CIRCULAR CHART RECORDERS • STRIP CHART RECORDERS • DATA ACQUISITION SYSTEMS
DATALOGGERS • ANALOG AND MICROBASED CONTROLLERS
MECHANICAL RECORDERS AND CONTROLLERS
PARTLOW CORPORATION • 2 CAMPION ROAD • NEW HARTFORD, NY 13413 USA
1-800-866-6659 • 315-797-2222 • FAX 315-797-0403
Information in this installation, wiring, and operation manual is subject to change
without notice. One manual is provided with each instrument at the time of shipment. Extra copies are available at the price published on the front cover.
This is the First Edition of the MIC 1460 manual. It was written and produced
entirely on a desk-top-publishing system. Disk versions are available by written
request to the Partlow Publications Department.
We are glad you decided to open this manual. It is written so that you can take full
advantage of the features of your new MIC 1460 setpoint programmer .
NOTE:
It is strongly recommended that Partlow equipped
applications incorporate a high or low limit protective device
which will shut down the equipment at a preset process
condition in order to preclude possible damage to property
or products.
Table of Contents
Section 1 - GeneralPage
1.1 Product Description1
Section 2 - Installation & Wiring
2.1 Unpacking Procedure3
2.2 Panel Mounting3
2.3 Wiring Guidelines5
2.4 Input Connections12
2.5 Output Connections15
Section 3 - Operation
3.1Power-up Procedure20
3.2Keypad Operation20
3.3Indicators22
3.4Displays23
3.5Alarm Status Indication23
3.6Viewing Program and Controller Parameters24
3.7Adjusting the Setpoint24
3.8Manual Control25
3.9Using the Pre-Tune Facility25
3.10 Using the Self-Tune Facility26
Section 4 - Configuration
4.1Entry into Configuration28
4.2Hardware Definition Mode29
4.3Configuration Mode Parameters31
4.4Alarm Inhibit Facility35
4.5Exit from Configuration Mode35
Section 5 - Controller Define Mode
5.1Controller Parameters37
5.2Base Mode Displays52
5.3Loop Alarm and Loop Alarm Time52
5.4Exiting Controller Define Mode53
MIC 1460 ManualEdition 1i
Section 6 - Program Define Mode
6.1Entry into Program Define54
6.2Paramters Common to All Programs55
6.3Parameters which apply to a Specific Program57
6.4Parameters in any/each Segment61
6.5Using Join, Repeat, and End Segments64
6.6Basic Rules to Remember66
6.7Exiting Program Define Mode66
Section 7 - Programs
7.1Selecting and Running a Program67
7.2Changing Timebase67
7.3Holding Manually67
7.4Jumping to Next Segment68
7.5Viewing Program Status68
7.6Aborting a Program69
7.7End of Progam Indication69
7.8Viewing Program/Control Parameters70
Appendices
A - Input Range Codes71
B - Board Layout - Jumper positioning73
Figure B-1 PCB Positions73
Figure B-2 Output 2/Output 3 Removal74
Figure B-3 CPU PWA75
Figure B-4 PSU PWA with Relay or SSR Out.176
Figure B-5 PSU PWA with DC Output 177
Figure B-6 Option PWA DC Output 2/Output 378
C - Specifications79
D - Model Number Hardware Matrix87
E - Software Reference Sheet88
This instrument is a powerful, easy-to-use 1/4 DIN setpoint programmer
with full PID control capability (complete with Self-Tune and Pre-T une facilities).
Its standard features include:
• Up to eight programs of up to 16 free-format (e.i. dwell, ramp, join, or
end) segments each.
• Facility to join programs to one another in any sequence (maximum
program length 121 segments)
• User can change currently-running program segment.
• Delayed Start of Program facility
• End of Program relay output
• Universal input-thermocouple, RTD (PT100) or DC linear user-selectable.
