Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety
Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1
your local Rockwell Automation® sales office or online at http://www.rockwellautomation.com/literature/
important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference,
and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment
must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the
use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
available from
) describes some
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment,
which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.
Identifies information that is critical for successful application and understanding of the product.
Allen-Bradley, Rockwell Software, Rockwell Automation, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Summary of Changes
This manual contains new and updated information. Changes throughout this
revision are marked by change bars, as shown to the right of this paragraph.
New and Updated
Information
This table contains the changes made to this revision.
TopicPage
Updated label on the dimension diagrams14
Updated wire temperature rating15
Updated chassis ground wire requirements20
Added Cross Current Compensation entity parameters to the
Generator Current Sensing table
Added Load Share entity parameters to the Metering table205
Updated the Zone 2 Certification information in the Agency
Certifications table
198
206
Rockwell Automation Publication 1407-UM001G-EN-P - April 20133
Summary of Changes
Notes:
4Rockwell Automation Publication 1407-UM001G-EN-P - April 2013
The information in this manual applies to the 1407-CGCM module, Series C,
Revision D, with host firmware revision 4.9 and ControlNet firmware revision
1.11. The manual notes differences with earlier versions of the product where
they occur.
Additional Resources
These documents contain additional information concerning related products
from Rockwell Automation.
ResourceDescription
Safety Guidelines for the Application,
Installation and Maintenance of Solid State
Controls, publication SGI-1.1
ControlNet Coax Media Planning and
Installation, publication CNET-IN002
Logix5000 Controllers Common Procedures,
publication 1756-PM001
CGCM Release Notes, publication 1407-RN001
Industrial Automation Wiring and Grounding
Guidelines, publication 1770.4.1.
Product Certifications website,
http://www.ab.com
Describes some important differences between
solid-state equipment and hard-wired
electromechanical devices.
Provides installation procedures for the
ControlNet network.
Provides information about RSLogix 5000
software.
Provides information on compatible RSLogix
5000 software versions and ControlLogix
controller firmware revisions.
Provides general guidelines for installing a
Rockwell Automation industrial system.
Provides declarations of conformity, certificates,
and other certification details.
You can view or download publications at http://www.rockwellautomation.com/
literature/. To order paper copies of technical documentation, contact your local
Allen-Bradley distributor or Rockwell Automation sales representative.
Rockwell Automation Publication 1407-UM001G-EN-P - April 20137
Preface
Notes:
8Rockwell Automation Publication 1407-UM001G-EN-P - April 2013
General Information
Chapter
1
Introduction
Functions
The Combination Generator Control Module (CGCM unit) is a
microprocessor-based control and protection device. The CGCM unit is
designed to integrate with a Logix family programmable controller to provide
generator control, protection and synchronization functions. Programmability of
system parameters, regulation settings, and protective functions enable the
CGCM unit to be used in a wide range of applications.
The following sections outline the functions of the unit.
