Information in this installation, wiring, and operation manual is subject to change
without notice. One manual is provided with each instrument at the time of shipment. Extra copies are available at the price published on the front cover.
This is the First Edition of the MIC 1820/1420 manual. It was written and produced entirely on a desk-top-publishing system. Disk versions are available by
written request to the Partlow Publications Department.
We are glad you decided to open this manual. It is written so that you can take full
advantage of the features of your new MIC 1820/1420 process controller.
NOTE:
It is strongly recommended that Partlow equipped
applications incorporate a high or low limit protective device
which will shut down the equipment at a preset process
condition in order to preclude possible damage to property
or products.
MIC 1820/MIC 1420 ManualEdition 12
Table of Contents
Section 1 - GeneralPage
1.1 Product Description5
Section 2 - Installation & Wiring
2.1 Installation & Wiring7
2.2 Preparations for Wiring9
2.3 Input Connections16
2.4 Output Connections20
Section 3 - Configuration & Operation
3.1 Operation24
3.2 Configuration31
3.3 Pre-Tune Mode39
3.4 Auto-T une Mode39
3.5 RaPID Feature42
3.6 Manual T uning Method42
Section 4 - Control Capability
4.1 Control Capability44
4.2 Control Responses44
4.3 Direct/Reverse Operation of Control Outputs45
4.4 On-Off Control45
4.5 Time Proportioning Control46
4.6 Current Proportioning Control47
4.7 Setpoint Adjustments48
Appendices
A - Glossary of Terms49
Figure A-1 Alarm Actuation55
Figure A-2 Alarm Hysteresis57
Figure A-3 Asymmetrical Band Alarm60
Figure A-4 Proportional Band & Deadband/Overlap 62
Figure B-5 CPU PWA67
Figure B-6 PSU PWA with Relay or SSR Out.168
Figure B-7 PSU PWA with DC Output 169
Figure B-8 Option PWA70
Figure B-9 CPU PW A with Remote Input Type71
C - Hardware Definition Code72
D - Input Range Codes/Remote Setpoint Input Codes75
E - RaPID Control Feature/Alarm Hysteresis77
F - Specifications80
G - Model Number Hardware Matrix89
H - Software Reference Sheet90
This instrument is a microprocessor based single loop controller capable of
measuring, displaying and controlling temperature, pressure, flow, and level
from a variety of inputs. Most outputs are easily tuned using the instrument
Pre-Tune and Auto-Tune, or RaPID (Response assisted PID) functions.
Control functions, alarm settings and other parameters are easily entered
through the front keypad. E
data loss during AC power outages.
The input is user configurable to directly connect to either thermocouple,
RTD, mVDC, VDC or mADC inputs. The instrument can operate from either
a 90-264 VAC, 50/60 HZ power supply, or optional 24V AC/DC power supply.
1.1.2 DISPLAYS
Each instrument is provided with dual displays and status indicators as
shown in Figure 1-1. The upper display (RED) displays the value of the
process variable. The lower display (GREEN) displays the setpoint value.
Status indication is as shown, see Figure 1-1, page 6.
2
Technology (100 year life) protects against
1.1.3 CONTROL
The instrument can be programmed for on-off, time proportioning, or current proportioning control implementations depending on the model number. A second control output is an available option. Proportional control
implementations are provided with fully programmable PID parameters.
1.1.4 ALARMS
Alarm indication is standard on all instruments. Up to two alarm outputs
are possible. Alarm type may be set as Process Direct or Reverse (high or
low), Deviation Direct or Reverse (above or below setpoint), Deviation
Band Type (closed or open within band), or Loop Reverse or Direct. Alarm
status is indicated by LED. An Alarm Inhibit is provided to prevent, when
activated, unwanted alarms during power-up.
MIC 1820/MIC 1420 ManualEdition 15
FIGURE 1-1
Keys and Indicators
1.1.5 PROCESS VARIABLE/SETPOINT VALUE
RE-TRANSMISSION OUTPUT
If the instrument is specified with this option, this output may be scaled over
any desired range and re-transmitted.
