x0F, FUNC = 0xA9)
PCCC Protected Logical Read Function w/3 Address Fields (CMD
= 0x0F, FUNC = 0xA2)
PCCC Protected Logical Write Function w/3 Address Fields
(CMD = 0x0F, FUNC = 0xAA)
PCCC Status Diagnostics (CMD = 0x06, FUNC = 0x03)
15Publication 1408-UM001B-EN-P - May 2008 15
Chapter 3 Communications Command Summary

Modbus RTU Serial and Optional Modbus/TCP Ethernet

The power monitor does not initiate Modbus commands but responds to commands sent by the Modbus master. These Modbus function codes are supported.
03 Read Holding Registers
04 Read Input Registers
16 Write Multiple Holding Registers
08 Diagnostics
00 Echo Command Data02 Return Diagnostic Counters10 Clear Diagnostic Counters
06 Write Single Holding Register
16 Publication 1408-UM001B-EN-P - May 2008
Chapter
4
Explicit Messaging
This section discusses data retrieval and parameter configuration using explicit messaging from Rockwell Automation controllers. Explicit messaging allows you to read and write from a controller to specific data tables within the power monitor. With explicit messages, users can read real-time power and energy values, configure analog input parameters, configure communications parameters, and also read energy logs.
In general, these instructions apply to Ethernet network communication (Ethernet/IP protocol) and Serial communication (DF1 half-duplex or full-duplex or DH485 protocols), provided that the protocol is supported by the controller. If using serial communication, the controller serial port must be correctly configured for protocol, communication rate, or parity. Refer to the appropriate controller user documentation for further details.
Explicit Message Setup – Examples
Please refer to Appendix descriptions of the power monitor data tables and their data access privileges, and data types.
The power monitor allows PLC-5 Typed, SLC Typed, and CIP Generic message requests.
This section gives examples on how to set-up explicit messaging.
A, Powermonitor 1000 Data Tables for
Read/Write Single or Multiple Elements
You can perform single or multiple element reads and writes to the power monitor. Below is a table documenting the message type to use for specific read/write type and communication scenarios.
17Publication 1408-UM001B-EN-P - May 2008 17
Chapter 4 Explicit Messaging
IMPORTANT
When performing a write to the power monitor, you must write the password value to the password element of that specific data table that you are writing to. This must be done in the same message; therefore you must perform a multiple element write. If you wish to perform only a single element write, you must write the password value to the Single Element Password Write table. This allows you to perform writes to any write access data table for the next 30 minutes.
Message Type
Read/Write Type Communication Read/Write Message Type
Single Element Serial SLC Typed Single Element Ethernet PLC5 Typed or SLC Typed Multiple Element Serial SLC Typed Multiple Element Ethernet
(1)
The CIP Generic message type is only available for RSLogix5000 software. All elements in the data table are written to or read back.
PLC5 Typed or SLC Typed or CIP Generic
(1)
RSLogix5000 – Message Configuration using PLC5 or SLC Typed Read/Write
This is an example of how to set up a message instruction to read or write single or multiple elements from a power monitor using PLC5 or SLC Typed messages. This setup applies to ControlLogix and CompactLogix programmable logic controllers.
18 Publication 1408-UM001B-EN-P - May 2008
Explicit Messaging Chapter 4
Follow these steps to configure a message.
1. Choose the appropriate parameters in the Message
Configuration window.
Parameter Choice
Message type Select the appropriate message type according to Message Type
page 18
.
Source Element Read: Refer to Appendix
address of the specific data table address you’re reading. If you are performing a multiple element read, this should be the first element in the array of elements you’re reading back.
Write: This is the controller tag in which to store the data being written to the power monitor.
Number of Elements
Destination Element
This is the number of elements being read or written to. If you are performing a single element read or write, then this value should be 1. If you are performing a multiple element read or write, then this should be the number of elements after the source element that you wish to read or write.
Read: This is the controller tag in which to store the data being read. Write: Refer to Appendix
address of the specific data table address you’re writing to.
A – Powermonitor 1000 Data Tables for the
A – Powermonitor 1000 Data Tables for the
on
2. Click the Communication tab to select the communication type,
either Ethernet or Serial.
Publication 1408-UM001B-EN-P - May 2008 19
Chapter 4 Explicit Messaging
3. Choose the communication type and then set the path and
communication method.
Communication Type Path Method
Ethernet <Backplane (always 1), Slot of Ethernet
Module, Port (always 2 for Ethernet), power monitor IP Address>
Serial Communications <Port, Power Monitor Serial Node Address> CIP
CIP
4. Click OK to complete the message setup.
RSLogix5000 Software – Message Setup Using CIP Generic
The following example shows how to set up your message instruction to read or write to a data table in the power monitor using a CIP Generic message type for RSLogix5000 software. This setup applies to ControlLogix and CompactLogix programmable logic controllers. The CIP Generic message type does not support single element reads or writes. In this example, we are reading the Voltage, Amps, and Frequency data table from the power monitor.
20 Publication 1408-UM001B-EN-P - May 2008
Explicit Messaging Chapter 4
Follow these steps to configure a message.
1. Choose the appropriate parameters in the Message
Configuration window.
Parameter Choice
Message Type Choose message type CIP Generic. Service Type Read: Select service type Get Attribute Single
Write: Select service type Set Attribute Single
Instance Refer to Appendix
requesting to read. In this example, the power monitor’s Voltage, Amp,
and Frequency data table is instance 14. Class 4 Attribute 3 Destination Get Attribute Single - This is the controller tag in which to store the
data being read. Source Element Set Attribute Single - Refer to Appendix
specific data table address you’re writing to. Source Length Set Attribute Single - This is the number of elements of the source
element, to be written to the power monitor.
A for the CIP Instance of the data table you are
A for the address of the
Publication 1408-UM001B-EN-P - May 2008 21
Chapter 4 Explicit Messaging
2. Click the Communication tab and enter the path and method.
Path Method
<Backplane (always 1), Slot of Ethernet Module, Port (always 2 for Ethernet), Power Monitor IP Address>
CIP
3. Click OK to complete message setup.
22 Publication 1408-UM001B-EN-P - May 2008
Explicit Messaging Chapter 4
RSLogix500 Software - Message Setup Using PLC5 or SLC Typed Read/Write
The following is an example of how to set up your message instruction to read or write single or multiple elements to a power monitor using Peer-To-Peer PLC5 or CPU 500 Typed messages in RSLogix500 software. This setup applies to SLC and MicroLogix programmable logic controllers.
Follow these steps to configure a message.
1. Set your MSG instruction.
Parameter Choice
Read/Write Select Read or Write Target Device Select the appropriate message type according to Message Type
page 18
. Local/Remote Select Local Control Block Select an available Integer word. In this example, we used N7:0.
2. Click Setup Screen at the bottom of the message instruction.
The message configuration window for either Ethernet network or Serial communication appears.
on
Publication 1408-UM001B-EN-P - May 2008 23
Chapter 4 Explicit Messaging
3. Choose the appropriate parameters in the Message
Configuration window.
Ethernet Network Communication
Serial Communication
Communication
Parameter Choice
Ty pe
Ethernet Data Table Address (This
Controller)
Size in Elements This is the number of elements being
Channel 1 Data Table Address
(Target Device)
MultiHop Yes
Read: This is the controller tag in which to store the data being read
Write: This is the controller tag that stores the value to be written to the power monitor.
read or written to. If you are performing a single element read or write, then this value should be 1. If you are performing a multiple element read or write, then this should be the number of elements after the source element that you wish to read or write.
Refer to Appendix
A for the address of
the specific data value you’re reading or writing to.
24 Publication 1408-UM001B-EN-P - May 2008
Explicit Messaging Chapter 4
Communication Ty pe
Serial Data Table Address (This
Parameter Choice
Controller)
Size in Elements This is the number of elements being
Channel 0 Data Table Address (Target
Device)
Local Node This is the serial node address of your
Read: This is the controller tag in which to store the data being read
Write: This is the controller tag that stores the value to be written to the power monitor.
read or written to. If you are performing a single element read or write, then this value should be 1. If you are performing a multiple element read or write, then this should be the number of elements after the source element that you wish to read or write.
Refer to Appendix the specific data value you’re reading or writing to.
power monitor.
A for the address of
Message setup is complete for Serial communication.
4. Click the MultiHop tab if configuring Ethernet communications.
5. Enter the IP Address of the power monitor in the To Address
box.
Message setup is complete.
Publication 1408-UM001B-EN-P - May 2008 25
Chapter 4 Explicit Messaging
RSLogix5 Software - Message Setup using PLC5 or SLC Typed Read/Write
The following is an example of how to set up your message instruction to read or write single or multiple elements to a power monitor using PLC5 or SLC Typed messages in RSLogix5. This setup applies to PLC5 programmable logic controllers.
Follow these steps to configure a message.
1. Choose an available message data block in your message
instruction.
In this example, we used MG9:0.
2. Click Setup Screen at the bottom of the message instruction.
The message configuration window for either Ethernet network or Serial communcation appears.
26 Publication 1408-UM001B-EN-P - May 2008
Explicit Messaging Chapter 4
3. Choose the appropriate parameters in the Message
Configuration window.
Ethernet Network Communication
Serial Communication
Communication Type Parameter Choice
Ethernet Communication Command Select the appropriate message type according to
Message Type
on page 18.
Data Table Address (This Controller) Read: This is the controller tag in which to store the data
being read. Write: This is the controller tag that stores the value to be
written to the power monitor.
Size in Elements This is the number of elements being read or written to. If
you are performing a single element read or write, then this value should be 1. If you are performing a multiple element read or write, then this should be the number of elements after the source element that you wish to read or
write. Port Number 2 Data Table Address (Target Device) Refer to Appendix
A for the address of the specific data
value you’re reading or writing to. MultiHop Yes
Publication 1408-UM001B-EN-P - May 2008 27
Chapter 4 Explicit Messaging
Communication Type Parameter Choice
Serial Communication Command Select the appropriate message type according to
Message Type
Data Table Address Read: This is the controller tag in which to store the data
being read.
Write: This is the controller tag that stores the value to be
written to the power monitor.
Size in Elements This is the number of elements being read or written to. If
you are performing a single element read or write, then
this value should be 1. If you are performing a multiple
element read or write, then this should be the number of
elements after the source element that you wish to read or
write.
Port Number 0 Data Table Address (Target Device) Refer to Appendix
value you’re reading or writing to.
Local Station Address This is the serial node address of your power monitor. Local / Remote Local
on page 18.
A for the address of the specific data
Message setup is complete for Serial communication.
4. Click the MultiHop tab if configuring Ethernet communication.
5. Enter the IP Address of the power monitor in the first row of the
To Address column.
Message setup is complete.
28 Publication 1408-UM001B-EN-P - May 2008
Explicit Messaging Chapter 4

Reading Logs

You can perform explicit messages to read data from log records in the power monitor.
For information on setting up explicit messages to the power monitor, please refer to Explicit Message Setup – Examples
The following logs can be read into a controller depending on the logs supported by your power monitor.
Unit Status Log
Min/Max Log
Energy Log
Load Factor Log
Time of Use Log kWh
Time of Use Log kVAR
Time of Use Log kVA
Please refer to Appendix log you are requesting.
A for the data table address of the specific
on page 17.
Log Data Table Methodology
The log data tables only hold one record instance for a specific log. Successive reads of the data table return a successive record instance for that log. By writing to specific configuration elements in the Log Request Table data table, you can configure the log to return in a forward or reverse direction. You can also configure the log to return a specific record for all logs except the Unit Status Log, and Energy Log.
Refer to
Log Request Table on page 64 for more information.
Publication 1408-UM001B-EN-P - May 2008 29
Chapter 4 Explicit Messaging
Example 1: Read the 5th Log Record in the Load Factor Log
This example explains how to configure the Log Request Table to read the 5
1. Create a write message to write the following values to the Log
Element Item Name Value
0 Selected Log 4 1 Chronology of Auto Return Data 0 2 Mix/Max Record to be Returned 0 3 Number of Unit Status Records 0 4 Number of Energy Log Records 0 5 Number of Time of Use Log Records 0 6 Number of Load Factor Log Records 0 7 Load Factor or TOU Record to be Returned 5
th
log record in the Load Factor Log.
Request Table.
2. Create a read message to read the values in the Load Factor Log
table.
30 Publication 1408-UM001B-EN-P - May 2008
Explicit Messaging Chapter 4
Example 2: Read Min/Max Log for Average Current
This example explains how to configure the Log Request Table to read the Min/Max log for Average Current.
Refer to
Min/Max Parameter List on page 84 for the specific record to
return.
In this example, Average Current is record 4.
1. Create a write message to write the following values to the Log
Request Table.
Element Item Name Value
0 Selected Log 2 1 Chronology of Auto Return Data 0 2 Mix/Max Record to be Returned 4 3 Number of Unit Status Records 0 4 Number of Energy Log Records 0 5 Number of Time of Use Log Records 0 6 Number of Load Factor Log Records 0 7 Load Factor or TOU Record to be Returned 0
2. Create a read message to read the values in the Min/Max Log
table.
Publication 1408-UM001B-EN-P - May 2008 31
Chapter 4 Explicit Messaging
32 Publication 1408-UM001B-EN-P - May 2008
Chapter
SCADA Applications
This section covers RSLinx driver setup, and OPC setup using the RSLinx OPC Server.
