In normal operation, the operator must not remove the Ramp/Soak
Profile Controller from its housing or have unrestricted access to the
rear terminals, as this would provide potential contact with hazardous
live parts.
Installation and configuration must be undertaken only by
technically-competent servicing personnel. This is covered in Volume II
of this manual.
CONTENTS
1BASE MODE1-1
1.1DISPLAY SEQUENCE - NO PROGRAM RUNNING1-1
1.2STARTING A PROGRAM1-2
1.3PUTTING A PROGRAM IN HOLD1-2
1.4RELEASING A PROGRAM FROM HOLD1-2
1.5ABORTING A PROGRAM1-2
1.6DISPLAY SEQUENCE - PROGRAM RUNNING1-3
1.7RaPID CONTROL FEATURE1-4
1.8PRE-TUNE FEATURE1-4
1.9ENGAGING BOTH PRE-TUNE AND RaPID FEATURES1-5
1.10INDICATION OF PRE-TUNE AND RaPID STATUS1-5
1.11VIEWING THE HARDWARE DEFINITION CODE1-6
1.12MANUAL CONTROL1-7
PM077-V1Volume I(iii)
PM-0077
2PROGRAM DEFINITION MODE -
CREATING/EDITING A PROGRAM2-1
2.1ENTRY2-1
2.2CREATING A PROGRAM2-2
2.3DEFAULT VALUES AND ADJUSTMENT RANGES2-9
2.4EXIT FROM PROGRAM DEFINE MODE2-9
3CONTROLLER SET-UP MODE3-1
3.1PARAMETER DETAILS3-3
3.2EXIT FROM CONTROLLER SET-UP MODE3-9
4MODBUS COMMUNICATIONS4-1
4.1INTRODUCTION4-1
4.2MODBUS FUNCTIONS SUPPORTED4-1
4.3MESSAGE FORMATS4-1
4.4PARAMETER NUMBERS4-7
4.5PROFILER STATUS BYTE4-11
4.6PROFILER COMMANDS4-11
(iv )Volume IPM077-V1
PM-0077
1BASE MODE
1.1DIS P L A Y SEQUENCE - NO PROGRAM RUNNING
O077-1Volume I1-1
1.2STARTING A PROGRAM
To start a program running:
PM-0077
1.3PUTTING A PROGRAM IN HOLD
A program can be put in Hold (i.e. frozen) at any time whilst it is running. The
program setpoint will stay at its value at the instant the program entered Hold until
the program is released (see Subsection 1.4) or aborted (see Subsection 1.5). To
put a program in hold, momentarily press the RUN key. The RUN indicator will
flash whilst the program is in hold.
1.4RELEASING A PROGRAM FROM HOLD
To release a program currently in Hold, momentarily press the RUN key. The
RUN indicator will then go ON continuously.
1.5ABORTING A PROGRAM
To abort the current-running (or held) program, hold down the RUN key for 5
seconds. The program will be aborted, the RUN indicator will go OFF and the
normal Controller functions will be resumed.
1-2Volume IO077-1
PM-0077
NOTE: When a program is aborted, the instrument returns to the Controller
Setpoint value. If a program is successfully completed, the Controller
Setpoint is automatically set to the final setpoint value of the program. If it is
desired to restore the initial Controller Setpoint value after the program is
completed, this value should be used as the program Final Setpoint value.
1.6DISPLA Y SEQ U EN CE - PROGRAM RUNNING
O077-1Volume I1-3
PM-0077
1.7RaPID CONTROL FEATURE
The RaPID control feature may be used when extra fast responses and minimum
overshoot are required. The RaPID feature works best when PID terms are
well-tuned; therefore, it is recommended that the Pre-Tune feature (see Subsection
1.8) is run before the RaPID feature is engaged.
To disengage RaPID control, use the same key actions. NOTE: The RaPID feature
cannot be engaged if Proportional Band 1 or Proportional Band 2 is set to 0.
1.8PRE-TUNE FEATURE
This facility may be used to provide initial tuning of the Profile Controller’s PID
parameters. Pre-Tune may be engaged (and subsequently disengaged) as
follows:
NOTE: The Pre-Tune facility will not engage if (a) a program is currently
running, (b) the process variable is within 5% of input span of the setpoint,
or (c) an erroneous key sequence is used. Pre-Tune is a single-shot process
which automatically disengages itself when completed.
1-4Volume IO077-1
PM-0077
1.9ENGAGING BOTH PRE-TUNE AND RaPID FEATURES
The Pre-Tune and RaPID features can be engaged in one key action sequence:
Pre-Tune will operate first. When it is completed it will disengage itself and the
RaPID feature will then operate automatically.
