Rockwell Automation 1402-LSM User Manual

Allen-Bradley
ALLEN-BRADLEY
Line Synchronization Module
Installation and Operation Manual

Important User Information

Solid state equipment has operational characteristics differing from those of electromechanical equipment. “Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls” (Publication SGI-1.1) describes some important differences between solid state equipment and hard–wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will the Allen-Bradley Company be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, the Allen-Bradley Company cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Allen-Bradley Company with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of the Allen-Bradley Company is prohibited.
Throughout this manual we use notes to make you aware of safety considerations.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
!
damage, or economic loss.
Attentions help you:
identify a hazard
avoid the hazard
recognize the consequences
Important: Identifies information that is especially important for successful application and understanding of the product.
PLC and PLC–5 are registered trademarks of Allen-Bradley Company, Inc. ControlView is a trademark of the Allen-Bradley Company, Inc.

Table of Contents

Product Description 1–1.
. . . . . . . . . . . . . . . . . . . . . . . . .
Chapter Objectives 1–1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Introduction 1–1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General Description 1–1. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Synchronization and Load Share Errors 1–2. . . . . . . . . . . . . .
Measurements 1–3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Module Configuration 1–3. . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation 2–1.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Location 2–1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Enclosure 2–1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mounting 2–1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Power Supply 2–1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chassis Grounding 2–1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Swing Arm 2–1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wiring 2–2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Prevent Electrostatic Discharge 2–2. . . . . . . . . . . . . . . . .
PT and CT Transformer Selection 2–3. . . . . . . . . . . . . . . . . .
PT Selection 2–3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CT Selection 2–3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PT and CT Wiring Connections 2–4. . . . . . . . . . . . . . . . . . . .
Connection for Three Phase WYE (Star),
4 Wire Systems 2–4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connection for Three Phase WYE (Star),
3 Wire Systems 2–4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connection for Three Phase Delta,
3 Wire Systems with 3 PT’s & 3 CT’S 2–5. . . . . . . . . . . .
Connection for Three Phase Open Delta,
3 Wire Systems with 2 PT’s & 3 CT’S 2–5. . . . . . . . . . . .
Connection for Three Phase Open Delta,
3 Wire Systems with 2 PT’s & 2 CT’S 2–5. . . . . . . . . . . .
Neutral Connection 2–5. . . . . . . . . . . . . . . . . . . . . . . . . . .
Current Transformer Connections 2–6. . . . . . . . . . . . . . .
Maintenance 2–6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Calibration 2–6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Field Service Considerations 2–6. . . . . . . . . . . . . . . . . . . . . .
General Operation 3–1.
. . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter Objectives 3–1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operational Characteristics 3–1. . . . . . . . . . . . . . . . . . . . . . .
Functional 3–1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuration 3–1. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Synchronization 3–4. . . . . . . . . . . . . . . . . . . . . . . . . .
Power Monitoring 3–6. . . . . . . . . . . . . . . . . . . . . . . . .
Load Sharing 3–7. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control 3–8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Self–test 3–8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Update Rate 3–9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Accuracy 3–9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
i
T
able of Contents
PLC Interface 3–9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Discrete I/O Interface 3–9. . . . . . . . . . . . . . . . . . . . . . . . .
Discrete Outputs (From the PLC Processor) 3–10. . . .
Discrete Inputs (To the PLC Processor) 3–10. . . . . . . .
Block Transfer Data Interface 3–10. . . . . . . . . . . . . . . . . . .
Configuration Software Support 3–11. . . . . . . . . . . . . . . . .
6200 Software 3–11. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Application Information 4–1.
. . . . . . . . . . . . . . . . . . . . . .
Overview 4–1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Modes of Operation 4–1. . . . . . . . . . . . . . . . . . . . . . . . . .
Monitor Only 4–1. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Monitor with Load Share 4–1. . . . . . . . . . . . . . . . . . .
Synchronization and Monitor 4–1. . . . . . . . . . . . . . . .
Synchronization and Monitor with Load Share 4–2. .
Interfacing to the LSM 4–2. . . . . . . . . . . . . . . . . . . . . . . . . . .
Block Transfer Communications 4–2. . . . . . . . . . . . . . . .
Configuration 4–3. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Acquiring Data From the LSM 4–4. . . . . . . . . . . . . . .
Discrete Input / Output Control of the LSM 4–4. . . . . . . .
Discrete Outputs From The PLC–5 4–4. . . . . . . . . . .
Discrete Inputs to the PLC–5 4–6. . . . . . . . . . . . . . . .
Ladder Program Description 4–8. . . . . . . . . . . . . . . . . . . . . .
Data Files Used 4–9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Accessing BTR Data from PLC Ladder 4–11. . . . . . . . . . .
Catalog Number Explanation A–1.
. . . . . . . . . . . . . . . . . . .
Line Synchronization Module A–1. Block Transfer and Discrete I/O Definition B–1. Sample Ladder Listing C–1.
. . . . . . . . . . . . . . . . . . .
. . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . .
Line Synchronization Module Mechanical Dimensions D–1.
Bulletin 1402 Technical Specifications E–1.
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . .
CSA Hazardouis Location Approval E–2. . . . . . . . . . . . . . . .
Compliance to European Union Directives E–4. . . . . . . . . . .
ii
Using This Manual
Preface
A–B