MIC 1820/MIC 1420 ManualEdition 16
Installation and Wiring 2.1
Electrical code requirements and safety standards should be observed and
installation performed by qualified personnel.
The electronic components of the instrument may be removed from the
housing during installation. To remove the components, grip the side
edges of the front panel and pull the instrument forward. During re-installation, the vertically mounted circuit boards should be properly aligned in the
housing.
Ensure that the instrument is correctly orientated. A stop will operate if an
attempt is made to insert the instrument incorrectly.
Recommended panel opening sizes are illustrated in Figure 2-1. After the
opening is properly cut, insert the instrument into the panel opening. Ensure that the panel gasket is not distorted and that the instrument is positioned squarely against the panel. Slide the mounting clamp into place on
the instrument (see Figure 2-3, page 8) and push it forward until it is firmly
in contact with the rear face of the mounting panel.
Note: The mounting clamp tongues may engage either on the
sides or the top/bottom of the instrument housing. Therefore, when
installing several instruments side-by-side in one cut out, use the
ratchets on the top/bottom faces.
FIGURE 2-1
Panel Cut-Out Dimensions
92 mm +0.5 - 0.00
(3.62”+.020 - .000)
PANEL
CUTOUT
SIZE
92 mm + 0.5 - 0.0
(3.62” + .020 - .000)
45 mm +0.5 - 0.0
(1.77" +.020 - .000)
PANEL
CUTOUT
SIZE
92 mm +0.05 - 0.0
(3.62”+.020 -.000
MIC 1820/MIC 1420 ManualEdition 17
FIGURE 2-2
Main Dimensions
MIC 1420
100 mm (3.94 in.)
96 mm
(3.78 in)
Side View
MIC 1820
96 mm
(3.78 in.)
10 mm (0.39 in.)
Max. Panel thickness 6.0mm (.25 in)
100 mm (3.94 in.)
96 mm
(3.78 in)
48 mm
(1.89 in.)
MIC 1820/MIC 1420 ManualEdition 18
10 mm (0.39 in.)
Max. Panel Thickness 6.0mm (.25 in)
Side View
FIGURE 2-3
Panel Mounting the Controller
Mounting Clamp
Controller Housing
Tongues on mounting clamp engage in
ratchet slots on controller housing
Preparation for Wiring 2.2
2.2.1 WIRING GUIDELINES
Electrical noise is a phenomenon typical of industrial environments. The
following are guidelines that must be followed to minimize the effect of
noise upon any instrumentation.
2.2.1.1 INSTALLATION CONSIDERATIONS
Listed below are some of the common sources of electrical noise in the
industrial environment:
• Ignition Transformers
• Arc Welders
• Mechanical contact relay(s)
• Solenoids
Before using any instrument near the device listed, the instructions below
should be followed:
MIC 1820/MIC 1420 ManualEdition 19
1.If the instrument is to be mounted in the same panel as any of the
listed devices, separate them by the largest distance possible. For
maximum electrical noise reduction, the noise generating devices
should be mounted in a separate enclosure.
2.If possible, eliminate mechanical contact relay(s) and replace with
solid state relays. If a mechanical relay being powered by an
instrument output device cannot be replaced, a solid state relay can
be used to isolate the instrument.
3.A separate isolation transformer to feed only instrumentation should
be considered. The transformer can isolate the instrument from noise
found on the AC power input.
4.If the instrument is being installed on existing equipment, the wiring in
the area should be checked to insure that good wiring practices have
been followed.
2.2.1.2 AC POWER WIRING
Neutral (For 115 VAC)
It is good practice to assure that the AC neutral is at or near ground potential. To verify this, a voltmeter check between neutral and ground should be
done. On the AC range, the reading should not be more than 50 millivolts.
If it is greater than this amount, the secondary of this AC transformer supplying the instrument should be checked by an electrician. A proper neutral
will help ensure maximum performance from the instrument.
