Partlow MIC 3200 Operating Manual

1/32-DIN TEMPERATURE CONTROLLER
INSTALLATION, WIRING AND OPERATION MANUAL
FORM 3882
This manual is intended for use in support of installation, commissioning and configuration of the 1/32-DIN Temperature Controller.
The procedures described in this manual should be undertaken only by personnel competent and authorized to do so.
Form 2 Edition 1
Table of ContentsTable of Contents
Table of Contents
Table of ContentsTable of Contents
PagePage
Page
PagePage
Section 1 - Installation - Panel-MountingSection 1 - Installation - Panel-Mounting
Section 1 - Installation - Panel-Mounting
Section 1 - Installation - Panel-MountingSection 1 - Installation - Panel-Mounting
1.1 Unpacking the Instrument 5
1.2 Installing the Controller in the Mounting Panel 6
Section 2 - Installation - Wiring ConnectionsSection 2 - Installation - Wiring Connections
Section 2 - Installation - Wiring Connections
Section 2 - Installation - Wiring ConnectionsSection 2 - Installation - Wiring Connections
2.1 Mains (Line) Supply 8
2.2 Low V oltage (24V AC/DC) Supply - Option 8
2.3 Thermocouple Input 9
2.4 RTD Inputs 9
2.5 DC Inputs 9
2.6 Relay Outputs (Output 2 & Output 3) 9
2.7 SSR Drive Output (Output 1) 10
2.8 RS485 Communications 10
Section 3 - Front PanelSection 3 - Front Panel
Section 3 - Front Panel
Section 3 - Front PanelSection 3 - Front Panel
3.1 Indicators 11
3.2 Keys 11
Section 4 - Instrument ConfigurationSection 4 - Instrument Configuration
Section 4 - Instrument Configuration
Section 4 - Instrument ConfigurationSection 4 - Instrument Configuration
4.1 Entry into Instrument Configuration Mode 13
4.2 Parameter Sequence 13
4.3 Exit from Instrument Configuration Mode 18
Section 5 - Operation ModeSection 5 - Operation Mode
Section 5 - Operation Mode
Section 5 - Operation ModeSection 5 - Operation Mode
5.1 Normal Operation (Yellow LED OFF) 20
Section 6 - Control Setup (Yellow LED ON)Section 6 - Control Setup (Yellow LED ON)
Section 6 - Control Setup (Yellow LED ON)
Section 6 - Control Setup (Yellow LED ON)Section 6 - Control Setup (Yellow LED ON)
6.1 Adjustment Ranges 23
6.2 Default V alues/Settings 23
Section 7 - Calibration ModeSection 7 - Calibration Mode
Section 7 - Calibration Mode
Section 7 - Calibration ModeSection 7 - Calibration Mode
7.1 Pre-Requisites 24
7.2 Entry into Calibration Mode 25
7.3 Calibration Procedure 26
7.4 Exiting Calibration Mode 27
AppendixAppendix
Appendix
AppendixAppendix
A - Product Specification 28
Figures & TablesFigures & Tables
Figures & Tables
Figures & TablesFigures & Tables
Figure 1-1 Main Dimensions 5 Figure 1-2 Panel Cut-out Dimensions 5 Figure 2-1 Rear Terminal Connections 7 Figure 2-2 Mains (Line) Supply Connections 8 Figure 2-3 Low Voltage AC/DC Supply Connections 9 Figure 2-4 RS485 Line Termination 10
Table 4-1 Sensor Selection Codes 17 Table 4-2 Output Selection Codes 17
Form 4 Edition 1
Installation - Panel-MountingInstallation - Panel-Mounting
Installation - Panel-Mounting
Installation - Panel-MountingInstallation - Panel-Mounting
1.11.1
1.1
1.11.1
1. Remove the Controller from its packing. A panel gasket and a “no tools required” fixing strap are supplied. Retain the packing for future use (e.g. moving the Controller to a different site).
2. Examine the delivered items for damage or deficiencies. If any is found, notify the carrier immediately. Check that the Product Code on the label affixed to the Controller housing corresponds to that ordered.
UNPACKING THE INSTRUMENTUNPACKING THE INSTRUMENT
UNPACKING THE INSTRUMENT
UNPACKING THE INSTRUMENTUNPACKING THE INSTRUMENT
FIGURE 1-1FIGURE 1-1
FIGURE 1-1 Main Dimensions
FIGURE 1-1FIGURE 1-1
FIGURE 1-2FIGURE 1-2
FIGURE 1-2 Panel Cut-out Dimensions
FIGURE 1-2FIGURE 1-2
1.21.2
1.2
1.21.2
INSTALLING THE CONTROLLER IN THE MOUNTING PANELINSTALLING THE CONTROLLER IN THE MOUNTING PANEL
INSTALLING THE CONTROLLER IN THE MOUNTING PANEL
INSTALLING THE CONTROLLER IN THE MOUNTING PANELINSTALLING THE CONTROLLER IN THE MOUNTING PANEL
CAUTION: Do not remove the front panel gasket from the Controller , as this may cause inadequate clamping of the Controller to the mounting panel. Ensure that this gasket is not distorted and that the Controller is positioned squarely against the mounting panel. Apply pressure to the front panel bezel only .