Generator Regulation and Control Functions
This list contains the generator regulation and control functions:
• Four excitation control modes
• Automatic voltage regulation (AVR)
• Manual or field current regulation (FCR)
• Power factor (PF)
• Reactive power (VAR)
• Soft start voltage buildup with an adjustable ramp in AVR and FCR
control modes
• Over-excitation (OEL) and under-excitation (UEL) limiting in AVR,
VAR , and PF contr ol modes
• Under-frequency compensation (Volts/Hertz)
• Line drop compensation
• Auto-tracking between operating modes and between redundant CGCM
units
• Automatic transfer to a back-up CGCM unit in redundant systems
• Generator paralleling with reactive droop compensation or cross-current
(reactive differential) compensation
• Generator paralleling with real power load sharing
• Synchronizing for one or two circuit breakers
Rockwell Automation Publication 1407-UM001G-EN-P - April 20139
Chapter 1 General Information
Generator Protection Functions
This list contains the generator protection functions:
• Loss of excitation current (40)
• Over-excitation voltage (59F)
• Generator over-voltage (59)
• Generator under-voltage (27)
• Loss of sensing (60FL)
• Loss of permanent magnet generator
(PMG/Excitation power) (27)
• Reverse VAR (40Q)
• Over-frequency (81O)
• Under-frequency (81U)
• Reverse power (32R)
• Rotating diode monitor
• Phase rotation error (47)
• Generator over-current (51)
Metering Functions
This list contains the metering functions:
• Vo l t a g e
• Current
• Fre que ncy
• Real Power
• Apparent Power
• Reactive Power
• Power Factor
• Real Energy (kWh)
• Apparent Energ y (kVAh)
• Reactive Energy (kVARh)
• Controller Excitation Current and Voltage
• Diode Monitor Ripple Level
• Load Share Error
• Synchronization Parameters
10Rockwell Automation Publication 1407-UM001G-EN-P - April 2013
General Information Chapter 1
Inputs
This list contains the inputs for the CGCM unit:
• Single-phase or 3-phase true rms generator voltage sensing
• Single-phase dual bus or 3-phase single bus voltage sensing
• 3-phase generator current sensing (1 or 5 A nominal)
• Single-phase cross current loop 1 or 5 A current transformer (CT) input
• Auxiliary ±10V DC input providing remote control of the setpoints
• DC power input
Outputs
This list contains the outputs for the CGCM unit:
• Pulse-width modulated output power stage rated at 15 A
• Discrete redundancy relay output
• Discrete fault output driver
• Load sharing connection for use with the Allen-Bradley Line
Synchronization Module (1402-LSM) or compatible hardware
Communication Interfaces
The CGCM unit has these three communication ports:
• Redundant ControlNet connector
• RS-232 port for dedicated communication with a redundant CGCM
• RS-232 port for factory configuration and test (not for customer use)
Rockwell Automation Publication 1407-UM001G-EN-P - April 201311
Chapter 1 General Information
Notes:
12Rockwell Automation Publication 1407-UM001G-EN-P - April 2013
Installation
Chapter
2
Mounting Requirements
This equipment is intended for use in a Pollution Degree 2 Industrial
Environment, in over-voltage Category II applications (as defined by IEC
publication 60664-1). Because the units contain a heat sink, they must be
mounted vertically. Any other mounting angle reduces the heat dissipation
capabilities of the units, possibly leading to premature failure of critical
components. The unit can be mounted anywhere that the ambient temperature
does not exceed the rated environmental conditions or clearance requirements.
The clearance requirements for the CGCM unit are:
• 63.5 mm (2.5 in.) of clearance is required on both sides of the unit when
mounted.
• 101.6 mm (4 in.) of clearance is required above and below the unit when
mounted.
Overall dimensions for the unit are shown in CGCM Unit Overall Dimensions
on page 14.
WARNING: Explosion Hazard
• Substitution of components can impair suitability for Class I, Division 2.
• Do not replace components or disconnect equipment unless power has been switched
off or the area is known to be non-hazardous.
• Do not connect or disconnect components unless power has been switched off or the
area is known to be non-hazardous.
• This product must be installed in an enclosure. All cables connected to the product
must remain in the enclosure or be protected by conduit or other means.
• All wiring must comply with N.E.C. article 501-4(b).
