Partlow MIC 1166 Operating Manual

Page 1
1
-DIN
1 6
RAMP/SOAK PROFILE
CONTROLLER
Product Manual
Page 2
HOW TO USE THIS MANUAL
This manual comprises two volumes:
Page 3
PM-0077
-DIN RAMP/SOAK PROFILE CONTROLLER
1 6
PRODUCT MANUAL
VOLUME I
OPERATING INSTRUCTIONS
In normal operation, the operator must not remove the Ramp/Soak Profile Controller from its housing or have unrestricted access to the rear terminals, as this would provide potential contact with hazardous live parts.
Installation and configuration must be undertaken only by technically-competent servicing personnel. This is covered in Volume II of this manual.
CONTENTS
1 BASE MODE 1-1
1.1 DISPLAY SEQUENCE - NO PROGRAM RUNNING 1-1
1.2 STARTING A PROGRAM 1-2
1.3 PUTTING A PROGRAM IN HOLD 1-2
1.4 RELEASING A PROGRAM FROM HOLD 1-2
1.5 ABORTING A PROGRAM 1-2
1.6 DISPLAY SEQUENCE - PROGRAM RUNNING 1-3
1.7 RaPID CONTROL FEATURE 1-4
1.8 PRE-TUNE FEATURE 1-4
1.9 ENGAGING BOTH PRE-TUNE AND RaPID FEATURES 1-5
1.10 INDICATION OF PRE-TUNE AND RaPID STATUS 1-5
1.11 VIEWING THE HARDWARE DEFINITION CODE 1-6
1.12 MANUAL CONTROL 1-7
PM077-V1 Volume I (iii)
Page 4
PM-0077
2 PROGRAM DEFINITION MODE -
CREATING/EDITING A PROGRAM 2-1
2.1 ENTRY 2-1
2.2 CREATING A PROGRAM 2-2
2.3 DEFAULT VALUES AND ADJUSTMENT RANGES 2-9
2.4 EXIT FROM PROGRAM DEFINE MODE 2-9
3 CONTROLLER SET-UP MODE 3-1
3.1 PARAMETER DETAILS 3-3
3.2 EXIT FROM CONTROLLER SET-UP MODE 3-9
4 MODBUS COMMUNICATIONS 4-1
4.1 INTRODUCTION 4-1
4.2 MODBUS FUNCTIONS SUPPORTED 4-1
4.3 MESSAGE FORMATS 4-1
4.4 PARAMETER NUMBERS 4-7
4.5 PROFILER STATUS BYTE 4-11
4.6 PROFILER COMMANDS 4-11
(iv ) Volume I PM077-V1
Page 5
PM-0077

1 BASE MODE

1.1 DIS P L A Y SEQUENCE - NO PROGRAM RUNNING
O077-1 Volume I 1-1
Page 6

1.2 STARTING A PROGRAM

To start a program running:
PM-0077

1.3 PUTTING A PROGRAM IN HOLD

A program can be put in Hold (i.e. frozen) at any time whilst it is running. The program setpoint will stay at its value at the instant the program entered Hold until the program is released (see Subsection 1.4) or aborted (see Subsection 1.5). To
put a program in hold, momentarily press the RUN key. The RUN indicator will flash whilst the program is in hold.

1.4 RELEASING A PROGRAM FROM HOLD

To release a program currently in Hold, momentarily press the RUN key. The
RUN indicator will then go ON continuously.

1.5 ABORTING A PROGRAM

To abort the current-running (or held) program, hold down the RUN key for 5 seconds. The program will be aborted, the RUN indicator will go OFF and the
normal Controller functions will be resumed.
1-2 Volume I O077-1
Page 7
PM-0077
NOTE: When a program is aborted, the instrument returns to the Controller Setpoint value. If a program is successfully completed, the Controller Setpoint is automatically set to the final setpoint value of the program. If it is desired to restore the initial Controller Setpoint value after the program is completed, this value should be used as the program Final Setpoint value.

1.6 DISPLA Y SEQ U EN CE - PROGRAM RUNNING

O077-1 Volume I 1-3
Page 8
PM-0077

1.7 RaPID CONTROL FEATURE

The RaPID control feature may be used when extra fast responses and minimum overshoot are required. The RaPID feature works best when PID terms are well-tuned; therefore, it is recommended that the Pre-Tune feature (see Subsection
1.8) is run before the RaPID feature is engaged.
To disengage RaPID control, use the same key actions. NOTE: The RaPID feature
cannot be engaged if Proportional Band 1 or Proportional Band 2 is set to 0.

1.8 PRE-TUNE FEATURE

This facility may be used to provide initial tuning of the Profile Controller’s PID parameters. Pre-Tune may be engaged (and subsequently disengaged) as follows:
NOTE: The Pre-Tune facility will not engage if (a) a program is currently running, (b) the process variable is within 5% of input span of the setpoint, or (c) an erroneous key sequence is used. Pre-Tune is a single-shot process which automatically disengages itself when completed.
1-4 Volume I O077-1
Page 9
PM-0077

1.9 ENGAGING BOTH PRE-TUNE AND RaPID FEATURES

The Pre-Tune and RaPID features can be engaged in one key action sequence:
Pre-Tune will operate first. When it is completed it will disengage itself and the RaPID feature will then operate automatically.

1.10 INDICATION OF PRE-TUNE AND RaPID STATUS

The responses to the RaPID feature being engaged are:
Pre-Tune Status when
RaPID engaged
Not operational. RaPID activated.
Operational. Pre-Tune completes routine,
then RaPID activated.
The responses to the RaPID feature being disengaged are:
Pre-Tune Status when
RaPID disengaged
Not operational. RaPID de-activated.
Operational. Pre-Tune completes routine,
then RaPID de-activated ­return to normal control.
The responses to Pre-Tune being engaged are:
Response Indication
AT indicator goes ON.
AT indicator flashes at
double rate then comes ON.
Response Indication
AT indicator goes OFF.
AT indicator flashes at
double rate then goes OFF.
RaPID status when Pre-Tune engaged
Not operational. Pre-Tune activated and
routine completed
Operational. RaPID interrupted, Pre-Tune
activated. Pre-Tune completes routine, then RaPID control resumed.
O077-1 Volume I 1-5
Response Indication
AT indicator flashes at
normal rate the goes OFF.
AT indicator flashes at
double rate then goes ON.
Page 10
PM-0077
The responses to Pre-Tune being disengaged (manually or automatically) are:
RaPID Status when
Pre-Tune disengaged
Not operational. Pre-Tune disengaged,
normal control resumed.
Operational. Pre-Tune disengaged, RaPID
control resumed.
Response Indication
AT indicator goes OFF.
AT indicator goes ON.

1.11 VIEWING THE HARDWARE DEFINITION CODE

NOTE: An automatic return is made to the normal Base Mode display after 30 seconds.
The Hardware Definition Code has the following significance:
Value 0 1 2 3 4 5 7 8
Input RTD/
Linear DC mV
Output 1
Output 2/3
Not fitted
Relay SSR
Relay SSR
Thermo­couple
Drive
Drive
Linear DC mA
DC 0 - 10VDC0 - 20mADC0 - 5VDC4 - 20mA
DC 0 - 10VDC0 - 20mADC0 - 5VDC4 - 20mA
Linear DC V
* Output 2 only
Solid State
Solid State*
1-6 Volume I O077-1
Page 11
PM-0077

1.12 MANUAL CONTROL

In Base Mode, with no program running or held, Manual Control may be selected as follows:
The lower display shows the output power in the form Pxxx (xxx is in the range 000% to 100% of maximum output power). This may be adjusted using the Up and Down keys.
To return to automatic control:
O077-1 Volume I 1-7
Page 12
2 PROGRAM DEFINITION MODE -
CREATING/EDITING A PROGRAM