5

RSLinx Classic Drivers Configuration

The Powermonitor 1000 unit EDS file should be installed on the computer running RSLinx software before configuring drivers. RSLinx software supports DF1 Half-duplex, DF1 Full-duplex, and EtherNet/IP network communication.
Configure DF1 Half-duplex Slave
You need to use a RS232 to RS485 converter like the 1761-NET-AIC or B&B Electronics Converter – Model 485SD9TB.
1. Create a DF1 Polling Master Driver in RSLinx software.
2. Verify that the communication rate in the Port Configuration tab
is the same as the communication rate set for your power monitor.
3. Set the Error Checking Mode in the DF1 Protocol Settings tab to
CRC.
4. Set the Destination Station Out-of-List Strategy in the Polling
Strategies tab to Allow Msgs to Stns that are not in lists.
5. Perform an RSWho to verify that RSLinx software is
communicating to the power monitor.
RSLinx software driver configuration is complete.
33Publication 1408-UM001B-EN-P - May 2008 33
Chapter 5 SCADA Applications
Configure DF1 Full-duplex
You need to use a RS232 to RS485 converter, like the 1761-NET-AIC or B&B Electronics Converter – Model 485SD9TB.
1. Create a RS232 DF1 devices driver in RSLinx software.
2. Perform an Auto-configure.
3. Verify connections if Auto-configure fails.
4. Perform an RSWho to verify that RSLinx software is
communicating to the power monitor.
RSLinx software driver configuration is complete.
Configure RSLinx Software Driver Configuration for DH485
You need to use an RS232 to RS485 converter like the 1761-NET-AIC converter or B&B Electronics Converter - Model 485SD9TB.
1. Open the RSLinx Launch Control Panel.
2. Start RSLinx software to run as normal application, not as
service.
3. Create a 1747-PIC/AIC+ Driver in RSLinx software.
4. Verify that the communication rate is the same as the
communication rate set for your power monitor.
5. Set the node address and maximum node address of RSLinx
Driver.
6. Perform an RSWho to verify that RSLinx software is
communicating to the power monitor.
7. Restart RSLinx software to run as service.
34 Publication 1408-UM001B-EN-P - May 2008
SCADA Applications Chapter 5
Configure EtherNet/IP Network Using Ethernet Devices Driver
1. Create an Ethernet devices driver in RSLinx software.
2. Add the IP address of the power monitor to the driver station
mapping.
3. Perform an RSWho to verify that RSLinx software is
communicating to the power monitor.
RSLinx software driver configuration is complete.
Configure EtherNet/IP Network Using Ethernet/IP Driver
1. Create an Ethernet/IP driver in RSLinx software.

RSLinx Classic Software OPC Server Setup

2. Make selections to browse the local or remote subnet as
appropriate.
3. Perform an RSWho to verify that RSLinx software is
communicating to the power monitor.
RSLinx software driver configuration is complete.
IMPORTANT
You can setup RSLinx software as an OPC Server to serve data from a power monitor to an OPC 2.0 compliant application. You must first setup an RSLinx driver to communicate to the power monitor. You can then create an OPC topic to serve data to your SCADA application.
The power monitor makes a connection to either the RSLinx Ethernet Devices driver or the Ethernet/IP driver on a single computer but not both simultaneously.
Setup OPC Topic
Follow these steps to setup a DDE/OPC topic in RSLinx software for the power monitor.
1. Open RSLinx software.
Publication 1408-UM001B-EN-P - May 2008 35
Chapter 5 SCADA Applications
2. From the DDE/OPC menu, choose Topic Configuration.
This configuration window appears.
3. Click New.
This creates a topic in the left hand pane.
4. Name the topic pertinent to your application.
36 Publication 1408-UM001B-EN-P - May 2008
SCADA Applications Chapter 5
5. In the right hand pane, under the Data Source tab, browse to
your power monitor.
You may use a serial or Ethernet network driver.
TIP
When using a DH485 driver, change the connection type to local addressing mode in the Advanced Communication tab. This is especially important when several topics use the DH485 driver.
6. Make sure that the topic is highlighted in the left pane, and that
the power monitor is also highlighted in the right pane, then click Apply.
7. Click the Data Collection tab.
Publication 1408-UM001B-EN-P - May 2008 37
Chapter 5 SCADA Applications
8. From the Processor Type menu, choose SLC 500 or SLC 503+.
9. Click Done.
OPC Topic configuration is complete.
You can now use the RSLinx OPC Server, and the topic just created, to serve data to your application.
OPC item addresses are of the format [OPC Topic Name]Address,Ln,C1 where Address is the power monitor data address (example: F21:7). Optional argument Ln is the length of the array requested in elements. If the Ln argument is used, C1 (number of array columns) must also be specified.
38 Publication 1408-UM001B-EN-P - May 2008
SCADA Applications Chapter 5
Browse OPC Tags
The power monitor supports OPC tag browsing. The example uses the RSI OPC Test Client to illustrate tag browsing.
1. Open the RSI Test Client and connect to the RSLinx Classic OPC
Server.
2. Add a group, then add an item. Browse to the OPC topic and
then to the table and element in the Online tags.
Publication 1408-UM001B-EN-P - May 2008 39
Chapter 5 SCADA Applications
In this example, the User Configured Read Instance F9, element 8, in the OPC topic EM3_LAB is selected.
3. Click OK and start viewing data.
User-configured Data Table
The 1408-EM3 model provides a user configured data table. You may select the 16 floating-point parameters that comprise this table. Your application may read this table as connected input instance 1, or as CSP file F9 using explicit messaging.
Setup
You must use serial or Ethernet network communication to set up and read the user configured data table.
To set up the user configured table, using explicit messaging, write a new configuration to the User Configured Table Setup table.
See page 92 of the setup table. Pages 93…96 parameters.
for the content, default parameters and addressing details
list the available selections for the
40 Publication 1408-UM001B-EN-P - May 2008
SCADA Applications Chapter 5
Reading the User Configured Table as Connected Instance 1
The following example illustrates the steps required to set up an I/O connection between a Logix controller and the user configured Instance 1. The example uses a CompactLogix controller and RSLogix 5000 software.
Follow these steps to configure the connection.
1. Open an offline project in RSLogix 5000 software.
2. Open the Ethernet network interface and select the Ethernet
network.
3. Add a new module and choose Generic Ethernet Module from
the Communications group.
4. Configure the properties of the new module and click OK.
Parameter Choice
Name Your choice of name Comm Format Input Data - REAL IP Address The IP address of your power monitor Input Assembly Instance 1; Size 16 (32-bit) Output Assembly Instance 2 Configuration Assembly Instance 3; Size 0 Open Module Properties Leave checked
Publication 1408-UM001B-EN-P - May 2008 41
Chapter 5 SCADA Applications
5. On the connection tab, enter the desired Requested Packet
Interval (RPI).
Do not enter an RPI less than 50 mS.
6. Click OK, then Save and download the offline project into the
controller.
The data from the user configured table is read into the controller tag [Module Name]:I.Data without any further logic programming, at the selected RPI rate.
A power monitor connected instance may be owned by only one controller. An error results if you attempt to establish a connection with more than one controller. You may use explicit messaging to read the F9 table from any number of controllers.
42 Publication 1408-UM001B-EN-P - May 2008
Powermonitor 1000 Data Tables
Appendix
A

Summary of Data Tables

Summary of Powermonitor 1000 Data Tables for all Communication Protocols
Name of data table Data
Access
User Configured Table Results R F9 1 31601…31632 16 45 Analog Input Configuration RW F10 3 40001…40014 7 •••••46 Advanced Configuration RW F11 4 40101…40144 22 •••••47
The Summary of Powermonitor 1000 Data Tables for all Communication Protocols table summarizes all data tables available and their general attributes
The rest of the tables detail each specific data table and its associated elements, such as Modbus address, default value, ranges, and description.
IMPORTANT
CSP File No.
CIP Modbus
The lock symbol designates that the parameter that is marked will not be able to be written when the hardware lock terminals are connected together.
No of
Addressing
Elements
TR1
TR2
EM1
EM2
EM3
Refer to Page
RS485 Configuration RW N12 5 40201…40209 9 •••••51 Ethernet Configuration RW N13 6 40301…40323 23 •••••52 Time Zone Information 54 Date and Time Configuration RW N14 7 40401…40408 8 •••••57 Log Configuration RW N15 8 40501…40512 12 •••58 Command W F16 9 40601…40644 22 •••••61 Log Request RW N17 10 40701…40711 11 •••••64 Controller Interface W N18 11 40801…40808 8 ••66 Discrete Result R N19 12 30001…30006 6 •••••67 Wiring Diagnostics Results R F20 13 30101…30142 21 •••••68 Volts, Amps and Frequency
Results Power Results R F22 15 30301…30334 17 •• •71 Energy Results R F23 16 30401…30438 19 •••72
Publication 1408-UM001B-EN-P - May 2008 43
R F21 14 30201…30232 16 •• •70
Appendix A Powermonitor 1000 Data Tables
Summary of Powermonitor 1000 Data Tables for all Communication Protocols
Name of data table Data
Access
CSP File No.
CIP Modbus
Addressing
No of Elements
TR1
TR2
EM1
EM2
Refer to Page
EM3
Demand Results R F24 17 30501…30518 9 ••73 Unit Status Log Results R N25 18 30601…30613 13 •••••74 Unit Status Log Code 76 Energy Log Results R F26 19 30701…30742 21 •••78 Write Error Status Results R N27 20 30801…30803 3 •••••79 Unit Run Status Results R N28 21 30901…30925 25 •••••80 Min/Max Log Results R F29 22 31001…31022 11 •• •83 Min/Max Parameter List •• •84 Load Factor Log Results R F30 23 31101…31128 14 ••85 Time of Use Log Results- Real
R F31 24 31201…31224 12 •••87
Energy and Demand Time of Use Log Results -
R F32 25 31301…31324 12 ••88
Reactive Energy and Demand Time of Use Log Results -
R F33 26 31401…31424 12 ••89
Apparent Energy and Demand Catalog Number and WIN R N34 27 31501…31519 19 •••••90 Single Element Password Write W N35 28 40901 1 •••••91 User Configurable Table Setup R/W N36 29 41001…41017 17 92 Parameters for Configurable
Table
93
44 Publication 1408-UM001B-EN-P - May 2008
Powermonitor 1000 Data Tables Appendix A

Data Tables

User Configured Table Results
Element No. Modbus
Address
0 31601-2 User selected Parameter #1 Parameters previously setup during a write to User Configured Table 1 31603-4 User selected Parameter #2 2 31605-6 User selected Parameter #3 3 31607-8 User selected Parameter #4 4 31609-10 User selected Parameter #5 5 31611-12 User selected Parameter #6
Element Name Description
User Configured Table Results Parameters
CSP File No. F9 CIP Instance 1 Applies to EM3 only No. of Elements 16 No. of Words 32 Data Type Float Data Access Read Only
Setup table.
6 31613-14 User selected Parameter #7 7 31615-16 User selected Parameter #8 8 31617-18 User selected Parameter #9 9 31619-20 User selected Parameter #10 10 31621-22 User selected Parameter #11 11 31623-24 User selected Parameter #12 12 31625-26 User selected Parameter #13 13 31627-28 User selected Parameter #14 14 31629-30 User selected Parameter #15 15 31631-32 User selected Parameter #16
Publication 1408-UM001B-EN-P - May 2008 45
Appendix A Powermonitor 1000 Data Tables
Analog Input Configuration
Analog Input Configuration Parameters
CSP File No. F10 CIP Instance 3 Applies to All models No. of Elements 7 No. of Words 14 Data Type Float Data Access Read/Write
Element No.
Modbus Address
Element Name Default
Value
Range Description
0 40001-2 Password 0 0…9999 When writing the complete table this parameter allows the
input data to be accepted. When writing a single parameter the separate password table should be used. Returns -1 on a read.
1 40003-4 Voltage Mode 2 0…4 Should match the external electrical system and how it is
wired to the Powermonitor’s voltage and current input terminals. Refer to the installation manual wiring diagrams.
0 = Direct Delta 1 = Open Delta 2 = Wye 3 = Single Phase 4 = Demo
2 40005-6 PT Primary 480 1.00…
50,000
The first value of the PT ratio (xxx:xxx) indicating the nominal voltage present at the high-end of the transformer. If no transformer is used (for direct connect of up to 347V L-N or 600V L-L), set the PT ratio to any valid 1:1 ratio (for example 480:480).
3 40007-8 PT Secondary 480 1.00…
600.00
The second value of the PT ratio (xxx:xxx) indicating the nominal voltage present at the low-end of the transformer.
4 40009-10 CT Primary 5 5.00…
50,000
The first value of the CT ratio (xxx:5) indicating the nominal current present at the high-end (primary side) of the transformer.
Example: PRI = 1000. Setting = 1000:5.
5 A is the nominal secondary current of the CT.
5 40011-12 System PF Setting 2 0…2 0 = Leading -97…89
1 = High -85…98 2 = Low -52…-95
6 40013-14 Reserved 0 0 Reserved for future use.
46 Publication 1408-UM001B-EN-P - May 2008
Advanced Configuration
Powermonitor 1000 Data Tables Appendix A
Advanced Configuration Parameters
CSP File No. F11 CIP Instance 4 No. of Elements 22 No. of Words 44 Data Type Float Data Access Read/Write
Element No.