Rockwell Automation Publication 1407-UM001G-EN-P - April 201313
CNA
CNB
Manufactured by
aB
R
BAT (-)
BAT (+)
DANGER
elrle Esricc
4
5
ID (+) 1A
ID (+) 5A
ID (-)
I3 (+) 1A
I3 (+) 5A
I3 (-)
I2 (+) 1A
I2 (+) 5A
I2 (-)
I1 (+) 1A
I1 (+) 5A
I1 (-)
TB5
TB6
TB3
SHLD 2
SHLD 2
EXC (+)
EXC (-)
TB2
Combination
Generator
Control Module
TB4
FLT
RD RLY
CH GND
TB7
ControlNet
Address
TB1
PMG A
PMG B
PMG C
SHLD 1
SHLD 1
V Bus A
V Bus B
V Bus C
V Bus N
V Gen A
V Gen B
V Gen C
V Gen N
VREF (+)
VREF (-)
SHLD 3
SHLD 3
A-COM
EX-D (+)
EX-D (-)
LS (+)
LS (-)
SHLD 4
Factory
Test
Port
247.7
(9.75)
355.6
(14.00)
363
(~14.3)
1/4 - 20 Ground
Stud (2 Places)
7.14 (0.281) DIA
Mounting Hole
(6 Places)
209.6
(8.25)
25.4
(1.00)
152.4
(6.00)
152.4
(6.00)
228.6
(9.00)
9.7
(0.38)
159.0
(6.26)
190.0
(~7.5)
Notes:
1. Weight = 7.7 kg (17 lb)
2. Dimensions are in millimeters (inches)
Ground Studs
HAZARDOUS VOLTAGE CAN CAUSE SHOCK, BURNS, OR DEATH.
1) DISCONNECT AND LOCK OUT ALL POWER SOURCES AND,
2) SHORT ALL CURRENT TRANSFORMER SECONDARIES BEFORE SERVICING.
MORE THAN ONE LIVE CIRCUIT. SEE DIAGRAM.
ADVERTISSMENT: CET EQUIPEMENT RENFERME PLUSIEURS CIRCUITS SOUS TENSION, V OIR LE SCHEMA
DEMKO 13 ATEX 1202591U
MADE IN U.S.A.
1201 SOUTH SECOND ST.
MILWAUKEE, WISCONSIN
53204
AEx nC IIC T3, Ex nL IIC T3 Gc X
Chapter 2 Installation
Figure 1 - CGCM Unit Overall Dimensions
14Rockwell Automation Publication 1407-UM001G-EN-P - April 2013
Installation Chapter 2
Electrical Connections
The CGCM unit’s connections are dependent on the application and excitation
scheme. All inputs or outputs cannot be used in a given installation. Incorrect
wiring can result in damage to the unit.
Connect the CGCM unit’s terminals with copper wire rated for a minimum of
°
600V. General appliance wire rated for minimum temperatures of 105
°
F) is acceptable. All wire must be copper. Select circuit conductors based on good
C (221
design practice.
The wire gauge range listed in the Te rm i na l B l oc k L ab el D e sc ri p ti on
table
indicates the physical capabilities of the connector.
The CGCM unit’s terminals are on the front, bottom, and right panel of the unit.
The nine-pin connector on the bottom of the unit is used for communication
between CGCM units in a redundant system. Suggested torque for terminal
screws is 1 N•m (9 lb•in).
Refer to pages 17
…34 for typical connection diagrams.
Terminals to be used as landing points for shielded wires are provided on several
terminal strips. Shield terminals with the same name are internally connected
together but are not connected to protective earth or any internal unit circuitry.
