Partlow MIC 1401 Operating Manual

MIC 1401
1/4 DIN MICROBASED LIMIT CONTROLLER
OPERATORS MANUAL
FORM 3669 EDITION 1 © OCT. 1995 PRICE $10.00
Information in this installation, wiring, and operation manual is subject to change without notice. One manual is provided with each instrument at the time of ship­ment. Extra copies are available at the price published on the front cover.
Copyright © Oct. 1995, The Partlow Corporation, all rights reserved. No part of this publication may be reproduced, transmitted, transcribed or stored in a retrieval system, or translated into any language in any form by any means without the written permission of the Partlow Corporation.
This is the First Edition of the MIC 1401 manual. It was written and produced entirely on a desk-top-publishing system. Disk versions are available by written request to the Partlow Publications Department.
We are glad you decided to open this manual. It is written so that you can take full advantage of the features of your new MIC 1401 limit controller.
MIC 1401 Manual Edition 1
2
Table of Contents
Section 1 - General Page
1.1 Product Description 5
Section 2 - Installation & Wiring
2.1 Installation & Wiring 7
2.2 Preparations for Wiring 9
2.3 Input Connections 15
2.4 Output Connections 17
Section 3 - Configuration & Operation
3.1 Operation 19
3.2 Configuration 24
Appendices
A - Glossary of Terms 30 B - Exploded View & Board Layout 34
Figure B-1 Exploded View 34 Figure B-2 Output 2/Output 3 Removal 35 Figure B-3 CPU PWA 36
Figure B-4 Option PWA DC Output 3 37 C - Hardware Definition Code 48 D - Input Range Codes 40 E - Specifications 42 F - Model Number Hardware Matrix 46 G - Software Reference Sheet 47
Edition 1
3
MIC 1401 Manual
Figures & Tables
Figure 1-1 Display Illustration 6 Figure 2-1 Panel Cut-Out Dimensions 8 Figure 2-2 Main Dimensions 8 Figure 2-3 Panel Mounting 9 Figure 2-4 Noise Suppression 12 Figure 2-5 Noise Suppression 12 Figure 2-6 Wiring 14 Figure 2-7 AC Power 15 Figure 2-8 Thermocouple Input 15 Figure 2-9 RTD Input 15 Figure 2-10 Volt, mV mADC Input 16 Figure 2-11 Remote Reset 16 Figure 2-12 Remote Digital Connections 17 Figure 2-13 Relay Output 1 17 Figure 2-14 Relay Output 2 17 Figure 2-15 Relay Output 3 18 Figure 2-16 mADC Output 3 18
Table 3-1 Enable Mode Configuration Procedures 25 Table 3-2 Program Mode Configuration Procedures 26 Table 3-3 Set-Up Mode Configuration Procedures 28
MIC 1401 Manual Edition 1
4
Product Description 1.1
1.1.1 GENERAL
This instrument is a microprocessor based single loop limit controller, user configurable to either High Limit type or Low Limit type.
The input is user configurable to directly connect to either thermocouple, RTD, mVDC, VDC or mADC inputs. The instrument can operate from a 90-264 VAC, 50/60 HZ power supply, or optional 24 V AC/DC power supply.
Features include fail safe operation (relay de-energized by the limit ex­ceeded condition), front panel Reset switch, time limit exceeded display and maximum/minimum tracking of excursions of the process variable.
1.1.2 DISPLAYS
Each instrument is provided with dual displays and status indicators as shown in Figure 1-1. The upper display displays the value of the process variable. The lower display displays the setpoint value. Status indication is as shown in Figure 1-1, page 6.
1.1.3 ALARMS
Alarm indication is standard on all instruments. Up to two alarm outputs are possible. Alarm type may be set as Process Direct or Reverse (high or low), Logical Combination of the two alarms and Annunciator Direct or Reverse. Alarm status is indicated by LED.
1.1.4 PROCESS VARIABLE/SETPOINT VALUE
RE-TRANSMISSION OUTPUT
If the instrument is specified with this option, this output may be scaled over any desired range and re-transmitted.
Edition 1
5
MIC 1401 Manual
FIGURE 1-1
Keys and Indicators
AUTO
MIC 1401 Manual Edition 1
6
Installation and Wiring 2.1
Electrical code requirements and safety standards should be observed and installation performed by qualified personnel.
