RISCO Group GT490X User Manual

GT490X
Control Panel
Quick Start Instructions
Download the complete GT490X Engneer’s Ref. Guide at
RISCO Group UK Ltd
Tel: 0161 655 5500 Fax: 0161 655 5501
Int Tel: +44 161 655 5500 Fax: +44 161 655 5501
Technical Support Tel: 0161 655 5600
Technical Support Fax: 0161 655 5610
This Quick Start Guide gives brief installation information for the
Control Panel. RISCO Group UK Ltd reserve the right to amend the software and features
www.riscogroup.co.uk
e-mail: sales@riscogroup.co.uk
(Mon - Fri 08:30-1730)
GT490X
without prior notice.
5IN490IMQ C
PR5846 Rev1.2
IMPOR
Input: GT490X AC230V +/-10% ~50Hz 125mA Max. 35W Max Nominal Temp Range: 0 - 50°C
Humidity 70% non condensing
This equipment is intended only for use as a Security Alarm Control Panel. Adequate ventilation away from heat and humidity must be provided. The unit must be fixed securely to a non-flammable surface using suitable fixings.
All mains wiring must conform to the relevant current IEEE wiring regulations (or appropriate international regulatory standards). See Mains Supply Connection section within this manual for more detailed instructions.
All wiring must be protected from sharp or jagged edges.
All Low voltage (alarm) wiring must be to the appropriate international regulatory standards and comply to good wiring practice and should be routed away from the mains cables.
Replacement fuses should be of the same type and rating conforming to IEC 127.
The GT490X Control Panel is fitted with resettable fuses.The areas protected are Battery, Aux and Keypad. In the event of a fuse tripping or an input/ output not working, remove the source of the load and check wiring for shorts. Check any added devices for full functionality before any reconnection.
The maximum current draw from the unit for all output combinations must not exceed
the rated output.
The unit is intended for use with a suitable re-chargeable lead acid battery permanently connected to the appropriate terminals. All documentation and manuals must be thoroughly read by suitably qualified installation personnel prior to installation.
T
ANT!
GT490X Metal
For Indoor Use Only
Important Safety Information. Hazardous Voltages Inside,The unit has no user
serviceable parts inside. No User Access. Internal access should only be by suitably qualified personnel.
GT490X
Metal
The unit MUST be Earthed. It is the responsibility of the installation engineer to
ensure that the earth connection to the unit lid is good on completion of the installation or after service.
Page 1
Introduction
The GT490X Control Panel is a microprocessor based unit that has been designed to be suitable for all types of domestic and commercial installations. All zones are fully programmable by the engineer.
On power up / reset, the Control Panel can be set to the old BS or EN2 (Grade 2) operating standards. Selection for PD6662 2004 /PD6662 2010 standard can also be set at this point. (See page 10 for further details).
Upon completion of the installation the engineer may, if required, re-program several factory set options so as to tailor the Control Panel to suit the requirements of the system.
It should be noted that if the engineer code has been locked into the system it may only be changed by using the code again (default to factory settings will have no effect).
We recommend that the Installation manual and the user manual are read and fully understood before any installation of the system is carried out. This Quick Start Guide is intended for use by engineers who have experience in installing GT security equip­ment. Greater detail is given in the GT490X Manual available from our website.
Planning the Control Panel Location
Consideration in locating the fixing position of the Control Panel should be given to:
Access for the routing of cables for the system from detection devices, sounders (internal and external), remote keypads, mains, etc.
The position of the underside retaining screw.
The fixing of a 3 amp unswitched fused spur.
When fitting the RKP(s) consideration should be given to: Operation of the keypad.
The Panel should be fixed to the wall using appropriate wall plugs and No.8 screws at least 30mm long. Do not tighten the screws at this stage, wait until all your wiring is in place.
Readability of the display.
Mains Supply Connection - WARNING: Electricity can KILL
Before connecting the control panel ALWAYS disconnect the supply at the consumer unit. A 230V a.c supply should be taken directly from the consumer unit. In order to comply with the relevant current wiring regulations this should be via a 3 Amp fused spur with disconnection facility. This must be carried out by a suitably qualified electri­cian. If you are in any doubt please contact your local electricity company for advice.