Table 1 - Terminal Block Label Description
Terminal BlockWire Gauge
TB1
TB2SHLD2Shield 2 landing points are tied together but are not connected internally to protective earth or
Range
2.6…2.1 mm
(10…12 AWG)
LabelDescription
2
PMG APhase A excitation power supply
PMG BPhase B excitation power supply (three phase only)
PMG CPhase C excitation power supply
SHLD1Shield 1 landing points are tied together but are not connected internally to protective earth or
SHLD1
Rockwell Automation Publication 1407-UM001G-EN-P - April 201315
Chapter 2 Installation
Table 1 - Terminal Block Label Description
Terminal BlockWire Gauge
LabelDescription
Range
2
TB3
2.6…2.1 mm
(10…12 AWG)
ID(+)1 A1 A cross-current compensation CT input
ID(+)5 A5 A cross-current compensation CT input
ID(-)Cross-current compensation CT common input
I3(+)1 A1 A phase C CT input
I3(+)5 A5 A phase C CT input
I3(-)Phase C CT common input
I2(+)1 A1 A phase B CT input
I2(+)5 A5 A phase B CT input
I2(-)Phase B CT common input
I1(+)1 A1 A phase A CT input
I1(+)5 A1 A phase A CT input
I1(-)Phase A CT common input
TB4
1.6…1.0 mm
(14…18 AWG)
2
BAT(+)24V DC control power input
BAT(-)24V DC control power return
FLTOpen collector fault output
RD RLYOpen collector output for redundancy relay
CH GNDChassis ground
TB5V Gen APhase A generator voltage input
V Gen BPhase B generator voltage input
V Gen CPhase C generator voltage input
V Gen NNeutral generator voltage input
TB6V Bus A
V Bus B
Phase A bus voltage input
Phase B bus voltage input
(1)
(1)
V Bus CPhase C bus voltage input
V Bus NNeutral bus voltage input
2
TB7
1.6…1.0 mm
(14…18 AWG)
VREF(+)Remote setpoint adjust input
VREF(-)Remote setpoint adjust input return
SHLD3Shield 3 landing points are tied together but are not connected internally to protective earth or
SHLD3
other unit circuitry
A-COMAnalog common
EX-D(+)Excitation enable input
EX-D(-)Excitation enable return
LS(+)Real power load sharing input
LS(-)Real power load sharing return
SHLD4Shield 4 landing point is not connected internally to protective earth or other unit circuitry
(1) When used in a dual breaker configuration, Bus A voltage input is wired from V Bus A to V Bus N and Bus B is wired from V Bus B to V Bus N.
16Rockwell Automation Publication 1407-UM001G-EN-P - April 2013
Installation Chapter 2
TB1
PMG A
PMG B
PMG C
SHL D 1
SHL D 1
PMG
TB1
PMG A
PMG B
PMG C
SHLD 1
SHLD 1
Fuse
G
AC
B
Excitation Power
Excitation power is wired to the PMG terminals, whether connected to the
generator output (Shunt Excited) or to a PMG. Connect shunt excited inputs
with a voltage transformer (VT).
PMG inputs are on TB1 and are labeled PMG A, PMG B, and PMG C,
illustrating their respective phase relationships. Single-phase excitation power
must be connected to terminals PMG A and PMG C. Twisted, shielded cabling is
required for the PMG inputs.
Refer to the wiring diagrams below.
Figure 2 - Excitation Power Connections, 3-phase PMG
Figure 3 - Excitation Power Connections, Single-phase PMG
PMG A
PMG
Figure 4 - Excitation Power Connections, Single-phase Shunt
Rockwell Automation Publication 1407-UM001G-EN-P - April 201317
PMG B
PMG C
SHLD 1
SHLD 1
TB1
Chapter 2 Installation
TB1
PMG A
PMG B
PMG C
SHLD 1
SHLD 1
Fuse
Fuse
G
AC
B
TIP
Figure 5 - Excitation Power Connections, 3-phase Shunt
Figure 6 - Excitation Power Connections, AREP Generator
This diagram is based on a Leroy Somer 300 kW AREP (auxiliary winding
regulation excitation principle) machine. Details can differ on other
machines.
18Rockwell Automation Publication 1407-UM001G-EN-P - April 2013
Installation Chapter 2
TB2
Shld2
Shld2
EXC (-)
EXC (+)
Exciter field
Exciter voltage
connections
Excitation Output
The excitation outputs are on TB2 and are labeled EXC(+) and EXC(-).
Twisted, shielded cabling is required for the excitation outputs.
When the redundancy function is used, three or four external flyback diodes in
series must be placed across the generator field winding.
Refer to the redundancy wiring diagrams on pages 31
…32.
Control Power
The 24V DC control power inputs are on TB4 and are labeled BAT(+) and
BAT(-).