The electronic components of the instrument may be removed from the housing during installation. To remove the components, grip the side edges of the front panel and pull the instrument forward. During re-installa­tion, the vertically mounted circuit boards should be properly aligned in the housing.
Ensure that the instrument is correctly orientated. A stop will operate if an attempt is made to insert the instrument incorrectly.
can be over-ridden with enough force. If in doubt, check orientation again!
Recommended panel opening sizes are illustrated in Figure 2-1, page 8. After the opening is properly cut, insert the instrument into the panel open­ing. Ensure that the panel gasket is not distorted and that the instrument is positioned squarely against the panel. Slide the mounting clamp into place on the instrument (see Figure 2-3, page 9) and push it forward until it is firmly in contact with the rear face of the mounting panel.
CAUTION: This stop
Note: The mounting clamp tongues may engage either on the sides or the top/bottom of the instrument housing. Therefore, when installing several instruments side-by-side in one cut out, use the ratchets on the top/bottom faces.
Edition 1
7
MIC 1401 Manual
FIGURE 2-1
Panel Cut-Out Dimensions
92 mm ± 0.8
(3.62”± .031)
FIGURE 2-2
Main Dimensions
PANEL CUTOUT SIZE
92 mm ± 0.8
(3.62”± .031)
100 mm (3.94 in.)
96 mm (3.78 in)
Side View
96 mm (3.78 in.)
MIC 1401 Manual Edition 1
8
10 mm (0.39 in.)
FIGURE 2-3
Panel Mounting the Controller
Mounting Clamp
Controller Housing
Tongues on mounting clamp engage in ratchet slots on controller housing
Preparation for Wiring 2.2
2.2.1 WIRING GUIDELINES
Electrical noise is a phenomenon typical of industrial environments. The following are guidelines that must be followed to minimize the effect of noise upon any instrumentation.
2.2.1.1 INSTALLATION CONSIDERATIONS
Listed below are some of the common sources of electrical noise in the industrial environment:
• Ignition Transformers
• Arc Welders
• Mechanical contact relay(s)
• Solenoids
Edition 1
9
MIC 1401 Manual
Before using any instrument near the device listed, the instructions below should be followed:
1. If the instrument is to be mounted in the same panel as any of the
listed devices, separate them by the largest distance possible. For
maximum electrical noise reduction, the noise generating devices
should be mounted in a separate enclosure.
2. If possible, eliminate mechanical contact relay(s) and replace with
solid state relays. If a mechanical relay being powered by an
instrument output device cannot be replaced, a solid state relay can
be used to isolate the instrument.
3. A separate isolation transformer to feed only instrumentation should
be considered. The transformer can isolate the instrument from noise
found on the AC power input.
4. If the instrument is being installed on existing equipment, the wiring in
the area should be checked to insure that good wiring practices have
been followed.
2.2.1.2 AC POWER WIRING
Neutral (For 115 VAC) It is good practice to assure that the AC neutral is at or near ground poten­tial. To verify this, a voltmeter check between neutral and ground should be done. On the AC range, the reading should not be more than 50 millivolts. If it is greater than this amount, the secondary of this AC transformer sup­plying the instrument should be checked by an electrician. A proper neutral will help ensure maximum performance from the instrument.
2.2.1.3 WIRE ISOLATION
Four voltage levels of input and output wiring may be used with the unit:
• Analog input or output (i.e. thermocouple, RTD, VDC, mVDC, or mADC)
• SPDT Relays
• AC power The only wires that should run together are those of the same category. If
they need to be run parallel with any of the other lines, maintain a minimum 6 inch space between the wires. If wires must cross each other, do so at 90 degrees. This will minimize the contact with each other and reduces “cross talk”.
MIC 1401 Manual Edition 1
10
“Cross Talk” is due to the EMF (Electro Magnetic Flux) emitted by a wire as current passes through it. This EMF can be picked up by other wires run­ning in the same bundle or conduit.
In applications where a High Voltage Transformer is used (i.e. ignition sys­tems) the secondary of the transformer should be isolated from all other cables.
