Partlow MIC 1462 Operating Manual

MIC 1462
1/4 DIN SETPOINT PROGRAMMER
OPERATORS MANUAL
FORM 3806 EDITION 1 © Jan.1998 PRICE $10.00
Brand
Information in this installation, wiring, and operation manual is subject to change without notice. One manual is provided with each instrument at the time of ship­ment. Extra copies are available at the price published on the front cover.
Copyright © January 1998, The Partlow-West Company, all rights reserved. No part of this publication may be reproduced, transmitted, transcribed or stored in a retrieval system, or translated into any language in any form by any means without the written permission of the Partlow-West Company.
This is the First Edition of the MIC 1462 manual. It was written and produced entirely on a desk-top-publishing system. Disk versions are available by written request to the Partlow-West Company Publications Department.
We are glad you decided to open this manual. It is written so that you can take full advantage of the features of your new MIC 1462 setpoint programmer.
NOTE: It is strongly recommended that Partlow Brand equipped applications incorporate a high or low limit protective de­vice which will shut down the equipment at a preset process condition in order to preclude possible damage to property or products.
Table of Contents
Section 1 - General Page
1.1 Product Description 1
Section 2 - Installation & Wiring
2.1 Unpacking Procedure 3
2.2 Panel Mounting 3
2.3 Preparation for Wiring 5
2.4 Input Connections 12
2.5 Output Connections 15
Section 3 - Operation
3.1 Power-up Procedure 23
3.2 Keypad Operation 23
3.3 Indicators 25
3.4 Displays 26
3.5 Alarm Status Indication 26
3.6 Viewing Operating Modes 27
3.7 Adjusting the Setpoint 27
3.8 Viewing Input Values 28
3.9 Base Mode/Off Mode Outputs 29
3.10 Viewing the Time and Day 29
3.11 Manual Control 29
3.12 Using the Pre-Tune Facility 30
3.13 Using the Self-Tune Facility 31
Section 4 - Configuration
4.1 Entry into Configuration 32
4.2 Hardware Definition Mode 33
4.3 Configuration Mode Parameters 36
4.4 Exit from Configuration Mode 41
Section 5 - Tune Mode
5.1 Tune Parameters 43
5.2 Exiting Tune Mode 48
Section 6 - Alarm Mode
6.1 Alarm Parameters 49
6.2 Alarm Inhibit 53
6.3 Loop Alarm and Loop Alarm Time 53
i MIC 1462 ManualEdition 1
Section 7 - Profile Define Mode
7.1 Entry into Profile Define 58
7.2 Parameters Common to All Profiles 59
7.3 Parameters which apply to a Specific Profile 62
7.4 Parameters in any/each Segment 66
7.5 Using Join, Repeat, and End Segments 69
7.6 Basic Rules to Remember 71
7.7 Exiting Program Define Mode 71
Section 8 - Programs
8.1 Selecting and Running a Program 72
8.2 Changing Timebase 72
8.3 Holding Manually 72
8.4 Jumping to Next Segment 73
8.5 Viewing Program Status 73
8.6 Aborting a Program 74
8.7 End of Progam Indication 74
8.8 Accessing Modes of the Controller 75
Section 9 - Test Mode 76
Section 10- Calibration Mode
10.1 Calibration Procedure 77
10.2 Exit From Calibration 80
10.3 Calibration Check 80
Appendices
A - Input Range Codes 81 B - Board Layout - Jumper positioning 83
Figure B-1 PCB Positions 83 Figure B-2 Output 2/Output 3 Removal 84 Figure B-3 CPU PWA 85 Figure B-4 PSU PWA with Relay or SSR Out.1 86 Figure B-5 PSU PWA with DC Output 1 87
Figure B-6 Option PWA DC Output 2/Output 3 88 C - Specifications 89 D - Model Number Hardware Matrix 98 E - Software Reference Sheet 99
MIC 1462 Manual
ii
Edition 1
Figures
Figure 1-1 Front Panel 2 Figure 2-1 Panel Cut-Out Dimensions 3 Figure 2-2 Main Dimensions 4 Figure 2-3 Panel Mounting the controller 5 Figure 2-4 Noise Suppression 8 Figure 2-5 Noise Suppression 8 Figure 2-6 Rear Terminal Connections 10 Figure 2-6A Rear Terminal Connections 11 Figure 2-7 Main Supply 12 Figure 2-7A 24V Nominal AC/DC Supply 13 Figure 2-8 Thermocouple (T/C) Input 13 Figure 2-9 RTD Input 13 Figure 2-10 Volt, mV Input 14 Figure 2-11 mA DC Input 14 Figure 2-12 Remote Digital Communications 15 Figure 2-13 Relay Output 1 15 Figure 2-14 SSR Driver Output 1 15 Figure 2-15 mADC Output 1 16 Figure 2-16 Relay Output 2 16 Figure 2-17 SSR Driver Output 2 16 Figure 2-18 mADC Output 2 17 Figure 2-19 Transmitter Power Supply Out 2 17 Figure 2-20 Relay Output 3 17 Figure 2-21 SSR Driver Output 3 18 Figure 2-22 mADC Output 3 18 Figure 2-23 Transmitter Power Supply Out 3 18 Figure 2-24 End of Program Output 19 Figure 2-25 Event Outputs 19 Figure 2-26 Remote Program Output 20 Figure 2-27 Valve Motor Drive 21 Figure 2-28 VMD with Interlock 22 Figure 5-1 Proportional Band and Deadband/Overlap 47 Figure 6-1 Alarm Operation 55 Figure 6-2 Alarm Hysteresis Operation 57 Figure 7-1 Auto Hold Operation 65 Figure 10-1 Jumper Positions Calibration 79 Figure 10-2 Connections for Calibration 80
iii MIC 1462 ManualEdition 1
MIC 1462 Manual
iv
Edition 1
Section 1 - General
1.1 PRODUCT DESCRIPTION
This instrument is a powerful, easy-to-use 1/4 DIN setpoint programmer with full PID control capability (complete with Self-Tune and Pre-Tune facili­ties).