Figure 8 - Control Power and Chassis Ground Connections
24 VDCControl
Power Source
Ground bus
Ground stud
Rockwell Automation Publication 1407-UM001G-EN-P - April 201319
BAT(+)
BAT(-)
FLT
RD RLY
CH GND
TB4
(typical)
CGCM
Chapter 2 Installation
Chassis Ground
The terminal labeled CH GND, on TB4, is the chassis ground. Ground studs are
also provided on the lower part of the mounting flanges and are internally
connected to the CH GND terminal. Connect chassis ground to earth ground
2
with minimum 2.6 mm
(10 AWG) copper wire attached to either stud on the
lower part of either side of the unit and to the CH GND terminal with 1.6 mm
(14 AWG) copper wire. When installed in a system with other CGCM units, use
a separate lead to the ground bus from each unit.
AC Voltage and Current Sensing
The CGCM unit supports generator and bus voltage sensing and generator
current sensing.
Generator and Bus Voltage Sensing
2
CGCM units accept single-phase or 3-phase generator and bus voltage sensing
input with nominal voltages of 120 or 208V AC.
Refer to Terminal Block Label Description
on page 15 for possible wiring
configurations.
The terminals found on TB5 provide connections for generator voltage sensing
and are labeled V GEN A, V GEN B, V GEN C, and V GEN N. The terminals
found on TB6 provide connections for bus voltage sensing and are labeled V BUS
A, V BUS B, V BUS C, and V BUS N. The connection examples below show
typical connections for various generator and bus connection schemes.
The CGCM unit supports these generator connection schemes:
• Single-phase
• Delta or Two-transformer Open Delta
• Three-wire Wye
• Four-wire Wye
The CGCM supports these bus connection schemes:
• Single-phase
• Delta or Two-transformer Open Delta
• Three-wire Wye
• Four-wire Wye
• Dual Breaker, Single-phase only
20Rockwell Automation Publication 1407-UM001G-EN-P - April 2013
Installation Chapter 2
Generator Current Sensing
CGCM units provide 3-phase AC current sensing with provisions for 1 A and 5
A nominal sensing ranges. The inputs for 3-phase current sensing are on TB3.
The ID (+) and ID (-) terminals are used for systems connected in a cross-current
compensation system.
Voltage and Current Sensing Connection Examples
The following examples depict typical connections of voltage (also called
potential) transformer (VTs) and current transformers (CTs) to the CGCM unit
for various bus and generator power system configurations. These diagrams do
not show all connections to the CGCM unit, nor are they intended to show all
possible wiring combinations. For assistance in wiring a CGCM unit in a power
system configuration not shown below, please contact Rockwell Automation.
Rockwell Automation Publication 1407-UM001G-EN-P - April 201321
L1
L2L3
G
CB
TB 3
TB 6
VBus A
VBus B
VBus C
VBus N
TB 5
AC
B
Fuse
Optional
Ground
Optional
Ground
Use of a third potential
transformer is optional. The
CGCM unit can be connected
in either open or closed delta.
Use of a third potential
transformer is optional. The
CGCM unit can be connected
in either open or closed delta.
Fuse
Fuse
Fuse
Fuse
Fuse
VGen A
VGen B
VGen C
VGen N
To optional cross-current
reactive compensation loop.
Cross-current CT input
not required for parallel
droop operation.
Customer Supplied CT
Shorting Switch or Test
Block
Chapter 2 Installation
Figure 9 - Voltage and Current Connection for Two (or three) Transformer Delta Bus
and Two (or three) Transformer Delta Generator System
22Rockwell Automation Publication 1407-UM001G-EN-P - April 2013
L1NL2 L3
CB
N
Fuse
Fuse
Fuse
Fuse
Fuse
Fuse
G
AC
B
TB3
I1 (+) 5A
I1 (-)
ID (+) 5A
I3 (+) 5A
I2 (+) 5A
I2 (-)
I3 (-)
ID (-)
I1 (+) 1A
I2 (+) 1A
I3 (+) 1A
ID (+) 1A
TB6
VBus A
VBus B
VBus C
VBus N
TB5
VGen A
VGen B
VGen C
VGen N
To optional cross-current
reactive compensation loop.
