Partlow MIC 1400 Operator's Manual

Page 1
MIC 1400
1/4 DIN MICROBASED CONTROLLER
OPERATORS MANUAL
FORM 3665 EDITION 1 © OCT. 1995 PRICE $10.00
Page 2
Information in this installation, wiring, and operation manual is subject to change without notice. One manual is provided with each instrument at the time of ship­ment. Extra copies are available at the price published on the front cover.
Copyright © Oct. 1995, The Partlow Corporation, all rights reserved. No part of this publication may be reproduced, transmitted, transcribed or stored in a retrieval system, or translated into any language in any form by any means without the written permission of the Partlow Corporation.
This is the First Edition of the MIC 1400 manual. It was written and produced entirely on a desk-top-publishing system. Disk versions are available by written request to the Partlow Publications Department.
We are glad you decided to open this manual. It is written so that you can take full advantage of the features of your new MIC 1400 process controller.
NOTE: It is strongly recommended that Partlow equipped applications incorporate a high or low limit protective device which will shut down the equipment at a preset process condition in order to preclude possible damage to property or products.
MIC 1400 Manual Edition 1
2
Page 3
Table of Contents
Section 1 - General Page
1.1 Product Description 5
Section 2 - Installation & Wiring
2.1 Installation & Wiring 7
2.2 Preparations for Wiring 9
2.3 Input Connections 14
2.4 Output Connections 16
Section 3 - Configuration & Operation
3.1 Operation 19
3.2 Configuration 24
3.3 Pre-Tune Mode 31
3.4 Auto-T une Mode 31
3.5 Manual T uning Method 32
Section 4 - Control Capability
4.1 Control Capability 34
4.2 Control Responses 34
4.3 Direct/Reverse Operation of Control Outputs 35
4.4 On-Off Control 35
4.5 Time Proportioning Control 36
4.6 Current Proportioning Control 37
4.7 Setpoint Adjustments 38
Appendices
A - Glossary of Terms 39
Figure A-1 Proportional Band & Deadband/Overlap 49
B - Board Layout - Jumper positioning 50
Figure B-1 PCB Positions 50 Figure B-2 Output 2/Output 3 Removal 51 Figure B-3 CPU PWA 52 Figure B-4 PSU PWA with Relay or SSR Out.1 53 Figure B-5 PSU PWA with DC Output 1 54 Figure B-6 Option PWA 55
(Continued on next page)
MIC 1400 ManualEdition 1 3
Page 4
Appendices cont.
C - Hardware Definition Code 56 D - Input Range Codes 58 E - Specifications 60 F - Model Number Hardware Matrix 66 G - Software Reference Sheet 67
Figures & Tables
Figure 1-1 Controller Display Illustration 6 Figure 2-1 Panel Cut-Out Dimensions 7 Figure 2-2 Main Dimensions 8 Figure 2-3 Panel Mounting the controller 8 Figure 2-4 Noise Suppression 1 1 Figure 2-5 Noise Suppression 12 Figure 2-6 Wiring Label 13 Figure 2-7 AC Power 14 Figure 2-8 Thermocouple Input 14 Figure 2-9 RTD Input 14 Figure 2-10 Volt, mV mADC Input 15 Figure 2-11 Remote Digital Connections 15 Figure 2-12 Relay Output 1 16 Figure 2-13 SSR Driver Output 1 16 Figure 2-14 mADC Output 1 16 Figure 2-15 Relay Output 2 17 Figure 2-16 SSR Driver Output 2 17 Figure 2-17 mADC Output 2 17 Figure 2-18 Relay Output 3 18 Figure 2-19 SSR Driver Output 3 18 Figure 2-20 mADC Output 3 18
Figure 4-1 Proportional Bandwidth Effect on Output 37 Table 3-1 Enable Mode Configuration Procedures 24
Table 3-2 Program Mode Configuration Procedures 25 Table 3-3 Tune Mode Configuration Procedures 27
MIC 1400 Manual Edition 1
4
Page 5
Product Description 1.1
1.1.1 GENERAL
This instrument is a microprocessor based single loop controller capable of measuring, displaying and controlling temperature, pressure, flow, and level from a variety of inputs. Most outputs are easily tuned using the instrument Pre-Tune and Auto-Tune functions.
Control functions, alarm settings and other parameters are easily entered through the front keypad. E data loss during AC power outages.
The input is user configurable to directly connect to either thermocouple, RTD, mVDC, VDC or mADC inputs. The instrument can operate from a 90-264 VAC, 50/60 HZ power supply, or optional 24V AC/DC power supply.
1.1.2 DISPLAYS
Each instrument is provided with dual displays and status indicators as shown in Figure 1-1. The upper display displays the value of the process variable. The lower display displays the setpoint value. Status indication is as shown, see Figure 1-1, page 6.
2
Technology (100 year life) protects against
1.1.3 CONTROL
The instrument can be programmed for on-off, time proportioning, or cur­rent proportioning control implementations depending on the model num­ber. A second control output is an available option. Proportional control implementations are provided with fully programmable PID parameters.
1.1.4 ALARMS
Alarm indication is standard on all instruments. Up to two alarm outputs are possible. Alarm type may be set as Process Direct or Reverse (high or low), Deviation Direct or Reverse (above or below setpoint), Deviation Band Type (closed or open within band), or Loop Reverse or Direct. Alarm status is indicated by LED.
MIC 1400 ManualEdition 1 5
Page 6
FIGURE 1-1
Keys and Indicators
AUTO
1.1.5 PROCESS VARIABLE/SETPOINT VALUE RE-TRANSMISSION OUTPUT
If the instrument is specified with this option, this output may be scaled over any desired range and re-transmitted.
MIC 1400 Manual Edition 1
6
Page 7
Installation and Wiring 2.1
Electrical code requirements and safety standards should be observed and installation performed by qualified personnel.
The electronic components of the instrument may be removed from the housing during installation. To remove the components, grip the side edges of the front panel and pull the instrument forward. During re-installa­tion, the vertically mounted circuit boards should be properly aligned in the housing.
Ensure that the instrument is correctly orientated. A stop will operate if an attempt is made to insert the instrument incorrectly.
Recommended panel opening sizes are illustrated in Figure 2-1. After the opening is properly cut, insert the instrument into the panel opening. En­sure that the panel gasket is not distorted and that the instrument is posi­tioned squarely against the panel. Slide the mounting clamp into place on the instrument (see Figure 2-3, page 8) and push it forward until it is firmly in contact with the rear face of the mounting panel.
Note: The mounting clamp tongues may engage either on the sides or the top/bottom of the instrument housing. Therefore, when installing several instruments side-by-side in one cut out, use the ratchets on the top/bottom faces.
92 mm ± 0.8
FIGURE 2-1
Panel Cut-Out Dimensions
(3.62”± .031)
PANEL CUTOUT
92 mm ± 0.8
(3.62”± .031)
SIZE
MIC 1400 ManualEdition 1 7
Page 8
FIGURE 2-2
Main Dimensions
100 mm (3.94 in.)
96 mm (3.78 in)
Side View
96 mm (3.78 in.)
FIGURE 2-3
Panel Mounting the Controller
Mounting Clamp
10 mm (0.39 in.)
Controller Housing
Tongues on mounting clamp engage in ratchet slots on controller housing
MIC 1400 Manual Edition 1
8
Page 9
Preparation for Wiring 2.2
2.2.1 WIRING GUIDELINES
Electrical noise is a phenomenon typical of industrial environments. The following are guidelines that must be followed to minimize the effect of noise upon any instrumentation.
2.2.1.1 INSTALLATION CONSIDERATIONS
Listed below are some of the common sources of electrical noise in the industrial environment:
• Ignition Transformers
• Arc Welders
• Mechanical contact relay(s)
• Solenoids Before using any instrument near the device listed, the instructions below
should be followed:
1. If the instrument is to be mounted in the same panel as any of the listed devices, separate them by the largest distance possible. For maximum electrical noise reduction, the noise generating devices should be mounted in a separate enclosure.
2. If possible, eliminate mechanical contact relay(s) and replace with solid state relays. If a mechanical relay being powered by an instrument output device cannot be replaced, a solid state relay can be used to isolate the instrument.
3. A separate isolation transformer to feed only instrumentation should be considered. The transformer can isolate the instrument from noise found on the AC power input.
4. If the instrument is being installed on existing equipment, the wiring in the area should be checked to insure that good wiring practices have been followed.
MIC 1400 ManualEdition 1 9
Page 10
2.2.1.2 AC POWER WIRING
Neutral (For 115 VAC) It is good practice to assure that the AC neutral is at or near ground poten­tial. To verify this, a voltmeter check between neutral and ground should be done. On the AC range, the reading should not be more than 50 millivolts. If it is greater than this amount, the secondary of this AC transformer sup­plying the instrument should be checked by an electrician. A proper neutral will help ensure maximum performance from the instrument.
2.2.1.3 WIRE ISOLATION
Four voltage levels of input and output wiring may be used with the unit:
• Analog input or output (i.e. thermocouple, RTD, VDC, mVDC, or mADC)
• SPDT Relays
• SSR driver outputs
• AC power
The only wires that should run together are those of the same category. If they need to be run parallel with any of the other lines, maintain a minimum 6 inch space between the wires. If wires must cross each other, do so at 90 degrees. This will minimize the contact with each other and reduces “cross talk”. “Cross Talk” is due to the EMF (Electro Magnetic Flux) emitted by a wire as current passes through it. This EMF can be picked up by other wires running in the same bundle or conduit.
