Partlow MIC 1167, MIC 1407, MIC 1807 Operating Manual

MIC 1167/1807/1407
VALVE MOTOR DRIVER (VMD) CONTROLLERS
OPERATORS MANUAL
FORM 3719 EDITION 1 © SEPT. 1996 PRICE $10.00
Information in this installation, wiring, and operation manual is subject to change without notice. One manual is provided with each instrument at the time of ship­ment. Extra copies are available at the price published on the front cover.
Copyright © Sept. 1996, The Partlow Corporation, all rights reserved. No part of this publication may be reproduced, transmitted, transcribed or stored in a retrieval system, or translated into any language in any form by any means without the written permission of the Partlow Corporation.
This is the First Edition of the MIC 1167/1807/1407 manual. It was written and produced entirely on a desk-top-publishing system. Disk versions are available by written request to the Partlow Publications Department.
We are glad you decided to open this manual. It is written so that you can take full advantage of the features of your new MIC 1167/1807/1407 Valve Motor Drive controller.
NOTE: It is strongly recommended that Partlow equipped applications incorporate a high or low limit protective device which will shut down the equipment at a preset process condition in order to preclude possible damage to property or products.
!
THE INTERNATIONAL HAZARD SYMBOL IS INSCRIBED ADJACENT TO THE REAR CONNECTION TERMINALS. IT IS IMPOR TANT T O READ THIS MANUAL BEFORE INSTALLING OR COMMISSIONING THE UNIT.
MIC 1167/1807/1407 Manual Edition 12
Table of Contents
Section 1 - General Page
1.1 Product Description 5
Section 2 - Installation & Wiring
2.1 Installation & Wiring 8
2.2 Preparations for Wiring 12
2.3 Input Connections 19
2.4 Output Connections 23
Section 3 - Configuration & Operation
3.1 Operation 27
3.2 Configuration 33
3.3 Pre-Tune Mode 39
3.4 Auto-T une Mode 40
3.5 Manual T uning Method 41
Section 4 - Control Capability
4.1 Control Capability 43
4.2 Setpoint Adjustments 43
Appendices
A - Glossary of Terms 44 B - Board Layout - Jumper positioning 54
Figure B-1 PCB Positions 54 Figure B-2 Output 2/Output 3 Removal - 1/16 DIN 55 Figure B-3 Output 2/Output 3 Removal - 1/8 DIN 56 Figure B-4 Output 2/Output 3 Removal - 1/4 DIN 57 Figure B-5 CPU PWA 58
Figure B-6 Option PWA Output 3 59 C - Hardware Definition Code 60 D - Input Range Codes 62 E - Specifications 64 F - Model Number Hardware Matrix 70 G - Software Reference Sheet 71
3
MIC 1167/1407/1807 ManualEdition 1
Figures & Tables
Figure 1-1 Controller Display Illustration 6,7 Figure 2-1 Panel Cut-Out Dimensions 8,9 Figure 2-2 Main Dimensions 10,11 Figure 2-3 Panel Mounting the controller 12 Figure 2-4 Noise Suppression 14 Figure 2-5 Noise Suppression 15 Figure 2-6 Wiring Label 16, 17, 18 Figure 2-7 Main Power Supply 19 Figure 2-7A 24V Nominal AC/DC Supply 20 Figure 2-8 Thermocouple Input 21 Figure 2-9 RTD Input 21 Figure 2-10 Volt, mV mADC Input 22 Figure 2-11 Remote Digital Connections 22 Figure 2-12 Dual Setpoint Selection 23 Figure 2-13 Relay Output 1 & 2 23 Figure 2-14 Valve Relay 24 Figure 2-15 Relay Output 3 25 Figure 2-16 SSR Driver Output 3 25 Figure 2-17 mADC Output 3 25 Figure 2-18 24V DC Transmitter Power Supply 26
Figure 3-1 Manual Tuning Technique 42 Table 3-1 Enable Mode Configuration Procedures 33
Table 3-2 Program Mode Configuration Procedures 34 Table 3-3 Tune Mode Configuration Procedures 36
MIC 1167/1807/1407 Manual Edition 14
Product Description 1.1
1.1.1 GENERAL
This instrument is a microprocessor based process controller for use in open loop valve motor drive (VMD) applications. Its standard features include:
• Dual four-digit LED display
• Universal sensor input (thermocouple, 3 wire RTD or
DC Linear -mA, mV, V)
• Pre-Tune and Auto-T une
• 90 to 264V AC Power
• Designed to comply with EN50081 Part 2 (Emission) and EN50082
Part 2 (Immunity) EMC specifications
• Auto/Manual control - user selectable
• Setpoint Ramping
Some optional features:
• 24V AC/DC line voltage
• One alarm output or retransmission output
• RS-485 Communications
• 24V DC T ransmitter Power Supply
• Dual Setpoint
1.1.2 DISPLAYS
Each instrument is provided with dual displays and status indicators as shown in Figure 1-1. The upper display displays the value of the process variable. The lower display displays the setpoint value. Status indication is as shown, see Figure 1-1, page 6 & 7.
