Partlow MRC 7800 Operating Manual

Page 1
Form 2971 • Price $21.00
Edition 7 • © October 1997
ONE AND TWO PEN CIRCLE CHART FLOW RECORDER
MRC 7800
Installation, W iring, Operation Manual
The Partlow-West Company • Two Campion Road • New Hartford NY 13413 • 315.797.2222 • Fax: 315.797.0403
QUALITY INSTRUMENTATION DESIGNED & MANUFACTURED IN THE U.S.A.
Page 2
PAGE 2
I
shipment. Extra copies are available at the price published on the front cover.
Copyright © October 1997, The Partlow-West Company, all rights reserved. No part of this publication may be repro­duced, transmitted, transcribed or stored in a retrieval sys­tem, or translated into any language in any form by any means without the written permission of the Partlow-West Company.
This is the Seventh Edition of the MRC 7800 Flow Recorder manual. It was written and produced entirely on a desk­top-publishing system. Disk versions are available by writ­ten request to the Partlow Advertising and Publications Department.
We are glad you decided to open this manual. It is written so that you can take full advantage of the features of your new MRC 7800 Flow Recorder.
Page 3
Table of Contents
SECTION 1 - GENERAL Page Number 1.1
Product Description 5
SECTION 2­INSTALLATION & WIRING
2.1 Installation & Wiring 7
2.2 Unpacking 7
2.3 Location 7
2.4 Mounting 7
2.5 Preparation for Wiring 8
2.6 Wiring Connections 9
SECTION 3 - GENERAL OPERATION
3.1 How the instrument operates 14
PAGE 3
SECTION 4 ­CONFIGURATION & OPERATION
4.1 Configuration Introduction 18
4.2 Shipped Configuration / Jumper Positioning 19
4.3 Operation Summary 19
4.4 Start Up Procedure 20
4.5 Configuration & Operation 21
4.6 Data Logger Display Mode 32
SECTION 5 - SERVICE
5.1 Service 34
5.2 Changing Charts 34
5.3 Changing Pens 34
5.4 Calibration 35
5.5 Test Mode 37
5.6 Troubleshooting and Diagnostics 40
APPENDICES
A - Board Layouts
A-1 Processor Board 46 A-2A Relay (SPST) Output Board 47 A-2B Relay (SPDT) Output Board 48
A-3 Current Output Board 49 B - Glossary 50 C - Model Number Hardware Matrix Details 52 D - Specifications 53 E - Software Record/Reference Sheet 55
Warranty Inside Back Page
Page 4
PAGE 4
FIGURES & TABLES
Figure 1-1 Front View 5 Figure 1-2 Display Features 6 Figure 2-1, Panel Dimensions 8 Figure 2-2 Board & Terminal Locations 9 Figure 2-3 AC Power Input 10 Figure 2-4 Volt, millivolt, & milliamp Input 11 Figure 2-5 Transmitter Power Supply Input 11 Figure 2-6 Remote Reset Input 12 Figure 2-7A Relay Output (SPST) 12 Figure 2-7B Relay Output (SPDT) 13 Figure 2-8 SSR Driver Output 13 Figure 2-9 Current Output-Standard 13 Figure 4-1 Keypad Features 19 Figure 5-1 Changing Pens 34 Table 3-1 Variable exponents of Parshall flumes 16 Table 3-2 Totalizer Factor 17 Table 3-3 Totalizer Factor Example 17 Table 4-1 Enable Mode Configuration Procedure 25 Table 4-2 Program Mode Configuration Procedure 26 Table 4-3 Alarm Set Mode Configuraton Procedure 30 Table 4-4 Data logger Setup Mode Configuration 30 Table 4-5 Preset Adjust Mode Configuration 31 Table 4-6 Data logger Display Mode Configuration 33 Table 5-1 Calibration Procedure 35 Table 5-2 Test Procedure and Description 37
Page 5
Product Description 1.1
1.1.1 GENERAL
The instrument is a microprocessor based circular chart recorder capable of measuring, displaying, recording, and datalogging flow process variables. Three square root extraction algorithms are available for use with a variety of transmitters and transducers, and four algorithms are available for use with a variety of weirs and flumes.
Recording functions, alarm settings, and other parameters are easily entered via the front keypad. All user data can be protected from unauthorized changes by the Enable mode security system, and is protected against loss from AC power failure by battery back-up.
The process input for each pen is user configurable to directly connect to either mVDC, VDC, or mADC inputs. Changes in input type are easily accomplished in the field. The unit's process input is isolated from the rest of the unit. An isolated 24VDC regulated transmitter power supply can be provided for use with two-wire mADC inputs.
The unit can be ordered for either 115VAC or 230VAC power at 50/60Hz. The 230VAC option includes a switch for changing back and forth between 230VAC and 115VAC. The unit is housed in a plastic enclosure suitable for panel or surface mounting.
1.1.2 RECORDING
The unit incorporates a 10 inch circular chart. One box of standard charts is provided with each unit. Charts are available in a wide selection of ranges. Chart rotation speed is programmable from 0.1 to 999.9 hours per revolution in 0.1 hour increments. The instrument can be provided with one or two pens. Pen 1 is red and Pen 2 is green. Pens are of the disposable fiber-tip type. Changes in pens, as well as charts, are quickly and easily accom­plished.
PAGE 5
A programmable chart/display filter is provided. This filter provides adjustable dampening of the value displayed and recorded. The filter need not be used. (Configured in program mode as "dFF," Display Filter Factor.)
FIGURE 1-1
Pen 1 Auto/Manual
Display
Key
Select Key
Pen 2 Auto/Manual Key
PEN 1 DISPLAY
Keypad Scroll Key Up Key Down Key
PEN 2 DISPLAY
Page 6
PAGE 6
1.1.3 DISPLAYS
Each unit is provided with an eight character digital display and status indicators for each pen provided. The display provided in the upper right corner is for Pen 1, and the display in the lower right corner is for Pen 2. Status indication is provided for Alarm 1 and Alarm 2. The display is programmable for none, one, two or three decimal places for process value and total, with additional scaling ability for the total. The second display is also optional on one pen units with totalization for simultaneous display of the process value and total.
1.1.4 ALARMS
Alarm indication is standard on all units. Alarm settings are fully programmable. Alarm type may be set as Process high or low. Indication is via status LED's provided for each pen. Alarm outputs can be provided by assigning any specified relays (SPST, SPDT or SSR driver) to the respective alarm.
1.1.5 PROCESS VALUE OUTPUT
If a unit is specified with 4 to 20 mADC outputs, these outputs may be programmed to operate as a Process Value Output. As such, the output is scaleable.
FIGURE 1-2
PV
ALRM1 ALRM2
TOT
Page 7
Installation & Wiring 2.1
CAUTION: The Instrument AC power input is as specified in the model number; 115VAC or 230VAC. Verify the AC power input provided with the instrument prior to proceeding with installation.
Read these instructions carefully before proceeding with installation and operation. Electrical code requirements and safety standards should be observed. Installation should be per­formed by qualified personnel.
Unpacking 2.2
Remove the unit from the carton and inspect it for any damage due to shipment. If any damage is noticed due to transit, report and file a claim with the carrier. Write the model number and serial number of the unit on the inside of the front cover of this Operation Manual for future reference when corresponding with the factory.
Location 2.3
Locate the instrument away from excessive moisture, oil, dust, and vibration. Do not subject the instrument to operating temperatures outside of 0 to 55˚ C.
PAGE 7
Mounting 2.4
Figure 2-1 (page 8) shows installation view and physical dimensions for a panel mounted unit.
The panel that the unit will be mounted in must provide rigid support for the approximately 20 pound unit . Adjacent units may be mounted within a minimum of 2 inches horizontally and 3 inches vertically, providing that proper panel support is supplied.
PANEL MOUNTING HARDWARE REQUIRED: (not provided with instrument)
(4) 9/32" x 2" bolts w/nuts (4) appropriate lockwashers
PANEL MOUNTING:
1) Cut panel hole to dimensions shown in Figure 2-1 (page 8).
2) If the rear of the panel is accessible for wiring after mounting, place the unit in the
panel cutout and fasten it to the panel through mounting holes supplied in the case flange.
3) If the rear of the panel is not accessible for wiring, proceed with wiring preparation and wiring, then mount the unit.
SURFACE MOUNTING:
1) If surface mounting is required, use Kit # 64402001 (ordered separately) Install mounting
brackets on sides of case and mount on the mounting surface.
Page 8
PAGE 8
FIGURE 2-1
EC1
15 1/8
WIDTH OF COVER
2 19/32 (65.9mm)
12 5/8
7 1/2
(320.7 mm)
(190.5 mm)
Preparation for Wiring 2.5
(384.2 mm).
9/32
13 1/2
(342.5 mm )
13 15/16
(354 mm)
EC3
EC4
EC2
DIA.(7.1mm)
(64 mm)
13 3/16
(335 mm)
7/32
(5.5 mm)
Mounting Bracket
3 3/4 (92.3 mm)
4 11/16
(119.1 mm)
(2)
2.5.1 WIRING GUIDELINES
Electrical noise is a phenomenon of the typical industrial environment. The following are guidelines that must be followed to minimize the effect of noise upon any instrumentation.
2.5.1.1 INSTALLATION
Listed below are some of the common sources of electrical noise in the industrial environ­ment: * Ignition Transformers * Arc Welders * Mechanical contact relays * Solenoids * Motors Before using any instrument with devices listed previously, the instructions below should be followed:
1. If the unit is to be mounted in the same panel as any of the listed devices, separate them by the largest distance possible. For maximum electrical noise reduction, the noise generating devices should be mounted in a separate enclosure.
2. If possible, eliminate mechanical contact relays and replace them with solid state relays. If a mechanical relay being powered by the unit's output device cannot be replaced, you may wish to use a solid state relay to isolate the instrument from this source of noise.
3. A separate isolation transformer which feeds only instrumentation should be considered. If available, it can isolate many noise sources from the AC power input of the unit.
4. If the unit is being installed in an existing installation, a review of the wiring in the existing area should be done.
Page 9
2.5.1.2 AC POWER WIRING
5
4
2
Earth Ground Each unit includes noise suppression components attached to the chassis that require an earth ground connection. To verify that it is earth ground being attached, make a resistance check from instrument chassis to the nearest metal water pipe or proven earth ground. This reading should not exceed 100 ohms.
Neutral (For 115 VAC) It is good practice to assure that the AC neutral is at or near ground potential. To verify this, a voltmeter check between neutral and ground should be done. On the AC range, the reading should not be more than 50 millivolts. If it is greater than this amount, the secondary of this AC transformer supplying the instrument should be checked by an electrician. A proper neutral will help ensure maximum performance from the instrument.
2.5.1.3 WIRE ISOLATION
The instrument is designed to promote proper separation of the wiring groups that connect to the instrument. The AC power wire terminals are located near the top of the instrument boards. The analog signal terminals are located near the bottom of the intrument boards. Maintain this separation of the wires to insure the best protection from electrical noise. If the wires need to be run parallel with any of the other lines, maintain a minimum 6 inch space between the wires. If wires must cross each other, do so at 90 degrees. This will minimize the contact with each other and reduces "cross talk". "Cross talk" is due to the EMF (Electro Magnetic Flux) emitted by a wire as current passes through it. This EMF can be picked up by other wires running in the same bundle or conduit.
PAGE 9
2.5.1.4 USE OF SHIELDED CABLE
Shielded cable helps eliminate pickup of noise the wires may be exposed to. Shielded cable is a single or multi-pair of insulated wires with each wire or pair of wires surrounded by a wire mesh or conductive foil and then covered with plastic insulation.
It is recommended that all analog signals be run with shielded cable. Connection lead length should be kept as short as possible, thus keeping wires protected by the shielding. The shield should be grounded at one end only, at the transmitter or transducer and the shield should be stripped back before going inside the unit case .
Wiring Connections 2.6
All wiring connections are typically made to the unit with it installed. Connections should be made at the terminal blocks, two 12 gauge wires maximum, using copper conductors only. Terminal blocks are designated TB1 thru TB13. See Figure 2-2 for the terminal block locations.
FIGURE 2-2
Processor Board
12
TB1
1 2 3 4 1 2 3 4 1 2 3
TB6 TB7 TB8
RELAY/SSR Driver Board
TB9
1 2 3 4
Current Output Board
TB 2
1 2
TB3 TB4
1 2 1 2 3 4 5 1 2 3 4
TB5
TB10 TB11 TB12 TB13
1 2
1 2 1 2 1
Page 10
PAGE 10
2.6.1 ELECTRICAL CONDUIT OPENINGS
The instrument case will have 3 or 4 conduit openings, depending upon the number of outputs specified. To help minimize electrical noise that may adversely affect the operation of the instrument, the wires indicated below should be routed through the conduit opening specified. See Figure 2-1 (page 8) for conduit opening locations.