In applications where a High Voltage Transformer is used (i.e. ignition sys­tems) the secondary of the transformer should be isolated from all other cables.
This instrument has been designed to operate in noisy environments, how­ever, in some cases even with proper wiring it may be necessary to sup­press the noise at its source.
2.2.1.4 USE OF SHIELDED CABLE
Shielded cable helps eliminate electrical noise being induced on the wires. All analog signals should be run with shielded cable. Connection lead length should be kept as short as possible, keeping the wires protected by the shielding. The shield should be grounded at one end only. The pre­ferred grounding location is the sensor, transmitter or transducer.
MIC 1400 Manual Edition 1
10
Page 11
2.2.1.5 NOISE SUPPRESSION AT THE SOURCE
Usually when good wiring practices are followed no further noise protection is necessary. Sometimes in severe electrical environments, the amount of noise is so great that it has to be suppressed at the source. Many manu­facturers of relays, contactors, etc. supply “surge suppressors” which mount on the noise source.
For those devices that do not have surge suppressors supplied, RC (resis­tance-capacitance) networks and/or MOV (metal oxide varistors) may be added.
Inductive Coils - MOV’s are recommended for transient suppression in inductive coils connected in parallel and as close as possible to the coil. See Figure 2-4. Additional protection may be provided by adding an RC network across the MOV.
FIGURE 2-4
0.5 mfd 1000V
220
Coil
ohms
115V 1/4W 230V 1W
Contacts - Arcing may occur across contacts when the contact opens and closes. This results in electrical noise as well as damage to the contacts. Connecting a RC network properly sized can eliminate this arc.
For circuits up to 3 amps, a combination of a 47 ohm resistor and 0.1 microfarad capacitor (1000 volts) is recommended. For circuits from 3 to 5 amps, connect 2 of these in parallel. See Figure 2-5, page 12.
MIC 1400 ManualEdition 1 11
Page 12
FIGURE 2-5
MOV
R C
Inductive Coil
2.2.2 SENSOR PLACEMENT (Thermocouple or RTD)
Two wire RTD’s should be used only with lead lengths less than 10 feet. If the temperature probe is to be subjected to corrosive or abrasive condi-
tions, it should be protected by the appropriate thermowell. The probe should be positioned to reflect true process temperature:
In liquid media - the most agitated area In air - the best circulated area
MIC 1400 Manual Edition 1
12
Page 13
FIGURE 2-6
Wiring Label
OUTPUT 3
Relay
+
INPUT
Linear (mA)
-
No external connections to be made to these terminals
-
­+
+
RTD
Linear (V/mV)
Thermocouple
N/C
SSR/DC
-
9 8 7 6 5 4 3
2 1
24
N/OC
+
11
1210
23 22
13 14 15 16
17 18 19
20 21
MAINS (LINE) SUPPLY
24V 24V
L
AC DC
N
B
RS485
A
COM
-
+
SERIAL COMMS.
N/C
C
SSR/DC
N/O
-
+
Relay
OUTPUT 1
+
SSR/DC
N/O
C
Relay
OUTPUT 2
-
N/C
MIC 1400 ManualEdition 1 13
Page 14
Input Connections 2.3
In general, all wiring connections are made to the instrument after it is installed. Avoid Electrical Shock. AC power wiring must not be connected to the source distribution panel until all wiring connection procedures are completed.
FIGURE 2-7
Main Supply Connect the AC line voltage, hot and neutral, to terminals 13 and 14 re­spectively as illustrated below. Connect the positive to terminal 14 and negative to terminal 13 for 24 V DC supply.
-
13
14
L
N
+
FIGURE 2-8
Thermocouple (T/C) Input Make thermocouple connections as illustrated below. Connect the positive leg of the thermocouple to terminal 2 and the negative leg to terminal 3.
-
+
Thermocouple
FIGURE 2-9
RTD Input Make RTD connections as illustrated below . For a three wire RTD, connect the resistive leg of the RTD to terminal 1 and the common legs to terminals 2 and 3. For a two wire RTD, connect one leg to terminal 2 and the other leg to terminal 3 as shown below. A jumper wire supplied by the customer must be installed between terminals 2 and 3. Input conditioning jumper must be positioned correctly (see Appendix B) and Hardware Definition Code must be correct (see Appendix C).
3
2
MIC 1400 Manual Edition 1
14
Page 15
3
2
RTD
1
FIGURE 2-10
V olt, mV Input Make volt and millivolt connections as shown below . Terminal 2 is positive and terminal 3 is negative. Input conditioning jumper must be positioned correctly (see Appendix B) and Hardware Definition Code must be correct (see Appendix C).
mADC Input Make mADC connections as shown below. Terminal 4 is positive and ter­minal 1 is negative. Input conditioning jumper must be positioned correctly (see Appendix B) and Hardware Definition Code must be correct (see Ap­pendix C).
+
-
+
Linear (mA)
-
Linear (V/mV)
FIGURE 2-11
Remote Digital Communications - RS485 Make digital communication connections as illustrated below .
4
3
2
1
16
17
B
A
18
COM
MIC 1400 ManualEdition 1 15
Page 16
Output Connections 2.4
FIGURE 2-12
Relay Output 1 Connections are made to Output 1 relay as illustrated below. The contacts are rated at 2 amp resistive, 120/240 V AC.
19
20
N/C
C
Relay
21
N/O
FIGURE 2-13
SSR Driver Output 1 Connections are made to Output 1 SSR Driver as illustrated below. The solid state relay driver is a non-isolated 0-4 VDC nominal signal. Output impedance is 250 ohms.
19
-
20
SSR
21
+
FIGURE 2-14
mADC Output 1 Make connections for DC Output 1 as illustrated below.
19
-
20
DC
21
MIC 1400 Manual Edition 1
16
+
Page 17
FIGURE 2-15
Relay Output 2 Connections are made to Output 2 relay as illustrated below. The contacts are rated at 2 amp resistive, 120/240 V AC.
24 23 22
N/O
FIGURE 2-16
SSR Driver Output 2 Connections are made to Output 2 SSR Driver as illustrated below. The solid state relay driver is a non-isolated 0-4 VDC nominal signal. Output impedance is 250 ohms.
24 23 22
+
FIGURE 2-17
mADC Output 2 Make connections for DC Output 2 as illustrated below.
C
Relay
SSR
N/C
-
24 23 22
+
DC
-
MIC 1400 ManualEdition 1 17
Page 18
FIGURE 2-18
Relay Output 3 Connections are made to Output 3 relay as illustrated below. The contacts are rated at 2 amp resistive, 120/240 VAC.
Relay
N/OCN/C
10 11 12
FIGURE 2-19
SSR Driver Output 3 Connections are made to Output 3 SSR Driver as illustrated below. The solid state relay driver is a non-isolated 0-4 VDC nominal signal. Output impedance is 250 ohms.
SSR
-
10 11 12
FIGURE 2-20
mADC Output 3 (Recorder Output Only) Make connections for DC output 3 as illustrated below.
DC
-
10 11 12
+
+
MIC 1400 Manual Edition 1
18
Page 19
Operation 3.1
3.1.1 POWER UP PROCEDURE
Verify all electrical connections have been properly made before applying power to the instrument.
If the instrument is being powered for the first time, it may be desirable to disconnect the controller output connections. The instrument will be into control following the power up sequence and the output(s) may turn ON. During power up, a self-test procedure is initiated during which all LED segments in the two front panel displays appear and all LED indicators are ON. When the self-test procedure is complete, the instrument reverts to normal operation.
Note: A delay of about 3 seconds, when power is first applied, will be seen before the displays light up.
3.1.2 KEYPAD OPERATION
AUTO/MANUAL KEY This key is used to:
1. Enter the Auto/Manual mode and vice versa.
2. Used to activate the Auto Tune mode.
3. Used to confirm a change in the Program mode. SCROLL KEY
This key is used to:
1. Select adjustment of the ramping setpoint, if enabled.
2. Select a parameter to be viewed or adjusted.
3. Display enabled modes of operation.
4. Display a mode parameter value.
5. Advance display from a parameter value to the next parameter code.
6. Activate the Pre-tune mode.
7. With the DOWN key to view the current Hardware Definition Code setting.
MIC 1400 ManualEdition 1 19
Page 20
UP KEY This key is used to:
1. Increase the displayed parameter value.
2. Increase setpoint.
3. With the DOWN key to enter Pre and Auto Tune mode.
DOWN KEY This key is used to:
1. Decrease the displayed parameter value.
2. Decrease setpoint.
3. With the UP key to enter the Pre and Auto Tune mode.
4. With the SCROLL key to view the current Hardware Definition Code setting.
3.1.3 DISPLAYS
During configuration the upper display shows the parameter setting. The lower display shows the parameter code for the currently selected param­eter. During operation, the upper display shows the value of the process variable. The lower display shows the setpoint value.
3.1.3.1 ALARM STATUS DISPLAY*
The user may view the status of the instrument's alarm(s) by depressing the SCROLL key until the lower display shows the legend "ALSt" and the upper display shows the alarm status in the following format:
Loop Alarm Status L = Energized Blank = De-energized
Alarm 1 Status 1 = Energized Blank = De-energized
Alarm 2 Status 2 = Energized Blank = De-energized
*This display is available only if one or more of the alarms is/are energized. When "ALSt" is seen in the lower display, to enter the Program or T une
modes, press the UP key with "ALSt" displayed, then the SCROLL key to Program or T une.