2.1 ENTRY

To enter Program Definition Mode:
PM-0077
NOTE: If the Program Define Mode lock code has been set to 0, pressing the Scroll key in Step 2 will give direct access to Program Define Mode; no entry of lock code is required.
Upon entry into Program Define Mode, the first Segment Definition parameter for Segment 1 of Program 1 will be displayed.
2-1 Volume I O077-2
Page 13
PM-0077

2.2 CREATING A PROGRAM

A program is created in two steps:
1. Define the segments of your program; the parameters used depend on what Program Mode has been configured - Rate Mode (see Subsection
2.2.2) or Time Mode (see Subsection 2.2.3). The segment definitions determine whether the selected segment is a Ramp Segment, a Soak Segment or an End Segment.
2. Set the required Program Options (see Subsection 2.2.4). These determine:
(i) The number of cycles performed by the program, (Ii) The timebase to be used (hours/minutes or minutes/seconds) (Iii) The width of the Guaranteed Soak Band (if enabled), (Iv) The state of the event indicator for each segment in the program, (v) The lock code to be used for subsequent entries into Program Define Mode.
2.2.1 Basic Guidelines
1. The Ramp/Soak Profile Controller may contain up to four programs.
2. Each program may comprise up to 16 segments.
3. Each segment may be:
(a) a Ramp Segment (setpoint changing at a defined rate or between the initial value and a pre-determined final value over a defined time), (b) a Soak Segment (setpoint constant for a defined time,) or (c) an End Segment (marking the end of the program).
4. A program may contain only one End Segment (the last segment in the program).
5. If the program comprises 16 segments, Segment 16 is automatically an End Segment.
O077-2 Volume I 2-2
Page 14
2.2.2 Defining Segm ents - Rate Mode
PM-0077
2-3 Volume I O077-2
Page 15
PM-0077
2.2.3 Defining Segments - Time Mode
O077-2 Volume I 2-4
Page 16
2.2.4 Prog ram O ptions
PM-0077
2-5 Volume I O077-2
Page 17
PM-0077
2.2.5 Guaran teed Soak Band
The Guaranteed Soak Band is applicable to Soak segments only and operates as follows (depending on whether Guaranteed Soak has been enabled or Manual Guaranteed Soak has been configured):
O077-2 Volume I 2-6
Page 18
PM-0077
2.2.6 Segment Event Status
For every segment in a program there is an event indicator. This may be set ON or OFF for that segment. The status for the segments in the currently-selected program appears in the following form in the upper display:
The first display shows the current event status for Segments 1 - 8 and the second display shows the current event status for Segments 9 - 16. Each event marker may be set ON (Up key) or OFF (Down key) in order of segment number. Only the event indicators for the segments in the program are displayed. If the program has less than 16 segments (including the End Segment), the non-applicable display positions are blank; if the program has eight segments or less, the second display is not included.. The lower display shows the current segment number. Thus, the key sequence to define the event markers for Segments 1 - 8 could be:
2 -7 Volume I O077-2
Page 19
PM-0077
O077-2 Volume I 2-8
Page 20
PM-0077
Pressing the Scroll key would then display the event markers for Segments 9 - 16 (as applicable), which could be defined in a similar manner.

2.3 DEFAULT VALUES AND ADJUSTMENT RANGES

Parameter Range Minimum Range Maximum Default
Ramp Rate 0 = Soak segment
-1 = End segment
Final (End of Ramp) Setpoint
Segment Time 00:00 99:59 01:00
Number of Cycles 1 9999 then INF 1
Guaranteed Soak Band
Range Minimum Range Maximum Range Minimum
1 Span plus OFF OFF
9999, then INF 100

2.4 EXIT FROM PROGRAM DEFINE MODE

A return is then made to the normal Base Mode display.
2-9 Volume I O077-2
Page 21
PM-0077

3 CONTROLLER SET-UP MODE

In this mode, the parameters which define the operation of the controller are defined. Controller Set-Up Mode can be entered (whether or not there is a program currently running) as follows:
NOTES:
1. If the Controller Set-Up Mode lock code has been set to 0, pressing the Scroll key in Step 2 will give direct access to Controller Set-Up Mode; no entry of lock code is required.
2. If the upper display initially shows all decimal points illuminated (see right), one or more configuration parameters have been altered and, as a consequence, all Controller Set Up Mode parameters have been automatically set to their default values/settings. To clear this display, simply alter the value/setting of any Controller Set Up Mode parameter.
Upon entry into Controller Set-Up Mode, the first in a sequence of controller parameters will be displayed. The operator may then step through the parameter sequence using the Scroll key, adjusting the setting/value of each displayed parameter using the Up/Down keys. The parameter sequence is as follows:
O077-3 Volume I 3-1
Page 22
PM-0077
3-2 Volume I O077-3
Page 23
PM-0077
NOTES
1. Not operative if Proportional Band = 0.
2. Switching differential for ON/OFF control output.
3. Optional; only one legend will appear for each alarm.
4. Only applicable if a DC linear input is fitted.
5. Only applicable if Output 2 is fitted as a secondary control (COOL) output.
6. Applicable only if the Communications Option is fitted.
7. When a program is running, respective to program setpoint.