Customer Supplied CT
Shorting Switch or Test
Block
Cross-current CT input
not required for parallel
droop operation.
Installation Chapter 2
Figure 10 - Voltage and Current Connection for Four-wire Wye Bus and Four-wire
Wye Generator System with Grounded Neutral
Rockwell Automation Publication 1407-UM001G-EN-P - April 201323
Chapter 2 Installation
L1NL2L3
G
CB
AC
B
Fus e
Fuse
Fuse
Fuse
Fuse
Fuse
TB3
I1 (+) 5A
I1 (-)
ID (+) 5A
I3 (+) 5A
I2 (+) 5A
I2 (-)
I3 (-)
ID ( -)
I1 (+) 1A
I2 (+) 1A
I3 (+) 1A
ID (+) 1A
TB 6
VBu s A
VBu s B
VBu s C
VBu s N
TB5
VGe n A
VGe n B
VGe n C
VGe n N
Customer Supplied CT
Shorting Switch or Test
Block
Cross-current CT input
not required for parallel
droop operations.
To optional cross-current
reactive compensation loop.
Optional
Ground
Use of a third potential
transformer is optional. The
CGCM unit can be connected
in either open or closed delta.
Figure 11 - Voltage and Current Connection for Four-wire Wye Bus and Two (or
three) Transformer Delta Generator System
24Rockwell Automation Publication 1407-UM001G-EN-P - April 2013
L1L2 L3
G
CB
AC
B
Fuse
Fuse
Fuse
Fuse
Fuse
Fuse
N
TB3
I1 (+) 5 A
I1 (- )
ID (+) 5A
I3 (+) 5 A
I2 (+) 5 A
I3 (- )
ID (- )
I1 (+) 1 A
I2 (+) 1 A
I3 (+) 1 A
ID (+) 1A
TB 6
VBus A
VBus B
VBus C
VBus N
TB 5
V Gen A
VGe n B
V Gen C
V Gen N
I2 (- )
Optional
Ground
To optional cross-current
reactive compensation loop.
Customer Supplied CT
Shorting Switch or Test
Block
Cross-current CT input
not required for parallel
droop operation.
Use of a third potential
transformer is optional. The
CGCM unit can be connected
in either open or closed delta.
Installation Chapter 2
Figure 12 - Voltage and Current Connection for Two (or three) Transformer Delta
Bus and Four-wire Wye Generator System
Rockwell Automation Publication 1407-UM001G-EN-P - April 201325
Chapter 2 Installation
L1L2 L3
CB
N
Fuse
Fuse
Fuse
Fuse
Fuse
Fuse
G
AC
B
TB3
I1 ( +) 5 A
I1 ( -)
ID ( +) 5 A
I3 ( +) 5 A
I2 ( +) 5 A
I2 ( -)
I3 ( -)
ID (-)
I1 ( +) 1 A
I2 ( +) 1 A
I3 ( +) 1 A
ID ( +) 1 A
TB 6
VBus A
VBus B
VBus C
VBus N
TB5
VGen A
VGen B
VGen C
VGen N
Customer Supplied CT
Shorting Switch or Test
Block
Cross-current CT input
not required for parallel
droop operation.
To optional cross-current
reactive compensation loop.
Figure 13 - Voltage and Current Connection for Three-wire Wye Bus and Four-wire
Wye Generator System with Grounded Neutral
26Rockwell Automation Publication 1407-UM001G-EN-P - April 2013
Installation Chapter 2
L1 A L 2A L 3A
CB
Fus e
Fuse
CB
L1 B L 2B L 3B
Fuse
Fuse
Fus e
G
TB 3
I1 (+ ) 5A
I1 (-)
ID (+ ) 5A
I3 (+ ) 5A
I2 (+ ) 5A
I2 (-)
I3 (-)
ID (-)
I1 (+ ) 1A
I2 (+ ) 1A
I3 (+ ) 1A
ID (+ ) 1A
TB 6
VBus A
VBus B
VBus C
VBus N
TB 5
VGen A
VGen B
VGen C
VGen N
AC
B
Optional
Ground
To optional crosscurrent reactive
compensation loop.