Its standard features include:
• Up to eight programs of up to 16 free-format (e.i. dwell, ramp, join, or end) segments each.
• Facility to join programs to one another in any sequence (maximum program length 121 segments)
• User can change currently-running program segment.
• Delayed Start of Program facility
• End of Program relay output
• Universal input-thermocouple, RTD (PT100) or DC linear ­ user-selectable.
• Universal power supply (90 -264V AC 50/60 Hz)
• Configurable from front panel
• Comprehensive front panel displays
• Front panel sealing to NEMA 4 standard
• Behind-panel depth only 100mm (3.94 inches)
• Power Failure Recovery
Optional features include:
• Remote control and selection of program (plug-in option)
• Up to four Event relay outputs (plug-in option)
• Second control output
• Recorder output (setpoint or process variable)
• RS-485 serial communications
• User-definable program tag names
• Support software (Off-line Configurator, On-line Graphic Program Editor) - operates via RS-485 communications link.
• Real Time Clock
1 MIC 1462 ManualEdition 1
The Setpoint Programmer has numerous operating modes:
Base Mode: Day to day PID control operations with no program running. In this mode, a program may be selected to run.
Profile Run Mode: A selected program is running, held or waiting for a pre-defined delay before starting. In this mode, the operator can view status and program information.
Profile Define Mode: Used to view/create/edit programs. this mode is entered either from Base Mode (selected program may be edited/cre­ated) or from Program Run Mode (currently-running program may be edited).
Controller Define Mode: Used to define the controller characteristics.
Tune: Used to adjust tuning parameters
Alarm: Used to define and set alarms
Enable: Provides a means of enabling or disabling access to setpoint changes and each of the non-control modes.
FIGURE 1-1
Front Panel
2
MIC 1462 Manual
2
Edition 1
Section 2 - Installation & Wiring
2.1 UNPACKING PROCEDURE
1. Remove the instrument from its packing. The instrument is supplied with a panel gasket and push-fit strap. Retain the packing for future use, should it be necessary to transport the instrument to a different site or return it to the factory for repair/testing.
2. Examine the delivered items for damage or deficiencies. If any is found, notify the carrier immediately. Check that the model number shown on the label affixed to the instrument housing corresponds to that ordered (see Appendix D).
2.2 PANEL-MOUNTING THE SETPOINT PROGRAMMER
The panel on which the instrument is to be mounted must be rigid and may be up to 6.0 mm (.25 inches ) thick. The cutout required for a single instru­ment is shown in Figure 2-1.
FIGURE 2-1
Cut-Out Dimensions
92 mm +0.5 - 0.00
(3.62”+.020 - .000)
PANEL CUTOUT SIZE
92 mm + 0.5 - 0.0
(3.62” + .020 - .000)
3 MIC 1462 ManualEdition 1
The main dimensions of the instrument are shown below.
FIGURE 2-2
Main Dimensions
100 mm (3.94 in.)
96 mm (3.78 in)
Side View
96 mm (3.78 in.)
Max. Panel Thickness 6.0mm (.25 inches)
10 mm (0.39 in.)
To panel-mount the instrument:
1. Insert the rear of the instrument housing through the cutout (from the front of the mounting panel) and hold the instrument lightly in position against the panel. Ensure that the panel gasket is not distorted and that the instrument is positioned squarely against the mounting panel. Apply pressure to the front panel bezel only.
Caution: Do not remove the panel gasket, as this may result in inadequate clamping of the instrument in the panel.
2. Slide the fixing strap in place (Figure 2-3) and push it forward until it is firmly in contact with the rear face of the mounting panel (the tongues on the strap should have engaged in matching rachet positions on the instrument housing and the fixing strap springs should be pushing firmly against the mounting panel rear face).
MIC 1462 Manual
4
Edition 1
Once the instrument is installed in its mounting panel, it may be subse­quently removed from its housing, if necessary, as described in Appendix B.
FIGURE 2-3
Panel-Mounting the Instrument
Mounting Clamp
Controller Housing
Tongues on mounting clamp engage in ratchet slots on controller housing
2.3 PREPARATION FOR WIRING
Electrical noise is a phenomenon typical of industrial environments. The following are guidelines that must be followed to minimize the effect of noise upon any instrumentation.
2.3.1 INSTALLATION CONSIDERATIONS
Listed below are some of the common sources of electrical noise in the industrial environment:
• Ignition Transformers
• Arc Welders
• Mechanical contact relay(s)
• Solenoids
5 MIC 1462 ManualEdition 1
Before using any instrument near the device listed, the instructions below should be followed:
1. If the instrument is to be mounted in the same panel as any of the listed devices, separate them by the largest distance possible. For maximum electrical noise reduction, the noise generating devices should be mounted in a separate enclosure.
2. If possible, eliminate mechanical contact relay(s) and replace with solid state relays. If a mechanical relay being powered by an instrument output device cannot be replaced, a solid state relay can be used to isolate the instrument.
3. A separate isolation transformer to feed only instrumentation should be considered. The transformer can isolate the instrument from noise found on the AC power input.
4. If the instrument is being installed on existing equipment, the wiring in the area should be checked to insure that good wiring practices have been followed.