This instrument has been designed to operate in noisy environments, how­ever, in some cases even with proper wiring it may be necessary to sup­press the noise at its source.
2.2.1.4 USE OF SHIELDED CABLE
Shielded cable helps eliminate electrical noise being induced on the wires. All analog signals should be run with shielded cable. Connection lead length should be kept as short as possible, keeping the wires protected by the shielding. The shield should be grounded at one end only. The pre­ferred grounding location is the sensor, transmitter or transducer.
2.2.1.5 NOISE SUPPRESSION AT THE SOURCE
Usually when good wiring practices are followed no further noise protection is necessary. Sometimes in severe electrical environments, the amount of noise is so great that it has to be suppressed at the source. Many manu­facturers of relays, contactors, etc. supply “surge suppressors” which mount on the noise source.
For those devices that do not have surge suppressors supplied, RC (resis­tance-capacitance) networks and/or MOV (metal oxide varistors) may be added.
Inductive Coils - MOV’s are recommended for transient suppression in inductive coils connected in parallel and as close as possible to the coil. See Figure 2-4, page 12. Additional protection may be provided by adding an RC network across the MOV.
Edition 1
11
MIC 1401 Manual
FIGURE 2-4
0.5 mfd 1000V
220
Coil
ohms
115V 1/4W 230V 1W
Contacts - Arcing may occur across contacts when the contact opens and closes. This results in electrical noise as well as damage to the contacts. Connecting a RC network properly sized can eliminate this arc.
For circuits up to 3 amps, a combination of a 47 ohm resistor and 0.1 microfarad capacitor (1000 volts) is recommended. For circuits from 3 to 5 amps, connect 2 of these in parallel. See Figure 2-5.
FIGURE 2-5
MOV
R C
Inductive Coil
MIC 1401 Manual Edition 1
12
2.2.2 SENSOR PLACEMENT (Thermocouple or RTD)
Two wire RTD’s should be used only with lead lengths less than 10 feet. If the temperature probe is to be subjected to corrosive or abrasive condi-
tions, it should be protected by the appropriate thermowell. The probe should be positioned to reflect true process temperature:
In liquid media - the most agitated area In air - the best circulated area
Edition 1
13
MIC 1401 Manual
FIGURE 2-6
Wiring Label
OUTPUT 3
Relay
+
INPUT
Linear (mA)
-
No external connections to be made to these terminals
-
­+
+
RTD
Linear (V/mV)
Thermocouple
N/C
SSR/DC
-
9 8 7 6 5 4 3
2 1
24
N/OC
+
11
1210
23 22
13 14 15 16
17 18 19
20 21
MAINS (LINE) SUPPLY
24V 24V
L
AC DC
N
B
RS485
A
COM
-
+
SERIAL COMMS.
N/C
C
SSR/DC
N/O
-
+
Relay
OUTPUT 1
+
SSR/DC
N/O
MIC 1401 Manual Edition 1
C
Relay
OUTPUT 2
14
-
N/C
Input Connections 2.3
In general, all wiring connections are made to the instrument after it is in­stalled. Avoid electrical shock. AC power wiring must not be connected to the source distribution panel until all wiring connection procedures are completed.
FIGURE 2-7
Main Supply Connect the AC line voltage, hot and neutral, to terminals 13 and 14 re­spectively as illustrated below. Connect the positive to terminal 14 and the negative to terminal 13 for 24 VDC supply.
-
13
14
L
N
+
FIGURE 2-8
Thermocouple (T/C) Input Make thermocouple connections as illustrated below. Connect the positive leg of the thermocouple to terminal 2 and the negative leg to terminal 3.
-
+
Thermocouple
FIGURE 2-9
RTD Input Make RTD connections as illustrated on page 16. For a three wire RTD, connect the resistive leg of the RTD to terminal 1 and the common legs to terminals 2 and 3. For a two wire RTD, connect one leg to terminal 2 and the other leg to terminal 1 as shown. A jumper wire supplied by the cus­tomer must be installed between terminals 3 and 2. Input conditioning jumper must be positioned correctly (see Appendix B) and Hardware Defini­tion Code must be correct (see Appendix C).
3
2
Edition 1
15
MIC 1401 Manual
Loading...
+ 35 hidden pages