Partlow MIC 2000 Data Sheet

Data Sheet
Process Automation Worldwide Brands: LFE
TM
• Partlow
TM
• PMA
TM
• Rustrak
TM
TM
MIC 2000
Versatile with High-End Features
APPLICATIONS:
Ideal for temperature control applications requiring a value-priced, user-friendly, versatile and full featured temperature controller.
INDUSTRIES:
Industrial and lab ovens/furnaces, plastics and
thermal forming
Form/Fill and seal
Packaging applications
And any others where low costs, smaller size
and unmatched connectivity are critical requirements.
FEATURES/BENEFITS
Single, 4-digit, 0.56” LED display
1/4 DIN panel mount
Universal Input for thermocouple, RTD DC
linear V, DC linear mA/mV user-selectable
Up to 3 outputs; relay, SSR driver, 4-20mA
Process or deviation/band alarm functions
ON/OFF, position proportioning, PID Control
Optional RS-485 serial communications
Program security
DESCRIPTION
The MIC 2000 is a single loop, 1/4 DIN controller capable of controlling a variety of processes ranging from simple on/off to dual 4-20mA output with full PID. Inputs include thermocouple, RTD, millivolt, volt, and milliamp.
Standard features include: isolated process input, setpoint and output limits, and .56 inch high LEDs. It will display programming of process deviation and setpoint, of percent output, and scaling with decimal point positioning.
Optional features include: up to three relay outputs, three types of alarms, remote setpoint input, electric motor modulation, RS-485 communications and process value retransmission output as well as restricted security access. Access to configuration parameters and setpoint may be restricted by using the instrument's security-access mode.
1/4 DIN Temperature Controller
Controllers
Process Automation Worldwide Brands: LFE
TM
• Partlow
TM
• PMA
TM
• Rustrak
TM
TM
MIC 2000
Versatile with High-End Features
1/4 DIN Temperature Controller
SPECIFICATIONS*
DISPLAY
Digital Display: Four 7 segment LEDs each
.56 inches high. Status Indicators Individual LED indictors for Setpoint, Out 1, Out 2, Manual, Alarm, Degrees F, Degrees C, or Engineering Units, and minus sign for negative values.
ALARM ADJUSTMENT
Process Alarm: -9999 to 9999 units Deviation Alarm: -3000 to 3000 units Deviation Band Alarm: 1 to 3000 units
CONTROL ADJUSTMENTS
On/Off Hysteresis: 0 to 300 units Proportional Band: 1 to 3000 units Manual Reset: -1500 to 1500 units Auto Reset: 0.0 to 100.0 repeats/minute Rate: 0.0 to 10.0 minutes Cycle Time: 1 to 240 seconds Position Prop. Sensitivity: 0.0 to 50.0% First Output Position: -1000 to 1000 units Spread: -1000 to 1000 units
(Second Output Position)
STANDARD FEATURES
Full PID capability Single or dual outputs via relay, 4-20 mA
current or SSR driver Separate alarm output Universal input plus remote setpoint and
sensor break detection
ENVIRONMENTAL CHARACTERISTICS
Operating Temperature: 0 to 55°C, 32 to
131°F
Storage Temperature: -40 to 65°C, -40 to
149°F
Humidity: 0 to 90% RH, non condensing Vibration: 0.5 to 100Hz at 0.5g
ELECTRICAL
Line Voltage: 115/230VAC +/- 10% 50/60 Hz Power Consumption: 15VA maximum Transmitter Power Supply: Provides up to
40mA @ 24 VDC.
INPUTS
Thermocouple types: J, K, T, R, S, E, B, N,
and C.
RTD: 100 ohm platinum (.00385
Ohm/Ohm/C)
Volts: 0 to 5VDC, 1 to 5 VDC Millivolts: 0 to 25mVDC, 0 to 50mVDC, 10
to 50mVDC
Milliamps: 0 to 20 or 4 to 20mADC,
accommodated via the addition of a shunt resistor
Remote Setpoint: 0 to 5VDC, 1 to 5 VDC Sensor Fault Detection: Displays Hi or Lo
for thermocouple or RTD inputs (10% above or below range) and sensor break, SnSr. On/Off outputs go off, proportional outputs go to 0%. Sensor fault detection is not functional for 0 to 5VDC or 0 to 20mADC.
OUTPUTS
Relay: SPST
115VAC: 5.0 A Resistive; 1/8HP or 250VA 230VAC: 2.5 A Resistive; 1/8HP or 250VA
SSR Driver: Open collector output Short
circuit protected at 100mA maximum Provides 4VDC at 20mA or 3VDC at 40mA
Current Output: 0-20 or 4-20 mADC into 650
ohms maximum
PERFORMANCE
Measurement Error Limit:
Type J, K, T, E, N, C thermocouples and RTD +/- 0.25% of reading plus 1 degree at 25°C
Type R, S, B thermocouple +/- 0.25% of span at 25°C
mVDC, mADC and VDC +/- 0.25% of span, plus 1 least-significent-digit at 25°C
Ambient Temperature Error: 0.01% of span per
degree C deviation from 25°C
Scan Rate: 1 scan per second (3 scans per
second available on EA option)
Display Resolution: T/C & RTD: 0.1 or 1 degree
mV & VDC: 0.001, 0.01, 0.1, or 1.0
Auto Reset Windup Inhibit: Auto reset is
disabled when the process is outside of the proportional band
Cold Junction Compensation: Self compensation
for ambient temperature. All calibration values are stored in memory.
Noise Rejection: Normal mode, 85dB minimum
@ 60Hz or greater. Common mode, 90dB minimum ±8 VDC maximum peak for RTD input, 115VAC maximum for other inputs.
PHYSICAL DIMENSIONS
Dimensions: 1/4 DIN front panel, 5.8" deep Weight: 3 pounds maximum
COMMUNICATIONS
Type: RS-485 serial communication port Protocol: Partlow ASCII
RATINGS/AGENCY APPROVALS
UL & cUL recognized (E67237), CSA (LR39885)
WARRANTY
3 years Made in USA
* Specifications are for base models with standard features
only unless otherwise noted. Specifications subject to change without notice in accordance with our DBS policy of continuous improvement. All product and brand names are trademarks of their respective owners. All rights reserved.
Partlow™ brand and MIC 2000™ are trademarks of Danaher Industrial Controls Group. All rights reserved.
© 2005 DICG Corp. Partlow Brand MIC 2000 Data Sheet (7/05)