REMKO CLK 80-RV User Manual

REMKO CLK 80-RV CLK 170-RV
Oil heaters
Operation · Technology · Replacement parts
Edition GB - D09
Contents
Safety notes
Unit description
Installation instructions
Safety device
Exhaust ducting
Before commissioning
Commissioning
Shutdown
Care and maintenance
Troubleshooting
Intended use
Customer service and guarantee
Environmental protection and recycling
4
5
6
7
8
9-10
10-11
11
12-14
14
15
15
15
Exploded view of the unit
Spare parts list
Electrical wiring diagram CLK 80-RV
Electrical wiring diagram CLK 170-RV
Commissioning fan oil burner
Maintenance protocol
Technical data
16
17
18
19
20-21
22
23
Carefully read this operating manual prior to commissioning / using the unit! This operating manual is a translation of the German original.
Made by REMKO
These instructions are an integral part of the unit and must always be kept in the vicinity of the installation location or on the unit itself.
Subject to modifications; no liability accepted for errors or misprints!
3
REMKO CLK 80/170-RV
Safety notes
Always observe the respective local building code and fire prevention guidelines as well as the guidelines of the accident prevention and insurance associations as a basic rule when using the unit.
The units may only be operated
by persons that have been extensively instructed in the operation of the equipment
The units must be installed
in a stable position.
The units must be installed
and operated in such a way that personnel are not endangered by exhaust, warm air and radiant heat and no fires may occur
The units must then only
be operated in areas where the units can be supplied with an adequate amount of air for the combustion
If the units are being operated
without exhaust gas routing then they may only be operated in well ventilated areas. Under such circumstances it is forbidden for personnel to remain in these areas for extended periods. Appropriate prohibition signs should be put up at the entrances
A safety zone of 1.5 m should
be maintained around the units
- incl. non-combustible items
All electrical cables for the units
must be protected against damage (e.g. by animals etc.)
The units must not be exposed
to direct jets of water, e.g.
pressure washers etc.
Portable fuel containers must
only be set up and used in observance of the technical rules for combustible liquids "TRbF 20".
Any additional conditions from
the respective regional building regulations must be observed
The protective grid of the unit's
intake must always be kept free of dirt and loose objects
Never stick foreign objects into
the units
The power plug must be pulled
out of the mains socket before the start of work on the unit as a matter of principle
Safety devices may be neither
bypassed nor disabled
The personnel tasked with
operating the units must check the units for visible defects on the operating and safety devices as well as the presence of the protective devices at the start of work.
In the case of defects that
endanger the operational safety of the unit, it must be taken out of service immediately.
ATTENTION
The units may never be disconnected from the mains prior to the completion of the follow-up cooling phase (except in emergencies).
NOTE
Only type-approved forced-air oil burners in WLE design per DIN EN 267 should be used.
The units may only be installed
on a level and non-combustible surface.
The units may not be installed
or operated in potentially flammable or explosive environments
4
NOTE
For optimum operation the units should not be operated above an ambient temperature of 25 °C.
Unit description
The units are portable, directly fired fan-assisted heaters (WLE) with heat exchanger and exhaust gas connections exclusively for commercial applications.
The units are directly fired with EL heating oil or Diesel fuel.
The units can be operated with or without exhaust gas pipe (depending on the conditions on the customer's side). They have been designed for universal and straightforward use.
The units must be exclusively operated with separate type­approved forced-air WLE-type burners.
The units are equipped with a noise-optimised and low­maintenance, high performance radial fan, a room thermostat receptacle and a mains cable with a 230 V shock-proof plug or CLK 170-RV with 400 V CEE connector.
The CLK 170-RV units are equipped with a device for automatically checking the turning direction of the fan motor, as standard.
With factory fitted forced-air oil burners the CLK 170-RV units have integrated REMKO Multiflex oil pre-heating fitted as standard. With the CLK 80-RV this is available as an option (EDP no. 1071411) .
The units conform to the fundamental health and safety requirements of the appropriate EU stipulations and are simple to operate.
Operating sequence
If the units are set to heating mode, then the forced-air burner starts automatically. In fully automatic heating mode with room thermostat the forced-air burner starts only when heat is required.
After the burner has run for a short time the temperature controller "TR" (target temperature ca. 40°C) switches the supply air fan on automatically. Warm air is blown out.
When operating with a room thermostat this process is repeated automatically depending on the heat demand.
The temperature monitor "TW" (target temperature 80 to 85°C) monitors the internal temperature of the unit.
After switching off the units via the operating switch or the room thermostats the supply air fan runs to cool the combustion chamber with the heat exchanger for a certain time and then switches off automatically. This process may be repeated several times if necessary, depending on the temperature profile.
In simple ventilating mode the unit can be used to recirculate the air permanently. Thermostatic control is not possible in this case.
Locations at which units are used
As mobile, directly fired fan­assisted heaters, the units deliver instant heat. They are designed exclusively for commercial use, with and without warm air hoses.
The units may be used for the heating, temperature adjustment or drying of:
Warehouses
Exhibition halls
Trade fairs
Lightweight construction halls
Large tents / marquees
Large construction sites
Building drying
5
REMKO CLK 80/170-RV
Installation instructions
The safety regulations of the accident prevention and insurance associations, the respective regional building regulations and the combustion appliances regulations apply in principle to the operation of the unit.