2.3.2 AC POWER WIRING
Neutral (For 115 VAC) It is good practice to assure that the AC neutral is at or near ground poten­tial. To verify this, a voltmeter check between neutral and ground should be done. On the AC range, the reading should not be more than 50 millivolts. If it is greater than this amount, the secondary of this AC transformer sup­plying the instrument should be checked by an electrician. A proper neutral will help ensure maximum performance from the instrument.
2.3.3 WIRE ISOLATION
Four voltage levels of input and output wiring may be used with the unit:
• Analog input or output (i.e. thermocouple, RTD, VDC, mVDC, or mADC)
• SPDT Relays
• SSR driver outputs
• AC power
MIC 1462 Manual
6
Edition 1
The only wires that should run together are those of the same category. If they need to be run parallel with any of the other lines, maintain a minimum 6 inch space between wires. If wires must cross each other, do so at 90 degrees. This will minimize the contact with each other and reduces "cross talk". "Cross Talk" is due to the EMF (Electro Magnetic Flux) emitted by a wire as current passes through it. This EMF can be picked up by other wires running in the same bundle or conduit.
In applications where a High Voltage Transformer is used (i.e. ignition sys­tems) the secondary of the transformer should be isolated from all other cables.
This instrument has been designed to operate in noisy environments, how­ever, in some cases even with proper wiring it may be necessary to sup­press the noise at the source.
2.3.4 USE OF SHIELDED CABLE
Shielded cable helps eliminate electrical noise being induced on the wires. All analog signals should be run with shielded cable. Connection lead length should be kept as short as possible, keeping the wires protected by the shielding. The shield should be grounded at one end only. The pre­ferred grounding location is the sensor, transmitter, or transducer.
2.3.5 NOISE SUPPRESSION AT THE SOURCE
Usually when good wiring practices are followed no further noise protection is necessary. Sometimes in severe electrical environments, the amount of noise is so great that it has to be suppressed at the source. Many manu­facturers of relays, contactors, etc. supply "surge suppressors" which mount on the noise source.
For those devices that do not have surge suppressors supplied. RC (resis­tance-capacitance) networks and/or MOV (metal oxide varistors) may be added.
Inductive Coils - MOV's are recommended for transient suppression in inductive coils connected in parallel and as close as possible to the coil. See Figure 2-4. Additional protection may be provided by adding an RC network across the MOV.
7 MIC 1462 ManualEdition 1
FIGURE 2-4
0.5 mfd 1000V
115V 1/4W 230V 1W
220 ohms
Inductive Coil
Contacts - Arcing may occur across contacts when the contact opens and closes. This results in electrical noise as well as damage to the contacts. Connecting a RC network properly sized can eliminate this arc.
For circuits up to 3 amps, a combination of a 47 ohm resistor and 0.1 mi­crofarad capacitor (1000 volts) is recommended. For circuits from 3 to 5 amps, connect 2 of these in parallel. See Figure 2-5, below.
FIGURE 2-5
AC
MOV
R C
Inductive Coil
MIC 1462 Manual
8
Edition 1
2.3.5 SENSOR PLACEMENT (THERMOCOUPLE OR RTD)
Two wire RTD's should be used only with lead lengths less than 10 feet.
If the temperature probe is to be subjected to corrosive or abrasive condi­tions, it should be protected by the appropriate thermowell. The probe should be positioned to reflect true process temperature:
In liquid media - the most agitated area In air - the best circulated area
9 MIC 1462 ManualEdition 1
FIGURE 2-6
Rear Terminal Connections
END OF PROGRAM OUTPUT
+
INPUT
Linear (mA)
-
N/O
N/C
-
-
+
+
RTD
Linear (V/mV)
Thermocouple
Transmitter Power Supply
9
C
8
7
6
5
4
3
2
1
OUTPUT 3
-
Relay
N/C
SSR/DC
-
11
23 22
24
+
N/OC
+
MAINS (LINE)
L
N
B
A
COM
-
+
SUPPLY
24V 24V
-
AC DC
+
RS485 SERIAL COMMS.
N/C
C
SSR/DC
N/O
Relay
OUTPUT 1
1210
13
14
15
16
17
18
19
20
21
+
SSR/DC
N/O
C
Relay
+
Transmitter Power Supply
Output 2
-
N/C
-
MIC 1462 Manual
10
Edition 1
FIGURE 2-6A
RESET
RUN/HOLD
REMOTE INPUTS
X60 (FAST)
R0
R1
R2
C
33
32
31
30
29
28
27
26
25
34
#1
35
36
#2
37
38
#3
39
EVENT OUTPUTS
40
#4
41
42
11 MIC 1462 ManualEdition 1
2.4 Input Connections
In general, all wiring connections are made to the instrument after it is in­stalled. Avoid electrical shock. AC power wiring must not be connected to the source distribution panel until all wiring connection procedures are completed.
Caution: This equipment is designed for installation in an enclosure which provide adequate protection against elec­tric shock. Local regulations regarding electrical installa­tion should be rigidly observed. Consideration should be given to prevention of access to the power terminations by unauthorized personnel. Power should be connected via a two pole isolating switch (preferably situated near the equipment) and a 1 A fuse, as shown in Figure 2-7.
FIGURE 2-7
Main Supply The instrument will operate on 90-264V AC 50/60 Hz mains (line) supply. The power consumption is approximately 4 VA. If the instrument has relay outputs in which the contacts are to carry mains (line) voltage, it is recom­mended that the relay contact mains (line) supply should be switched and fused in a similar manner but should be separate from the instrument mains (line) supply.
