Red Lion PXU User Manual

5 (1)

Drawing No. LP0951B Released 02/14

Tel +1 (717) 767-6511

Fax +1 (717) 764-0839 www.redlion.net

PXU

Temperature/Process Controller

Installation Guide

C UR L US LISTED

13RW PROCESS CONTROL EQUIPMENT

See the Red Lion website at www.redlion.net for a complete user manual.

CAUTION: Risk of electric shock.

When the power is on, DO NOT touch the AC terminals, an electric shock may occur. Make sure the power is disconnected when you check the input power supply.

1.Prevent dust or metallic debris from falling into the controller and causing malfunctions. DO NOT modify the controller.

2.The PXU is an open-type device. Make sure it is installed in an enclosure free of dust and humidity in case of an electric shock.

3.Wait for one minute after the power is switched off to allow the unit to discharge. DO NOT touch the internal wiring within this period of time.

SPECIFICATIONS

POWER:

Line Voltage Models:

100 to 240 VAC -20/+8 %, 50/60 Hz, 5 VA

Low Voltage Models:

DC Power: 24 VDC, ±10%, 5 W

INPUT CAPABILITIES:

Thermocouple Inputs:

Types: T, E, J, K, R, S, B, N, L, U, and TXK

RTD Inputs:

Type: 2 or 3 wire, 2 wire can be compensated for lead wire resistance

Excitation: 180 µA typical

Input Type:

100

Ω Pt alpha = .00385

100 Ω Pt alpha = .00392

120

Ω Nickel alpha = .00672

50 Ω Copper alpha = .00428

Process Input Ranges:

 

 

0-5 VDC

0-20 mA

0-50 mV

0-10 VDC

4-20 mA

 

USER INPUT (Optional):

Contact/NPN Open Collector Input:

ON Resistance 1 Kmax.

OFF Resistance 100 Kmin.

Response Time: 1 sec max

Functions: Programmable

OUTPUT:

CONTROL RELAY OUTPUTS (OUT1/OUT2): Type: Form A

Contact Rating: 5 A @ 250 VAC

Contact Isolation to all I/O: 2300 VAC for 1 min. CONTROL SSR DRIVE OUTPUT (OUT1):

Rating: 12 VDC ± 10% @ 40 mA max.

CONTROL OUTPUT (OUT1) Analog Models:

Analog Types: 4 to 20 mA or 0 to 10 VDC

Isolation To Sensor & Communication Common: 500 VDC for 1 min.

Compliance: 10 VDC: 1 Kload min., 20 mA: 500 load max.

ALARMS: 2 relay alarm outputs.

Type: Form A or Form C, model and alarm dependent

Contact Rating: 3 A @ 250 VAC

ENVIRONMENTAL CONDITIONS: Operating Temperature Range: 0 to 50 °C Storage Temperature Range: -20 to 65 °C

Vibration Resistance: Operational 10 to 55 Hz, 1 g Shock Resistance: Operational 30 g

Operating and Storage Humidity: 80% max relative humidity (noncondensing) from 0°C to 50°C

Altitude: Up to 2000 meters

CERTIFICATIONS AND COMPLIANCES:

CE Approved

EN 61326-1 Immunity to Industrial Locations Emission CISPR 11 Class A

EN 61010-1 RoHS Compliant

UL Listed: File #E179259

IP65 Enclosure rating (Face only) CONNECTIONS: Wire-clamping screw terminals

CONSTRUCTION: Black plastic alloy case and panel latch. Black plastic textured bezel with transparent display window. Controller meets IP65 requirements for indoor use when properly installed. Installation Category II, Pollution Degree 2.

WEIGHT:

1/4 DIN: 11.0 oz (312 g) 1/8 DIN: 7.8 oz (221 g) 1/16 DIN: 5.3 oz (150 g)

DIMENSIONS In inches (mm) - 1/16 DIN

1.89

0.26

3.14 (79.70)

0.31

(48.0)

(6.70)

(7.80)

 

 

 

 

 

0.47 (11.88)

1.89

 

 

0.83 (21.0)

(48.0)

 

 

 

 

 

 

PANEL CUT-OUT

 

 

 

1.77

 

 

 

(45.0)

 

 

1

 

7

 

2

13

8

 

 

 

 

3

14

9

1.77

15

4

16

10

(45.0)

 

17

 

 

5

18

11

 

 

 

6

 

12

 

1

Red Lion PXU User Manual

DIMENSIONS In inches (mm) - 1/8 DIN

 

 

PANEL CUT-OUT

 

 

1.89

0.45

2.82 (71.5)