• Universal power supply (90 -264V AC 50/60 Hz)
• Configurable from front panel
• Comprehensive front panel displays
• Front panel sealing to NEMA 4 standard
• Behind-panel depth only 100mm (3.94 inchs)
Optional features include:
• Remote control and selection of program (plug-in option)
• Up to four Event relay outputs (plug-in option)
• Second control output
• Recorder output (setpoint or process variable)
• RS-485 serial communications
• User-definable program tag names
• Support software (Off-line Configurator, On-line Graphic Program
Editor) - operates via RS-485 communications link.
MIC 1460 ManualEdition 11
The Setpoint Programmer has four operating modes:
Base Mode: Day to day PID control operations with no program running.
In this mode, a program may be selected to run.
Program Run Mode: A selected program is running, held or waiting for a
pre-defined delay before starting. In this mode, the operator can view
status and program information.
Program Define Mode:* Used to view/create/edit programs. this mode
is entered either from Base Mode (selected program may be edited/
created) or from Program Run Mode (currently-running program may be
edited).
Controller Define Mode:** Used to define the controller characteristics.
* Entry via Lock Code; also optional Program Lock prevents changing of
program definitions while a program is running.
** Enry via a Lock Code.
FIGURE 1-1
Front Panel
MIC 1460 ManualEdition 12
Section 2 - Installation & Wiring
2.1 UNPACKING PROCEDURE
1. Remove the instrument from its packing. The instrument is supplied
with a panel gasket and push-fit strap. Retain the packing for future use,
should it be necessary to transport the instrument to a different site or
return it to the factory for repair/testing.
2. Examine the delivered items for damage or deficiencies. If any is
found, notify the carrier immediately. Check that the model number
shown on the label affixed to the instrument housing corresponds to that
ordered (see Appendix D).
2.2 PANEL-MOUNTING THE SETPOINT PROGRAMMER
The panel on which the instrument is to be mounted must be rigid and may
be up to 6.0 mm (.25 inches ) thick. The cutout required for a single instrument is shown in Figure 2-1.
FIGURE 2-1
Cut-Out Dimensions
92 mm +0.5 - 0.00
(3.62”+.020 - .000)
PANEL
CUTOUT
SIZE
92 mm + 0.5 - 0.0
(3.62” + .020 - .000)
MIC 1460 ManualEdition 13
The main dimensions of the instrument are shown below.
FIGURE 2-2
Main Dimensions
100 mm (3.94 in.)
96 mm
(3.78 in)
Side View
96 mm
(3.78 in.)
Max. Panel Thickness 6.0mm (.25 inches)
10 mm (0.39 in.)
To panel-mount the instrument:
1. Insert the rear of the instrument housing through the cutout (from the
front of the mounting panel) and hold the instrument lightly in position
against the panel. Ensure that the panel gasket is not distorted and that
the instrument is positioned squarely against the mounting panel. Apply
pressure to the front panel bezel only.
Caution: Do not remove the panel gasket, as this may result
in inadequate clamping of the instrument in the panel.
2. Slide the fixing strap in place (Figure 2-3) and push it forward until it
is firmly in contact with the rear face of the mounting panel (the tongues
on the strap should have engaged in matching rachet positions on the
instrument housing and the fixing strap springs should be pushing firmly
against the mounting panel rear face).
MIC 1460 ManualEdition 14
Once the instrument is installed in its mounting panel, it may be subsequently removed from its housing, if necessary, as described in Appendix
B.
FIGURE 2-3
Panel-Mounting the Instrument
Mounting Clamp
Controller Housing
Tongues on mounting clamp engage in
ratchet slots on controller housing
2.3 PREPARATION FOR WIRING
Electrical noise is a phenomenon typical of industrial environments. The
following are guidelines that must be followed to minimize the effect of
noise upon any instrumentation.