MIC 1462 Manual
13
14
L
N
12
Line
Neutral
Edition 1
FIGURE 2-7A
24V Nominal AC/DC Supply The supply connection for the 24V AC/DC option of the instrument are as shown below. Power should be connected via a two pole isolating switch and a 315 mA slow -blow (anti-surge type T) fuse. With the 24V AC/DC supply option fitted, these terminals will accept the following supply voltage ranges:
24V (nominal) AC 50/60Hz - 20-50V 24V (nominal) DC - 22-65V
L
13
14
N
24V AC 50/60Hz
-
24V DC
+
FIGURE 2-8
Thermocouple (T/C) Input Make the thermocouple connections as illustrated below. Connect the positive leg of the thermocouple to terminal 2 and the negative leg to terminal 3.
-
+
Thermocouple
FIGURE 2-9
RTD Input Make RTD connections as illustrated below. For a three wire RTD, con­nect the resistive leg of the RTD to terminal 1 and the common legs to terminals 2 and 3. For a two wire RTD, connect one leg to terminal 2 and the other leg to terminal 3 as shown below. A jumper wire supplied by the customer must be installed between terminals 2 and 3. (Continued on next page)
3
2
13 MIC 1462 ManualEdition 1
Input conditioning jumper must be positioned correctly (see Appendix B) and Hardware Definition Code must be correct (see Appendix C).
3
2
RTD
1
FIGURE 2-10
Volt, mV Input Make volt and millivolt connections as shown below. Terminal 2 is positive and terminal 3 is negative. Input conditioning jumper must be positioned correctly (see Appendix B) and Hardware Definition Code must be correct (see Appendix C).
-
+
Linear (V/mV)
FIGURE 2-11
mADC Input Make mADC connections as shown below. Terminal 4 is positive and ter­minal 1 is negative Input conditioning jumper must be positioned correctly (see Appendix B) and Hardware Definition Code must be correct (see Ap­pendix C).
+
3
2
1
4
3
MIC 1462 Manual
Linear (mA)
-
2
1
14
Edition 1
FIGURE 2-12
Remote Digital Communications - RS485 Make digital communication connections as illustrated below.
16
17
18
B
A
COM
Output Connections 2.5
FIGURE 2-13
Relay Output 1 (Control Output 1) Connections are made to Output 1 relay as illustrated below. The contacts are rated at 2 amp resistive, 120/240 VAC .
19
N/C
20
21
FIGURE 2-14
SSR Driver Output 1 (Control Output 1) Connections are made to Output 1 SSR Driver as illustrated below. The solid state relay driver is a non-isolated 0-4 VDC nominal signal. Output impedance is 250 ohms.
19
20
21
C
Relay
N/O
-
SSR
+
15 MIC 1462 ManualEdition 1
FIGURE 2-15
mADC Output 1 (Control Output 1) Make connections for DC Output 1 as illustrated below.
19
20
21
FIGURE 2-16
Relay Output 2 (Control Output 2 OR Alarm 2) Connections are made to Output 2 relay as illustrated below. The contacts are rated at 2 amp resistive, 120/240 VAC.
24 23 22
-
DC
+
N/O
FIGURE 2-17
SSR Driver Output 2 (Control Output 2 OR Alarm 2) Connections are made to Output 2 SSR Driver as illustrated below. The solid state relay driver is a non-isolated 0-4 VDC nominal signal. Output impedance is 250 ohms.
24 23 22
+
C
Relay
SSR
N/C
-
MIC 1462 Manual
16
Edition 1
FIGURE 2-18
mADC Output 2 (Control Output 2) Make connections for DC Output 2 as illustrated below.
24 23 22
+
DC
FIGURE 2-19
Transmitter Power Supply Out 2 Make connections for 24V DC transmitter power supply as illustrated below
24 23 22
+
24VDC Transmitter Power
Supply
FIGURE 2-20
Relay Output 3 (Alarm 1) Connections are made to Output 3 relay as illustrated below. The contacts are rated at 2 amp resistive, 120/240 VAC.
-
-
Relay
N/OCN/C
10 11 12
17 MIC 1462 ManualEdition 1
FIGURE 2-21
SSR Driver Output 3 (Alarm 1) Connections are made to Output 3 SSR Driver as illustrated below. The solid state relay driver is a non-isolated 0-4 VDC nominal signal. Output impedance is 250 ohms.
SSR
-
10 11 12
FIGURE 2-22
mADC Output 3 (Recorder Output Only) Make connections for DC output 3 as illustrated below.
DC
-
10 11 12
+
+
FIGURE 2-23
Transmitter Power Supply Out 3 Make connections for 24V DC transmitter power supply as illustrated be­low.
24VDC Transmitter Power
Supply
+
Edition 1
MIC 1462 Manual
-
10 11 12
18
FIGURE 2-24
End of Program Output Connections are made to End of Program Output as shown below. The contacts are rated at 5 amp resistive, 120/240 VAC.
N/O
9
END OF PROGRAM
C
8
OUTPUT
N/C
7
FIGURE 2-25
Event Outputs (optional) If the Event Outputs have been specified and if the External Option param­eter in Hardware Definition is set to either OUT of BOTH, Event Outputs are available. Make connections as shown on top of next page. The con­tacts are rated at 5 amps, 120/240 VAC.
34
#1
35
36
37
38
39
40
41
42
#2
#3
EVENT OUTPUTS
#4
19 MIC 1462 ManualEdition 1
FIGURE 2-26
Remote Program Outputs (optional) If the Remote Program Control Inputs has been specified, make connec­tions as shown. These inputs can be either TTL or switch contact, select­able in Hardware Definition. The following applies:
Terminals 31 (R2) to 33 (RO) provide a binary-coded input which is used to select the program:
Digital Inputs=TTL Level Digital Inputs=Contacts (switches) R0 R1 R2 Progran Select R0 R1 R2 Program Select
0 0 0 Program 1 Closed Open Open Program 1 1 0 0 Program 2 Open Closed Open Program 2 0 1 0 Program 3 Closed Closed Open Program 3 1 1 0 Program 4 Open Open Closed Program 4 0 0 1 Program 5 Closed Open Closed Program 5 1 0 1 Program 6 Open Closed Closed Program 6 0 1 1 Program 7 Closed Closed Closed Program 7 1 1 1 Program 8 Open Open Open Program 8
For the Program Control Inputs, the following convention has been adopted: for TTL inputs OFF=logic 0, ON=logic 1; for contacts (switch) inputs OFFG=open, ON=closed.