2.2.1.3 WIRE ISOLATION
Four voltage levels of input and output wiring may be used with the unit:
• Analog input or output (i.e. thermocouple, RTD, VDC, mVDC, or mADC)
• SPDT Relays
• SSR driver outputs
• AC power
The only wires that should run together are those of the same category. If
they need to be run parallel with any of the other lines, maintain a minimum
6 inch space between the wires. If wires must cross each other, do so at
90 degrees. This will minimize the contact with each other and reduces
“cross talk”. “Cross Talk” is due to the EMF (Electro Magnetic Flux) emitted
by a wire as current passes through it. This EMF can be picked up by
other wires running in the same bundle or conduit.
MIC 1820/MIC 1420 ManualEdition 110
In applications where a High Voltage Transformer is used (i.e. ignition systems) the secondary of the transformer should be isolated from all other
cables.
This instrument has been designed to operate in noisy environments, however, in some cases even with proper wiring it may be necessary to suppress the noise at its source.
2.2.1.4 USE OF SHIELDED CABLE
Shielded cable helps eliminate electrical noise being induced on the wires.
All analog signals should be run with shielded cable. Connection lead
length should be kept as short as possible, keeping the wires protected by
the shielding. The shield should be grounded at one end only. The preferred grounding location is the sensor, transmitter or transducer.
2.2.1.5 NOISE SUPPRESSION AT THE SOURCE
Usually when good wiring practices are followed no further noise protection
is necessary. Sometimes in severe electrical environments, the amount of
noise is so great that it has to be suppressed at the source. Many manufacturers of relays, contactors, etc. supply “surge suppressors” which
mount on the noise source.
For those devices that do not have surge suppressors supplied, RC (resistance-capacitance) networks and/or MOV (metal oxide varistors) may be
added.
Inductive Coils - MOV’s are recommended for transient suppression in
inductive coils connected in parallel and as close as possible to the coil.
See Figure 2-4. Additional protection may be provided by adding an RC
network across the MOV.
MIC 1820/MIC 1420 ManualEdition 111
FIGURE 2-4
0.5
mfd
1000V
220
Coil
ohms
115V 1/4W
230V 1W
Contacts - Arcing may occur across contacts when the contact opens and
closes. This results in electrical noise as well as damage to the contacts.
Connecting a RC network properly sized can eliminate this arc.
For circuits up to 3 amps, a combination of a 47 ohm resistor and 0.1
microfarad capacitor (1000 volts) is recommended. For circuits from 3 to 5
amps, connect 2 of these in parallel. See Figure 2-5, below.
FIGURE 2-5
MOV
R C
MIC 1820/MIC 1420 ManualEdition 112
Inductive
Coil
2.2.2 SENSOR PLACEMENT (Thermocouple or RTD)
Two wire RTD’s should be used only with lead lengths less than 10 feet.
If the temperature probe is to be subjected to corrosive or abrasive condi-
tions, it should be protected by the appropriate thermowell. The probe
should be positioned to reflect true process temperature:
In liquid media - the most agitated area
In air - the best circulated area
MIC 1820/MIC 1420 ManualEdition 113
FIGURE 2-6
U
E
E
Wiring Label
1/4 DIN
REMOTE
SETPOINT
SELECTION
REMOTE
SETPOINT
INPUT
+
-
+
-
COM
V/mA/mV
Pot
-
OUTPUT 3
Relay
11
N/OC
+
1210
13
L
N/C
SSR/DC
-
9
+
8
7
6
5
4
3
14
15
16
17
18
19
N
MAINS (LINE)
B
A
RS485
COM
N/C
-
24V 24V
AC DC
SUPPLY
.