3.1 PARAMETER DETAILS

Parameter Function Adjustment Range
Input Filter Time Constant
P rocess Variable Offset
Output Power 1 Current Output 1 power level 0 to 100% Read only
Output Power 2 Current Output 2 power level 0 to 100% Read only
Proportional Band 1 (PB1)
Proportional Band 2 (PB2)
Reset (Integral Time Constant)
Filter removes extraneous impulses from the process variable input
Modifies actual process variable (PV) value: Offset PV + actual PV
= PV value used
Portion of input span in which Output 1 power level is proportional to the (offset) process variable value (see Figure 3-1).
Portion of input span in which Output 2 power level is proportional to the (offset) process variable value (see Figure 3-1).
Integral time constant 1sec. to 99min. 59
OFF, 0.5 to 100.0 seconds in 0.5 second increments
±input span of
Controller
0.0 to 999.9% of input span
0.0 to 999.9% of input span
secs. and OFF
Default
value
2.0 seconds
0
10.0%
10.0%
5 mins. 00 secs.
Rate (Derivative Time Constant)
Overlap/ Deadband
Manual Reset (Bias)
O077-3 Volume I 3-3
Derivative time constant 00 secs. to 99 mins. 59
secs.
Portion of proportional band (PB1 + PB2) in which both outputs are active (overlap) or neither output is active (deadband) - see Figure 3-1).
Bias applied to output power, expressed as a percentage of output power.
20% to +20% of
(Proportional Band 1 + Proportional Band 2)
0% to 100% (Output 1 only);
−100% to +100%
(Output 1 & Output 2)
1 min. 15 secs.
0%
25%
Page 24
PM-0077
Parameter Function Adjustment Range
ON/OFF Differential
Setpoint Lock Enables/disables setpoint (SP)
Recorder Output Scale Maximum
Recorder Output Scale Minimum
Output 1 Power Limit
Output 1 Cycle Time
Output 2 Cycle Time
Switching differential for one output or both outputs set to ON/OFF control (PB1, PB2 or both = 0) - see Figure 3-1.
adjustment in Base Mode.
Process variable or setpoint value (as applicable) for which the recorder output is a maximum
Process variable or setpoint value (as applicable) for which the recorder output is a minimum
Limits Output 1 power level (to protect the process)
Limits the frequency of operation of output relay to maximise relay life
Limits the frequency of operation of output relay to maximise relay life
0.1% to 10.0% of input span
OFF - SP adjustable ON - SP not adjustable
1999 to 9999
(decimal point position as for input range)
1999 to 9999
(decimal point position as for input range)
0% to 100% of full power
0.5, 1, 2, 4, 8, 16, 32, 64, 128, 256 or 512 secs.
0.5, 1, 2, 4, 8, 16, 32, 64, 128, 256 or 512 secs.
Default
value
0.5%
OFF
Input Range Maximum
Input Range Minimum
100%
32 secs.
32 secs.
Process High Alarm 1
Process Low Alarm 1
Band Alarm 1 If Alarm 1 is a Band Alarm, the band of
Deviation Alarm 1
Alarm 1 Hysteresis
If Alarm 1 is a Process High Alarm, the value of the process variable at or above which Alarm 1 will be active (see Figure 3-2)
If Alarm 1 is a Process Low Alarm, the value of the process variable at or below which Alarm 1 will be active (see Figure 3-2)
process variable values, centred on the (program) setpoint, outside which the process variable will cause this alarm to be active (see Figure 3-2)
If Alarm 1 is a Deviation Alarm, gives a value above (positive value) or below (negative value) the (program) setpoint. If the process variable deviates from the setpoint by a margin greater than this value, the alarm becomes active (see Figure 3-2)
Defines a hysteresis band on the “safe” side of the Alarm 1 value
Input Range Minimum to Input Range Maximum
Input Range Minimum to Input Range Maximum
0 to input span from (program) setpoint
± input span from
(program) setpoint
1 to 250 units 1 unit
Input Range Maximum
Input Range Minimum
5 units
5 units
3-4 Volume I O077-3
Page 25
PM-0077
Parameter Function Adjustment Range
Process High Alarm 2
Process Low Alarm 2
Band Alarm 2 If Alarm 2 is a Band Alarm, the band
Deviation Alarm 2
If Alarm 2 is a Process High Alarm, the value of the process variable at or above which Alarm 2 will be active (see Figure 3-2)
If Alarm 2 is a Process Low Alarm, the value of the process variable at or below which Alarm 2 will be active (see Figure 3-2)
of process variable values, centred on the (program) setpoint, outside which the process variable will cause this alarm to be active (see Figure 3-2)
If Alarm 2 is a Deviation Alarm, gives a value above (positive value) or below (negative value) the (program) setpoint. If the process variable deviates from the setpoint by a margin greater than this value, the alarm becomes active (see Figure 3-2)
Input Range Minimum to Input Range Maximum
Input Range Minimum to Input Range Maximum
0 to input span from (program) setpoint
±input span from
(program) setpoint
Default
value
Input Range Maximum
Input Range Minimum
5 units
5 units
Alarm 2 Hysteresis Defines a hysteresis band on the
“safe” side of the Alarm 2 value
Scale Range Decimal Point Position
Scale Range Maximum
Scale Range Minimum
Manual Control Enable/Disable
Setpoint Strategy Determines whether or not the
Communications Enable/Disable
Controller Set-Up Mode Lock Code
For linear inputs only, defines the decimal point position
For linear inputs only, defines the scaled input value when the process variable input is at its maximum value
For linear inputs only, defines the scaled input value when the process variable input is at its minimum value
setpoint is adjustable in the normal Base Mode display
Enables/disables changing of parameter values via the communications link
Defines the four-digit code required to enter the Controller Set-Up Mode
1 to 250 units 1 unit
0 (xxxx), 1 (xxx.x), 2 (xx.xx) or 3 (x.xxx)
1999 to 9999
1999 to 9999
0 (Disabled) or 1 (Enabled)
0 = not adjustable, 1 = adjustable
0 (disabled) or 1 (Enabled)
0 to 9999 10
1 (xxx.x)
1000
0000
0 (Disabled)
1
1 (Enabled)
O077-3 Volume I 3-5
Page 26
PM-0077
Figure 3-1 Proportional Band and O verlap/Dead band
3-6 Volume I O077-3
Page 27
PM-0077
Figure 3-2 Alarm Operation
O077-3 Volume I 3-7
Page 28
PM-0077
Figure 3-3 Alarm Hysteresis Operation
3 -8 Volume I O077-3
Page 29
PM-0077

3.2 EXIT FROM CONTROLLER SET-UP MODE

A return will then be made to the normal Base Mode display.
O077-3 Volume I 3-9
Page 30
PM-0077

4 MODBUS COMMUNICATIONS

4.1 INTRODUCTION

This Section specifies the MODBUS communications protocol as implemented on
1
the
-DIN Ramp/Soak Profile Controller.
1 6
Certain restrictions have been imposed upon this implementation:
(i) Baud rates may be set to 1200, 2400, 4800 and 9600 only
(ii) Support for multi-parameter Writes is limited to support of the Multi-word Write Function (Number 16) but will permit writing of one parameter only per message
(iii) The multi-parameter Read function supports a maximum of 10 parameters in one message.

4.2 MODBUS FUNCTIONS SUPPORTED

In the following list, the original Gould MODBUS function names have been used, followed by the JBUS names in italics, where such an equivalence exists. The MODBUS Function number follows the names.
A Read Coil Status (Read n Bits) 01/02
B Read Holding Registers (Read n Words) 03/04
C Force Single Coil (Write 1 Bit) 05
D Preset Single Register (Write 1 Word) 06
E Loopback Diagnostic Test 08
F Preset Multiple Registers (Write n Words) 16
The instrument will identify itself in reply to a Read Holding Registers message which enquires the values of parameter numbers 121 & 122, as specified in the CNOMO documentation, and MODBUS Function 17 (Report Slave ID) will not be supported.

4.3 MESSAGE FORMATS

The first character of every message is an instrument address. The valid range of such an address is 0 to 255. The second character is always the Function
4 -1 Volume I O077-4
Page 31
PM-0077
Number. The contents of the remainder of the message depends upon the function number.
In most cases the instrument is required to reply by echoing the address and function number, together with an echo of all or part of the message received (in the case of a request to write a value or carry out a command) or the information requested (in the case of a read parameter operation). Broadcast Messages (to which the controller responds by taking some action without sending back a reply) are supported at instrument address zero. Commands which can be broadcast are marked with the symbol B .
Data is transmitted as eight-bit binary bytes with 1 start bit, 1 stop bit and optional parity checking (None, Even or Odd).
A message is terminated solely by a delay of more than three character lengths at the given Baud Rate, and any character received after such a delay is treated as a potential address at the start of a new message.
The following individual message formats apply. Since only the RTU form of the protocol is being supported, each message is followed by a two-byte CRC16. Details of how the checksum must be calculated are given at the end of this section.
A. Read Coil Status (Read n Bits) 01/02
The message sent to the controller will consist of 8 bytes, as follows:
The normal reply will echo the first two characters of the message received, and will then contain a single-byte data byte count, which will not include itself or the CRC. For this message, there will be one byte of data per eight bits-worth of information requested, with the LSbit of the first data byte transmitted depicting the state of the lowest-numbered bit required.
O077-4 Volume I 4-2
Page 32
PM-0077
This function will be used largely to report controller status information, and so a bit set to 1 indicates that the corresponding feature is currently enabled/active, and a bit reset to 0 indicates the opposite.
If an exact multiple of eight bits is not requested, the data is padded with trailing zeros to preserve the 8-bit format. After the data has been transmitted, the CRC16 value is sent.
B. Read Holding Registers (Read n Words) 03/04
The message sent to the controller to obtain the value of one or more registers is an eight-byte message as follows:
The reply sent by the controller echoes the first 2 characters received and then contains a single-byte data byte count, the value of which does not include either itself or the CRC value to be sent. For this message, the count equals the number of parameters read times two. Following the byte count, that number of parameter values are transmitted, MSB first, followed by the CRC16.
C. Force Single Coil (Write 1 Bit) 05 B
The message received by the controller is 8 bytes long, consisting of the standard preamble and the address of the bit to force, followed by a two-byte word whose MSB contains the desired truth value of the bit expressed as 0xFF (TRUE) or 0x00 (FALSE).
Generally, this function will be used to control such features as Auto/Manual and Tuning.
The normal reply sent by the controller will be a byte-for-byte echo of the message received.
4-3 Volume I O077-4
Page 33
PM-0077
D. Preset Single Register (Write 1 Word) 06 B
The message sent to the controller consists of 8 bytes: the address and function number as usual, the address of the parameter to be written, and the two-byte value to which the parameter will be set, and finally the CRC16.
The normal response is to echo the message in its entirety.
E. Loopback Diagnostic Test 08
The controller is sent an 8 byte message consisting of the usual preamble, a two-byte diagnostic code, and two bytes of data, followed by the CRC16.
Full MODBUS support in this area is not appropriate - consequently, the only Diagnostic Code supported is code 00. In response to the message, the controller must echo the message received exactly.
F. Preset Multiple Registers (Write n Words) 16 B
This message consists of eleven bytes. Only one parameter may be written at a time, even though this function number is supported. The preamble is followed by the address of the parameter to be written, and then a two-byte word count (always set to 1) and a single-byte byte count (always set to 2). Finally, the value to be written is followed by the CRC16.
The controller normally responds with a eight-byte reply, as follows:
O077-4 Volume I 4-4
Page 34
PM-0077
G. Error and Exception Responses
If the controller receives a message which contains a corrupted character (parity check fail, framing error etc.), or if the CRC16 check fails, the controller ignores the message. If the message is otherwise syntactically flawed (e.g. the byte count or word count is incorrect) the controller will also not reply.
However, if the controller receives a syntactically correct message which nonetheless contains an illegal value, it will send an exception response, consisting of five bytes as follows:
The Function Number field consists of the function number contained in the message which caused the error, with its top bit set (i.e. function 3 becomes 0x83), and the Exception Number is one of the codes contained in the following table:
Code Name Cause
1 ILLEGAL FUNCTION Function Number out of range
2 ILLEGAL DATA ADDRESS Parameter ID out of range or not supported
3 ILLEGAL DATA VALUE Attempt to write invalid data/action not
carried out
4 DEVICE FAILURE N/A
5 ACKNOWLEDGE N/A
6 BUSY N/A
7 NEGATIVE ACKNOWLEDGE N/A
H. CRC16 Calculation
This is a 16-bit cyclic redundancy checksum. It is calculated in accordance with a formula which involves recursive division of the data by a polynomial, with the input to each division being the remainder of the results of the previous one.
The formula specifies that input is treated as a continuous bit-stream binary number, with the most significant bit being transmitted first. However, the transmitting device sends the least significant bit first.
According to the formula, the dividing polynomial is 216 + 215 + 22 + 1 (Hex
18005), but this is modified in two ways:
i. Because the bit-order is reversed, the binary pattern is reversed also, making the MSB the rightmost bit, and
4-5 Volume I O077-4
Page 35
PM-0077
ii. Because only the remainder is of interest, the MSB (the rightmost bit) may be discarded.
This means the polynomial has the value Hex A001. The CRC algorithm is as follows:
O077-4 Volume I 4-6
Page 36
PM-0077