What This Manual Contains

Review the table below to familiarize yourself with the topics contained in this manual.
For information about: Refer to chapter:
Product features and System applications Synchronization Functions Extensive Array of Monitoring Information Installing the Line Synchronization Module Wiring and Transformer Selection Operational Characteristics PLC Interface Configuration Software Support – 6200 Software Modes of Operation Block Transfer Communications Configuration Information Ladder Program Description Catalog Number Explanation Appendix A Block Transfer and Discrete I/O Definition Appendix B Sample Ladder Listing Appendix C Mechanical Dimensions Appendix D Technical Specifications Appendix E
1
2
3
4

For More Information on Additional Power Quality Products

For this information: Refer to:
Catalog Number 1400–PD Installation and Operation Manual Publication 1400–5.2 Catalog Number 1400–SP Installation and Operation Manual Publication 1400–801 Installing the Communications Card Instructions
Catalog Number 1400–DCU RS–232C and RS–485 Convertor Instructions
Catalog Number 1400–CC LSM Application Notes Publication 1402­Catalog Number 1403-MM Powermonitor II Instruction Sheet Publication 1403-5.0 Catalog Number 1003-NSC Smart Communications Card
Instruction Sheet Powermonitor II Tutorial Publication 1403-1.0.2
Publication
1400–5.0
Publication
1400–5.1
Publication 1403-5.1
i
Preface
Using This Manual

Terms and Conventions

In this manual, the following terms and conventions are used:
Abbreviation Term
AWG American Wire Gage BTR Block Transfer Read BTW Block Transfer Write CT Current Transformer EEPROM Electrically Erasable Programmable ROM EMI Electromagnetic Interference ID Identification LED Light Emitting Diode I/O Inputs and Outputs should be considered with respect to the PLC processor LSM Line Synchronization Module PT Potential Transformer RAM Random Access Memory RFI Radio Frequency Interference RMS Root–mean–square ROM Read Only Memory VA Volt–ampere VAR Volt–ampere Reactive
ii
Chapter
Chapter
Objectives

Introduction

A–B
1
Product Description
After reading this chapter, you should be able to identify the product features and system applications.
The Bulletin 1402, Line Synchronization Module (LSM), is designed to meet the needs of manufacturers, system integrators, and users of 3 phase alternators and cogeneration systems or for applications that require two three–phase systems to be synchronized with each other. The module provides means for automatic synchronization, load sharing, and high speed power system monitoring.

General Description

The Line Synchronization Module (LSM) is a two slot 1771 form factor module that fits into a standard Allen–Bradley 1771 I/O chassis. It performs three functions:
1. Measures appropriate parameters from the two three–phase systems and provides control and error signals to implement engine governor control for synchronization.
2. Provides an analog output that is representative of the ratio of the power being supplied by the alternator to the output rating of the alternator, reads an analog input that represents the ratio of the total system load being supplied to the total system capacity, and provides an error signal to adjust the alternator for proper load sharing based on the instantaneous load requirements.
3. Performs as a multi–function digital power monitor for the system.
These functions provide data and control signals which are communicated to the PLC-5 via the 1771 backplane.
1–1
Chapter 1
Product Description