1.1.3 CONTROL
The instrument can be programmed for motor drive control only, with fully programmable PID parameters.
1.1.4 ALARMS
Alarm indication is standard on all instruments. One alarm output is pos­sible. Alarm type may be set as Process Direct or Reverse (high or low), Deviation Direct or Reverse (above or below setpoint), Deviation Band Type (closed or open within band), or Loop Reverse or Direct. Alarm status is indicated by LED.
5
MIC 1167/1407/1807 ManualEdition 1
FIGURE 1-1
Keys and Indicators
MIC 1167/1807/1407 Manual Edition 16
1.1.5 PROCESS VARIABLE/SETPOINT VALUE RETRANSMISSION OUTPUT
If the instrument is specified with this option, this output may be scaled over any desired range and retransmitted.
7
MIC 1167/1407/1807 ManualEdition 1
Installation and Wiring 2.1
Electrical code requirements and safety standards should be observed and installation performed by qualified personnel.
The electronic components of the instrument may be removed from the housing during installation. To remove the components, grip the side edges of the front panel and pull the instrument forward. During reinstallation, the vertically mounted circuit boards should be properly aligned in the housing.
Ensure that the instrument is correctly orientated. A stop will operate if an attempt is made to insert the instrument incorrectly.
Recommended panel opening sizes are illustrated in Figure 2-1. After the opening is properly cut, insert the instrument into the panel opening. En­sure that the panel gasket is not distorted and that the instrument is posi­tioned squarely against the panel. Slide the mounting clamp into place on the instrument (see Figure 2-3, page 11) and push it forward until it is firmly in contact with the rear face of the mounting panel.
Note: The mounting clamp tongues may engage either on the sides or the top/bottom of the instrument housing. Therefore, when installing several instruments side-by-side in one cut out, use the ratchets on the top/bottom faces.
FIGURE 2-1
Panel Cut-Out Dimensions
1/16 DIN
45 mm +0.5 - 0.00
(1.77”+.020 - .000)
PANEL
CUTOUT
45 mm +0.5 - 0.00
(1.77”+.020 - .000)
SIZE
MIC 1167/1807/1407 Manual Edition 18
1/8 DIN
45 mm +0.5 - 0.00
(1.77”+.020 - .000)
1/4 DIN
PANEL CUTOUT SIZE
92 mm +0.5 - 0.00
(3.62”+.020 - .000)
92 mm + 0.5 - 0.0
(3.62” + .020 - .000)
PANEL CUTOUT SIZE
92 mm + 0.5 - 0.0
(3.62” + .020 - .000)
9
MIC 1167/1407/1807 ManualEdition 1
FIGURE 2-2
Main Dimensions
1/16 DIN
48 mm (1.89 in.)
48 mm (1.89 in.)
110 mm (4.33 in.)
Side View
10 mm (0.39 in.) Note: Max. panel thickness 6.0 mm (.25 in.)
1/8 DIN
48 mm (1.89 in.)
100 mm (3.94 in.)
96 mm (3.78 in)
Side View
10 mm (0.39 in.) Note: Max. panel thickness 6.0 mm (.25 in)
MIC 1167/1807/1407 Manual Edition 110
1/4 DIN
96 mm (3.78 in.)
96 mm (3.78 in)
100 mm (3.94 in.)
Side View
10 mm (0.39 in.) Max. panel thickness
6.0 mm (.25 in.)
FIGURE 2-3
Panel Mounting the Controller
Mounting Clamp
Controller Housing
Tongues on mounting clamp engage in ratchet slots on controller housing
11
MIC 1167/1407/1807 ManualEdition 1
Preparation for Wiring 2.2
2.2.1 WIRING GUIDELINES
Electrical noise is a phenomenon typical of industrial environments. The following are guidelines that must be followed to minimize the effect of noise upon any instrumentation.