Modbus Address Range
Element Name
Default Value
Range
Description
TR1
TR2
EM1
EM2
EM3
0 40101-2 Password 0 0…9999 •••••When writing the complete table this
parameter allows the input data to be accepted. When writing a single parameter the separate password table should be used. Returns -1 on a read.
1 40103-4 New
Password
0 0…9999 •••••This becomes the new password when the
proper the configuration password entry has been made and this parameter is greater than (-1).
2 40105-5 Metering
Result Averaging
101•••••The metering results for volts, amps,
power and frequency is averaged over 8 cycles of data to provide a steady output reading.
0 = Off 1 = On
3 40107-8 Log Status
Input Changes
001•••••0 = Disable recording of status input
changes into the status log. 1 = Enable recording of status input changes into the status log.
4 40109-10 Use Daylight
Savings
001•••••0 = Disable Daylight Savings
1 = Enable Daylight Savings
Correction
Publication 1408-UM001B-EN-P - May 2008 47
Appendix A Powermonitor 1000 Data Tables
Advanced Configuration
Element No.
Modbus Address
Element Name
Range
5 40111-12 Daylight
Savings Month/Week /Day Start
6 40113-14 Hour of Day
Start
7 40115-16 Return from
Daylight Savings Month/Week /Day
Default
Range
Description
Value
TR1
TR2
EM1
EM2
EM3
030201
March, 2nd,
10101… 120507
•••••This is the day that the power monitor will
add an hour to the time. This feature also looks at Ethernet SNTP offset and corrects for Daylight Savings.
Sunday
Example: 040107 = April/1st week/Sunday
Month Settings: 01 = January…12 = December
Week Settings: 01 = 1st week…05 = Last Week
Day of the Week Settings: 01 = Sunday…07 = Saturday
2023•••••The hour of day the daylight savings
adjustment should be made to add an hour.
110101
November, 1st, Sunday
10101… 120507
•••••This is the day that the power monitor will
subtract an hour from the time. This feature also looks at Ethernet SNTP offset and corrects for the return from Daylight Savings.
8 40117-18 Hour of Day
End
9 40119-20 KYZ Solid
State Output Parameter
10 40121-22 KYZ Solid
State Output Scale
Month Settings: 01 = January…12 = December
Week Settings: 01 = 1st week…05 = Last Week
Day of the Week Settings: 01 = Sunday…07 = Saturday
2023•••••The hour of day the daylight savings
adjustment should be made to subtract an hour.
005 •••The parameter selected will pulse the KYZ
output at a rate that equals the parameter value divided by KYZ scale.
0 = Disable 1 = Wh Fwd 2 = Wh Rev 3 = VARh Fwd (EM2 and EM3 Only) 4 = VARh Rev (EM2 and EM3 Only) 5 = Vah (EM2 and EM3 Only)
1,000 1…
100,000
•••The KYZ output parameter divided by the
scale is the output pulse rate. Example: Wh is selected for the parameter and 1,000 is the scale value. The output is pulsed every kWh.
48 Publication 1408-UM001B-EN-P - May 2008
Advanced Configuration
Powermonitor 1000 Data Tables Appendix A
Element No.
Modbus Address
Element Name
Range
11 40123-24 KYZ Pulse
Duration Setting
12 40125-26 Status Input
1 Input Scale
13 40127-28 Status Input
2 Input Scale
14 40129-30 Demand
Source
Default
Range
Description
Value
TR1
TR2
EM1
EM2
EM3
250 ms 0 or
50…1000
•••Set as 50…1000 to indicate the duration
of the pulse in milliseconds, or set to 0 for KYZ-style transition output. (Toggle) The value for delay is rounded off to the nearest 10ms internally during this function.
11
1,000,000
•••When a status pulse is received the count
is increased by the scale factor. Input pulse * input scale added to total status count.
11
1,000,000
•••When a status pulse is received the count
is increased by the scale factor. Input pulse * input scale added to total status count.
003 ••When item Demand Broadcast Master
Select of the ethernet table is set to master a selection of 0 through 2 sets the type of master input. In this case item 3 is ignored. When the Demand Broadcast Master Select of the ethernet table is set to slave then any of these inputs can set the end of the demand period. Selections of 0 through 2 can be selected for RS485 units.
15 40131-32 Demand
Period Length
16 40133-34 Number of
Demand Periods
0 = Internal Timer 1 = Status Input 2 2 = Controller Command 3 = Ethernet Demand Broadcast
Selection 3 can only be programmed when the Ethernet option is installed.
15 min 0…99 ••Specifies the desired period for demand
calculations. When set to 0 there are no projected demand calculations. If the internal timer is selected a setting of 0 turns the demand function off.
1115 ••Specifies the number of demand periods
to average for demand measurement.
Publication 1408-UM001B-EN-P - May 2008 49
Appendix A Powermonitor 1000 Data Tables
Advanced Configuration
Element No.
Modbus Address
Element Name
Range
17 40135-36 Forced
Demand Sync Delay
18 40137-38 Unit Error
Action
19 40139-40 Software
Error Log Full Action
Default
Range
Description
Value
TR1
TR2
EM1
EM2
EM3
10 s 0…900 s ••When the power monitor is configured for
external demand control the unit delays for xxx seconds after the expected control pulse has not been received. The demand period starts over and a record is recorded in the status log.
0 = Wait forever 1…900 = Wait this many seconds before starting a new demand period.
This setting becomes active when the demand interval is set from -1…-99 minutes.
101•••••This parameter determines the action
when a unit error occurs.
0 = Halt on error and make status LED solid red 1 = Reset power monitor hardware.
101•••••This parameter determines the action
when a firmware failure is detected and the error log is full.
0 = Halt on error and wait for clear log command, also make status LED solid red 1 = Perform a firmware reset.
20 40141-42 Reserved 0 0 Reserved for future use. 21 40143-44 Reserved 0 0 Reserved for future use.
50 Publication 1408-UM001B-EN-P - May 2008
Serial RS-485 Port Configuration
Powermonitor 1000 Data Tables Appendix A
Serial RS-485 Port Configuration Parameters
CSP File No. N12 CIP Instance 5 Applies to All models No. of Elements 9 No. of Words 9 Data Type Integer Data Access Read/Write
Element No.
Modbus Address
Element Name Default
Value
Range Description
0 40201 Password 0 0…9999 When writing the complete table this parameter allows the input
data to be accepted. When writing a single parameter the separate password table should be used. Returns -1 on a read.
1 40202 Protocol Setting 1 0…3 The protocol selection for communications.
0 = DF1 Half Duplex Slave 1 = DF1 Full Duplex 2 = Modbus RTU Slave 3 = Auto Sense 4 = DH485
2 40203 Serial Delay 2
(10 ms)
1…15 The setting times 5 = milliseconds that the unit waits before
responding to a communication request. Useful for consistent communications and slow devices.
3 40204 Baud Rate 5 0…6 The serial communications baud rate.
0 = 1200 1 = 2400 2 = 4800 3 = 9600 4 = 19200 5 = 38,400 6 = 57,600
4 40205 DF1, DH485,
Modbus Address
Device ID, 31 for DH485
1…247 (DF1, Modbus) 0…31
During production the Device ID is printed on the nameplate. This ID then becomes the default address for DF1 and Modbus.
(DH485)
Publication 1408-UM001B-EN-P - May 2008 51
Appendix A Powermonitor 1000 Data Tables
Serial RS-485 Port Configuration
Element No.
5 40206 Data Format 0 0…2
Modbus Address
Element Name Default
Value
Range Description
Parity, number of data bits, number of stop bits (2 for DH485)
0 = No parity, 8 data bits, 1 stop bit
1 = Odd parity, 8 data bits, 1 stop bit
2 = Even parity, 8 data bits, 1 stop bit
6 40207 Inter Character
Timeout
00
6553
Specifies the minimum delay between characters that indicates the
end of a message packet for Modbus protocol. 0 = 3.5 character
times in default. The unit is ms.
8 40208 Maximum Node
3 1…31 Specifies the maximum node address on a DH485 network.
Address
9 40209 Reserved 0 0 Reserved for future use.
Ethernet Configuration Parameters
CSP File No. N13 CIP Instance 6 No. of Elements 23 No. of Words 23 Data Type Integer Data Access Read/Write
Ethernet Configuration
Element No.
Modbus Address
Element Name Default
Value
Range
TR1
TR2
EM1
EM2
Description
EM3
0 40301 Password 0 0…9999 •••••When writing the complete table this
parameter allows the input data to be accepted. When writing a single parameter the separate password table should be used. Returns -1 on a read.
1 40302 IP Address Byte a
192 0…255 •••••The 1st Octet of the Static IP Address.
(aaa.xxx.xxx.xxx)
2 40303 IP Address Byte b
168 0…255 •••••The 2nd Octet of the Static IP Address.
(xxx.bbb.xxx.xxx)
3 40304 IP Address Byte c
254 0…255 •••••The 3rd Octet of the Static IP Address.
(xxx.xxx.ccc.xxx)
4 40305 IP Address Byte d
Unit ID 0…255 •••••The 4th Octet of the Static IP Address.
(xxx.xxx.ddd.xxx)
52 Publication 1408-UM001B-EN-P - May 2008
Ethernet Configuration
Powermonitor 1000 Data Tables Appendix A
Element No.
Modbus Address
Element Name Default
Value
Range
TR1
TR2
EM1
EM2
Description
EM3
5 40306 Subnet Mask Byte a 255 0…255 •••••Specifies the subnet mask to apply to
the IP address.
6 40307 Subnet Mask Byte b 255 0…255 •••••Specifies the subnet mask to apply to
the IP address.
7 40308 Subnet Mask Byte c 0 0…255 •••••Specifies the subnet mask to apply to
the IP address.
8 40309 Subnet Mask Byte d 0 0…255 •••••Specifies the subnet mask to apply to
the IP address.
9 40310 Gateway IP Address
Byte a
10 40311 Gateway IP Address
Byte b
11 40312 Gateway IP Address
Byte c
12 40313 Gateway IP Address
Byte d
128 0…255 •••••IP address of the gateway to other
subnets for wide area networking.
1 0…255 •••••IP address of the gateway to other
subnets for wide area networking.
1 0…255 •••••IP address of the gateway to other
subnets for wide area networking.
1 0…255 •••••¸ IP address of the gateway to other
subnets for wide area networking.
13 40314 SNTP Mode Select 0 0…2 •••••This mode selects the mode of the SNTP
function or to disable the SNTP function.
0 = Disable 1 = Unicast - The SNTP address points to a unicast server. 2 = Anycast Mode - The SNTP address is a broadcast address of an anycast group.
14 40315 SNTP Update
Interval
300 1…32766 •••••Indicates how often the time is updated
from the SNTP Server. The unit is minute.
15 40316 Time Zone Select 7 0…32 •••••The time zone table has detailed time
zone information.
16 40317 Time Server IP
Address Byte a
0 0…255 •••••The internal clock is set after each Time
set interval has expired. The Time server IP address is the SNTP time server where the request is handled.
17 40318 Time Server IP
Address Byte b
0 0…255 •••••The internal clock is set after each Time
set interval has expired. The Time server IP address is the SNTP time server where the request is handled.
18 40319 Time Server IP
Address Byte c
0 0…255 •••••The internal clock is set after each Time
set interval has expired. The Time server IP address is the SNTP time server where the request is handled.
Publication 1408-UM001B-EN-P - May 2008 53
Appendix A Powermonitor 1000 Data Tables
Ethernet Configuration
Element No.
19 40320 Time Server IP
Modbus Address
Element Name Default
Value
0 0…255 •••••The internal clock is set after each Time
Address Byte d
Range
TR1
TR2
EM1
Description
EM2
EM3
set interval has expired. The Time server IP address is the SNTP time server where the request is handled.
20 40321 Demand Broadcast
Master Select
001 ••When configured as a Master the power
monitor broadcasts an end of demand interval broadcast to the UDP port number configured.
0 = Slave 1 = Master control
21 40322 Broadcast Port
Number
300 300…400 ••When configured as a Master and
External Demand Source or Ethernet Demand Broadcast the port number is the listening or broadcast port for the UDP message.
22 40323 Reserved 0 0 Reserved for future use.