Synchronization and Load Share Errors

In order to synchronize two three phase systems without high instantaneous energy transfer, the voltage, frequency, and phase displacement of the two systems must be matched. Kilowatt Load Sharing can be implemented by matching the ratio of power system load to system capacity to the ratio of actual alternator power to rated alternator power. The LSM provides the following information to allow the user’s system to achieve the necessary control actions.
Voltage Match Error (in steps of 0.05 percent)
Frequency Match Error, or slip (in steps of 0.01 Hz)
Synchronizing Bus to Reference Bus Phase Match Error (in steps of 1
degree)
Load Sharing Error (scalar quantity between 0.000 and 1.000)
Synchronization Status
— Frequency Within Limits — Voltage Within Limits — Phase Within Limits — Synchronization Mode Conflict Failure — Phase Rotation Mismatch Failure (3 phase synchronization mode only) — No Reference Bus Voltage Present Failure — No Synchronizing Bus Voltage Present Failure — Reference Bus Over Voltage Failure — Synchronizing Bus Over Voltage Failure
1–2
Chapter 1
Product Description

Measurements

Synchronizing Bus
Synchronizing Bus
Reference Bus
In addition to the synchronization function, the LSM provides an extensive array of monitoring information for systems wired in Wye, Delta, or Open Delta. The monitored data is shown below:
T
able 1.1
Current in Amps (per phase & neutral) Average Current in Amps Positive Sequence Current in Amps Negative Sequence Current in Amps Percent Current Unbalance Voltage in Volts (per phase L–L, also L–N on 4–wire systems) Average Voltage in Volts (L–L, also L–N on 4–wire systems) Positive Sequence Voltage in Volts Negative Sequence Voltage in Volts Percent Voltage Unbalance Frequency in Hz Phase Rotation (ABC, ACB) Power Factor in Percent (total, also per phase on 4–wire systems) Watts (total & per phase on 4–wire systems) VA (total & per phase on 4–wire systems) VAR (total & per phase on 4–wire systems) Power Consumption in kW Hours Reactive Power Consumption in kVAR Hours Demand (Amps, VA, & Watts) Voltage per phase in Volts (per phase L–L, also L–N on 4–wire systems) Average Voltage in Volts (L–L, also L–N on 4–wire systems) Frequency in Hz Phase Rotation (ABC, ACB)

Module Configuration

All voltage and current measurements are true RMS. The power measurements are calculated from the instantaneous voltage and current measurements. The remainder of the monitoring information is derived from these values.
Before the LSM can perform its intended functions, it must be configured by the user. The module is configured by providing the required data via a block transfer to the module. The block transfer data can be entered into the PLC-5 manually or with the 6200 Version 4.4 I/O Configuration Software. The 6200 Software can also be used to monitor the operation of the module.
1–3
Chapter 1
Product Description
1–4
Chapter

Location

Enclosure

A–B
2
Installation
The Bulletin 1402 Line Synchronization Module (LSM) should be installed in a Bulletin 1771 I/O chassis that is located in a dry, dirt free environment away from heat sources and very high electric or magnetic fields. The module is designed to operate in an ambient temperature between 0 and 60° Celsius. The LSM is typically installed in a local rack in order to maximize data transfer rates.
This equipment is classified as open equipment and must be installed (mounted in an enclosure during operation as a means of providing safety protection. The enclosure chosen should protect the LSM from atmospheric contaminants such as oil, moisture, dust, corrosive vapors, or other harmful airborne substances. A steel enclosure is recommended to guard against EMI (Electromagnetic Interference) & RFI (Radio Frequency Interference).

Mounting

Power Supply

Chassis Grounding

The enclosure should be mounted in a position that allows the doors to open fully. This will allow easy access to the wiring of the LSM and related components so that servicing is convenient.
When choosing the enclosure size, extra space should be allowed for associated application equipment such as, transformers, fusing, disconnect switch, master control relay, and terminal strips.
The LSM mounts in two slots of a Bulletin 1771 Series B, I/O chassis. Mounting dimensions will vary with the size of the chassis selected. Refer to the appropriate 1771 literature for specific dimensions.
The LSM backplane power requirement is 1.1A at 5V DC. Refer to the appropriate 1771 literature for additional information on available power supply current.
For correct and reliable performance, the grounding recommendations specified for Allen–Bradley PLC systems must be followed.
2–1
Chapter 2
Installation