Controller
Form 6 Edition 1
Installation - Wiring ConnectionsInstallation - Wiring Connections
Installation - Wiring Connections
Installation - Wiring ConnectionsInstallation - Wiring Connections
FIGURE 2-1FIGURE 2-1
FIGURE 2-1 Rear Terminal Connections
FIGURE 2-1FIGURE 2-1
2.12.1
2.1
2.12.1
MAINS (LINE) SUPPLYMAINS (LINE) SUPPLY
MAINS (LINE) SUPPLY
MAINS (LINE) SUPPLYMAINS (LINE) SUPPLY
This version of the Controller will operate on a 96 - 264V AC 50/60Hz mains (line) supply. The power consumption is approximately 4W.
CAUTION: This equipment is designed for installation in an enclosure which provides adequate protection against electric shock. Local regulations regarding electrical installation should be rigidly observed. Consideration should be given to prevention of access to the power terminations by unauthorized personnel. Power should be connected via a two-pole isolating switch (preferably situated near the Controller) and a 1A fuse, as shown in Figure 2-2.
FIGURE 2-2FIGURE 2-2
FIGURE 2-2 Mains (Line) Supply Connections
FIGURE 2-2FIGURE 2-2
If the contacts of the relay output(s) are used to carry mains (line) voltage, it is recommended that the relay contacts mains (line) supply should be switched and fused in a similar manner but should be separate from the Controller mains (line) supply.
2.22.2
2.2
2.22.2
LOW VOLTAGE (24V AC/DC) SUPPLY - OPTIONLOW VOLTAGE (24V AC/DC) SUPPLY - OPTION
LOW VOLTAGE (24V AC/DC) SUPPLY - OPTION
LOW VOLTAGE (24V AC/DC) SUPPLY - OPTIONLOW VOLTAGE (24V AC/DC) SUPPLY - OPTION
This version of the Controller will operate on 12 - 24V AC 50/60Hz or 12 ­30V DC supply . The power consumption is approximately 4W. The connections are shown in Figure 2-3; these should be made via a two-pole isolating switch and a 315mA slow-blow (anti-surge Type T) fuse.
Form 8 Edition 1
FIGURE 2-3FIGURE 2-3
FIGURE 2-3 Low Voltage AC/DC Supply Connections
FIGURE 2-3FIGURE 2-3
2.32.3
2.3
2.32.3
THERMOCOUPLE INPUTTHERMOCOUPLE INPUT
THERMOCOUPLE INPUT
THERMOCOUPLE INPUTTHERMOCOUPLE INPUT
The correct type of thermocouple extension leadwire or compensating cable must be used for the full distance between the Controller and the thermo­couple, ensuring that the correct polarity is observed throughout. Joints in the cable should be avoided, if possible.
NOTE: Do not run the thermocouple cables adjacent to power-carrying conductors. If the wiring is run in a conduit, use a separate conduit for the thermocouple wiring. If the thermocouple is grounded, this must be done at one point only. If the thermocouple extension lead is shielded, the shield must be grounded at one point only.
2.42.4
2.4
2.42.4
RTD INPUTSRTD INPUTS
RTD INPUTS
RTD INPUTSRTD INPUTS
The compensating lead should be connected to Terminal 3. For two-wire RTD inputs, Terminals 2 and 3 should be linked. The extension leads should be of copper and the resistance of the wires connecting the resistance element should not exceed 5 ohms per lead (the leads should be of equal length).
2.52.5
2.5
2.52.5
DC INPUTSDC INPUTS
DC INPUTS
DC INPUTSDC INPUTS
DC (mV) inputs are connected to Terminals 2 and 3 in the polarity shown in Figure 2-1; DC (V) inputs are connected to the same terminals with the same polarity but require an external attenuator. DC (mA) inputs are con­nected to Terminals 3 and 4 in the polarity shown in Figure 2-1 with Termi­nals 2 and 4 linked externally.
2.62.6
2.6
2.62.6
RELAY OUTPUTS (OUTPUT 2 & OUTPUT 3)RELAY OUTPUTS (OUTPUT 2 & OUTPUT 3)
RELAY OUTPUTS (OUTPUT 2 & OUTPUT 3)
RELAY OUTPUTS (OUTPUT 2 & OUTPUT 3)RELAY OUTPUTS (OUTPUT 2 & OUTPUT 3)
The contacts are rated at 2A resistive at 120/240V AC.
2.72.7
2.7
2.72.7
This output produces a time-proportioned non-isolated DC signal (0 - 10V nominal, into 500 minimum).
SSR DRIVE OUTPUT (OUTPUT 1)SSR DRIVE OUTPUT (OUTPUT 1)
SSR DRIVE OUTPUT (OUTPUT 1)
SSR DRIVE OUTPUT (OUTPUT 1)SSR DRIVE OUTPUT (OUTPUT 1)
2.82.8
2.8
2.82.8
The “A” terminal (Terminal 12) on the Controller should be connected to the “A” terminal on the master device; the “B” terminal (Terminal 11) on the Controller should be connected to the “B” terminal on the master device. This instrument uses standard RS485 devices, isolated from all other inputs and outputs. The devices present a 1/4-unit load to the RS485 line. Gener­ally, termination will not be required but may be necessary for line lengths greater than 100 metres. Where termination is necessary, it is recom­mended that a 120 resistance in series with a 0.1µF capacitor be used at each end of the line (see Figure 2-4).
RS485 COMMUNICATIONSRS485 COMMUNICATIONS
RS485 COMMUNICATIONS
RS485 COMMUNICATIONSRS485 COMMUNICATIONS
Controller
FIGURE 2-4FIGURE 2-4
FIGURE 2-4 RS485 Line Termination
FIGURE 2-4FIGURE 2-4
Form 10 Edition 1
Loading...
+ 23 hidden pages