4.4 PARAMETER NUMBERS

The parameter numbering system, in order to conform to the CNOMO standard, splits parameters into BITS and WORDS and numbers each group independently.
A. Bit Parameters (Controller Status Byte)
There are a maximum of sixteen of these:
No. Parameter Notes
1 Communications Write Status Read only - 1 = enabled, 0 = disabled
2 Auto/Manual Control 1 = Manual, 0 = Auto
3 RaPID Tuning Status 1 = active, 0 = inactive
4 Pre-Tune Status 1 = active, 0 = inactive
5 Alarm 1 Status Read only - 1 = active, 0 = inactive
6 Alarm 2 Status Read only - 1 = active, 0 = inactive
7 Over-range Flag Read only - 1 = active, 0 = inactive
8 Under-range Flag Read only - 1 = active, 0 = inactive
9 Sensor Break Flag Read only - 1 = break, 0 = no break
10 Reserved
11 Reserved
12 Reserved
13 Reserved
14 Reserved
15 Reserved
16 Reserved
4 -7 Volume I O077-4
Page 37
PM-0077
B. Word Parameters
No. Parameter Notes
Controller Parameters
1 Process Variable Read only
2 Setpoint Current setpoint, if ramping
3 Output Power Read only, unless in Manual Control
4 Arithmetic Deviation Read only
5 Proportional Band 2
6 Proportional Band 1
7 Controller Status
8 Reset
9 Rate
10 Output 1 Cycle Time
11 Scale Range Low Read only if non-linear input
12 Scale Range High Read only if non-linear input
13 Alarm 1 value
14 Alarm 2 value
15 Manual Reset
16 Overlap/Deadband
17 ON/OFF Differential
18 Decimal Point Position Read only if non-linear input
19 Output 2 Cycle Time
20 Output 1 Power Limit
21 Setpoint Lock 0 = Off, 1 = On
22 Reserved
23 Filter Time Constant
24 Process Variable Offset
25 Recorder Output Max.
26 Recorder Output Min.
27 Alarm 1 Hysteresis
28 Alarm 2 Hysteresis
Program Parameters
29 Segment Mode 0 = Rate, 1 = Time
30 Profiler Status Read only - see Subsection 4.5.
31 Current Program Number Read only
32 Current Segment Number Read only in current running/held program
33 Segment Time Remaining Read only
O077-4 Volume I 4-8
Page 38
PM-0077
No. Parameter Notes
34 Profiler Commands Write only - see Subsection 4.6.
35 Power Fail Recovery 0 = Cold start, 1 = Warm start
36 Guaranteed Soak Type 0 = disabled, 1 = enabled, 2 = manual
37 Cycles Remaining Read only
Instrument ID Parameters
121 Manufacturer ID Read only - 231
122 Equipment ID Read only - 6400
Segment Parameters - Program 1
1100 Run Program (value = Delayed Start value) Write only
1101 No. of Cycles Programmed 1 to 9999 plus 10000 (INF)
1102 Timebase 0 = hours/minutes, 1 = minutes/seconds
1103 Guaranteed Soak Band value 0 (OFF), 1 to span
1104
1119
1120
1135
1136
1151
1152 Event Marker settings
Final Setpoint values
to
(Soak = -32768, End = -16384)
Rate values (Soak = -32768, End = -16384) Segment 1 at address 1120
to
Time values Segment 1 at address 1136
to
Segment 1 at address 1104
Segment 16 at address 1119
Segment 16 at address 1135
Segment 16 at address 1151
Bit 0 = Event 16 Bit 15 = Event 1
Segment Parameters - Program 2
1200 Run Program (value = Delayed Start value) Write only
1201 No. of Cycles Programmed 1 to 9999 plus 10000 (INF)
1202 Timebase 0 = hours/minutes, 1 = minutes/seconds
1203 Guaranteed Soak Band value 0 (OFF), 1 to span
1204
1219
1220
1235
Final Setpoint values
to
(Soak = -32768, End = -16384)
Rate values (Soak = -32768, End = -16384) Segment 1 at address 1220
to
Segment 1 at address 1204
Segment 16 at address 1219
Segment 16 at address 1235
1236
1251
1252 Event Marker settings
4-9 Volume I O077-4
Time values Segment 1 at address 1236
to
Segment 16 at address 1251
Bit 0 = Event 16 Bit 15 = Event 1
Page 39
PM-0077
No. Parameter Notes
Segment Parameters - Program 3
1300 Run Program (value = Delayed Start value) Write only
1301 No. of Cycles Programmed 1 to 9999 plus 10000 (INF)
1302 Timebase 0 = hours/mnutes, 1 = minutes/seconds
1303 Guaranteed Soak Band value 0 (OFF), 1 to span
1304
1319
1320
1335
1336
1351
1352 Event Marker settings
Final Setpoint values
to
(Soak = -32768, End = -16384)
Rate values (Soak = -32768, End = -16384) Segment 1 at address 1320
to
Time values Segment 1 at address 1336
to
Segment 1 at address 1304
Segment 16 at address 1319
Segment 16 at address 1335
Segment 16 at address 1351
Bit 0 = Event 16 Bit 15 = Event 1
Segment Parameters - Program 4
1400 Run Program (value = Delayed Start value) Write only
1401 No. of Cycles Programmed 1 to 9999 plus 10000 (INF)
1402 Timebase 0 = hours/minutes, 1 = minutes/seconds
1403 Guaranteed Soak Band value 0 (OFF), 1 to span
1404
1419
1420
1435
Final Setpoint values
to
(Soak = -32768, End = -16384)
Rate values (Soak = -32768, End = -16384) Segment 1 at address 1420
to
Segment 1 at address 1404
Segment 16 at address 1419
Segment 16 at address 1435
1436
1451
1452 Event Marker settings
Time values Segment 1 at address 1436
to
Segment 16 at address 1451
Bit 0 = Event 16 Bit 15 = Event 1
Some of the parameters which do not apply to a particular instrument configuration (e.g. PB2 on a single output instrument) will accept reads & writes. Others will accept reads only, and will return an exception if an attempt is made to write values to them. The values read will in all cases be undefined. It is the user’s responsibility to make sure that values read reflect a possible state of the instrument.
O077-4 Volume I 4-10
Page 40