EC1 - AC power EC2 - Analog input and mAdc outputs EC3 - SPST, SPDT relay or SSR driver outputs EC4 - SPST, SPDT relay or SSR driver outputs
(provided when > 4 relays & SSR's are specified)
Unused conduit openings should be sealed if exposed to the environment.
2.6.2 AC POWER WIRING CONNECTIONS WARNING: To avoid electrical shock AC power wiring must not be
connected at the source distribution panel until all wiring connections are completed.
FIGURE 2-3
AC Instrument Power Input Connect the 115 VAC hot and neutral to terminals 1 and 2 respectively of TB1. See Figure 2­2 (page 9) for Terminal Board locations on the instrument. Connect the 230 VAC one leg to each terminal, be sure to check the position of the Voltage Selector switch provided with 230 VAC instruments. The switch position must match the voltage input to the instrument.
Connect the AC ground at the green ground screw on the left side of the inside of the case
Line 1
TB1
1
Line 2
2
Page 11
FIGURE 2-4
-
-
-
-
-
-
Volt, Millivolt and milliamp Input Make the volt, millivolt or milliamp conections as shown below. Use TB4 for Pen 1 and TB5 for Pen 2. Terminal 1 is positive and terminal 2 is negative. Be sure that input conditioning jumpers are in the correct positions for the input being connected. See Appendix A-1 (page
46).
TB4 or TB5
PAGE 11
+
-
2345
1
SHIELDED
NOTE: Fault Detection Not Functional for 0-5V Input.
TWISTED PAIR
MAY BE
+
SOURCE
GROUNDED OR UNGROUNDED
FIGURE 2-5
Transmitter Power Supply If the isolated 24 VDC regulated transmitter power supply has been specified, the connections should be made as shown. Connections are made using TB3, terminal 1 is positive and terminal 2 is negative. The power supply is capable of providing the power needed by up to 2 transmitters.
TB3
TB4 or TB5
TB3
TB4
TB5
+ 12
+
-
12345
SHIELDED
TWISTED
PAIRS
+
12
+
TWO WIRE
TRANSMITTERS
TWO WIRE
TRANSMITTERS
+
-
12345
+
TWO WIRE
TRANSMITTERS
+
-
12345
+
Page 12
PAGE 12
5
FIGURE 2-6
Remote Reset Input Make connections as shown. Use TB4 for Pen 1 and TB5 for Pen 2. Terminal 3 is ground and terminal 4 is the input.
TB4 or TB5
+
-
1 2 3 4
SHIELDED TWISTED PAIR
REMOTE DRY CONTACT
2.6.3 OUTPUT CONNECTIONS
Relay outputs, if provided in the instrument, may be assigned to alarm, preset, or pulsed output functions for Pen 1 and/or Pen 2 (if present). Current outputs may be assigned to process value retransmission output for Pen 1 and/or Pen 2 (if present). The assignment of the output function is accomplished in the Program mode, see Section 4.5.3 (page 22). SPST relay and/or SSR driver output(s) is/are designated as Relay A through Relay H. SPST relays begin with Relay A designation, then B, C, etc. SSR drivers begin with Relay H designation, then G, F, etc.
FIGURE 2-7A
Relay Output (SPST) Connections are made to relays A through F as shown. Terminal connections are made using TB6 (Relay/SSR Driver A, B), TB7 (Relay/SSR Driver C,D), and TB8 (Relay/SSR Driver E, F).
HOT NEU
POWER
LOAD
5 AMPERES
1234
MAXIMUM AT 115 VAC
TB6 OR TB7 OR TB8
Page 13
FIGURE 2-7B
7
-
-
Relay Output (SPDT)
HOT NEU
PAGE 13
POWER
LOAD
N.O C
TB6 OR TB
FIGURE 2-8
SSR Driver Output Connections are made to relays H through A as shown. Terminal connections are made using TB9, TB8, etc. depending on the number of SSR Driver outputs specified.
1 234
N.C
123
+
SSR
5 AMPERES MAXIMUM AT 115 VAC
SOLID STATE RELAY
TB6 THRU TB9
FIGURE 2-9
Current Output Connections are made to standard current outputs A through D as shown. Each current output is programmable as either 4 to 20mADC or 0 to 20mADC. Each output must be assigned to the desired function (refer to Table 4-2, page 26, for details). Terminal connec­tions are made using TB10 through TB13 for current output A through D respectively. Con­nect positive lead (+) to terminal 1 and the negative lead (-) to terminal 2. Current outputs will operate up to 650 ohms maximum load.
+
-
1 2
SHIELDED TWISTED PAIR
+
LOAD
650 OHMS MAXIMUM
Page 14
PAGE 14
How The Instrument Operates 3.1
3.1.1 OFF MODE
In the Off mode, the instrument alarm and preset function(s) is/are turned off, pulsed output(s) are inactive and process retransmission signal(s) remain(s) active. The chart rotation can be selected in the Program mode to stop or continue to rotate when the instrument is in the Off mode. The pen remains active. The totalization function is inactive, but datalogging functions continue.
The Off mode is entered by pressing and releasing the SCROLL key until the display reads oFF, then pressing the DOWN key. If the instrument was displaying process value, the display will read oFF, then the current process variable at two second intervals. If the instrument was displaying total, the display will read oFF, then the total at two second intervals. Entering the Off mode of a dual pen instrument will cause both pens to enter the Off mode. The second pen display will be blank as the upper display reads oFF and displays the value for the second pen at the same time as the upper display.
To exit the Off mode, depress the SCROLL key to proceed to any other mode, pressing the DOWN key to enter that mode.
3.1.2 OPERATE MODE
In the Operate mode, the instrument alarm function(s), the preset function(s), the pulsed output(s) and the process retransmission signal(s) are actively responding to the process variable as selected in the Program, Alarm Set and Preset modes and the chart will be rotating at the rate selected. The totalization function is active, as is the datalogging function.
3.1.2.1 TOTALIZATION
Totalization can be implemented on instruments provided with the totalization feature. Totalization can be programmed on or off for each pen.
To initiate totalization, depress the SCROLL key until oPEr is displayed, then depress the DOWN key.
To view the total, depress the DISPLAY SELECT key once with the PV value displayed. The TOT light should be lit and the total for Pen 1 in the upper display and the total for Pen 2 in the lower display.
Instruments with Totalization and second display will have the total displayed in the lower display whenever the upper display is set to PV.
On two pen units only, a Combined Total is available. When activated in the Program mode an additional step is added to the display choice sequence provided by the Display Select Key.
If the totals are displayed and the DISPLAY SELECT key is depressed, the Combined Flow Rate will appear in the top display with a C in the leftmost digit and the Combined Total will appear in the bottom display. The PV and TOT indicators will be lit, respectively.
Note: When Combined Total is being used, it is required that the decimal position, dPoS, and totalizer decimal position, tdP, in the Program mode, for both pens are the same. When the totalizer for Pen 1 is reset, the combined total is also reset.
Upon sensor break, the Combined Total will increment at a indeterminate rate.
Page 15
3.1.2.2 PULSED OUTPUTS
Pulsed output(s), one for each pen, can be implemented on instruments provided with the totalization feature and a relay that is not assigned to any other function.
Pulsed output is selected in the Program mode. With a pulsed output select (PoS) equal to 1, each time the Totalizer Display is incremented, the relay that is assigned, in the Program mode, as a pulsed output will close for a duration of 50 milliseconds or 60 milliseconds based on a 60 Hz or 50 Hz line frequency, respectively.
On two pen instruments, a Combined Pulse Output is available. This feature provides a pulsed output as the Combined Total increases.
Note: Upon sensor break, the Combined Pulse Output will increment at a indetermi­nate rate.
3.1.2.3 PROCESS VALUE RETRANSMISSION
Process value retransmission can be implemented on instruments provided with at least one 4 to 20mA output.
Process value retransmission is selected in the Program mode. When selected, a current output must be assigned and the process output must be scaled.
On two pen instruments, a Combined Flow Rate is available. When selected in the Program mode, this feature provides a process value retransmission value equal to the combined flow rate. The value is scaled using Pen 1 process output upper and lower parameters.
PAGE 15
3.1.2.4 DATA LOGGING
Data logging can be implemented on instruments provided with the data logging feature, and it will store data for up to 28 days.
Each day, at the time specified by ttLd (time to log data), the following data will be logged: date, minimum rate, its time, maximum rate, its time, daily total, and average rate. The daily total is derived by substracting "yesterday's total" from the current total. The average rate is derived from the daily total, taking into account the flow time base. After the data is logged, "yesterday's total" will be set to the current total, and the minimum and maximum rates and times are set to the current rate and time.
Logged data is accessed via a day number, with 1 through 7 corresponding to the current week. At the beginning of each week (00:01 on day 1 - each Monday) the data is shifted down one week, with the oldest weeks worth of data being discarded. All data for the current week is zeroed, including the date for each day.
3.1.2.5 ENGINEERING UNITS PROCESSING ALGORITHM
In the Program mode, the parameter EuPA, Engineering Units Processing Algorithm specifies how the engineering unit inputs are handled. This allows selection of the various algorithms to convert the raw input in to the desired process value.
LINEAR CONVERSION - EuPA = 0 For those sensors/transmitters that provide an output directly proportional to flow, or other applications where the instrument may be used with a linear input to output transformation.
SQUARE ROOT EXTRACTION - EuPA = 1 The square root extraction function applies to rate of flow measurments using differential pressure sensors. Differential pressure transmitters typically generate a 4-20mADC signal that represents differential pressure, not flow. The flow is a function of the square root of the differential pressure.
2 STAGE SQUARE ROOT EXTRACTION - EuPA = 2 This approach is used to minimize the process value below a 4% input, since it is less meaningful due to inaccuracy and repeatability problems. Below 4% a linear function is applied. (Continued on next page)
Page 16
PAGE 16
3 STAGE SQUARE ROOT EXTRACTION - EuPA = 3 This approach is used to further minimize the process value below a 1% input, since it is even less meaningful. Below 1% a low gain linear function is applied. Between 1% and 2.5% a higher gain linear function is applied. Above 2.5% the square root function applies, as the sensor begins to provide a reasonably accurate and repeatable output. Refer to the glossary (page 53).
VARIABLE EXPONENT - EuPA = 4 Open channel flow is used in wastewater and other applications. For rectangular weirs, the flow is proportional to the height/head to the 3/2 power. For triangular (or V notch) weirs, the flow is proportional to the height/head to the 5/2 power. For Parshall flumes, the flow is proportional to the height/head to approximately the 3/2 power. See Table 3-1. When variable exponent is selected in the Program mode, Engineering Units Exponent, EuE, must be set for the correct exponent value.
TABLE 3-1
The exponent for a number of common Parshall flumes are as follows:
1 - inch = 1.55 2 - inch = 1.55 3 - inch = 1.547 6 - inch = 1.58 9 - inch = 1.53 1 to 8 ft = 1.522w raised to the .023 power 10 to 50 ft = 1.6
w = throat width in feet
PIECEWISE LINEAR - EuPA = 5 For some applications, the relationship between the input and process value cannot be specified by one of the available algorithms. For these instances, the relationship can be approximated by a straight line relationship over portions of the span. Provided enough pieces, this method will provide the required accuracy. When piecewise linear is selected, the second set of Engineering Units parameters, Euu2 and EuL2 must be used to specify the
span of the input, and then iu1, iu2....iu20 and Pu1, Pu2.....Pu20 are the input and process
values for the respective points, in engineering units. VARIABLE EXPONENT WITH CORRECTION - EuPA = 6
For some applications, the relationship between the input and process value can be basically characterized as exponential, but not to within the accuracy desired. Use of the Piecewise Linear algorithm may require a large number of points to provide the desired accuracy. By using the piecewise linear method to provide a correction to the simple exponential, a high degree of accuracy can be achieved. This is especially applicable to open channel flow using Palmer-Bowlus flumes or H flumes. Consult factory for assitance, if needed, when using variable exponent with correction.
SATURATED STEAM FLOW WITH PRESSURE CORRECTION - EuPA = 7 Only available with a 2 Pen unit. For saturated steam flow, accurate flow measurement is dependent on pressure correction. By using the second pen to input and record pressure, the pressure data is available to correct the flow value. The input is typically gauge pressure, which is converted to absolute pressure by the instrument. Since the pressure may be in the 60 PSIG range, barometric pressure or elevation can induce an error. Therefore, the baro­metric pressure, bAro, needs to be set in the Alarm Set mode. If the input is absolute pressure, bAro must be set ot zero.
