Phoenix Contact PSR-PC20-1NO-1NC-24DC-SC, PSR-PC20-1NO-1NC-24DC-SP User guide [ml]

0 (0)
Phoenix Contact PSR-PC20-1NO-1NC-24DC-SC, PSR-PC20-1NO-1NC-24DC-SP User guide

NEDERLANDS

Veiligheidsrelais

1. Inhoud van de EG-conformiteitsverklaring

Fabrikant: PHOENIX CONTACT GmbH & Co.KG, Flachsmarktstr.8, 32825 Blomberg, Duitsland

Productomschrijving:

artikelnummer:

PSR-PC20-1NO-1NC-24DC-SC

2700577

PSR-PC20-1NO-1NC-24DC-SP

2700578

Het hierboven beschreven product voldoet aan de belangrijkste eisen van de volgende richtlijn(en) en de bijbehorende wijzigingsrichtlijnen:

2004/108/EG

EMC-richtlijn (elektromagnetische compatibiliteit)

2006/95/EG

Laagspanningsrichtlijn

94/9/EG

Ex-richtlijn (ATEX)

Om te beoordelen of een product aan de betreffende eisen voldoet, worden de volgende relevante normen gehanteerd:

EN 61000-6-2:2005+AC:2005; EN 61000-6-4:2007+A1:2011

EN 50178:1997; EN 60079-0:2012+A11:2013; EN 60079-15:2010

Deze toelichting bekrachtigt het feit dat een product aan de belangrijkste eisen van de genoemde richtlijn(en), voldoet, maar vormt geen garantie voor de eigenschappen.

Uitgever: Martin Müller, Head of Business Unit ION

2. Veiligheidsaanwijzingen:

Neem de veiligheidsvoorschriften van de elektrotechniek en de betreffende bedrijfsvereniging in acht!

Worden de veiligheidsvoorschriften niet in acht genomen, dan kan dit de dood, ernstig lichamelijk letsel of aanzienlijke materiële schade tot gevolg hebben!

De werkzaamheden voor inbedrijfstelling, montage, modificatie en uitbreiding mogen uitsluitend door een elektrotechnicus worden uitgevoerd!

Bedrijf in gesloten schakelkast overeenkomstig IP54!

Schakel het moduul voor aanvang van de werkzaamheden spanningsvrij!

Tijdens bedrijf staan delen van de elektrische schakelapparatuur onder gevaarlijke spanning!

Beschermkappen mogen tijdens de werking van elektrische schakelapparatuur niet worden verwijderd!

Verwissel het moduul beslist na het optreden van de eerste fout!

Reparaties aan het moduul, vooral het openen van de behuizing, mogen uitsluitend door de fabrikant worden uitgevoerd.

Als een fout wordt herkend door de hogere besturing, moet ervan uitgegaan worden dat de veiligheidsfunctie niet meer uitgevoerd kan worden.

Het verhelpen van storingen moet binnen 72 uur plaatsvinden of binnen de procesveiligheidstijd, voor zover de applicatie dit vereist.

Bewaar de handleiding!

Zorg dat u altijd de beschikking heeft over de geldige documentatie. U vindt deze op internet: phoenixcontact.net/products.

2.1 Installatie in de zone 2

Het apparaat van categorie 3 is geschikt voor installatie in de explosiegevaarlijke omgeving van zone 2. Het voldoet aan de vereisten van EN 60079- 0:2012+A11:2013 (IEC 60079-0:2011 6th ED.) en EN 60079-15:2010

(IEC 60079-15:2010 4th ED.).

Het apparaat moet in een behuizing (schakelof verdelerkast) ingebouwd worden die voldoet aan de eisen van EN 60079-15:2010 (IEC 6007915:2010 4th ED.) en minstens beschermmethode IP54 (EN/ IEC 60529) bezit.

Het apparaat moet in een omgeving gebruikt worden die maximaal vervuilingsgraad 2 volgens EN/ IEC 60664-1 bezit.