2.3.1 INST ALLATION CONSIDERA TIONS
Listed below are some of the common sources of electrical noise in the
industrial environment:
• Ignition T ransformers
• Arc Welders
• Mechanical contact relay(s)
• Solenoids
MIC 1460 ManualEdition 15
Before using any instrument near the device listed, the instructions below
should be followed:
1. If the instrument is to be mounted in the same panel as any of the
listed devices, separate them by the largest distance possible. For maximum electrical noise reduction, the noise generating devices should be
mounted in a separate enclosure.
2. If possible, eliminate mechanical contact relay(s) and replace with
solid state relays. If a mechanical relay being powered by an instrument
output device cannot be replaced, a solid state relay can be used to
isolate the instrument.
3. A separate isolation transformer to feed only instrumentation should
be considered. The transformer can isolate the instrument from noise
found on the AC power input.
4. If the instrument is being installed on existing equipment, the wiring in
the area should be checked to insure that good wiring practices have
been followed.
2.3.2 AC POWER WIRING
Neutral (For 1 15 VAC)
It is good practice to assure that the AC neutral is at or near ground potential. To verify this, a voltmeter check between neutral and ground should be
done. On the AC range, the reading should not be more than 50 millivolts.
If it is greater than this amount, the secondary of this AC transformer supplying the instrument should be checked by an electrician. A proper neutral
will help ensure maximum performance from the instrument.
2.3.3 WIRE ISOLA TION
Four voltage levels of input and output wiring may be used with the unit:
• Analog input or output (i.e. thermocouple, R TD, VDC, mVDC, or
mADC)
• SPDT Relays
• SSR driver outputs
• AC power
MIC 1460 ManualEdition 16
The only wires that should run together are those of the same category. If
they need to be run parallel with any of the other lines, maintain a minimum
6 inch space between wires. If wires must cross each other , do so at 90
degrees. This will minimize the contact with each other and reduces "cross
talk". "Cross Talk" is due to the EMF (Electro Magnetic Flux) emitted by a
wire as current passes through it. This EMF can be picked up by other
wires running in the same bundle or conduit.
In applications where a High Voltage Transformer is used (i.e. ignition systems) the secondary of the transformer should be isolated from all other
cables.
This instrument has been designed to operate in noisy environments, however , in some cases even with proper wiring it may be necessary to suppress the noise at the source.
2.3.4 USE OF SHIELDED CABLE
Shielded cable helps eliminate electrical noise being induced on the wires.
All analog signals should be run with shielded cable. Connection lead
length should be kept as short as possible, keeping the wires protected by
the shielding. The shield should be grounded at one end only. The preferred grounding location is the sensor, transmitter, or transducer .
2.3.5 NOISE SUPPRESSION AT THE SOURCE
Usually when good wiring practices are followed no further noise protection
is necessary. Sometimes in severe electrical environments, the amount of
noise is so great that it has to be suppressed at the source. Many manufacturers of relays, contactors, etc. supply "surge suppressors" which
mount on the noise source.
For those devices that do not have surge suppressors supplied. RC (resistance-capacitance) networks and/or MOV (metal oxide varistors) may be
added.
Inductive Coils - MOV's are recommended for transient suppression in
inductive coils connected in parallel and as close as possible to the coil.
See Figure 2-4. Additional protection may be provided by adding an RC
network across the MOV.
MIC 1460 ManualEdition 17
FIGURE 2-4
0.5
mfd
1000V
220
ohms
115V 1/4W
230V 1W
Coil
Contacts - Arcing may occur across contacts when the contact opens and
closes. This results in electrical noise as well as damage to the contacts.
Connecting a RC network properly sized can eliminate this arc.
For circuits up to 3 amps, a combination of a 47 ohm resistor and 0.1 microfarad capacitor (1000 volts) is recommended. For circuits from 3 to 5
amps, connect 2 of these in parallel. See Figure 2-5, below.
FIGURE 2-5
MOV
R C
Inductive
Coil
MIC 1460 ManualEdition 18
2.3.5 SENSOR PLACEMENT (THERMOCOUPLE OR RTD)
Two wire RTD's should be used only with lead lengths less than 10 feet.