MIC 1400 Manual Edition 1
20
Page 21
3.1.3.2 OVER-RANGE/UNDER-RANGE DISPLA Y
If the process variable attains a value higher than the input scale maximum limit, the upper display will show:
If the process variable attains a value lower than the input scale minimum, the upper display will show:
If a break is detected in the sensor circuit, the upper display will show:
3.1.4 FRONT PANEL INDICATORS
OP1 Indicates the state of the Output 1 relay or SSR driver. When the
indicator is ON the relay is energized or the SSR driver is ON.
OP2 Indicates the state of the Output 2 relay or SSR driver. When the
indicator is ON the relay is energized or the SSR driver is ON.
ALM When flashing, indicates an Alarm condition. MAN Flashes when the Manual mode has been entered AT Indicates when the Pre-Tune mode or Auto-Tune mode has been
selected; flashing for Pre-Tune and continuously ON for Auto-Tune.
3.1.5 SETPOINT ADJUSTMENT
3.1.5.1 LOCAL SETPOINT
To adjust the instrument setpoint, proceed as follows:
MIC 1400 ManualEdition 1 21
Page 22
To adjust the Setpoint, press the UP or DOWN key as applicable. Momentary depression will increment or decrement (as appropriate) the setpoint by one unit in the least significant digit. If the key is held for longer than 1 second, the least significant digit will change at the rate of 25 units per second. If the key is held for longer than 10 seconds, the second least significant digit will change at the rate of 25 units per second. If the key is held for more than 10 seconds, the third least significant digit will change at the rate of 25 units per second.
3.1.5.2 RAMPING SETPOINT
A selectable Ramp Rate function in the range of 1 to 9999 units per hour can be used to limit the rate at which the setpoint used by the control algo­rithm will change. This feature will also establish a soft start up. Upon power up, the instrument will take the initial process value as the setpoint. A setpoint ramp rate will be calculated to increase the setpoint from the initial process value to the setpoint selected. The setpoint ramp feature disables the Pre-Tune facility. The Auto-Tune facility, if selected, will com­mence only after the setpoint has completed the ramp.
Sudden changes in the setpoint value entered via the keypad can be inhib­ited from effecting the control outputs by use of this feature. The internal setpoint used to control the process will ramp to the setpoint value entered at the rate of change selected.
To view the Ramping Setpoint value while in the Control mode and "ESPr" in the Tune mode is disabled, press the SCROLL key until "SPrP" is dis­played in the lower display. This is the code for the ramping setpoint value. Press the SCROLL key one more time and the lower display shows "SPrP" and the upper display will show the current ramping setpoint.
SPRr not OFF and ESPr equal to 0
PV BLANK Ramping SP PV *SP SPrP SPrP *SP
If ESPr is enabled, the display sequence changes to:
PV BLANK Ramping SP BLANK *Ramp Rate PV *SP SPrP SPrP SPrr SPrr *SP
*Adjustable
MIC 1400 Manual Edition 1
22
Page 23
To enter the Program or Tune mode when setpoint ramping is selected, press the SCROLL key until the lower display shows "SPrP" or "SPrr" and the upper display is blank. With "SPrP" or "SPrr" display in the lower dis­play, press the UP key once and "CtrL should be displayed in the lower display. With "CtrL" displayed, press the SCROLL key until "Prog" or "tunE" is displayed in the lower display.
Setpoint Ramp
205 204
Setpoint in Degrees
203 202
201 200
0
Time in Hours
5
10
3.1.6 MANUAL CONTROL
Manual Control is not applicable if the Auto/Manual selection in Tune mode is disabled.
To enter the Manual mode, press the AUTO/MANUAL key. The Manual mode status LED will begin to flash indicating that the Manual mode is in use. Shifting from the Control to the Manual mode is bumpless. The pro­portional output(s) will stay at the last value(s) calculated by the control algorithm. The upper display will show the current process value. The lower display will show the current value output power in the form PXXX where X is equal to the percentage of output power. The value of output power may be adjusted using the UP and DOWN keys, as required.
The output power value can be varied in the range 0% of 100% for instru­ments using Output 1 only, and -100% to +100 % for instruments with both Output 1 and Output 2.
To exit from the Manual mode, press the Auto/Manual key. Shifting to the Control mode is bumpless.
MIC 1400 ManualEdition 1 23
Page 24
Configuration 3.2
All configurable parameters are provided in Tables 3-1 through 3-3 on the following pages. These tables illustrate the display sequence, parameter adjustment and factory setting for each step.
Depression of the SCROLL key will cycle the display if Setpoint Ramp Rate is not enabled (top display is blank, lower display shows the parameter code) through all enabled modes as follows:
CONTROL ---- PROGRAM ---- TUNE (Ctrl) (Prog) (tunE)
If a mode is not enabled it will be skipped over by the routine.
3.2.1 ENABLE MODE
The Enable mode provides a means of enabling or disabling access to the Program and Tune modes. If a mode has been disabled, then that mode will not be displayed or available to the user in the Control mode. See Table 3-1 (page 24-25) for the Enable Mode procedure.
3.2.2 PROGRAM MODE
The Program mode is used to configure or re-configure the instrument. The input and output selections are made in the Program mode. All pos­sible parameters are illustrated in Table 3-2 (page 25). Only those param­eters that are applicable to the hardware options chosen will be displayed.
3.2.3 TUNE MODE
The Tune mode is used to adjust the tuning parameters, alarm settings, setpoint limits, and retransmit scaling needed for proper operation of the instrument. See Table 3-3 (page 27) for Tune mode. Only those param­eters that are applicable will be displayed.
TABLE 3-1 ENABLE MODE
To enter the Enable mode, press and hold the UP and DOWN keys. After 5 seconds (the AT LED should have flashed once), the display returns to normal. After 5 more seconds, "EnAb" will be displayed. Release the keys, the display should show "EPro". Pressing the DOWN key will display the Enable mode codes in the following sequence:
MIC 1400 Manual Edition 1
EPro - - Etun - - ESPC
24
Page 25
Pressing the SCROLL key will display the Enable mode codes with the upper display blank. The next depression of the SCROLL key will add the Enable code status (ON or OFF) to the upper display. With the Enable code status displayed, use the UP key to change the status to ON and the DOWN key to change the status to OFF.
To exit the Enable mode, press the UP key with the Enable code displayed in the lower display and the upper display blank.
DISPLAY AVAILABLE FACTORY STEP DESCRIPTION CODE SETTINGS SETTING 1 Program Mode EPro ON/OFF ON 2 Tune Mode Etun ON/OFF ON 3 Setpoint ESPC ON/OFF ON
Changes
TABLE 3-2 PROGRAM MODE
To enter the Program mode, press and release the SCROLL key until "Prog" is displayed. Use the DOWN key to enter the Program mode. De­press and release the SCROLL key to sequence through the parameters and their values, alternately showing the parameter code in the lower dis­play with the upper display blank, then the parameter code with the param­eter value displayed. Use the UP and DOWN keys to adjust the parameter values. After adjusting a parameter, the upper display will flash, indicating that the new setting has yet to be confirmed. When the setting is as re­quired, it may be confirmed by pressing the AUTO/MANUAL key and the upper display stops flashing. After confirming a change, press the SCROLL key to proceed to the next parameter. Use the DOWN key to advance to the next parameter when a parameter code is showing in the lower display and the upper display is blank.
To exit the Program mode, press the UP key whenever a parameter code is displayed in the lower display and the upper display is blank.
DEFAULT PARAMETER INDICATION If a parameter value, such as Input Select, was changed while in the Pro­gram mode, when returning to the Control mode, a decimal point after each digit will be lit. This display indicates all Tune mode parameters have been set to their default condition. To clear this condition, enter the T une mode and make a parameter value change and review each parameter for its proper setting.
MIC 1400 ManualEdition 1 25
Page 26
DISPLAY AVAILABLE FACTORY
STEP DESCRIPTION CODE SETTINGS SETTING 1 Input Select inPS See App. D* 1420 2 Output 1 Action Out1 Reverse REV
Direct
3 Alarm 1 Type ALA1 P_hi =Proc High P_hi
nonE=No Alarm bAnd=Band dE =Deviation P_Lo=Proc Low
4 Alarm 2 Type ALA2 Same selection as nonE
ALA1
5 Output 2 Usage USE2 Out2 =Control Out2
(opposite of Out1 action) LP_r =Loop Reverse LP_d=Loop Direct Ad_r =Rev Logic AND Ad_d=Dir Logic AND Or_r =Rev Logic OR Or_d =Dir Logic OR A2_r =Alm Rev A2_d=Alm Dir
6 Output 3 Usage USE3 Al_d =Alm Dir Al_d
7 Com Bit Rate CbS 1200, 2400, 4800, 4800
MIC 1400 Manual Edition 1
rEcP =Rcdr Out P.V. rEcS =Rcdr Out S.P. LP_r =Loop Reverse LP_d=Loop Direct Ad_r =Rev Logic AND Ad_d=Dir Logic AND Or_r =Rev Logic OR Or_d=Dir Logic OR Al_r =Alm Rev
9600
26
Page 27
DISPLAY AVAILABLE FACTORY STEP DESCRIPTION CODE SETTINGS SETTING
8 Com Address CAd 1 - 32 1 9 CJC Enable CJC EnAb EnAb
diSA
* The Hardware Definition Code and input jumper configuration may need to be changed. See Appendix B and C.