Neem bij de installatie en bij de aansluiting van de voedingsen signaalcircuits de vereisten van EN/ IEC 60079-14 in acht.

Op de stroomcircuits in zone 2 mogen uitsluitend apparaten worden aangesloten, die geschikt zijn voor toepassing in Ex-zone 2 en die geschikt zijn voor de heersende omstandigheden op de plaats van installatie.

Het apparaat dient aangesloten te worden op voedingscircuits waarvan de nominale spanning de drempel van 140 % niet kan overschrijden, veroorzaakt door transiënte storingen.

Sluit geen kabels/leidingen in een bereik aan waar explosiegevaar heerst en koppel geen verbindingen af, als deze onder spanning staan.

Wanneer het apparaat beschadigd is, onjuist is belast of opgeslagen resp. niet correct functioneert, dient het buiten bedrijf te worden gesteld en onmiddellijk uit de Ex-omgeving te worden verwijderd..

2.2 Stofexplosiegevaarlijke bereiken

WAARSCHUWING: explosiegevaar

Het apparaat is niet geschikt voor toepassing in stofexplosiegevaarlijke omgevingen.

3. Voorgeschreven gebruik

Relais voor een veilige koppeling van digitale uitgangssignalen.

Met behulp van deze modulen worden stroomcircuits veiligheidsgericht onderbroken.

4. Productkenmerken

1 vrijgavecircuit, onvertraagd (naar keuze beveiligd)

1 retourmeldcircuit, onvertraagd

1 digitale meldingsuitgang

Geïntegreerd testpulsfilter

Actieve fout-retourmelding via A1

TBUS-aansluiting

2 interne 5AT-smeltveiligheden

5. Aansluitaanwijzingen

Blokschema ( )

Aansluitpuntbezetting ( - )

Bij inductieve belastingen dient een geschikte en effectieve beveiligingsschakeling te worden gerealiseerd. Deze dient parallel aan de belasting te worden uitgevoerd, niet parallel aan het schakelcontact.

Bij gebruik van relaismodulen dient de gebruiker aan de contactzijde rekening te houden met de eisen die worden gesteld ten aanzien van de stooremissie bij elektrische en elektronische bedrijfsmiddelen (EN/

IEC 61000-6-4) en evt. passende maatregelen te treffen.

Gebruik alleen voedingen met veilige scheiding en SELV / PELV-spanning volgens EN 50178/ VDE 0160 (SELV / PELV).

Vermijd magneetvelden met een magnetische veldsterkte > 30 A/m in de omgeving van het apparaat.

Schakel via de montagerail-busverbinder TBUS maximaal 10 apparaten in serie.

FRANÇAIS

Relais de sécurité

1. Contenu de la déclaration de conformité CE

Fabricant : PHOENIX CONTACT GmbH & Co.KG, Flachsmarktstr.8, 32825 Blomberg, Allemagne

Désignation du produit :

référence :

PSR-PC20-1NO-1NC-24DC-SC

2700577

PSR-PC20-1NO-1NC-24DC-SP

2700578

Le produit décrit ici est conforme aux exigences essentielles de la ou des directives suivantes dans leur version la plus récente :

2004/108/CE

Directive CEM (compatibilité électromagnétique)

2006/95/CE

Directive basse tension

94/9/CE

Directive Ex (ATX)

Les normes pertinentes suivantes ont été utilisées pour l'évaluation de la conformité :

EN 61000-6-2:2005+AC:2005; EN 61000-6-4:2007+A1:2011

EN 50178:1997; EN 60079-0:2012+A11:2013; EN 60079-15:2010

La présente déclaration certifie la conformité avec les exigences essentielles de la ou des directives mentionnées mais ne constitue en aucun cas une garantie des caractéristiques du produit.

Editeur : Martin Müller, Head of Business Unit ION

2. Consignes de sécurité :

Respectez les consignes de sécurité de l'industrie électrotechnique et celles des organisations professionnelles.