1.10INDICATION OF PRE-TUNE AND RaPID STATUS
The responses to the RaPID feature being engaged are:
Pre-Tune Status when
RaPID engaged
Not operational.RaPID activated.
Operational.Pre-Tune completes routine,
then RaPID activated.
The responses to the RaPID feature being disengaged are:
Pre-Tune Status when
RaPID disengaged
Not operational.RaPID de-activated.
Operational.Pre-Tune completes routine,
then RaPID de-activated return to normal control.
The responses to Pre-Tune being engaged are:
ResponseIndication
AT indicator goes ON.
AT indicator flashes at
double rate then comes ON.
ResponseIndication
AT indicator goes OFF.
AT indicator flashes at
double rate then goes OFF.
RaPID status when
Pre-Tune engaged
Not operational.Pre-Tune activated and
routine completed
Operational.RaPID interrupted, Pre-Tune
activated. Pre-Tune
completes routine, then
RaPID control resumed.
O077-1Volume I1-5
ResponseIndication
AT indicator flashes at
normal rate the goes OFF.
AT indicator flashes at
double rate then goes ON.
PM-0077
The responses to Pre-Tune being disengaged (manually or automatically) are:
RaPID Status when
Pre-Tune disengaged
Not operational.Pre-Tune disengaged,
normal control resumed.
Operational.Pre-Tune disengaged, RaPID
control resumed.
ResponseIndication
AT indicator goes OFF.
AT indicator goes ON.
1.11VIEWING THE HARDWARE DEFINITION CODE
NOTE: An automatic return is made to the normal Base Mode display after
30 seconds.
The Hardware Definition Code has the following significance:
Value01234578
InputRTD/
Linear
DC mV
Output
1
Output
2/3
Not
fitted
RelaySSR
RelaySSR
Thermocouple
Drive
Drive
Linear
DC mA
DC
0 - 10VDC0 - 20mADC0 - 5VDC4 - 20mA
DC
0 - 10VDC0 - 20mADC0 - 5VDC4 - 20mA
Linear
DC V
* Output 2 only
Solid
State
Solid
State*
1-6Volume IO077-1
PM-0077
1.12MANUAL CONTROL
In Base Mode, with no program running or held, Manual Control may be selected
as follows:
The lower display shows the output power in the form Pxxx (xxx is in the range
000% to 100% of maximum output power). This may be adjusted using the Up and
Down keys.
To return to automatic control:
O077-1Volume I1-7
2PROGRAM DEFINITION MODE -
CREATING/EDITING A PROGRAM
2.1ENTRY
To enter Program Definition Mode:
PM-0077
NOTE: If the Program Define Mode lock code has been set to 0, pressing
the Scroll key in Step 2 will give direct access to Program Define Mode; no
entry of lock code is required.
Upon entry into Program Define Mode, the first Segment Definition parameter for
Segment 1 of Program 1 will be displayed.
2-1Volume IO077-2
PM-0077
2.2CREATING A PROGRAM
A program is created in two steps:
1. Define the segments of your program; the parameters used depend on
what Program Mode has been configured - Rate Mode (see Subsection
2.2.2) or Time Mode (see Subsection 2.2.3). The segment definitions
determine whether the selected segment is a Ramp Segment, a Soak
Segment or an End Segment.
2. Set the required Program Options (see Subsection 2.2.4). These
determine:
(i) The number of cycles performed by the program,
(Ii) The timebase to be used (hours/minutes or minutes/seconds)
(Iii) The width of the Guaranteed Soak Band (if enabled),
(Iv) The state of the event indicator for each segment in the
program,
(v) The lock code to be used for subsequent entries into Program
Define Mode.
2.2.1Basic Guidelines
1. The Ramp/Soak Profile Controller may contain up to four programs.
2. Each program may comprise up to 16 segments.
3. Each segment may be:
(a) a Ramp Segment (setpoint changing at a defined rate or
between the initial value and a pre-determined final value over a
defined time),
(b) a Soak Segment (setpoint constant for a defined time,) or
(c) an End Segment (marking the end of the program).
4. A program may contain only one End Segment (the last segment in the
program).
5. If the program comprises 16 segments, Segment 16 is automatically an
End Segment.