NOTE
Overpressure and underpressure in the installation area should be avoided as this will inevitably lead to combustion-related faults.
Make sure that there is an
adequate fresh air supply appropriate to the respective forced-air burner capacity (see name plate). The forced-air oil burner may need to be fitted with a separate air supply for combustion
Installation in closed, well ventilated areas without exhaust gas connection
The operation of the units
is permissible if the minimum air quantity for combustion is supplied.
Reliable extraction
of the combustion gases must be guaranteed in all cases in order to exclude impermissible contamination of the room air with hazardous
substances. Fresh air is fed from below. Exhaust gases are routed
upwards.
It is forbidden for personnel
to remain in these areas for
extended periods.
Appropriate prohibition
signs should be put up
at the entrances
Room heating
The units may only be operated
for room heating with a room thermostat (accessory)
The fresh air supply required for
trouble-free combustion must be guaranteed. It is practical to have the fresh air supply provided by windows and doors or through appropriately dimensioned openings in the outside wall
The exhaust gases must be fed
to the outside via the flue gas pipes.
Safety distances
In order to guarantee safe
operation and maintenance of the units, 1.5 m safety distance should be maintained around the unit.
Installation outside
The operation of the units
must not present a hazard or unreasonable loading
The unit operator must ensure
that it is not possible for unauthorised persons to be able to manipulate either the unit or the power supply.
The unit must be protected
from unauthorised use
Precipitation such as rain
or snow can be sucked in through the supply air fan. For this reason suitable weather protection should be provided.
ATTENTION
The units must only be
installed in well ventilated
spaces and not in living areas
or similar recreational areas.
Flooring and ceilings must
be fire retardant
Intake and outlet diameters
must not be narrowed or blocked with foreign objects.
6
Safety equipment
Safety temperature limiter (STB)
The heating function is permanently interrupted by the safety temperature limiter (STB) in the event of the units overheating or malfunctioning.
Manually resetting of the STB can only be implemented after the units have cooled down.
The resetting of the STB is implemented by actuating the reset button 2.
ATTENTION
If the safety temperature limiter has been tripped then the cause of the malfunction should be identified and rectified before resetting it.
Regulating device
The temperature sensor of the controller is self-monitoring. The probes are cold-resistant to -25 °C. At temperatures below -25 °C the controller current flow will be interrupted - if the temperature rises above -25 °C the current flow will be released again.
In the event of the probe or the capillary tube being damaged, as well as if an overtemperature of ca. 220 °C is reached, the fill medium will be emptied and the safety device is permanently triggered. Resetting is no longer possible. The controller is no longer fully functional and must be replaced.
The units have the following control or safety equipment:
Temperature controller (TR)
The temperature controller controls the switching on and off of the recirculating fan. The switch point is set via the "Scale 21 - 60°" controller in the switching cabinet. Target value ca. 35 - 40 °C.
Temperature monitor (TW)
The temperature monitor limits the unit or outlet temperature in heating mode via the burner. The switch point is set via the "Scale 34 - 110°" controller in the switching cabinet. Target value ca. 80 - 85 °C.
1. Unscrew protective cap [1].
2
1
2. Carefully press in the reset button [2] with a suitable tool.
3. Screw the protective cap [1] back on again.
ATTENTION
Safety devices may be neither bypassed nor disabled.
NOTE
NOTE
Only
"REMKO original
replacement parts"
be used when replacing safety devices.
Ensure that the device is fitted
properly
The capillary tubes must
not be kinked or bent in the immediate vicinity of the soldering points
The capillary tubes must not
be damaged or kinked during installation
The probes must only be fitted
at the fastening points provided by the factory
must
Safety temperature limiter (STB)
The unit is permanently switched off by the safety temperature limiter (STB) in the event of the unit overheating or a temperature monitor malfunction. Manual resetting is required.
Automatic burner
The unit is permanently switched off by the automatic burner through the optical flame monitoring in the event of irregularities in the combustion, the flame extinguishing, fuel deficiencies etc. Manual resetting is required.
In order to prevent a renewed exceedance of the triggering temperature the operating conditions of the unit should be checked before resetting the STB.
The probes must always
be free of dust and dirt in order to be sure of their correct functioning
7
REMKO CLK 80/170-RV
Exhaust ducting
It is also possible to operate the units outside or in open rooms / halls without exhaust gas routing. However, we recommend fitting a 1m exhaust gas duct with a rain hood on top (example 2), in order to exclude the ingress of rainwater and dirt. If the units are used for room heating then the combustion gases must be routed away, to the outside if necessary.
The exhaust gas routing must
be designed such that the thermal lift of the exhaust gases is guaranteed at all times
Die The exhaust gas routing
must be designed such that there can be no counter­pressure
Fault-free operation
is guaranteed if the exhaust gas routing is fitted in a rising arrangement and with a vertical end pipe
The exhaust gas routing should
end at least above the height of the eaves but ideally above the height of the ridge, in order to prevent any counter-pressure being caused by poor weather conditions (e.g. wind)
The minimum distance of 0.6 m
to combustible parts must not be infringed
Exhaust gas ducting parts
and fastening materials are available as accessories
All parts of the exhaust gas
routing must be reliably fastened. Its diameter must not be smaller than the outlet nozzle of the unit.