Time Zone Information
Value Offset from GMT Time Zone Name Areas in Time Zone
0 GMT-12:00 Dateline Standard Time Eniwetok, Kwajalein 1 GMT-11:00 Samoa Standard Time Midway Island, Samoa 2 GMT-10:00 Hawaiian Standard Time Hawaii 3 GMT-09:00 Alaskan Standard Time Alaska 4 GMT-08:00 Pacific Standard Time Pacific Time (US & Canada,; Tijuana) 5 GMT-07:00 Mountain Standard Time Mountain Time (US & Canada)
US Mountain Standard Time Arizona
6 GMT-06:00 Canada Central Standard Time Saskatchewan
Central America Standard Time Central America Central Standard Time Central Time (US & Canada) Mexico Standard Time Mexico City
7 GMT-05:00 Eastern Standard Time Eastern Time (US & Canada)
SA Pacific Standard Time Bogota, Lima, Quito US Eastern Standard Time Indiana (East)
8 GMT-04:00 Atlantic Standard Time Atlantic Time (Canada)
Pacific SA Standard Time Santiago SA Western Standard Time Caracas, La Paz
9 GMT-03:30 Newfoundland Standard Time Newfoundland
54 Publication 1408-UM001B-EN-P - May 2008
Powermonitor 1000 Data Tables Appendix A
Time Zone Information
Value Offset from GMT Time Zone Name Areas in Time Zone
10 GMT-03:00 E. South America Standard Time Brasilia
Greenland Standard Time Greenland
SA Eastern Standard Time Buenos Aires, Georgetown 11 GMT-02:00 Mid-Atlantic Standard Time Mid-Atlantic 12 GMT-01:00 Azores Standard Time Azores
Cape Verde Standard Time Cape Verde Is. 13 GMT Standard Time Greenwich Mean Time: Dublin, Edinburgh, Lisbon, London
Greenwich Standard Time Casablanca, Monrovia 14 GMT+01:00 Central Europe Standard Time Belgrade, Bratislava, Budapest, Ljubljana, Prague
Central European Standard Time Sarajevo, Skopje, Sofija, Vilnius, Warsaw, Zagreb
Romance Standard Time Brussels, Copenhagen, Madrid, Paris
W. Central Africa Standard Time West Central Africa
W. Europe Standard Time Amsterdam, Berlin, Bern, Rome, Stockholm, Vienna 15 GMT+02:00 E. Europe Standard Time Bucharest
Egypt Standard Time Cairo
FLE Standard Time Helsinki, Riga, Tallinn
GTB Standard Time Athens, Istanbul, Minsk
Israel Standard Time Jerusalem
South Africa Standard Time Harare, Pretoria 16 GMT+03:00 Arab Standard Time Kuwait, Riyadh
Arabic Standard Time Baghdad
E. Africa Standard Time Nairobi
Russian Standard Time Moscow, St. Petersburg, Volgograd 17 GMT+03:30 Iran Standard Time Tehran 18 GMT+04:00 Arabian Standard Time Abu Dhabi, Muscat
Caucasus Standard Time Baku, Tbilisi, Yerevan 19 GMT+04:30 Afghanistan Standard Time Kabul 20 GMT+05:00 Ekaterinburg Standard Time Ekaterinburg
West Asia Standard Time Islamabad, Karachi, Tashkent 21 GMT+05:30 India Standard Time Calcutta, Chennai, Mumbai, New Delhi 22 GMT+05:45 Nepal Standard Time Kathmandu 23 GMT+06:00 Central Asia Standard Time Astana, Dhaka
N. Central Asia Standard Time Almaty, Novosibirsk
Sri Lanka Standard Time Sri Jayawardenepura 24 GMT+06:30 Myanmar Standard Time Rangoon
Publication 1408-UM001B-EN-P - May 2008 55
Appendix A Powermonitor 1000 Data Tables
Time Zone Information
Value Offset from GMT Time Zone Name Areas in Time Zone
25 GMT+07:00 North Asia Standard Time Krasnoyarsk
SE Asia Standard Time Bangkok, Hanoi, Jakarta
26 GMT+08:00 China Standard Time Beijing, Chongqing, Hong Kong, Urumqi
North Asia East Standard Time Irkutsk, Ulaan Bataar Singapore Standard Time Kuala Lumpur, Singapore Taipei Standard Time Taipei W. Australia Standard Time Perth
27 GMT+09:00 Korea Standard Time Seoul
Tokyo Standard Time Osaka, Sapporo, Tokyo Yakutsk Standard Time Yakutsk
28 GMT+09:30 AUS Central Standard Time Darwin
Cen. Australia Standard Time Adelaide
29 GMT+10:00 AUS Eastern Standard Time Canberra, Melbourne, Sydney
E. Australia Standard Time Brisbane Tasmania Standard Time Hobart Vladivostok Standard Time Vladivostok
West Pacific Standard Time Guam, Port Moresby 30 GMT+11:00 Central Pacific Standard Time Magadan, Solomon Is., New Caledonia 31 GMT+12:00 Fiji Standard Time Fiji, Kamchatka, Marshall Is.
New Zealand Standard Time Auckland, Wellington 32 GMT+13:00 Tonga Standard Time Nuku'alofa
56 Publication 1408-UM001B-EN-P - May 2008
Date and Time Configuration
Powermonitor 1000 Data Tables Appendix A
Date and Time Configuration Parameters
CSP File No. N14 CIP Instance 7 Applies to All models No. of Elements 8 No. of Words 8 Data Type Integer Data Access Read/Write
Element No.
Modbus Address
Element Name Default
Value
Range Description
0 40401 Password 0 0…9999 When writing the complete table this parameter allows the
input data to be accepted. When writing a single parameter the separate password table should be used. Returns -1 on a read.
1 40402 Date: Year 2005 2001…
The range is from 2001… 2100. A write sets the current year.
2100
2 40403 Date: Month 1 1…12 A write sets the current month.
A read returns current month. 1=January, 2=February,…12=December
3 40404 Date: Day 1 1…31 A write sets the current day of the month.
A reads returns the current day of the month. The internal real-time clock adjusts the date for leap-year.
4 40405 Time: Hour 0 0…23 A write sets the current hour.
A read returns the current hour. 0=12am, 1=1am,…23=11pm The internal real-time clock does not adjust for daylight savings time.
5 40406 Time: Minute 0 0…59 A write sets the current minutes.
A read returns the current minutes.
6 40407 Time: Seconds 0 0…59 A write sets the current seconds.
A read returns the current seconds.
7 40408 Time: Hundredths 0 0…99 Set this element to 0 for writes. Returns hundredths of a second
on read.
Publication 1408-UM001B-EN-P - May 2008 57
Appendix A Powermonitor 1000 Data Tables
Log Configuration
Log Configuration Parameters
CSP File No. N15 CIP Instance 8 No. of Elements 12 No. of Words 12 Data Type Integer Data Access Read/Write
Element No.
Modbus Address
Element Name Default
Value
Range
0 40501 Password 0 0…
9999
1 40502 Energy Log
15 min -1…60 •••Selects how often a record is logged
Interval
2 40503 Energy Log
101 •••This parameter set the action of the log
Mode
3 40504 Time of Use Log
31 0…31 •••Automatically stores the current record
Auto Log Setting
Description
TR1
TR2
EM1
EM2
EM3
•••When writing the complete table this
parameter allows the input data to be accepted. When writing a single parameter the separate password table should be used. Returns -1 on a read.
(minutes). A value of 0 disables periodic logging of records. A value of –1 causes logging of records to be synchronized to the end of the demand interval.
once is has filled to capacity. Setting the option to 0 allows the log to fill but stops at the end. Option 1 lets the log fill and then oldest records are deleted and replaced with new records.
0 = Fill and Stop 1 = Overwrite, When the log is filled new records replace the oldest records.
for the month replacing the oldest record if the log is full. The log holds 12 months plus the current record.
0 = Disables the auto clear feature. 1 = Store and clear the table on the 1st day of each month. 2 = 2nd Day 3 = 3rd day … 29…31 = Store and clear table at the last day of the month.
58 Publication 1408-UM001B-EN-P - May 2008
Log Configuration
Powermonitor 1000 Data Tables Appendix A
Element No.
Modbus Address
Element Name Default
Value
Range
TR1
TR2
EM1
EM2
Description
EM3
4 40505 Off Peak Days 65 0…127 •••This bit map field selects the off peak
days. OFF-PEAK days have only one rate for billing.
Bit0= Sunday Bit1= Monday Bit2= Tuesday Bit3= Wednesday Bit4= Thursday Bit5= Friday Bit6= Saturday Saturday and Sunday are default Off Peak days.
5 40506 MID Peak AM
Hours
1792 0…
4095
•••This bit map selects any AM hours that
are designated as MID Peak. Example: The hours from 8 AM to 11AM is designated as bit 8 through bit 10 = 1792d.
Bit0= 12 AM…1 AM Bit1= 1 AM…2 AM Bit2= 2 AM…3 AM … … Bit11= 11AM…12 AM Default is 8 AM…11 AM
6 40507 MID Peak PM
Hours
120 0…
4095
•••This bit map selects any PM hours that
are designated as MID Peak. Example: The hours from 3 PM to 7 PM is designated as bit 3 through bit 6 = 120d.
Bit0= 12 PM…1 PM Bit1= 1 PM…2 PM Bit2= 2 PM…3 PM … … Bit11= 11PM…12 PM Default is 3 PM…7 PM
7 40508 ON Peak AM
Hours
2048 0…
4095
•••This bit map selects any AM hours that
are designated as ON Peak. Example: The hours from 11AM to 12 PM is designated as bit 11 = 2048d.
Bit0= 12 AM…1 AM Bit1= 1 AM…2 AM Bit2= 2 AM…3 AM … Bit11= 11AM…12 AM Default is 11AM
Publication 1408-UM001B-EN-P - May 2008 59
Appendix A Powermonitor 1000 Data Tables
Log Configuration
Element No.
Modbus Address
Element Name Default
8 40509 ON Peak PM
hours
9 40510 Load Factor log
Auto Log Setting
Range
Value
7 0…409
5
TR1
TR2
EM1
EM2
•••This bit map selects any PM hours that
Description
EM3
are designated as ON Peak. Example: The hours from 12 PM to 3 PM is designated as bit 0 through bit 2 = 7d
Bit0= 12 PM…1 PM Bit1= 1 PM…2 PM Bit2= 2 PM…3 PM … Bit11= 11PM…12 PM Default is 12 PM…3 PM
31 0…31 •••Automatically stores the current peak,
average, and load factor results as a record in the non-volatile load factor log and resets the log at the specified day of the month.
0 = Disables the auto clear feature. 1 = Store and clear the table on the 1st day of each month. 2 = 2nd Day 3 = 3rd day … 29…31 = Store and clear table at the last day of the month.
10 40511 Reserved 0 0 Reserved for future use. 11 40512 Reserved 0 0 Reserved for future use.
Command Table Parameters
CSP File No. F16 CIP Instance 9 No. of Elements 22 No. of Words 44 Data Type Float Data Access Write
60 Publication 1408-UM001B-EN-P - May 2008
Command Table
Powermonitor 1000 Data Tables Appendix A
Element No.
Modbus Address
Element Name Default
Value
Range
TR1
TR2
EM1
EM2
Description
EM3
0 40601-2 Password 0 0…9999 •••••When writing the complete table this
parameter allows the input data to be accepted. When writing a single parameter the separate password table should be used. Returns -1 on a read.
1 40603-4 Command Word 10032•••••These commands can be sent to the
power monitor. When using the optional elements the command table must be sent complete with all elements present. If the single password table is used to gain access to configuration items then the command can be sent alone without optional settings. The command options are:
0 = No Action 1 = Set kWh Register 2 = Set kVARh Register 3 = Set kVAh Register 4 = Clear All Energy Registers 5 = Set Status 1 Count 6 = Set Status 2 Count 7 = Clear Energy Log 8 = Force KYZ Output On 9 = Force KYZ Output Off 10 = Remove Force from KYZ 11 = Restore Factory Defaults 12 = Perform Wiring Diagnostics 13 = Reset power monitor System 14…32 = Reserved If a command is received that is not supported by your catalog number the command will be ignored.
2 40605-6 Command Word 20032•••••0 = No Action
1 = Clear Min/Max Records 2 = Store and clear current Load Factor Record 3 = Clear Load Factor Log 4 = Store and clear current TOU Record 5 = Clear TOU Log 6 = Clear Error Log command 7 = Troubleshooting Mode Enable 8…32 = Reserved. If a command is received that is not supported by your catalog number the command will be ignored.
Publication 1408-UM001B-EN-P - May 2008 61
Appendix A Powermonitor 1000 Data Tables
Command Table
Element No.
Modbus Address
Element Name Default
3 40607-8 Clear Single
Min/Max Records
4 40609-10 Status 1 Count x
M Register Set Value
5 40611-12 Status 1 Count
X 1 Register Set Value
6 40613-14 Status 2 Count x
M Register Set Value
7 40615-16 Status 2 Count
X 1 Register Set Value
8 40617-18 GWh Fwd
Register Set Value
9 40619-20 kWh Fwd
Register Set Value
10 40621-22 GWh Rev
Register Set Value
11 40623-24 kWh Rev
Register Set Value
12 40625-26 GVARh Fwd
Register Set Value
13 40627-28 kVARh Fwd
Register Set Value
14 40629-30 GVARh Rev
Register Set Value
Range
Value
0 0…35
0…31 0…19
00
9,999,999
00
999,999
00
9,999,999
00
999,999
00
9,999,999
00
999,999
00
9,999,999
00
999,999
00
9,999,999
00
999,999
00
9,999,999
Description
TR1
TR2
EM1
EM2
EM3
•• When setting the Min/Max Clear bit this
value can be sent to specify a single parameter. If clearing all values this is not required.
EM3 = 0…35 TR2 = 0…31 TR1 = 0…19 0=Clear All Parameters 1= Clear the 1st Min/Max Record 2= Clear the 2nd Min/Max Record … 35=Clear the 35th Min/Max Record
•••Status 1 Count Register Start Value x
1,000,000
•••Status 1 Count Register Start Value x 1
•••Status 2 Count Register Start Value x
1,000,000
•••Status 2 Count Register Start Value x 1
•••Sets the GWh Fwd Register to the
desired Value
•••Sets the kWh Fwd Register to the
desired Value
•••Sets the GWh Rev Register to the
desired Value
Sets the kWh Rev Register to the
desired Value
••Sets the GVARh Fwd Register to the
desired Value
••Sets the kVARh Fwd Register to the
desired Value
••
Sets the GVARh Rev Register to the desired Value
62 Publication 1408-UM001B-EN-P - May 2008
Command Table
Powermonitor 1000 Data Tables Appendix A
Element No.