This contr
ol panel MUST be Earthed.
Page 2
Output Terminal Descriptions
Speaker Terminals
This pair of terminals provide connection for:-
System Speaker(s) Optional 16/32 Ohm Panel Speaker
A speaker is supplied in each keypad. If any additional speakers are fitted they should present a minimum impedance of 16 Ohm.
PGM 1, 2 & 3 Terminals
The PGM1 & 2 terminals are an open collector output held at 12V through an integral 1k resistor. Max current sink into PGM 1 & 2 terminals is 50mA. The terminals are programmable for various uses if required.
Note: PGM3 terminal is the strobe- terminal and is only available as a
Power Supply Rating
GT490X Max. O/P current - 0.8A plus 0.123mA for batt. charge.
Sounders, detectors and other auxiliary items, including the control panel and keypad(s), should be included when calculating current drawn by the system. Any damage caused through overloading the control panel supply will not be covered by the warranty. We recommend that additional power supplies are used to supply detectors on long cable runs.
AUX 12V Terminals
This pair of terminals supply the + and - supply for the detectors. 1A available from these terminals.
Strobe Terminals
This pair of terminals are the output for the Strobe. The negative terminal is switched during an alarm period. Max current for switch is 1A.
Bell Terminals
This pair of terminals are the output for the Bell or external sounder. The negative terminal is switched during an alarm period. Max sink current for switch is 1A.
Keypads
The + and - terminals supply power to the keypads.
programmable option if the Strobe terminal is not used for the External Sounder e.g. when NovActive sounders are used.
Max current for switch is 1A.
Page 3
Remote Keypads
Up to four remote keypads may be fitted to the GT490X control panel. Each Keypad offers a 32 character backlit LCD.
A four core connection will be required between the control panel and remote key­pad(s), keypads may be in a 'daisy chain' or ‘star’ format.
Note: 680 Ohm resistor must be fitted to ONE RKP. If the RKPs are wired
Note: Each keypad must be programmed onto the system in order for it to
Note: Depending on the variant of keypad fitted external G-Tag Proximity
in daisy chain format this should be the last RKP in the line.
be recognised by the system.
Reader(s) may be fitted to each Remote Keypad.
Fig.1 RKP Connections
GT490X Control Panel
D2 D1 0V 12V
RKP
D2/B D1/A 0V 12V
680Ohm
Page 4
- + -
STROBE BELL
BELL SAB PGM1 SPR+ SPR + - HOLD TMPR AUX 12V
EXTERNAL SOUNDER
/ STROBE MODULE
INTERNAL SPEAKERS
MIN 16 OHM
Strobe - Trigger
Bell / Strobe + Hold-Off
Bell - Trigger
Bell Hold-Off - Supply
- Tamper Return
Digi Modem - The GT490X control panel feature an onboard Digi modem. The
A5INB2
IN
C3
B2 A5
Terminal 5
(on existing BT socket)
OR
Terminal A
(on BT Terminal Block)
Terminal 2
(on existing BT socket)
OR
Terminal B
(on BT Terminal Block)
A5INB2
IN
C3
B2 A5
Terminal 5
(on existing BT Master socket)
Terminal 2
(on existing BT Master socket)
Terminal 3
(on existing BT Master socket)
Terminal 5
(on other extension sockets)
Terminal 2
(on other extension sockets)
Terminal 3
(on other extension sockets)
Digi provides all the features of an eight channel communicator whilst the Modem pro­vides facilities for Gardtec Remote Upload/Download software package.
Vo-Comm - (If fitted) Is a method of transmitting signals to a standard land-line
or mobile telephone, giving information regarding the status of your security system. If On is selected, the Vo-Comm menu will now appear in the USER mode. Please refer to GT490X User Guide for further programming information.
Fig.2 Telephone Connections
Standard Telephone Connection
Serial Telephone Connection (depending on model)
Fig.3 Control Panel Output Connections
Terminal positions may differ.