Cross-current CT input
not required for parallel
droop operation.
Customer Supplied CT
Shorting Switch or Test
Block
Use of a third potential
transformer is optional. The
CGCM unit can be connected
in either open or closed delta.
Figure 14 - Voltage and Current Connection for Dual Breaker Bus and Two (or three)
Transformer Delta Generator System
Rockwell Automation Publication 1407-UM001G-EN-P - April 201327
Chapter 2 Installation
L1 A L2A L3 A
CB
Fuse
Fuse
Fuse
Fuse
Fuse
N
CB
L1B L2 B L3B
G
TB3
I1 (+ ) 5A
I1 (- )
ID (+ ) 5 A
I3 (+ ) 5A
I2 (+ ) 5A
I2 (- )
I3 (- )
ID (- )
I1 (+ ) 1A
I2 (+ ) 1A
I3 (+ ) 1A
ID (+ ) 1 A
TB6
VBus A
VBus B
VBus C
VBus N
TB5
VGen A
VGen B
VGen C
VGen N
AC
B
To optional crosscurrent reactive
compensation loop.
Cross-current CT input
not required for parallel
droop operation.
Customer Supplied CT
Shorting Switch or Test
Block
Figure 15 - Voltage and Current Connection for Dual Breaker Bus and Four-wire
Wye Generator System
28Rockwell Automation Publication 1407-UM001G-EN-P - April 2013
L1L2 L3
CB
Fuse
Fuse
TB 6
VBus A
VBus B
VBus C
VBus N
TB5
VGen A
VGen B
VGen C
VGen N
G
AC
B
TB3
I1 (+) 5 A
I1 (-)
ID (+ ) 5 A
I3 (+) 5 A
I2 (+) 5 A
I2 (-)
I3 (-)
ID ( -)
I1 (+) 1 A
I2 (+) 1 A
I3 (+) 1 A
ID (+ ) 1 A
To optional cross-current
reactive compensation loop.
Cross-current CT input
not required for parallel
droop operation.
Customer Supplied CT
Shorting Switch or Test
Block
Installation Chapter 2
Figure 16 - Voltage and Current Connection for Single Phase Bus and Single-phase
Generator System
Rockwell Automation Publication 1407-UM001G-EN-P - April 201329
Chapter 2 Installation
Figure 17 - Current Connections for 3-phase Delta Generator with Two CTs
The connections shown in this diagram can be used if only two CTs are available
in the generator circuit. Two CTs can be used only with a three-wire delta
generator. The circuit shown in this diagram can be substituted for the CT
connections shown in Figures 9
B
AC
, 11, 14, and 16.
Customer Supplied CT
Shorting Switch or Test
Block
TB 3
I3 (+) 1A
I3 (+) 5A
I3 (-)
I2 (+) 1A
I2 (+) 5A
I2 (-)
I1 (+) 1A
I1 (+) 5A
I1 (-)
G
Auxiliary Input
The auxiliary input is a +/- 10V DC input. The auxiliary input terminals are on
TB7 and are labeled VREF(+) and VREF(-). SHLD3 is provided for landing the
cable shield. Twisted, shielded cabling is required for the VREF connections.
Remote Excitation Enable Input
The remote excitation enable input is a 24V DC input. The remote excitation
enable input terminals are on TB7 and are labeled EX-D(+) and EX-D(-).
Discrete Outputs
There are two types of discrete outputs: fault relay outputs and redundancy relay
outputs.
30Rockwell Automation Publication 1407-UM001G-EN-P - April 2013
Loading...
+ 216 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.