O077-2Volume I2-2
2.2.2Defining Segm ents - Rate Mode
PM-0077
2-3Volume IO077-2
PM-0077
2.2.3Defining Segments - Time Mode
O077-2Volume I2-4
2.2.4Prog ram O ptions
PM-0077
2-5Volume IO077-2
PM-0077
2.2.5Guaran teed Soak Band
The Guaranteed Soak Band is applicable to Soak segments only and operates as
follows (depending on whether Guaranteed Soak has been enabled or Manual
Guaranteed Soak has been configured):
O077-2Volume I2-6
PM-0077
2.2.6Segment Event Status
For every segment in a program there is an event indicator. This may be set ON or
OFF for that segment. The status for the segments in the currently-selected
program appears in the following form in the upper display:
The first display shows the current event status for Segments 1 - 8 and the second
display shows the current event status for Segments 9 - 16. Each event marker
may be set ON (Up key) or OFF (Down key) in order of segment number. Only the
event indicators for the segments in the program are displayed. If the program
has less than 16 segments (including the End Segment), the non-applicable
display positions are blank; if the program has eight segments or less, the second
display is not included.. The lower display shows the current segment number.
Thus, the key sequence to define the event markers for Segments 1 - 8 could be:
2 -7Volume IO077-2
PM-0077
O077-2Volume I2-8
PM-0077
Pressing the Scroll key would then display the event markers for Segments 9 - 16
(as applicable), which could be defined in a similar manner.
2.3DEFAULT VALUES AND ADJUSTMENT RANGES
ParameterRange MinimumRange MaximumDefault
Ramp Rate0 = Soak segment
-1 = End segment
Final (End of
Ramp) Setpoint
Segment Time00:0099:5901:00
Number of Cycles19999 then INF1
Guaranteed Soak
Band
Range MinimumRange MaximumRange Minimum
1Span plus OFFOFF
9999, then INF100
2.4EXIT FROM PROGRAM DEFINE MODE
A return is then made to the normal Base Mode display.
2-9Volume IO077-2
PM-0077
3CONTROLLER SET-UP MODE
In this mode, the parameters which define the operation of the controller are
defined. Controller Set-Up Mode can be entered (whether or not there is a
program currently running) as follows:
NOTES:
1. If the Controller Set-Up Mode lock code has been set to 0, pressing the
Scroll key in Step 2 will give direct access to Controller Set-Up Mode; no
entry of lock code is required.
2. If the upper display initially shows all decimal
points illuminated (see right), one or more
configuration parameters have been altered and,
as a consequence, all Controller Set Up Mode
parameters have been automatically set to their
default values/settings. To clear this display, simply alter the value/setting of
any Controller Set Up Mode parameter.
Upon entry into Controller Set-Up Mode, the first in a sequence of controller
parameters will be displayed. The operator may then step through the parameter
sequence using the Scroll key, adjusting the setting/value of each displayed
parameter using the Up/Down keys. The parameter sequence is as follows:
O077-3Volume I3-1
PM-0077
3-2Volume IO077-3
PM-0077
NOTES
1. Not operative if Proportional Band = 0.
2. Switching differential for ON/OFF control output.
3. Optional; only one legend will appear for each alarm.
4. Only applicable if a DC linear input is fitted.
5. Only applicable if Output 2 is fitted as a secondary control
(COOL) output.
6. Applicable only if the Communications Option is fitted.
7. When a program is running, respective to program setpoint.
3.1PARAMETER DETAILS
ParameterFunctionAdjustment Range
Input Filter Time
Constant
P rocess Variable
Offset
Output Power 1Current Output 1 power level0 to 100%Read only
Output Power 2Current Output 2 power level0 to 100%Read only
Proportional
Band 1 (PB1)
Proportional
Band 2 (PB2)
Reset (Integral
Time Constant)
Filter removes extraneous impulses from
the process variable input
Modifies actual process variable (PV)
value:
Offset PV + actual PV
= PV value used
Portion of input span in which Output 1
power level is proportional to the
(offset) process variable value (see
Figure 3-1).
Portion of input span in which Output 2
power level is proportional to the
(offset) process variable value (see
Figure 3-1).
Integral time constant1sec. to 99min. 59
OFF, 0.5 to 100.0
seconds in 0.5 second
increments
±input span of
Controller
0.0 to 999.9% of input
span
0.0 to 999.9% of input
span
secs. and OFF
Default
value
2.0
seconds
0
10.0%
10.0%
5 mins. 00
secs.
Rate (Derivative
Time Constant)
Overlap/
Deadband
Manual Reset
(Bias)
O077-3Volume I3-3
Derivative time constant00 secs. to 99 mins. 59
secs.
Portion of proportional band (PB1 +
PB2) in which both outputs are active
(overlap) or neither output is active
(deadband) - see Figure 3-1).