2.2.1.1 INST ALLA TION CONSIDERATIONS
Listed below are some of the common sources of electrical noise in the industrial environment:
• Ignition Transformers
• Arc Welders
• Mechanical contact relay(s)
• Solenoids Before using any instrument near the device listed, the instructions below
should be followed:
1. If the instrument is to be mounted in the same panel as any of the
listed devices, separate them by the largest distance possible. For
maximum electrical noise reduction, the noise generating devices
should be mounted in a separate enclosure.
2. If possible, eliminate mechanical contact relay(s) and replace with
solid state relays. If a mechanical relay being powered by an
instrument output device cannot be replaced, a solid state relay can
be used to isolate the instrument.
3. A separate isolation transformer to feed only instrumentation should
be considered. The transformer can isolate the instrument from noise
found on the AC power input.
4. If the instrument is being installed on existing equipment, the wiring in
the area should be checked to insure that good wiring practices have
been followed.
MIC 1167/1807/1407 Manual Edition 112
2.2.1.2 AC POWER WIRING
Neutral (For 115 VAC) It is good practice to assure that the AC neutral is at or near ground poten­tial. To verify this, a voltmeter check between neutral and ground should be done. On the AC range, the reading should not be more than 50 millivolts. If it is greater than this amount, the secondary of this AC transformer sup­plying the instrument should be checked by an electrician. A proper neutral will help ensure maximum performance from the instrument.
2.2.1.3 WIRE ISOLATION
Four voltage levels of input and output wiring may be used with the unit:
• Analog input or output (i.e. thermocouple, RTD, VDC, mVDC, or mADC)
• SPDT Relays
• SSR driver outputs
• AC power The only wires that should run together are those of the same category. If
they need to be run parallel with any of the other lines, maintain a minimum 6 inch space between the wires. If wires must cross each other, do so at 90 degrees. This will minimize the contact with each other and reduces “cross talk”. “Cross Talk” is due to the EMF (Electro Magnetic Flux) emitted by a wire as current passes through it. This EMF can be picked up by other wires running in the same bundle or conduit.
In applications where a High Voltage Transformer is used (i.e. ignition sys­tems) the secondary of the transformer should be isolated from all other cables.
This instrument has been designed to operate in noisy environments, how­ever, in some cases even with proper wiring it may be necessary to sup­press the noise at its source.
2.2.1.4 USE OF SHIELDED CABLE
Shielded cable helps eliminate electrical noise being induced on the wires. All analog signals should be run with shielded cable. Connection lead length should be kept as short as possible, keeping the wires protected by the shielding. The shield should be grounded at one end only. The pre­ferred grounding location is the sensor, transmitter or transducer.
13
MIC 1167/1407/1807 ManualEdition 1
2.2.1.5 NOISE SUPPRESSION AT THE SOURCE
Usually when good wiring practices are followed no further noise protection is necessary. Sometimes in severe electrical environments, the amount of noise is so great that it has to be suppressed at the source. Many manu­facturers of relays, contactors, etc. supply “surge suppressors” which mount on the noise source.
For those devices that do not have surge suppressors supplied, RC (resis­tance-capacitance) networks and/or MOV (metal oxide varistors) may be added.
Inductive Coils - MOV’s are recommended for transient suppression in inductive coils connected in parallel and as close as possible to the coil. See Figure 2-4. Additional protection may be provided by adding an RC network across the MOV.
FIGURE 2-4
0.5 mfd 1000V
220 ohms
115V 1/4W 230V 1W
Coil
MIC 1167/1807/1407 Manual Edition 114
Contacts - Arcing may occur across contacts when the contact opens and closes. This results in electrical noise as well as damage to the contacts. Connecting a RC network properly sized can eliminate this arc.
For circuits up to 3 amps, a combination of a 47 ohm resistor and 0.1 microfarad capacitor (1000 volts) is recommended. For circuits from 3 to 5 amps, connect 2 of these in parallel. See Figure 2-5, page 12.