Page 17
3.1.2.6. TOTALIZER FACTOR
Scaling of the displayed total is possible, with the use of totalizer factor, tFAC. When used, the displayed value is multiplied by a factor to obtain the actual total. See Table 3-2.
TABLE 3-2
tFAC = 0 Actual Total = Displayed Total Times 1 tFAC = -1 Actual Total = Displayed Total Times 10 tFAC = -2 Actual Total = Displayed Total Times 100 tFAC = -3 Actual Total = Displayed Total Times 1000 tFAC = -4 Actual Total = Displayed Total Times 10000 tFAC = 1 Actual Total = Displayed Total Times 0.1 tFAC = 2 Actual Total = Displayed Total Times 0.01 tFAC = 3 Actual Total = Displayed Total Times 0.001
Example An application is measuring flow at a maximum rate of 6000 gallons per minute (6000 gpm). The steady flow rate is 2000 gallons per minute (2000 pgm). Table 3-3 shows how, with various settings in the Program mode, the process variable displayed and the total displayed can be configured.
PAGE 17
TABLE 3-3
6000 gpm, flow rate 2000 gpm dPoS Euu EuL PV tdP tFAC Ftb Total displayed at t = 1 min
0 6000 0 2000 0 0 2 XXXX2000 0 6000 0 2000 0 -1 2 XXXXX200 0 6000 0 2000 0 -3 2 XXXXXXX2
6000 gpm, flow rate 2000 pgm, PV in gps dPoS Euu EuL PV tdP tFAC Ftb Total displayed at t = 1 min
0 100 0 33 0 0 1 XXXX1980 0 100 0 33 0 -1 1 XXXXX198 0 100 0 33 0 -3 1 XXXXXXX1
6000 gpm, flow rate 2000 gpm, PV in gpm dPoS Euu EuL PV tdP tFAC Ftb Total displayed at t = 1 min
0 6000 0 2000 1 0 2 XXX2000.0 0 6000 0 2000 1 -3 2 XXXXXX2.0
6000 gpm, flow rate 2000 gpm, PV in gps dPoS Euu EuL PV tdP tFAC Ftb Total displayed at t = 1 min
0 100 0 33 1 1 1 XXX1980.0 0 100 0 33 1 -3 1 XXXXXX1.9
6000 gpm, flow rate 2000 gpm, PV in mgd dPoS Euu EuL PV tdP tFAC Ftb Total displayed at t = 1 min
3 8.640 0.000 0.002 0 0 4 XXXXXXX0 3 8.640 0.000 0.002 0 3 4 XXXXXXX2 3 8.640 0.000 0.002 2 3 4 XXXXX2.00
Page 18
PAGE 18
Configuration Introduction 4.1
After completing installation of the unit, the configuration procedures contained within this section must be performed to prepare the unit for operation on the intended application. The procedures include selecting specific parameters, entering data and possible jumper position­ing.
Parameter selections and data entry are made via the front keypad. To ease configuration and operation, user entered data has been divided up into several modes. Each mode contains a different type of data or may be used for specific operating functions. For two pen instruments, each mode is common to both pens. These modes are as follows:
Mode Display Code Function Description
Off oFF Operation Alarm Outputs off, Totalization off Operation oPEr Operation Operation Program Prog Configuration Configure operating parameters Alarm Set ASEt Configuration Set alarm settings Data logger dLS Configuration Adjust/set real time and log time
Setup Data logger dLd Operation View logged data
Display Preset PSA Operation Adjusts, sets preset values
Adjust Test tESt Service Perform unit tests Calibration CAL Service Perform unit calibration Enable Enab Configuration Lockout or enable access to any
mode
Associated with each mode is a series of unique displays which are accessed via the front keypad.
Prior to first time operation of the unit, the configuration procedures for the Program, Preset Adjust, Data logger Setup, and Alarm Set modes must be performed as applicable.
Calibration and Test modes are not used as part of the unit configuration or operation. These are used for service and maintenance functions and are discussed in detail in Section 5.6 of this manual (page 40).
Page 19
Shipped Configuration/Jumper Positioning 4.2
Each instrument is factory shipped ready to accept a 4-20 mA process input on each speci­fied pen. All configuration parameters in each mode are set to default values. These defaults are shown in tabular form under the description for each mode. Instrument AC power input is as specified in the instrument model number and as shown on the ratings label. The 230VAC option includes a switch for changing between 230VAC and 115VAC. If this feature is provided, verify AC input and switch position before applying power to the instrument.
4.2.1 JUMPER POSITIONING
Jumpers are used in all units to provide a security lockout feature and to condition the process input for each pen. All jumpers are typically of the three pin type and have two functions. All jumpers are located on the instrument's Processor board. A board layout and jumper loca­tions are shown in Appendix A-1 (page 46). Check the actual jumper position in the unit to be configured and verify the proper position for the intended application. If the current position is not correct, make changes.
The process input jumpers JU4 and JU5 condition the hardware at a basic level. Detailed input type selection is made in the Program mode configuration (page 26).
PAGE 19
Operation Summary 4.3
The configuration and operating modes, the method of moving from one mode to another, and the basic parameter functions are described in each individual section . Data and parameter entry is made by stepping through each mode and making an appropriate response or entry to each step.
4.3.1 KEYPAD OPERATION
Refer to Figure 4-1 for the Keypad features. Use the SCROLL, UP and DOWN keys as indicated to program and operate the intrument.
4.3.1.1 UP/DOWN CHANGE RATE
The Up and Down keys are used to adjust numerical values up or down respectively. The rate at which a given value will change is dependent upon the length of time the key is kept depressed, initially slow then increasingly faster.
FIGURE 4-1
SCROLL Key
DISPLAY SELECT Key
UP Key
DISP SEL
DOWN Key
Page 20
PAGE 20
4.3.2 CONFIGURATION DISPLAYS
Each pen specified is provided with its own 4 digit LED display (8 digits for totalization option). These are used during configuration to display the parameter codes and values. The display located in the upper right hand corner of the instrument is used to show the codes for Pen 1 and those that are common between Pens 1 and 2. The display in the lower right hand corner is used to show the configuration codes for Pen 2 (if provided).
During normal operation, the display(s) are used to indicate process value(s) as selected in the Program mode.
4.3.3 MODE SELECTION
If the instrument is either in the Off mode or the Operation mode, repeated pressing and releasing of the SCROLL key will cause the instrument to display the code corresponding to each mode that is enabled. To enter a mode, while the code is displayed, press the DOWN key.
Entry into any mode, except the Operation and Enable modes, will cause the alarm(s) to turn off and any process re-transmission value output(s) to be 0%.
Start Up Procedure 4.4
All configuration parameters are listed in Tables 4-1 through 4-3 (pages 25-30) For a single pen instrument, parameters for each mode are displayed in the upper right
display. If the instrument being configured is a two pen, a sequence of applicable parameters will be displayed in the Pen 2 display after Pen 1 parameters have been reviewed and configured. After the Pen 2 parameters have been completed, parameters common to both pens will be configured and displayed in the Pen 1 display.
The instrument is provided with a time out feature. If the instrument is in any mode and no keypad activity takes place for 30 seconds, the instrument will time out and exit the mode automatically. The display will be the code for the respective mode. If a mode code is displayed for 5 seconds with no keypad activity, then the time out will cause the instrument to proceed to either the Operation or Off mode, depending upon which operational state was in use before entrance into the mode.
4.4.1 POWER UP PROCEDURE
Step 1 Verify that all electrical connections have been properly made before applying power to the unit.
Step 2A - For instruments with software revision R2.99 and below Upon power up, 7XXX will be displayed (X representing digits), then XXXX, then XXXX, identifying the twelve digit model number as defined in the order matrix. Next, the EPROM part number will be indicated P-XX. After the EPROM part number, the software revision level will be displayed in the format rX.XX then tSt1, tSt2, and tSt3 will be displayed while Test 1 through 3 are executed automatically. Upon successful completion of these test, oPEr or oFF will be displayed for about 3 seconds. The mode displayed will be the mode the instrument was in when the power was turned off. During this time, the operator may select another mode (Alarm Set, Enable) or non-operational mode (Test, Program, Cal).
Page 21
Step 2B - For instruments with software revision r3.00 and above Upon power up, a brief flash on all displays (upper and, if equipped, lower) will occur to show the instrument is "alive". Then 7XXX will be displayed (X representing digits) then XXXX, then XXXX, identifying the twelve digit model number as defined in the order matrix. Next, the EPROM part number will be indicated P-XX. After the EPROM part number, the software revision level will be displayed in the format rX.XX followed by P.dn (if Pen Action on Power Up, PAPU, in Program Mode is set to 0, pens go to "home" position at power up). During this display, the decimal point after the "P" will blink to show the mode is active. Upon successful completion of this routine, oPEr or oFF will be displayed for about 3 seconds. The mode displayed will be mode that the instrument was in when the power was turned off. During this time the operator may select another mode (Alarm Set, Enable) or non-operational mode (Test, Program, Cal).
Step 3 If any error messages are displayed, refer to Section 5.6 (page 40) for a definition of these error messages and the required action.
Configuration 4.5
4.5.1 DIGITAL DISPLAY AND STATUS LED's
The digital display provided for each pen has 4 digits (8 digits for totalization option) and a decimal point. Each digit has seven segments and is capable of producing numeric characters from 0-9 and certain alpha characters. The digital display is used to provide indication of process variable as well as displaying codes used for configuration and operation of the instrument. The following status indicators are also provided:
PAGE 21
ALRM1 Red Lights when Alarm 1 is on ALRM2 Red Lights when Alarm 2 is on PV Red Lights to indicate that the Process Value is being
displayed TOT Red Lights to indictae that the Total is being displayed Refer to Figure 1-2 (page 6) for the display features.
4.5.2 KEYPAD CONTROLS
The keys provided on the keypad and their functions include: SCROLL: Used to: 1. Advance the display through the enabled modes.
2. While in a mode, used to sequence the parameter
codes and values
3. Exit some Test and Calibration functions.
4. Work in conjuction with other keys.
UP: Used to: 1. Exit a mode.
2. Turn a mode On in the Enable mode.
3. Increase a numerical value.
4. Work in conjuction with other keys.
DOWN: Used to: 1. Enter a mode.
2. Turn a mode Off in the Enable mode.
3. Decrease a numerical value.
4. Work in conjuction with other keys.
Page 22
PAGE 22
DISPLAY SELECT: Used to: 1. For units specified with totalization, to change the
value displayed between Process Value (PV) Total (TOT), Combined Flow/Total, and Alternate Process Value.
2. For units not specified with totalization, this key has no function.
3. DISP/SEL and UP will reset 1st pen total. DISP/SEL and DOWN will reset 2nd pen total. They must be kept depressed for 5 seconds.
Lamp test
All display and status LED's can be illuminated simultaneously by depressing the UP and DOWN keys at the same time. Any defective LED's will not light.
*CHANGE CHART (also see Changing Charts, Section 5.2) If the UP and DOWN keys are held depressed for more than 2 seconds but less than 4 seconds, the display will show Cchg momentarily. The pen(s) will move to and remain at a point above the top graduation on the chart and the chart will stop rotation to allow the chart to be changed. The pens will remain fully upscale with the chart OFF; otherwise, the unit will continue to operate normally in the current mode. To restore pen(s) position and chart rotation, press the UP and DOWN keys for more than 2 seconds but less than 4 seconds.
PEN RESYNCHRONIZATION
To resynchronize the pen(s), depress the UP and DOWN keys for 4 seconds, the display will show P dn momentarily, the pen(s) are driven to the "Pen Home" position below the bottom graduation on the chart while the unit resynchronizes their position. After about 14 seconds, the pen(s) will return to their correct position. All other functions of the unit's present mode continue to operate normally.
4.5.2.1 ENTERING THE ENABLE MODE
The Enable mode is entered by pressing and holding the UP and DOWN keys simultaneously while in the Operate or Off modes. Holding the two keys depressed for 10 seconds will cause the display to show the EnAb prompt which is the entry point into the Enable mode.
A hardware jumper located on the Processor Board (Appendix A-1, page 46) can be used to lock/unlock the Enable mode. When the jumper is moved to the locked position, entry into the Enable mode is not possible until the jumper is moved to the unlock position.
4.5.3 PROGRAM MODE CONFIGURATION PROCEDURE
The Program mode provides a means to configure or reconfigure the unit operation within the limits of the hardware specified and provided. Only those parameters that are applicable, as determined by the hardware provided, will appear.