Terminal 30 is the Program Abort control. It is EDGE SENSITIVE; an OFF­ON transition at any time will cause an immediate Program Abort.
Terminal 29 provides the Remote Run/Hold Program control and has an identical effect to that of the Run/Hold key on the front panel. An OFF-ON transition will cause the currently selected program to be run (or to be re­sumed if it is currently held); AN ON-OFF transition will cause the currently running program to be held. Powering up the instrument with this terminal ON will not cause a program to run.
Terminal 28 provides the "x60" program time base selection. This terminal is LEVEL SENSITIVE (ON=minutes/seconds, OFF=hours/minutes). When the instrument is powered up, the initially powered time bese will be ac­cording to the level on this terminal at power-up. NOTE: All remote selection/control functions except the Abort function have
MIC 1462 Manual
20
Edition 1
precedence over the corresponding front panel controls. The "x60" func- tion will also take precedence over any present x60 parameter settings.
33
R0
32
R1
31
R2
RESET
RUN/HOLD
30
29
REMOTE INPUTS
C
28
27
X60 (FAST)
Note: Only one remote connection shown for clarity.
FIGURE 2-27
Valve Motor Drive (VMD) Control Relay Outputs 1 & 2
The contacts are rated at 2A resistive at 120V (motor drive). Connections are made as shown below.
19
20
N/C
C
Relay
Output 1
24 23 22
N/O
C
Relay Output 2
N/C
21
N/O
NOTE: With VMD control, the controller is designed to switch on either Output 1 or Output 2 (to open or close the valve). However, under fault conditions, both Output 1 and Output 2 relays could be switched on simul­taneously. For safety purposes, an interlock can be included which con­nects the supply to the motor via the "normally closed" relay contacts on the Output 1 and Output 2 relays (see Figure 2-26)
21 MIC 1462 ManualEdition 1
FIGURE 2-28
19
N/C
Motor
Supply
Close
Open
Common
24 23 22
N/O
"Close Valve" Relay
C
N/C
20
21
C
N/O
"Open Valve"
Relay
MIC 1462 Manual
22
Edition 1
Section 3 - Operation
3.1 POWER UP PROCEDURE
Verify all electrical connections have been properly made before applying power to the instrument.
If the instrument is being powered for the first time, it may be desirable to disconnect the controller output connections. The instrument will be into control following the power up sequence and the output(s) may turn ON . During Power up, a self-test procedure is initiated during which all LED segments in the two front panel displays appear and all LED indicators are ON . When the self-test procedure is complete, the instrument reverts to normal operation.
Note: When power is first applied, a delay of approx. 3 seconds will be seen before the displays light up.
3.2 KEYPAD OPERATION
Mode Key
MODE
Cycles through modes available in the instrument.
Scroll Key Displays the next parameter in sequence (indicated by Mes­sage display).
Up Key Increments displayed parameter value/cycles through options.
Down Key Decrements displayed parameter value/cycles through options.
23 MIC 1462 ManualEdition 1
PROF
PROF Key Cycles through Program (profile) numbers.
RUN/HOLD
RUN/HOLD Key Runs, holds or aborts current program (profile).
+
+
+
PROF
MODE
Jumps to next segment, when program is running.
Selects/de-selects Manual Control
Sets a segment to Dwell when defining a program.
MIC 1462 Manual
24
Edition 1
3.3 INDICATORS
Control Status Indicators
AT - ON when Self-Tune is active; flashes when Pre-
AT
ALM - Flashes when any alarm is active.
ALM
OP1 - ON when primary control output is active.
OP1
OP2 - ON when secondary control output (if fitted) is
OP2
MAN - ON when Manual Control is selected.
MAN
Run Status Indicators
RUN - ON - Program running or (if HLD ON also) held
RUN
HLD - ON - Program held
HLD
x60 - OFF - timebase = hours/minutes
x60
Tune is active.
active.
Flashing - Program in Delayed state
Flashing - Program in Auto-Hold
ON - timebase = minutes/seconds
EV1
EV2
EV3
EV4
SET
PRG
Event Indicators
Each indicates the status (active or inactive) of a user-defined event (OFF = inactive, ON = active)
Mode Indicators
SET - ON when any mode is entered; flashes when in
Controller Parameter Mode.
PRG - ON when Profile Set Mode is entered.
25 MIC 1462 ManualEdition 1
3.4 DISPLAYS
UPPER DISPLAY
Process Variable value
LOWER DISPLAY
Setpoint value or value/setting of parameter being viewed/edited.
MESSAGE DISPLAY
CURRENT RAMP STATE
= UP Ramp = DOWN Ramp
PROGRAM NUMBER
Number of currently­selected program
SEGMENT NUMBER
Number of current segment
3.5 ALARM STATUS INDICATION
When any alarm is active, the ALM indicator will flash. To view the main status in the Message Display, press the SCROLL key until a display ap­pears in the form:
BOTH ON = Dwell Both flashing = In Manual Control while program is running
Appears only if Alarm 1 is active
Appears only if Alarm 2 is active
Appears only if the Loop Alarm is active
MIC 1462 Manual
26
Edition 1
3.6 VIEWING PROGRAM AND CONTROLLER PARAMETERS
In Base Mode (i.e. with no profile currently running or held), pressing the SCROLL key will cause the instrument to display various information. The operator may view and change the setpoint, view the units the instrument is using, weather the outputs are on or off, the alarm status, the present time and day (if the real time clock is fitted), and the percent output of the control instrument if operating in Manual Mode.
