Pilz PMD s10 Data Sheet

Electronic monitoring relays PMDsigma
True power monitoring
PMD s10
Gertebild
Bildunterschrift
True power converter for single and three-phase electrical machinery
PMD s10
Zulassungen
Unit features
Gertemerkmale PMD s10_Text_1
` Relay output:
2 auxiliary changeover contacts (C/ O)
` Analogue output for current and
voltage
` Galvanic isolation of the analogue
outputs
` Measuring range set automatically
for current and voltage
Gertemerkmale
` Menu-driven parameter setting
Gertemerkmale PMD s10_Text_3
` Status indicators (LEDs) for:
– Supply voltage (Power) – Switching threshold for overload
(> max)
– Switching threshold for under-
load (< min) – Output 1 (Out 1) – Output 2 (Out 2) –Fault
` Display for measured value indica-
tor, diagnostics and menu naviga­tion
` Operating cycle counter for K1 and
K2
` Diagnostics: U
max
and I
max
` Display of operating hours and load
hours (resettable)
` Device parameters can be saved to
chip card (write)
` Device parameters can be restored
from the chip card (load)
` Suitable for use with frequency-
controlled drives
` Suitable for current transformers
Unit description
Gertebeschreibung PMD s10
The true power converter PMD s10 is used to measure and monitor the true power drawn and output by electrical loads. The PMD s10 is designed for use as a:
` True power converter for single and
three-phase electrical machines
` Trip device for underload and over-
load
Block diagram
A1 A2
~
Power
Power
Blockschaltbild
K1 U/I1 24
I
M1
L1 L2 L3
U
M
K3 W/I3
I
M3
12
=
K1
P
U
out Iout
U I 0 V
Reset
Y2 Y1
K2
11
14
22
21
NSG-D-2-422-2010-11
Electronic monitoring relays PMDsigma
True power monitoring
PMD s10
Function description
Funktionsbeschreibung_Text_1
The PMD s10 monitors the true power on a single, three phase or DC supply to ensure it doesn't exceed or drop below a certain value. The unit oper­ates in accordance with the Aron cir­cuit principle.
Relay outputs (K1 and K2)
K1 and K2 operate in normally ener­gised mode. In their default state, aux­iliary contacts 11-14 and 21-24 are closed and auxiliary contacts 11-12 and 21-22 are open. Normally ener­gised mode is the default setting; this setting can be changed via the menu.
Analogue outputs (U
out
and I
out
):
The unit forms two output signals which are proportional to the true power. The limit value corresponds to
(see timing diagram). The status
P
max
of the threshold monitoring function is displayed at the auxiliary contacts and LEDs, along with the analogue output
Timing diagram
signals. The hysteresis of the switch­ing thresholds can be set between 0 % ... 50 %.
Current transformer CT:
With continuous currents > 12 A, the measuring current must be measured via an external current transformer.
Po function (K1 overload):
If the measured true power exceeds the switching threshold Po, the "> max" LED is lit. Once the response time has elapsed (t
), the auxiliary con-
r
tact switches (default: relay K1) and the "Out 1" LED is lit.
Pwo function (overload warning threshold):
Serves as a warning; for function de­scription, see Po function (K1 over­load)
Funktionsbeschreibung_Text_2
Pu function (K2 underload):
If the measured true power drops be­low the switching threshold PU, the "< min" LED is lit. Once the response time has elapsed (t
), the auxiliary contact
r
switches (default: relay K2) and the "Out 2" LED is lit.
Pwu function (underload warning threshold):
Serves as a warning; for function de­scription, see Pu function (K2 under­load)
Start suppression time (t
Start
):
The measurement is suppressed dur­ing the machine's start-up phase, in order to avoid spurious output signals. The start suppression time t
Start
is infi-
nitely variable.
Response time (t
):
r
With transient load fluctuations, the switching threshold can be sup­pressed. The response time t
is infi-
r
nitely variable.
Reset mode:
The fault status (value below Pu or above Po) can be reset automatically or via an external reset button.
P
100%
Po
Pu
5% 0%
OUT1
LED >max
OUT2
LED <min
Zeitdiagramm
ts tr tr
tr
ts
ts
tr tr
tr
Hysterese/ Hysteresis/ Hystérésis
Hysterese/ Hysteresis/ Hystérésis
t
t
t
t
P tatsächliche Wirkleistung/Actual true power/puissance active réelle t
s Startunterdrückungszeit/Start suppression time/Temps de suppression au démarrage
t
r Reaktionszeit/Response time/Temps de résponse
ts
t
NSG-D-2-422-2010-11
-2
Electronic monitoring relays PMDsigma
True power monitoring
PMD s10
Timing diagram
Zeitdiagramm
Generatorbetrieb/ Generator/ Fonctionnement avec générateur
-P
max
U
P tatsächliche Wirkleistung/Actual true power/puissance active réelle U/I analoges Ausgangssignal, Spannung oder Strom/Analogue output signal, voltage or current/
signal de sortie analogique, intensité ou tension
Wiring
Inbetriebnahme_fuer_PDB
Note:
` Only wire the unit when the supply
voltage is switched off!
` Use copper wiring. ` To prevent contact welding, a fuse
should be connected before the output contacts (see technical de­tails).
10 V 20 mA
4 mA 0
1* U bei/at/à 10 ... 0 V
1*
V
-10 V
U/I
Motorbetrieb/ Motor/ Fonctionnement avec moteur
P
max
` Ensure that the cables are laid care-
fully, because an open circuit in the measuring circuit will cause the unit function to fail.
` Information given in the “Technical
details” must be followed.
P
W
NOTICE
Ensure that there is adequate fuse protection on the connection cables to terminals L1, L2, L3, K1, K3, A1 and A2!
Preparing for operation
Inbetriebnahme_Anschluss
` Connect the supply voltage UB to
A1/A2.
` Single-phase:
– Measuring voltage U
: Connect
M
to terminals L1 and L2 – Link terminals L1-K1 – Measuring circuit: Connect
phase L1 of the motors to termi-
nal U/I1
` Three-phase:
– Measuring voltage U
: Connect
M
to terminals L1, L2 and L3 – Link terminals L1-K1, L3-K3 – Measuring circuit: Connect
phase L1 of the motor to terminal
U/I1, phase L2 to terminal L2 and
L3 to W/I3
` Please refer to the connection dia-
grams for details of how to connect
external current transformers
and an external reset (see "Appli­cation").
` Connect the output contacts in ac-
cordance with the relevant applica­tion circuit.
Leerzeilen
Inbetriebnahme_Anwendung
NOTICE
Only connect the unit as shown in the examples below! Do not connect unla­belled terminals.
The following circuit examples show typical applications for the true power converter PMD s10. With continuous currents > 12 A, the measuring current must be measured via an external current transformer.
NSG-D-2-422-2010-11
Loading...
+ 6 hidden pages