ATTENTION
There must be no counter pressure arising from incorrect installation of exhaust gas ducting under any circumstances.
Notes for implementing the 1st. BImSchV
Units that are not expected to be operated for longer than 3 months in the same location are not subject to any approvals or monitoring per the 1st. BImSchV. (§1, section 3)
Example 1
Operation with extended exhaust gas ducting
Condensate trap required.
Max. 1 metre
Example 2
Operation without extended exhaust gas ducting.
Max. 1 metre
More than 1 metre
Example 3
Impermissible arrangement
In order to avoid the combustion chamber being damaged due to condensation of moisture (condensate) in example 3, make sure that the exhaust gas ducting is correctly installed with a condensate trap as shown in example 1.
NOTE
After installing an exhaust gas system the settings on the burner should be adapted to suit the new conditions.
8
Before commissioning
The units should be checked for visible defects on the operating and safety devices as well as proper installation and correct electrical connections before commissioning.
It is essential that the following points be observed:
The units must be installed
in a stable position
Ensure there is sufficient supply
of combustion air
Check that the inlet and outlet
are free
Prevent overpressure
or underpressure in the installation area
Ensure that there is sufficient
fuel supply and that it complies with the respective local regulations
Only use clean EL heating oil or
Diesel fuel. Do not use Bio-
Diesel!
The suction pipe in the base
of the tank must be fitted with a foot valve as a matter of principle
NOTE
After fulfilling the respective local regulations as well as a professional installation of the unit, the exhaust values for the forced-air burner must be checked and adjusted if necessary by authorised specialists.
NOTE
Air feeds on the intake side must always be implemented by means of non-distorting hoses/ducts (no unstable hoses).
Air distribution
The units are equipped with a high performance radial fan, which has been designed to transport the heated air efficiently and effectively over large distances.
The distribution of the air is preferably implemented via ducting or special warm air or membrane hoses.
Use hot air hoses approved
by us (accessories) exclusively
Observe the air flow direction
of the hoses with this! The inner overlapping on the seams of the hot air hoses must point in the direction of the air flow.
Make sure that the hose
or ducting is securely fastened onto the unit outlet nozzle and any connection pieces that may be being used
Only suitable air distributors
or air distributors approved by ourselves should be used for the air distribution
NOTE
The hot air hoses must only be used in fully extended form and without any constrictions.
Enclosed spaces being heated
via hoses must not present any overpressure
The forced-air burner can
be switched off briefly during operation by the temperature monitor (TW) in the event of there being increased intake temperatures or resistance at the unit's outlet.
After the temperature drops again the burner starts anew automatically!
If the cycle intervals are too
short the length and layout of the hot air routing should be checked
NOTE
Cycled operation of the forced-air burner with run times under 5 min. should certainly be avoided.
There should be no kinks
or bends in the layout of the hoses in order to prevent hot­spots forming. Membrane hoses must not be twisted
ATTENTION
If a build-up of heat should occur then the heating operation will be interrupted by the STB permanently.
Suction air
Fresh air, mixed air or circulated air operating modes can be selected on the unit. The following information refers to the installation of the unit outside the space to be heated.
Fresh air operation:
The air intake is implemented in the factory through 2 intake grills, right / left.
Mixed air operation:
For operation of the unit in mixed air mode it is necessary to fit the intake nozzles, available as accessories. In order to guarantee adequate air throughput the second intake grill must not be covered.
Circulated air operation: For operation of the unit
with 100% recirculated air it is necessary to fit two intake nozzles, available as accessories, in place of the 2 factory-fitted intake grills.
9
REMKO CLK 80/170-RV
s
s
s
Commissioning
Paraffin formation with low outside temperatures
Even at low outside temperatures it is necessary to ensure that there is an adequate supply of heating oil that is capable of flowing.
Paraffin formation can start
with temperatures as high as 5 °C
To avoid this appropriate
preventative measures must be implemented. e.g. Winter-proof EL heating
oil or winter Diesel, heated oil tank, insulated oil lines etc.
Note that fault-free operation
of the Multiflex oil pre-heating can only be guaranteed if the unit has been supplied with electrical power for a long period of time before starting
It is not possible to rectify
paraffin separation that has already occurred with the heating. If paraffin has already formed it is necessary to clean out the complete fuel system
NOTE
Paraffin formation can start with temperatures as high as 5 °C. To avoid this appropriate preventative measures must be implemented, e.g. winter Diesel.
One person, who has been adequately trained in the handling of the unit, should be tasked with the operation and monitoring of the unit.
Connecting the units with the electrical power supply
The electrical connection is made using a built-in mains cable with plug.
1. Move the operating switch to the "0" (off) position.
2.
Connect the power plug
with a properly installed and appropriately safeguarded mains socket
400V/3~N/50Hz .
3. Open all of the oil supply shut-
off devices.
With the initial commissioning, air in the lines can lead to a fault shut-down of the burner.
NOTE
The electrical connection for the units must be made at a separate feedpoint with a residual current device in accordance with VDE 0100, Section 55.
ATTENTION
All cable extensions must only be used in fully un-reeled or reeled off condition.
NOTE
The 400V version of the unit is equipped with a device for automatically checking the turning direction of the fan motor, as standard.