Bias applied to output power,
expressed as a percentage of output
power.
− 20% to +20% of
(Proportional Band 1 +
Proportional Band 2)
0% to 100% (Output 1
only);
−100% to +100%
(Output 1 & Output 2)
1 min. 15
secs.
0%
25%
PM-0077
ParameterFunctionAdjustment Range
ON/OFF
Differential
Setpoint LockEnables/disables setpoint (SP)
Recorder Output
Scale Maximum
Recorder Output
Scale Minimum
Output 1 Power
Limit
Output 1 Cycle
Time
Output 2 Cycle
Time
Switching differential for one output or
both outputs set to ON/OFF control (PB1,
PB2 or both = 0) - see Figure 3-1.
adjustment in Base Mode.
Process variable or setpoint value (as
applicable) for which the recorder
output is a maximum
Process variable or setpoint value (as
applicable) for which the recorder
output is a minimum
Limits Output 1 power level (to protect
the process)
Limits the frequency of operation of
output relay to maximise relay life
Limits the frequency of operation of
output relay to maximise relay life
Band Alarm 1If Alarm 1 is a Band Alarm, the band of
Deviation
Alarm 1
Alarm 1
Hysteresis
If Alarm 1 is a Process High Alarm, the
value of the process variable at or
above which Alarm 1 will be active (see
Figure 3-2)
If Alarm 1 is a Process Low Alarm, the
value of the process variable at or
below which Alarm 1 will be active (see
Figure 3-2)
process variable values, centred on the
(program) setpoint, outside which the
process variable will cause this alarm to
be active (see Figure 3-2)
If Alarm 1 is a Deviation Alarm, gives a
value above (positive value) or below
(negative value) the (program) setpoint.
If the process variable deviates from
the setpoint by a margin greater than
this value, the alarm becomes active
(see Figure 3-2)
Defines a hysteresis band on the “safe”
side of the Alarm 1 value
Input Range Minimum
to Input Range
Maximum
Input Range Minimum
to Input Range
Maximum
0 to input span from
(program) setpoint
± input span from
(program) setpoint
1 to 250 units1 unit
Input
Range
Maximum
Input
Range
Minimum
5 units
5 units
3-4Volume IO077-3
PM-0077
ParameterFunctionAdjustment Range
Process High
Alarm 2
Process Low
Alarm 2
Band Alarm 2If Alarm 2 is a Band Alarm, the band
Deviation
Alarm 2
If Alarm 2 is a Process High Alarm, the
value of the process variable at or
above which Alarm 2 will be active
(see Figure 3-2)
If Alarm 2 is a Process Low Alarm, the
value of the process variable at or
below which Alarm 2 will be active
(see Figure 3-2)
of process variable values, centred
on the (program) setpoint, outside
which the process variable will cause
this alarm to be active (see Figure
3-2)
If Alarm 2 is a Deviation Alarm, gives
a value above (positive value) or
below (negative value) the (program)
setpoint. If the process variable
deviates from the setpoint by a
margin greater than this value, the
alarm becomes active (see Figure
3-2)
Input Range Minimum
to Input Range
Maximum
Input Range Minimum
to Input Range
Maximum
0 to input span from
(program) setpoint
±input span from
(program) setpoint
Default
value
Input
Range
Maximum
Input
Range
Minimum
5 units
5 units
Alarm 2 HysteresisDefines a hysteresis band on the
“safe” side of the Alarm 2 value
Scale Range
Decimal Point
Position
Scale Range
Maximum
Scale Range
Minimum
Manual Control
Enable/Disable
Setpoint StrategyDetermines whether or not the
Communications
Enable/Disable
Controller Set-Up
Mode Lock Code
For linear inputs only, defines the
decimal point position
For linear inputs only, defines the
scaled input value when the process
variable input is at its maximum value
For linear inputs only, defines the
scaled input value when the process
variable input is at its minimum value
setpoint is adjustable in the normal
Base Mode display
Enables/disables changing of
parameter values via the
communications link
Defines the four-digit code required
to enter the Controller Set-Up Mode
1 to 250 units1 unit
0 (xxxx), 1 (xxx.x), 2
(xx.xx) or 3 (x.xxx)
−1999 to 9999
−1999 to 9999
0 (Disabled) or
1 (Enabled)
0 = not adjustable,
1 = adjustable
0 (disabled) or
1 (Enabled)
0 to 999910
1 (xxx.x)
1000
0000
0
(Disabled)
1
1
(Enabled)
O077-3Volume I3-5
Loading...
+ 57 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.