4.5 PROFILER STATUS BYTE

The Profiler Status byte has the following format:
PM-0077

4.6 PROFILER COMMANDS

The Profiler Commands are as follows:
0001 Manually hold currently-running program
0002 Release Manual Hold on current program
0003 Abort currently-running/held program
4-11 Volume I O077-4
Page 41
PM-0077
1
-DIN RAMP/SOAK PROFILE CONTROLLER
1 6
PRODUCT MANUAL
VOLUME II
INSTALLATION & CONFIGURATION
INSTRUCTIONS
The procedures described in this Volume must be undertaken only by technically-competent servicing personnel.
CONTENTS
1 INSTALLATION 1-1
1.1 UNPACKING PROCEDURE 1-1
1.2 PANEL-MOUNTING THE CONTROLLER 1-1
1.3 CONNECTIONS AND WIRING 1-2
2 INTERNAL LINKS AND SWITCHES 2-1
2.1 REMOVING THE PROFILE CONTROLLER FROM ITS HOUSING 2-1
2.2 REMOVING/REPLACING THE OUTPUT 2/OUTPUT 3 OPTION PCBs 2-3
2.3 REMOVING/REPLACING THE RS485 COMMUNICATIONS OPTION PCB OR REMOTE RUN/HOLD OPTION PCB 2-3
2.4 REPLACING THE INSTRUMENT IN ITS HOUSING 2-3
2.5 SELECTION OF INPUT TYPE AND OUTPUT 1 TYPE 2-4
2.6 OUTPUT 2 TYPE/OUTPUT 3 TYPE 2-6
3 CONFIGURATION MODE 3-1
3.1 ENTRY INTO CONFIGURATION MODE 3-1
3.2 HARDWARE DEFINITION CODE 3-1
3.3 OPTION SELECTION 3-3
PM077-V2 Volume II (i)
Page 42
PM-0077
3.4 CONFIGURATION MODE PARAMETERS 3-4
3.5 EXIT FROM CONFIGURATION MODE 3-9
APPENDIX A PRODUCT SPECIFICATION
APPENDIX B SUMMARY OF DISPLAYS
(ii) Volume II PM077-V2
Page 43
PM-0077

1 INSTALLATION

1.1 UNPACKING PROCEDURE

1. Remove the Profile Controller from its packing. The Controller is supplied with a panel gasket and push-fit fixing strap. Retain the packing for future use, should it be necessary to transport the Profile Controller to a different site or to return it to the supplier for repair/testing.
2. Examine the delivered items for damage or deficiencies. If any is found, notify the carrier immediately.

1.2 PANEL-MOUNTING THE CONTROLLER

The panel on which the Profile Controller is to be mounted must be rigid and may be up to
6.0mm (0.25 inches) thick. The cut-out
required for a single Profile Controller is as shown in Figure 1-1.
Several instruments may be installed in a single cut-out, side-by-side. For n Profile Controllers mounted side-by-side, the width of the cut-out would be:
(48n - 4) millimetres or (3.78n - 0.16) inches.
The Profile Controller is 110mm deep (measured from the rear face of the front panel). The front panel is 48mm high and 48mm wide. When panel-mounted, the front panel projects 10mm from the mounting panel. The main dimensions of the Profile Controller are shown in Figure 1-2.
Figure 1 -1 Cut-out Dimensions
45mm +0.5 -0.0
Figure 1-2 Main Dimensions
S077-1 Volume II 1-1
Page 44
The procedure to panel-mount the Profile Controller is shown in Figure 1-3.
CAUTION: Do not remove the panel gasket, as this may result in
inadequate clamping of the instrument in the panel.
NOTE: When installing several instruments side-by-side in one cut-out, use the ratchets on the top/bottom faces.
PM-0077
Figure 1 -3 Panel-Mounting the Profile Controller
Once the Profile Controller is installed in its mounting panel, it may be subsequently removed from its housing, if necessary, as described in Subsection
2.1.

1.3 CONNECTIONS AND WIRING

The rear terminal connections are illustrated in Figure 1-4.
This instrument is designed for installation in an enclosure which provides adequate protection against electric shock. All pertinent local regulations should be rigidly observed. Consideration should be given to prevention of access to the rear terminals by unauthorised personnel.
1 -2 Volume II S077-1
Page 45
PM-0077
Figure 1 -4 Rear Terminal Connections
S077-1 Volume II 1-3
Page 46
PM-0077
1.3.1 Mains (Line) Input
The Profile Controller will operate on 96 - 264V AC 50/60Hz mains (line) supply. The power consumption is approximately 4 VA. Power should be connected via a two-pole isolating switch (preferably situated near the equipment) and a 1A fuse.
If the Profile Controller has relay outputs in which the contacts are to carry mains (line) voltage, it is recommended that the relay contact mains (line) supply should be switched and fused in a similar manner but should be separate from the Profile Controller mains (line) supply.
1.3.2 24V (Nominal) AC/DC Supply
The supply connections for the 24V AC/DC option of the Profile Controller are as shown in Figure 1-4. Power should be connected via a two-pole isolating switch and a 315mA slow-blow (anti-surge Type T) fuse.
With the 24V AC/DC supply option fitted, these terminals will accept the following supply voltage ranges:
24V (nominal) AC 50/60Hz - 20 - 50V 24V (nominal) DC - 22 - 65V
1.3.3 Thermocouple Input
The correct type of thermocouple extension leadwire or compensating cable must be used for the entire distance between the Profile Controller and the thermocouple, ensuring that the correct polarity is observed throughout. Joints in the cable should be avoided, if possible. The CJC facility must be enabled (normal conditions) for this input (see Subsection 3.4).
NOTE: Do not run thermocouple cables adjacent to power-carrying conductors. If the wiring is run in a conduit, use a separate conduit for the thermocouple wiring. If the thermocouple is grounded, this must be done at one point only. If the thermocouple extension lead is shielded, the shield must be grounded at one point only.
1.3.4 RTD Inputs
The compensating lead should be connected to Terminal 4. For two-wire RTD inputs, Terminals 4 and 5 should be linked. The extension leads should be of copper and the resistance of the wires connecting the resistance element should not exceed 5 ohms per lead (the leads should be of equal resistance).
1-4 Volume II S077-1
Page 47
PM-0077
1.3.5 Linear Inputs
For linear mA input ranges, connection is made to Terminals 4 and 6 in the polarity shown in Figure 1-4. For linear mV and V ranges, connection is made to Terminals 4 and 5 in the polarity shown in Figure 1-4. For details of the linear input ranges available, refer to Appendix A.
1.3.6 Remote Run/Hold Input
With this option fitted, Terminals 11 and 12 are used for external Run/Hold control of the currently-selected program; this has an effect identical to that of the front panel RUN key. These terminals may be connected to (a) the voltage-free contacts of a switch or relay, or (b) a TTL-compatible voltage. This is an edge-sensitive input for which the following convention has been adopted:
For TTL input, OFF = logic 1 and ON = logic 0 For a voltage-free input, OFF = open and ON = closed
Program control is as follows:
OFF-ON transition: The currently-selected program will run (or
will resume running if it is currently held).
ON-OFF transition: The currently-running program will be held.
NOTE: When this input is used, the front panel RUN key can be used only to abort a program. Powering-up the Profile Controller whilst this input is ON will not cause a program to run. The RS485 Serial Communications option and the Remote Run/Hold option are mutually exclusive.
1.3.7 Relay Outputs
The contacts are rated at 2A resistive at 120/240V AC.
1.3.8 SSR Drive Outputs
These outputs produce a time-proportioned non-isolated DC signal (0 - 4.2V nominal into 1kΩ minimum).
1.3.9 Solid State Outputs
These outputs provide up to 1A AC drive with a longer lifetime than an electromechanical relay. For further details, refer to Appendix A.
S077-1 Volume II 1-5
Page 48
PM-0077
1.3.10 DC Outputs
See Appendix A.
1.3.11 RS485 Serial Communications Link
The cable used should be suitable for data transfer at the selected rate (1200, 2400, 4800 or 9600 Baud) over the required distance. Transmitters/receivers conform to the recommendations in the EIA Standard RS485.
The “A” terminal (Terminal 11) on the Profile Controller should be connected to the “A” terminal on the master device; the “B” terminal (Terminal 12) on the Profile Controller should be connected to the “B” terminal on the master device. Where several Profile Controllers are connected to one master port, the master port transceiver in the active state should be capable of driving a load of 12kΩ per Profile Controller; the master port transceiver in the passive state must have pull-up/pull-down resistors of sufficiently low impedance to ensure that it remains in
the quiescent state whilst supplying up to ± 100µA each to the Profile Controller
transceivers in the high impedance state.
NOTE: The RS485 Serial Communications option and the Remote Run/Hold option are mutually exclusive.
1-6 Volume II S077-1
Page 49
PM-0077