230V or shock-proof
Control panel
8765
1 = Thermostat receptacle
2 = Strapping plug
5 = Operating switch
6 = Indicator light "GREEN" "Operation"
7 = Indicator light "RED"
"Burner fault"
8 = Reset button "Burner"
9 = Mains cable with plug
Heating without room thermostat
The units are operating in permanent operating mode.
1. Connect the strapping plug supplied [2] with the thermostat receptacle [1] on the unit.
1
2
2. Move the operating switch to the "I" (on) position.
2
1
9
10
Shutdown
Heating with room thermostat
(Accessories)
The units operate fully automatically and exclusively in accordance with the room temperature.
1. Pull out the strapping plug [2].
2. Connect the room thermostat [4] plug [3] with the thermostat receptacle [1] on the unit.
1
3
3. Place the room thermostat [4] at a suitable location in the room. The thermostat sensor must not be located directly in the warm air flow and should also not be placed directly on the cold floor.
4. Set the desired temperature on the room thermostat [4].
4
5. Move the operating
switch to the "I" (Heating) position.
Ventilate
In this switch position the supply air fan runs permanently. The units can be used for air recirculation or ventilation purposes.
1. Move the operating switch to the "II" (Ventilate) position.
Thermostatic control as well as heating operation is not possible in this operating mode.
NOTE
Indicator light "Operation"
The indicator light signals the "Heating" operating mode. There is no display in the "Ventilate" operating mode or with the room thermostat switched off and when the STB has been triggered.
ATTENTION
The thermal overcurrent relay must be operated exclusively in the "Manual resetting" position. It is not permitted for the relay to be able to switch itself back on again after the cooling down phase.
1. Move the operating switch to the "0" (off) position.
2. Shut off fuel supply.
3. With longer periods of inactivity, disconnect the units from the mains power supply.
The supply air fan runs on to cool the combustion chamber and the heat exchanger and only switches off after the cooling down phase is complete. The fan can switch on and run several times before the final shutdown.
ATTENTION
Never interrupt the power supply prior to the completion of the follow-up cooling phase. There is no warranty claim for damage to the units from overheating.
The unit starts automatically after a brief burner pre-ventilation if heat is required and then runs fully automatically.
NOTE
If the overcurrent relay is operated in the "Automatic resetting" position, then motor damage cannot be excluded.
Guarantee claims are voided!
NOTE
The burner setting should be checked after every change of location and adapted to the new environmental conditions and atmospheric conditions if necessary.
11
REMKO CLK 80/170-RV
Care and maintenance
Regular care and observation of some basic points will ensure trouble-free operation and a long service life.
ATTENTION
The power plug must be pulled out of the mains socket before the start of work on the unit as a matter of principle.
NOTE
Adjustment and maintenance work may only be carried out by authorised qualified technicians.
Keep the units free of dust
and other debris
Only clean the units with a dry
or moistened cloth
Never subject to direct jets
of water.
such as a high-pressure cleaner etc.
Never use abrasive or solvent-
based cleaners
Use only suitable cleaners for
heavy contamination
Only use clean EL heating oil
or Diesel fuel.
Watch for paraffin formation!
Check the fuel filter for
contamination at regular intervals. Replace contaminated filters immediately
Check the units for mechanical
damage and have defective parts properly replaced
Check the fan blades and
combustion chamber with heat exchanger for contamination at regular intervals and clean these if necessary
Check the on-site oil tank
regularly for contamination and foreign bodies and clean this if necessary
Inspect V-belt pre-tensioning.
The press-down deflection depth for the V-belts should be ca. 10 mm (a thumb width)
Check that the safety devices
are operating correctly at regular intervals
Keep the probes for the safety
devices free of dust and dirt
Have the exhaust gas values for
the forced-air burner checked by authorised specialists at regular intervals. For safety reasons we recommend the conclusion of a maintenance contract.
Observe maintenance and care
intervals
Cleaning tasks
The units, including the heat exchanger, combustion chamber and forced-air burner must be cleared of dust and dirt after every heating period, or possibly earlier depending on the operating conditions. Wearing parts, such as exhaust gas suppressors, seals, V-belts, oil filter inserts and oil nozzles for example, should be checked and replaced if necessary.
Cleaning the heat exchanger
1. Set the operating switch to the "0" position and remove the power plug from the mains socket.
2. Take off the exhaust hood [1] after removing the 4 fastening screws. Hot air hoses present need not necessarily be removed.
3. Remove the inspection cover [2] and withdraw the exhaust gas suppressors 4.
4.
Clean the flue [5]. A special cleaning brush is available as an accessory with EDP no. 1103110.
4 3 2 15
5. Clean the exhaust gas suppressors or replace damaged exhaust gas suppressors.
6. Check the seal [3] for the inspection cover and replace any damaged seals.
7. After the maintenance work is complete all parts should be carefully re-fitted in reverse order.
NOTE
Always check that the seal is correctly seated in the inspection cover.
When fitting the inspection cover ensure that the fastening screws are tightened evenly.