+
-
SERIAL
COMMS
D
S
S
+
Linear (mA)
UNIVERSAL
INPUT
-
Linear (V/mV)
+
RTD
Thermocouple
2
1
2322
24
+
SSR/DC
N/O
Relay
OUTPUT 2
-
C
N/C
20
21
+
C
SSR/DC
N/O
Relay
OUTPUT 1
MIC 1820/MIC 1420 ManualEdition 114
1/8 DIN
REMOTE
SETPOINT
SELECTION
REMOTE
SETPOINT
INPUT
+
+
COM
V/mA/mV
(Wiper)
Potentiometer
OUTPUT 3
Relay
11
N/OC
+
1210
L
13
N
14
MAINS
(LINE)
15
16
17
18
B
A
COM
SUPPLY
RS485
COMMS.
24 AC
+
DUAL
SETPOINT
SELECTION
-
SUPPLY
+ l
24V DC
SUPPLY
N/C
SSR/DC
-
9
-
8
7
6
5
4
-
UNIVERSAL
INPUT
Linear
(mA)
Linear
(V/mV)
+
-
+
T/C
RTD
3
2
1
2322
24
N/O
C
Relay
+
SSR/DC
OUTPUT 2
N/C
-
19
20
21
N/C
C
N/O
-
Relay
+
SSR/DC
OUTPUT 1
MIC 1820/MIC 1420 ManualEdition 115
Input Connections 2.3
In general, all wiring connections are made to the instrument after it is
installed. Avoid Electrical Shock. AC power wiring must not be connected
to the source distribution panel until all wiring connection procedures are
completed.
Caution: This equipment is designed for installation in an enclosure
which provide adequate protection against electric shock. Local
regulations regarding electrical installation should be rigidly observed. Consideration should be given to prevention of access to the
power terminations by unauthorized authorized personnel. Power
should be connected via a two pole isolating switch (preferably situated neat the equipment) and a 1 A fuse, as shown in Figure 2-7.
FIGURE 2-7
Main Supply
The instrument will operate on 90-264V AC 50/60 Hz mains (line) supply.
The power consumption is approximately 4 VA. If the instrument has relay
outputs in which the contacts are to carry mains (line) voltage, it is recommended that the relay contact mains (line) supply should be switched and
fused in a similar manner but should be separate from the instrument
mains (line) supply .
L
13
N
14
MIC 1820/MIC 1420 ManualEdition 116
Line
Neutral
FIGURE 2-7A
24V Nominal AC/DC Supply
The supply connection for the 24V AC/DC option of the instrument are as
shown below . Power should be connected via a two pole isolating switch
and a 315 mA slow-blow (anti-surge type T) fuse. With the 24V AC/DC
supply option fitted, these terminals will accept the following supply voltage
ranges:
24V (nominal) AC 50/60Hz - 20-50V
24V (nominal) DC - 22-65V
L
13
24V AC
N
14
FIGURE 2-8
Thermocouple (T/C) Input
Make thermocouple connections as illustrated below. Connect the positive
leg of the thermocouple to terminal 2 and the negative leg to terminal 3.
50/60Hz
-
24V DC
+
-
+
Thermocouple
3
2
MIC 1820/MIC 1420 ManualEdition 117
FIGURE 2-9
RTD Input
Make RTD connections as illustrated below . For a three wire RTD, connect
the resistive leg of RTD to terminal 1 and the common legs to terminals 2
and 3. For a two wire RTD, connect one leg to terminal 2 and the other leg
to terminal 3 as shown below. A jumper wire supplied by the customer
must be installed between terminals 2 and 3. Input conditioning jumper
must be positioned correctly (see Appendix B) and Hardware Definition
Code must be correct (See Appendix C).
3
2
RTD
1
FIGURE 2-10
V olt, mV Input
Make volt and millivolt connections as shown below . Terminal 2 is positive
and terminal 3 is negative. Input conditioning jumper must be positioned
correctly (see Appendix B) and Hardware Definition Code must be correct
(see Appendix C).
mADC Input
Make mADC connections as shown below. Terminal 4 is positive and terminal 1 is negative. Input conditioning jumper must be positioned correctly
(see Appendix B) and Hardware Definition Code must be correct (see Appendix C).