Page 5
Fig.4 Typical Novagard 2G/4G Connections
+12V
0V
S-
ST-
R TMP
F TMP
BELL+
BELL-
SAB TMP
BELLHOLD-
STROBE-
N/C Devices
N/C Devices
N/C Devices
N/C Devices
N/C Devices
N/C Devices
N/C Devices
N/C Devices
6k8
6k8
4k7
4k7
4k7
4k7
4k7
4k7
4k7
4k7
Tam per Zon e
becomes Zone 9
ONLY when 9 (EOL)
is selected
4k7
N/C Devices
AZ1
+ -
AZ2
+ -
AZ3
+ -
AZ4
+ -
AZ5
+ -
AZ6
+ -
AZ7
+ -
AZ8
+ -
TZ
+ -
N/O Devices (PA etc)
connect across Tamper & Zone
N/C Devices
multiple devices are in series
N/C Devices
N/C Devices
N/C Devices
N/C Devices
N/C Devices
N/C Devices
Novagard 2G/4G
(Strobe terminals omitted)
GT490X Control Panel
Fig.5 Control Panel Input (Zone) Connections
A maximum of four detectors per
zone may be use with EOL wiring
End of Line Zone Wiring
Standard (2 Wire) Zone Wiring
Please see Page 19 for further
wiring modes where Anti-Mask
Page 6
detectors are used.
Zone Doubling (8+8)
AZ (Alarm)
2nd Detector
N/C Tamper
Contact
2nd Detector
N/C Alarm
Contact
6K8 27K
1st Detector
N/C Tamper
Contact
1st Detector
N/C Alarm
Contact
16K
RS485 (RADIO EXPANDER)
CONNECTIONS
RS485
RED BLK YEL GRN
GRN YEL BLK RED
RADIO RECEIVER
KEY ID
ZONEID1ST RECEIVER
DIP SWITCH
SETTINGS
1 2 3 4ON1 2 3 4
ON
RADIO EXPANDER WIRING & SWITCH SETTINGS
Fig.6 Zone Doubling Mode (8+8)
Zone Doubling
Detector on Zone 1 will be Zone 1 and the Doubled Zone will be Zone 9.
The first detector on Zone 2 will be Zone 2 and the Doubled Zone will be Zone 10. E.g Zone number + 8 = Zone num­ber for Doubled Zone.
The Zone triggered will be identified through the resistor value by the system.
Radio Zone Expander
One GardTec Radio Zone Expander may be fitted directly to the RS485 Bus connections on the control panel PCB without the need for any interface card. A Radio Expander card will allow eight wireless zones & eight wireless Fobs.
Radio Zone Programming
When programming Radio Zones the zone numbering for the Radio Zones will start at 91. When programming Radio Fobs the numbering of the Fobs will start at 81.
Fig.7
Page 7
Initial Power Up
When the Control Panel is powered up it will be either set or unset dependent on the state of the Control Panel when it was powered down.The factory default state will be unset.
Reset to Default Modes
Note: It is
The Control Panel is now back to factory defaults.
If you intend to program the control panel via Gardtec Remote you should default the panel using 5 5 YES NO. This will default the control panel and set-up all the remote comms options.
Two other reset modes are also available:
3 7 YES NO defaults the system and codes but leaves user names and zone descriptors intact.
1 9 YES NO defaults the Master User to 5678 and Engineer to 1234
Note: If the engineer code has been ‘Locked’ into the system resetting to
ESSENTIAL
before commencement of programming.
default modes will have no effect on the engineer code. The only way to release this state is to return the PCB to the factory (please note this is a chargeable service).
that a 4 6 Yes No reset is done to all new systems
System Programming
The system may be programmed by the engineer by use of the engineer code (1234 factory default). Other Engineer/User functions are also available to the engineer, these are as follows.
Set Unset Remove
Test Log Chime
Note: Details of the above functions are given in the User Manual.
Program Engineer Code
Programming of the Engineer Code is only possible via the Engineer Code (e.g
1234). See Engineer Programming.
Page 8
Engineer Programming Mode
Engineer Programming
To enter the engineer programming mode follow the steps outlined below:-
1. Remove all power from the system for at least 10 seconds.
2. Apply mains power to the control panel.The display will show, for example:-
3. Whilst this display is showing (the first five seconds) press for the reset required. (E.g 4 6 Yes No).
The display will then show:­This may show for several minutes.