Swing Arm

Wiring

The LSM requires the use of a Cat. No. 1771-WC (10 position, gold contacts) Swing Arm.
There are two sets of terminals associated with the LSM; a 10 position swingarm and an 8 position fixed terminal block. All customer wiring to the LSM is accomplished via these terminals on the front of the module. The 10–position swingarm is used to make all of the voltage (PT) connections to the module as well as the Load Share connections. These connections are designed to accommodate wire size 0.5 mm
2
mm
(14 AWG). The 8–position fixed terminal block is used to make all of the current (CT) connections. These connections are designed to accommodate gauge wire size 0.5 mm
3.25 mm Phasing and polarity of the AC current and voltage inputs and their
relationship are critical for the correct operation of the unit. Figure 2.1 through Figure 2.5 shown on Pages 2–7 through 2–11 provide wiring diagrams to help ensure correct installation.
Two (2) conductor shielded wire (22 gauge or greater) should be used for Load Share wiring. The shield shall be grounded at the PLC Chassis ground point only.
2
(12 AWG).
2
(22 AWG) through size 2.0
2
(22 AWG) through ring lugs size
Prevent Electrostatic Discharge
ATTENTION: Electrostatic discharge can damage integrated circuits or semiconductors if you touch backplane connector pins.
!
Follow these guidelines when you handle the module:
Touch a grounded object to discharge static potential.
Wear an approved wrist-strap grounding device.
Do not touch the backplane connector or connector pins.
Do not touch circuit components inside the module.
If available, use a static-safe work station.
When not in use, keep the module in its static-shield box.
2–2
Chapter 2
Installation

PT and CT Transformer Selection

For proper monitoring and synchronization, correct selection of current transformers (CT’s) and potential transformers (PT’s) is critical. The following paragraphs provide the information required to choose these transformers. Also refer to transformer operational characteristics Pages 3–2 and “Factory Configuration Parameters” listed on Page B–2.
PT Selection
The LSM is designed for a nominal full scale input voltage of 120V AC. The user must supply transformers to scale down the system L–N (Wye) or L–L (Delta) voltage to the full scale input rating of the module. The PT’s should be selected as follows:
Wye (Star) Configuration – PT primary rating = L–N voltage or nearest
higher standard size. PT secondary rating = 120 Volts.
Delta or Open–Delta Configuration – PT primary rating = system L–L
voltage. PT secondary rating = 120 Volts.
PT quality directly affects system accuracy. The PT’s must provide accurate linearity and maintain the proper phase relationship between voltage and current in order for the Phase Error, Volts, kW, and Power Factor readings to be valid. Instrument accuracy Class 1 or better is recommended. The LSM PT inputs represent a O.O2 VA burden.
CT Selection
The LSM uses current transformers (CT’s) to sense the current in each phase of the power feed from the synchronizing voltage source, and may optionally be included in the ground or neutral conductor. The precision of the selected CT’s will directly affect the device accuracy.
The CT secondary should have a rating of 5A full scale and a burden capacity greater than 3VA. The LSM Module CT Inputs represent a burden of 0.0025VA.
ATTENTION: The CT primary rating is normally selected to be equal to the current rating of the power feed protection device. However, if the peak anticipated load is much less than the rated
!
system capacity, then improved accuracy and resolution can be obtained by selecting a lower rated CT. Generally, the CT size should be the maximum expected peak current +25%, rounded up to the nearest standard CT size.
2–3
Chapter 2
PT an
ing Connections
Installation
Other factors may affect CT accuracy. The length of the CT cabling should be minimized because long cabling could contribute to excessive power load on the CT and inaccuracy. The CT burden rating must exceed the combined burden of the LSM plus cabling plus any other devices connected in the measuring circuit (burden is the amount of load being fed by the CT, measured in Volt–Amps calculated at 5A full scale.).
Overall accuracy is dependent on the combined accuracy of the Bulletin 1402, the CT’s, and the PT’s. Instrument accuracy Class 1 or better is recommended.