+
-
+
Linear (mA)
-
Linear (V/mV)
4
3
2
1
MIC 1820/MIC 1420 ManualEdition 118
FIGURE 2-11
Remote Digital Communications - RS485
Make digital communication connections as illustrated below .
16
17
18
B
A
COM
FIGURE 2-12
Remote Setpoint Input - V/mA/mV and Potentiometer
Connections are illustrated below. Terminal 6 is positive and terminal 7 is
negative. The remote setpoint input can be configured for linear DC mv,
linear DC mA, linear DC Volt or potentiometer. Make sure that the input
selected matches the Second Input Usage selected in the Hardware Definition Mode and the Secondary Analog Input conditioning jumper is posi-
tioned correctly (see Appendix B.)
_
_
7
6
+
mA/mV
VOLT
+
5
FIGURE 2-13
Remote Setpoint Selection
Connections are made as shown.
+
DRY
CONTACT
7
6
5
Potentiometer
2 Kohms max
9
CONTACTS OPEN - LOCAL SETPOINT
8
-
CONTACTS CLOSED - REMOTE SETPOINT
MIC 1820/MIC 1420 ManualEdition 119
FIGURE 2-14
Dual Setpoint Selection
CONTACTS OPEN - SETPOINT 1
CONTACTS CLOSED - SETPOINT 2
16
17
DRY
CONTACT
Output Connections 2.4
FIGURE 2-15
Relay Output 1 (Control Output 1)
Connections are made to Output 1 relay as illustrated below. The contacts
are rated at 2 amp resistive, 120/240 V AC.
19
20
N/C
C
Relay
21
N/O
FIGURE 2-16
SSR Driver Output 1 (Control Output 1)
Connections are made to Output 1 SSR Driver as illustrated below. The
solid state relay driver is a non-isolated 0-4 VDC nominal signal. Output
impedance is 250 ohms.
19
-
20
SSR
21
+
MIC 1820/MIC 1420 ManualEdition 120
FIGURE 2-17
mADC Output 1 (Control Output 1)
Make connections for DC Output 1 as illustrated below.
C
-
DC
+
N/C
19
20
21
FIGURE 2-18
Relay Output 2 (Control Output 2
Connections are made to Output 2 relay as illustrated below. The contacts
are rated at 2 amp resistive, 120/240 V AC.
242322
OR Alarm 2)
N/O
Relay
FIGURE 2-19
SSR Driver Output 2 (Control Output 2
Connections are made to Output 2 SSR Driver as illustrated below. The
solid state relay driver is a non-isolated 0-4 VDC nominal signal. Output
impedance is 250 ohms.
242322
+
OR Alarm 2)
-
SSR
MIC 1820/MIC 1420 ManualEdition 121
FIGURE 2-20
mADC Output 2 (Control Output 2)
Make connections for DC Output 2 as illustrated below.
242322
+
DC
FIGURE 2-21
Relay Output 3 (Alarm 1)
Connections are made to Output 3 relay as illustrated below. The contacts
are rated at 2 amp resistive, 120/240 V AC.
Relay
101112
FIGURE 2-22
SSR Driver Output 3 (Alarm 1)
Connections are made to Output 3 SSR Driver as illustrated below. The
solid state relay driver is a non-isolated 0-4 VDC nominal signal. Output
impedance is 250 ohms.
-
N/OCN/C
SSR
-
101112
MIC 1820/MIC 1420 ManualEdition 122
+
FIGURE 2-23
mADC Output 3 (Recorder Output Only)
Make connections for DC output 3 as illustrated below.
DC
-
101112
+
MIC 1820/MIC 1420 ManualEdition 123
Operation 3.1
3.1.1 POWER UP PROCEDURE
Verify all electrical connections have been properly made before applying
power to the instrument.
If the instrument is being powered for the first time, it may be desirable to
disconnect the controller output connections. The instrument will be into
control following the power up sequence and the output(s) may turn ON.
During power up, a self-test procedure is initiated during which all LED
segments in the two front panel displays appear and all LED indicators are
ON. When the self-test procedure is complete, the instrument reverts to
normal operation.