NOTE: If the SCROLL key is held for longer than two seconds, the instru­ment will automatically scroll through the displays.
BASE
SETPOINT
(Units)
AlSt
OUTPUTS
time
Day
MODE
3.7 ADJUSTING THE CONTROLLER SETPOINT
With the Setpoint Programmer in Base Mode (i.e. with the RUN, HLD, SET, MAN and PRG indicators OFF), the two main displays will show the pro-
cess variable value (upper display) and the setpoint value (lower display ­Read Only). To change the setpoint value:
1. Press the SCROLL key, the Message Area will display:
2. If Setpoint has been enabled in the Enable mode, use the UP and DOWN keys to change the setpoint value (in the lower display) as re­quired.
3. When the setpoint value is set as desired, press the SCROLL key again to view other Base mode parameters.
27 MIC 1462 ManualEdition 1
3.8 VIEWING THE INPUT UNITS
To see what type of input the control is using press the SCROLL key until the Units display is shown. The Units display shows the temperature scale for thermocouple and RTD inputs <DEGF> or <DEGC> or unspecified engineering UNITS for other input types. This display can be deactivated, if desired.
OVER-RANGE/UNDER-RANGE DISPLAY If the process variable attains a value higher than the input scale maximum limit, the upper display will show:
If the process variable attains a value lower than the input scale minimum, the upper display will show:
If a break is detected in the sensor circuit, the upper display will show:
If the CJC facility in the Configuration Mode is disabled, the initial display in Operator Mode will show:
flashing in the lower display.
MIC 1462 Manual
28
Edition 1
3.9 BASE MODE AND OFF MODE OUTPUTS
The Base Mode allows for the process and event outputs to be turned on or off. When all outputs are off, the Base Mode becomes Off Mode. In Base Mode the process output is adjusted by the controller based on the process input and setpoint. The event outputs for the Base Mode are set in the Configuration Mode. To view the present status of the outputs, press the SCROLL key until OUTPUTS is displayed in the message display. Use the UP and DOWN keys to turn the outputs ON or OFF (toggle between Base Mode and Off Mode).
3.10 VIEWING THE TIME AND DAY
If the real time clock option is fitted, the operator may view the present time and day. Press the SCROLL key until HH:MM Tim is displayed. This is the present time of day in hours and minutes. Press the SCROLL key again and Day: XXX is displayed with XXX being an abbreviation for the present day of the week. If TIME BAD is displayed, the time and day must be set in the Profile Mode (see sec. 6)
3.11 MANUAL CONTROL
In any mode except Configuration Mode, the operator may select manual control of the process by simultaneously pressing the SCROLL and MODE keys, provided Manual Mode is enabled in Controller Define Mode. The instrument will then enter Base Mode or (if a program is currently running) Program Run Mode with the program held. The Message Display will show:
The lower Main Display will show the power output value, which may then be adjusted using the UP and DOWN keys and the MAN indicator will be lit. While manual control is being used, the power output display is included in the displays available in Base Mode and Program Run Mode.
29 MIC 1462 ManualEdition 1
To cancel manual control, press the SCROLL and MODE keys simulta­neously, wereupon the power out value display and the Power message display will disappear and the Setpoint Controller will remain in whatever mode prevailed when manual control was cancelled (if this is Program Run Mode, the currently-running program will be resumed from the point at which it was held).
3.12 USING THE PRE-TUNE FACILITY
The Pre-Tune facility is used to set the instrument's PID control parameters to values which are approximately correct in order to provide a base from which the Self-Tune facility may subsequently optimize tuning. Pre-Tune may be activated as follows:
1. With the instrument in Base mode (with the RUN and HLD indicators OFF), press the MODE key until the Message Display shows:
and the lower Main Display shows:
2. Press the UP key to change the lower Main Display to:
indicating that the Pre-Tune facility is now activated. The AT indicator will flash.
NOTES:
1. If the process variable is within 5% of the input span from the setpoint, the Pre-Tune facility cannot be activated and any attempt to do so will have no effect.
2. Since the Pre-Tune facility is a single-shot operation, it will auto­matically de-activate itself once the operation is complete.
MIC 1462 Manual
30
Edition 1
To de-activate the Pre-Tune facility manually (with the instrument in Base Mode), press the MODE key to obtain the same Message Displays above; then press the DOWN key simultaneously to change the lower Main display from ON to OFF.
3.13 USING THE SELF-TUNE FACILITY
The Self-Tune facility is used to optimize tuning while the Controller part of the instrument is operating. Self Tune may be activated as follows:
1. With the instrument in Base Mode (with RUN and HLD indicators OFF), press the MODE key until the Message Display shows:
and the lower Main Display shows:
2. Press the UP key to change the lower Main Display to:
indicating that the Self-Tune facility is now activated. The AT indicator is on continuously.
To de-activate the Self-Tune facility, press the MODE key to obtain the same Message Display as above; then press the DOWN key to change the lower Main Display from ON to OFF.