Modbus Address
Element Name Default
15 40631-32 kVARh Rev
Register Set
Range
Value
00
999,999
TR1
TR2
EM1
EM2
••Sets the kVARh Rev Register to the
Description
EM3
desired Value
Value
16 40633-34 GVAh Register
Set Value
17 40635-36 kVAh Register
Set Value
18 40637-38 Troubleshooting
Password
00
9,999,999
00
999,999
••Sets the GVAh Register to the desired
Value
••Sets the kVAh Register to the desired
Value
00 •••• Password for Troubleshooting Mode
provided by the password generator program.
19 40639-40 Reserved 0 0 Reserved for future use. 20 40641-42 Reserved 0 0 Reserved for future use. 21 40643-44 Reserved 0 0 Reserved for future use.
Publication 1408-UM001B-EN-P - May 2008 63
Appendix A Powermonitor 1000 Data Tables
Log Request Table
Log Request Table Parameters
CSP File No. N17 CIP Instance 10 No. of Elements 11 No. of Words 11 Data Type Integer Data Access Read/Write
Element No.
Modbus Address
Element Name Default
Value
Range
TR1
TR2
EM1
EM2
Description
EM3
0 40701 Selected Log 0 0…5 •••••Selects the log that information is
returned from. Once a single request has been made the auto return feature will bring back successive records each time the log is read. Some logs support individual record requests. 1 = Unit Status Log 2 = Min/Max Log 3 = Energy Log 4 = Load Factor Log 5 = Time of Use Log kWh 6 = Time of Use Log kVAR 7 = Time of Use Log kVA If your catalog number does not support the requested log item the power monitor will ignore the request.
1 40702 Chronology of
Auto Return Data
101•••••The date chronology of the returned
records. 0 = Reverse direction 1 = Forward direction
2 40703 The Min/Max
record to be returned
0035
0…31 0…15
•• Selects the Min/Max record number
to be returned. See the table for Min/Max record list. 0 = Use incremental return and the chronology selected. EM3 = 1…35 TR2 = 1…31 TR1 = 1…15
3 40704 Number of Unit
Status Records
-150•••••On a read of this table the value of this
parameter is the number of Unit Status Records available. This log is only returned using the incremental return method.
64 Publication 1408-UM001B-EN-P - May 2008
Log Request Table
Powermonitor 1000 Data Tables Appendix A
Element No.
Modbus Address
Element Name Default
4 40705 Number of
Energy Log Records
5 40706 Number of Time
of Use Log Records
6 40707 Number of Load
Factor Log Records
7 40708 Load Factor or
TOU Record to be Returned.
Range
Value
-0… 17,280
TR1
TR2
EM1
EM2
•••On a read of this table the value of this
Description
EM3
parameter is the number of Energy Log Records available.
-113 •••On a read of this table the value of this
parameter is the number of Time of Use Log Records available. One is the current record being updated before logging.
-113 ••On a read of this table the value of this
parameter is the number of Load Factor Log Records available. One is the current record being updated before logging.
-013•••••Selects the Load Factor or TOU record
number to be returned.
0 = Use incremental return and the chronology selected 1 through 13 selects an individual record.
8 40709 Reserved - 0 Reserved for future use. 9 40710 Reserved - 0 Reserved for future use. 10 40711 Reserved - 0 Reserved for future use.
Publication 1408-UM001B-EN-P - May 2008 65
Appendix A Powermonitor 1000 Data Tables
Controller Interface Table
Controller Interface Table Parameters
CSP File No. N18 CIP Instance 11 Applies to EM2, EM3 only No. of Elements 8 No. of Words 8 Data Type Integer Data Access Write
Element No.
Modbus Address
Element Name Default
Value
Range Description
0 40801 Password 0 0…9999 When writing the complete table this parameter allows the input
data to be accepted. When writing a single parameter the separate password table should be used. Returns -1 on a read.
1 40802 Controller
Command Word
0 0…1 Bit 0 = When this bit is written to the power monitor it signals the
end of the demand period. The power monitor resets the bit to 0 and sends the end of demand broadcast to all of the slaves configured for the master/slave demand system. The power monitor must be configured as a Master for external demand pulse input. Bit 1…15 = Reserved
2 40803 Reserved 0 0 Reserved for future use. 3 40804 Reserved 0 0 Reserved for future use. 4 40805 Reserved 0 0 Reserved for future use. 5 40806 Reserved 0 0 Reserved for future use. 6 40807 Reserved 0 0 Reserved for future use. 7 40808 Reserved 0 0 Reserved for future use.
66 Publication 1408-UM001B-EN-P - May 2008
Discrete Results
Powermonitor 1000 Data Tables Appendix A
Discrete Results Parameters
CSP File No. N19 CIP Instance 12 Applies to All models No. of Elements 6 No. of Words 6 Data Type Integer Data Access Read
Element No.
Modbus Address
Element Name Range Description
0 30001 Status Input States 0…3 Indicates the current states of the status input.
Bit 0 = Status 1 activated Bit 1 = Status 2 activated Bit 2…15 = Reserved
1 30002 Output Word 0…15 Bit 0 = KYZ relay actuated
Bit 1 = KYZ output forced on Bit 2 = KYZ output forced off Bit 3 = External demand pulse timeout Bit 4 = Terminal Locked Bit 5…15 = Reserved
2 30003 Reserved 0 Reserved for future use. 3 30004 Reserved 0 Reserved for future use. 4 30005 Reserved 0 Reserved for future use. 5 30006 Reserved 0 Reserved for future use.
Publication 1408-UM001B-EN-P - May 2008 67
Appendix A Powermonitor 1000 Data Tables
Wiring Diagnostics Results
Wiring Diagnostics Results Parameters
CSP File No. F20 CIP Instance 13 No. of Elements 21 No. of Words 42 Data Type Float Data Access Read
Element No.
Modbus Address
Element Name Units Range
TR1
TR2
EM1
EM2
Description
EM3
0 30101-2 Wiring Status 0…5 •••••This is the overall status of the
wiring diagnostic test. 0 = Pass 1 = Failed 2 = Input Level Low 3 = Disabled 4 = Waiting Command 5 = Out of range
1 30103-4 Voltage Input
Missing
-1…123 •••••Reports on all three phases.
-1 = Test not run. 0 = Test passed. 1 = Phase 1 missing 2 = Phase 2 missing 3 = Phase 3 missing 12 = Phase 1 and 2 missing 13 = Phase 1 and 3 missing 23 = Phase 2 and 3 missing 123 = All phases missing
2 30105-6 Voltage Input
Inverted
-1…123 •••••Reports on all three phases.
-1 = Test not run. 0 = Test passed. 1 = Phase 1 inverted 2 = Phase 2 inverted 3 = Phase 3 inverted 12 = Phase 1 and 2 inverted 13 = Phase 1 and 3 inverted 23 = Phase 2 and 3 inverted 123 = All phases inverted
68 Publication 1408-UM001B-EN-P - May 2008
Wiring Diagnostics Results
Powermonitor 1000 Data Tables Appendix A
Element No.
3 30107-8 Current Input
Modbus Address
Element Name Units Range
-1…123 •••••Reports on all three phases.
Missing
Description
TR1
TR2
EM1
EM2
EM3
-1 = Test not run. 0 = Test passed. 1 = Phase 1 missing 2 = Phase 2 missing 3 = Phase 3 missing 12 = Phase 1 and 2 missing 13 = Phase 1 and 3 missing 23 = Phase 2 and 3 missing 123 = All phases missing
4 30109-10 Current Input
Inverted
-1…123 •••••Reports on all three phases.
-1 = Test not run. 0 = Test passed. 1 = Phase 1 inverted 2 = Phase 2 inverted 3 = Phase 3 inverted 12 = Phase 1 and 2 inverted 13 = Phase 1 and 3 inverted 23 = Phase 2 and 3 inverted 123 = All phases inverted
5 30111-12 Voltage Rotation -1…132 •••••Reports on all three phases. The
reported sequence represents each phase. Example: 123 = Phase 1 then phase 2 then phase 3
-1 = Test not run 4 = Invalid rotation 1…132 designating phase and rotation.
6 30113-14 Current Rotation -1…321 •••••Reports on all three phases. The
reported sequence represents each phase. Example: 123 = Phase 1 then phase 2 then phase 3
-1 = Test not run 4 = Invalid rotation 1…321 designating phase and rotation.
7 30115-16 Voltage Phase 1
Angle
Degrees 0…359.99 •• •Shows the present phase angle
of this channel. Should always be 0 degrees for voltage phase 1.
8 30117-18 Voltage Phase 1
Magnitude
Volts 0…9,999,999 •• •Shows the present magnitude of
this phase.
9 30119-20 Voltage Phase 2
Angle
10 30121-22 Voltage Phase 2
Magnitude
11 30123-24 Voltage Phase 3
Angle
Publication 1408-UM001B-EN-P - May 2008 69
Degrees 0…359.99 •• •Shows the present phase angle
of this channel.
Volts 0…9,999,999 •• •Shows the present magnitude of
this phase.
Degrees 0…359.99 •• •Shows the present phase angle
of this channel.
Appendix A Powermonitor 1000 Data Tables
Wiring Diagnostics Results
Element No.
12 30125-26 Voltage Phase 3
13 30127-28 Current Phase 1
14 30129-30 Current Phase 1
15 30131-32 Current Phase 2
16 30133-34 Current Phase 2
17 30135-36 Current Phase 3
18 30137-38 Current Phase 3
19 30139-40 Degrees out of
Modbus Address
Element Name Units Range
Volts 0…9,999,999 •• •Shows the present magnitude of
Magnitude
Degrees 0…359.99 •• •Shows the present phase angle
Angle
Amperes 0…9,999,999 •• •Shows the present magnitude of
Magnitude
Degrees 0…359.99 •• •Shows the present phase angle
Angle
Amperes 0…9,999,999 •• •Shows the present magnitude of
Magnitude
Degrees 0…359.99 •• •Shows the present phase angle
Angle
Amperes 0…9,999,999 •• •Shows the present magnitude of
Magnitude
0…360 •••••When Status = 5, how many
range
Description
TR1
TR2
EM1
EM2
EM3
this phase.
of this channel.
this phase.
of this channel.
this phase.
of this channel.
this phase.
degrees out of range.
20 30141-42 Reserved 0 Reserved for future use
Volts, Amps, Frequency Results Parameters
CSP File No. F21 CIP Instance 14 No. of Elements 16 No. of Words 32 Data Type Float Data Access Read
Volts, Amps, Frequency Results
Element No.
Modbus Address
Element Name Range
TR1
TR2
EM1
EM2
Description
EM3
0 30201-2 L1 Current 0.000…9,999,999 •• •Phase 1 scaled RMS Current 1 30203-4 L2 Current 0.000…9,999,999 •• •Phase 2 scaled RMS Current 2 30205-6 L3 Current 0.000…9,999,999 •• •Phase 3 scaled RMS Current 3 30207-8 Average Current 0.000…9,999,999 •• •Average RMS Current 4 30209-10 L1-N Volts 0.000…9,999,999 •• •Phase 1 scaled RMS Voltage 5 30211-12 L2-N Volts 0.000…9,999,999 •• •Phase 2 scaled RMS Voltage
70 Publication 1408-UM001B-EN-P - May 2008
Volts, Amps, Frequency Results
Powermonitor 1000 Data Tables Appendix A
Element No.
Modbus Address
Element Name Range
TR1
TR2
EM1
EM2
Description
EM3
6 30213-14 L3-N Volts 0.000…9,999,999 •• •Phase 3 scaled RMS Voltage 7 30215-16 Average L-N Volts 0.000…9,999,999 •• •Averaged RMS Voltage 8 30217-18 L1-L2 Volts 0.000…9,999,999 •• •Line 1 to Line 2 Volts 9 30219-20 L2-L3 Volts 0.000…9,999,999 •• •Line 2 to Line 3 Volts 10 30221-22 L3-L1 Volts 0.000…9,999,999 •• •Line 3 to Line 1 Volts 11 30223-24 Average L-L Volts 0.000…9,999,999 •• •Average Line to Line Volts 12 30225-26 Frequency 40.0 Hz…70.0 Hz •• •Last frequency reading. 13 30227-28 Percent Current
Unbalance
14 30229-30 Percent Voltage
Unbalance
0.0…100.0 •• •Percent maximum deviation from
Ave. / Ave.
0.0…100.0 •• •Percent Maximum deviation from
Ave. / Ave.
15 30231-32 Metering Iteration 0…9,999,999 •• •Increments by 1 for each new
metering calculation.
Power Results Parameters
Power Results
Element No.
Modbus Address
Element Name Range
0 30301-2 L1 True Power
Factor
1 30303-4 L2 True Power
Factor
2 30305-6 L3 True Power
Factor
3 30307-8 3 Phase True
Power Factor
CSP File No. F22 CIP Instance 15 No. of Elements 17 No. of Words 34 Data Type Float Data Access Read
Description
TR1
TR2
EM1
EM2
EM3
-100.0…+100.0 ••Percent ratio between power and
apparent power. The value is
-100.0…+100.0 ••
signed to (+) leading and (-) lagging.