Review the entry procedure in 4.4.1 and the configuration procedures in Table 4-2 (page 26). Use the "Your Setting" column in the table to record your programming.
4.5.3.1 ENTERING THE PROGRAM MODE
From the Operate or Off mode, or with any other mode code displayed, depress the SCROLL key until Prog is displayed. This is the mode code for the Program mode. With Prog in the top display depress the DOWN key to enter the Program mode. If the Prog code does not appear, then the mode has been disabled. Refer to Table 4-1 (page 25) for Enable mode instructions.
Upon entering the Program mode, PEn1 wil be displayed. The Program mode is broken into three parts. The parameters that are associated solely with Pen 1 will be displayed in the upper display. The parameters associated with Pen 2, will be displayed in the lower display. The parameters that are common to both pens, such as chart rotation speed, will be displayed in the upper display. Access to the Pen 1, Pen 2, or Unit (common) parameters may be quickly obtained by depressing the SCROLL key, if necessary, until the desired code, PEn1, PEn2, or unit is displayed and then depressing the DOWN key. Once into the parameters, the three parts automatically follow one another.
Page 23
4.5.3.2 MOVEMENT IN THE PROGRAM MODE
Each time the DOWN key is depressed while a parameter code is being displayed, such as inPS, another parameter code will be displayed.
Depressing the SCROLL key while a parameter code is displayed will cause the parameter value to appear. Depressing the SCROLL key with a parameter value displayed will cause the next parameter code to appear.
Depressing the UP key while a parameter code is being displayed will exit the Program mode and Prog will appear in the display. Use the DOWN key to re-enter the mode, or the SCROLL key to proceed to another mode.
4.5.3.3 ONE PEN INSTRUMENTS
For instruments specified and provided with only one pen, all configuration and operating parameters and values will appear in the upper display, which is dedicated to Pen 1 and Unit parameters. This is the only display provided. PEn2 will not appear.
4.5.3.4 TWO PEN INSTRUMENTS
Instruments specified and provided with two pens require configuration of each pen.
4.5.3.5 PROGRAM MODE CONFIGURATION
Refer to Table 4-2 (page 26) for configuration procedures for the Program mode. All possible parameters are shown for illustration purposes. Only those parameters applicable to each respective pen and the unit will actually be shown.
PAGE 23
4.5.4 ALARM SET MODE CONFIGURATION PROCEDURE
The Alarm Set mode allows the entry, review or altering of any of the alarm settings. Para­meters to be configured will be only those that are applicable as determined by the hardware provided or as assigned in the Program mode. Review the entry procedure and the configuration procedures in Table 4-3 (page 30). Use the "Your Setting" column in the table to record your programming.
4.5.4.1 ENTERING THE ALARM SET MODE
From the Operation or any other mode code, depress the SCROLL key until ASEt is dis­played. With ASEt in the top display depress the DOWN key to enter the mode. If ASEt does not appear, then the mode has been disabled. Refer to Table 4-1 (page 25) for Enable mode instructions.
4.5.4.2 MOVEMENT IN THE ALARM SET MODE
Each time the DOWN key is depressed while a parameter code is being displayed another parameter code will be displayed.
Depressing the SCROLL key while a parameter code is displayed will cause the parameter value to appear. Depressing the SCROLL key with a parameter value displayed will cause the next parameter code to come up in the display.
Depressing the UP key while a parameter code is being displayed will exit the Alarm Set mode and ASEt will appear in the display. Using the SCROLL key at this point will allow you to proceed to any other mode.
4.5.4.3 ALARM SET MODE CONFIGURATION
Refer to Table 4-3 (page 30) for configuration procedures for the Alarm Set mode. All possible parameters are shown for illustration purposes. Only those parameters applicable to each respective pen will actually be shown.
Page 24
PAGE 24
4.5.5 DATA LOGGER SETUP MODE CONFIGURATION PROCEDURE
The Data logger setup mode allows the entry, review, or altering of the datalog settings.
4.5.5.1 ENTERING THE DATA LOGGER SETUP MODE
From the Operation or any other mode code, depress the SCROLL key until dLS is displayed. With dLS in the top display, depress the DOWN key to enter the mode. If dLS does not appear, then the mode has been disabled. Refer to Table 4-1 (page 25) for Enable mode instructions.
4.5.5.2 MOVEMENT IN THE DATA LOGGER SETUP MODE
Each time the DOWN key is depressed while a parameter code is being displayed, another parameter code will be displayed.
Depressing the SCROLL key while a parameter code is displayed will cause the parameter value to appear. Depressing the SCROLL key with a parameter value displayed will cause the next parameter code to come up in the display.
Depressing the UP key while a parameter code is being displayed will exit the Data logger Setup mode and dLS will appear in the display. Using the SCROLL key at this point will allow you to proceed to any other mode.
4.5.5.3 DATA LOGGER SETUP MODE CONFIGURATION
Refer to Table 4-4 (page 30) for configuration procedures for the Datalog Setup mode.
4.5.6 PRESET ADJUST MODE CONFIGURATION PROCEDURE (TOTALIZATION OPTION ONLY)
The Preset mode allows the entry, review, and altering of the preset parameters. These parameters are used to trigger relays at selected totalization totals.
4.5.6.1 ENTERING THE PRESET ADJUST MODE
From the Operate or any other mode code, depress the SCROLL key until PSA is displayed. This is the mode code for the Preset Adjust mode. With PSA in the top display, depress the DOWN key to enter the mode. If the PSA code does not appear, then the mode has been disabled. Refer to Table 4-1 (page 25) for Enable mode instructions.
4.5.6.2 MOVEMENT IN THE PRESET ADJUST MODE
The preset values will be changeable in the Preset Adjust mode as follows: With the PSA mode code displayed, depress the DOWN key. PS1H (preset high value) will be displayed in the upper display, assuming that the Preset has been selected in the Program mode. When the SCROLL key is depressed, the value will be displayed. The UP or DOWN keys can now be used to increment or decrement the value by a factor of ten thousand (10,000) units per depression. When the SCROLL key is depressed again, PS1L (preset low value) will be displayed. The UP or DOWN keys can now be used to increment or decrement the values by single units (ignoring the decimal position). When the SCROLL key is depressed again, the next preset code will be displayed in the appropriate display. Refer to Table 4-5 (page 31).
4.5.6.3 PRESET ADJUST MODE CONFIGURATION
Refer to Table 4-5 (page 31) for configuration procedures for the Preset Adjust mode. All possible paramters are shown for illustration purposes. Only those parameters applicable to each respective pen will actually be shown. Access to either Pen 1 or Pen 2 parameters may be quickly obtained by depressing the DOWN key at either the PEn1 or PEn2 code.
Page 25
4.5.7 TOTALIZATION CONFIGURATION
Selection of the totalization funciton, how to reset the totalizer, the decimal position, the low flow cutoff point, the time base and the functions of the presets are all covered in the Program mode. Preset values are adjusted in the Preset Adjust mode.
4.5.8 RESETTING THE TOTALIZER
Resetting the Totalizer (to 0) can be accomplished from the keypad or from a remote contact closure.
Resetting the totalizer from the keypad for Pen 1 is accomplished by selecting the totalizer display and by depressing the UP key and then also depressing the DISPLAY SELECT key for 5 seconds. Resetting Pen 2 is accomplished by selecting the totalizer display and by depressing the DOWN key and then also depressing the DISPLAY SELECT key for 5 seconds.
When the totalizer for Pen 1 is reset, the combined total is also reset.
Note: Remote Resetting of the totalizer will not operate if the unit is in the Off mode.
TABLE 4-1 ENABLE MODE
Press the UP and DOWN keys while in oPEr or oFF modes. All display lamps will light. After 10 seconds, the lamps will go out and EnAb will be displayed. Release the keys and the display will change to EtSt. Press and release the DOWN key and each mode to be enabled/ disabled will be displayed. With the Enable mode prompt for the desired mode displayed, press the SCROLL key to verify that the displayed mode is either on (enabled) or oFF (disabled). Press the DOWN key to turn off the mode, press the UP key to turn on the mode or press the SCROLL key to advance the display to the next Enable mode prompt. Use the "Your Setting" column in the table to record your programming. The Test and Calibration modes are factory set to oFF (disabled).
PAGE 25
DISPLAY AVAILABLE FACTORY YOUR
STEP DESCRIPTION CODE SETTINGS SETTING SETTING
1 Enable Test Mode EtSt on or oFF 2 Enable Calibration Mode ECAL on or oFF 3 Enable Program Mode EPro on or oFF 4 Enable Alarm Set Mode EASt on or oFF 5 Enable Data Logger Setup EdLS on or oFF 6 Enable Data Logger Display EdLd on or oFF 7 Enable Preset Adjust Mode EPSA on or oFF
oFF
oFF on on
on on
on
Page 26
PAGE 26
TABLE 4-2 PROGRAM MODE CONFIGURATION PROCEDURE
Press the SCROLL key until Prog is displayed. Press the DOWN key to enter the Program mode. PEn1 will be displayed in the upper display. To enter the Pen 1 parameter, press the DOWN key. To enter the Pen 2 parameter, if provided, press the SCROLL key, then the DOWN key. To enter the unit parameter, press the SCROLL key with either PEn1 or PEn2 displayed until unit is displayed, then press the DOWN key. Press the SCROLL key to advance the display through the parameter codes and their values. Use the UP and DOWN keys to adjust the values. After adjusting a parameter, press the SCROLL key to proceed to the next parameter. After all selections have been made, press the UP key with a parameter in the display (not a setting) to exit the mode. For two pen instruments, the parameters and values which are applicable to Pen 1 will appear in the upper display, then the parameters and values which are applicable to Pen 2 will appear in the lower display, then the unit parameters and values will appear in the upper display.
DISPLAY AVAILABLE FACTORY YOUR
STEP DESCRIPTION CODE SETTINGS SETTING SETTING
1 Input Select inPS 0=4-20mA with the shunt
NOTE: Fault Detection Not Functional for 0-5V Input.
2 Input Correction iCor -1000 to 1000 units 3 Alarm 1 AL1 0=None
4 Alarm 2 AL2 Same selections as Alarm1 5 Decimal Position dPoS 0 to 3 6 Engineering Units EuPA 0=Linear 0
Processing Algorithm 1=Square Root 0 to 7 for Pen 1 of 2=Two Stage Square Root 2 pen units; 3=Three Stage Square Root 0 to 6 otherwise 4 = Variable Exponent
7 Engineering Units Euu 0 to 9999
Upper Value
8 Engineering Units EuL 0 to 9999
Lower Value (parameter applies only if EuPA=0)
9 Engineering Units EuE 0.400 to 4.000
Exponent (parameter applies only if EuPA=4 or 6)
10 Low Flow Cutoff LFC -25.0 to 25.0%
resistor in place 0=1-5V with resistor removed 1-100=variable mV span with JU4 (pen 1), JU5 (pen 2) in mV position and resistor removed (i.e., 50=0-50mV input) 100=0-5V with jumper JU4 (pen 1), JU5 (pen 2) in the volt/mA position and the resistor removed
1=Process Alarm-Direct 2=Process Alarm-Reverse
5 = Piecewise Linear Conversion 6 = Variable Exponent plus Piecewise Linear Correction 7 = Saturated Steam Flow with Pressure correction
(of Euu value)
0
0.0 0
0 1
100.0
0.0
1.500
-10.0
Note: Parameters dP2 through Pu20 only appear if EuPA = 5 or 6.