Le non-respect de ces consignes peut entraîner la mort, des blessures graves ou d'importants dommages matériels!

La mise en service, le montage, les modifications et les extensions ne doivent être confiés qu'à des électriciens qualifiés!

Fonctionnement en armoire électrique fermée selon IP54 !

Avant de commencer les travaux, mettez l'appareil hors tension!

Pendant le fonctionnement, certaines pièces des appareillages électriques sont soumis à une tension dangereuse !

Ne jamais déposer les capots de protection des appareillages électriques lorsque ceux-ci sont en service.

Remplacer impérativement l'appareil dès la première défaillance !

Les réparations de l'appareil, et plus particulièrement l'ouverture du boîtier, ne doivent être effectuées que par le fabricant.

Lorsqu'un automate de niveau supérieur détecte une erreur, il est probable que la fonction de sécurité ne pourra plus être appliquée. L'erreur doit être éliminée dans les 72 heures ou pendant la période de sécurité du process si l'application concernée le demande.

Conservez impérativement ce manuel d'utilisation !

S'assurer de toujours travailler avec la documentation actuelle. Elle est disponible sur Internet à l'adresse phoenixcontact.net/products.

2.1 Installation en zone 2

L'appareil de catégorie 3 est conçu pour être installé dans des atmosphères explosibles de zone 2. Il répond aux exigences des normes EN 60079- 0:2012+A11:2013 (CEI 60079-0:2011 6ème ED.) et EN 60079-15:2010 (CEI 60079-15:2010 4ème ED.).

L'appareil doit être monté dans un boîtier (coffret de commande ou de distribution) satisfaisant aux exigences des normes EN 60079-15:2010

(CEI 60079-15:2010 4ème ED.) et avec un indice de protection minimum IP54 (EN /CEI 60529).

L'appareil doit être utilisé dans un environnement qui présente un degré de pollution maximum de 2 selon EN/ CEI 60664-1.

Lors de l'installation et du raccordement des circuits d'alimentation et de signaux, respecter les exigences de la norme EN/ CEI 60079-14.

Seuls les appareils destinés à être utilisés dans la zone Ex 2 et conçus pour être utilisés conformément aux conditions présentes du lieu d'utilisation peuvent être raccordés à des circuits de la zone 2.

L'appareil doit être raccordé aux circuits d'alimentation dont la tension nominale ne peut être dépassée de 140 % en raison de perturbations transitoires.

Ne pas raccorder de câble/ligne dans la zone explosible et ne pas séparer de liaisons si elles sont sous tension.

L’appareil doit être mis hors service et retiré immédiatement de la zone Ex s’il est endommagé ou s’il a été soumis à des charges ou stocké de façon non conforme, ou s’il présente un dysfonctionnement.

2.2 Zones avec présence de poussières explosives

AVERTISSEMENT : Risque d'explosion

L’appareil n’est pas conçu pour être utilisé dans des atmosphères dangereuses (poussière).

3. Utilisation conforme

Relais pour couplage fiable de signaux de sortie numériques Ce module permet d'interrompre les circuits en toute sécurité.

4. Caractéristiques du produit

1 circuit à fermeture non temporisé (au choix, sécurisé)

1 circuit report de signalisation non temporisé

1 sortie de signalisation TOR

Filtre à impulsion de test intégré

Signalisation d'erreurs via A1 active

Raccordement TBUS

2 fusibles 5 AT internes

5. Conseils relatifs au raccordement

Schéma synoptique ( )

Affectation de borne ( - )

Un circuit de protection adapté et efficace doit être mis en œuvre pour les charges inductives. Ce dernier doit être parallèle à la charge, et non parallèle au contact de commutation.

L'exploitant de sous-ensembles à relais est tenu de respecter, du côté contacts, les exigences en matière d'émission de bruit auxquelles sont soumis les matériels électriques et électroniques (EN/ IEC 61000-6-4) et, le cas échéant, de prendre les mesures nécessaires.