12
Cleaning the combustion chamber
1. Set the operating switch to the "0" position and remove the power plug from the mains socket.
2. Remove the burner cladding [1] after opening the two quick couplings [2].
3. Loosen the 2 lower fastening screws on the burner flange [6].
4. Loosen the clamping screw [7] on the burner flange 6 and withdraw the burner towards the front.
5
Installation of the burner flange and the burner
X
7
6
Burner CLK 80-RV: X = 20 mm Burner CLK 170-RV: X = 30 mm
1. Check the flange seal and replace if necessary.
2. Fasten the burner flange to the unit housing with the four fastening screws. Note the "UP" marking!
3. Tighten the top 2 fastening screws firmly.
Additional notes for unit maintenance
All work must be carried out
exclusively by authorised specialists with the appropriate equipment. A log should be created and kept safely by the operator
It is essential that the forced-air
burner is serviced and adjusted by authorised specialists
ATTENTION
Repair work on the electrical installation and on the burner must be performed exclusively by authorised specialists for safety reasons.
3
6
4
2
1
5. Withdraw the burner and carefully set it down beside the unit.
6. Remove the burner flange [6].
7. Take care not to damage the flange seals, as far as is possible.
Damaged flange seals can result in incorrect air induction.
8. Clean the combustion chamber through the burner opening with a vacuum cleaner. A special boiler cleaning set for the REMKO industrial vacuum cleaner is available as an accessory.
4. Tighten the lower 2 fastening screws gently and with only light force so that the burner flange can still be pulled together.
5. Slide the flame tube of the burner into the burner flange.
Observe dimensions in the sketch!
6. Clamp the flame tube firmly into place with the clamping screw [7] whilst lifting the burner slightly (3° tilt).
7. Lastly, tighten the bottom 2 fastening screws firmly.
8. Check the fuel filter insert [3] for leaks and replace if necessary.
9. Re-fit burner cladding and fasten with the quick couplings.
ATTENTION
An electrical safety check must be carried out in accordance with VDE 0701 after any work on the units.
NOTE
The restrictions on exhaust gas losses per §11 of the ordinance on small furnace systems (1st. BImSchV) must be observed.
s
s
s
13
REMKO CLK 80/170-RV
s
s
s
Troubleshooting
Tensioning the V-belt
1. Remove the two side air intake grills.
2. Loosen the screws (size 13) [7]. The screw on the opposite side is not shown.
3. Set the pre-tension of the V-belt with the (size 17) nuts [8] and [9].
4. The press-down deflection depth for the V-belts should be ca. 10 mm, width"
5. Counter-lock the nuts [8] and [9] again and then tighten the two fastening screws [7] again.
6. Re-fit the two air intake grills.
8
9
The press-down deflection depth for the V-belts should be ca. 10 mm (a thumb width).
.
NOTE
"a thumb
7
ATTENTION
Before undertaking any work on the units, the power plug must be removed from the mains socket.
The unit does not start
1. Check power supply. 400 V/3~N/50Hz.
2. Move the operating switch to the "I" (Heating) position.
3. The "Operating" indicator light on the control panel must illuminate.
4. Check the strapping connector or the room thermostat plug, if fitted, is seated properly and making good contact.
5. Check the setting of the room thermostat. The temperature set must be higher than the current room temperature.
6. Check whether the safety temperature limiter (STB) has tripped. To do so, remove the protective cap next to the control panel.
7. Before an STB reset ensure that the causes have been analysed and rectified. The following causes are possible:
- The units were not able to cool
down because the electrical connection was interrupted.
- Too high an outlet temperature
due to incorrectly implemented air routing when operating with hoses.
- Air inlets or outlets are not free
or are inadequate.
9. Move the operating switch to the "II" (Ventilate) position. If the supply air fan now starts up the fault may well be in the burner area.
Forced-air burner and power supply
1. Check the oil filter(s) for contamination. Replace contaminated oil filter(s).
2. Check whether the shut-off cock on the oil filter is open.
3. Check the fuel tank for sufficient fuel level.
4. Check the heating oil for paraffin separation.
Possible from 5 °C!
5. Check the oil hoses for damage.
6. Check the safety devices' capillary tubes and probes for damage or contamination.
7. Use appropriate means to check that the temperature monitor (TW) is functioning properly.
8. Check the forced-air burner for possible damage to the nozzles, baffle plate, filter etc.
The supply air fan does not start
1. Check the fan can move freely.
2. Check the controller fuse in the switching cabinet.
3. Check whether the motor protection switch in the switching cabinet has tripped.
4. Use appropriate means to check that the temperature controller (TR) is functioning properly.
14
8. Check whether the "Burner fault" indicator light on the control panel is illuminated. If this is the case, then reset the automatic burner.
Intended use
The units are designed exclusively for heating and ventilation purposes in industrial or commercial use (no living space heating in private use) on the basis of their structural design and equipment.
The units must only be operated by appropriately instructed personnel.
With non-observance of the manufacturer's specifications, the respective local legal requirements or after arbitrary alterations to the units, the manufacturer shall not be liable for resulting damages.
Customer service and Guarantee
As a prerequisite for any guarantee claims to be considered, it is essential that the ordering party or its representative complete and return the "certificate of guarantee" to REMKO GmbH & Co. KG at the time when the units are purchased and commissioned.
The units were tested at the factory several times to verify their correct function. However, if malfunctions should arise that cannot be remedied by the operator with the assistance of the troubleshooting section, please contact your specialist dealer or contractual partner.