TABLE 3-3 TUNE MODE
To enter the Tune mode, press and release the SCROLL key until tunE is displayed. Use the DOWN key to enter the Tune mode. Depress and release the SCROLL key to sequence through the parameters and their values, alternately showing the parameter code in the lower display with the upper display blank, then the parameter code with the parameter value displayed. Use the UP and DOWN keys to adjust the parameter values. After adjusting a parameter, depress the SCROLL key to proceed to the next parameter. Use the DOWN key to advance to the next parameter when a parameter code is showing in the lower display and the upper dis­play is blank.
To exit the Tune mode, press the UP key whenever a parameter code is displayed in the lower display and the upper display is blank.
1 Ramping SPrP ± Setpoint Limits Read Only
Setpoint Value
2 Setpoint Ramp SPrr 1 to 9999 units/hour OFF
Rate and OFF
3 Input Filter Filt 0.0 to 100.0 2.0
seconds in .5 sec.
increments 4 Input Correct iCor ± Span 0 5 Output 1% Po1 0 to 100% Read Only
(Continued on next page)
MIC 1400 ManualEdition 1 27
Page 28
DISPLAY AVAILABLE FACTORY
STEP DESCRIPTION CODE SETTINGS SETTING 6 Output 2% Po2 0 to 100% Read Only
7 1st Output Pb1 0 to 999.9% 5.0
Prop. Band of Input Span
0%=On/OFF 8 2nd Output Pb2 0 to 999.9% 5.0
Prop. Band of Input Span
0%=ON/OFF 9 Automatic ArSt OFF to 99 mins. OFF
Reset 59 secs
10 Rate rAtE 0 sec to 99 mins. 0 secs.
59 secs. 11 Overlap/ SPrd -20 to 20% of 0%
Deadband Pb1 and Pb2
12 Manual Reset rSEt 0 to 100% Output 1 25%
-100 to 100% Out 2
13 Hysteresis
Output 1 HyS1 0.1 to 10.0% of span 0.5 Output 2 HyS2 0.1 to 10.0% of span 0.5 Out 1 & Out 2 HySt 0.1 to 10.0% of span 0.5
14 Setpoint SPuL Span Max. Span Max.
Upper Limit
15 Setpoint SPLL Span Min. Span Min.
Lower Limit
16 Process Pou -1999 to 9999 Span Max.
Output Upper
17 Process PoL -1999 to 9999 Span. Min.
Output Lower
MIC 1400 Manual Edition 1
28
Page 29
DISPLAY AVAILABLE FACTORY
STEP DESCRIPTION CODE SETTINGS SETTING 18 Output 1 o1PL 0 to 100% 100
% Limit
19 Output 1 Ct1 .5, 1, 2, 4, 8, 16, 32, 32
Cycle Time 64, 128, 256, 512
secs 20 Output 2 Ct2 .5, 1, 2, 4, 8, 16, 32, 32
Cycle Time 64, 128, 256, 512
secs 21 Process High PHA1 ± Span Span Max.
Alarm 1
22 Process Low PLA1 ± Span Span Min.
Alarm 1 23 Band Alarm 1 bAL1 0 to Span 5 24 Deviation dAL1 ± Span 5
Alarm 1 25 Process High PHA2 ± Span Span Max.
Alarm 2 26 Process Low PLA2 ± Span Span Min.
Alarm 2 27 Band Alarm 2 bAL2 0 to Span 5 28 Deviation dAL2 ± Span 5
Alarm 2 29 Loop Alarm LAEn 0=Disable 0
Enable 1=Enable 30 Loop Alarm LAti 1 sec to 99 mins. 99 mins.
Time 59 secs. 59 secs.
MIC 1400 ManualEdition 1 29
Page 30
DISPLAY AVAILABLE FACTORY
STEP DESCRIPTION CODE SETTINGS SETTING 31 Decimal dPoS 0, 1, 2, 3 1
Position (Linear Input Only) 32 Engineering Euu -1999 to 9999 1000
Units Upper 33 Engineering EuL -1999 to 9999 0
Units Lower 34 *Enable Pre EPtn 0=Disable 0
Tune 1=Enable 35 Enable Manual ESby 0=Disable 0
Control 1=Enable 36 **Setpoint Ramp ESPr 0=Disable 0
Rate Enable 1=Enable 37 Comm. Enable CCon 0=Disable 1
1=Enable
* Activates Pre-Tune on power-up when enabled. ** When enabled, allows user to change ramp rate without having to enter Tune mode.
MIC 1400 Manual Edition 1
30
Page 31
Pre-Tune Mode 3.3
The Pre-Tune mode may be used to set the instrument's PID parameters to values which are approximately correct, in order to provide a base from which the Auto Tune mode may optimize tuning.
To engage the Pre-Tune mode, with the instrument in Control mode, press and hold the UP and DOWN keys for approximately 5 seconds (the display will flash during this period) until the AT LED flashes once. Release the UP and DOWN keys. Press and hold the SCROLL key for approximately 3 seconds until the AT LED flashes.
To disengage the Pre-Tune mode, press and hold the UP and DOWN keys until the AT LED flashes once. Release the UP and DOWN keys. Press and hold the SCROLL key for approximately 3 seconds until the AT LED is continuously OFF.
Note: Since the Pre-Tune mode is a single-shot operation, it will auto­matically disengage itself once the operation is complete. If the En­able Pre-Tune parameter in the Tune mode is enabled, then a power interruption, the unit will first engage the Pre-Tune mode prior to en­gaging the Auto-Tune mode when power is restored.
Also note: The Pre-Tune mode will not engage during setpoint ramp­ing. Additionally, if the process variable is within 5% of input span from the setpoint, or if an incorrect key sequence is used, the Pre­Tune mode will not be engaged.
Auto-Tune Mode 3.4
The Auto-Tune mode is used to optimize tuning while the instrument is operating.
To engage the Auto-Tune mode, with the instrument in Control mode, press and hold the UP and DOWN keys for approximately 5 seconds (the display will flash during this period) until the AT LED flashes once. Release the UP and DOWN keys. Press and hold the AUTO/MAN key for approximately 3 seconds until the A T LED lights continuously.
MIC 1400 ManualEdition 1 31
Page 32
Note: If the Enable Pre-Tune parameter in the Tune mode is enabled, then on power-up, the unit will automatically engage the Pre-Tune mode prior to engaging the Auto-Tune mode when power is restored.
To disengage the Auto-Tune mode, press and hold the UP and DOWN keys until the AT LED flashes once. Release the UP and DOWN keys. Press and hold the AUTO/MAN key for approximately 3 seconds until the AT LED is continuously OFF.
Manual Tuning Method 3.5
1. Cycle Time - Time Proportioning Outputs
A. Adjusting the cycle time affects instrument operation
1. Shorter Cycle Time a. More accurate control b. Shorter life span of electromechanical components
2. Proportional Bandwidth A. Proportional Bandwidth is the inverse of gain. Increased Bandwidth = Decreased Gain B. Increase the Proportional Bandwidth if:
1. The process overshoots excessively
2. The process oscillates excessively
C. Decrease the Proportional Bandwidth if:
1. The process responds slowly
2. The process fails to reach setpoint
3. Add Automatic Reset A. Increase the Automatic Reset until the process becomes unstable, then decrease until stability is restored. B. Be sure to allow sufficient time for the process and the instrument to react.
4. Rate Adjustment A. Rate can cause process instability. Typically add Rate as 1/10 th of the automatic reset value. B. Decrease Rate if:
1. The process overshoots/undershoots
2. If the process oscillates excessively
MIC 1400 Manual Edition 1
32
Page 33
5. Manual Reset A. After making all other adjustments, use if an offset exists between the setpoint and the process variable. B. If the process is:
1. Below setpoint use a positive Manual Reset value
2. Above the setpoint use a negative Manual Reset value
MIC 1400 ManualEdition 1 33
Page 34
Control Capability 4.1
A variety of user programmable control features and capabilities are avail­able including:
• Auto Tune • Single On-Off Control
• Alarm Functions • Single Time Proportioning Control
• Auto/Manual Switching • Single Current Proportioning
• Process Retransmission • Dual On-Off Control
• Setpoint Retransmission • Dual Time Proportioning
• Setpoint Ramp Rate • Dual Current Proportioning
• Proportioning (Time or Current)/
On-Off Control The capabilities available in a specific unit are dependent upon the hard-
ware options specified when the instrument is ordered. Refer to Appendix F for the decoding of the instrument model number. Current proportioning control cannot be implemented if a current output was not ordered. The available output types and quantity of each are as follows:
Type of Output Quantity Available
• SPDT mechanical relay output Up to three
• SSR Driver Up to three
• mADC current output Up to two
Control Responses 4.2
Each instrument may be configured to provide 3 mode proportional control. Proportional control is provided with Proportional Band, Integration, and Derivative responses. The PID parameters are defined as follows:
Out 1 Out2 P (Proportional) Proportional Band Pb1 Pb2 I (Integration) Automatic Reset ArSt ArSt D (Derivative) Rate rAtE rAtE
Manual Reset is provided for use in lieu of, or in conjunction with automatic reset. A cycle time adjustment parameter is provided for use with each time proportioning control output.
