The true power converter PMD s10 is
used to measure and monitor the true
power drawn and output by electrical
loads.
The PMD s10 is designed for use as a:
` True power converter for single and
three-phase electrical machines
` Trip device for underload and over-
load
Block diagram
A1 A2
~
Power
Power
Blockschaltbild
K1 U/I124
I
M1
L1 L2 L3
U
M
K3 W/I3
I
M3
12
=
K1
P
U
out Iout
U I 0 V
Reset
Y2 Y1
K2
11
14
22
21
NSG-D-2-422-2010-11
Electronic monitoring relays PMDsigma
True power monitoring
PMD s10
Function description
Funktionsbeschreibung_Text_1
The PMD s10 monitors the true power
on a single, three phase or DC supply
to ensure it doesn't exceed or drop
below a certain value. The unit operates in accordance with the Aron circuit principle.
Relay outputs (K1 and K2)
K1 and K2 operate in normally energised mode. In their default state, auxiliary contacts 11-14 and 21-24 are
closed and auxiliary contacts 11-12
and 21-22 are open. Normally energised mode is the default setting; this
setting can be changed via the menu.
Analogue outputs (U
out
and I
out
):
The unit forms two output signals
which are proportional to the true
power. The limit value corresponds to
(see timing diagram). The status
P
max
of the threshold monitoring function is
displayed at the auxiliary contacts and
LEDs, along with the analogue output
Timing diagram
signals. The hysteresis of the switching thresholds can be set between 0 %
... 50 %.
Current transformer CT:
With continuous currents > 12 A, the
measuring current must be measured
via an external current transformer.
Po function (K1 overload):
If the measured true power exceeds
the switching threshold Po, the ">
max" LED is lit. Once the response
time has elapsed (t
), the auxiliary con-
r
tact switches (default: relay K1) and
the "Out 1" LED is lit.
Pwo function (overload warning
threshold):
Serves as a warning; for function description, see Po function (K1 overload)
Funktionsbeschreibung_Text_2
Pu function (K2 underload):
If the measured true power drops below the switching threshold PU, the "<
min" LED is lit. Once the response time
has elapsed (t
), the auxiliary contact
r
switches (default: relay K2) and the
"Out 2" LED is lit.
Pwu function (underload warning
threshold):
Serves as a warning; for function description, see Pu function (K2 underload)
Start suppression time (t
Start
):
The measurement is suppressed during the machine's start-up phase, in
order to avoid spurious output signals.
The start suppression time t
Start
is infi-
nitely variable.
Response time (t
):
r
With transient load fluctuations, the
switching threshold can be suppressed. The response time t
is infi-
r
nitely variable.
Reset mode:
The fault status (value below Pu or
above Po) can be reset automatically
or via an external reset button.
P
100%
Po
Pu
5%
0%
OUT1
LED >max
OUT2
LED <min
Zeitdiagramm
tstrtr
tr
ts
ts
trtr
tr
Hysterese/
Hysteresis/
Hystérésis
Hysterese/
Hysteresis/
Hystérésis
t
t
t
t
P tatsächliche Wirkleistung/Actual true power/puissance active réelle
t
sStartunterdrückungszeit/Start suppression time/Temps de suppression au démarrage
t
rReaktionszeit/Response time/Temps de résponse
ts
t
NSG-D-2-422-2010-11
-2
Electronic monitoring relays PMDsigma
True power monitoring
PMD s10
Timing diagram
Zeitdiagramm
Generatorbetrieb/
Generator/
Fonctionnement
avec générateur
-P
max
U
P tatsächliche Wirkleistung/Actual true power/puissance active réelle
U/Ianaloges Ausgangssignal, Spannung oder Strom/Analogue output signal, voltage or current/
signal de sortie analogique, intensité ou tension
Wiring
Inbetriebnahme_fuer_PDB
Note:
` Only wire the unit when the supply
voltage is switched off!
` Use copper wiring.
` To prevent contact welding, a fuse
should be connected before the
output contacts (see technical details).
10 V
20 mA
4 mA
0
1* U bei/at/à 10 ... 0 V
1*
V
-10 V
U/I
Motorbetrieb/
Motor/
Fonctionnement
avec moteur
P
max
` Ensure that the cables are laid care-
fully, because an open circuit in the
measuring circuit will cause the unit
function to fail.
` Information given in the “Technical
details” must be followed.
P
W
NOTICE
Ensure that there is adequate fuse
protection on the connection cables to
terminals L1, L2, L3, K1, K3, A1 and
A2!
Preparing for operation
Inbetriebnahme_Anschluss
` Connect the supply voltage UB to
A1/A2.
` Single-phase:
– Measuring voltage U
: Connect
M
to terminals L1 and L2
– Link terminals L1-K1
– Measuring circuit: Connect
phase L1 of the motors to termi-
nal U/I1
` Three-phase:
– Measuring voltage U
: Connect
M
to terminals L1, L2 and L3
– Link terminals L1-K1, L3-K3
– Measuring circuit: Connect
phase L1 of the motor to terminal
U/I1, phase L2 to terminal L2 and
L3 to W/I3
` Please refer to the connection dia-
grams for details of how to connect
external current transformers
and an external reset (see "Application").
` Connect the output contacts in ac-
cordance with the relevant application circuit.
Leerzeilen
Inbetriebnahme_Anwendung
NOTICE
Only connect the unit as shown in the
examples below! Do not connect unlabelled terminals.
The following circuit examples show
typical applications for the true power
converter PMD s10.
With continuous currents > 12 A, the
measuring current must be measured
via an external current transformer.
NSG-D-2-422-2010-11
Loading...
+ 6 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.