Pilz PMD s20 Data Sheet

Electronic monitoring relays PMDsigma
U
M
A1 A2
~
Power
B1 B2
Reset Test
G
Feedback Earth
Y1 Y2 Y3
K1
K2
11 21
12 14 22 24
+
-
FE
Insulation monitor
PMD s20
Gertebild
Bildunterschrift
The insulation monitor monitors the in­sulation resistance of unearthed AC/ DC systems (IT systems). It meets the requirements of EN 61557-8, IEC 60364-7-710 and DIN VDE 0100-710.
Approvals
PMD s20
Zulassungen
Unit features
Gertemerkmale
Relay output:
2 auxiliary changeover contacts (C/ O)
Detects symmetrical and asymmet-
rical insulation faults
Two insulation measuring circuitsConnection for external switch con-
tacts to trigger the manual reset and for function testing
Unit parameter settings are menu-
driven and infinitely variable via a display and rotary encoder with key function (turn and push)
Configuration is stored on a chip
card
Status indicators (LEDs) for:
– Supply voltage (Power) – Insulation resistance –Fault
Unit description
Gertebeschreibung
The insulation monitor monitors the in­sulation resistance of unearthed AC/ DC systems (IT systems). It meets the
requirements of EN 61557-8, IEC 60364-7-710 and DIN VDE 0100­710 and may be used:
To monitor unearthed AC/DC sys-
tems (including on board ships)
In medical locationsAs a trip device if insulation resist-
ances are outside the permitted range
Block diagram
Blockschaltbild
1001753-EN-02-2011-05
Electronic monitoring relays PMDsigma
R
an
UB
t
t
LED
t
tr
0
1
R
ab
t
R
E
t
Reset
t
tr
tr
Auto reset
Manual reset
0
1
11
-
14
21
-
24
11
14
21 24
-
-
Hysteresis
UB = Versorgungsspannung/Supply voltage/Tension d'alimentation
R
an
= Ansprechwert/Response value/Seuil de déclenchement
R
ab
= Rücksetzwert/Release value/Valeur de réarment
R
E
= Isolationswiderstand/Insulation resistance/Résistance de'isolement
Insulation monitor
PMD s20
Function description
Funktionsbeschre ibung PMS s20
The insulation monitor prevents haz­ardous insulation faults in galvanically separated systems. The insulation re­sistances are measured between the network phases and the operating earth. The measuring principle detects symmetrical and asymmetrical insula­tion faults.
Relay outputs (K1 and K2)
K1 and K2 operate in normally ener­gised mode. In their default state, aux-
Timing diagram
iliary contacts 11-14 and 21-24 are closed and auxiliary contacts 11-12 and 21-22 are open. Normally ener­gised mode is the default setting; this setting can be changed via the menu.
Response resistance
If the insulation resistance falls below the set response resistance R
an
ther of the two measuring circuits (R < R
), the LED "Out 1" or "Out 2" will
an
light and the relay contacts will de-en­ergise.
Funktionsdiagram PMD s20
in ei-
Response resistance Ran1:
Auxiliary contacts 11-14 will open and auxiliary contacts 11-12 will close (normally energised mode).
Response resistance Ran2:
Auxiliary contacts 21-24 will open and auxiliary contacts 21-22 will close (normally energised mode).
Monitoring the operating earth
E
If the connection between the operat­ing earth and the FE terminal is bro­ken, contacts 11-12 and 21-22 will close (normally energised mode).
Wiring
Inbetriebnahme _Isolationswäch ter
When commissioning, please note the following:
Output contacts 11-12-14 and 21-
22-24 are auxiliary contacts (e.g. for a display or contactor control)
Only wire the unit when the supply
voltage is switched off!
Use copper wiring.To prevent contact welding, a fuse
should be connected before the output contacts (see technical de­tails).
Ensure that the cables are laid care-
fully, because an open circuit in the
measuring circuit will cause the unit to malfunction.
Ensure there is adequate fuse pro-
tection on the connection cables at terminals B1 and B2.
1001753-EN-02-2011-05
Electronic monitoring relays PMDsigma
L1
N
PE
1L1 1L2
E1
R
e
R
e
F1
F2
T1
Test
Y3
Reset
12
14
11
A1
A2
24
22
21
Y1
Y2
B1
B2
FE
PMD s20
Insulation monitor
PMD s20
Only one insulation monitor should
be connected to galvanically con­nected systems.
Preparing for operation
Inbetriebnahme_Anschluss
Supply voltage UB:
– Connect the supply voltage UB
to A1/A2. The supply voltage UB can also be taken from the measuring circuit.
Measuring circuit (system to be
monitored): – 2-phase system: – Connect one phase of the moni-
tored system to the terminals
Application circuit AC
A function test involving a real earth
fault (resistance) must be carried out in order to check that the unit is properly connected.
B1/B2 respectively. – 3-phase system: – Link terminals B1/B2 and con-
nect them to the system's star
point.
Connect the output contacts in ac-
cordance with the relevant applica­tion circuit.
Function test:
– By pressing a button at terminals
Inbetriebnahme_Anwendung_Bild_1
Information given in the “Technical
details” must be followed.
Y1 and Y3 or
– Pressing the rotary knob for at
least 3 seconds
Leerzeilen
Inbetriebnahme
Please note: Do not connect any cables to undesig­nated terminals.
1001753-EN-02-2011-05
Loading...
+ 5 hidden pages