The display will then show:-
The display may differ from the sample shown
Selecting 1:BS - Panel may be programmed to comply with the old BS4737 Standards. DD243 requirements will still apply. Selecting 2:EN2 - Panel may be programmed to comply with EN50131-1 for Grade 2 Systems. BS8243 requirements will still apply.
4. Select 2:EN2.
Note: This document assumes that 2:EN2 has been selected. If 1:BS has been chosen, please refer to GT490X Control Eng. Ref. Guide for further information. Available from the GardTec web site.
The display will show:­This may show for several minutes.
.
Page 9
GT490X xx-xx
Version
Please WAIT
Select Standard 1:BS 2:EN2
Please WAIT
The display will then show:-
Select 1: PD2004 2: PD2010
5. Select either 1 or 2 depending on which standard you require.
The display will show:-
6. Enter Engineer code. (1234 default). The display will show:-
01 Jan 00: 00: 01
Enter Authorisor
Code . . . . . .
7. Enter the Authorisor code.The Authorisor code is the Master User, (default 5678). The display will show:-
Do you want to . . Use ENGNR. Mode ?
8. Press Yes. The display will show:-
Program . . . . - - -
Zones ?
A Header is indicated by three underscores on the display.
From this point the panel is Engineer Mode and all Tampers will be disabled.
Note: At any point when three underscores are shown on the display you are
viewing a Header.You may move to the next Header by Pressing the NO Key or access the functions under the Header by pressing the YES Key.
You are able to jump to various common options when programming by entering the relevant menu numbers.With a Header showing, key in the appropriate menu number, then press Yes.
Page 10
Note: Throughout the programming routine you may use the 0 (zero) Key to
escape back one level.This does not apply when a numeric entry is expected, in this case complete the input before using the 0 Key to
escape.
Factory Default Codes:
Engineer BS / EN2 - 1234
User 1 (Master) BS/EN2 - 5678
Page 11
Available Headers & Options
Below is shown some of the Headers (menu numbers, see page 14) that are available and the options that appear under each Header.
Reference Guide for further details. The manual is available from the web site.
Program Zones...
Zone Types Zone Descriptors Zone Wiring Zone Attributes
Please refer to the GT490X Engineer’s
Program Digicom...
Digicom Type or Test Vo-Comm Digicom Delay / Part Digicom Channels
(Test/Part/Chime/Cleaner/Walk)
Zone Double Knock, Arm, Log Zone E/E Mode Zone Event Tags
Program Setting Modes...
Setting for Full Set Setting for Part 1 Set Setting for Part 2 Set Setting for Part 3 Set Setting Delay Setting Sounders Setting Confirmation Setting for Auto-Part Set
Program Entry Times...
Entry Time 1 Entry Time 2
Program Bells & Sounders...
Bell Type & NovActive On/Off Bell Delay Number of Arms Bell & Sounder Ring Bell Tamper Mode Bell in Part Set
Program Keypad...
Keypad Alert 1 Keys Keypad Alert 2 Keys Quick Key Keypad Number of Keypads Keypad Backlight Mode Ace/Prox
Digicom Functions
Digicom View Modem Log Modem Functions Comms Functions Comms Off Site ID Tel No. 1 Tell No. 2 Line Monitor Line Security Restore Reports Open / Close Channels Advanced Functions
Modem Functions
Modem Comms Off/On Modem Mode Double Ring
Keypad Lock / In-Use Text Site ID Code Password Tel No. 1 Tel No. 2 Modem Access Send Keys / Status
Program Linefault Modes...
Linefault Sounders Linefault In Exit Mode Linefault Log Mode Line Fault Detect Time
Page 12
Panic / Duress
PA Mode / Bells Only / Bells Always Silent Always / Bells if Line Fault Testable / Non-Testable PA Confirm
Off/8Hr/10Hr/12Hr/14Hr/16Hr/18Hr/20Hr.
Duress Off
(PA Confirm is defaulted to Off).