FIGURE 2-5
MOV
R C
Inductive Coil
2.2.2 SENSOR PLACEMENT (Thermocouple or RTD)
Two wire RTD’s should be used only with lead lengths less than 10 feet. If the temperature probe is to be subjected to corrosive or abrasive condi-
tions, it should be protected by the appropriate thermowell. The probe should be positioned to reflect true process temperature:
In liquid media - the most agitated area In air - the best circulated area
15
MIC 1167/1407/1807 ManualEdition 1
FIGURE 2-6
Wiring Label
1/16 DIN
Output 3 is used either as Alarm 1 Output (Relay or SSRD only) or Retransmission Output (DC only)
OUTPUT 3
Relay
SSR/DC
-
16 17 18
OUTPUT 1
N/O
C
Relay
N/C
1
2
3
N/OCN/C
Top of controller
+
No external
7
connections to be made
8
to these terminals
L
9
-
+
INPUT
Linear (mA)
-
+
+
Linear (V/mV)
Thermocouple
RTD
4
5
6
-
-
Output 1 is normally used as the "Open Valve" output.
Output 2 is normally used as the "Close Valve" output.
13 14 15
N/O
C
Relay
OUTPUT 2
N/C
10
11
12
N
A
RS485 SERIAL COMMS.
B
MAINS
(LINE)
SUPPLY
+
24V AC
-
+
SUPPLY
24V DC
SUPPLY
DUAL SETPOINT SELECTION
MIC 1167/1807/1407 Manual Edition 116
1/8 DIN
Output 3 is used either as Alarm 1 Output (Relay or SSRD only) or Retransmission Output (DC only), or T ransmitter Power Supply
OUTPUT 3
Transmitter Power Supply
-
N/C
-
Relay
SSR/DC
11
+
N/OC
+
1210
+
-
­+
+
Linear (mA)
UNIVERSAL
INPUT
-
Linear (V/mV)
Thermocouple
Output 1 is normally used as the "Open Valve" output.
RTD
9 8 7 6 5 4 3
2 1
24
23 22
N/O
C
Relay
OUTPUT 2
N/C
13 14 15 16 17 18 19
20 21
L
N
B A
COM
N/C
C
N/O
MAINS
(LINE)
SUPPL Y
.
RS485
SERIAL
COMMS
Relay
-
+
24V AC
SUPPLY
24V DC
SUPPLY
+
-
DUAL SETPOINT SELECTION
OUTPUT 1
Output 2 is normally used as the "Close Valve" output.
17
MIC 1167/1407/1807 ManualEdition 1
1/4 DIN
Output 3 is used either as Alarm 1 Output (Relay or SSRD only) or Retransmission Output (DC only), or T ransmitter Power Supply
Transmitter Power Supply
OUTPUT 3
-
Relay
+
+
INPUT
Linear (mA)
-
No external connections to be made to these terminals
-
­+
+
RTD
Linear (V/mV)
Thermocouple
11
N/OC
+
1210
13
L
-
N/C
SSR/DC
-
9
+
8 7 6 5 4 3 2 1
24
23 22
14 15 16 17 18 19
20 21
N
MAINS
B
RS485 SERIAL COMMS.
A
COM
N/C
C
N/O
(LINE)
SUPPLY
+
-
Relay
OUTPUT 1
24V AC
SUPPLY
DUAL SET­POINT SELEC­TION
24V DC
SUPPLY
N/O
C
Relay
OUTPUT 2
Output 1 is normally used as the "Open Valve" output.
Output 2 is normally used as the "Close V alve" output.
MIC 1167/1807/1407 Manual Edition 118
N/C
Input Connections 2.3
In general, all wiring connections are made to the instrument after it is installed. Avoid Electrical Shock. AC power wiring must not be connected to the source distribution panel until all wiring connection procedures are completed.
Caution: This equipment is designed for installation in an enclosure which provide adequate protection against electric shock. Local regulations regarding electrical installation should be rigidly ob­served. Consideration should be given to prevention of access to the power terminations by unauthorized personnel. Power should be connected via a two pole isolating switch (preferably situated near the equipment) and a 1 A fuse, as shown in Figure 2-7, below.
FIGURE 2-7
Main Supply The instrument will operate on 90-264V AC 50/60 Hz mains (line) supply. The power consumption is approximately 4 VA. If the instrument has relay outputs in which the contacts are to carry mains (line) voltage, it is recom­mended that the relay contact mains (line) supply should be switched and fused in a similar manner but should be separate from the instrument mains (line) supply .
