The MiniPowermonitor (1405-M620) measures all the important
parameters of 3-phase power lines in low-voltage AC power
applications. The measurements are indicated on a 3-line display, one
parameter at time, either by auto-sequencing or by manual access.
There are 6 parameter groups:
• Line-to-line voltages
• Line-to-neutral voltages
• Instantaneous, time-averaged and peak currents
• Real power per phase, apparent power per phase, total real and
apparent power, and 3-phase power factor
• Power factor (Cos φ) per phase
• Net real energy: per phase and total for all 3 phases
Phase voltages are monitored continuously for under- and
over-voltage conditions, and when such a condition is detected, an
alarm relay is activated. Energy units are also transmitted as relay
pulses. Relay contacts are connected via rear panel terminal points.
Measured values for each of the 3 phases are indicated simultaneously
on bright red 7-segment LED displays, 14 mm high, arranged in 3
horizontal lines of 5 digits each. The displayed values can be easily
read even in high ambient light conditions, at substantial viewing
distances, and at acute viewing angles.
The left-most 7-segment digit on each of the three lines functions as a
limited alphanumeric indicator. These digits, along with the LED status
lamps on the right of the instrument front panel, indicate either which
measurement parameter is being displayed at any instant, or the
set-up status.
The instrument is operated through three key-switches (‘-’, ‘F’, and ‘+’)
arranged in a row at the bottom right of the front panel. These keys
are used for instrument set-up, and for manual selection of displayed
measurements. Different functions are selectable using the function
(‘F’) key-switch, by keeping it pressed for varying lengths of time. The
left-most character of the lowest display line indicates the selected
function.
1Publication 1405-IN002C-EN-P - November 2004
2 Bulletin 1405 (M620) Operating Instructions
External connections to the instrument are terminated on plug-in
connector blocks with spring-clamp wire terminals, at the rear of the
instrument. Phase voltage connections are terminated on a 7-pin
connector block. Another 12-pin connector block is used for the
current transformer inputs, and alarm and energy pulse relay outputs.
The instrument’s operating power supply is drawn from a separate
120V or 240V ac power supply input, through an additional 3-pin
connector block. An optional 400V or 480V version of the unit is
available with operating power drawn from two of the phase voltage
input lines (L1 - L2). Therefore the M620 can be used with either
3-wire (3 phase) or 4-wire (3 phase and neutral) power systems.
The M620 is a compact instrument, with a 96 x 96 mm front panel,
and a depth of approximately 85 mm.
Installation
Only qualified personnel should install and wire this equipment. Refer
to the following safety guidelines prior to installation.
ATTENTION
Only qualified personnel, following accepted safety
procedures, should install and wire the
MiniPowermonitor. Before beginning any work,
disconnect all sources of power and verify that they
are de-energized and locked out. Failure to follow
these instructions may result in personal injury or
death, property damage or economic loss.
ATTENTION
Never open a current transformer (CT) secondary
circuit with primary current applied. Wiring between
the CTs and the MiniPowermonitor should include a
shorting terminal block in the CT secondary circuit.
Shorting the secondary with primary current present
allows other connections to be removed if needed.
An open CT secondary with primary current applied
produces a hazardous voltage, which can lead to
personal injury, death, property damage or economic
loss.
Publication 1405-IN002C-EN-P - November 2004
Bulletin 1405 (M620) Operating Instructions 3
1. Install your module within a suitable enclosure. Make sure the
enclosure provides adequate clearance for ventilation and wiring
of the module.
Refer to Dimensions on page 20 for dimensions and spacing
guidelines for the MiniPowermonitor.
2. Determine your wiring mode and install wiring between the
MiniPowermonitor and your power system.
Refer to Electrical Connections on page 3 for more information.
3. Configure the instrument settings to match those used in your
power system connections.
Refer to Instrument Set-Up on page 14 for more information.
Grounding
Electrical Connections
MiniPowermonitors do not need to be grounded because of the
isolated enclosures. Follow all local requirements for grounding of PT
and CT secondaries.