MIC 1400 Manual
Edition 134
Page 35
Direct/Reverse Operation of Outputs 4.3
Direct operation is typically used with cooling applications. On-Off direct output(s) will turn on when the process variable exceeds setpoint. Propor­tional direct output(s) will increase the percentage of output as the process value increases within the proportional band.
Reverse operation is typically used with heating applications. On-Off re­verse output(s) will turn off when the process variable exceeds setpoint. Proportional reverse output(s) will decrease the percentage of output as the process value increases within the proportional band.
Output 2 will be Direct when Output 1 is selected as Reverse and Reverse when Output 1 is selected as Direct.
On-Off Control 4.4
On-Off control can be implemented with SPDT relay or SSR driver output(s) by setting the corresponding proportional band (Pb) to 0.0. On­Off operation can be assigned to Output 1 only (Output 2 not present), Output 1 AND Output 2, or Output 2 only (Output 1 is time proportional or current proportional). A hysteresis adjustment is provided for On-Off out­puts, "HyS1" for Output 1 only, "HySt" for Output 1 AND Output 2, or "HyS2" for Output 2 only. This adjustment is in % of input span and defines the bandwidth of the hysteresis. Relay chatter can be eliminated by proper adjustment of this parameter . When operating in On-Off control, the output(s) will turn on or off depending upon the setpoint, the process value, and the hysteresis adjustment.
MIC 1400 ManualEdition 1 35
Page 36
Time Proportioning Control 4.5
Time Proportioning control can be implemented with a SPDT relay or SSR driver. Time proportioning control can be selected for either Output 1 or Output 1 and Output 2, depending on hardware configuration. Time pro­portioning control is accomplished by cycling the output on and off during a prescribed period of time when the process variable is within the propor­tional band.
Ex: Calculated output % = 40%; Cycle time adjustment = 32 seconds
Output on time = .4 x 32 = 12.8 seconds Output off time = .6 x 32 = 19.2 seconds
When the unit is operating in the Control mode, the control algorithm deter­mines the output % required to correct for any difference between the pro­cess value and the setpoint. The output calculation is affected by Tune mode parameter adjustments. See Figure 4-1 (page 37) for proportional bandwidth effect on the output.
MIC 1400 Manual
Edition 136
Page 37
Current Proportioning Control 4.6
Current Proportioning control can be implemented on units provided with mADC current output(s). Current Proportioning control provides a 4 to 20mADC or 0-20mADC output in response to process value and setpoint. As with Time proportioning, the calculated output % for Current proportion­ing is affected by the Tune mode parameter adjustments.
See Figure 4-1 (below) for proportional bandwidth effect on the output.
FIGURE 4-1
Proportional Band 1
Pb1
Output 1
Output 2
Setpoint
Output Power (%)
Proportional
Band 1
Pb1
Output 1
Output 2
Output Power (%)
Setpoint
Proportional
Band 1
Output 1
Pb1
Proportional Band 2
Pb2
Overlap
(Positive value)
SPrd
Deadband
(negative value)
SPrd
Proportional Band 2
Output 2
Output 1
Process Variable
Proportional
Band 2
Pb2
Output 2
Output 1
Process Variable
Pb2 = 0
Output 2
Output 2
Output Power (%)
Positive values Negative values
Setpoint
Overlap/Deadband
Sprd
Output 2 OFF
Output 2 ON
Output 1
Process Variable
ON/OFF
Differential
HyS2
MIC 1400 ManualEdition 1 37
Page 38
Setpoint Adjustment 4.7
To adjust the setpoint with the instrument in the Control mode, press the UP key to raise the setpoint and the DOWN key to lower the setpoint.
Depressing the SCROLL key, if setpoint ramping is enabled and if ramp rate is not OFF will change the displays to:
Upper Display = Ramping Setpoint Value (Read Only) Lower Display = SPrP
MIC 1400 Manual
Edition 138
Page 39
Appendix A Glossary of Terms
Input Filter Time Constant
This parameter is used to filter out any extraneous impulses on the process variable. This filtered PV is used for all PV-dependent functions (control, alarm, etc). The time constant is adjustable from 0.0 seconds (of f) to 100.0 seconds, in 0.5 second increments. Default value is 2.0 seconds. Display code is FiLt.
Input Correction
This parameter is used to modify the actual process variable and is adjust­able in the range ± input span. Default value is 0. Display code is iCor.
Proportional Band 1
This parameter is the portion of the input span over which the Output 1 power level is proportional to the displayed process variable value. It may be adjusted in the range 0.0% (ON/OFF) to 999.9%. Default value is 5.0%. Display code is Pb1. The function is illustrated in Figure A-1, page 49.
Proportional Band 2
This parameter is the portion of the input span over which the Output 2 power level is proportional to the displayed process variable value. It may be adjusted in the range 0.0% (ON/OFF) to 999.9%. Default value is 5.0%. Display code is Pb2. In Figure A-1 (page 49), Proportional Band 2 is shown (a) with a nonzero value (Case 1 and Case 2) - PID Control, and (b) with a zero value (Case 3) - ON-OFF control.
Automatic Reset (Integral)
This parameter is used to bias the proportional output(s) to compensate for process load variations. It is adjustable in the range 1 second to 99 min­utes 59 seconds per repeat and OFF (value greater than 99 minutes 59 seconds). Decreasing the time increases the Reset. This parameter is not available if Pb1 is set to 0. Default value is OFF. Display code is ArSt.
MIC 1400 ManualEdition 1 39
Page 40
Rate (Derivative)
This parameter is adjustable in the range 00 seconds to 99 minutes 59 seconds and specifies how the control action responds to the rate of change in the process variable. This parameter is not available if Pb1 is set to 0. Default value is 0.0. Display code is rAtE.
Overlap/Deadband
This parameter defines the portion of the proportional band (Pb1 + Pb2) over which both outputs are active (or, in the case of a deadband, neither output is active ). It is adjustable in the range -20% to +20% (negative value = deadband). The function is illustrated in Figure A-1, page 49. This parameter is not applicable if Pb1 = 0 or if there is no Output 2. Default value is 0%. Display code is SPrd.
Note: With Output 2 set on ON/OFF (Figure A-1, page 50, Case 3) the Overlap/Deadband parameter has the effect of moving the ON hysteresis band of Output 2 to create an overlap (positive values) or a deadband (negative values). When Overlap/Deadband = 0, the Output 2 OFF edge of the Output 2 ON/OFF hysteresis band coincides with the point at which Output 1 = 0%.
Manual Reset
This parameter is expressed as a percentage of output power and is ad­justable in the range 0% to 100% (if only Output 1) or -100% to +100% (if both Output 1 and Output 2). This parameter is not applicable if Pb1 = 0. Default value is 25%. Display code is rSEt.
Hysteresis
This parameter is a switching differential used when one or both outputs have been set to ON/OFF. This parameter is adjustable within the range
0.1% to 10.0% of input span. Default value is 0.5%. Display code is HyS1, HyS2, HySt. Note: Alarm output hysteresis is fixed at 2° C/F.
Setpoint Upper Limit
This parameter is the maximum limit for setpoint adjustment. It should be set to a value which prevents the setpoint being given a value which will cause damage to the process. The range of adjustment is to Maximum Input Range. Default value is Range Maximum. Display code is SPuL.
MIC 1400 Manual
Edition 140
Page 41
Setpoint Lower Limit
This parameter is the minimum limit for setpoint adjustment. It should be set to a value which prevents the setpoint being given a value which will cause damage to the process. The range of adjustment is to Minimum Input Range. Default value is Range Minimum. Display code is SPLL.
Process Output Upper Value
This parameter defines the value of the retransmitted output (process vari­able or setpoint , whichever is applicable) at its maximum value; for ex­ample, for a 0-5V output, this value corresponds to 5V. It may be adjusted within the range -1999 to 9999. The decimal position is always the same as that for the process variable input. Default value is Input Range Maxi­mum. Display code is Pou.
Note: If this parameter is set to a value less than that for the Process Out­put Lower Value, the relationship between the process variable/setpoint value and the retransmission output is reversed.
Process Output Lower Value
This parameter defines the value of the retransmitted output (process vari­able or setpoint, whichever is applicable) at its minimum value; for ex­ample, for a 0-5V output, this value corresponds to 0 V. It may be adjusted within the range -1999 to 9999. The decimal position is always the same as that for the process variable input. Default value is Input Range Mini­mum. Display code is PoL.
Note: If this parameter is set to a value greater than that for the Process Output Upper Value, the relationship between the process variable/setpoint value and the retransmission output is reversed.
Output 1 Percent Limit
This parameter is used to limit the power level of Output 1 and may be used to protect the process being controlled. It may be adjusted between 0 % and 100%. This parameter is not applicable if Pb1 = 0. Display code is o1PL.
Cycle Time
This parameter is used to select the on/off cycle time for time proportioning outputs (Ct1 for Output 1 and Ct2 for Output 2). The permitted range of value is 0.5, 1, 2, 4, 8, 16, 32, 64, 128, 256, or 512 seconds. Default value is 32. Display codes Ct1 & Ct2.
MIC 1400 ManualEdition 1 41
Page 42
Process High Alarm 1 Value
This parameter, applicable only when Alarm 1 is selected to be a Process High alarm, defines the process variable value at or above which Alarm 1 will be active. Its value may be adjusted between Input Range Maximum and Input Range Minimum. Its default value is Input Range Maximum. Display code is PHA1.