If the temperature probe is to be subjected to corrosive or abrasive condi-
tions, it should be protected by the appropriate thermowell. The probe
should be positioned to reflect true process temperature:
In liquid media - the most agitated area
In air - the best circulated area
MIC 1460 ManualEdition 19
FIGURE 2-6
Rear Terminal Connections
OUTPUT 3
Relay
END OF
PROGRAM
OUTPUT
+
INPUT
Linear (mA)
-
N/O
N/C
-
+
+
RTD
Linear (V/mV)
Thermocouple
C
N/C
SSR/DC
-
9
8
7
6
5
4
3
2
1
24
N/OC
+
11
1210
2322
13
14
15
16
17
18
19
20
21
MAINS (LINE)
SUPPLY
24V 24V
L
AC DC
N
B
RS485
A
COM
-
+
SERIAL
COMMS.
N/C
C
SSR/DC
N/O
-
+
Relay
OUTPUT 1
+
SSR/DC
N/O
MIC 1460 ManualEdition 110
C
Relay
OUTPUT 2
-
N/C
FIGURE 2-6A
RESET
RUN/HOLD
REMOTE INPUTS
X60 (FAST)
R0
R1
R2
C
33
32
31
30
29
28
27
26
25
34
#1
35
36
#2
37
38
#3
39
EVENT OUTPUTS
40
#4
41
42
MIC 1460 ManualEdition 111
2.4 Input Connections
In general, all wiring connections are made to the instrument after it is installed. Avoid electrical shock. AC power wiring must not be connected to
the source distribution panel until all wiring connection procedures are
completed.
Caution: This equipment is designed for installation in an
enclosure which provide adequate protection against electric shock. Local regulations regarding electrical installation should be rigidly observed. Consideration should be
given to prevention of access to the power terminations by
unauthorized personnel. Power should be connected via a
two pole isolating switch (preferably situated near the equipment) and a 1 A fuse, as shown in Figure 2-7.
FIGURE 2-7
Main Supply
The instrument will operate on 90-264V AC 50/60 Hz mains (line) supply.
The power consumption is approximately 4 VA. If the instrument has relay
outputs in which the contacts are to carry mains (line) voltage, it is recommended that the relay contact mains (line) supply should be switched and
fused in a similar manner but should be separate from the instrument
mains (line) supply.
L
13
N
14
MIC 1460 ManualEdition 112
Line
Neutral
FIGURE 2-7A
24V Nominal AC/DC Supply
The supply connection for the 24V AC/DC option of the instrument are as
shown below . Power should be connected via a two pole isolating switch
and a 315 mA slow -blow (anti-surge type T) fuse. With the 24V AC/DC
supply option fitted, these terminals will accept the following supply voltage
ranges:
24V (nominal) AC 50/60Hz - 20-50V
24V (nominal) DC -22-65V
L
13
14
N
24V AC
50/60Hz
-
24V DC
+
FIGURE 2-8
Thermocouple (T/C) Input
Make the thermocouple connections as illustrated below. Connect the
positive leg of the thermocouple to terminal 2 and the negative leg to
terminal 3.
-
+
Thermocouple
FIGURE 2-9
RTD Input
Make RTD connections as illustrated below. For a three wire RTD, connect
the resistive leg of the RTD to terminal 1 and the common legs to terminals
2 and 3. For a two wire RTD, connect one leg to terminal 2 and the other
leg to terminal 3 as shown below. A jumper wire supplied by the customer
must be installed between terminals 2 and 3. (Continued on next page)
3
2
MIC 1460 ManualEdition 113
Input conditioning jumper must be positioned correctly (see Appendix B)
and Hardware Definition Code must be correct (see Appendix C).
3
2
RTD
1
FIGURE 2-10
V olt, mV Input
Make volt and millivolt connections as shown below . Terminal 2 is positive
and terminal 3 is negative. Input conditioning jumper must be positioned
correctly (see Appendix B) and Hardware Definition Code must be correct
(see Appendix C).