Electrical connections are terminated on two plug-in connector blocks
with spring-clamp wire terminals, at the rear of the instrument. These
connector blocks, 7- and 12-pin respectively, can accept wire sizes
from 28 to 14 AWG (0.08 to 2.5 sq.mm).
Publication 1405-IN002C-EN-P - November 2004
4 Bulletin 1405 (M620) Operating Instructions
-
Current Inputs
M620
-
-
L1
GND
Aux. Supply
(120V or 240V only)
L2
NCNCL3
NNGND
TIP
L1
Voltage Inputs
Pins 2 and 4 (counting from the left side) of the 7-pin
connector are not used: no external wires should be
connected to these terminals!
CT Connection: Careful consideration should be given when
connecting the secondary of the CT to the current inputs of the
MiniPowermonitor. Extended lengths of connection wire will cause
the VA rating of the CT to increase and will create higher common
mode input voltage. It is recommended that the wire size be selected
to limit the impedance to 200 milliohms. Exceeding this limit may
cause current readings to become less accurate when using a star
connection.
Publication 1405-IN002C-EN-P - November 2004
Aux Supply: With this option, instrument power is supplied by a
separate 120V or 240V line, independent of the measured power lines.
A third connector block (3-pin, spring-clamp terminals type) is added
at the rear with this option.
Bulletin 1405 (M620) Operating Instructions 5
IMPORTANT
Units are rated 120V or 240V but not both. A 120V
unit will not accept 240V, and a 240V unit will not
accept 120V.
A unit with the 120V supply option is not designed to operate on
240V or any other voltage. Likewise, a unit with the 240V supply
option is not designed to operate on 120V or any other voltage. Units
designed for 400V and 480V operation do not have an auxiliary
supply connection and receive power from the measurement line.
Ensure that each unit is properly supplied with a power source that
matches the voltage designation of your unit.
Relay Output Connections
Alarm and energy pulse relay contact connections are made to the
spring-clamp wire terminals on the 12-pin connector block, as
follows:
Table 1 Alarm and Energy Pulse Relay Contact Connections
Measurement Operations
Alarm:Terminals 7 - 8
Energy pulses:Terminals 9 - 10
Immediately after the instrument is switched on, the software version
is first displayed for 8 seconds, after which the measured values are
displayed. The measured parameter that is displayed when the
instrument is switched on will be the main displayed parameter group
that was on display when the instrument was switched off. This will
happen regardless of whether the instrument was in the “constant
parameter” or auto-sequencing display mode at that time the
instrument was switched off.
In the “constant parameter” display mode, any one of the 6 parameter
groups can be manually selected, by forward or backward sequential
stepping, using the “+” or “-“keys. Only that parameter will be
displayed, until another parameter is manually selected, or the
instrument is switched to auto-sequencing display mode. Some of the
parameter groups (current, power, and energy) have a main displayed
parameter and also additional parameters within the same group. The
additional parameters can be accessed when the instrument is
displaying the main parameter of that group. For example, when the
instrument is displaying current measurements, the main parameter
Publication 1405-IN002C-EN-P - November 2004
6 Bulletin 1405 (M620) Operating Instructions
displayed is instantaneous phase currents, while the additional
parameters are time-averaged phase currents and peak phase currents.
For power measurements, the main parameters displayed are real
power for each phase. The additional parameters in this group are
apparent power of each phase, total real and apparent power, and
3-phase power factor. When the instrument is displaying the main
parameter of a group, the additional parameters within that group can
be scrolled using the “F” key.
Measurement Modes
The functions of the instrument are accessedas follows:
Table 2
KeyFunction
Indication
“+”Skip to the next measured parameterShort
Auto-sequencing display mode: enable /
disable
Re-set average and peak values- “c” Very long
“F”Sequentially display one parameter type: e.g.,
current
Enter set-up modeVery long
“-“Go back to the previous displayed parameter
- “r”Long
Key Press
Duration
Short
The instrument measures voltage and current for each of three phases
in an alternating sequence of 2 seconds each. This corresponds to the
integrating time of the A/D converter circuits. At the same time, the
values of power, power factor (Cos f), and energy consumption are
computed. The energy value is computed for each phase over the
integration period, and the accumulated values are stored in memory.