11 Decimal Position for dP2 0 to 3
12 Engineering Units Euu2 0 to 9999
Engineering Units Value 2 Upper Value 2
1
100
Page 27
DISPLAY AVAILABLE FACTORY YOUR
STEP DESCRIPTION CODE SETTINGS SETTING SETTING
PAGE 27
13 Engineering Units EuL2 0 to 9999 14 Number of piecewise nPtS 2 to 20
15 Hysteresis for Alarm HyAo 0 to 1000 units 16 Process Rounding Prnd 1 to 1000 units 17 Display Filter Factor dFF 1 to 20 units
18 Process Filter Factor PFF 1 to 20 units
19 Process Output Pout 0=Not selected 20 Process Output Pou 0 to 9999 units 21 Process Output PoL 0 to 9999 units
Lower Value 2 linear points Input Units-Point 1 iu 1
Input Units-Point 2 iu 2 Input Units-Point 3 iu 3
• Input Units-Point 20 iu20
Process Units-Point 1 Pu 1 Process Units-Point 2 Pu 2
Process Units-Point 3 Pu 3
• Process Units-Point 20 Pu20
Outputs
Upper Value Lower Value
0=No rounding (number of values averaged)
1=no filtering (number of values averaged)
1=no filtering 1=Selected
0
2
0.0
100.0
0.0
0.0
0.0
100.0
0.0
0.0
10.0
0.0 1
1
0
100.0
0.0
The output will be 0% when PV PoL and 100% when PV Pou and
will increase linearly from 0 to 100% as the Process Value goes from PoL to Pou. 22 Chart Range Cru 0 to 9999 units 23 Chart Range CrL 0 to 9999 units 24 Pen Action on PAEC 0=Pen goes to 0% span 25 Totalizer Select tSEL 0=Off
26 Totalizer Reset trES 0=Off (Non-Resettable)
27 Totalizer Decimal Position tdP 0 to 3 28 Totalizer Factor tFAC -4 to 3
29 Totalizer Low Flow Cutoff tLFC 0.0 to 25.0% (of Euu value) 30 Flow Time Base Ftb 1=units/second
Upper Value
Lower Value
Error Condition 1=Pen goes to 100% span
0 to 3 only for Pen 1 1=On
of 2 pen units; 2=Combined total
0 to 1 otherwise activated (Pen 1 plus Pen 2)
(if tSEL >0)
3=Combined total activated (Pen 1 minus Pen 2)
1=Resettable from keypad 2=Resettable by remote contact closure 3=Resettable from either
2=units/minute 3=units/hour 4=units/day
100.0
0.0 1 0
1
0 0
1.0 1
Page 28
PAGE 28
DISPLAY AVAILABLE FACTORY YOUR
STEP DESCRIPTION CODE SETTINGS SETTING SETTING
31 Preset Select 1 PSS1 0=Off
32 Preset Select 2 PSS2 Same selection as PSS1 33 Preset Select 3 PSS3 Same selection as PSS1
34 Pulsed Output Select PoS 0=Off
35 Scan Rate SCnr 3 scans/second on
36 Relay Assignment rLyA 0=Not assigned
37 Relay B Assignment rLyb Same selection as rLyA 38 Relay C Assignment rLyC Same selection as rLyA 39 Relay D Assignment rLyd Same selection as rLyA 40 Relay E Assignment rLyE Same selection as rLyA 41 Relay F Assignment rLyF Same selection as rLyA 42 Relay G Assignment rLyg Same selection as rLyA 43 Relay H Assignment rLyH Same selection as rLyA 44 Current OutputA CurA 0=Not Assigned
(if tSEL >0) 1 to 9999 (decimal point
Assignment 1=Assigned to Process
1=On when Total>Preset Value 2=On when Total<Preset Value 3=On when Combined Total > Preset Value 4=On when Combined Total < Preset Value
per tdP) 2 Pen units
5 scans/second on 1 Pen units
1=Assigned to Alarm 1­ Pen 1 2=Assigned to Alarm 2­ Pen 1 3=Assigned to Alarm 1­ Pen 2 4=Assigned to Alarm 2­ Pen 2 9=Assigned to Preset 1­ Pen 1 10=Assigned to Preset 2­ Pen 1 11=Assigned to Preset 3­ Pen 1 12=Assigned to Preset 1­ Pen 2 13=Assigned to Preset 2­ Pen 2 14=Assigned to Preset 3­ Pen 2 15=Assigned to Pulsed Output-Pen 1
16=Assigned to Pulsed Output-Pen 2
17=Assigned to Pulsed Output-Combined
Value Output-Pen1 2=Assigned to Process Value Output-Pen2 3=Assigned to Process Value Output-Combined
1
1 1
0
3 5
0
0 0 0 0 0 0 0 0
Page 29
DISPLAY AVAILABLE FACTORY YOUR
STEP DESCRIPTION CODE SETTINGS SETTING SETTING
PAGE 29
45 Current OutputB Curb Same selection as CurA
Assignment 46 Current Output C CurC Same selection as CurA
Assignment 47 Current Output D Curd Same selection as CurA
Assignment 48 Current OutputA CoAr 0=0-20mA
Range 1=4-20mA 49 Current Output B Cobr Same selection as CoAr
Range 50 Current Output C CoCr Same selection as CoAr
Range 51 Current Output D Codr Same selection as CoAr
Range 52 Chart Rotation Time Crt 0.1 to 999.9 hours per
rotation
53 Pen Action on Power Up PAPu 0=Pen(s) go to the "home"
position (towards chart center) when powered up 1=Pen(s) remain in last position prior to power down
54 Chart Operation Coo 0=Chart continues rotating
in Off mode while in the Off mode
1=Chart stops rotating while in the Off mode
0
0 0
1 1 1
1
24.0
0
1
Page 30
PAGE 30
TABLE 4-3 ALARM SET MODE CONFIGURATION PROCEDURE
Press and release the SCROLL key until ASEt is displayed, then press the DOWN key. Press the SCROLL key to advance the display through the parameters
DISPLAY AVAILABLE FACTORY YOUR
STEP DESCRIPTION CODE SETTINGS SETTING SETTING
1 Process Alarm1 PAL1 0 to 9999 units 2 Process Alarm 2 PAL2 0 to 9999 units 3 Barometric Pressure bAro 0.0 to 35.9
(EuPA = 7 only)
0.0
0.0
29.9
TABLE 4-4 DATA LOGGER SETUP MODE CONFIGURATION
Depress the SCROLL key until dLS is displayed. Use the DOWN key to enter the Data logger setup mode. Depress the SCROLL key to scroll through the parameters and their values. Use the UP and DOWN keys to adjust the values. After adjusting a parameter, depress the SCROLL key to proceed to the next parameter. After all selections have been made, depress the UP key with a parameter code in the display (not a setting) to exit the mode.
DISPLAY AVAILABLE FACTORY YOUR
STEP DESCRIPTION CODE SETTINGS SETTING SETTING
1 Day of the week dAy 1 to 7
1=Monday through 7=Sunday
2 Time of Day in tod 00.00 to 23.59
HH.MM format
1
00.00
3 Time to Log Data ttLd 00.01 to 23.59 4 Date in MM.DD dAtE 1.01 to 12.31
month and day format
5 Year yEAr 1990 to 2089
Note: Before using the Data Logger Display mode, it is suggested that a CAL8 be performed to initialize the data table.
23.59
01.01
1997
Page 31
TABLE 4-5 PRESET ADJUST MODE CONFIGURATION
Depress the SCROLL key until PSA is displayed. With PSA displayed, press the DOWN key to enter the Preset Adjust mode. PS1H will be displayed in the upper display, assuming it has been selected in the Program mode. When the SCROLL key is depressed, the value will be displayed. The UP and DOWN keys can now be used to increment or decrement the dis­played value by a factor of ten thousand (10,000) per depression (ignoring the decimal point). When the SCROLL key is depressed again, PS1L will be displayed. When the SCROLL key is depressed again, the value will be displayed again. The UP or DOWN keys can now be used to increment or decrement the value by one (ignoring the decimal point). After adjusting a parameter, depress the SCROLL key to proceed to the next parameter. After all selections have been made, depress the UP key with a parameter in the display (not a setting) to exit the mode
DISPLAY AVAILABLE FACTORY YOUR
STEP DESCRIPTION CODE SETTINGS SETTING SETTING
PAGE 31
1 Preset 1 High Value PS1H 0 to 99999999 units
Increment/Decrement
value by 10000
Preset 1 Low Value PS1L 0 to 99999999 units
Increment/Decrement
value by 1 2 Preset 2 High Value PS2H 0 to 99999999 units
Increment/Decrement
value by 10000
Preset 2 Low Value PS2L 0 to 99999999 units
Increment/Decrement
value by 1 3 Preset 3 High Value PS3H 0 to 99999999 units
Increment/Decrement
value by 10000
Preset 3 Low Value PS3L 0 to 99999999 units
Increment/Decrement
value by 1
Note: Upon a sensor error condition (SnSr), the preset outputs will remain in the state they were in upon entering the error condition.
5000
10000
15000
Page 32
PAGE 32
Data Logger Display Mode 4.6
4.6.1 DATA LOGGER DISPLAY MODE OPERATION
The Data Logger Display mode allows the user to view the parameters and values that are stored during data logging. In the Data Logger Display mode, the instrument operational functions are all active, as in the Operate mode. This provides a means of viewing the logged
data, on-line, while the unit continues normal operation.
4.6.1.1 ENTERING THE DATA LOGGER DISPLAY MODE
From the Operation or any other mode code, depress the SCROLL key until dLd is displayed. With dLd in the top display depress the DOWN key to enter the mode. If dLd does not appear, then the mode has been disabled. Refer to Table 4-1 (page 25) for Enable mode instructions.
4.6.1.2 MOVEMENT IN THE DATA LOGGER DISPLAY MODE
Each time the DOWN key is depressed while a parameter code is being displayed, another parameter code will be displayed.
Depressing the SCROLL key while a parameter code is displayed will cause the parameter value to appear. Depressing the SCROLL key with a parameter value displayed will cause the next parameter code to come up in the display.
Depressing the UP key while a parameter code is being displayed will exit the Data Logger Display mode and dLd will appear in the display. Using the SCROLL key at this point will allow you to proceed to any other mode.
Page 33
TABLE 4-6 DATA LOGGER DISPLAY MODE
Depress the SCROLL key until dLd is displayed. Use the DOWN key to enter the Data Logger Display mode. With dAy displayed, press the SCROLL key. Use the UP or DOWN key to set the value equal to the day that is to be viewed. Press the SCROLL key to scroll through the parameters and their values. After all parameters have been reviewed, depress the UP key with a parameter code in the display (not a setting) to exit the mode.
DISPLAY AVAILABLE
STEP DESCRIPTION CODE SETTINGS
1 Day of the Week dAy 1 to 28
1= Monday through 7= Sunday of this week 8=Monday through 14=Sunday of previous week etc.
2 Corresponding Date dAtE
in MM.DD format 3 Low or Minimum Flow LFLo
Rate for the 24 hour
period 4 Time of Day of Ltod
of minimum rate in
HH.MM format
PAGE 33
5 High or Maximum Flow HFLo
Rate for the 24 hour
period 6 Time of Day of maximum Htod
rate in HH.MM format 7 Average Flow Rate for AFLo
the 24 hour period 8 Total Flow for the dtot
24 hour period
Default parameters don't apply as this mode only displays data.
Page 34
PAGE 34
Service 5.1
This section contains information regarding calibration and test procedures that can be performed in the field as well as items concerning the normal maintenance of the instrument.
Changing Charts 5.2
Chart changes may be done while in the normal operating mode.
CAUTION: The chart flange assembly pin is sharp to perforate the chart. Use caution while installing the chart to avoid coming into contact with the pin.
1. Depress and hold the UP and DOWN keys for between 2 and 3 seconds. Immediately after depressing the keys, the unit will do a Lamp Test with all LED segments and indicators lighted on the upper (and lower) display.
2. After 2-3 seconds, the display will show Cchg, the pen(s) will move to and remain at a point above the top graduation on the chart and the chart will stop rotating. All other functions remain active (Operate, Display, etc).
3. Open the instrument door, snap up the chart hold down lever on the chart flange assem­bly, gently lift the pen(s) and remove old chart.
4. With the pen(s) held up, install new chart. Be sure to line up the chart time line so that the current time is aligned with the time setting mark on the chart platen.
5. Snap down chart hold down lever and close the instrument door.
6. Depress and hold the UP and DOWN keys for between 2 and 3 seconds. Immediately after depressing the keys, the unit will do a Lamp Test with all LED segments and indicators lighted on the upper (and lower) display.
7. After 2-3 seconds, the display will show Cchg momentarily, then the pen(s) position and chart rotation will be restored.
Changing Pens 5.3
Open the instrument door. Refer to Figure 5-1 for pen changing procedure. This procedure is also provided on a label on the instrument chart platen. Be sure to replace the pen cartridge with the same type (color) that was removed. Be careful not to bend the pen arm while changing the pen.
FIGURE 5-1
For replacement pens, order: Green #60500401 Red #60500402
2
1
To install pen, slide pen into holder (1) and push down (2) as shown by arrows
(Pens are sold in lots of five)
To remove pen, pull up at back end (1) and push out
1
2
Page 35
Calibration 5.4
CAUTION: Do not attempt any calibrations without the proper test equipment that meets or exceeds the specifications listed.
To enter the calibration mode it must first be turned on in the Enable mode (page 25). Once enabled, press and release the SCROLL key until CAL appears on the display, then press the DOWN key to enter the mode. The display will change to CAL1. Press the SCROLL key to advance the display to the other calibration modes available. Table 5-1 provides a listing of field calibration routines. All instruments are calibrated prior to shipment from factory.
