MIC 1167, 1807, 1407
1/16, 1/8 and 1/4 DIN VMD CONTROLLERS
1 7 1 1
ORDERING
16 1/16 DIN
40 1/4 DIN
80 1/8 DIN
1 Relay
1 Relay
0 None
1 Relay
2 SSR Driver
3 4-20mA* Driver
4 Transmitter Power Supply**
0 None
1 RS-485 Communications
2 Dual Setpoint
(Blank) None
02 Line Voltage 24 V AC/DC
* For alarm output only.
** Not available for MIC 1167
MODEL
FIXED CHARACTER
OUTPUT 1
OUTPUT 2
OUTPUT 3
OPTIONS
SUFFIX
WARRANTY
This instrument is backed by
the Partlow comprehensive 2
year warranty. A complete
warranty statement is
published in the back of the
product instruction manual.
If you have further questions
about warranties, please
contact the Partlow factory.
10
ORDERING INFORMATION
For pricing and additional
ordering information, refer to
Form 3265, Electronic Price
Book, Page 11.
DESCRIPTION
Partlow's new MIC 1167, MIC 1807 and MIC 1407 Series of microbased, 1/16 DIN, 1/8 DIN and 1/4 DIN VMD process
controllers have been designed specifically to drive valve motors, with a unique VMD tuning algorithm. The series consists of
controllers with continuous on-line open loop tuning which gives stable control at all times. With pre-tune and auto-tune, the
user set up is also much easier in what is generally considered to be a complex measurement area.
In addition to tuning the P and I terms, the auto-tune also reduces valve activity to an absolute minimum without compromising
the control quality, thereby reducing wear and tear on mechanical components such as valves, contactors and relays.
This VMD series incorporates the latest in surface-mount and CMOS technology to ensure reliable and accurate control in a
wide variety of applications.
SPECIFICATIONS
CONTROLLERS
Input
Thermocouple types J, K, T, R, S, B, L and N
RTD 100 ohm (.00385 ohm/ohm/C)
Volts 0 to 5VDC, 1 to 5VDC, 0 to 10VDC and
2 to 10 VDC
Millivolts 0 to 50mVDC and 10 to 50mVDC
Milliamps 0 to 20mADC and 4 to 20mADC
Sensor Fault Detection Displays or for thermocouple
or RTD inputs and sensor break, SnSr.
"Close Valve" input set to ON; alarms
operate as if the process variable has
gone over-range (TC & RTD) and
under-range (V, mV, mA)
Dual Setpoint
Selection Type Voltage free or TTL compatible
Outputs
Outputs 1 & 2
Relay Only SPDT (Output 1 - Open Valve,
Output 2 - Close Valve)
2A @ 120V AC (Motor Drive)
2A @ 240V AC (resistive or independent
contactor drive)
Output 3 Relay SPDT
2A resistive @ 120/240V AC
SSR Driver > 4.2V DC into 1 K ohm minimum
Current Output 0 to 20mADC into 500 ohms max.
(retransmission only) 4 to 20mADC into 500 ohm max.
Volts DC Output 0 to 10VDC 500 ohm minimum
(retransmission only) 0 to 5VDC 500 ohm minimum
Transmitter Power 20 to 28VDC (24VDC nominal)
Supply (not available 910 ohm (22mA @ 20VDC)
on 1167)
Display
Digital Display Four 7 segment LEDs
1/16 DIN: Top: .39", Bottom: .28"
1/8 DIN: Top: .39", Bottom: .28"
1/4 DIN: Top: .53",Bottom: .39"
Alarm Adjustment
Process Alarm – Input Span
Deviation Alarm – Input Span
Deviation Band Alarm 0 to Input Span
Control Adjustment
Proportional Band 0.5% to 999.9% of Input Span
Auto Reset 1 sec to 99 min 59 sec/repeat
Rate 0 sec to 99 min 59 sec
Motor Travel Time 5 sec to 5 min
Performance
Measurement Accuracy – 0.25% of span, – 1 LSD at 20 deg C
Note: Reduced performance with
Type "B" thermocouple between
100-600C (212-1112F)
Ambient Temperature Error 0.01% of span /deg C change in
ambient
Linearization Accuracy Better than – 0.2 deg C any point,
(TC and RTD) any 0.1 deg C range (– 0.05 deg C
typical). Better than – 0.5 deg C any
point, any 1 deg C range
Cold Junction Compensation Better than – 0.7 deg C
Noise Rejection Common mode: >120dB at 50/60Hz
giving negligible effect at up to 264V
50/60Hz
Series Mode: >500% of span (at 50/60
Hz) causes negligible effect
Line Voltage 90 to 264VAC 50/60 Hz (standard)
20 to 50V AC 50/60Hz or
22 to 65V DC (optional)
Operating Temperature 0 to 55 C
Storage Temperature -20 to 80 C
Humidity 20 to 95% non condensing
Source Resistance 1000 ohm maximum (thermocouple)
Lead Resistance 50 ohm per lead maximum balanced
(Pt100)
EMI Susceptibility Designed to meet EN50082 Part 2
EMI Emissions Designed to meet EN50081 Part 2
Dimensions 1/16 DIN:
Front Panel: 48mm x 48mm
(1.89" x 1.89") 110mm deep (4.33")
1/8 DIN:
Front Panel: 48mm x 96mm
(1.89" x 3.78") 100mm deep (3.94")
1/4 DIN:
Front Panel: 96mm x 96mm
(3.78" x 3.78") 100mm deep (3.94")
Weight 1/16 DIN & 1/8 DIN: 8 ounces max.
1/4 DIN: 16 ounces max.
Front Panel Sealing IP66/NEMA4 (1407 only)
Power Consumption 4 Watts
Agency Approvals
UL Recognized (pending)
cUL Certified for use in Canada (pending)
Digital Communications
Type RS-485 serial communication port:
Protocol Modbus RTU
Bit Rate User configurable to 1200, 2400,
4800, 9600
Address User configurable 1 to 32
11