2 INTERNAL LINKS AND SWITCHES

2.1 REMOVING THE PROFILE CONTROLLER FROM ITS HOUSING

CAUTION: Before removing the instrument from its housing, ensure
that all power has been removed from the rear terminals.
To withdraw the instrument from its housing, simply grip the side edges of the front panel (there is a finger grip on each edge) and pull the instrument forwards. This will release the instrument from its rear connectors in the housing and will give access to the instrument PCBs. Take note of the orientation of the instrument for subsequent replacement into the housing.The positions of the PCBs in the instrument are shown in Figure 2-1.
Figure 2 -1 PCB Positions
S077-2 Volume II 2-1
Page 50
PM-0077
Figure 2 -2 Removing the Output 2/Output 3 Option PCBs
2-2 Volume II S077-2
Page 51
PM-0077

2.2 REMOVING/ REPLACING THE OUTPUT 2/OUTPUT 3 OPTION PCBs

With the instrument removed from its housing:
1. Gently push the rear ends of the CPU PCB and Power Supply PCB apart slightly, until the two tongues on each of the Output 2/Output 3 Option PCBs become disengaged - see Figure 2-2B; The Output 2 Option PCB tongues engage in holes in the Power Supply PCB and the Output 3 Option PCB tongues engage in holes on the CPU PCB.
2. Carefully pull the required Option PCB (Output 2 or Output 3) from its connector (Output 2 Option PCB is connected to the CPU PCB and Output 3 Option PCB is connected to the Power Supply PCB) - see Figure 2-2C. Note the orientation of the PCB in preparation for its replacement.
Adjustments may now be made to the link jumpers on the CPU PCB, the Output 2/Output 3 Option PCBs (if DC output) and (if fitted) the DC Output 1 PCB. The replacement procedure is a simple reversal of the removal procedure.

2.3 REMOVING/REPLACING THE RS485 COMMUNICATIONS OPTION PCB OR REMOTE RUN/HOLD OPTION PCB

The RS485 Communications Option PCB or Remote Run/Hold Option PCB is mounted on the inner surface of the Power Supply PCB and can be removed when the instrument is removed from its housing (see Subsection 2.1) Figure 2-3 illustrates the removal/replacement procedure. It is not necessary to remove the
Output 2/Output 3 Option PCBs to perform this procedure.

2.4 REPLACING THE INSTRUMENT IN ITS HOUSING

To replace the instrument, simply align the CPU PCB and Power Supply PCB with their guides and connectors in the housing and slowly but firmly push the instrument into position.
CAUTION: Ensure that the instrument is correctly orientated. A stop will operate if an attempt is made to insert the instrument in the wrong orientation (e.g. upside-down). This stop must not be
overridden.
S077-2 Volume II 2-3
Page 52
PM-0077
Figure 2 -3 Removing the RS485 Communications Option PCB
or the Remote Run/Hold Option PCB

2.5 SELECTION OF INPUT TYPE AND OUTPUT 1 TYPE

The selection of input type and Output 1 type is accomplished on link jumpers on the CPU PCB. The CPU PCB may be either of two forms: (a) for a relay, solid state or SSR drive Output 1 (see Figure 2-4) or for a DC Output 1 (see Figure 2-5).
2.5.1 Input Type
The required input type is selected on link jumpers LJ1/LJ2/LJ3 on the CPU PCB (see Figure 2-4 or 2-5, as appropriate, and Table 2-1).
Table 2 -1 Selection of Input Type
Input Type Link Jumpers Fitted
RTD or DC (mV) None (Parked)
Thermocouple LJ3
DC (mA) LJ2
DC (V) LJ1
2-4 Volume II S077-2
Page 53
PM-0077
Figure 2 -4 CPU PCB (Relay/SSR Drive/Solid State Output 1)
Figure 2 -5 CPU PCB (DC Output 1)
2.5.2 Primary Output (Output 1) Type
The required type of Output 1 is selected by Link Jumpers LJ4, LJ5, LJ6 and LJ7 on the Relay/SSR Drive/Solid State Output 1 CPU PCB (see Figure 2-4 and Table 2-2) or, on the DC Output 1 CPU PCB, Link Jumpers LJ8 and LJ9 (see Figure 2-5 and Table 2-2).
Table 2 -2 Selection of Output 1 Type
Output 1 Type Link Jumpers Fitted
Relay or Solid State LJ5 & LJ6
SSR Drive LJ4 & LJ7
DC (0 - 10V) LJ8
DC (0 - 20mA) LJ9
DC (0 - 5V) LJ8
DC (4 - 20mA) LJ9
S077-2 Volume II 2-5
Page 54
PM-0077

2.6 OUTPUT 2 TYPE/ OUTPUT 3 TYPE

The type of output for Output 2 and Output 3 is determined by the Option PCB fitted in the appropriate position (see Figure 2-1) and, in the case of the DC Output Option PCB being fitted, the setting of Link Jumpers LJ8 and LJ9 on that Option PCB (see Figure 2-6 and Table 2-3). There are three types of option PCB which may be used for Output 2 and Output 3:
1. Relay Output Option PCB (no link jumpers)
2. Solid State Output Option PCB (no link jumpers)
3. SSR Drive Output Option PCB (no link jumpers)
3. DC Output Option PCB (link jumpers as shown in Figure 2-6)
Table 2 -3 Selection of Output 2 &
Output 3 Type
DC Output Range Link Jumpers Fitted
DC (0 - 10V) LJ8
Figure 2-6 DC Output Option PCB
(Output 2/Output 3)
DC (0 - 20mA) LJ9
DC (0 - 5V) LJ8
DC (4 - 20mA) LJ9
2-6 Volume II S077-2
Page 55
PM-0077