TABLE 5-1 CALIBRATION PROCEDURES
Calibration Procedure Description
CAL1 Reinitialization of program and tuning values. CAL2 Main calibration necessary for all input types. CAL6 & 7 Factory use only.
PAGE 35
CAL8 Data Logger Re-initialization. CAL9 Pen position calibration used to calibrate pens to chart.
5.4.1 CAL 1 PARAMETER RE-INITIALIZATION
This routine is used to clear all information in the Program, Alarm Set, and Preset modes. All parameters will be reset to default values. Before performing this procedure, make sure that the Program, Alarm, and Preset values are written down so that they can be re-entered after Calibration 1 is completed. No test equipment required.
With CAL1 displayed, press and hold the DOWN key, then press the SCROLL key. The display will momentarily blank; release the keys. Upon completion of the routine, CAL1 will re-appear on the display.
5.4.2 CAL 2 MAIN CALIBRATION
This routine determines and saves calibration values which correct for component variations relating to the basic measuring function of the unit. A 100.00 mVDC ± .01 mVDC source is required for testing.
non-volt positions. See Appendix A-1 (page 46) for proper positioning. After complet­ing CAL2, be sure to re-position these jumpers to the appropriate position for your input.
With CAL2 displayed, press and hold the DOWN key, then press the SCROLL key. Release the keys when the instrument displays hLd1. Short the input terminals or apply 0.00 ± .01 mVDC to TB4 terminals 1 and 2. Press the DOWN key and dELy will appear for 10 seconds, then SCAn will appear for 10 seconds. A calibration reference number will then appear, this should be 0 ± 50. If this number falls outside these limits, press the SCROLL key and CAL2 will be displayed. Perform the calibration again. Repeat the calibration until the number falls within the tolerance limits. If the number remains outside the limits, check the connections and try the calibration again. If the number does not approach the tolerance limts, contact the nearest representative or factory for assistance. With an acceptable reference number on the display, remove the short and connect a 100.00, ± .01 mVDC source to the TB 4 terminals 1 and 2. Be sure to observe the proper polarity when connecting the source. Terminal 1 is positive and terminal 2 is negative. (Continued on next page)
Make sure that the Processor board jumpers JU4 and JU5 are in the
Page 36
PAGE 36
(Continued from page 35) Press the DOWN key, deLy will be displayed for 10 seconds and then SCAn for 10 seconds.
When the calibration is complete CAL2 will reappear. CAL2 QUICK CALIBRATION
This routine will allow the operator to execute a rough calibration on their unit via the keypad with no other equipment or disturbance to established wiring. It is intended to provide a partial recovery from a calibration corruption where the necessary equipment indicated may not be available. It should be noted that this is not intended as a substitution to the main calibration procedure described earlier and may deter considerably from the accuracy of the instrument.
With CAL2 displayed, press and hold the DOWN ARROW key, then press the SCROLL key. Release both keys and the instrument will display hLd1. Press and hold the UP ARROW key, then press the SCROLL key. The display will momentarily blank and then CAL1 will be displayed. Release both keys and depress the UP ARROW key. CAL will be displayed.
Error recovery: See section 5.6 (page 40) for details. Insure that the millivolt source is connected correctly and functioning properly.
The calibration can be exited when hLd1 or the calibration reference number is displayed by pressing the SCROLL key.
5.4.3 CAL8 DATA TABLE INITIALIZATION
This routine initializes the logged data on the recorder. With CAL8 displayed, while pressing the DOWN ARROW key, press the SCROLL key. The
display will momentarily blank while the initialization is in progress. Upon completion of the routine, CAL8 will be displayed. The routine can be executed again or another routine selected.
5.4.4 CAL 9 PEN CALIBRATION
This procedure is used to calibrate the pen(s). No special test equipment required. Valid inputs must be connected to TB 4 and TB 5 before performing this calibration. With CAL
9 displayed, push and hold the DOWN key, then press the SCROLL key . Release both keys and the display will indicate PEn1. For 2 Pen instruments, press the DOWN key to toggle the display between pen 1 and pen 2. With desired pen displayed, press the SCROLL key.
FOR INSTRUMENTS WITH SOFTWARE REVISION R2.99 AND BELOW:
dELY will be displayed as the pen selected moves toward the center chart hub. PEnL will be displayed; use the UP and/or DOWN keys to adjust the pen to the low end or 0% of the chart. When adjusted, press the SCROLL key, SCAn will appear for 10 seconds and the pen location value will be saved in memory. Next dELY will appear as the pen moves to the outer edge or, 100% mark on the chart. PEnh will appear, use the UP and/or DOWN keys to adjust the pen position to the proper 100% of chart position. Press the SCROLL key and SCAn will be displayed as the pen position value is saved. Then dELy will be displayed as the pen moves to about mid-scale. CAL9 will be displayed showing that the calibration is complete. When the calibration is complete, with CAL9 displayed, press the UP key twice to properly exit the calibration mode. CAL9 can now be repeated on the other pen of a 2 pen instrument or another routine can be selected.
Page 37
FOR INSTRUMENT WITH SOFTWARE REVISION R3.00 AND ABOVE:
P.dn will be displayed while the selected pen is moved to it's "HOME" position (toward the chart hub) with the decimal point flashing to indicate this mode. Once "Pen Home" is found, the pen will move to the inner ring and PEnL will be displayed. At this point, one of two adjustments may be made; Pen Arc or Zero and Span.
Pen Arc - To adjust the pen arc, the UP and DOWN keys are pressed simultaneously to draw an arc for visual reference. The display will show P uP while the selected pen moved upscale to the top stop position. The pen then moves back downscale to nominally place the pen at the outer ring (100%) of the chart. The display will now display ArC. The pen arm may be loosened and the length adjusted to a position and angle to place the pen tip near the outer ring then re-tighten the pen arm. Press any key and the pen will drive to "HOME", then back to the inner ring (0%) and PEnL will be displayed.
Zero and Span - To begin a pen zero, with PEnL in the display, the UP or DOWN key may be pressed to move the pen to the low end of the chart span (0%). When adjusted, press the SCROLL key and P uP is displayed while the pen is moved to the outer edge (100%) of the chart, then PEnh is displayed. To adjust pen span, use the UP and DOWN keys to adjust the pen for the high end (100%) of the chart. When adjusted, press the SCROLL key and P dn will be displayed for about 5 seconds while the pen is moved to the 50% point on the chart, then PEn1 is displayed. Calibration may now be performed again to verify the accuracy, or press the UP key twice to exit back to the CAL mode.
PAGE 37
Test Mode 5.5
To enter the Test mode, press and release the SCROLL key until tESt appears on the display then press the DOWN key. tSt1 will be displayed, press and release the SCROLL key to advance the display to the desired test. Tests 1, 2 and 3 are performed as a unit so the display will advance directly to tSt4 from tSt1. Listed below in Table 5-2 are the test proce­dures available. Test 1, 2 and 3 are performed on start up, periodically during operation, and on entry into the Test mode. Test 4 is executed on entry into and periodically during the Operation mode. These tests can be used as a trouble shooting aid.
TABLE 5-2 TEST PROCEDURES AND DESCRIPTION
Test Description Test 1 Microprocessor internal RAM test. Used to check the processor RAM to
make sure it is functioning correctly. Test 2 External RAM test, used to test the RAM chip for proper function. Test 3 EPROM checksum test, used to check that the EPROM program is correct. Test 4 External RAM checksum test; instrument test and identifies how many
times Errors 16 and 17 have occured. Test 5 Verifies that all keys are functional and all LEDs are working. Test 6 Used to verify that all relays and solid state relay driver outputs are working
correctly. Test 7 This procedure will allow operator to adjust the current output value to
check the output and to test the operation of the external device. Test 8 Pen and chart motor operational check. Test 9 Auxiliary input test, used to test remote reset.
Page 38
PAGE 38
5.5.1 TEST 1 INTERNAL RAM TEST
Tests the Random Access Memory internal to the microprocessor. No special test equipment is required.
With tSt1 displayed, press and hold the DOWN key, then press the SCROLL key. tSt1 will be displayed momentarily while the test is in progress. Upon successful completion, the instru­ment will proceed to Test 2.
5.5.2 TEST 2 EXTERNAL RAM TEST
Tests the battery backed up RAM external to the microcomputer. No special test equipment is required.
After completion of Test 1, tSt2 will be displayed momentarily while the test is in progress. Upon successful completion, the instrument will proceed to Test 3.
5.5.3 TEST 3 PROGRAM EPROM TEST
This is a checksum test to verify data integrity of the stored program. No special test equip­ment is requried.
After completion of Test 2, tSt3 will be displayed momentarily while the test is in progress. Upon successful completion of Test 3, tSt1 will be displayed.
5.5.4 TEST 4 EXTERNAL RAM CHECKSUM TEST
This is a checksum test to verify the integrity of date stored in RAM and indicate the number of times the instrument has had an Error 16 or 17. The unit may have automatically recovered from these errors. No special test equipment is required.
5.5.5 TEST 5 KEYPAD/DISPLAY TEST
This test allows the operator to verify that the keys work and that all display elements can be lighted. No special test equipment is required.
With tSt5 displayed, press and hold the DOWN key, then press the SCROLL key and then release both keys. The display will go blank. The following code will be displayed while the corresponding key is pressed:
Key Display SCROLL SCrL
UP uAro DOWN dAro UP and DOWN (All Led's and segments lit) DISPLAY SELECT diSp SCROLL and UP (exit)
To exit, press the SCROLL and UP keys simultaneously, tSt5 will be displayed.
5.5.6 TEST 6 RELAY/SOLID STATE RELAY DRIVER OUTPUT TEST
Allows the operator to verify that the Relay and/or the Solid State Relay Driver output(s) are working. A volt/ohm meter will be required to test the output.
With tSt6 displayed, press and hold the DOWN key, then press the SCROLL key. oFF will be displayed. For SPST or SPDT Relay outputs, connect the meter across the relay output in the ohm scale. For SPDT Relay outputs, connect the meter across the N.O. and COM output in the ohm scale. The meter should read continuity with the relay on and infinity when the relay is off. For SSR Driver outputs, connect the meter across the output in the Volt DC scale.
Page 39
The meter should read 5 VDC when the SSR driver is on and 0 VDC when the driver is off. Press and release the DOWN key to advance through the following sequence:
Display Relay ON SPST RELAY ON SPDT
rLYA AA rLYb BB rLYC CC rLYd DD rLYE E None rLYF F None rLYg GG rLYH HH oFF None None
To exit, press the SCROLL key and tSt6 will be displayed. The existence of Relay and Solid State Relay Driver output(s) is dependent upon the hardware configuration.
5.5.7 TEST 7 CURRENT OUTPUT TEST
This test allows the operator to verify that the current output(s) are functioning properly or will allow the selection of an output value for testing of associated equipment. A milliamp meter is required for testing.
With tSt7 displayed, press and hold the DOWN key, then press the SCROLL key. The display will indiicate CurA, for the first current output. By pressing the DOWN key, the instrument will advance through the selection sequence of Curb, CurC, Curd, and then back to CurA. Choose the desired output to be tested and connect the milliamp meter across the output terminals being tested. Be sure to observe the proper polarity when connecting the meter. Terminal 1 is positive and terminal 2 is negative. Press the SCROLL key and the display will indicate 4 milliamps.
PAGE 39
Use the UP and/or DOWN key to increase or decrease the current output in 1 mADC steps from 0 to 20mADC. The current output reading should be ± 0.5 mADC at any output value. A ± 5% of span adjustment for the current output(s) is provided by using the potentiometer adjacent to the current output on the Current Output board. See Appendix A-3 (page 51). To exit the test, press the SCROLL key and tSt7 will be displayed. The existence of a mADC current output is dependent upon the hardware configuration.
5.5.8 TEST 8 PEN/CHART MOTOR TEST
This test allows the operator to verify that pen and chart motors are functioning properly. No special test equipment is required.
With tSt8 displayed, press and hold the DOWN key, then press the SCROLL key. The display will show ALL while the test is in progress. This test functions automatically. The chart speed will be at maximum, 72 seconds per revolution. Starting at the current pen position, pen 1 will move (sweep) upscale for about 5 seconds, then downscale for about 5 seconds. Pen 2 (if provided) will sweep in the opposite direction. The pens will continue to cycle until the test is exited. To exit, press the SCROLL key. The display will show tSt8.
5.5.9 TEST 9 AUXILIARY INPUT TEST
This test allows the operator to verify that the auxilliary input(s) are functioning properly. With tSt9 displayed, press and hold the DOWN key, then press the SCROLL key. The display will show Ai1, Auxiliary Input 1. By pressing the DOWN key the instrument will alternate between Ai1 and Ai2. With the desired input selected, press the SCROLL key. The corresponding value will be displayed. To terminate a particular test, press the SCROLL key. The display will show tSt9.