31 MIC 1462 ManualEdition 1
Section 4 - Configuration
4.1 ENTRY INTO CONFIGURATION MODE
To enter Configuration Mode:
1. Press the MODE Key until Conf Par appears in the message display.
2. Press the SCROLL Key to enter the Configuration Mode
The instrument will then enter Configuration Mode, whereupon the main display will initially be of the form:
showing the current input code selected, and the Message Display will show:
The user may then step through the Configuration Mode parameters using the SCROLL key. For each parameter, the Message Display will show a legend identifying that parameter and the lower main display will show the current setting of that parameter. The setting may be adjusted using the UP/DOWN keys. As soon as the setting is changed, the lower main display will flash, indicating that the new setting has yet to be confirmed. When the setting is as required, it may be confirmed by pressing the MODE key, whereupon the upper display will stop flashing.
NOTE: Changes to certain Configuration Mode parameters (i.e. input range, output use and type) will cause other mode param­eters to be automatically set to their defauly values. Items affect include Tune Mode, and Pretune and Auto Tune Facilities. Until the Tune Mode setting have been verified by changing at least one paraneter, the upper main display will show decimal points to indi­cate that the values are in their default condition.
Changes to Configuration Mode parameters will not be accepted until they have been verified with the PROF key.
MIC 1462 Manual
32
Edition 1
4.2 HARDWARE DEFINITION CODE
This parameter is a special facility in Configuration Mode, which is used to specify the hardware fitted (input type, output types, etc); this must be com­patible with the hardware actually fitted. It can be accessed, with the in­strument in Configuration Mode, by simultaneously pressing the DOWN and SCROLL keys. The Message Display will then show:
and lower main display will be of the form:
Input Type 1 RTD/Linear (mV) 2 Thermocouple 3 Linear DC (mA) 4 Linear DC (V)
Output 1 Type 1 Relay Output 2 SSR Output 3 DC Output (0-10V) 4 DC Output (0-20mA) 5 DC Output (0-5V) 7 DC Output (4-20mA)
Output 3 Type 0 None 1 Relay Output (Alarm Output Only) 2 SSR Output (Alarm Output Only) 3 DC Output 0-10V (Recorder Output Only) 4 DC Output 0-20mA (Recorder Output Only) 5 DC Output 0-5V (Recorder Output Only) 7 DC Output 4-20mA (Recorder Output Only)
Output 2 Type 0 None 1 Relay Output (Control or Alarm Output) 2 SSR Output (Control or Alarm Output) 3 DC Output 0-10V (Control Output Only) 4 DC Output 0-20mA (Control Output Only) 5 DC Output 0-5V (Control Output Only) 7 DC Output 4-20mA (Control Output Only)
33 MIC 1462 ManualEdition 1
The displayed code may be incremented/decremented using the UP/ DOWN keys as required. The maximum setting available for this code is
4777. For example, the code for a thermocouple input, 4-20mA DC primary output (Output 1) and relay Output 3 would be 2701. When the code is first altered, the code display will flash, until the desired value is displayed and confirmed by pressing the MODE key.
NOTE: It is essential that this code is changed promptly whenever there is a change to the instrument's hardware configuration (change of input/output type, alarm/recorder output added/removed etc.). The instrument software depends upon this code to operate correctly.
Hardware Definitions may be viewed as Read Only displays in Base Mode by pressing the SCROLL and DOWN keys simultaneously.
While the Hardware Definition Code is displayed, pressing the SCROLL key will cause the Message Display to change to:
and the lower main display to change to one of:
No option PCB
fitted
Digital Input Option PCB
fitted
Both Option
PCBs fitted
Event Output
Option PCB
fitted
The desired setting can be achieved using the UP/DOWN keys.
MIC 1462 Manual
34
Edition 1
Press the SCROLL key to change the Message Display to:
and the lower main display to one of:
RS485
Communications
Option PCB not
fitted
RS485
Communications
Option PCB fitted -
Programmer acting as
slave device
Option PCB fitted -
Programmer acting as
RS485
Communications
master device
The desired setting can be achieved using the UP/DOWN keys.
Pressing the SCROLL key again will display Inputs in the Message Display. Press the UP and DOWN keys to select from contact (cont) and low volt­age (ttl) type inputs.
Pressing the SCROLL key again will display the desired function of the remote input wired to terminal 28 (see Sec. 2). Press the UP and DOWN keys to select from X60 timebase (60) or jump to next segment (SEGJ). This input can be used to remotely control the appropriate function in the Program Run Mode.
To exit from the Hardware Definition Code facility, press the DOWN and SCROLL keys simultaneously (which will cause a return to the normal Con­figuration Mode). Alternatively, either of the methods of exit from Configu­ration Mode may be used here.