Environmental protection and recycling
Disposing of packaging
When disposing of packaging material, please consider our environment. Our units are carefully packed and delivered in sturdy transport packaging made from cardboard and on a wooden pallet. The packaging materials are environmentally-friendly and can be recycled. By recycling packaging materials, you make a valuable contribution to the reduction of waste and conservation of raw materials.
Therefore, only dispose of packaging material at appropriate collection points.
NOTE
Operation other than the types listed in this operating manual is prohibited. With non-observance, any liability and claim to guarantee expire.
!
ATTENTION
Copyright The redistribution, even in part, or the use of this documentation for purposes other than intended is strictly prohibited without the written authorisation of
REMKO GmbH & Co. KG
NOTE
Adjustment and maintenance work may only be carried out by authorised qualified technicians.
Disposal of the old unit
The manufacturing process for the units is subject to continuous quality control.
Only high-grade materials are processed, the majority of which are recyclable.
You also contribute to environmental protection by ensuring that your old equipment is only disposed of in an environmentally-friendly manner.
Therefore, only bring the old unit to an authorised recycling business or to an appropriate collection point
.
15
REMKO CLK 80/170-RV
Exploded view of the unit
41
47
48
40
55
60
54
61
8
62
42
60
50
52
53
51
36
1
44
43
2
3
60
35
61
62
Temperature probe
34
4
46
5
33
32
46
69
70
71
72
68
67
61
REMKO Multiflex oil pre-heating, serial with CLK 170-RV with factory­fitted oil burner.
66
38
20
28
21 22
23
27
6
30
7
9
24
10
12
REMKO 2-strand oil filter,
Serial with CLK 80-RV with factory-fitted oil burner.
11
13
31
45
12
25
26
16
We reserve the right to modify the dimensions and design as part of the ongoing technical development process.
Spare parts list
No. Description CLK 80-RV CLK 170-RV
01 Cover panel 1104740-1 1104851 02 Upper insulation 1104741-1 1104852
03 Insulation right / left 1104742 1104853 04 Upper side cover (right / left) 1104743 1104854 05 Lower side cover (right / left) 1104744-1 1104855 06 Lower insulation 1104746 1104872 07 Base tray, front 1104745 1104856 08 Base tray, rear 1104836 1104857 09 Support foot 1104790 1104790 10 Front wall cmpl. 1104755 1104858 11 Front wall insulation 1104756 1104786 12 Guide bracket 1104757 1104787 13 Hose pass-through 1104722 1104722 20 Multiflex oil pre-heating, compl. 1071411 1071411 21 O-ring 1108464 1108464 22 Filter insert 1108462 1108462 23 Oil filter cup 1108463 1108463 24 Oil filter, compl. 1002526 — 25 Outlet nozzle 1104758 1104788 26 Burner cladding cmpl. 1104759 1104789 27 Axle 1104760-1 1104791 28 Wheel 1108369 1108369 30 Combustion chamber, cmpl. 1104761-2 1104806-2 31 Exhaust gas suppressor (set) 1104793 1104810 32 Inspection cover 1104763 1104794 33 Seal for inspection cover 1104764 1104795 34 Sealing cap 1104728 1104784 35 Centre wall 1104841 1104862 36 Intake grill, right / left 1104842 1104863 40 Back wall 1104843 1104864 41 Switching cabinet cmpl. 1104783-1 1104865 42 Seal for switching cabinet 1104754 1104866 43 Crane eye 1102554 1102554 44 Exhaust gas nozzle collar 1104732 1104796 45 Transportation bracket, front 1104765 1104867 46 Transportation bracket, middle 1104767 1104868 47 Transportation bracket, rear 1104766-1 1104869 48 Spacing roller 1104849 1104849 50 Radial fan 1108603 1108607 51 Fan belt pulley 1113111 1102777 52 V-belt 1113112 1102774 53 Motor belt pulley 1113110 1102784 54 Electric motor IE2 1102737 1102733 55 Motor bracket with clamp 1104850 1104870 60 Temperature controller (TR) 1103166 1103166 61 Safety temperature limiter (STB) 1101197 1101197 62 Temperature monitor (TW) 1103146 1103146 66 Operating switch 1101188 1101188 67 Indicator light, green (Operation) 1105514 1105514 68 Indicator light, red (Burner fault) 1105363 1105363 69 Reset button (Burner) 1103408 1103408 70 Thermostat receptacle 1101018 1101018 71 Strapping plug 1101019 1101019 72 Mains cable with plug 1104701 1105100
Not shown Not shown Not shown Not shown Not shown
Burner connector, 7-pole 1102537 1102537 Drum fitting, cmpl. 1002544 1002544 Cleaning brush, cmpl. 1103110 1103110 Locking ring 1101622 1101622 Hubcap 1101623 1101623
When ordering spare parts, please state the EDP no., unit number and type (see name plate)!