Page 40
PAGE 40
Trouble-shooting and Diagnostics 5.6
This section consists of two columns. The first column is a list of some possible instrument conditions. The second column is a list of steps that should improve the condition. The steps should be performed in order until the condition improves or all the steps have been com­pleted. If the instrument condition has not improved, contact the nearest representative or the factory for assistance.
Trouble-shooting should be performed by qualified personnel using the proper equipment and following all safety precautions. Whenever possible, the trouble-shooting should be accom­plished with the electrical power disconnected. The instrument contains static sensitive components so care should be take to observe anti-static procedures.
Condition Correction Steps Display(s) is/are blank 1. Verify that the correct instrument power, as indicated
on the wiring label on the platen, is supplied to TB1 terminals 1 & 2. Check the position of the power select switch, on 230 VAC models, correctly indicates the power that is connected to the instrument. If the switch does not indicate the correct voltage, reposition as necessary. If the voltage is not correct, check the power source.
2. Turn off the instrument power. Wait about 5 seconds then turn the power on again .
3. Turn off the instrument power, open the cover, loosen the platen hold down screw, and swing the platen out of the way. Inspect the instrument for poor connections.
a. The white ribbon cables that connect the Processor board (Appendix A-1, page 46) to the platen must be properly aligned and seated in the sockets.
b. The display board(s) white ribbon cable(s) pins should be properly aligned and seated in the sockets on the platen potentiometer segment board.
c. Inspect the EPROM (U3), RAM (U8) and microprocessor chips (U5) to see that the legs are properly seated in their sockets on the Processor Board (page 46).
d. Close the platen and tighten the hold down screw. Close the cover and turn on the power to see if the display(s) will now light.
4. Turn off the instrument power. Press and hold the UP and DOWN keys. Turn on the power. Hold the keys pressed for about 10 seconds. If the display(s) light(s) the model number, Program and Alarm Set mode parameters will need to be re-entered (pages 26 & 30 or Software Ref. Sheet, page 55, if already filled out).
Page 41
Model Number Displayed 1. Turn off the instrument power, wait 5 seconds then during power up is re-apply the power. Verify that the number displayed incorrect during the power up sequence is the same as
indicated on the label affixed to the platen. If the number displayed is incorrect, perform the following steps:
a. Turn off the power to the instrument. Press and hold the UP and DOWN keys. Turn on the power and keep the keys pressed until the model number displayed resets to 78X0­ 0000-0021. Release the keys and turn off the power.
b. To enter the correct model number, press and hold the SCROLL and DOWN keys and turn on the instrument power. 78X0 should be displayed. Wait about 5 seconds and release the keys. The display should stay 78X0. Use the UP/DOWN keys as neces sary to change the displayed number to match the first 4 digits of the model number as indicated on the label on the platen. After adjusting the first 4 digits to the proper values, press the SCROLL key and the display will change to 0000. Use the UP/ DOWN keys to set the next 4 digits of the model number to the correct values. Press the SCROLL key and the display will be
0000. Use the UP/DOWN keys to set the last 4 digits of the model number. Press the SCROLL key and the power sequence will complete. The Program, Alarm Set, Preset and Datalog mode parameters will need to be re-entered (pages 26 & 30 or Software Ref. Sheet, page 55, if already filled out).
PAGE 41
Relay/SSR Driver 1. Verify that the Program, Alarm Set and Preset mode Malfunction parameters are correctly set (pages 26 & 30 or
Software Ref. Sheet, page 55, if already filled out).
2. Turn off the power to the instrument. Wait about 5 seconds and turn the power on again. Confirm that the model number displayed during the power up sequence indicates that the output(s) is/are present in the instrument. See Appendix C (page 52) for the model number explaination/decoding. This number should match the number on the label affixed to the platen.
3. Turn off the power to the instrument. Open the cover. Loosen the platen hold down screw and swing the platen open. Inspect the instrument Relay/SSR Driver board (See Figure 2-2, page 9) for the presence of the output device(s). A relay output will appear to be a cube. The SSR Driver will appear as a resistor and a jumper wire. The output will not work if the hardware is not present. Inspect that the output terminal connections are present and firmly attached. (Continued on next page)
Page 42
PAGE 42
(Continued from page 43)
4. Check the output(s) operation by performing Test 6 as described in the Test section (page 38). If the output(s) function(s) in the Test mode, re-examine the Program, Alarm Set and Preset mode parameter settings (pages 26 & 30 or Software Ref. Sheet, page 55, if already filled out).
5. If the output appears not to turn off, remove the power to the instrument. Open the cover and loosen the platen hold down screw. Swing the platen open. Clip the resistor located on the Relay Board adjacent to the output(s) that seem to stay on (See Appendix A-2A or A-2B, page 47 or 48). A .01 microfarrad, 1 KV capacitor should be connected from the terminal listed below, for the output where the resistor indicated was removed, to the AC ground.
SPST Relay A R1 TB6 Terminal 1 Relay B R2 TB6 Terminal 3 Relay C R3 TB7 Terminal 1 Relay D R4 TB7 Terminal 3 Relay E R5 TB8 Terminal 1 Relay F R6 TB8 Terminal 3
SPDT Relay A R1 TB6 Terminal 1 Relay A R2 TB6 Terminal 3 Relay B R3 TB7 Terminal 1 Relay B R4 TB7 Terminal 3 Relay C R5 TB8 Terminal 1 Relay D R6 TB8 Terminal 3
Close the platen and tighten the hold down screw. Close the cover and turn the power on to the instrument. Check the operation of the output(s).
mADC Output(s) 1. Verify that the Program mode parameters are correctly Malfunction set (page 26).
2. Turn off the power to the instrument. Wait about 5 seconds and turn the power on again. Confirm that the model number displayed during the power up sequence indicates that the output(s) is/are present in the instrument. See Appendix C (page 52) for the model number explaination/decoding. This number should match the number on the label affixed to the platen.
3. Turn off the power to the instrument. Open the cover. Loosen the platen hold down screw and swing the platen open. Inspect the instrument Current Output board (See Figure 2-2, page 9) for the presence of the output device(s). The output will not work if the hardware is not present. Inspect that the output terminal connections are present and firmly attached. Close the platen and tighten the hold down screw. Close the cover and turn on the power.
Page 43
4. Refer to the Test section and carry out the procedure for the Current Output(s) Test 7 (page 39). If the current output operates properly in the Test mode, re-check the Program mode parameters (page 26 or Software Ref. Sheet, page 55) if already filled out).
Pen(s) do not operate 1. Verify that the Program mode parameters are properly
set (page 26 or Software Ref. Sheet, page 55, if already filled out).
2. If the process value in the display exceeds the chart upper or chart lower values selected in the Program mode, the pen will appear stuck at the chart upper or lower edge respectively. Re-configure values as needed by the application (may require a new chart).
3. Perform Test 8 as described in the Test section of the manual (page 39). If the pen(s) operate(s) in Test 8, perform the pen calibration, Cal 9, as described in the Calibration section of the manual (page 36). Return the instrument to the oPEr and check the operation of the pen(s).
4. For software revision R2.99 and below, perform Test 9 as described in the Test Section of the manual (page 39). If the pen feedback voltage does not vary, check the pen Potentiometer Segment board for proper ribbon cable connection to the Processor board (Appendix A-1, page 46) and that the pen position fingers are making contact with Potentiometer Segment board.
5. For software revision R2.99 and below, inspect to see that the Potentiometer Segment of the pen feed back is clean. Use a non-residue type cleaner that does not affect the plastic to clean the segment if necessary.
6. Verify the instrument is not in Change Chart function.
PAGE 43
Error Code Displayed
SnSr - Sensor Break or 1. Inspect the sensor for proper operation and
Over Range connection to the instrument. Acceptable sensor
ranges for the instrument are listed in the Specifications section of Appendix D (page 53).
2. Verify that the Program mode input selection matches the sensor input connected (page 26 or Software Ref. Sheet, page 55, if already filled out).
3. Check that the input conditioning jumpers on the processor board (Appendix A-1, page 46) are in the proper position for the sensor input. Check that the jumpers are in the proper position for the Terminal Board where the sensor is connected.
4. Perform the calibration procedure(s), as described in the Calibration section (page 35), for the sensor input type.
Page 44
PAGE 44
Hi - Input more than 10% 1. Perform the steps listed for the SnSr Error Condition Over Span (above).
Lo - Input more than 10% 1. Perform the steps listed for the SnSr Error Condition Under Span (above).
o - display overranged 1. If this error code is displayed as a Program, Alarm (the "broken 6" Set, or Preset mode parameter, perform the CAL1 appears on the left procedure as described in the Calibration section of segment of the display) the manual (page 35).
2. If this error code appears as part of the model number during the power up sequence, follow the steps listed for the "Model Number is not correct" condition (page
41).
3. If this error appears, check the Program mode parameter dPos, if set to 1, change to 0 and see if the error clears.
Er1 - Microprocessor RAM 1. Turn off the power to the instrument. Wait 5 seconds, Failure and turn the power on.
2. Turn off the power to the instrument. Open the cover, and loosen the platen hold down screw. Swing open the platen and inspect that the microprocessor chip (U5) is properly seated in the socket located on the Processor board (Appendix A-1, page 46). Close the platen and tighten the screw. Close the cover and turn on the power.
Er2 - External RAM Failure 1. Turn off the power to the instrument. Wait 5 seconds,
and turn the power on.
Er3 - EPROM Checksum 1. Perform the steps listed for Er1 except that the Failure EPROM (U7) on the Processor board should be
inspected.
Er5 - No Zero Crossings 1. Turn off the power to the instrument. Wait 5 seconds, Detected and turn the power on.
2. Connect the instrument to another AC power source.
Er6 - AC line below 45 HZ 1. Turn off the power to the instrument. Wait 5 seconds,
and turn the power on.
2. Connect the instrument to another AC power source.
Er7 - AC line over 65 HZ 1. Turn off the power to the instrument. Wait 5 seconds,
and turn the power on.
2. Connect the instrument to another AC power source.
Page 45
Er8 - Cal2 Volt Input 1. Check that 100mVDC is properly connected to the Error instrument and is within the tolerance limts as
indicated in the CAL2 procedure of the Calibration section (page 35).
2. Turn off the power to the instrument and open the cover. Loosen the platen hold down screw and swing the platen open. Inspect the Processor board (Appendix A-1, page 46) to insure that the input conditioning jumper JU4 is in the non-volt position. The jumper must be in the non-volt position to perform the CAL2 procedure properly. Close the platen and tighten the hold down screw. Close the cover and turn on the power to the instrument.
3. Perform the CAL2 procedure as described in the Calibration section (page 35).
Er9 - ADC Reference 1. Perform the CAL2 procedure as described in the Number Error Calibration section (page 35).
PAGE 45
Er10 - ADC Reference 1. Perform the CAL2 procedure as described in the Voltage Error Calibration section (page 35).
Er12 - CAL2 Voltage Error 1. Check that 100 mVDC is properly connected to the
instrument and is within the tolerance limits as indicated in the CAL2 procedure of the Calibration section (page 35)
2. Turn off the power to the instrument and open the cover. Loosen the platen hold down screw and swing the platen open . Inspect the Processor board (Appendix A-1, page 46) to insure that the input conditioning jumper JU4 is in the non-volt position.
3. Perform the CAL2 procedure as described in the Calibration section (page 35).
Page 46
PAGE 46
M
O
Appendix A Board Layout
FIGURE A-1 - Processor Board
Top
JU1 ENABLE MODE
UNLOCKED
JU4 PEN 1 INPUT
LOCKED
JU8 RAM SIZE
JU3
EPROM SIZE
mV
VOLT/mA
64K
64K
MICR
U5
JU1
230
SWI for Rev. Y and above
SWI for Rev. X and below
RAM
EPRO
U8
JU8
TB1
230
230/115 VAC SWITCH 230 VAC MODEL ONLY
JU3
U7
Battery
JU4
JU5 PEN 2 INPUT
(REVERSE OF JU4)
mV
VOLT/mA
TB2
TB3
TB4 TB5
JU5
Page 47
FIGURE A-2A - Relay/SSR (SPST) Driver Output Board
PAGE 47
TB6
TS1
R1 TS2 R2 TS3 R3
C1 C2
K1 K2
P7
TB7
TS4
R4 TS5
C3 C4 C5 C6
K3 K4 K6
K5
R5
TB8
TS6
TB9
R6
If the relay is connected to a high impedance AC device, the snubber network used to protect the relay contact may cause the output to appear to be activated when the relay is off. To cure the problem, cut the snubber resistor for the output that is being affected.