Process Low Alarm 1 Value
This parameter, applicable only when Alarm 1 is selected to be a Process Low alarm, defines the process variable value at or below which Alarm 1 will be active. Its value may be adjusted between Input Range Maximum and Input Range Minimum. Its default value is Input Range Minimum. Display code is PLA1.
Band Alarm 1 Value
This parameter, applicable only if Alarm 1 is selected to be a Band Alarm, defines a band of process variable values, centered on the setpoint value. If the process variable value is outside this band, the alarm will be active. This parameter may be adjusted from 0 to span from the setpoint. The default value is 5. The display code is bAL1.
Deviation Alarm 1 Value
This parameter, applicable only if Alarm 1 is selected to be a Deviation High/Low Alarm, defines a value above (positive value - Deviation High Alarm) or below (negative value - Deviation Low Alarm) the setpoint; if the process variable deviates from the setpoint by a margin greater than that defined by this parameter, Alarm 1 goes active. This parameter may be adjusted in the range ± span from setpoint. The default value is 5. Display code is dAL1.
Process High Alarm 2 Value
This parameter, applicable only when Alarm 2 is selected to be a Process High Alarm, defines the process variable value at or above which Alarm 2 will be active. Its value may be adjusted between Input Range Maximum and Input Range Minimum. Its default value is Input Range Maximum. Display code is PHA2.
MIC 1400 Manual
Edition 142
Page 43
Process Low Alarm 2 Value
This parameter, applicable only when Alarm 2 is selected to be a Process Low Alarm, defines the process variable value at or below which Alarm 2 will be active. Its value may be adjusted between Input Range Maximum and Input Range Minimum. Its default value is Input Range Minimum. Display code is PLA2.
Band Alarm 2 Value
This parameter, applicable only if Alarm 2 is selected to be a Band Alarm, defines a band of process variable values, centered on the setpoint value. If the process variable is outside this band, the alarm will be active. This parameter may be adjusted from 0 to span from the setpoint. The default value is 5. Display code is bAL2.
Deviation Alarm 2 Value
This parameter, applicable only if Alarm 2 is selected to be a Deviation High/Low Alarm, defines a value above (positive value - Deviation High Alarm) or below (negative value - Deviation Low Alarm) the setpoint; if the process variable deviates from the setpoint by a margin greater than that defined by this parameter, Alarm 2 goes active. This parameter may be adjusted in the range ± span from setpoint. The default value is 5. Display code is dAL2.
Process High Alarm
direct-acting
Process High Alarm
reverse-acting
Process Low Alarm
direct-acting
Process Low Alarm
reverse-acting
"ALM" Off Relay Off
"ALM" Off Relay On
"ALM" flashes
Relay On
"ALM" flashes
Relay Off
"ALM" flashes
Relay On
PV
ALARM POINT
"ALM" flashes
Relay Off
PV
ALARM POINT
"ALM" Off Relay Off
PV
ALARM POINT
"ALM" Off Relay On
PV
ALARM POINT
MIC 1400 ManualEdition 1 43
Page 44
Band Alarm
direct-acting
open within band
Band Alarm
reverse-acting
closed within band
"ALM" flashes
Relay On
"ALM" flashes
Relay Off
ALARM VALUE
"ALM" Off Relay Off
SP
ALARM VALUE
"ALM" Off Relay On
SP
"ALM" flashes
Relay On
PV
"ALM" flashes
Relay Off
PV
Deviation High Alarm
direct-acting
(positive value)
Deviation Low Alarm
direct-acting
(negative value)
Deviation High Alarm
reverse-acting
(positive value)
"ALM" Off
Relay Off
"ALM" flashes
Relay On
"ALM" Off
Relay Off
SP
ALARM POINT
SP
"ALM" flashes
Relay On
PV
ALARM POINT
"ALM" Off
Relay Off
PV
SP
"ALM" flashes
Relay Off
PV
ALARM POINT
Deviation Low Alarm
reverse-acting
(negative value)
MIC 1400 Manual
"ALM" flashes
Relay On
ALARM POINT
"ALM" Off
Relay Off
PV
SP
Edition 144
Page 45
Loop Alarm Enable
This parameter is the means by which the user can enable or disable the Loop Alarm. The Loop Alarm is a special alarm which detects faults in the control feedback loop by continuously monitoring process variable re­sponse to the control output(s).
The Loop Alarm, when enabled, repeatedly checks the control output(s) for being at the maximum or minimum limit. If an output is found to be at the limit, the Loop Alarm mode starts a timer; thereafter, if the high output has not caused the process variable to be corrected by a predetermined amount V after a time T has elapsed, the Loop Alarm goes active. Subse­quently, the Loop Alarm mode repeatedly checks the process variable and the control output(s). When the process variable starts to change value in the correct sense or when the output comes below the limit, the Loop Alarm is deactivated.
For PID control, the Loop Alarm Time T is always set to twice the value of the Auto Reset parameter. For ON/OFF control, the user defined value of the Loop Alarm Time Set Up parameter is used.
The value of V is dependent upon the input type: Deg C: 2°C or 2.0°C
Deg F: 3°F or 3.0°F Linear Range: 10 least significant display units
For single output instruments, the limits are 0% and Out 1 Max %. For dual output instruments, the limits are -100% and Out 1 Max %.
Notes:
1. Correct operation of the Loop Alarm depends upon reasonably accurate PID tuning.
2. The Loop Alarm is automatically disabled during Manual Control mode and during execution of the Pre-Tune mode. Upon exit from Manual mode or after completion of the Pre-Tune routine, the Loop Alarm is automatically re-enabled.
MIC 1400 ManualEdition 1 45
Page 46
Loop Alarm Time
When full ON/OFF control is selected and Loop Alarm is enabled, this pa­rameter determines the duration of the limit condition after which the Loop Alarm will be activated. It may be adjusted within the range of 1 second to 99 minutes 59 seconds. This parameter is omitted from the Tune mode display sequence if ON/OFF control is not selected or Loop Alarm is dis­abled. The default setting 99:59. Display code is LAti.
Logical Combination of Alarms
Two alarms may be combined logically to create an AND/OR situation. They may be configured for Reverse-acting or Direct-acting. Either Output 2 or Output 3 may be assigned as Logical Outputs.
Example:
Logical OR of Alarm 1 with Alarm 2
Direct-Acting Reverse-Acting AL1 OFF, Al2 OFF: Relay OFF AL1 OFF, Al2 OFF: Relay ON AL1 ON, Al2 OFF: Relay ON AL1 ON, Al2 OFF: Relay OFF AL1 OFF, Al2 ON: Relay ON AL1 OFF, Al2 ON: Relay OFF AL1 ON, Al2 ON: Relay ON AL1 ON, Al2 ON: Relay OFF
Logical AND of Alarm 1 with Alarm 2
Direct-Acting Reverse-Acting AL1 OFF, Al2 OFF: Relay OFF AL1 OFF, Al2 OFF: Relay ON AL1 ON, Al2 OFF: Relay OFF AL1 ON, Al2 OFF: Relay ON AL1 OFF, Al2 ON: Relay OFF AL1 OFF, Al2 ON: Relay ON AL1 ON, Al2 ON: Relay ON AL1 ON, Al2 ON: Relay OFF
MIC 1400 Manual
Edition 146
Page 47
Direct Logic OR
ASYMMETRICAL BAND ALARM
ALARM 1
VALUE
ALARM 2
VALUE
"ALM" flashes Relay On
ALARM 1 TYPE - Deviation ALARM 2 TYPE - Deviation
Reverse Logic OR
"ALM" flashes Relay Off
ALARM 1 TYPE - Deviation ALARM 2 TYPE - Deviation
"ALM" Off Relay Off
ALARM 2
VALUE
"ALM" Off Relay On
"ALM" flashes Relay On
PV
SP
ALARM 1
VALUE
"ALM" flashes Relay Off
PV
SP
Decimal Point
This parameter, applicable only if a linear input is specified, defines the position of the decimal point in values for the process variable, setpoint, alarm levels and retransmission outputs as follows:
Value Decimal Point Position 0 XXXX 1 XXX.X 2 XX.XX 3 X.XXX The default value is 0. Display code is dPoS.
MIC 1400 ManualEdition 1 47
Page 48
Engineering Units Upper
This parameter, applicable only if a linear input is specified, defines the scaled input value when the process variable input is at its maximum value. It is adjustable between -1999 to 9999. The default value is 1000. This parameter can be set to a value less than (but not equal to) Engineering Units Lower, in which case the sense of the input is reversed. Display code is Euu.
Engineering Units Lower
This parameter, applicable only if a linear input is specified, defines the scaled input value when the process variable input is at its minimum value. It is adjustable between -1999 and 9999. The default value is 0. This pa­rameter can be set to a value greater than (but not equal to) Engineering Units Upper, in which case the sense of the input is reversed. Display code is EuL.
Pre-Tune Enable/Disable
This parameter determines whether or not the instrument Pre-Tune mode is activated on power up or not (0=disabled, 1=enabled). Default is 0. Dis­play code is EPtn.
Manual Mode Enable/Disable
This parameter determines whether operator selection of manual control is enabled or disabled (0=disabled, 1=enabled). The default setting is 0. Display code is ESby.
Setpoint Ramp Enable/Disable
This parameter enables/disables use of the Setpoint Ramp feature (0=dis­abled, 1=enabled). The default setting is 0. Display code is ESPr.
Communications Enable
This parameter enables/disables the changing of parameter values via the RS485 communications link, if the Communications option is specified. Settings are 0=disabled and 1=enabled. Default setting is 0. Display code is CCon.