Note: A delay of about 3 seconds, when power is first applied, will be
seen before the displays light up.
3.1.2 KEYPAD OPERATION
AUTO/MANUAL KEY
This key is used to:
1.Enter the Auto/Manual mode and vice versa.
2.Used to activate the Auto Tune mode.
3.Used to confirm a change in the Program mode.
SCROLL KEY
This key is used to:
1.Select adjustment of the ramping setpoint, if enabled.
2.Select a parameter to be viewed or adjusted.
3.Display enabled modes of operation.
4.Display a mode parameter value.
5.Advance display from a parameter value to the next parameter code.
6.Activate the Pre-tune mode.
7.With the DOWN key to view the current Hardware Definition Code
setting.
MIC 1820/MIC 1420 ManualEdition 124
UP KEY
This key is used to:
1.Increase the displayed parameter value.
2.Increase setpoint.
3.With the DOWN key to enter Pre and Auto Tune mode, and to engage
the RaPID function.
DOWN KEY
This key is used to:
1.Decrease the displayed parameter value.
2.Decrease setpoint.
3.With the UP key to enter the Pre and Auto Tune mode, and to engage
the RaPID function.
4.With the SCROLL key to view the current Hardware Definition Code
setting.
3.1.3 INITIAL DISPLAYS
After the instrument has performed its power up self test (during which, if
the SCROLL key is held down during power up, the current instrument
firmware revision is displayed), the initial Operator Mode displays appear.
These are dependent upon whether the instrument is configured for single
setpoint operation, dual setpoint operation or remote/local setpoint operation.
3.1.3.1 SINGLE SETPOINT OPERATION
Normally the initial displays are:
Upper Display = Process V ariable value
Lower Display = Setpoint value adjustable
The setpoint may be adjusted by using the UP/DOWN keys.
Press the SCROLL key again, if setpoint ramping is not disabled and if the
ramp rate is not switched OFF, to change the displays to:
Upper Display - Ramping Setpoint value ("Read Only")
Lower Display = the legend SPrP
MIC 1820/MIC 1420 ManualEdition 125
3.1.3.2 DUAL SETPOINT OPERATION
If dual setpoint operation has been selected, the normal Operator Mode
displays will be as follows:
Upper Display = Process V ariable value
Lower Display = Active Setpoint value (adjustable)
Press the SCROLL key to change displays to :
Upper Display = Setpoint 1 value (adjustable)
Lower Display = the legend SP1
Press the SCROLL key again to obtain the equivalent display for Setpoint 2
(with legend SP2).
NOTE: The lower display uses the left-most character to distinguish between the active and inactive setpoints in the following manner:
SP2SP2SP2
Active SetpointActive SetpointInactive Setpoint
(selected via(selected via
digital input) keypad override)
Press the SCROLL key again, if setpoint ramping is not disabled and if the
ramp rate is not switched OFF, to change the displays to:
3.1.3.3 REMOTE SETPOINT OPERATION
If remote setpoint operation has been selected the normal Operator Mode
displays will be as follows:
Upper Display = Process V ariable value
Lower Display = Active setpoint value (Adjustable)
Press the SCROLL key to change the displays to:
Upper Display = Ramping Setpoint value
Lower Display = the legend SPrP
Press the SCROLL key again to obtain the equivalent display for Remote
Setpoint (with the legend rSP).
NOTE:The lower display uses the left-most character to distinguish
between the active and inactive setpoints in the following manner:
SPSPrSP
MIC 1820/MIC 1420 ManualEdition 126
3.1.3.4 OVERRIDE FEA TURE
While the instrument is being used with either Dual Setpoint operation or
Remote Setpoint operation, the Override feature is available. This enables
the active setpoint selected by the digital input to be manually overridden
from the keypad. To engage the Override feature, with the instrument displaying the desired setpoint (legend in lower display), press the UP and
DOWN keys simultaneously. This will cause the left-most character of the
lower display to show a flashing " ". This indicates that the display setpoint
is now the active setpoint, regardless of the state of the digital input.