(To conform with EN standards, Duress is defaulted to Off and cannot be changed)
Program PGM 2 / 3 / Timers...
PGM2/3 Operating Mode PGM2 Mode PGM3 Mode Timer 1 On Time Timer 1 Off Time
Program Reset / Mains...
Mains Fail Delay
Alarm Reset Tamper Reset Fault Reset Alarm Restore On/Off Abort Time
Program Sounder Levels...
Chime Level Entry / Exit Level Key Beep Level
Program PGM1
PGM 1 O/P Custom Output 1- 8
Program Engineer Code...
Code Lock / Unlock
Program Service...
Mains OK 50Hz
Save Panel NVM to PTM Load Panel NVM to PTM Service Timer Time To Next Service Service Tel No. Lock-Out On/Off Engineer Mode Constant/Time
Program Custom Screens...
LCD Status Display
(To conform with EN standards, LCD Status is defaulted to Off and cannot be changed).
LED Status Display Custom Display On / Off Program Custom Text
Program Diagnostics / Log...
List Event Log Change List Diagnostics PSU Diagnostics NovActive Diagnostics PSU Test Time Change / List Test Limits Aux Volts Battery Volts On Charge Battery Volts Off Charge
Program Alarm Confirm...
Confirm Window Time Confirm On Entry Confirm Sounder Mode Confirm Reset Mode Confirm Secondary Time Confirm ET Mode Confirm Bell Mode Confirm Strobe Mode Confirm Start Delay Confirm Comms Restore Confirm Keypad Opening Confirm ACE Battery Monitor
d
Page 13
Common Options With Menu Numbers
Blue Grey Red
Brown
6K8
Brown
Blue Orange Brown
16K
Red Violet Orange
Brown
27K
Yellow Violet Red
Brown
4K7
Brown Red Orange
Brown
12K
You are able to jump to various common options when programming by
entering the relevant menu numbers.With a Header showing, key in the
appropriate menu number, then press Yes.
For a full list of Common Options please refer to the GT490X
Engineer’s Reference Guide which is available on the web site.
Menu Item
12 Full Set Setting Time / Setting Mode 22 No. of Keypads / Multi On Off / K/Switch 28 Entry Time 1 34 Digicom Type 38 Engineer Code 46 Main Fail Delay 47 Tamper / Fault Reset Mode 50 Zone Response 52 Zone (Attributes) 155 Confirm Time Window (BS8243 Section) 139 PSU Test Time
Note: If any Zones (panel or expander zones) are not used the terminals for that
Zone should be left open (no link) and the Zone should be programmed as Off
Fig.8
Resistor Colour Codes
Page 14
Programming Alarm Confirm
This section is used to program options that are relevant to BS8243. Before programming these options please take time to read the following notes that will help in your understanding of BS8243 All communications systems that require a Police URN will need to conform to BS8243. These notes intended as a guide only and should be read in conjunction with the relevant standards relating to the alarm system giving particular attention to EN50131-1and BS8243. These may be obtained from the British Standards Institute.
BS8243 options available are.
Confirm Time Window (default = 60)
This time window may be programmed between 1 and 120 minutes. To comply the required time should be between 30 and 60 minutes.
Confirm on Entry (default = On)
This option may be programmed to On or Off. If Confirm on Entry = Off then confirmed alarms to central station are disabled if the entry timer is started. If ACE or G-Tag is used then it is permissible to set this option to On.
Sounder Mode (default = Unconfirmed)
This option controls the system speakers fitted, options are confirmed or un­confirmed. If Sounder Trigger = Confirmed then internal sounder will only trigger with a confirmed alarm. If Sounder Trigger = Unconfirmed then internal sounders will trigger with un­confirmed alarms. This feature is not mandatory for BS8243
Reset Mode (default = Any)
Choose from Any or Normal. If Unconfirm = Any then any code can be used to reset an un-confirmed alarm. If Unconfirm = Normal then the programmed reset mode for alarm will still be required i.e. if alarm reset has been programmed as engineer and Unconfirm reset is Normal then an engineer reset will be required for Un-confirmed alarms.