MIC 1400 Manual
Edition 148
Page 49
FIGURE A-1
Proportional Band & Deadband/Overlap
Case 1
Proportional Band 1
Pb1
Output Power (%)
Case 2
Output Power (%)
Case 3
Output 1
Output 2
Setpoint
Output 1
Output 2
Output 1
(Positive value)
Proportional
Band 1
Pb1
Setpoint
Proportional
Band 1
Pb1
Proportional Band 2
Pb2
Overlap
SPrd
Deadband
(negative value)
SPrd
Proportional Band 2
Process Variable
Proportional
Band 2
Process Variable
Pb2 = 0
Pb2
Output 2
Output 1
Output 2
Output 1
Output 2
Output 2
Output Power (%)
Output 2 OFF
Output 2 ON
Setpoint
Positive values Negative values
Overlap/Deadband
Sprd
Output 1
Process Variable
ON/OFF
Differential
HyS2
MIC 1400 ManualEdition 1 49
Page 50
Appendix B Board Layout - Jumper Positioning
FIGURE B-1 PCB POSITIONS
Front Panel (top edge)
Power Supply PCB
Output 3 Option PCB
(Relay, SSR or DC Output)
Output 3 Jumpers
(DC Output only)
RS485 Serial Communications Option PCB
CPU PCB
Output 2 Option PCB
(Relay, SSR of DC Output)
Output 2 Jumpers
(DC Output only)
MIC 1400 Manual
Edition 150
Page 51
FIGURE B-2 OUTPUT 2, OUTPUT 3 REMOVAL
Top of Front Panel
Output 3 Option PCB
CPU PCB
Tongues become dis-engaged
Power Supply PCB
Output 2 Option PCB
REAR VIEW OF
UNHOUSED
CONTROLLER
MIC 1400 ManualEdition 1 51
Page 52
FIGURE B-3 CPU PWA
LJ3 LJ2
LJ1
IC6
Input Type
RTD, DC (mV)
T/C
DC (mA)
DC (V)
LJ1, LJ2, LJ3
Jumper Position
None (parked)
LJ3
LJ2
LJ1
MIC 1400 Manual
Edition 152
Page 53
FIGURE B-4 PSU PWA WITH RELAY OR SSR OUPUT 1
TX1
Output Type
Relay
SSR
SK3
LJ4, LJ5
Jumper Position
LJ6
LJ7
LJ5 LJ4
LJ6, LJ7
Jumper Position
LJ6
LJ7
MIC 1400 ManualEdition 1 53
Page 54
FIGURE B-5 PSU PWA WITH DC OUTPUT 1
TX1
Output Type
DC (0-10V)
DC (0-20mA)
LJ8
SK3
LJ9
LJ8, LJ9
Jumper Position
LJ8
LJ9
DC (0-5V)
DC (4-20mA)
MIC 1400 Manual
LJ8
LJ9
Edition 154
Page 55
FIGURE B-6 OPTION PWA DC OUTPUT 2/OUTPUT 3
LJ9
LJ8
Output Type
DC (0-10V)
DC (0-20mA)
LJ8, LJ9
Jumper Position
LJ8
LJ9
DC (0-5V)
DC (4-20mA)
LJ8
LJ9
MIC 1400 ManualEdition 1 55
Page 56
Appendix C Hardware Definition Code
The Hardware Definition Code is used to represent the hardware installed (input type, Output 1 type, Output 2 type and Output 3 type); this must be compatible with the hardware actually installed. It can be accessed, with the instrument in Program mode, by simultaneously depressing the DOWN and SCROLL keys. The displays will show "XXXX" (where X represents any number) in the upper display and "dEFn" in the lower display, where:
the first (left-most) digit is input type:
1=RTD/Linear mV 2=Thermocouple 3=Linear DC mA 4=Linear DC V
the second digit is Output 1 type:
1=Relay 2=SSR 3=DC 0-10V 4=DC 0-20mA 5=DC 0-5V 7=DC 4-20mA
the third digit is Output 2 type:
0=Output 2 not installed 1=Relay (control or alarm 2) 2=SSR (control or alarm 2) 3=DC 0-10V (control only) 4=DC 0-20mA (control only) 5=DC 0-5V (control only) 7=DC 4-20mA (control only)
the fourth digit is Output 3 type:
0=Output 3 not installed 1=Relay (alarm 1 only) 2=SSR (alarm 1 only) 3=DC 0-10V (retransmit only) 4=DC 0-20mA (retransmit only)
MIC 1400 Manual
Edition 156
Page 57
5=DC 0-5V (retransmit only) 7=DC 4-20mA (retransmit only)
The displayed code may be incremented/decremented using the UP/ DOWN keys as required. The maximum setting available is 4777. For example, the code for a thermocouple input, DC 4-20mA Output 1and relay Output 3 would be 2701. When the code is first altered, the code display will flash, until the desired value is displayed and confirmed by pressing the Auto/Manual key.
While the Hardware Definition Code is displayed, depressing the SCROLL key will cause the display to change to:
nonE or r485 OPtn OPtn
Where nonE indicates the absence of the communications option and r485 indicates the presence of the communications option.
NOTE: It is essential that this code is changed whenever there is a change to the instrument's hardware configuration (change of input/output type, alarm/retransmit output added/removed etc.). The instrument's software depends upon this code to ensure that the instrument operates correctly.
To exit from the Hardware Definition Code display, depress the DOWN and SCROLL keys simultaneously.
MIC 1400 ManualEdition 1 57
Page 58
Appendix D Input Range Codes
The input ranges available (selectable via the front panel) are: For Thermocouple Inputs
INPUT DISPLAYED INPUT DISPLAYED
TYPE RANGE CODE TYPE RANGE CODE
R 0 - 1650°C 1127 K 0 - 760°C 1719 R 32 - 3002°F 1128 K 32 - 1400°F 1720 S 0 - 1649°C 1227 K 0 - 1373°C 1723 S 32 - 3000°F 1228 K 32 - 2503°F 1724 J 0.0 - 205.4°C 1415 L 0.0 - 205.7°C 1815 J 32.0 - 401.7°F 1416 L 32.0 - 402.3°F 1816 J 0 - 450°C 1417 L 0 - 450°C 1817 J 32 - 842°F 1418 L 32 - 842°F 1818 J 0 - 761°C 1419 L 0 - 762°C 1819 J 32 - 1402°F 1420 L 32 - 1404°F 1820 T -200 - 262°C 1525 B 212 - 3315°F 1934 T -328 - 504°F 1526 B 100 - 1824°C 1938 T 0.0 - 260.6°C 1541 T 32.0 - 501.1°F 1542
For RTD Inputs Note: Input conditioning jumper JU1 needs to be changed, see Appendix B.
INPUT DISPLAYED INPUT DISPLAYED RANGE CODE RANGE CODE
0 - 600°C 2221 0.0 - 100.9°C 2295 32 - 1112°F 2222 32.0 - 213.6°F 2296 32 - 572°F 2229 -200 - 206°C 2297
-101.0 - 100.0°C 2230 -328 - 403°F 2298
-149.8 - 212.0°F 2231 -101.0 - 300.5°C 7201 0 - 300°C 2251 -149.8 - 572.9°F 7202
MIC 1400 Manual
Edition 158
Page 59
For DC Inputs Note: Input conditioning jumper JU1 needs to be changed, see Appendix B. Also, the Hardware Definition Code for the input type must also be changed, see Appendix C.
INPUT DISPLAYED INPUT DISPLAYED RANGE CODE RANGE CODE
0 - 20mA 3413 0 - 5V 4445 4-20mA 3414 1 - 5V 4434 0 - 50mV 4443 0 - 10V 4446 10 - 50mV 4499 2 - 10V 4450
MIC 1400 ManualEdition 1 59
Page 60
Appendix E Specifications
INPUT SPECIFICATIONS
General Input Sample Rate: Four per second Input Resolution: 14 bits approximately Input Impedance: Greater than 100M ohm resistive
(except for DC mA and V inputs)
Isolation: Universal input isolated from all outputs
except SSR at 240 V AC.
Thermocouple Types: R, S, J, T, K, L and B Calibration: Complies with BS4937, NBS125 and IEC584. Sensor Break Protection: Break detected within 2 seconds. Control
outputs set to OFF (0% power); alarms operate as if the process variable has gone over-range.
RTD and DC mV Type and Connection: Three-wire Pt100 Calibration: Complies with BS1904 and DIN43760. Lead Compensation: Automatic Sensor Break Protection: Break detected within 2 seconds. Control
outputs set to OFF (0% power); alarms operate as if the process variable has gone under-range.
DC mA and DC V Scale Range Maximum: -1999 to 9999 Scale Range Minimum: -1999 to 9999 Minimum Span: 1 display LSD Sensor Break Protection: Applicable to 4-20mA, 1-5V, and 2-10V
ranges only. Break detected within 2 seconds. Control outputs set to OFF (0% power); alarms operate as if the process variable has gone under-range.
MIC 1400 Manual
Edition 160
Page 61
Output Specifications
Output 1
General Types Available: Relay (standard), SSR and DC as options.
Relay Contact Type: SPDT Rating: 2A resistive at 120/240V AC Lifetime: > 500,000 operations at rated voltage/current Isolation: Inherent
SSR Drive/TTL Drive Capability: SSR>4.2V DC into 1K ohm minimum Isolation: Not isolated from input or other SSR outputs.