17
REMKO CLK 80/170-RV
Electrical wiring diagram CLK 80-RV
TR
TW
STB
RT
1
3
2
1A
2A
3A
31
34
B
S1
I
II
HR
M
2
1
4
4B
5B
6B
A
11
14
1232
KL
10
1112
schwarz
C
blau
4
1
2 2
H2 H1
N
N
#2
1
S2
5
6789
#1
#5
3
4
#4
#3
12
L1
N
T1
T2
S3 B4
WS
HW 07.13
Legend:
C = Capacitor H1 = Operating lamp (green) H2 = External burner fault lamp (red) HR = Auxiliary relay KL = Terminal block M = B3 Fan motor ÖV = Multiflex oil pre-heating (option)
ÖV
Option (EDV-Nr.: 1071411)
N
230 V / 50 Hz
RT = Thermostat receptacle S1 = Operating switch S2 = Reset button - burner relay STB = Safety temperature limiter TR = Temperature controller TW = Temperature monitoring device WS = Burner connector, 7-pole
(only fitted with factory burner delivery)
L1
PE
18
We reserve the right to modify the dimensions and design as part of the ongoing technical development process.
Electrical wiring diagram CLK 170-RV
Control circuit
Legend:
S1 = Operating switch S2 = Reset button (burner) H1 = Operating lamp (green) H2 = External burner fault lamp (red) TR = Temperature controller TW = Temperature monitoring device STB = Safety temperature limiter X1 = Terminal block M = Fan motor WS = Burner connector, 7-pole RT = Thermostat receptacle ÖV = Multiflex oil pre-heating 1F3.1 = Controller fuse 2K2.1 = Mains fuse 2K2.2 = Time relay 2K3.1 = Mains fuse 2K5.1 = Delta contactor 2K5.2 = Star contactor 1K6.1 = Phase sequence relay 2K6.1 = Star-delta relay 1Q3.1 = Motor overload protection switch
Load circuit
We reserve the right to modify the dimensions and design as part of the ongoing technical development process.
19
REMKO CLK 80/170-RV
Commissioning the forced-air oil burner
Preparatory tasks
ATTENTION
The commissioning of the forced-air oil burner may only be carried out by trained specialists.
After loosening the 4 fastening bolts the mounting baseplate M is pulled off the housing G. From size SL 44, 6 fastening screws must be removed (note marking arrows).
NOTE
Because the air flap, up to size 44, is sprung this should be closed beforehand with the help of the adjustment screw [3] (turn adjusting screw approx. as far as scale value 1).
The most important functional parts for the installation / maintenance are now immediately accessible, as per the respective requirements.
Fig.: 1
MG
Adjusting the ignition electrode and baffle plate
Size / dimensions A B C D CLK 80-RV 5 5 7 3 CLK 170-RV 7 8 5 3
Required nozzle size
The selection of the required oil nozzle is dependent on the pump pressure and the unit capacity. Only a nozzle that is approved for the respective combustion chamber geometry with corresponding spray angle and cone characteristics may be used. Refer to the technical data for the required oil nozzle size.
All sizes are approximate values and are in mm. The optimum setting must be adapted to the unit-specific and structural conditions.
Air inlet nozzle
The required blower pressure can be adjusted with the adjustable air inlet nozzle A in accordance with the combustion chamber resistance and chimney draft, without having to change the output diameter.
1. Loosen the Allen screw B.
2. Turn the air inlet nozzle A to the desired position (note arrows!).
"min" = Smaller blower pressure "max" = Larger blower pressure
For maintenance work or for installing / replacing the oil nozzle, the mounting baseplate M can be positioned on the burner housing G in 2 ways (see figs. 1 and 2).
The baseplate can be positioned in the desired / possible position on the special mounting points in accordance with the unit­specific options.
20
Fig.: 2
G
A
B
Mounting baseplate
M
After having replaced the nozzle and carried out any adjustments required to the air inlet nozzle A, the mounting baseplate M is re­fitted in reverse order.
Adjusting the secondary air (Nozzle fitting adjustment)
2
Air flap
Setting the pump pressure
The pump pressure should be adjusted, and checked
3
if necessary, during burner commissioning and during every service.
1
Carry out the presetting of the secondary air as follows:
Set the nozzle fitting 2 to the desired value with the adjusting screw 1.
CLK 80-RV
Turning to the left (–) = smaller scale value larger pressure behind the baffle plate
lower power range
Turning to the right (+)
= larger scale value smaller pressure behind the baffle plate upper power range
CLK 170-RV
Turning to the left (+) = larger scale value smaller pressure behind the baffle plate
upper power range
Turning to the right (–)
= smaller scale value larger pressure behind the baffle plate
lower power range
4
The quantity of combustion air required is adjusted by means of the adjusting screw 3. The air flap is set according to the unit capacity and the further burner settings.
Adjusting the air flap
Adjust the air flap as follows:
1. Loosen the knurled nut 4.
2. Set the adjusting screw 3 accordingly.
Turn to the right = Less air
Turn to the left = More air
4. After having set the adjusting screw 3 lock it again with the knurled knob 4.
Additional notes
If the flame should give off
sooty smoke or break away with a fully opened air flap, reduce the pressure behind the baffle plate with the help of the secondary air setting
It may also be necessary
to open the air inlet nozzle further
NOTE
Never let the pump run for extended periods without any fuel. Never leave the units for extended periods with a pump that has run dry.