ATTENTION: A CT circuit must not be opened under power. Wiring between the CT’s and the LSM should include a terminal
!
block for shorting the CT’s. Open CT’s secondaries can produce hazardous voltages, which can lead to personal injury or death, property damage or economic loss.
d CT Wir
Connection for Three Phase WYE (Star), 4 Wire Systems
Figure 2.1 shown on Page 2–7 provides a wiring diagram for 4–wire WYE (Star) systems. The “Voltage Mode” of the LSM should be set to “1” (as described in Chapter 3, “General Operation”) for 4–wire WYE systems.
The LSM senses the line to neutral (or ground) voltage of each phase. The PT primaries and secondaries must be wired in a WYE (Star) configuration as shown in the figure. Voltage input leads should be protected by circuit breakers or fuses at their source. If the power rating of the PT’s is over 25 Watts, secondary fuses should be used. Wiring and polarity marks must be exactly as shown for correct operation.
Connection for Three Phase WYE (Star), 3 Wire Systems
Figure 2.2 shown on Page 2–8 provides a wiring diagram for 3–wire WYE (Star) systems. The “Voltage Mode” of the LSM should be set to “1” (as described in Chapter 3, “General Operation”) for 3–wire WYE systems.
The LSM senses the line to neutral voltage of each phase. The PT primaries and secondaries must be wired in a WYE (Star) configuration as shown in the figure. Voltage input leads should be protected by circuit breakers or fuses at their source. If the power rating of the PT’s is over 25 Watts, secondary fuses should be used. Wiring and polarity marks must be exactly as shown for correct operation.
2–4
Chapter 2
PT an
ing Connections
Installation
d CT Wir
Continued
Connection for Three Phase Delta, 3 Wire Systems with 3 PT’s & 3 CT’S
When configured for ungrounded (floating) Delta operation, the LSM senses the L–L voltages between each of the phases. The “Voltage Mode” of the LSM should be set to “2” (as described in Chapter 3, “General Operation”). Figure 2.3 shown on Page 2–9 provides the wiring diagram for this configuration. Wiring and polarity marks must be exactly as shown for correct operation.
Connection for Three Phase Open Delta, 3 Wire Systems with 2 PT’s & 3 CT’S
When configured for ungrounded or Open Delta operation, the LSM senses the L–L voltages between each of the phases. The “Voltage Mode” of the LSM should be set to “4” (as described in Chapter 3, “General Operation”). Figure 2.4 shown on Page 2–10 provides the wiring diagram for this configuration. Wiring and polarity marks must be exactly as shown for correct operation.
Connection for Three Phase Open Delta, 3 Wire Systems with 2 PT’s & 2 CT’S
When configured for ungrounded (floating) Open Delta operation, the LSM senses the L–L voltages between each of the phases. The “Voltage Mode” of the LSM should be set to “4” (as described in Chapter 3, “General Operation”). Figure 2.5 shown on Page 2–11 provides the wiring diagram for this configuration. Wiring and polarity marks must be exactly as shown for correct operation.
Neutral Connection
The voltage reference terminal, “Neutral”, of the LSM serves as the zero voltage reference for voltage readings. A low impedance Neutral connection is essential for accurate measurement. The length of the wire should be as short as possible. It should be made using a dedicated size 2.0 mm AWG) wire, or larger, to a point in close proximity to the LSM. This will provide minimal voltage error due to other distribution voltage drops.
The connection point for “Neutral” is the point where the PT secondary leads are common.
2
(14
2–5
Chapter 2
Installation
Current Transformer Connections
The LSM is equipped with four CT inputs, designated I1 – I4. Inputs I1 – I3 are used to measure the current in the synchronizing circuit. These inputs are wired as shown on Pages 2–7 through 2–11 in Figure 2.1 through Figure 2.5. Input I4 is optional and is typically used to measure current in the neutral or ground conductor. The primary rating for I4 can be different than the primary rating for transformers I1 – I3. However, the secondary rating for all of the CT’s must be 5 Amps.
Current connections may remain unused for a system that only performs synchronization. Unused terminals should be wired to chassis ground for noise immunity.