The measured voltage values are continuously evaluated for over- and
under-voltage occurrences, and the energy transfer rate is converted
to an output pulse rate. Voltage limit alarms and energy unit pulses
are transmitted by relay contacts.
Publication 1405-IN002C-EN-P - November 2004
In the auto-sequencing displayed mode, the displayed parameter
change every 6 seconds. The user can halt the auto-sequencing of
displayed parameters, so that one desired parameter is displayed
continuously. Independent of the sequencing mode, the measured
values are updated and displayed in 2-second intervals.
Bulletin 1405 (M620) Operating Instructions 7
The measured values of the electrical parameters are available with six
analog retransmission outputs (4-20 mA) (optional). Details of these
analog outputs are found on
V
Line-to-line voltage
A
L1-L2
P
L2-L3
cos
ϕ
L1-L3
E
F
+
page 22.
"+" Key
Scrolls Down
"-" Key
Scrolls Up
Line-to-neutral voltage
V
A
L1-N
P
L2-N
cos
ϕ
L1-N
E
F
+
V
A
P
cos
ϕ
E
F
+
V
A
P
cos
ϕ
E
F
+
V
A
P
cos
ϕ
E
F
+
V
A
P
cos
ϕ
E
F
+
V
Left:
A
Instantaneous current
P
Middle:
cos
ϕ
Time-averaged current
E
+
V
A
P
cos
ϕ
E
+
Right:
Peak current
Left:
Real power
Middle:
Apparent power
Right:
Total real power
F
F
Total apparent power
V
A
Power factor (Cos φ)
P
L1
cos
ϕ
L2
E
F
L3
+
3-phase power factor
V
A
P
cos
ϕ
E
F
+
V
A
P
cos
ϕ
E
F
+
"F" Key Scrolls Right
Left
Net real energy
L1
L2
L3
Right:
Total net real energy
Publication 1405-IN002C-EN-P - November 2004
8 Bulletin 1405 (M620) Operating Instructions
Auto-Sequencing Display Mode
In this display mode, the instrument automatically switches the
displayed values from one parameter group to the next, at intervals of
6 seconds, cycling continuously through all 6 parameter groups.
Any of the additional parameters can be selected instead of the main
parameter. Thereafter only the selected additional parameter will be
displayed when the turn of that parameter group comes up during
display sequencing. For example, if time-averaged phase currents are
selected in the current (I) parameter group, only these values will be
displayed when it is the turn of this group during auto-sequencing.
Irrespective of the specific parameter selected for display within each
group, the total period of the display cycle for the 6 parameter groups
remains constant.
Line-to-neutral voltages and line-to-line voltages are treated as
separate parameter groups, so that both these parameters are always
displayed during auto-sequencing.
Analog Outputs
Examples of all the parameter displays, and parameters grouping, are
illustrated on the next page.
The M620 is also available with six analog retransmission outputs.
These outputs can be user programmed for 0-20 mA or 4-20 mA, and
assigned to any of the measured power-line measured variables.
These outputs are electrically isolated from the rest of the instrument’s
circuits. Each output has a positive polarity. A common return line at 0
V potential is used for all analog outputs. Each output can drive a load
of up to 250 ohms, with output voltage of up to 5V dc. These outputs
may be connected in parallel.
Configure the analog outputs during instrument setup. The following
key sequences and indications apply during setup.
The “-” key scrolls through the parameters that may be assigned as a
0 to 20 mA output:
VVoltage P-P
nVoltage P-N
ICurrent instantaneous
=Current time average
Preal power
Sapparent power
Ccos phi (power factor)
Publication 1405-IN002C-EN-P - November 2004
Loading...
+ 16 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.