1/8 & 1/4 DIN
1/16 DIN
13
14
9
10
L
N
L
N
19
Line
Neutral
Line
Neutral
MIC 1167/1407/1807 ManualEdition 1
FIGURE 2-7A
4
5
-
+
Thermocouple
24V Nominal AC/DC Supply The supply connection for the 24V AC/DC option of the instrument are as shown below . Power should be connected via a two pole isolating switch and a 315 mA slow-blow (anti-surge Type T) fuse. With the 24V AC/DC supply option fitted, these terminals will accept the following supply voltage ranges:
24V (nominal) AC 50/60 Hz - 20-50V 24V (nominal) DC - 22-65V
1/8 & 1/4 DIN
L
13
14
N
24V AC 50/60Hz
-
24V DC
+
1/16 DIN
L
9
24V AC
N
10
FIGURE 2-8
Thermocouple (T/C) Input Make thermocouple connections as illustrated below. Connect the positive leg of the thermocouple to terminal 2 (1/8 & 1/4 DIN) or terminal 5 (1/16 DIN) and the negative leg to terminal 3 (1/8 & 1/4 DIN) or terminal 4 (1/16 DIN).
1/8 & 1/4 DIN
-
3
1/16 DIN
50/60Hz
-
24V DC
+
MIC 1167/1807/1407 Manual Edition 120
+
Thermocouple
2
FIGURE 2-9
RTD Input Make RTD connections as illustrated below . For a three wire RTD, connect the resistive leg of the RTD to terminal 1 (1/8 & 1/4 DIN) or terminal 6 (1/16 DIN) and the common legs to terminals 2 and 3 (1/8 & 1/4 DIN) or termi­nals 4 and 5 (1/16 DIN). For a two wire RTD, connect one leg to terminal 2 (1/8 & 1/4 DIN) or terminal 5 (1/16 DIN) and the other leg to terminal 1 (1/8 & 1/4 DIN) or terminal 6 (1/16 DIN) as shown below. A jumper wire sup­plied by the customer must be installed between terminals 2 and 3 (1/8 & 1/ 4 DIN) or terminals 4 and 5 (1/16 DIN). Input conditioning jumper must be positioned correctly (see Appendix B) and Hardware Definition Code must be correct (see Appendix C).
1/8 & 1/4 DIN
3
2
RTD
1
FIGURE 2-10
V olt, mV Input Make volt and millivolt connections as shown below. Input conditioning jumper must be positioned correctly (see Appendix B) and Hardware Defini­tion Code must be correct (see Appendix C).
mADC Input Make mADC connections as shown below. Input conditioning jumper must be positioned correctly (see Appendix B) and Hardware Definition Code must be correct (see Appendix C).
1/16 DIN
4
5
RTD
6
1/8 & 1/4 DIN
+
Linear (mA)
-
Linear (V/mV)
+
1/16 DIN
4
+
-
3
2
1
21
Linear (mA)
-
-
+
Linear (V/mV)
MIC 1167/1407/1807 ManualEdition 1
4
5
6
FIGURE 2-11
Remote Digital Communications - RS485 Make digital communication connections as illustrated below .
1/8 & 1/4 DIN
16
17
18
B
A
COM
FIGURE 2-12
Dual Setpoint Selection
1/8 & 1/4 DIN
1/16 DIN
11
12
A
B
Contacts Open - Setpoint 1 Contacts Closed - Setpoint 2
1/16 DIN
16
17
Dry Contact
Contacts Open - Setpoint 1 Contacts Closed - Setpoint 2
11
Dry Contact
12
MIC 1167/1807/1407 Manual Edition 122
Output Connections 2.4
FIGURE 2-13
Relay Outputs 1 & 2 The contacts are rated at 2A resistive at 120V (motor drive) or 2A at 240V AC (resistive or independent contactor drive). Connections are made as shown below.
1/8 & 1/4 DIN
1/16 DIN
24 23 22
N/O
C
N/C
Relay
Output 2
N/O
1
19
20
21
N/C
C
Relay
Output 1
N/O
Output 1 is normally used as the "Open Valve" output.
Output 2 is normally used as the "Close Valve" output.
Relay
Output 1
C
N/C
2
3
13 14 15
N/O
23
C
Relay
Output 2
N/C
MIC 1167/1407/1807 ManualEdition 1
Loading...
+ 52 hidden pages