Maintenance

Calibration

Field
Service Considerations
The LSM does not require any special maintenance.
The calibration interval for the LSM depends on the user’s accuracy requirements. To meet general operating requirements, regular calibration is not necessary.
Contact your nearest Allen–Bradley Sales Office for calibration or service information.
If the LSM requires servicing, please contact your nearest Allen-Bradley Sales Office. To minimize your inconvenience, the initial installation should be performed in a manner which makes removal easy.
1. A CT shorting block should be provided to allow the LSM current inputs
to be disconnected without open circuiting the user supplied CTs. The shorting block should be wired to prevent any effect on the external protective relays.
2. All wiring should be routed to allow easy maintenance at connections to
the LSM terminal strips, the swing-arm, and the LSM itself.
2–6
ATTENTION: A CT circuit must not be opened with primary current present.. Wiring between the CT’s should include a
!
terminal block for shorting the CT’s. Open CT secondaries will produce hazardous voltages, which can lead to personal injury or death, property damage, economic loss or CT failure.
Chapter 2
Installation
Synchronizing
L1 L2 L3 N
CT
CT
Bus V
oltage
CT
Fuse
Fuse
Fuse
Figure 2.1
PT
PT
PT
– Wiring Diagram for 4–Wire Wye Connection
Customer Supplied CT Shorting Switch or T
est Block
Load Share Circuit
1
L3+
2
L3–
3
L2+
4
L2–
5
L1+
6
L1–
7
Neutral +
Neutral –
8
A
Load Share +
0
Load Share –
LSM
CT Terminal Block
LSM
Swingarm
Reference Bus V
L1 L2 L3 N
oltage
Fuse
Fuse
Fuse
PT
PT
PT
NOTE: See Appendix E for CE compliant wiring requirements.
Customer Chassis Ground
1
Load Share Shield No Internal Connection
2
Synchronizing Bus V3
3
Synchronizing Bus V2
4
Synchronizing Bus V1
5
Neutral
6
Reference Bus V3
7
Reference Bus V2
B
Reference Bus V1
2–7
Chapter 2
Installation
Synchronizing
L1 L2 L3
CT
Bus V
CT
oltage
CT
Fuse
Fuse
Fuse
Figure 2.2
PT
PT
PT
– Wiring Diagram for 3–Wire Wye Connection
Customer Supplied CT Shorting Switch
est Block
or T
1
4
5
6
7
Load Share Circuit
A
L3+
2
L3–
3
L2+
L2–
L1+
L1–
Neutral +
Neutral –
8
Load Share +
0
Load Share –
LSM
CT Terminal Block
LSM
Swingarm
2–8
Reference Bus V
L1 L2 L3
oltage
Fuse
Fuse
Fuse
PT
PT
PT
NOTE: See Appendix E for CE compliant wiring requirements.
Customer Chassis Ground
1
Load Share Shield No Internal Connection
2
Synchronizing Bus V3
3
Synchronizing Bus V2
4
Synchronizing Bus V1
5
Neutral
6
Reference Bus V3
7
Reference Bus V2
B
Reference Bus V1
Chapter 2
Installation
Synchronizing
L1 L2 L3
CT
Bus V
CT
oltage
CT
Fuse
Figure 2.3
PT
– Wiring Diagram for 3 Transformer Delta Connection
Customer Supplied CT Shorting Switch or T
est Block
1
2
3
4
5
6
7
8
L3+
L3–
L2+
L2–
L1+
L1–
Neutral +
Neutral –
CT Terminal Block
LSM
Reference Bus V
L1 L2 L3
oltage
Fuse
Fuse
Fuse
Fuse
Fuse
PT
PT
PT
PT
PT
NOTE: See Appendix E for CE compliant wiring requirements.
Customer Chassis Ground
Load Share Circuit
A
0
1
2
3
4
5
6
7
B
LSM
Swingarm
Load Share +
Load Share –
Load Share Shield No Internal Connection
Synchronizing Bus V3
Synchronizing Bus V2
Synchronizing Bus V1
Neutral
Reference Bus V3
Reference Bus V2
Reference Bus V1
2–9
Chapter 2
Installation
Synchronizing
L1 L2 L3
CT
Bus V
CT
oltage
CT
Fuse
Figure 2.4
PT
– Wiring Diagram for 2 Transformer Open–Delta Connection
Customer Supplied CT Shorting Switch or T
est Block
1
2
3
4
5
6
7
8
L3+
L3–
L2+
L2–
L1+
L1–
Neutral +
Neutral –
LSM
CT Terminal Block
Reference Bus V
L1 L2 L3
oltage
Fuse
Fuse
Fuse
PT
PT
PT
NOTE: See Appendix E for CE compliant wiring requirements.
Customer Chassis Ground
Load Share Circuit
A
0
1
2 3
4
5
6
7
B
LSM
Swingarm
Load Share +
Load Share –
Load Share Shield No Internal Connection
Synchronizing Bus V3
Synchronizing Bus V2
Synchronizing Bus V1
Neutral
Reference Bus V3
Reference Bus V2
Reference Bus V1
2–10
Chapter 2
Installation
Synchronizing
L1 L2 L3
CT
Bus V
oltage
CT
Fuse
Figure 2.5
PT
– Wiring Diagram for 2 Transformer Open–Delta Connection With 2 CT’
Customer Supplied CT Shorting Switch
est Block
or T
1
2
3
4
5
6
7
8
L3+
L3–
L2+
L2–
L1+
L1–
Neutral +
Neutral –
LSM
CT Terminal Block
s
Reference Bus V
L1 L2 L3
oltage
Fuse
Fuse
Fuse
PT
PT
PT
NOTE: See Appendix E for CE compliant wiring requirements.
Customer Chassis Ground
Load Share Circuit
A
0
1
2 3
4
5
6
7
B
LSM
Swingarm
Load Share +
Load Share –
Load Share Shield No Internal Connection
Synchronizing Bus V3
Synchronizing Bus V2
Synchronizing Bus V1
Neutral
Reference Bus V3
Reference Bus V2
Reference Bus V1
2–11
Chapter 2
Installation
2–12
Chapter
ational
acteristics
Chapter
Oper
Objectives
Char
A–B
3
General Operation
This chapter:
introduces the user to the controls and operation
describes each function
defines operating parameters
Functional
The LSM has six different modes of operation. These modes are described below.
Configuration