-
+
Linear (V/mV)
FIGURE 2-11
mADC Input
Make mADC connections as shown below. Terminal 4 is positive and terminal 1 is negative Input conditioning jumper must be positioned correctly
(see Appendix B) and Hardware Definition Code must be correct (see Appendix C).
+
3
2
1
4
3
Linear (mA)
-
MIC 1460 ManualEdition 114
2
1
FIGURE 2-12
Remote Digital Communications - RS485
Make digital communication connections as illustrated below .
16
17
18
B
A
COM
Output Connections 2.5
FIGURE 2-13
Relay Output 1 (Control Output 1)
Connections are made to Output 1 relay as illustrated below. The contacts
are rated at 2 amp resistive, 120/240 VAC .
19
N/C
20
21
FIGURE 2-14
SSR Driver Output 1 (Control Output 1)
Connections are made to Output 1 SSR Driver as illustrated below. The
solid state relay driver is a non-isolated 0-4 VDC nominal signal. Output
impedance is 250 ohms.
19
20
21
C
Relay
N/O
-
SSR
+
MIC 1460 ManualEdition 115
FIGURE 2-15
mADC Output 1 (Control Output 1)
Make connections for DC Output 1 as illustrated below.
19
20
21
FIGURE 2-16
Relay Output 2 (Control Output 2 OR Alarm 2)
Connections are made to Output 2 relay as illustrated below. The contacts
are rated at 2 amp resistive, 120/240 VAC.
242322
-
DC
+
N/O
FIGURE 2-17
SSR Driver Output 2 (Control Output 2 OR Alarm 2)
Connections are made to Output 2 SSR Driver as illustrated below. The
solid state relay driver is a non-isolated 0-4 VDC nominal signal. Output
impedance is 250 ohms.
242322
+
C
Relay
SSR
N/C
-
MIC 1460 ManualEdition 116
FIGURE 2-18
mADC Output 2 (Control Output 2)
Make connections for DC Output 2 as illustrated below.
242322
+
DC
FIGURE 2-19
Relay Output 3 (Alarm 1)
Connections are made to Output 3 relay as illustrated below. The contacts
are rated at 2 amp resistive, 120/240 VAC.
Relay
101112
FIGURE 2-20
SSR Driver Output 3 (Alarm 1)
Connections are made to Output 3 SSR Driver as illustrated below. The
solid state relay driver is a non-isolated 0-4 VDC nominal signal. Output
impedance is 250 ohms.
-
N/OCN/C
SSR
-
101112
+
MIC 1460 ManualEdition 117
FIGURE 2-21
mADC Output 3 (Recorder Output Only)
Make connections for DC output 3 as illustrated below.
DC
-
101112
FIGURE 2-22
End of Program Output
Connections are made to End of Program Output as shown below. The
contacts are rated at 5 amp resistive, 120/240 V AC.
N/O
END OF
PROGRAM
OUTPUT
C
N/C
+
9
8
7
FIGURE 2-23
Event Outputs (optional)
If the Event Outputs have been specified, make connections as shown on
top of next page. The contacts are rated at 5 amps, 120/240 VAC.
MIC 1460 ManualEdition 118
34
35
36
37
38
39
40
41
42
#1
#2
#3
EVENT OUTPUTS
#4
FIGURE 2-24
Remote Program Inputs (optional)
If the Remote Program Control Inputs has been specified, make connections as shown.
33
R0
32
R1
31
R2
RESET
RUN/HOLD
30
29
REMOTE INPUTS
C
28
27
X60 (FAST)
Note: Only one remote connection shown for clarity.
MIC 1460 ManualEdition 119
Section 3 - Operation
3.1 POWER UP PROCEDURE
Verify all electrical connections have been properly made before applying
power to the instrument.
If the instrument is being powered for the first time, it may be desirable to
disconnect the controller output connections. The instrument will be into
control following the power up sequence and the output(s) may turn ON .
