Partlow MIC 1801 Data sheet

MIC 1801
MICROBASED 1/8 DIN LIMIT CONTROLLER
1 8 0 1

ORDERING

1 Relay
0 None 1 Relay* 4 Transmitter Power Supply
0 None 1 Relay* 3 4-20mA** 4 Transmitter Power Supply
0 None 1 RS-485 Communications 2 Remote Reset
(Blank) None 02 Line Voltage 24 V AC/DC
* For alarm output only. ** For retransmission only.
+
Cannot be used if output 3=4.
++
Cannot be used if output 2=4.
OUTPUT 1
OUTPUT 2
OUTPUT 3
OPTIONS
SUFFIX
+
++
WARRANTY
This instrument is backed by the Partlow comprehensive 2 year warranty. A complete warranty statement is published in the back of the product instruction manual. If you have further questions about warranties, please contact the Partlow factory.
20
ORDERING INFORMATION
For pricing and additional ordering information, refer to Form 3265, Electronic Price
Book, Page 21.

DESCRIPTION

The MIC 1801 is a new line of limit controllers designed to provide a programmable safety cut out and optional alarm for use in a wide variety of applications.
Packaged in 1/8 DIN, the MIC 1801 provides a latched relay output which is activated when process parameters either exceed or fall below the desired value, providing a fail safe shutoff which has to be manually reset before the process can continue.
The instrument can be configured to be either a high limit unit where the relay will de-energize when the PV is above the limit point setpoint, or a low limit where the relay will drop out when the PV falls below the setpoint.
LED indication shows when limits have been exceeded and when the relay is latched out. It offers a full range of universal sensor input options, versatile configuration and a front panel sealed to NEMA4 type/IP65. The MIC 1801 provides a valuable safety control element in most applications and systems.

SPECIFICATIONS

Input
Thermocouple types J, K, T, R, S, B, L and N. RTD 100 ohm (.00385 ohm/ohm/C) Volts 0 to 5VDC, 1 to 5VDC, 0 to 10VDC and
2 to 10 VDC Millivolts 0 to 50mVDC and 10 to 50mVDC Milliamps 0 to 20mADC and 4 to 20mADC Sensor Fault Detection Displays or for thermocouple
or RTD inputs and sensor break, SnSr.
Control outputs set to OFF (0% power);
alarms operate as if the process variable
has gone over-range (TC) and under-range
(RTD & V, mV, mA) Remote Reset Voltage free contact, closure required to
reset
Limit Output
Relay SPDT
5.0 A Resistive at 120/240 VAC
Alarm Output
Relay 2.0A Resistive at 120/240 VAC
Retransmit Output
0-20mADC into 500 ohm maximum
4-20mADC into 500 ohm maximum
0-10VDC 500 ohm minimum
0-5VDC 500 ohm minimum Resolution >10 bits in >1000ms typical
Display
Digital Display Four 7 segment LEDs, top .36" high,
bottom .28" high Status Indicators Individual LED indictors for OUT, Exceed,
ALM, and when in Setup
Maximum/Minmum Hold
Feature that tracks and saves the maximum (high limit) or minimum (low limit) excursions of the process variable
Time Exceed
Feature that measures the amount of time that the limit is exceeded
Alarms
Maximum Number Two "soft" alarms Maximum # Outputs Up to 2 outputs can be used for alarm
purposes Comb. of Alarms Logical ORing and ANDing of alarms to an
individual hardware output is available
Alarm Adjustment
Process Alarm – Input Span
Performance
Measurement Accuracy – 0.25% of span, – 1 LSD at 20 deg C
Note: Reduced performance with Type "B" thermocouple between 100-600C (212-1112F)
Ambient Temperature Error 0.01% of span /deg C change in
ambient Linearization Accuracy Better than – 0.2 deg C any point, (TC and RTD) any 0.1 deg C range (– 0.05 deg C
typical). Better than – 0.5 deg C any
point, any 1 deg C range Cold Junction Compensation Better than – 0.7 deg C Scan Rate 4 per second Noise Rejection Common mode: >120dB at 50/60Hz
giving negligible effect at up to 264V
50/60Hz
Series Mode: >500% of span (at 50/60
Hz) causes negligible effect Line Voltage 90 to 264VAC 50/60 Hz Operating Temperature 0 to 55 C Storage Temperature -20 to 80 C Humidity 20 to 95% non condensing Source Resistance 1000 ohm maximum (thermocouple) Lead Resistance 50 ohm per lead maximum balanced
(Pt100) Dimensions 1/8 DIN front panel, 4.33" deep Weight 8 ounces maximum Front Panel Sealing IP65/NEMA4 Power Consumption 4 Watts
Agency Approvals
FM File 120694.MMO
Digital Communications
Type RS-485 serial communication port: Character Format ASCII Bit Rate User configurable to 1200, 2400,
4800, 9600 Address User configurable 1 to 32
CONTROLLERS