-100.0…+100.0 ••
-100.0…+100.0 ••
4 30309-10 L1 kWatts +/- 0.000…9,999,999 ••Line 1 kWatts 5 30311-12 L2 kWatts +/- 0.000…9,999,999 ••Line 2 kWatts
Publication 1408-UM001B-EN-P - May 2008 71
Appendix A Powermonitor 1000 Data Tables
Power Results
Element No.
6 30313-14 L3 kWatts +/- 0.000…9,999,999 ••Line 3 kWatts 7 30315-16 Total kWatts +/- 0.000…9,999,999 ••Total kWatts 8 30317-18 L1 kVAR +/- 0.000…9,999,999 ••Line 1 kVAR 9 30319-20 L2 kVAR +/- 0.000…9,999,999 ••Line 2 kVAR 10 30321-22 L3 kVAR +/- 0.000…9,999,999 ••Line 3 kVAR 11 30323-24 Total kVAR +/- 0.000…9,999,999 ••Total kVAR 12 30325-26 L1 kVA 0.000…9,999,999 ••Line 1 kVA 13 30327-28 L2 kVA 0.000…9,999,999 ••Line 2 kVA 14 30329-30 L3 kVA 0.000…9,999,999 ••Line 3 kVA 15 30331-32 Total kVA 0.000…9,999,999 ••Total kVA 16 30333-34 Metering Iteration 0…9,999,999 ••Increments by 1 for each new
Modbus Address
Element Name Range
IMPORTANT
TR1
TR2
EM1
EM2
Only total power values are returned in delta wiring modes.
Description
EM3
metering calculation.
Zeroes are returned for individual phase values.
Energy Results Parameters
CSP File No. F23 CIP Instance 16 No. of Elements 19 No. of Words 38 Data Type Float Data Access Read
Energy Results
Element No.
0 30401-2 Status 1 Count xM 0…9,999,999 •••Status 1 Count times 1,000,000 1 30403-4 Status 1 Count x1 0…999,999 •••Status 1 count times 1 2 30405-6 Status 2 Count xM 0…9,999,999 •••Status 2 Count times 1,000,000 3 30407-8 Status 2 Count x1 0…999,999 •••Status 2 count times 1
Modbus Address
Element Name Range
TR1
TR2
EM1
EM2
Description
EM3
72 Publication 1408-UM001B-EN-P - May 2008
Energy Results
Powermonitor 1000 Data Tables Appendix A
Element No.
Modbus Address
Element Name Range
TR1
TR2
EM1
EM2
Description
EM3
4 30409-10 GWh Fwd 0…9,999,999 •••Forward gigawatt hours 5 30411-12 kWatth Fwd 0.000…999,999 •••Forward kilowatt hours 6 30413-14 GWh Rev. 0…9,999,999 •••Reverse gigawatt hours 7 30415-16 kWatth Rev. 0.000…999.999 •••Reverse kilowatt hours 8 30417-18 GWh Net +/- 0…9,999,999 •••Net gigawatt hours 9 30419-20 kWatth Net +/- 0.000…999,999 •••Net kilowatt hours 10 30421-22 GVARH Fwd 0…9,999,999 ••Forward gigaVAR hours 11 30423-24 kVARh Fwd 0.000…999,999 ••Forward kiloVAR hours 12 30425-26 GVARH Rev. 0…9,999,999 ••Reverse gigaVAR hours 13 30427-28 kVARh Rev. 0.000…999,999 ••Reverse kiloVAR hours 14 30429-30 GVARH Net +/- 0…9,999,999 ••Net gigaVAR hours 15 30431-32 kVARh Net +/- 0.000…999,999 ••Net kiloVAR hours 16 30433-34 GVAh Net 0…9,999,999 ••Net gigaVA hours 17 30435-36 kVAh 0.000…999,999 ••Net kiloVA hours 18 30437-38 Metering Iteration 0…9,999,999 •••Increments by 1 for each new
metering calculation.
Demand Results Parameters
CSP File No. F24 CIP Instance 17 No. of Elements 9 No. of Words 18 Data Type Float Data Access Read
Demand Results
Element No.
Modbus Address
Element Name Range
TR1
TR2
EM1
EM2
Description
EM3
0 30501-2 kWatt Demand +/- 0.000…9,999,999 ••The average real power during the
last demand period.
1 30503-4 kVAR Demand +/- 0.000…9,999,999 ••The average reactive power during
the last demand period.
2 30505-6 kVA Demand 0.000…9,999,999 ••The average apparent power during
the last demand period.
Publication 1408-UM001B-EN-P - May 2008 73
Appendix A Powermonitor 1000 Data Tables
Demand Results
Element No.
Modbus Address
Element Name Range
TR1
TR2
EM1
EM2
Description
EM3
3 30507-8 Demand PF -100.0…+100.0 ••The average demand for PF during
the last demand period.
4 30509-10 Projected kWatt
Demand
5 30511-12 Projected kVAR
Demand
6 30513-14 Projected kVA
Demand
7 30515-16 Elapsed Demand
Period Time
+/- 0.000…9,999,999 ••The projected total real power for
the current period.
+/- 0.000…9,999,999 ••The projected total reactive power
for the current period.
0.000…9,999,999 ••The projected total apparent power
for the current period.
0.00…99.99 ••The amount of time that has
elapsed during the current period.
8 30517-18 Metering Iteration 0…9,999,999 ••Increments by 1 for each new
metering calculation.
Unit Status Log Results Parameters
CSP File No. N25 CIP Instance 18 Applies to All models No. of Elements 13 No. of Words 13 Data Type Integer Data Access Read
Unit Status Log Results
Element No.
0 30601 Status Record Internal
Modbus Address
Element Name Range Description
1…50 Used to verify record sequence when returning multiple
Identifier
records. 1 30602 Timestamp Year of record - The year when the record was recorded. 2 30603 Timestamp Month/Day - The month and day when the record was recorded. 3 30604 Timestamp Hour/Minute - The hour and minute when the record was recorded. 4 30605 Timestamp
- The seconds and hundredths when the record was recorded.
Seconds/Hundredths 5 30606 Status Event Type 0…512 Indicates the type of status event that has occurred. 6 30607 General Code 0…4096 Indicates general information about the status event. 7 30608 Information Code 0…256 Indicates specific information about the status event.
74 Publication 1408-UM001B-EN-P - May 2008
Unit Status Log Results
Powermonitor 1000 Data Tables Appendix A
Element No.
Modbus Address
Element Name Range Description
8 30609 Reserved 0 Reserved for future use. 9 30610 Reserved 0 Reserved for future use. 10 30611 Reserved 0 Reserved for future use. 11 30612 Reserved 0 Reserved for future use. 12 30613 Reserved 0 Reserved for future use.
Publication 1408-UM001B-EN-P - May 2008 75
Appendix A Powermonitor 1000 Data Tables
Unit Status Log Codes
Status Event Type
Event # General Code (Decimal) Code # Information Code (Decimal) Code #
(Decimal)
Self Test Status 1 Pass 0
Flash Memory 1 Overall Status 1
SRAM 2 Failed Read/Write Test 1 NVRAM 4 Failed Read/Write Test 1 SPI Interface 8 SPI Device Not Responding 1
Real Time Clock 16 Real Time Clock Failed 1
Watchdog Timer 32 Watchdog Time Out 1 Metering 64 Metering Status Failed 1
Boot Code Checksum 2 Application Code Checksum 4 Calibration Data CRC 8 No Calibration Data 16 Wrong Application FRN 32 Invalid Model Type 64 WIN Mismatch 128 Missing Upgrade Block 256
SPI Interface Failed 2
Real Time Clock not Set 2
LCD Interface 128 LCD Interface Failure 1 Serial Communications 256 Serial Communication Port Failed 1 Ethernet Communications 512 Ethernet Communications Port Failed 1
Modbus Stack Initialization Failed 2 Demand Broadcast Thread Init Failed 4 SNTP Thread Init Failed 8
Input Over Range 1024 Input Over Range Voltage 1
Input Over Range Current 2
Voltage Phase Loss 2048 Voltage Channel 1 Loss 1
Voltage Channel 2 Loss 2 Voltage Channel 3 Loss 4
Process Error 4096
76 Publication 1408-UM001B-EN-P - May 2008
Unit Status Log Codes
Powermonitor 1000 Data Tables Appendix A
Status Event Type
Event # General Code (Decimal) Code # Information Code (Decimal) Code #
(Decimal)
Configuration Changed 2 Clock Set 1
Status Input Counter Set 2 Status Input 1 1
Factory Defaults Restored 4 Energy Register Set 8 Wh Register 1
Terminal Locked 16 Terminal Unlocked 32
Log Cleared or Set 4 Min/Max Log Cleared 1
Energy Log Cleared 2 LoadFactor Log Cleared 4 TOU Log Cleared 8
KYZ Forced 8 KYZ Forced On 1
KYZ Forced Off 2
Status Input Activated 16 Status Input 1 1
Status Input 2 2 All Status Input 4
VARh Register 2 VAh Register 4 All Energy Registers Cleared 8
Status Input 2 2
Status Input Deactivated 32 Status Input 1 1
Status Input 2 2
Energy Register Rollover 64 Wh Register 1
VARh Register 2 VAh Register 4 Status Input 1 Register 8
Status Input 2 Register 16 Device Power Up 128 Device Power Down 256 Missed External Demand
512
Sync
Publication 1408-UM001B-EN-P - May 2008 77
Appendix A Powermonitor 1000 Data Tables
Energy Log Results
Energy Log Results Parameters
CSP File No. F26 CIP Instance 19 No. of Elements 21 No. of Words 42 Data Type Float Data Access Read
Element No.
0 30701-2 Internal Record
Modbus Address
Element Name Range
TR1
TR2
EM1
•••
EM2
Description
EM3
Identifier.
1 30703-4 Timestamp Year of
record
2 30705-6 Timestamp
- •••The date and time when the
record was recorded.
- •••
Month/Day
3 30707-8 Timestamp
- •••
Hour/Minute
4 30709-10 Timestamp
- •••
Seconds/
Hundredths
5 30711-12 Status 1 Count xM 0…9,999,999 •••Status 1 Count times
1,000,000
6 30713-14 Status 1 Count x1 0…999,999 •••Status 1 count times 1 7 30715-16 Status 2 Count xM 0…9,999,999 •••Status 2 Count times
1,000,000
8 30717-18 Status 2 Count x1 0…999,999 •••Status 2 count times 1 9 30719-20 GWh Net +/- 0…9,999,999 •••Net gigawatt hours 10 30721-22 kWatth Net +/- 0.000…999,999 •••Net kilowatt hours 11 30723-24 GVARH Net +/- 0…9,999,999 ••Net gigaVAR hours 12 30725-26 kVARh Net +/- 0.000…999,999 ••Net kiloVAR hours 13 30727-28 GVAh Net 0…9,999,999 ••Net gigaVA hours 14 30729-30 kVAh Net 0.000…999,999 ••Net kiloVA hours 15 30731-32 kWatt Demand +/- 0.000…9,999,999 ••The average real power during
the last demand period.
16 30733-34 kVAR Demand +/- 0.000…9,999,999 ••The average reactive power
during the last demand period.
78 Publication 1408-UM001B-EN-P - May 2008
Energy Log Results
Powermonitor 1000 Data Tables Appendix A
Element No.
Modbus Address
Element Name Range
TR1
TR2
EM1
EM2
Description
EM3
17 30735-36 kVA Demand 0.000…9,999,999 ••The average apparent power
during the last demand period.
18 30737-38 Demand PF -100.0…+100.0 ••The average demand for PF
during the last demand period.
19 30739-40 Reserved 0 Reserved for future use. 20 30741-42 Reserved 0 Reserved for future use.
Write Error Status Results Parameters
CSP File No. N27 CIP Instance 20 Applies to All Models No. of Elements 3 No. of Words 3 Data Type Integer Data Access Read
Write Error Status Results
Element
No.
0 30801 Table Number or
Modbus
Address
Element Name Range Description
All Write Enabled Tables Indicates the last table that was written.
Instance
1 30802 Offending Element Length of current table - 1 If the most recent write was successful this
returns a (-1). If the write was unsuccessful this is the first rejected element in the table write.
2 30803 Terminal Lock On 0…1 If a write was made to a table that has elements
that are locked this value is 1.
Publication 1408-UM001B-EN-P - May 2008 79
Appendix A Powermonitor 1000 Data Tables
Unit Run Status Results
Unit Run Status Results Parameters
CSP File No. N28 CIP Instance 21 Applies to All models No. of Elements 25 No. of Words 25 Data Type Integer Data Access Read
Element No.
Modbus Address
Element Name Range Description
0 30901 Bulletin Number 1408 Always returns 1408 1 30902 Series Letter 0…8 Indicates the unit hardware series letter, for
example. 0 = A 1 = B . . 8 = H
2 30903 Catalog Device Type 0…4 The catalog number type of this device.