3 CONFIGURATION MODE

3.1 ENTRY INTO CONFIGURATION MODE
Figure 3-1 Entry into Configuration Mode
NOTE: Changes to the value/setting of certain Configuration Mode parameters (e.g. input range, output use and type) will cause the Set Up Mode parameters to be automatically set to their default values the next time Set Up Mode is entered (see also Volume I, beginning
of Section 3).
3.2 HARDWARE DEFINITION CODE
This parameter is a special facility in Configuration Mode, which is used to represent the hardware fitted (input type, Output 1 type, Output 2 type and Output 3 type); this must be compatible with the hardware actually fitted. For access to, and adjustment of, the Hardware Definition Code, see Figure 3-2 and Table 3-1.
S077-3 Volume II 3-1
Page 56
PM-0077
Figure 3 -2 Hardware Definition Code - Access and Adjustment
3-2 Volume II S077-3
Page 57
PM-0077
Table 3 -1 Hardware Definition Code - Input/Output Type Selection
Value 0 1 2 3 4 5 7 8
Input RTD/
Linear
Thermo­couple
Linear DC mA
Linear DC V
DC mV
Output 1
Output 2/3
Not fitted
Relay SSR
Drive
Relay SSR
Drive
DC 0 - 10VDC0 - 20mADC0 - 5VDC4 - 20mA
DC 0 - 10VDC0 - 20mADC0 - 5VDC4 - 20mA
* Output 2 only
NOTES:
1. If Output 2 is a relay/SSR drive/solid state output, it may be a control output (COOL), an event output or an alarm output; if it is set to be a DC output, it can only be a control output (COOL).
2. If Output 3 is a relay/SSR drive output (it cannot be a solid state output), it can only be an event output or an alarm output; if it is set to be a DC output, it can only be a recorder (i.e. retransmitted process variable or setpoint) output.
Solid State
Solid State*
The maximum setting available for this code is 4887. For example, the code for a thermocouple input, DC 4 - 20mA primary output (Output 1) and relay Output 3 would be 2701.
NOTE: It is essential that this code is changed promptly whenever there is a change to the instrument’s hardware configuration (change of input/output type, alarm/recorder output added/removed etc.). The instrument software depends upon this code to ensure that the instrument operates correctly.
This code may be viewed as a Read Only display in Base Mode (see Volume I, Subsection 1.11).

3.3 OPTION SELECTION

This indicates the option fitted (Communications Option, Remote Run/Hold option or no option at all). It is accessed whilst the Hardware Definition Code is displayed (see Figure 3-3).
S077-3 Volume II 3-3
Page 58
PM-0077
Figure 3 -3 Option Selection

3.4 CONFIGURATION MODE PARAMETERS

Parameter Identifier Description
Input Range
Output 1 Action
Alarm 1 Type
A four-digit code (see Appendix A). Default settings:
Thermocouple - 1419 (Type J, 0 - 761 °C) RTD/Linear mV - 7220 (RTD Pt100 0 - 800°C)
Linear mA - 3414 (4 - 20mA) Linear V - 4446 (0 - 10V)
Reverse-acting
Direct-acting
Process High Alarm
Process Low Alarm
Deviation Alarm
Band Alarm
No alarm
3-4 Volume II S077-3
Page 59
PM-0077
Parameter Identifier Description
Alarm 2 Type
Alarm Inhibit
Program Mode
Process High Alarm
Process Low Alarm (default)
Deviation Alarm
Band Alarm
No alarm
No alarms inhibited
Alarm 1 inhibited
Alarm 2 inhibited
Both Alarm 1 & Alarm 2 inhibited
Rate
Time
S077-3 Volume II 3-5
Page 60
Parameter Identifier Description
PM-0077
Output 2 Usage
Output 2 secondary control (COOL) output
Alarm 2 hardware output, direct-acting. Avail­able only if relay/SSR drive/solid state output.
Alarm 2 hardware output, reverse-acting. Avail­able only if relay, SSR drive or solid state output.
Direct-acting output for Logical OR of Alarm 1 and Alarm 2. Available only if relay, SSR drive, or solid state output.
Reverse-acting output for Logical OR of Alarm 1 and Alarm 2. Available only if relay, SSR drive, or solid state output.
Direct-acting output for Logical AND of Alarm 1 and Alarm 2. Available only if relay, SSR drive, or solid state output.
Reverse-acting output for Logical AND of Alarm 1 and Alarm 2. Available only if relay, SSR drive, or solid state output.
Profile Active output, direct-acting. Available only if relay, SSR drive or solid state output.
Profile Active output, reverse-acting. Available only if relay, SSR drive or solid state output.
Event output, direct-acting. Available only if relay, SSR drive or solid state output.
Example of Logical Combination of Alarms - Logical OR of Alarm 1 & Alarm 2
Direct-acting Reverse-acting
AL1 OFF, AL2 OFF: Relay de-energised AL1 OFF, AL2 OFF: Relay energised
AL1 ON, AL2 OFF: Relay energised AL1 ON, AL2 OFF: Relay de-energised
AL1 OFF, AL2 ON: Relay energised AL1 OFF, AL2 ON: Relay de-energised
AL1 ON, AL2 ON: Relay energised AL1 ON, AL2 ON: Relay de-energised
3 -6 Volume II S077-3
Page 61
PM-0077
Parameter Identifier Description
Output 3 Usage
Alarm 1 hardware output, direct-acting. Avail­able only if relay/SSR drive/solid state output.
Alarm 1 hardware output, reverse-acting. Avail­able only if relay, SSR drive or solid state output.
Direct-acting output for Logical OR of Alarm 1 and Alarm 2. Available only if relay, SSR drive, or solid state output.
Reverse-acting output for Logical OR of Alarm 1 and Alarm 2. Available only if relay, SSR drive, or solid state output.
Direct-acting output for Logical AND of Alarm 1 and Alarm 2. Available only if relay, SSR drive, or solid state output.
Reverse-acting output for Logical AND of Alarm 1 and Alarm 2. Available only if relay, SSR drive, or solid state output.
Recorder Output - Setpoint (DC output only)
Recorder Output - Process Variable (DC Output only)
Profile Active output, direct-acting. Available only if relay or SSR drive output.
Profile Active output, reverse-acting. Available only if relay or SSR drive output.
Event output, direct-acting. Available only if relay or SSR drive output.
Example of Logical Combination of Alarms - Logical AND of Alarm 1 & Alarm 2
Direct-acting Reverse-acting
AL1 OFF, AL2 OFF: Relay de-energised AL1 OFF, AL2 OFF: Relay energised
AL1 ON, AL2 OFF: Relay de-energised AL1 ON, AL2 OFF: Relay energised
AL1 OFF, AL2 ON: Relay de-energised AL1 OFF, AL2 ON: Relay energised
AL1 ON, AL2 ON: Relay energised AL1 ON, AL2 ON: Relay de-energised
S077-3 Volume II 3-7
Page 62
Parameter Identifier Description
PM-0077
& ∇ LEDs Usage
(on Front Panel)
Guaranteed Soak Enable/Disable (see Volume I, Subsection 2.2.5)
Delayed Start Enable/Disable
Power Loss Recovery
Ramp direction:
= positive ramp = negative ramp
both = soak
Output state:
= Output 1 ON = Output 2 ON
Enabled
Disabled
Manual
Enabled
Disabled
Cold Start (program re-started from beginning)
Warm Start (program resumed from point at which power failed)
Start On Start program with setpoint at
current process variable value Start program with setpoint at
Controller Setpoint value
Communications
MODBUS with odd parity
Protocol
MODBUS with even parity
MODBUS with no parity
Communications
Selectable: 1200, 2400, 4800, 9600 Baud
Baud Rate
Communications Address
Cold Junction
Unique address assigned to the Profile Controller; in the range 1 - 255.
Enabled (default) Compensation Enable/Disable*
Disabled
* Appears only if a thermocouple input is selected (see Hardware Definition Code).
3 -8 Volume II S077-3
Page 63
PM-0077
Parameter Identifier Description
Controller Set-Up Mode Lock Code
Program Define Mode Lock Code
Read Only display of current four-digit Set Up Mode Lock Code.
Read Only display of current four-digit Program Define Mode Lock Code.