Resistor Relay R1 Relay A
R2 Relay B R3 Relay C R4 Relay D R5 Relay E R6 Relay F
Page 48
PAGE 48
FIGURE A-2B - Relay (SPDT) Output Board
TB6
TS1
R1 TS2 R2 TS3 R3
C1 C2
P7
K1
TB7
TS4
R4 TS5
C3 C4 C5 C6
K2
TB8
R5
TS6
K3 K4
TB9
R6
If the relay is connected to a high impedance AC device, the snubber network used to protect the relay contact may cause the output to appear to be activated when the relay is off. To cure the problem, cut the snubber resistor for the output that is being affected.
Resistor Relay R1 Relay A N.O
R2 Relay A N.C. R3 Relay B N.O. R4 Relay B N.C. R5 Relay C R6 Relay D
Page 49
FIGURE A-3 - Current Output Board
PAGE 49
U2
R50 R51
U1
U3
TB10 TB11
U4
U5
U6
U7
TB12
R52
U8
U9
TB13
R53
If this option board was ordered, you will find it located in the lower right hand corner of the instrument.
Page 50
PAGE 50
Appendix B Glossary
Display Filter Factor
This parameter is adjustable from 1 to 20 which represents the number of scans of the process variable that are averaged together before updating the displayed and recorded value, and process value for retransmission. The factory default is 1=no filtering. Display code dFF.
Flow Time Base
Specifies whether the displayed process value is in units/second, units/minute, units/hour or units/day, such that the units/second. Display code Ftb.
Hysteresis
The paramter is adjustable from 0 to 1000 units representing the width of the band (half above and half below alarm setting). Factory default =10. Display code HyAo.
Input Correction
This parameter is adjustable from -1000 to 1000 units and is used as a method to compen­sate for a linear sensor error. Factory default is 0=no correction. Display code iCor.
flow rate can be converted to flow for totalization. Factory default = 1,
Platen
The flat surface in the instrument upon which the chart rotates.
Process Filter Factor
This parameter is adjustable from 1 to 20 which represents the number of scans per second of the process variable that are averaged together before updating the process value used for alarm, presets. The factory default value is 1=no filtering. Display code PFF.
Process Output
Allows retransmisstion of the process variable. Factory default is 0=not selected. Display code Pout. If selected, a current output must be assigned to it and scaled using Process Output upper and lower values.
Process Output Upper and Lower Values (used in conjunction with process output)
These parameters specify the process value range over which the assigned current output will decrease linearly from 100% to 0%. If the process value is greater than Pou the output will be 100%. If the process value is less than PoL the output will be 0%. Factory default values are 100.0 for the upper value and 0 for the lower value. Display codes Pou (upper) and PoL (lower).
Process Rounding
This parameter is adjustable from 0 to 1000 units and is used to round the process value to the nearest value specified. Intended for use where the engineering units span is large, to reduce fluctuation. Factory default is 0=no rounding. Display code Prnd (e.g.Prnd=3, Process Value=-6, -3, 0, 3, 6, 9 ...).
Page 51
Square Root Extraction Algorithms (Engineering Units Processing Algorithm)
This parameter chooses the equation for processing the input from a transmitter or transducer. EuPA = 0 - Linear is for inputs that are directly proportional to flow (no square root extraction needed). EuPA = 1 - Square Root, takes the square root of the input (pressure or differential pressure) over the whole range of the input. EuPA = 2 - Two Stage Square Root, takes the square root of the input when the input is greater than 4% of input (20% of flow) and uses a linear relationship below 4% with a slope of
5. EuPA = 3 - Three Stage Square Root, uses a linear relationship when input is less than 1% with a slope of 1, a linear relationship between 1 and 2.5% with a slope of 10 and a square root above 2.5%. EuPA = 4 - Variable Exponent, when properly set , provides a means of accurately accommo­dating weirs and flumes. EuPA = 5 - Piecewise Linear, provides the user with a means of inputing data from a non­linear sensor. EuPA = 6 - Variable Exponent with correction, provides a means to use Palmer-Bowlus or H flumes. EuPA = 7 - Saturated Steam Flow with Pressure Correction. Display code EuPA.
Totalizer Decimal Position
Specifies how the total, preset, and pulsed output values will be displayed. The factory default=0, no decimal. Display code tdP.
PAGE 51
Totalizer Factor
Specifies how the total will be scaled, and as a result, the corresponding scaling of the preset and pulsed output values. For totalizer factor = -4, -3, -2, -1, 0, 1, 2, or 3, the total will be multiplied by .0001, .001, .01, .1, 1, 10, 100, or 1000 respectively. The factory default=0. Display code tFAC.
Totalizer Low Flow Cutoff
Below the specified percent of full scale Process Value, the flow will not be added to the total. The factory default = 1.0. Display code tLFC.
Page 52
PAGE 52
Appendix C Order Matrix
7
08
0
Pen and Totalization Selection
5 1 Pen Recorder 6 1 Pen Recorder with To­talization 7 2 Pen Recorder 8 2 Pen Recorder with To­talization 9 1 Pen Recorder with Totalization and Second Display
*Relay Outputs
0 None 1 One SPST 2 Two SPST 4 Four SPST 6 Six SPST 7 One SPDT 8 Two SPDT 9 Two SPST Two SPDT
*SSR Driver Outputs
0 None 1 One 2 Two 4 Four 6 Six 8 Eight
4 to 20mA Outputs
0 None 1 One Std. 2 Two Std. 3 Three Std. 4 Four Std.
Option Suffix
Blank - None N3 - NEMA 3†
Voltage
1 115VAC Input 2 115/230VAC Input
CSA Approved 4 115VAC Input 5 115/230VAC Input
Enclosure Option
2 Standard Cover (Plastic Window) 4 Door Lock** 6 Sealed conduit Conn. 7 Combination of 4 & 6.**
Fixed Character
Fixed Character Data Logger
0 None 1 Data Logging
Transmitter Power Supply
0 None 1 24VDC Regulated/Isolated
*Total quantity of Relays and SSR Drivers must be less than or equal to (8) eight. ** This option comes with structural foam cover. † N3-NEMA3 Equivalent Spray Resistant Enclosure.
Page 53
Appendix D Specifications
Measurement Error Limit mA, mV, and VDC +/- 0.25% of scaled span plus 1 Least
Significant Digit @ 25 degrees C Ambient Temperature Error 0.01% of span per degree C deviation from 25 degrees C Scan Rate 1 to 5 scans/second (One pen units)
1 to 3 scans/second (Two pen units) Display Decimal Positions None, One, two or three decimal places Noise Rejection Normal mode, 85dB minimum at 60Hz or greater
Common mode, 90dB minimum, 115VAC maximum Line Voltage 115/230VAC +/- 10% 50/60 Hz Power Consumption 25VA maximum
PAGE 53
Operating Temperature 0 to 55° C (ambient)
32 to 131° F Storage Temperature -40 to 65° C
-40 to 149°F Humidity 0 to 90% RH, noncondensing Dimensions 13.19" H x 15.13" W x 3.63" Deep Weight 20 pounds maximum Transmitter Fault Detection Displays SnSr for sensor or transmitter break. Alarm
Outputs go off. Presets remain as they were, Pulsed outputs stop.Fault detection is not functional for 0-5V
or 0-20mA inputs. Agency Approvals UL and CSA Transmitter Power Supply Provides up to 42mA of current at 24VDC Warranty 3 years, see back page for details.
Page 54
PAGE 54
INPUTS
Milliamps Millivolts
4-20mADC 0 to 100mV
(Can be scaled to any portion of this range)
Volts
0 to 5VDC* 1 to 5VDC*
*Volt inputs are accomodated by removal of a shunt resistor
ALARM ADJUSTMENTS
Process Alarm 0 to 9999 Hysteresis 0 to 1000
PROCESS VALUE OUTPUT
Current 0 to 20 or 4 to 20 mADC
ALARM, PRESET, AND PULSED OUTPUTS
Relay SPST/SPDT
115VAC: 5.0A Resistive, 1/8HP or 250VA 230VAC: 2.5A Resistive, 1/8HP or 250VA
SSR Driver Open collector output
Short circuit protected @ 100mA maximum Provides 4VDC at 20mA or 3VDC at 40mA
DISPLAY
Digital Display Two possible; one per installed pen. Red LEDs 0.36" high Status Indicators LED indicators for Alarm 1 and Alarm 2, Process Value Displayed
(PV) and Total displayed (TOT)
RECORD
Chart 10 inch circular chart; 100 charts furnished with each instrument if
standard range Chart Range 0 to 9999 units Chart Drive DC stepper motor Chart Rotation User configurable from 0.1 to 999.9 hours per revolution Pen Type Disposable fiber tip Pen Color Pen 1 - Red
Pen 2 - Green Pen Response Time < 9 Seconds over chart span Accuracy ±1% of chart span max. error from displayed value Chart Rotation Accuracy ±.5% of chart rotation
Page 55
Appendix E Software Record/Reference Sheet
PROGRAM MODE
Pen 1 Pen 2 Pen 1 Pen 2 unit
PAGE 55
Pen 1 Pen 2
inPS iCor AL1 AL2 dPos EuPA Euu EuL EuE LFC dP2 Euu2 EuL2 nPtS iu1 iu2 iu3 iu4 iu5 iu6 iu7 iu8 iu9 iu10 iu11 iu12 iu13 iu14 iu15 iu16 iu17 iu18 iu19 iu20 Pu1 Pu2 Pu3
Pu4 Pu5 Pu6 Pu7 Pu8 Pu9 Pu10 Pi11 Pu12 Pu13 Pu14 Pu15 Pu16 Pu17 Pu18 Pu19 Pu20 HyAo Prnd dFF PFF Pout Pou PoL Cru CrL PAEC tSEL trES tdP tFAC tLFC Ftb PSS1 PSS2 PSS3 PoS
SCnr rLyA rLyb rLyC rLyd rLyE rLyF rLyg rLyH CurA Curb CurC Curd CoAr Cobr CoCr Codr Crt Coo PAPu CbS CAd1 CAd2
ENABLE MODE
EtSt ECAL EPro EASt EdLS EdLd EPSA
DATA LOGGER
SETUP MODE
dAy tod ttLd dAtE YEAr
ALARM SET
Pen 1 Pen 2
PAL1 PAL2 bAro
PRESET ADJUST
Pen 1 Pen 2
PS1H PS1L PS2H PS2L PS3H PS3L
Page 56
PAGE 56
Page 57
Warranty and Return Statement
These products are sold by The Partlow Corporation (Partlow) under the warranties set forth in the following paragraphs. Such warranties are extended only with respect to a purchase of these products, as new merchandise, directly from Partlow or from a Partlow distributor, representative or reseller, and are extended only to the first buyer thereof who purchases them other than for the purpose of resale.
Warranty
These products are warranted to be free from functional defects in materials and workman­ship at the time the products leave the Partlow factory and to conform at that time to the specifications set forth in the relevant Partlow instruction manual or manuals, sheet or sheets, for such products for a period of three years.
THERE ARE NO EXPRESSED OR IMPLIED WARRANTIES WHICH EXTEND BEYOND THE WARRANTIES HEREIN AND ABOVE SET FORTH. PARTLOW MAKES NO WAR­RANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE WITH RESPECT TO THE PRODUCTS.
Limitations
PAGE 57
Partlow shall not be liable for any incidental damages, consequential damages, special damages, or any other damages, costs or expenses excepting only the cost or expense of repair or replacement as described above.
Products must be installed and maintained in accordance with Partlow instructions. Users are responsible for the suitability of the products to their application. There is no warranty against damage resulting from corrosion, misapplication, improper specifications or other operating condition beyond our control. Claims against carriers for damage in transit must be filed by the buyer.
This warranty is void if the purchaser uses non-factory approved replacement parts and supplies or if the purchaser attempts to repair the product themselves or through a third party without Partlow authorization.
Returns
Partlow’s sole and exclusive obligation and buyer’s sole and exclusive remedy under the above warranty is limited to repairing or replacing (at Partlow’s option), free of charge, the products which are reported in writing to Partlow at its main office indicated below.
Partlow is to be advised of return requests during normal business hours and such returns are to include a statement of the observed deficiency. The buyer shall pre-pay shipping charges for products returned and Partlow or its representative shall pay for the return of the products to the buyer.
Approved returns should be sent to: PARTLOW CORPORATION
2 CAMPION ROAD NEW HARTFORD, NY 13413 USA
Loading...