To cancel an override condition, simply press the UP and DOWN keys
again with this display shown.
3.1.3.5 VIEWING/ADJUSTING THE SETPOINT RAMP RATE
If setpoint ramping is enabled, the ramp rate display may be selected using
the SCROLL key. The ramp rate may be adjusted (using the UP/DOWN
keys) within the range 1 to 999. Any attempt to increase the value beyond
999 will cause the upper display to go blank and setpoint ramping to be
switched OFF (default).
3.1.3.6 ALARM STATUS DISPLA Y*
The user may view the status of the instrument's alarm(s) by depressing
the SCROLL key until the lower display shows the legend "ALSt" and the
upper display shows the alarm status in the following format:
Loop Alarm Status
L = Energized
Blank = De-energized
Alarm 1 Status
1 = Energized
Blank = De-energized
Alarm 2 Status
2 = Energized
Blank = De-energized
*This display is available only if one or more of the alarms is/are energized.
When "ALSt" is seen in the lower display, to enter the Program or Tune
modes, press the UP key with "ALSt" displayed, then the SCROLL key to
Program or T une.
MIC 1820/MIC 1420 ManualEdition 127
3.1.3.7 OVER-RANGE/UNDER-RANGE DISPLA Y
If the process variable attains a value higher than the input scale maximum
limit, the upper display will show:
If the process variable attains a value lower than the input scale minimum,
the upper display will show:
If a break is detected in the sensor circuit, the upper display will show:
3.1.4 FRONT PANEL INDICATORS
OP1 Indicates the state of the Output 1 relay or SSR driver. When the
indicator is ON the relay is energized or the SSR driver is ON.
OP2 Indicates the state of the Output 2 relay or SSR driver. When the
indicator is ON the relay is energized or the SSR driver is ON.
ALMWhen flashing, indicates an Alarm condition.
MANFlashes when the Manual mode has been entered
ATIndicates when the Pre-Tune, Auto-Tune or RaPID mode has been
selected; flashing RED for Pre-T une, continuously ON RED for Auto-Tune
or flashing GREEN for RaPID activated.
MIC 1820/MIC 1420 ManualEdition 128
3.1.5 SETPOINT ADJUSTMENT
3.1.5.1 LOCAL SETPOINT
To adjust the instrument setpoint, proceed as follows:
To adjust the Setpoint, press the UP or DOWN key as applicable.
Momentary depression will increment or decrement (as appropriate) the
setpoint by one unit in the least significant digit. If the key is held for longer
than 1 second, the least significant digit will change at the rate of 25 units
per second. If the key is held for longer than 10 seconds, the second least
significant digit will change at the rate of 25 units per second. If the key is
held for more than 10 seconds, the third least significant digit will change at
the rate of 25 units per second.
3.1.5.2 RAMPING SETPOINT
A selectable Ramp Rate function in the range of 1 to 9999 units per hour
can be used to limit the rate at which the setpoint used by the control algorithm will change. This feature will also establish a soft start up. Upon
power up, the instrument will take the initial process value as the setpoint.
A setpoint ramp rate will be calculated to increase the setpoint from the
initial process value to the setpoint selected. The setpoint ramp feature
disables the Pre-Tune facility. The Auto-Tune facility, if selected, will commence only after the setpoint has completed the ramp.
Sudden changes in the setpoint value entered via the keypad can be inhibited from effecting the control outputs by use of this feature. The internal
setpoint used to control the process will ramp to the setpoint value entered
at the rate of change selected.
To view the Ramping Setpoint value while in the Control mode and "ESPr"
in the Tune mode is disabled, press the SCROLL key until "SPrP" is displayed in the lower display. This is the code for the ramping setpoint value.
Press the SCROLL key one more time and the lower display shows "SPrP"
and the upper display will show the current ramping setpoint.
MIC 1820/MIC 1420 ManualEdition 129
Loading...
+ 65 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.