0 = TR1 1 = TR2 2 = EM1 3 = EM2 4 = EM3
3 30904 Communication Type 0…1 The communication type of this device
0 = Serial only
1 = both serial and Ethernet 4 30905 Application FRN - The current firmware revision 5 30906 Boot Code FRN - The current boot code revision 6 30907 Default Device ID 1…247 A semi-unique number assigned to a device at the
time it is manufactured. Used for out of the box
communications over DF1 and Ethernet. 7 30908 Accuracy Class 0…3 Indicates the revenue metering accuracy class of
the power monitor as it is shipped from the
factory.
0 = No Class Designation
1 = Class 1
2 = Class 0.5
3 = Class 0.2
80 Publication 1408-UM001B-EN-P - May 2008
Unit Run Status Results
Powermonitor 1000 Data Tables Appendix A
Element No.
Modbus Address
Element Name Range Description
8 30909 Overall Status 0…16383 0 indicates normal operation. Each bit indicates a
different fault condition. Bit 0 = Flash Memory Bit 1 = SRAM Bit 2 = NVRAM Bit 3 = SPI Interface Bit 4 = Real Time Clock Bit 5 = Watchdog Timer Bit 6 = Metering Bit 7 = LCD Interface Bit 8 = Serial Communications Bit 9 = Ethernet Communications Bit 10 = Error Log Full
9 30910 Flash Memory 0…511 0 indicates normal operation. Status bits are
Bit 0 = Overall status Bit 1 = Boot code checksum Bit 2 = Application code checksum Bit 3 = Calibration data CRC Bit 4 = No calibration data Bit 5 = Wrong application FRN Bit 6 = Invalid model type Bit 7 = WIN mismatch Bit 8 = missing upgrade block
10 30911 SRAM 0…1 0 indicates normal operation.
Bit 0 = Read/write test
11 30912 NVRAM 0…1 0 indicates normal operation.
Bit 0 = Read/write test
12 30913 SPI Interface 0…1 0 indicates normal operation.
Bit 0 = SPI device not responding
13 30914 Real Time Clock 0…3 0 indicates normal operation.
Bit 0 = RTC status Bit 1 = Time Zone Set Failed
14 30915 Watchdog Timer 0…1 0 indicates normal operation.
Bit 0 = Watchdog time out
15 30916 Metering 0…1 0 indicates normal operation.
Bit 0 = Metering status
16 30917 LCD Interface 0…1 0 indicates normal operation.
Bit 0 = LCD Interface status
17 30918 Serial Communications 0…1 0 indicates normal operation.
Bit 0 = Serial Interface status
Publication 1408-UM001B-EN-P - May 2008 81
Appendix A Powermonitor 1000 Data Tables
Unit Run Status Results
Element No.
Modbus Address
Element Name Range Description
18 30919 Ethernet Communications 0…511 0 indicates normal operation.
Bit 0 = Ethernet Communications status
Bit 1 = SNTP Server timeout status
Bit 2 = Duplicate IP Address status
Bit 3 = Invalid IP/Netmask address
Bit 4 = Invalid gateway address
Bit 5 = Invalid SNTP time server address
Bit 6 = Modbus stack run status
Bit 7 = Demand broadcast thread run status
Bit 8 = SNTP thread run status 19 30920 Input Over Range 0…3 0 indicates normal operation.
Bit 0 = Voltage Input over range
Bit 1 = Current Input over range 20 30921 Phase Loss Detection 0…7 0 Indicates normal running condition.
Bit 0 = Loss of phase A
Bit 1 = Loss of phase B
Bit 2 = Loss of phase C 21 30922 Configuration Locked 0…1 Reports 1 if configuration lock is applied. 22 30923 Password Accepted 0…1 1 indicates the password is verified and active 23 30924 Error Recorded 0 Is incremented by 1 when an internal error
happens 24 30925 Troubleshooting Times
Remaining
0…30 Remaining times for troubleshooting mode.
82 Publication 1408-UM001B-EN-P - May 2008
Min/Max Log Results
Powermonitor 1000 Data Tables Appendix A
Min/Max Log Results Parameters
CSP File No. F29 CIP Instance 22 No. of Elements 11 No. of Words 22 Data Type Float Data Access Read
Element No.
0 31001-2 Parameter Being
Modbus Address
Element Name Range
1…35 •• •Indicates the Parameter Number (See
Returned
1 31003-4 MIN Value +/-
0.000…9,999 ,999
2 31005-6 MAX Value +/-
0.000…9,999 ,999
3 31007-8 Timestamp Year of
MIN
4 31009-10 Timestamp
Month/Day of MIN
5 31011-12 Timestamp
Hour/Minute of MIN
6 31013-14 Timestamp Seconds/
Hundredths of MIN
7 31015-16 Timestamp Year of
MAX
8 31017-18 Timestamp
Month/Day of MAX
9 31019-20 Timestamp
Hour/Minute of MAX
10 31021-22 Timestamp Seconds/
Hundredths of MAX
Description
TR1
TR2
EM1
EM2
EM3
Min/Max Parameter List).
•• The minimum value recorded for
parameter being returned since the last clear command.
•• The maximum value recorded for
parameter being returned since the last clear command.
•• The year when the MIN value was
recorded.
•• The month and day when the MIN
value was recorded.
•• The hour and minute when the MIN
value was recorded.
•• The seconds and hundredths when the
MIN value was recorded.
•• The year when the MAX value was
recorded.
•• The month and day when the MAX
value was recorded.
•• The hour and minute when the MAX
value was recorded.
•• The seconds and hundredths when the
MAX value was recorded.
Publication 1408-UM001B-EN-P - May 2008 83
Appendix A Powermonitor 1000 Data Tables
Min/Max Parameter List
No. Parameter TR1 TR2 EM3
1 L1 Current ••• 2 L2 Current ••• 3 L3 Current ••• 4 Average Current ••• 5L1-N Volts ••• 6L2-N Volts ••• 7L3-N Volts ••• 8 Average L-N Volts ••• 9 L1-L2 Volts ••• 10 L2-L3 Volts ••• 11 L3-L1 Volts ••• 12 Average L-L Volts ••• 13 Frequency ••• 14 Percent Current Unbalance ••• 15 Percent Voltage Unbalance ••• 16 L1 True Power Factor •• 17 L2 True Power Factor •• 18 L3 True Power Factor •• 19 3 Phase True Power Factor •• 20 L1 kWatts •• 21 L2 kWatts •• 22 L3 kWatts •• 23 Total kWatts •• 24 L1 kVAR •• 25 L2 kVAR •• 26 L3 kVAR •• 27 Total kVAR •• 28 L1 kVA •• 29 L2 kVA •• 30 L3 kVA •• 31 Total kVA •• 32 kWatt Demand
84 Publication 1408-UM001B-EN-P - May 2008
Powermonitor 1000 Data Tables Appendix A
Min/Max Parameter List
No. Parameter TR1 TR2 EM3
33 kVAR Demand 34 kVA Demand 35 PF Demand
Load Factor Log Results Parameters
CSP File No. F30 CIP Instance 23 No. of Elements 14 No. of Words 28 Data Type Float Data Access Read
Load Factor Log Results
Element No.
Modbus Address
Element Name Range
Description
TR1
TR2
EM1
EM2
EM3
0 31101-2 Record Number 1…13 ••The record number of this data. 1 31103-4 End Date
- ••The date that this record was stored.
yy/mm/dd
2 31105-6 Elapsed Time 0.000…
9,999,999
••Amount of time (in hours) that has
elapsed since the last clear of the peak and average values. Updated at the end of each demand interval.
3 31107-8 Peak Demand
kWatts
+/-
0.000…9,999, 999
••The largest magnitude demand for
kwatts that occurred over all of the demand intervals since the last clear command or auto-clear day.
4 31109-10 Average Demand
kWatts
+/-
0.000…9,999, 999
••A running average of demand for
kwatts from the end of each demand period since the last clear command or auto-clear day.
5 31111-12 Load Factor
kWatts
0…100% ••Average Demand kW / Peak Demand
kW. This is a demand management metric that indicates how ‘spiky’ (or ‘level’) a load is over a period of time (usually 1 month). A value approaching 100% indicates a constant load.
Publication 1408-UM001B-EN-P - May 2008 85
Appendix A Powermonitor 1000 Data Tables
Load Factor Log Results
Element No.
Modbus Address
Element Name Range
6 31113-14 Peak Demand
kVAR
+/- 0.000… 9,999,999
TR1
TR2
EM1
EM2
••The largest magnitude demand for
Description
EM3
kVAR that occurred over all of the demand intervals since the last clear command or auto-clear day.
7 31115-16 Average Demand
kVAR
+/- 0.000… 9,999,999
••A running average of demand for kVAR
from the end of each demand period since the last clear command or auto-clear day.
8 31117-18 Load Factor kVAR 0…100% ••Average Demand kVAR / Peak Demand
kVAR. This is a demand management metric that indicates how ‘spiky’ (or ‘level’) a load is over a period of time (usually 1 month). A value approaching 100% indicates a constant load.
9 31119-20 Peak Demand kVA 0.000…
9,999,999
••The largest magnitude demand for kVA
that occurred over all of the demand intervals since the last clear command or auto-clear day.
10 31121-22 Average Demand
kVA
0.000… 9,999,999
••A running average of demand for kVA
from the end of each demand period since the last clear command or auto-clear day.
11 31123-24 Load Factor kVA 0…100% ••Average Demand kVA / Peak Demand
kVA. This is a demand management metric that indicates how ‘spiky’ (or ‘level’) a load is over a period of time (usually 1 month). A value approaching 100% indicates a constant load.
12 31125-26 Reserved 0 Reserved for Future Use 13 31127-28 Reserved 0 Reserved for Future Use
86 Publication 1408-UM001B-EN-P - May 2008
Time of Use Log Results - Real Energy and Demand Parameters
CSP File No. F31 CIP Instance 24 No. of Elements 12 No. of Words 24 Data Type Float Data Access Read
Time of Use Log Results - Real Energy and Demand
Powermonitor 1000 Data Tables Appendix A
Element No.
Modbus Address
Element Name Range
TR1
TR2
EM1
EM2
Description
EM3
0 31201-2 Record Number 1…13 •••The record number of the log. Record 0 is
always the current record before being logged.
1 31203-4 Time Stamp Start
- •••The Date this record was started.
Date (yy/mm/dd)
2 31205-6 Time Stamp End
- •••The Date this record was ended.
Date (yy/mm/dd)
3 31207-8 Off Peak GWh
Net
4 31209-10 Off Peak kWh
Net
5 31211-12 Off Peak kW
Demand
6 31213-14 Mid Peak GWh
Net
7 31215-16 Mid Peak kWh
Net
8 31217-18 Mid Peak kW
Demand
9 31219-20 On Peak GWh
Net
+/- 0… 9,999,999
+/- 0.000… 999,999
+/- 0.000… 9,999,999
+/- 0… 9,999,999
+/- 0.000… 999,999
+/- 0.000… 9,999,999
+/- 0.000… 9,999,999
•••Net Off Peak giga watt hours
•••Net Off Peak kilo watt hours
•••Off Peak Demand for kilo watts
•••Net Mid Peak giga watt hours
•••Net Mid Peak kilowatt hours
•••Mid Peak Demand for kilo watts
•••Net On Peak giga watt hours
10 31221-22 On Peak kWh Net +/- 0…
•••Net On Peak kilo watt hours
999,999
11 31223-24 On Peak kW
Demand
Publication 1408-UM001B-EN-P - May 2008 87
+/- 0.000… 9,999,999
••On Peak Demand for kilo watts
Appendix A Powermonitor 1000 Data Tables
Time of Use Log Results - Reactive Energy and Demand Parameters
CSP File No. F32 CIP Instance 25 No. of Elements 12 No. of Words 24 Data Type Float Data Access Read
Time of Use Log Results - Reactive Energy and Demand
Element No.
Modbus Address
Element Name Range
TR1
TR2
EM1
EM2
Description
EM3
0 31301-2 Record Number 1…13 •••The record number of the log. Record 0 is
always the current record before being logged.
1 31303-4 Time Stamp
- •••The Date this record was started.
Start Date (yy/mm/dd)
2 31305-6 Time Stamp End
- •••The Date this record was ended.
Date (yy/mm/dd)
3 31307-8 Off Peak GVARH
Net
4 31309-10 Off Peak kVARh
Net
5 31311-12 Off Peak kVAR
Demand
6 31313-14 Mid Peak
GVARH Net
7 31315-16 Mid Peak kVARh
Net
8 31317-18 Mid Peak kVAR
Demand
+/- 0… 9,999,999
+/- 0.000… 999,999
+/- 0.000… 9,999,999
+/- 0… 9,999,999
+/- 0.000… 999,999
+/- 0.000… 9,999,999
•••Net Off peak giga VAR hours
•••Net Off Peak kilo VAR hours
•••Off Peak Demand for kilo VAR
•••Net Mid Peak giga VAR hours
•••Net Mid Peak kilo VAR hours
•••Mid Peak Demand for kilo VAR
9 31319-20 On Peak GVARH
Net
10 31321-22 On Peak kVARh
Net
11 31323-24 On Peak kVAR
Demand
88 Publication 1408-UM001B-EN-P - May 2008
+/- 0.000… 9,999,999
+/- 0… 999,999
+/- 0.000… 9,999,999
•••Net On Peak giga VAR hours
•••Net On Peak kilo VAR hours
••On Peak Demand for kilo VAR
Time of Use Log Results - Apparent Energy and Demand Parameters
CSP File No. F33 CIP Instance 26 No. of Elements 12 No. of Words 24 Data Type Float Data Access Read
Time of Use Log Results - Apparent Energy and Demand
Powermonitor 1000 Data Tables Appendix A
Element No.