Before the LSM can perform its intended functions, it must be configured by the integrator/OEM or user. Configuration is accomplished by sending the appropriate information to the module via the “Block Transfer Write” mechanism. Configuration data is compared with acceptable values. The user can obtain acknowledgment of the configuration data by using the “Block Transfer Read” mechanism for access to the module’s response. If out–of–range or illegal values were entered, an error indication that identifies the illegal or out–of–range entries is returned. If the data is acceptable, an acknowledgment indication is returned. The new configuration data is then used to scale the monitoring data and to set up the synchronization and load sharing functions.
Whenever new configuration data is sent to the LSM, all module functions (synchronization, load–sharing, and monitoring) are terminated, and the values for “Amps Demand”, “kVA Demand”, and “kW Demand” are cleared. The values for “kW Hours” and “kVAR Hours” are maintained at the values present before the new configuration data was sent. The new configuration data is then evaluated. Upon acceptance of the new configuration data, the module resumes normal operation.
A detailed description of the required configuration data follows. See “Block Transfer Communications”, on Page 4–2 in the Application Information chapter of this manual and Appendix B, “Block Transfer Tables and Discrete I/O Definition”, for a detailed description of how the module performs block transfers and how the associated data is organized.
3–1
Chapter 3
ational
acteristics
General Operation
Oper Continued
Char
Voltage Mode
This entry is used to indicate if the system being monitored is wired in a WYE, a Delta, or an open Delta. A value of “1” will indicate a WYE system, a value of “2” will indicate a three transformer Delta system, and a value of “4” will indicate a two transformer Open Delta system. Line–to–Neutral values will be provided only when a WYE is configured.
PT Primary Rating
This entry is used to indicate the primary voltage rating of the user supplied potential transformers. This information is used for scaling purposes. The value of this parameter must be between 120 and 115,000.
Line and Neutral CT Primary Ratings
These entries are used to indicate the primary ampere rating of the user supplied line and neutral current transformers. This information is used for scaling purposes. The value of this parameter must be between 5 and 10,000.
Synchronization Method
This configuration entry is used to indicate which method of synchronization is to be implemented. A value of “0” indicates the delayed acceptance window method.
3–2
ATTENTION: The following acceptance limit values must be set to fit the customer applications.
!
Voltage Match Error Upper and Lower Acceptance Limits
These entries are used to specify the upper and lower acceptance limits for matching Synchronizing Bus voltage to the Reference Bus voltage. The value is specified in steps of 0.05% and must be between 0.00 and 25.00 percent.
Frequency Match Error Upper and Lower Acceptance Limits
These entries are used to specify the upper and lower acceptance limits for matching Synchronizing Bus frequency to the Reference Bus frequency. The value is specified in steps of 0.01 Hz and must be between
0.00 and 1.00.
Chapter 3
ational
acteristics
General Operation
Oper Continued
Char
Phase Match Error Upper and Lower Acceptance Limits
These entries are used to specify the upper and lower acceptance limits for matching Synchronizing Bus phasing to the Reference Bus phasing. The value is specified in degrees and must be between 0 and 45.
Acceptance Window Delay
This entry is used for the delayed acceptance window method of synchronization. The value is specified in steps of 0.05 seconds and must be between 0.00 and 10.00.
Maximum Synchronizing Bus Output Power
This entry is used to specify the power level at which the load sharing output voltage will be at its maximum value. The ratio of the actual power output to the value of this parameter is used to adjust the load sharing output voltage. This value will be specified in kW and must be between 0 and 999,999.
Load Share Full–scale Voltage
This entry is used to specify the load share circuit’s full scale output voltage. The value is specified in steps of 0.01 volts and must be between
2.00 and 4.00.
Load Share Excess
This entry is used to specify the threshold for initiating action to decrease the Synchronizing Bus output power to the appropriate portion of the total system load. The value is a scalar quantity between 0.000 and –0.500.
Load Share Deficit
This entry is used to specify the threshold for initiating action to increase the Synchronizing Bus output power to the appropriate percentage of the total system load. The value is a scalar quantity between 0.000 and +0.500.
3–3
Chapter 3
ational
acteristics
General Operation
Oper Continued
Char
Demand Period
This entry is used to specify the desired period for demand measurement. The value is specified in minutes and must be between 1 and 99.
Number Of Demand Periods
