Technical data: Inductive proximity switch 3RG4
3RG4012-0GB33-PF |
NO / Schließer |
|
Cable / Kabel (eingegossen) |
|
|||
3RG4012-3GB33-PF |
NO / Schließer |
|
Connector / Stecker M12 |
|
|||
3RG4012-0GA33-PF |
NC / Öffner |
|
|
Cable / Kabel (eingegossen) |
|
||
3RG4012-3GA33-PF |
NC / Öffner |
|
|
Connector / Stecker M12 |
|
||
|
|
|
|
|
|
|
|
Size / Bauform |
|
|
: |
cylindrical M12 / zylindrisch M12 |
|
||
|
|
|
|
|
|
|
|
Mounting / Einbau |
|
|
: |
embeddable / bündig |
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Operating distance / Schaltabstand |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Rated operating distance / |
|
sn |
: |
2,0 mm |
|
|
|
Bemessungsschaltabstand |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Effective operating distance / |
|
sr |
: |
1,80 ... 2,20 mm |
|
|
|
Realschaltabstand |
|
|
|
|
|
|
|
Assured operating distance / |
|
sa |
: |
1,62 mm |
|
|
|
Gesicherter Schaltabstand |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Standard target mild steel / |
|
|
: |
12 x 12 x 1 mm |
|
|
|
Meßplatte Stahlfahne St 37 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Repeat accuracy / Reproduzierbarkeit |
R |
: |
0,10 mm |
|
|
|
|
|
|
|
|
|
|
|
|
Hysteresis / Hysterese |
|
H |
: |
0,02 ... 0,44 mm |
|
|
|
|
|
|
|
|
|
|
|
Reduction factors / Reduktionsfaktoren |
|
: |
Al: |
0,40 |
Cu: |
0,20 |
|
|
|
|
|
|
|
|
|
|
|
|
|
Ms: |
0,50 |
Stainl. steel / Edelst.: |
0,70 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Power supply voltage / |
|
|
|
|
|
|
|
Versorgungsspannung |
|
|
|
|
|
|
|
Rated operational voltage / |
|
Ue |
: |
24 V DC |
|
|
|
Bemessungsbetriebsspannung |
|
|
|
|
|
|
|
Operating voltage range / |
|
UB |
: |
15 ... 34 V DC |
|
|
|
Betriebsspannungsbereich |
|
|
|
|
|
|
|
|
|
|
|
|
|||
No-load supply current / Leerlaufstrom |
lo |
: |
17mA (24 V DC); 30mA (34 V DC) |
|
|||
|
|
|
|
|
|
|
|
max. ripple content / zul. Restwelligkeit |
|
: |
10% |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Output / Ausgang |
|
|
|
|
|
|
|
|
|
|
|
|
|
||
Output / Ausgangsart |
|
|
: |
3 wire DC npn / 3 Leiter DC npn |
|
||
|
|
|
|
|
|||
Rated operational current / |
|
le |
: |
200 mA (to / bis 50 Cel); 150 mA (to / bis 85 Cel) |
|||
Bemessungbetriebsstrom |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Output voltage drop / Spannungsfall max. |
Ud |
: |
2,5 V |
|
|
|
|
|
|
|
|
|
|
|
|
Off-state current / Reststrom |
|
|
: |
0,01 mA |
|
|
|
|
|
|
|
|
|
||
Short-circuit strength / Kurzschlußfestigkeit |
|
: |
built-in / eingebaut |
|
|
||
|
|
|
|
|
|
||
Overload withstand capability / |
|
: |
built-in / eingebaut |
|
|
||
Überlastfestigkeit |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Times / Zeiten |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Frequency of operating cycles / |
f |
: |
1200 Hz |
|
|
|
|
Schaltfrequenz |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Time delay before availability / |
tv |
: |
40 ms |
|
|
|
|
Bereitschaftsverzug |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Temperatures / Temperaturen |
|
|
|
|
|
|
|
Rated temperature / |
|
Tu |
25 Cel |
|
|
|
|
Bemessungstemperatur |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Ambient temperature range / |
|
Ta |
-25...+85 Cel |
|
|
|
|
zul. Umgebungstemperatur |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Storage temperature range / |
|
Ts |
-40...+85 Cel |
|
|
|
|
zul. Lagertemperatur |
|
|
|
|
|
|
|
Subject to modifications without notice |
Release: 09.09.2010 |
Copyright Pepperl+Fuchs |