Adjust the pump pressure as follows:
1. Remove the stopper on the measurement nozzle "P".
2. Fit a suitable oil pressure manometer here.
3. Open all oil shut-off devices.
4. Switch on the burner.
5. Set the required oil pressure in accordance with the nozzle size and the unit capacity.
6. Switch off the burner after completing the adjustments.
7. Remove the oil pressure manometer again. Re-fit stopper incl. seal.
ATTENTION
If the burner should carry out a fault shut-down once again after the start phase, then another reset should be carried out after a waiting period of 5 minutes has passed.
Further reset procedures must be prohibited as there is a danger of deflagration.
All values provided are only preliminary settings and must be adapted or calibrated in accordance with the exhaust gas analysis.
21
REMKO CLK 80/170-RV
Maintenance protocol
Unit type: .................................. Unit number: ...................................
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Unit cleaned - outside ­Unit cleaned - inside ­Fan blade cleaned Combustion chamber cleaned Heat exchanger cleaned Exhaust gas suppressors replaced Inspection cover seal replaced Fuel filter insert replaced Safety equipment checked Safety devices checked Unit checked for damage Electrical safety check Burner maintenance *) Test run
Comments: .....................................................................................................................................................
.............................................................................................................................................................................
.............................................................................................................................................................................
1. Date: .................
..............................
Signature
6. Date: .................
..............................
Signature
11. Date: ...............
..............................
Signature
16. Date: ...............
..............................
Signature
2. Date: ..............
..............................
Signature
7. Date: ..............
..............................
Signature
12. Date: ............
..............................
Signature
17. Date: ............
..............................
Signature
3. Date: .................
..............................
Signature
8. Date: .................
..............................
Signature
13. Date: ...............
..............................
Signature
18. Date: ...............
..............................
Signature
4. Date: ..............
..............................
Signature
9. Date: ..............
..............................
Signature
14. Date: ............
..............................
Signature
19. Date: ............
..............................
Signature
5. Date: .................
..............................
Signature
10. Date: ...............
..............................
Signature
15. Date: ...............
..............................
Signature
20. Date: ...............
..............................
Signature
*) Have the forced-air burner maintained and adjusted only by authorised specialists and in accordance with the legal provisions (1st. BImSchV.). A corresponding measurement log should be generated.
Unit to be maintained only by authorised specialists in accordance with the statutory regulations.
22
Technical data
Unit type
Max. nominal heating capacity kW 84 155
CLK 80-RV CLK 170-RV
Nominal heat capacity kW 77 143
1)
Nominal flow rate
(Max. total) pressure Pa 410 520
m3/h 6,140 10,340
Fuel Heating oil EL acc. to DIN 51603-1 or diesel fuel
Max. fuel consumption l/h 8.3 15.5
2)
Danfoss oil nozzle Pump pressure,
Max. exhaust gas loss % 9 9
Exhaust gas flow, Combustion chamber resistance,
USG 1.75 / 60°S 3.00 / 80°S
approx.
2)
bar 12 13
approx. kg/h 136 240
approx. Pa 100 110
Required chimney draft Pa 0 0 Power supply V/Hz 230/1~/50 400/3~N / 50
Max. power consumption (complete unit) kW 1.75 3.4 Max. nominal current (complete unit) A 9.5 8.0
Max. power consumption
Customer-provided electrical protection A 16 16
(Multiflex oil preheating) W -- 30
Temperature increase ( Sound pressure level L
) K 48 54
t
3)
pA
1m
dB (A) 62 65 Air outlet Ø mm 400 500 Air intake Ø
4)
mm 2 x 400 2 x 500 Exhaust gas nozzles Ø mm 150 200 Dimensions: Length mm 2,000 2,380 Width mm 800 920 Height mm 1,160 1,350 Weight with forced-air oil burner kg 234 375 EDP no.: (with/without oil burner) 131300/131100 131700/131500
1) At
45K / 1.2 kg/m3)
t
2) The specified nozzle sizes and pump pressures are based on test bench results. The oil flow rate was derived from this.
Based on the product-specific nozzle and pressure tolerances as well as the oil temperature, the specifications should only be
considered guidelines.
3) Noise level measurement (with hose and without burner operation) DIN 45635 - 01 - KL 3
4) Only with intake ports (accessories) for recirculating or mixed air operation
We reserve the right to modify the dimensions and design as part of the ongoing technical development process.
23
REMKO INTERNATIONAL
... and also right in your neighbourhood! Take advantage of our experience and advice
REMKO GmbH & Co. KG Klima- und Wärmetechnik
Im Seelenkamp 12 D-32791 Lage Postfach 1827 D-32777 Lage Telephone +49 5232 606-0 Fax +49 5232 606-260 e-mail info@remko.de Internet www.remko.de
Consulting
Thanks to intensive training, our consultants are always completely up-to-date when it comes to technical expertise. This has given us the reputation of being more than just an excellent, reliable supplier: REMKO, a partner who helps to solve problems.
Sales
REMKO offers not just a well­established sales network both nationally and internationally, but also has exceptionally highly­qualified sales specialists. REMKO employees in the field are more than mere salespeople: above all, they must be advisers to our customers in air conditioning and heating technology.
Customer service
Our units operate precisely and reliably. However, in the event of a malfunction REMKO customer service is quickly on the scene. Our comprehensive network of experienced dealers guarantees quick and reliable service.
We reserve the right to make technical changes and provide no warranty as to the accuracy of this data!
Loading...