N'utiliser que des alimentations à isolation sûre avec tension SELV / PELV selon EN 50178/VDE 0160 (SELV / PELV).

Eviter les champs magnétiques dont l'intensité est > 30 A/m à proximité de l'appareil.

Commuter au maximum 10 appareils en série via le connecteur sur profilé TBUS.

ENGLISH

Safety relay

1. Content of the EC Declaration of Conformity

Manufacturer: PHOENIX CONTACT GmbH & Co.KG, Flachsmarktstr.8, 32825 Blomberg, Germany

Product designation:

Order No.:

PSR-PC20-1NO-1NC-24DC-SC

2700577

PSR-PC20-1NO-1NC-24DC-SP

2700578

The above mentioned product conforms with the most important requirements of the following directive(s) and their modification directives:

2004/108/EC

Electromagnetic Compatibility Directive (EMC)

2006/95/EC

Low Voltage Directive

94/9/EC

Ex directive (ATEX)

In order to assess conformity, the following relevant standards were consulted: EN 61000-6-2:2005+AC:2005; EN 61000-6-4:2007+A1:2011

EN 50178:1997; EN 60079-0:2012+A11:2013; EN 60079-15:2010

This declaration certifies conformity with the key requirements of the indicated directive(s), it does not, however, covenant any characteristics.

Exhibitor: Martin Müller, Head of Business Unit ION

2. Safety Notes:

Please observe the safety regulations of electrical engineering and industrial safety and liability associations.

Disregarding these safety regulations may result in death, serious personal injury or damage to equipment!

Startup, mounting, modifications, and upgrades should only be carried out by a skilled electrical engineer!

Operation in a closed control cabinet according to IP54!

Before working on the device, disconnect the power!

During operation, parts of electrical switching devices carry hazardous voltages!

During operation, the protective covers must not be removed from the electric switchgear!

In the event of an error, replace the device immediately!

Repairs to the device, particularly the opening of the housing, must only be carried out by the manufacturer.

When an error is detected by the higher-level controller, it is assumed that the safety function can no longer be performed.

The error must be removed within 72 hours or within the process safety time if required by the application.

Keep the operating instructions in a safe place!

Make sure you always use valid documentation. This is available from the Internet at phoenixcontact.net/products.

2.1 Installation in Zone 2

The category 3 device is suitable for installation in the zone 2 potentially explosive area. It fulfills the requirements of EN 60079-0:2012+A11:2013 (IEC 60079-0:2011 6th ED.) and EN 60079-15:2010 (IEC 6007915:2010 4th ED.).

The device should be installed in a housing (control or distributor box) that fulfills the requirements of EN 60079-15:2010 (IEC 60079-15:2010 4th ED.) and at least IP54 (EN/ IEC 60529) degree of protection.

The device must be used in no more than a pollution degree 2 environment as defined by EN/ IEC 60664-1.

When installing and connecting the supply and signal circuits observe the requirements of EN/ IEC 60079-14.

Only devices which are designed for operation in Ex zone 2 and are suitable for the conditions at the installation location may be connected to the circuits in the Ex zone.

The device shall be connected to supply circuits where the rated voltage cannot be exceeded by 140 % caused by transient disturbances.

Do not connect any cables/lines within the potentially explosive area nor disconnect any live connections.

The device must be stopped and immediately removed from the Ex area if it is damaged, was subject to an impermissible load, stored incorrectly or if it malfunctions.

2.2 Potentially dust-explosive areas

WARNING: Explosion hazard

The device is not designed for use in atmospheres with a danger of dust explosions.

3. Intended Use

Relay for the safe connection of digital output signals.

Using this module, circuits are interrupted in a safety-oriented manner.

4. Product features

1 undelayed enabling current path (optionally fused)

1 undelayed confirmation current path

1 digital signal output

Integrated test pulse filter.