DC Resolution: Eight bits in 250mS (10 bits in 1 second typical, >10
bits in >1 second typical). Update Rate: Every control algorithm execution Ranges: 0-20mA, 4-20mA, 0-10V, and 0-5V* Load Impedance: 0-20mA: 500 ohm maximum
4-20mA: 500 ohm maximum
0-10V: 500 ohm minimum
0-5V: 500 ohm minimum Isolation: Isolated from all other inputs and outputs.
*Changes between V and mA ranges also require JU movement.
OUTPUT 2
General Types Available: Relay, SSR and DC
Relay Contact Type: SPDT Rating: 2A resistive at 120/240V AC Lifetime: > 500,000 operations at rated voltage/current Isolation: Isolated from all other inputs and outputs
MIC 1400 ManualEdition 1 61
Page 62
SSR Drive/TTL Drive Capability: SSR>4.3V DC into 250 ohm minimum Isolation: Not isolated from input or other SSR outputs
DC Resolution: Eight bits in 250mS (10 bits in 1 second typical, >10
bits in >1 second typical) Update Rate: Every control algorithm execution Ranges: 0-10mA, 4-20mA, 0-10V, and 0-5V* Load Impedance: 0-20mA: 500 ohm maximum
4-20mA: 500 ohm maximum
0-10V: 500 ohm minimum
0-5V: 500 ohm minimum Isolation: Isolated from all other inputs and outputs
*Changes between V and mA ranges also require JU movement.
OUTPUT 3
General Types Available: Relay, SSR and DC linear (retransmit only)
Relay Contact Type: SPDT Rating: 2A resistive at 120/240V AC Lifetime: > 500,000 operations at rated voltage/current Isolation: Inherent
SSR Drive/TTL Drive Capability: SSR>4.3V DC into 250 ohm minimum Isolation: Not isolated from input or other SSR outputs
DC Resolution: Eight bits in 250mS (10 bits in 1 second typical, >10
bits in >1 second typical). Update Rate: Every control algorithm execution Ranges: 0-20mA, 4-20mA, 0-10V, and 0-5V* Load Impedance: 0-20mA: 500 ohm maximum
4-20mA: 500 ohm maximum
0-10V: 500 ohm minimum
0-5V: 500 ohm minimum
MIC 1400 Manual
Edition 162
Page 63
Isolation: Isolated from all other inputs and outputs. * Changes between V and mA ranges also require JU movement.
CONTROL SPECIFICATIONS
Auto Tune Types: Pre-Tune and Auto-Tune Proportional Bands: 0 (OFF), 0.5% - 999.9% of input span @ 0.1%
increments Auto Reset: 1s-99min 59s/repeat and OFF Rate: 0 (OFF) - 99min 59s Manual Reset: Adjustable in the range 0-100% of output power
(single output) or -100% to +100% of output power
(dual output) Deadband/Overlap: -20% to +20% of proportional band 1 + proportional
band 2 ON/OFF Hysteresis: 0.1% to 10.0% of input span (control relay only)
Alarm relay hysteresis is fixed at 2°C/F Auto/Manual Control: User-selectable with "bumpless" transfer into and
out of Manual control. Cycle Times: Selectable for 0.5s to 512s in binary steps Setpoint Range: Limited by Setpoint Upper and Setpoint Lower limits Setpoint Ramp: Ramp rate selectable 1-9999 LSDs per hour and
infinite. Number displayed is decimal point aligned
with selected range. Alarms
Maximum Number: Two "soft" alarms plus Loop Alarm Maximum # Outputs: Up to 2 outputs can be used for alarm purposes Combination Alarms: Logical OR or AND of alrms to an individual
hardware output is available.
PERFORMANCE
Reference Conditions Ambient Temperature: 20°C ± 2°C Relative Humidity: 60-70% Supply Voltage: 90-264V AC 50Hz ±1% Source Resistance: <10 ohm for T/C input Lead Resistance: <0.1 ohm/lead balanced (Pt100) Common Mode Rejection: >120dB at 50/60Hz giving negligible effect at up to
264V 50/60Hz
MIC 1400 ManualEdition 1 63
Page 64
Series Mode Rejection: >500% of span (at 50/60Hz) causes negligible effect
DC Linear Inputs Measurement Accuracy: ± 0.25% of span ± -1 LSD
Thermocouple Inputs Measurement Accuracy: ± 0.25% of span ± -1LSD
Note: Reduced performance with Type B T/C
between 100-600 °C (212 - 1112 °F) Linearization Accuracy: Better than ± 0.2°C any point, any 0.1°C range
(± 0.05°C typical). Better than ± 0.5°C any point,
any 1°C range. Cold Junction
Compensation: Better than ± 0.7°C RTD Inputs
Measurment Accuracy: ± 0.25% of span ± 1 LSD
Linearization Accuracy: Better than ± 0.2°C any point, any 0.1°C range
(± 0.05°C typical). Better than ± 0.5°C any point,
any 1°C range.
MIC 1400 Manual
Edition 164
Page 65
OPERATING CONDITIONS
Ambient Operating 0° to 55°C Temperature:
Ambient Storage -20° to 80°C Temperature:
Relative Humidity: 20% - 95% non-condensing Supply Voltage: 90 - 264VAC 50/60Hz (standard) Source Resistance: 1000 maximum (thermcouple) Lead Resistance: 50 per lead maximum balanced (Pt100)
PHYSICAL
Dimensions: 1/4 DIN front panel (96mm x 96mm) 3.94 inches
deep Mounting: Plug-in with panel mounting fixing strap.
Panel cut-out 92mm x 92mm. Terminals: Screw type (combination head) Weight: 16 ounces maximum Front Panel Sealing: NEMA4 type / IP65 Display Character Height: Top - .53", Bottom - .39" Power Consumption: 4 watts
MIC 1400 ManualEdition 1 65
Page 66
Appendix F Order Matrix
OUTPUT 1
1 Relay 2 SSRD 3 4-20 mA*
OUTPUT 2
0 None 1 Relay 2 SSRD 3 4-20 mA*
1 4 0 0
OUTPUT 3
0 None 1 Relay 2 SSRD 3 4-20 mA**
OPTIONS
0 None 1 RS-485
SUFFIX
(Blank) None 02 24V AC/DC
*For control output only ** For retransmission only
MIC 1400 Manual
Edition 166
Page 67
Appendix G Software Reference Sheet
HDW DEF OPTION
Program Mode
inPS Out1 ALA1 ALA2 USE2 USE3 CbS CAd CJC
Enable Mode
ENAB ON OFF EPro EtuN ESPC
(continued on next page)
MIC 1400 ManualEdition 1 67
Page 68
Tune Mode
SPrP SPrr Filt iCor Po1 Po2 Pb1 Pb2 ArSt rAtE SPrd rSEt HyS1 HyS2 HySt SPuL SPLL Pou PoL o1PL Ct1 Ct2
MIC 1400 Manual
Edition 168
Page 69
Tune Mode
PHA1 PLA1 bAL1 dAL1 PHA2 PLA2 bAL2 dAL2 LAEn LAti dPoS Euu EuL EPtn ESby ESPr CCon
MIC 1400 ManualEdition 1 69
Page 70
Warranty and Return Statement
These products are sold by The Partlow Corporation (Partlow) under the warranties set forth in the following para­graphs. Such warranties are extended only with respect to a purchase of these products, as new merchandise, directly from Partlow or from a Partlow distributor, representative or reseller, and are extended only to the first buyer thereof who purchases them other than for the purpose of resale.
Warranty
These products are warranted to be free from functional defects in materials and workmanship at the time the products leave the Partlow factory and to conform at that time to the specifications set forth in the relevant Partlow instruction manual or manuals, sheet or sheets, for such products for a period of two years.
THERE ARE NO EXPRESSED OR IMPLIED WARRANTIES WHICH EXTEND BEYOND THE WARRANTIES HEREIN AND ABOVE SET FORTH. PARTLOW MAKES NO WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE WITH RESPECT TO THE PRODUCTS.
Limitations
Partlow shall not be liable for any incidental damages, consequential damages, special damages, or any other damages, costs or expenses excepting only the cost or expense of repair or replacement as described above.
Products must be installed and maintained in accordance with Partlow instructions. Users are responsible for the suitability of the products to their application. There is no warranty against damage resulting from corrosion, misappli­cation, improper specifications or other operating condition beyond our control. Claims against carriers for damage in transit must be filed by the buyer.
This warranty is void if the purchaser uses non-factory approved replacement parts and supplies or if the purchaser attempts to repair the product themselves or through a third party without Partlow authorization.
Returns
Partlow’s sole and exclusive obligation and buyer’s sole and exclusive remedy under the above warranty is limited to repairing or replacing (at Partlow’s option), free of charge, the products which are reported in writing to Partlow at its main office indicated below.
Partlow is to be advised of return requests during normal business hours and such returns are to include a statement of the observed deficiency. The buyer shall pre-pay shipping charges for products returned and Partlow or its representative shall pay for the return of the products to the buyer.
Approved returns should be sent to: PARTLOW CORPORATION
2 CAMPION ROAD NEW HARTFORD, NY 13413 USA
MIC 1400 Manual
Edition 170
Page 71
THE PARTLOW-WEST COMPANY
2 CAMPION ROAD • NEW HARTFORD, NY 13413 USA
1-800-866-6659 • 315-797-2222 • FAX 315-797-0403
Loading...