35 MIC 1462 ManualEdition 1
4.3 CONFIGURATION MODE PARAMETERS
The Configuration Mode parameters are presented for view/edit in the fol­lowing sequence:
MESSAGE AVAILABLE
STEP DESCRIPTION DISPLAY FUNCTION SETTING
1 Primary Input Input Code display- See App. A
Range
5
ed defines input type/ range (see App. A)
2 Control Action Control Specifies dir - Direct
control Acting action of rEV- Reverse Output 1
1
Acting *Mdr-Motor
Drive
Reverse * Not available if Output 1 AND Output 2 are Not Relay Outputs
*Mdd-Motor
Drive
Direct
3 Output 2 Usage Out2 Use Specifies out2-Control
use of Output Output 2
2
A2_d-Alarm 1 (direct) A2_r-Alarm 2 (reverse)
NOTE: This parameter not available if Control Action is set to Mdr or Mdd-Output 2 automatically used as control output
Or_d-Alarm 1
OR 2
(direct)
Or_r-Alarm 1 OR 2
(reverse)
Ad_d-Alarm 1
AND 2
(direct)
Ad_r-Alarm 1
AND 2
(reverse)
MIC 1462 Manual
36
Edition 1
MESSAGE AVAILABLE
STEP DESCRIPTION DISPLAY FUNCTION SETTINGS
LP_d-Loop
Alarm
(direct)
LP_r-Loop
Alarm
(reverse)
4 Output 3 Useage Out3 Use Specifies Al_d-Alarm 1
use of (direct) Output 3
3
Al_r-Alarm 1 (reverse) Or_d-Alarm 1
OR 2
(direct)
Or_r-Alarm 1 OR 2
(reverse)
Ad_d-Alarm 1
AND 2
(direct)
Ad_r-Alarm 1
AND 2
(reverse)
LP_d-Loop
Alarm
(direct)
LP_r-Loop
Alarm
(reverse)
rEcS-Rcdr
Output
(SP)
rEcP-Rcdr
Output
(PV)
37 MIC 1462 ManualEdition 1
MESSAGE AVAILABLE STEP DESCRIPTION DISPLAY FUNCTION SETTINGS 5 Segment Mode Seg Mode Defines para- ti- Time
meter used to rA-Ramp Rate specify duration of each segment (along with final SP value)
6 Baud Rate
7 Protocol
8 Address
6
6,7
6
Baud Rate Selects Baud Numeric
Rate for RS485 value: 1200, Comms. 2400, 4800 or
9600
Protocol Select protocol Mbn-Modbus,
and parity for no parity RS-485 Comms Mbo-Modbus,
odd parity Mbe-Modbus, even parity WES-ASCII
Address Selects RS485 Numeric
comm. address value in range
1-32
9 CJC4 Enable/ CJC Enables/ EnAb-enabled
Disabled disables cold diSA-disabled
junction comp.
10 Events10 Events Set event status Binary with
in Base Mode LSD=Event 1
0100=Event3 on, all other events off
MIC 1462 Manual
38
Edition 1
MESSAGE AVAILABLE STEP DESCRIPTION DISPLAY FUNCTION SETTINGS
11 Scale Range DecPos For Linear 0 XXXX
Decimal Point
9
Inputs, defines 1 XXX.XDefault decimal point 2 XX.XX position 3 X.XXX
12 Scale Range EngU UP For linear inputs -1999 to 9999
Maximum
9
,defines the (decimal point scaled input as defined by value when the Scale Range process variable Decimal Point input is at its parameter) maximum value
13 Scale Range EngU LO For linear inputs -1999 to 9999
Minimum
9
,defines the (decimal point scaled input as defined by value when the Scale Range process variable Decimal Point input is at its parameter) minimum value
14 Setpoint High SP High The Maximum Current set-
8
Limit
limit for setpoint point value to adjustment. input range Should be set to max. a value which prevents set­point values causing damage to the process
39 MIC 1462 ManualEdition 1
MESSAGE AVAILABLE STEP DESCRIPTION DISPLAY FUNCTION SETTINGS
15 Setpoint Low SP Low The Minimum Current set-
8
Limit
limit for setpoint point value to adjustment. input range Should be set to min. a value which prevents set­point values causing damage to the process
16 Input Filter Filter Defines time 0.0 seconds
Time Constant constant for (filter OFF)
input filter (re- to 100.0 sec. moves extra- in 0.5 incre­neous impulse ments. from the process variable input.)
17 Output Power Out PL Determines max 0 to 100 (%)
Limit output setting
instrument will provide
18 Engineering Units3Units Sets units to be Unit
displayed in CEnt base mode FAHr
19 End of Program EOprelay Sets action of End=relay
relay active at end
of profile run=relay active during profile Default=End
For Notes on Configuration Mode Parameters, see next page.
MIC 1462 Manual
40
Edition 1
Notes on Configuration Mode Parameters
1. If the secondary output is chosen as Output 2 (COOL) control output, its action is always the compliment of the action of Output 1.
2. The default setting for Output 2 Usage is Alarm 2 hardware output, direct-acting (if relay/SSR output) or Output 2 - COOL (if DC output).
3. The default setting for Output 3 Usage is Alarm 1 hardware output, direct-acting (if relay/SSR output) or Process Variable Recorder Output (if DC output)
4. This parameter does not appear in the sequence if the input type selected is not thermocouple. If the CJC is disabled, the initial display in Operator Mode will show horizontal bars flashing in the lower display.
5. The primary input default setting is dependent upon the hardware fitted, as indicated in the Hardware Definition Code.
6. These parameters do not appear if the Hardware Definition Comms parameters is set to nonE.
7. This parameter does not appear if the Programmer communications option is set to operate in Master mode.
8. Internal software prevents (a) the Setpoint High Limit being given a value less than any setpoint value contained in currently-resident pro­ grams, and (b) the Setpoint Low Limit being given a value greater than any setpoint value contained in currently-resident programs.
9. These parameters are applicable only if a linear input is fitted.
10. These parameters do not appear if features are not fitted.
11. When X60 in Profile Set = OFF, Time = hours/minutes and Ramp Rate = LSD/hour When X60 in Profile Set = ON, Time = minutes/seconds and Ramp Rate - LSD/minute
4.4 EXIT FROM CONFIGURATION MODE
To leave Configuration Mode, depress and hold the MODE key for five seconds.
The exit is made via the power-up self-test routines which includes a lamp test.
41 MIC 1462 ManualEdition 1
Section 5 - Defining The Tune Parameters
Entry can be made into this mode from Program Define Mode, Program Run Mode or Base Mode.
To enter from Base Mode or Program Run Mode:
1. Press the MODE key until the Message Display will show:
2. Press the SCROLL key.
The instrument is now in the Tune Mode.
Upon entry into the Tune Mode, the SET indicator will then come ON and the first of the Tune parameters (Input Correction) will be presented for editing/viewing. Using the SCROLL key, step through the sequence of Tune parameters, editing as required (using the UP/DOWN keys).
MIC 1462 Manual
42
Edition 1
Loading...