Active error acknowledgment via A1

TBUS connection

2 internal 5AT fuses

5. Connection notes

Block diagram ( )

Terminal point assignment ( - )

A suitable and effective protective circuit is to be provided for inductive loads. This is to be implemented parallel to the load and not parallel to the switch contact.

When operating relay modules the operator must meet the requirements for noise emission for electrical and electronic equipment (EN/ IEC 61000-6-4) on the contact side and, if required, take appropriate measures.

Only use power supply units with safe isolation and SELV / PELV in accordance with EN 50178/VDE 0160 (SELV / PELV).

Avoid magnetic fields with a magnetic field strength > 30 A/m in the vicinity of the device.

Connect at most 10 devices in series via the TBUS DIN rail connector.

DEUTSCH

Sicherheitsrelais

1. Inhalt der EG-Konformitätserklärung

Hersteller: PHOENIX CONTACT GmbH & Co.KG, Flachsmarktstr.8, 32825 Blomberg, Germany

Produktbezeichnung:

Artikelnummer:

PSR-PC20-1NO-1NC-24DC-SC

2700577

PSR-PC20-1NO-1NC-24DC-SP

2700578

Das vorstehend bezeichnete Produkt stimmt mit den wesentlichen Anforderungen der nachfolgenden Richtlinie(n) und deren Änderungsrichtlinien überein:

2004/108/EG

EMV-Richtlinie (Elektromagnetische Verträglichkeit)

2006/95/EG

Niederspannungsrichtlinie

94/9/EG

Ex-Richtlinie (ATEX)

Für die Beurteilung der Übereinstimmung wurden folgende einschlägige Normen herangezogen:

EN 61000-6-2:2005+AC:2005; EN 61000-6-4:2007+A1:2011

EN 50178:1997; EN 60079-0:2012+A11:2013; EN 60079-15:2010 Diese Erklärung bescheinigt die Übereinstimmung mit den wesentlichen

Anforderungen der genannten Richtlinie(n), enthält jedoch keine Zusicherung von Eigenschaften.

Aussteller: Martin Müller, Head of Business Unit ION

2. Sicherheitshinweise:

Beachten Sie die Sicherheitsvorschriften der Elektrotechnik und der Berufsgenossenschaft!

Werden die Sicherheitsvorschriften nicht beachtet, kann Tod, schwere Körperverletzung oder hoher Sachschaden die Folge sein!

Inbetriebnahme, Montage, Änderung und Nachrüstung darf nur von einer Elektrofachkraft ausgeführt werden!

Betrieb im verschlossenen Schaltschrank gemäß IP54!

Schalten Sie das Gerät vor Beginn der Arbeiten spannungsfrei!

Während des Betriebes stehen Teile der elektrischen Schaltgeräte unter gefährlicher Spannung!

Schutzabdeckungen dürfen während des Betriebes von elektrischen Schaltgeräten nicht entfernt werden!

Wechseln Sie das Gerät nach dem ersten Fehler unbedingt aus!

Reparaturen am Gerät, insbesondere das Öffnen des Gehäuses, dürfen nur vom Hersteller vorgenommen werden.

Bei Erkennung eines Fehlers durch die übergeordnete Steuerung ist davon auszugehen, dass die Sicherheitsfunktion nicht mehr ausgeführt werden kann.

Die Fehlerbehebung muss innerhalb von 72 Stunden erfolgen oder innerhalb der Prozesssicherheitszeit, sofern die Applikation dieses erfordert.

Bewahren Sie die Betriebsanleitung auf!

Stellen Sie sicher, dass Sie immer mit der gültigen Dokumentation arbeiten. Diese steht im Internet zur Verfügung unter phoenixcontact.net/products.