Confirm Secondary Time Window (default = 60 minutes)
This time window may be programmed between 1 and 120 minutes we would suggest a time between 30 and 60 minutes but should typically be the same time as the confirm time window. This option affects zones that have been allocated as secondary zones only. For functionality please refer to Secondary Zones Below.
Page 15
Keypad
This controls the keypad option during Entry/Alarm, and controls whether the keypad will lock-out during entry or in an alarm condition. The option is used for BS8243 systems using G-Tag and the keypads need to lock-out in certain circumstances. Settings available are:
Always On Keypads will always be accessible
Off in Entry Keypads will be locked-out during Entry period
Off in Ent/Alm Keypads will be locked-out during Entry period or during
Default = Always On
ET (Exit Terminator) Mode (default = Set)
If ET Mode = Set then the exit terminator zone will terminate the exit procedure. If ET Mode = Door Lock and the ET zone (door lock) is operated on entry then all confirmed alarms will be disabled.
Bell Mode (default = Unconfirmed)
This option controls the bells fitted to the system, options are confirmed or un­confirmed. If Bell Trigger = Confirmed then Bell will only trigger with a confirmed alarm. If Bell Trigger = Unconfirmed then Bell will trigger with un-confirmed alarms. This feature is not mandatory for BS8243
Strobe Mode (default = Unconfirmed)
This option controls the Strobe(s) fitted to the system, options are confirmed or un­confirmed. If Strobe Trigger = Confirmed then Strobe will only trigger with a confirmed alarm. If Strobe Trigger = Unconfirmed then Strobe will trigger with un-confirmed alarms. This gives the ability to show to the keyholder from outside the premises that a previously unconfirmed alarm has is now confirmed. This feature is not mandatory for BS8243
Confirmed Start Delay (default = 000m)
May be programmed between 0 & 120 minutes (default 0). If programmed to anything other than 0 the panel cannot send confirmed signals until the time programmed has expired. This time starts when the system has set and will prevent confirmed alarms being generated in situations when a person has been accidentally locked in the building. This feature is not mandatory for BS8243
Opening (default = Always On)
alarm
Page 16
Ace Low Battery (default = On)
Options are On or Off. This option allows for the use of new control panel boards with V5.1 or later software to be used with earlier keypads. If older non BS8243 compliant type keypads are used with V5.1 or later this option should programmed to Off. It is a requirement of BS8243 that when using ACE Low Battery is reported to the end user if the system is set using ACE. See BS8243 Portable ACE used for setting and unsetting.
Secondary Zones
The Program Part / Test /Chime option has now been renamed to Program Zone Attributes. Within this section you are able to allocate zones as Secondary Zones. Secondary type zones would be used for detectors that may be deemed as having an over sensitive nature, this will stop unwanted user call-outs. Zones that are entered as Secondary will follow the chain of events below.
During a set period triggering a Secondary Zone will star t the Secondary Time Window. This will be logged but no further action is taken. If the second zone to alarm during the same set period is also a Secondary Zone then it will be logged and the Secondary Time Window will be restarted.
If the time set within the Secondary Time Window is still running and a zone that is not allocated as a Secondary Zone is triggered the event will be logged an Alarm A (un­confirmed) and Alarm B (confirmed) will be transmitted. This feature is not mandatory for BS8243.
Comms Restore
With Comms Restore turned on any outstanding alarm channels will be restored at the end of the Confirm Time Window. This feature is mandatory for BS8243
Perimeter Zones
Within the Program Zone Attribute section you are able to allocate zones as Perimeter. Zones that are entered as Perimeter will follow the chain of events below.
When activated an unconfirmed alarm will be transmitted to the central station. An output or digi channel may be programmed as perimeter (or if using Point ID a new signal type of perimeter will be sent). This will allow central station to inform the keyholder that an unconfirmed alarm has been received and is a perimeter type device i.e window backdoor etc. etc. This feature is not mandatory for BS8243.
Scenarios Relating to BS8243.
Sounder / Bell Considerations Please note careful consideration should be given when programming Confirm Sounder and Confirm Bell Modes. If both are programmed for confirmed and any of the above scenarios occur no local sounders will activate.
