Red Lion XCCN User Manual

0 (0)

Bulletin No. XCCN-B Drawing No. LP0667 Released 03/14

Tel +1 (717) 767-6511

Fax +1 (717) 764-0839 www.redlion.net

MODEL XCCN - CANopen OPTION CARD FOR DATA STATION PLUS AND MODULAR CONTROLLER

CONFIGURED USING CRIMSON SOFTWARE (VERSION 2.0 OR LATER)

DIGITALLY ISOLATED CANopen PORT CAPABLE OF COMMUNICATING WITH ANY CANopen DEVICE

EASY INSTALLATION

GENERAL DESCRIPTION

Both the Modular Controller Master (enhanced models) and Data Station Plus contain a proprietary expansion port which provides a high speed, parallel architecture that extends the functionality and flexibility of the platform. This approach allows these products to evolve concurrently with the latest advances in communications and standards, without sacrificing performance. This high bandwidth channel has significantly greater throughput when compared to the traditional (external) serial gateway approach.

The XCCN option card adds a CANopen communication port to the series. This isolated card protects user equipment from potentially harmful ground loops while providing the ability to communicate to any high speed CANopen device. The XCCN option card has a termination resistor built-in, which is selectable via a jumper setting. Additionally, the XCCN connector is pluggable for easy removal of the Modular Controller Master or Data Station Plus from the CANopen bus without disturbing communications with other devices on the bus.

The XCCN communication card is easily installed by removing the blank expansion port cover of your Modular Controller or Data Station Plus, and plugging the XCCN card into the expansion port. Configuration is simple using Red Lion's free Crimson 2.0 software.

SAFETY SUMMARY

All safety related regulations, local codes and instructions that appear in the literature or on equipment must be observed to ensure personal safety and to prevent damage to either the instrument or equipment connected to it. If equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.

Do not use the controller to directly command motors, valves, or other actuators not equipped with safeguards. To do so can be potentially harmful to persons or equipment in the event of a fault to the controller.

 

 

 

 

CAUTION: Risk of Danger.

 

 

 

 

 

 

 

 

 

 

 

 

Read complete instructions prior to

 

 

 

 

 

 

installation and operation of the unit.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ORDERING INFORMATION

 

 

MODEL NO.

DESCRIPTION

PART NUMBER

 

XCCN

CANopen option card for Modular Controller or

XCCN0000

 

Data Station Plus

 

 

 

 

 

SFCRM2

Crimson 2.0 with G3/Data Station Manual 1

SFCRM200

SFCRM2

Crimson 2.0 with Modular Controller Manual 1

SFCRM2MC

1Use these part numbers to purchase Crimson 2.0 on CD with a printed manual, USB cable and RS-232 cable. Otherwise, download free of charge from www.redlion.net.

CONTENTS OF PACKAGE

-XCCN option card

-This hardware bulletin

SPECIFICATIONS

1.POWER REQUIREMENTS: 24 V @ 50 mA max. Power is supplied to the option card from the main board of the Modular Controller Master or Data Station Plus.

2.COMMUNICATIONS:

CANopen Port: The CANopen port has format and baud rates that are software programmable up to 1M baud and are digitally isolated. This port may be configured for various CANopen protocols. Check www.redlion.net for currently supported protocols.

Isolation from XCCN Communication ports to the Modular Controller Master or Data Station Plus:1000 VDC for 1 minute.

3.CERTIFICATIONS AND COMPLIANCES:

Refer to main unit manual or “Agency Approvals” section of Red Lion’s website for agency certifications.

ELECTROMAGNETIC COMPATIBILITY

Emissions and Immunity to EN 61326: Electrical Equipment for Measurement, Control and Laboratory use.

Reference Modular Controller Master or Data Station Plus unit for EMC specifications

4.ENVIRONMENTAL CONDITIONS:

Refer to the specifications of the Modular Controller Master or Data Station Plus you are installing this card in.

5.CONSTRUCTION: For indoor use only. Installation Category II, Pollution Degree 2.

6.INSTALLATION REQUIREMENTS: See “Installing the XCCN Option card” for more details.

7.WEIGHT: 2.3 oz (65.2 g)

BLOCK DIAGRAM

 

 

4

CAN +

 

 

TX/RX

 

+

 

2

CAN -

ISOLATING

 

 

-

DC : DC

1

GND

A

 

B

 

1

Red Lion XCCN User Manual

INSTALLING THE XCCN OPTION CARD

1.Remove power from the unit

2.Insert a flat-bladed screwdriver into the slot at the top of the expansion port cover. Gently apply pressure on the screwdriver in an upward direction until the expansion port cover disengages from the unit as shown in Figure 1.

3.Verify that the option card knobs are in the “unlocked” position as shown in Figure 2.

4.Carefully insert the option card into the expansion port opening while aligning the card-edge connector on the option card with the main board's header, as shown in Figure 3. Once aligned, gently press on the front of the card until it is flush with the front of the case.

5.Turn the option card knobs to the locked position as shown in Figure 4.

Figure 1

Figure 3

XCCN

 

RUN/ERR

N-

LD

N+

Caution: The expansion and main circuit boards contain static sensitive components. Before handling the cards, discharge static charges from your body by touching a grounded bare metal object. Ideally, handle the cards at a static controlled clean workstation. Also, handle the cards by the edges only. Dirt, oil, or other contaminants that may contact the cards can adversely affect circuit operation.

Warning: Risk of Danger: Be sure to remove all power before removing the expansion port cover

XCCN

RUN/ERR

Figure 2

GND

CAN-

SHLD

CAN+

V+

XCCN

RUN/ERR

GND

CAN-

SHLD

CAN+

V+

Figure 4

2