Modbus Address
Element Name Range
TR1
TR2
EM1
EM2
Description
EM3
0 31401-2 Record Number 1…13 •••The record number of the log. Record 0 is
always the current record before being logged.
1 31403-4 Time Stamp Start
- •••The Date this record was started.
Date (yy/mm/dd)
2 31405-6 Time Stamp End
- •••The Date this record was ended.
Date (yy/mm/dd)
3 31407-8 Off Peak GVAh
Net
4 31409-10 Off Peak kVAh
Net
5 31411-12 Off Peak kVA
Demand
6 31413-14 Mid Peak GVAh
Net
7 31415-16 Mid Peak kVAh
Net
8 31417-18 Mid Peak kVA
Demand
9 31419-20 On Peak GVAh
Net
+/- 0… 9,999,999
+/- 0.000… 999,999
+/- 0.000… 9,999,999
+/- 0… 9,999,999
+/- 0.000… 999,999
+/- 0.000… 9,999,999
+/- 0.000… 9,999,999
•••Net Off peak giga VA hours
•••Net Off Peak kilo VA hours
•••Off Peak Demand for kilo VA
•••Net Mid Peak giga VA hours
•••Net Mid Peak kilo VA hours
•••Mid Peak Demand for kilo VA
•••Net On Peak giga VA hours
10 31421-22 On Peak kVAh
Net
11 31423-24 On Peak kVA
Demand
Publication 1408-UM001B-EN-P - May 2008 89
+/- 0… 999,999
+/- 0.000… 9,999,999
•••Net On Peak kilo VA hours
••On Peak Demand for kilo VA
Appendix A Powermonitor 1000 Data Tables
Catalog Number and WIN
Catalog Number and WIN Parameters
CSP File No. N34 CIP Instance 27 Applies to All models No. of Elements 19 No. of Words 19 Data Type Integer Data Access Read
Element No.
Modbus Address
Element Name Range Description
0 31501 Catalog # text char pair #1 0…32767 Contains the product number (example: 1408-EM3A-485A, but with 1 31502 Catalog # text char pair #2 2 31503 Catalog # text char pair #3 3 31504 Catalog # text char pair #4
out the dashes). A read of this table returns the catalog # as 4 integers: each integer contains a character pair. For each character pair, character 1=integer/256 and character 2 = remainder of integer/256.
4 31505 Catalog # text char pair #4 5 31506 Catalog # text char pair #4 6 31507 Reserved 0 Reserved for future use. 7 31508 Hardware Series 0…25 Indicates the product series letter.
For example, 0=A, 1=B, 8 31509 WIN # text char pair #1 0…32767 Contains the product WIN(Warranty Identification Number). This is 9 31510 WIN # text char pair #2 10 31511 WIN# text char pair #3
the same alpha-numeric string that can be found on the master
module label (example: 21AW0AT5HO). 5 integers each contains two
characters as displayed by the Catalog parameter method. 11 31512 WIN# text char pair #4
12 31513 WIN# text char pair #5 13 31514 Reserved 0 Reserved for future use. 14 31515 Reserved 0 Reserved for future use. 15 31516 Original Model 0
10 This number represents the catalog number type.
0 = TR1
1 = TR2
2 = EM1
3 = EM2
4 = EM3
5 through 10 = Reserved
90 Publication 1408-UM001B-EN-P - May 2008
Catalog Number and WIN
Powermonitor 1000 Data Tables Appendix A
Element No.
Modbus Address
Element Name Range Description
16 31517 Current Model 010 The current model of the product. This can be the same as the
original model (if no upgrades have been performed). 17 31518 Reserved 0 Reserved for future use. 18 31519 Reserved 0 Reserved for future use.
Single Element Password Write Parameters
CSP File No. N35 CIP Instance 28 Applies to All models No. of Elements 1 No. of Words 1 Data Type Integer Data Access Write
Single Element Password Write
Element No.
Modbus Address
Element Name
Range Description
0 40901 Password 0…9999 A write of this table allows any configuration parameter to be written as a single
element or poke. The password stays active for 30 minutes and resets to another 30 minutes when a single element is configured.
Publication 1408-UM001B-EN-P - May 2008 91
Appendix A Powermonitor 1000 Data Tables
User Configured Table Setup
User Configurable Table Setup Parameters
CSP File No. N36 CIP Instance 29 Applies to EM3 only No. of Elements 17 No. of Words 17 Data Type Integer Data Access Read/Write
Element No.
Modbus Address
Element Name Default Value Range Description
0 41001 Password 0 0…9999 Required for configuration,
returns -1. 1 41002 Selection for Parameter #1 29 (L1 Current) 0…110 2 41003 Selection for Parameter #2 30 (L2 Current) 3 41004 Selection for Parameter #3 31 (L3 Current) 4 41005 Selection for Parameter #4 37 (L1-L2 Voltage) 5 41006 Selection for Parameter #5 38 (L2-L3 Voltage) 6 41007 Selection for Parameter #6 39 (L3-L1 Voltage) 7 41008 Selection for Parameter #7 41 (Frequency) 8 41009 Selection for Parameter #8 52 (Total Real Power) 9 41010 Selection for Parameter #9 56 (Total Reactive Power) 10 41011 Selection for Parameter #10 60 (Total Apparent Power) 11 41012 Selection for Parameter #11 48 (3 Phase True Power Factor) 12 41013 Selection for Parameter #12 70 (Real Energy Net (kWh)) 13 41014 Selection for Parameter #13 62 (Status 1 Count x1) 14 41015 Selection for Parameter #14 64 (Status 2 Count x1) 15 41016 Selection for Parameter #15 79 (Real Power Demand) 16 41017 Selection for Parameter #16 8 (Status Input States)
92 Publication 1408-UM001B-EN-P - May 2008
Parameters for Configurable Table
Parameter No. Parameter Name Description
0 None No Parameter.
Powermonitor 1000 Data Tables Appendix A
1 Date: Year Refer to Date and Time Configuration 2 Date: Month 3 Date: Day 4 Time: Hour 5 Time: Minute 6 Time: Seconds 7 Time: Hundredths 8 Status Input States Refer to Discrete Results
table. 9 Output Word 10 Wiring Status Refer to Wiring Diagnostics Results 11 Voltage Input Missing 12 Voltage Input Inverted 13 Current Input Missing 14 Current Input Inverted 15 Voltage Rotation 16 Current Rotation 17 Voltage Phase 1 Angle 18 Voltage Phase 1 Magnitude
table.
table.
19 Voltage Phase 2 Angle 20 Voltage Phase 2 Magnitude 21 Voltage Phase 3 Angle 22 Voltage Phase 3 Magnitude 23 Current Phase 1 Angle 24 Current Phase 1 Magnitude 25 Current Phase 2 Angle 26 Current Phase 2 Magnitude 27 Current Phase 3 Angle 28 Current Phase 3 Magnitude 29 L1 Current Refer to Volts, Amps, Frequency Results
table. 30 L2 Current 31 L3 Current 32 Average Current 33 L1-N Volts
Publication 1408-UM001B-EN-P - May 2008 93
Appendix A Powermonitor 1000 Data Tables
Parameters for Configurable Table
Parameter No. Parameter Name Description
34 L2-N Volts Refer to Volts, Amps, Frequency Results table. 35 L3-N Volts 36 Average L-N Volts 37 L1-L2 Volts 38 L2-L3 Volts 39 L3-L1 Volts 40 Average L-L Volts 41 Frequency 42 Percent Current Unbalance 43 Percent Voltage Unbalance 44 Metering Iteration 45 L1 True Power Factor Refer to Power Results
table. 46 L2 True Power Factor 47 L3 True Power Factor 48 3 Phase True Power Factor 49 L1 kWatts 50 L2 kWatts 51 L3 kWatts 52 Total kWatts 53 L1 kVAR 54 L2 kVAR 55 L3 kVAR 56 Total kVAR 57 L1 kVA 58 L2 kVA 59 L3 kVA 60 Total kVA 61 Status 1 Count xM Refer to Energy Results 62 Status 1 Count x1 63 Status 2 Count xM 64 Status 2 Count x1 65 GWh Fwd 66 kWatth Fwd
table.
67 GWh Rev. 68 kWatth Rev. 69 GWh Net
94 Publication 1408-UM001B-EN-P - May 2008
Parameters for Configurable Table
Parameter No. Parameter Name Description
70 kWatth Net Refer to Energy Results table. 71 GVARH Fwd 72 kVARh Fwd 73 GVARH Rev. 74 kVARh Rev. 75 GVARH Net 76 kVARh Net 77 GVAh Net 78 kVAh 79 kWatt Demand Refer to Demand Results
table. 80 kVAR Demand 81 kVA Demand 82 Demand PF
Powermonitor 1000 Data Tables Appendix A
83 Projected kWatt Demand 84 Projected kVAR Demand 85 Projected kVA Demand 86 Elapsed Demand Period Time 87 Bulletin Number Refer to Unit Run Status Results 88 Series Letter 89 Catalog Device Type 90 Communication Type 91 Application FRN 92 Boot Code FRN 93 Default Device ID 94 Accuracy Class 95 Overall Status 96 Flash Memory 97 SRAM 98 NVRAM 99 SPI Interface 100 Real Time Clock 101 Watchdog Timer 102 Metering
table.
103 LCD Interface 104 Serial Communications 105 Ethernet Communications
Publication 1408-UM001B-EN-P - May 2008 95
Appendix A Powermonitor 1000 Data Tables
Parameters for Configurable Table
Parameter No. Parameter Name Description
106 Input Over Range Refer to Unit Run Status Results table. 107 Phase Loss Detection 108 Terminal Locked 109 Password Accepted 110 Error Recorded
96 Publication 1408-UM001B-EN-P - May 2008

Index

A
additional resources 7 advanced configuration analog input configuration
47
45, 46, 92
B
before you begin 7
C
catalog number and WIN 90 command table communications command summary
61
15
15
DH485 Modbus RTU serial optional EtherNet/IP optional Modbus/TCP Ethernet serial DF1 full-duplex slave serial DF1 half-duplex slave
communications overview
16
15
16
15
15
10
ethernet serial
controller interface table
11
10
66
D
data and time configuration 57 data table
access
13
addressing data format
data tables
advanced configuration analog input configuration catalog number and WIN command table controller interface table data and time configuration demand results discrete results energy log results energy results ethernet configuration load factor log results log configuration log request table min/max log results min/max parameter list power results serial RS-485 configuration
13
14
43
47
45, 46, 92
90
61
66
57 73 67
78
72
52
85 58 64
83
84
71
51
single element password write time of use log results apparent energy
and demand
time of use log results reactive energy
and demand
time of use log results real energy and
demand unit run status results unit status log results volts, amps, frequency results wiring diagnostics results write error status results
demand results discrete results
73
67
89
88
87
80
74
68
79
E
energy log results 78 energy results ethernet communications
EtherNet/IP protocol Modbus TCP Protocol
ethernet configuration explicit messaging
read write single or multiple elements RSLogix5 message setup PLC5 or SLC
RSLogix500 message setup PLC5 or SLC
RSLogix5000 message configuration
RSLogix5000 message setup CIP generic
setup
72
11
12
12
52
17
typed read write
typed read write
PLC5 or SLC typed read write
20
26
23
17
L
load factor log results 85 log configuration log request table
58
64
M
memory organization 13 min/max log results min/max parameter list
83
84
O
overview 9
P
power results 71
91
70
17
18
Publication 1408-UM001B-EN-P - May 2008 97
Index
R
reading logs 29
log data table methodology
RSLinx drivers configuration
29
33
DF1 full-duplex DF1 half-duplex slave EtherNet/IP devices driver EtherNet/IP EtherNet/IP drivers
RSLinx OPC server setup
OPC topic
34
33
35
35
35
S
safety 9 SCADA applications serial communications serial RS-485 port configuration single element password write
33
10
51
91
35
T
time of use log results apparent energy
and demand
time of use log results reactive energy
and demand
time of use log results real energy and
demand
time zone information
89
88
87
54
U
unit run status results 80 unit status log results using communications
74
10
V
volts, amps, frequency results 70
W
wiring diagnostics results 68 write error status results
79
98 Publication 1408-UM001B-EN-P - May 2008
Rockwell Automation Support
Rockwell Automation provides technical information on the Web to assist you in using its products. At http://support.rockwellautomation.com find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.
For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer TechConnect support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://support.rockwellautomation.com
, you can
.
Installation Assistance
If you experience a problem within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your product up and running.
United States 1.440.646.3434
Monday – Friday, 8am – 5pm EST
Outside United States
Please contact your local Rockwell Automation representative for any technical support issues.
New Product Satisfaction Return
Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.
United States Contact your distributor. You must provide a Customer Support case
number (call the phone number above to obtain one) to your distributor in order to complete the return process.
Outside United States
Please contact your local Rockwell Automation representative for the return procedure.
Publication 1408-UM001B-EN-P - May 2008 100 PN 40055-250-02(1)
Supersedes Publication 1408-UM001A-EN-P - June 2006 Copyright © 2008 Rockwell Automation, In c. All rights reserved. Printed in the U.S.A.
Loading...