Page 17
Other BS8243 Notes to Consider
When a system auto re-arms with a zone in fault condition The GardTec control panel will omit the zone concerned. A signal should be sent to the central station indicating that a detector(s) has (have) been isolated. To achieve this a Digi channel should be programmed as Zone Exclude, this will automatically send the required signal as the detector is omitted.
Output Option (Status)
This option has three operating modes and is intended to provide a visual indication of the system status.
System Set Output On for 10 seconds System Unset Output On for 1s Output Off for 1s for a 10 second period Confirmed Alarm Output On for 3 seconds Output Off for 1s until system reset.
It is envisaged that this status output would be fitted to an indicator (i.e. LED) that can be seen from outside the premises.
Page 18
Typical Wiring Modes
Where Anti-Mask detectors are used, one of the below wiring modes may be utilised.
ELF1 wiring is used for detectors that have a relay output (a pair of terminals) for Fault or Mask.
The installer should check what output type the detectors are, noting that all detectors should be of the same type with regards to the Fault / Mask output.
Fig.9
Typical ELF1 (End of Line Format 1) Wiring.
ELF2 wiring is used for detectors that have a transistor output (a single terminal) for Fault or Mask.
Note: For ELF2 wiring format the 12K resistor must be linked to the positive side of the zone terminals.
Fig.10
Typical ELF2 (End of Line Format 2) Wiring.
Page 19
PD6662:2010 Update - new features
EN50131-1 2006 and BS8243
PD 6662, the document describing how the European standards for Intrusion and Hold-up Alarm systems (I&HAS) should be applied in the UK, has been completely revised. The revision takes into account the publication of a number of new, revised or amended European standards. It also adds some new standards and documents published by British Standards that add or vary requirements for alarm confirmation, commissioning and maintenance and false alarm management.
PD 6662: 2010 will replace the 2004 version when it is published but for a two year period (ending May 31st 2012) systems may be installed under either the 2004 or 2010 version of PD 6662.
The most significant changes are listed below.
Engineer Access.
Can now be turned off if the customer has agreed, (in writing). When entering the engineer menu, the panel will generate an audible sound for approximately 8 seconds to indicate that the engineer is on site, (grades 1, 2, and 3). For grades 2/3 the ATS must also send an engineer on site signal.
Confirmed PA
Confirmed PA has been added to the Control Panel menu. (Programming Panic / Panic). Please note that Confirmed PA can only be produced by activating two zones programmed as panic or a keypad panic and a Panic zone.
If Mod + FF is used, the Alarm B channel will be transmitted for PA/Intruder confirmation. If Mod + PID is used the confirmed PA will transmit E129. If Mod + SIA is used the confirmed PA will transmit HV. Note: This would normally be used on systems that have lost police response for Panic.
Page 20
Keypad disabled for 90 seconds.
The keypad will monitor the number of attempts without a valid User Code being entered. More than seven attempts will cause a keypad tamper and lock-out the keypad for 90 seconds.This will be displayed as ‘LOCK-OUT Check’ and will require a valid User Code entry to stop the sounders (only after 90 seconds). If the system was Unset only the internal sounders will operate. If the system was Set a full alarm will be generated.
Setting by digital key
Setting the system must be initiated from within the premises; when using a radio fob interaction with the keypad will be required. Setting the system with a Gtag fob must be from a keypad (not from a remote setting point) to comply with the standards for monitored alarms.
Zones on soak test.
Zones that are put on test must be indicated to the user. When setting the system the user must acknowledge this by pressing No.
Entry Procedure
As per BS8243 - 2010, Annex G. A confirmed alarm may now be generated on entry by straying off from the entry route into a normal alarm zone.
Engineer on site channel.
BS-EN50131 - 3 2006 plus A1 2009, as per 8.3.1. When an Engineer code is entered a signal is sent to the ARC indicating an engineer is on site.
New Fast format channels.
Engineer on site. PA Confirm
New Contact ID and SIA triggers.
Engineer on site = Off/On.
New option for the reset modes.
Fault Reset = +Anti / Eng code / Anti code.
Page 21
Notes
Page 22
GT490X
Loading...