This entry specifies the number of demand periods that should be averaged to determine the actual demand. The value must be between 1 and 15.
Synchronization
functionality of the synchronization process is based on the
The synchronization discrete outputs from the PLC–5 received via the PLC backplane. The “Initiate Synchronization” output from the PLC–5 begins the synchronization process when it is asserted. It must remain asserted during the entire process. If the initiate signal is removed, the synchronization process is terminated. In addition to the initiate signal, one of the “Auto–Synchronization”, “Check Synchronization”, or the “Permissive Synchronization” discrete outputs from the PLC–5 must be asserted. If more than one of those signals is present, the synchronization fails and the “Synchronization Failure” discrete input to the PLC–5 will be asserted.
Additional information pertaining to the cause of the failure may be obtained by reading the appropriate block transfer data from the “Synchronizing Bus Error Parameters” table. (See Appendix B, “Block T Definition”, for additional information.) If new setup information is received via block transfer while the LSM is in the Synchronization mode, synchronization is terminated. The new configuration data is evaluated and normal operation is resumed upon acceptance of the data.
ransfer and Discrete I/O
3–4
The “Auto–Synchronization” discrete output from the PLC–5 causes the LSM to issue the appropriate error signals, both continuous discrete inputs and via block transfer, to cause, via the PLC–5, the synchronizing bus voltage, frequency, and phase to align with the reference bus. Once these conditions are satisfied, the “Close Breaker” discrete input to the PLC–5 is asserted based on the synchronization configuration. In the event a “dead reference bus” condition exists, the “Synchronization Failure” discrete input to the PLC–5 is asserted. Additional information pertaining to the cause of the failure may be obtained by reading the appropriate block transfer data from the “Synchronizing Bus Error Parameters” table. (See Appendix B, “Block Transfer and Discrete I/O Definition”, for additional information.)
The “Check Synchronization” discrete output from the PLC–5 causes the LSM to function in the same manner as the “Auto–Synchronization” discrete output from the PLC–5 except it will not assert the “Close Breaker” discrete input to the PLC–5. This mode is useful for testing the system.
Chapter 3
ational
acteristics
General Operation
Oper Continued
Char
Synchronization Continued
The “Permissive Synchronization” discrete output from the PLC–5 prevents the LSM from issuing any error signals, but it asserts the “Close Breaker” discrete input to the PLC–5 if the synchronization criteria are satisfied. This mode also recognizes a “dead reference bus” condition and asserts the “Close Breaker” discrete input to the PLC–5 to allow an operator to bring the synchronizing bus on line when the reference bus has failed.
The “Enable Single Phase Synchronization” discrete output from the PLC-5 allows for single phase synchronization. In this mode, only the voltages applied to the V3 inputs of the synchronization bus and reference bus are used for synchronization. Any voltages applied to the V1 and/or V2 inputs are not used for synchronization purposes (i.e. phase rotation, dead-bus conditions and over-voltage conditions). Other than not using the V1 and V2 inputs, single phase synchronization does not change the operation of Auto, Check or Permissive synchronization functions.
Voltage Match Error = 100 (Reference Bus Voltage – Synchronizing
Bus Voltage) /(Reference Bus Voltage)
Frequency Match Error = (Reference Bus Frequency) – ( Synchronizing
Bus Frequency)
Phase Match Error = (Reference Bus Voltage Zero–cross Degrees) –
(Synchronizing Bus Voltage Zero–cross Degrees) [This calculation is performed on either both rising zero–crosses or both falling zero–crosses and the result is adjusted to provide a value between –180 degrees and +180 degrees.]
In the “Delayed Acceptance Window” method of synchronization, the “Close Breaker” discrete input to the PLC–5 is asserted after the “Voltage Match Error”, the “Frequency Match Error”, and the “Phase Match Error” have all remained continuously within their respective acceptance windows for the configured delay time, called: “Acceptance Window Delay”.
In the event the reference bus and synchronizing bus systems are opposite in phase rotation, the synchronization fails. This is indicated by the “Synchronization Failure” discrete input to the PLC–5. Additional information pertaining to the cause of the failure may be obtained by reading the appropriate block transfer data from the “Synchronizing Bus Error Parameters” table. (See Appendix B, “Block Transfer and Discrete I/O Definition”, for additional information.)
Important: While still indicated in single phase synchronization mode, phase rotation mismatch will not set the “synchronization failure” discrete input to the PLC-5.
3–5
Loading...
+ 60 hidden pages