 

 

1.76

 

 

 

(48.0)

(11.4)

 

 

(44.5)

 

 

 

 

 

 

 

 

 

 

 

 

 

1

13

 

 

 

 

 

 

 

2

14

 

 

 

 

 

 

 

3

15

 

 

 

 

 

 

 

4

16

 

 

3.77

 

 

3.60

5

17

 

3.60

 

 

6

18

 

(95.8)

 

 

(91.5)

7

19

 

(91.5)

 

 

 

 

 

8

20

 

 

 

 

 

 

 

9

21

 

 

F1

F2

 

 

 

10

22

 

 

 

 

 

 

 

 

 

D

P

 

 

 

11

23

 

 

 

 

 

12

24

 

 

 

 

 

 

 

 

 

DIMENSIONS In inches (mm) - 1/4 DIN

 

 

PANEL CUT-OUT

 

 

3.77 (95.8)

0.45

2.82 (71.5)

 

 

3.58 (91.0)

 

 

(11.4)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

25

13

 

 

 

 

 

2

 

26

14

 

 

 

 

 

3

 

27

15

 

 

 

 

 

4

 

28

16

 

 

 

 

3.58

5

 

29

17

3.58

 

 

 

6

 

30

18

3.77

 

 

(91.0)

8

 

32

20

(91.0)

 

 

 

 

7

 

31

19

 

(95.8)

 

 

 

9

 

33

21

 

 

 

 

 

10

 

34

22

 

 

 

 

 

11

 

35

23

 

 

 

 

 

12

 

36

24

 

SAFETY SUMMARY

All safety related regulations, local codes and instructions that appear in the manual or on equipment must be observed to ensure personal safety and to prevent damage to either the instrument or equipment connected to it. If equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.

Do not use the controller to directly command motors, valves, or other actuators not equipped with safeguards. To do so can be potentially harmful to persons or equipment in the event of a fault to the controller. If redundant safeguards are not in place, an independent and redundant temperature limit indicator with alarm outputs is strongly recommended.

CAUTION: Risk of Danger.

Read complete instructions prior to installation and operation of the unit.

SETTING THE CURRENT INPUT JUMPER

When Input Type is selected as one of the two current input types (0-20 or 4-20), the current input jumper must be installed. The current input jumper is factory set for Temperature and Voltage input types. To change the jumper to configure the input for a current input type, the inside of the unit must be accessed and the jumper position changed.

To access the jumper, locate the two latches located on top and bottom of the front of the unit. Starting with the top latch, insert a small flat-blade screwdriver between the case latch and bezel while using your thumb to push out on the bezel until the latch is disengaged. Repeat this process with the bottom latch. After the latches are disengaged, using the flat-blade screwdriver, gently pry out on the bezel in several areas until the unit releases from the case.

Look for the Current Input Jumper which will be located close to the pc board area that connects to the input terminals. If a current input type is desired, position the jumper across both pins. If input type is anything other than a current input, position the jumper on only one pin.

Thermocouple, RTD

Current Input

or Voltage Input

(4-20 mA or 0-20 mA)

 

JUMPER

 

JUMPER

JP8

PIN HEADER

JP8

PIN HEADER

 

 

 

 

 

FACTORY SETTING

 

 

INSTALLING THE CONTROLLER

The controller is designed to be mounted into an enclosed panel. The unit must be inserted in the case during installation of the controller.

Instructions:

1.Prepare the panel cutout to the proper dimensions.

2.Assemble the mounting clip by inserting the nut into the slot and then insert the screw and thread through the nut as shown (See drawing)

3.Slide the panel gasket over the rear of the controller, seating it against the lip at the front of the case.

4.Insert the controller into the panel cutout. While holding the controller

in place, install the panel latch(es) and then slide it to the farthest

PANEL LATCH

forward slot possible.

(SUPPLIED W/UNIT)

5.To achieve a proper seal, tighten the panel latch screws evenly until the controller is snug in the panel, torquing the screws to 13.9 to 20.8 oz-in (9.8 to 14.7 N-cm). Overtightening can result in distortion of the

controller, and reduce the effectiveness of the seal.

Note: The installation location of the controller is important. Be sure to

 

keep it away from heat sources (ovens, furnaces, etc.) and away from

 

direct contact with caustic vapors, oils, steam, or any other process

1/16 DIN Installation

by-products in which exposure may affect proper operation.

7 8 9 10 11 12

PANEL GASKET

EXISTING PANEL CUT-OUT 1/16 DIN

1.77” (45.0 mm) X 1.77” (45.0 mm)

2