2.1 Installation in der Zone 2

Das Gerät der Kategorie 3 ist zur Installation in dem explosionsgefährdeten Bereich der Zone 2 geeignet. Es erfüllt die Anforderungen der EN 60079- 0:2012+A11:2013 (IEC 60079-0:2011 6th ED.) und EN 60079-15:2010 (IEC 60079-15:2010 4th ED.).

Das Gerät ist in ein Gehäuse (Schaltoder Verteilerkasten) einzubauen, dass die Anforderungen der EN 60079-15:2010 (IEC 60079-15:2010 4th ED.) und mindestens die Schutzart IP54 (EN/ IEC 60529) erfüllt.

Das Gerät ist in einer Umgebung zu verwenden, die höchstens den Verschmutzungsgrad 2 gemäß EN/ IEC 60664-1 aufweist.

Beachten Sie bei der Installation und beim Anschluss der Versorgungsund Signalstromkreise die Anforderungen der EN/ IEC 60079-14.

An Stromkreise in der Zone 2 dürfen nur Geräte angeschlossen werden, welche für den Betrieb in der Ex-Zone 2 und die am Einsatzort vorliegenden Bedingungen geeignet sind.

Das Gerät ist an Versorgungsstromkreise anzuschließen, deren Nennspannung nicht um 140 % überschritten werden kann, verursacht durch transiente Störungen.

Schließen Sie keine Kabel/Leitungen innerhalb des explosionsgefährdeten Bereiches an und trennen Sie dort auch keine Verbindungen auf, wenn diese unter Spannung stehen.

Das Gerät ist außer Betrieb zu nehmen und unverzüglich aus dem Ex-Bereich zu entfernen, wenn es beschädigt ist, unsachgemäß belastet oder gelagert wurde bzw. Fehlfunktionen aufweist.

2.2 Staubexplosionsgefährdete Bereiche

WARNUNG: Explosionsgefahr

Das Gerät ist nicht für den Einsatz in staubexplosionsgefährdeten Atmosphären ausgelegt.

3. Bestimmungsgemäße Verwendung

Relais zur sicheren Kopplung von digitalen Ausgangssignalen.

Mit Hilfe dieses Modules werden Stromkreise sicherheitsgerichtet unterbrochen.

4. Produktmerkmale

1 Freigabestrompfad unverzögert (wahlweise abgesichert)

1 Rückmeldestrompfad unverzögert

1 digitaler Meldeausgang

Integrierter Testpulsfilter

Aktive Fehlerrückmeldung über A1

TBUS-Anschluss

2 interne 5AT-Schmelzsicherungen

5. Anschlusshinweise

Blockschaltbild ( )

Klemmpunktbelegung ( - )

An induktiven Lasten ist eine geeignete und wirksame Schutzbeschaltung vorzunehmen. Diese ist parallel zur Last auszuführen, nicht parallel zum Schaltkontakt.

Bei dem Betrieb von Relaisbaugruppen ist vom Betreiber kontaktseitig die Einhaltung der Anforderungen an die Störaussendung für elektrische und elektronische Betriebsmittel (EN/ IEC 61000-6-4) zu beachten und ggf. sind entsprechende Maßnahmen durchzuführen.

Setzen Sie ausschließlich Netzteile mit sicherer Trennung mit SELV / PELV-Spannung nach EN 50178 / VDE0160 (SELV / PELV) ein.

Vermeiden Sie Magnetfelder mit einer Magnetfeldstärke > 30 A/m in der Umgebung des Gerätes.

Schalten Sie über den Tragschienen-Busverbinder TBUS maximal 10 Geräte in Reihe.