During Power up, a self-test procedure is initiated during which all LED
segments in the two front panel displays appear and all LED indicators are
ON . When the self-test procedure is complete, the instrument reverts to
normal operation.
Note: When power is first applied, a delay of approx. 3 seconds will be
seen before the displays light up.
3.2 KEYPAD OPERATION
Mode Key
MODE
Changes mode of instrument.
Scroll Key
Displays the next parameter in sequence (indicated by Message display).
Up Key
Increments displayed parameter value/cycles through options.
Down Key
Decrements displayed parameter value/cycles through options.
MIC 1460 ManualEdition 120
PROF
PROF Key
Cycles through Program (profile) numbers.
RUN/HOLD
RUN/HOLD Key
Runs, holds or aborts current program (profile).
Selects/de-selects Self-T une and Pre-Tune (when
MODE
+
+
+
PROF
MODE
message display shows appropriate message).
Jumps to next segment, when program is
running.
Selects/de-selects Manual Control
+
Sets a segment to Dwell when defining a
program.
MIC 1460 ManualEdition 121
3.3 INDICATORS
Control Status Indicators
AT
ALM
OP1
OP2
MAN
RUN
HLD
x60
A T -ON when Self-Tune is active; flashes when Pre-
Tune is active.
ALM -Flashes when any alarm is active.
OP1 -ON when primary control output is active.
OP2 -ON when secondary control output (if fitted) is
active.
MAN -ON when Manual Control is selected.
Run Status Indicators
RUN -ON - Program running or (if HLD ON also) held
Flashing - Program in Delayed state
HLD -ON - Program held
Flashing - Program in Auto-Hold
x60 -OFF - timebase = hours/minutes
ON - timebase = minutes/seconds
EV1
EV2
EV3
EV4
SET
PRG
Event Indicators
Each indicates the status (active or inactive) of a user-defined
event (OFF = inactive, ON = active)
Mode Indicators
SET -ON when Controller Define Mode or Program
Define Mode is entered; flashes when viewing
parameters in Controller Define Mode or Program
Define Mode after entry from Base Mode.
PRG -ON when Program Define Mode is entered.
MIC 1460 ManualEdition 122
3.4 DISPLAYS
PROGRAM NUMBER
Number of currentlyselected program
UPPER DISPLAY
Process Variable value
LOWER DISPLAY
Setpoint value or value/setting
of parameter being viewed/edited.
MESSAGE DISPLAY
CURRENT RAMP STATE
= UP Ramp
= DOWN Ramp
BOTH ON = Dwell
Both flashing = In Manual Control while
program is running
SEGMENT NUMBER
Number of current segment
3.5 ALARM STATUS INDICATION
When any alarm is active, the ALM indicator will flash. To view the main
status in the Message Display, press the SCROLL key until a display appears in the form:
Appears only if Alarm 1 is active
Appears only if Alarm 2 is active
Appears only if the Loop Alarm is active
MIC 1460 ManualEdition 123
3.6 VIEWING PROGRAM AND CONTROLLER PARAMETERS
In Base Mode (i.e. with no program currently running or held), the MODE
key gives "view only" access to Program Define Mode and Controller Define Mode.
VIEW ONLY
CONTROLLER
DEFINE
MODE
BASE
MODE
MODE
VIEW ONLY
PROGRAM
DEFINE
MODE
MODE
MODE
3.7 ADJUSTING THE CONTROLLER SETPOINT
With the Setpoint Programmer in Base Mode (i.e. with the RUN, HLD, SET,
and PRG indicators OFF), the two main displays will show the process
variable value (upper display) and the setpoint value (lower display - Read
Only). To change the setpoint value:
1. Press the SCROLL key, the Message Area will display:
2. Use the UP and DOWN keys to change the setpoint value (in the
lower display) as required.
3. When the setpoint value is set as desired, press the SCROLL key
again to return to the initial display.
MIC 1460 ManualEdition 124
Loading...
+ 68 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.