Inductive proximity switch
3RG4112-0AG01-PF |
NO / Schließer |
|
|
Cable / Kabel (eingegossen) |
|
||||
3RG4112-3AG01-PF |
NO / Schließer |
|
|
Connector / Stecker M12 |
|
||||
3RG4112-0AF01-PF |
NC / Öffner |
|
|
|
|
Cable / Kabel (eingegossen) |
|
||
3RG4112-3AF01-PF |
NC / Öffner |
|
|
|
|
Connector / Stecker M12 |
|
||
|
|
|
|
|
|
|
|
||
Size / Bauform |
|
|
|
cylindrical M12 / zylindrisch M12 |
|
||||
|
|
|
|
|
|
|
|
||
Mounting / Einbau |
|
|
|
embeddable / bündig |
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Operating distance / Schaltabstand |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
Rated operating distance / |
|
|
sn |
4,0 mm |
|
|
|
||
Bemessungsschaltabstand |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
Effective operating distance / |
|
|
sr |
3,60 ... 4,40 mm |
|
|
|||
Realschaltabstand |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
Assured operating distance / |
|
|
sa |
3,2 mm |
|
|
|
||
Gesicherter Schaltabstand |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
Standard target mild steel / |
|
|
|
12 x 12 x 1 mm |
|
|
|||
Meßplatte Stahlfahne St 37 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
Repeat accuracy / Wiederholgenauigkeit |
|
R |
0,20 mm |
|
|
|
|||
|
|
|
|
|
|
|
|
||
Hysteresis / Hysterese |
|
|
H |
(0,03 x sr) <=H <= (0,2 x sr) |
|
||||
|
|
|
|
|
|
|
|||
Reduction factors / Reduktionsfaktoren |
|
|
Al: |
0,50 |
Cu: |
0,40 |
|||
|
|
|
|
|
|
|
|
||
|
|
|
|
Ms: |
0,60 |
Stainl. steel / Edelst.: |
0,80 |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Power supply voltage / |
|
|
|
|
|
|
|
|
|
Versorgungsspannung |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
Rated operational voltage / |
|
|
Ue |
24 V DC |
|
|
|
||
Bemessungsbetriebsspannung |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
Operating voltage range / |
|
|
UB |
15 ... 34 V DC |
|
|
|||
Betriebsspannungsbereich |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
No-load supply current / Leerlaufstrom |
|
lo |
17 mA (24 V DC); 30 mA (34 V DC) |
|
|||||
|
|
|
|
|
|
|
|
||
max. ripple content / zul. Restwelligkeit |
|
|
10 % |
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Output / Ausgang |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
Output / Ausgangsart |
|
|
|
3 wire DC pnp / 3 Leiter DC pnp |
|
||||
|
|
|
|
|
|||||
Rated operational current / |
|
|
le |
200 mA (to / bis 50 Cel); 150 mA (to / bis 85 Cel) |
|||||
Bemessungbetriebsstrom |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
Output voltage drop / Spannungsfall max. |
|
Ud |
2,5 V |
|
|
|
|||
|
|
|
|
|
|
|
|
||
Off-state current / Reststrom |
|
|
|
0,01 mA |
|
|
|
||
|
|
|
|
|
|
||||
Short-circuit strength / Kurzschlußfestigkeit |
|
|
built-in / eingebaut |
|
|
||||
|
|
|
|
|
|
||||
Overload withstand capability / |
|
|
built-in / eingebaut |
|
|
||||
Überlastfestigkeit |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Times / Zeiten |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
Frequency of operating cycles / |
|
f |
400 Hz |
|
|
|
|||
Schaltfrequenz |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
Time delay before availability / |
|
tv |
40 ms |
|
|
|
|||
Bereitschaftsverzug |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Temperatures / Temperaturen |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
Rated temperature / |
|
|
Tu |
25 Cel |
|
|
|
||
Bemessungstemperatur |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
Ambient temperature range / |
|
|
Ta |
-25...+85 Cel |
|
|
|||
zul. Umgebungstemperatur |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
Storage temperature range / |
|
|
Ts |
-40...+85 Cel |
|
|
|||
zul. Lagertemperatur |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
||||
|
|
Release: 15.08.2013 |
|
|
|
||||
|
|
|
|
1 |
|
|
|