 

 

 

PHOENIX CONTACT GmbH & Co. KG

 

 

 

 

 

 

 

 

Flachsmarktstraße 8, 32825 Blomberg, Germany

 

 

 

 

 

 

 

 

Fax +49-(0)5235-341200, Phone +49-(0)5235-300

 

phoenixcontact.com

MNR 9065286 - 01

2015-03-09

DE

Betriebsanleitung für den Elektroinstallateur

 

EN

(Originalbetriebsanleitung)

 

 

Operating instructions for electrical personnel

 

FR

(original operating instructions)

 

 

Manuel d'utilisation pour l'électricien

 

 

NL

(instructions de service originales)

 

 

Bedieningshandleiding voor elektrotechnische installateurs

 

 

(originele bedieningshandleiding)

 

 

PSR-PC20-1NO-1NC-24DC-SC

 

2700577

PSR-PC20-1NO-1NC-24DC-SP

 

2700578

P

 

 

 

 

 

 

 

HOE

NIX

 

 

 

 

 

 

Flac

 

 

 

 

 

 

3282h5smarCkONTA

 

 

 

 

 

 

 

BlomtstrasCT

 

 

 

 

 

 

 

berg,se8GmbH

& CO.

 

 

 

 

 

 

Ger

 

 

 

 

 

 

many

KG

 

 

 

 

 

 

 

PSR-

 

 

 

 

 

 

 

...

 

 

 

 

 

Ord.-

 

 

 

 

 

Phoe

nix

No.:

xx

xx

 

 

 

 

Saf

xxx

 

 

 

 

ety

 

 

 

 

 

 

 

Re

 

 

 

 

 

 

 

la

 

 

 

 

 

 

 

ys

PSR-...-SP

AWG 24-16 0,2-1,5 mm2

8 mm

 

Docum

D

entation

 

ocum

 

entation

 

PWR

 

PWR

PSR-...-SC

 

<![if ! IE]>

<![endif]>PSR-...

 

<![if ! IE]>

<![endif]>PSR-...

 

 

 

 

AWG 24-12

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

0,2-2,5 mm

 

 

 

 

 

 

 

 

0,5-0,6 Nm

 

 

UL note

 

 

 

 

 

 

Use copper wires

 

 

7 mm

5-7 lb In

 

 

 

 

 

 

 

 

rated 60°C/75°C.

 

 

 

 

 

 

 

 

 

 

A1

A1'

T-Bus

31

 

13F

13F

13

 

 

 

PSR-PC20

 

 

F1

F2

 

 

 

 

ERR

 

K1

5A T

5A T

 

 

 

 

 

 

 

 

 

 

 

PWR

 

 

 

 

 

 

 

 

DGN

K2

 

 

 

 

 

 

 

 

 

 

 

 

 

24V DC

 

 

 

 

 

 

T-Bus A2

M1

32

 

 

 

14

 

 

 

 

 

 

 

 

 

Terminal

Pin

Label

Pin assignment

 

 

 

 

 

X1

1.1

M1

24 V - Digital alarm output (PNP); supplied by NC-contact 31

1.2

A1'

24 V - Relay control input without error acknowledgment

 

X2

2.1

31

24 V - Diagnostic current path input (NC contact); ref. A2

2.2

32

24 V - Diagnostic current path output (NC contact)

 

 

 

X3

3.1

A1

24 V - Relay control input with error acknowledgment

3.2

A2

0 V - GND

 

 

 

 

 

 

 

 

 

 

 

X4

4.1

13F

Enabling current path with 5AT safety fuse (NO contact, floating)

4.2

14

Enabling current path (NO contact, floating)

 

 

 

X5

5.1

13F

Enabling current path with 5AT safety fuse (NO contact, floating)

5.2

14

Enabling current path (NO contact, floating)

 

 

 

X6

6.1

13

Enabling current path (NO contact, floating)

 

6.2

14

Enabling current path (NO contact, floating)

 

 

 

X7

T-BUS

24 V - Diagnostic current path input (NC contact)

 

0 V - GND

 

 

 

 

 

 

 

 

 

 

 

 

 

TÜV Nord Cert GmbH (NB 0044)

Langemarcktstr. 20

D-45141 Essen

EC-Type-Examination

No. 44 205 13 7552 04

© PHOENIX CONTACT 2015

PNR 106374 - 01

DNR 83151914 - 02