3.5 EXIT FROM CONFIGURATION MODE

NOTE: An automatic exit to Operator Mode will be made if, in Configuration Mode, there is no front panel key activity for two minutes.
The exit is made via the power-up self-test routines which include a lamp test.
S077-3 Volume II 3-9
Page 64
PM-0077
APPENDIX A PRODUCT SPECIFICATION
UNIVERSAL INPUT General
Maximum per Controller: One
Input Sample Rate: Four samples/second
Digital Input Filter: Time constant selectable from front panel -
0.0 (i.e. OFF), 0.5 to 100.0 seconds in
0.5-second increments.
Input Resolution: 14 bits approximately; always four times
better than display resolution.
Input Impedance: Greater than 100M Ω resistive (except for
DC mA and V inputs).
Isolation: Universal input isolated from all outputs
except SSR at 240V AC.
Process Variable Offset:
Adjustable ±input span.
Thermocouple: Ranges selectable from front panel:
Type Input Range Displayed Code Type Input Range Displayed Code
R
R
S
S
J
J
J
0 - 1650 °C
32 - 3002°F
0 - 1649°C
32 - 3000°F
0.0 - 205.4 °C
32.0 - 401.7 °F 0 - 450 °C
1127 J
1128 T
1227 T
1228 T
1415 T
1416 K
1417 K
32 - 1401 °F
-200 - 262 °C
-328 - 503 °F
0.0 - 260.6 °C
32.0 - 501.0 °F
-200 - 760°C
-328 - 1399 °F
1420
1525
1526
1541
1542
6726
6727
J
J
A -1 Volume II S077-A
32 - 842°F
0 - 761 °C
* Default Continued overleaf....................
1418 K
1419 * K
-200 - 1373 °C
-328 - 2503 °F
6709 *
6710
Page 65
PM-0077
Type Input Range Displayed Code Type Input Range Displayed Code
L
L
0.0 - 205.7 °C
32.0 - 402.2 °F
L
L
32 - 841°F
L
L
32 - 1403°F
0 - 450°C
0 - 762°C
1815 B
1816 B
1817 N
1818 N
1819 C/W5
1820 C/W5
211 - 3315 °F
100 - 1824°C
0 - 1399°C
32 - 2550°F
0 - 2316°C
32 - 4201°F
1934
1938
5371
5324
5111
5112
Calibration: Complies with BS4937, NBS125 and IEC584.
Sensor Break Protection: Break detected within two seconds. Control
outputs set to OFF (0% power); Alarms operate as if the process variable has gone over-range.
Resistance Temperature Detector (RTD) and DC mV: Ranges
selectable from front panel:
Input Range Displayed Code Input Range Displayed Code
0 - 800 °C *
32 - 1471°F
32 - 571°F
-100.9 - 100.0°C
-149.7 - 211.9°F 0 - 300 °C
7220
7221
2229
2230
2231
2251
0.0 - 100.9 °C
32.0 - 213.6 °F
-200 - 206°C
-328 - 402°F
-100.9 - 537.3°C
-149.7 - 999.1°F
2295
2296
2297
2298
7222
7223
* Default
Type and Connection: Three-wire Pt100
Calibration: Complies with BS1904 and DIN43760.
Lead Compensation: Automatic scheme.
RTD Sensor Current: 150µA (approximately)
Sensor Break Protection: Break detected within two seconds. Control
outputs set to OFF (0% power). For RTD input, alarms operate as if the process variable has gone under-range. For DC (mV) input, alarms operate as if the process variable has gone over-range.
S077-A Volume II A-2
Page 66
PM-0077
DC Linear: Ranges Selectable from Front Panel:
Input Range Displayed Code Input Range Displayed Code
0 - 20mA 3413 0 - 5V 4445
4 - 20mA * 3414 1 - 5V 4434
0 - 50mV 4443 0 - 10V * 4446
10 - 50mV 4499 2 - 10V 4450
* Default
(Changes may also be required to the CPU PCB link jumpers - see Subsection
2.5.1.)
Scale Range Maximum: –1999 to 9999. Decimal point as required.
Scale Range Minimum: –1999 to 9999. Decimal point as for Scale
Range Maximum.
Minimum Span: 1 display LSD.
Sensor Break Protection: Applicable to 4 - 20mA, 1 - 5V and 2 - 10V
ranges only. Break detected within two seconds. Control outputs set to OFF (0% power); Alarms operate as if the process variable has gone under-range.
REMOTE RUN/HOLD INPUT (OPTION)
Type: Voltage-free or TTL-compatible;
edge-sensitive. OFF-ON transition - currently-selected program will run or (if currently held) resume running. ON-OFF transition - currently-running program will be held.
Voltage-Free Operation: Connection to contacts of external switch
or relay; contacts open = OFF (minimum contact resistance = 5000Ω), contacts closed = ON (maximum contact resistance = 50 Ω).
TTL levels: OFF: –0.6V to 0.8V
ON: 2.0V to 24V
Maximum Input Delay (OFF-ON):
A-3 Volume II S077-A
1 second
Page 67
PM-0077
Minimum Input Delay
1 second
(ON-OFF):
OUTPUT 1 General
Types Available: Relay (as standard), SSR drive, solid state
and DC as options.
Relay
Contact Type: Single pole double throw (SPDT).
Rating: 2A resistive at 120/240V AC.
Lifetime: >500,000 operations at rated
voltage/current.
Isolation: Inherent.
SSR Drive/TTL
Drive Capability: SSR >4.2V DC into 1k minimum.
Isolation: Not isolated from input or other SSR outputs.
Solid State
Operating Voltage Range: 20 - 280Vrms (47 - 63Hz)
Current Rating:
Max. Non-repetitive Surge Current (16.6ms):
Min. OFF-State
dv
@ Rated
dt
Voltage:
Max. OFF-State leakage @ Rated Voltage:
0.01 - 1A (full cycle rms on-state @ 25°C); derates linearly above 40 °C to 0.5A @ 80 °C.
25A peak
500V/µs
1mA rms
Max. ON-State Voltage
1.5V peak.
Drop @ Rated Current:
Repetitive Peak OFF-state
600V minimum
Voltage, Vdrm:
S077-A Volume II A-4
Page 68
DC
Resolution: Eight bits in 250mS (10 bits in 1 second
typical, >10 bits in >1 second typical).
Update Rate: Every control algorithm execution.
Ranges: 0 - 20mA
4 - 20mA 0 - 10V 0 - 5V
(Changes between V and mA ranges also require link jumper movement.)
Load Impedance: 0 - 20mA: 500 maximum
4 - 20mA: 500 maximum 0 - 10V: 500 minimum 0 - 5V: 500 minimum
PM-0077
Isolation: Isolated from all other inputs and outputs.
Range Selection Method: Link jumper or DIP switch and front panel
code.
OUTPUT 2 General
Types Available: Relay, SSR drive, solid state and DC.
Relay
Contact Type: Single pole double throw (SPDT).
Rating: 2A resistive at 120/240V AC.
Lifetime: >500,000 operations at rated
voltage/current.
Isolation: Inherent.
SSR Drive/TTL
Drive Capability: SSR >4.2V DC into 1k minimum.
Isolation: Not isolated from input or other SSR outputs.
A-5 Volume II S077-A
Page 69
PM-0077
Solid State
Operating Voltage Range: 20 - 280Vrms (47 - 63Hz)
Current Rating:
Max. Non-repetitive Surge Current (16.6ms):
Min. OFF-State
dv
@ Rated
dt
Voltage:
Max. OFF-State leakage @ Rated Voltage:
Max. ON-State Voltage Drop @ Rated Current:
Repetitive Peak OFF-state Voltage, Vdrm:
DC
0.01 - 1A (full cycle rms on-state @ 25°C); derates linearly above 40 °C to 0.5A @ 80 °C.
25A peak
500V/µs
1mA rms
1.5V peak.
600V minimum
Resolution: Eight bits in 250mS (10 bits in 1 second
typical, >10 bits in >1 second typical).
Update Rate: Every control algorithm execution.
Ranges: 0 - 20mA
4 - 20mA 0 - 10V 0 - 5V
(Changes between V and mA ranges also require link jumper movement.)
Load Impedance: 0 - 20mA: 500 maximum
4 - 20mA: 500 maximum 0 - 10V: 500 minimum 0 - 5V: 500 minimum
Isolation: Isolated from all other inputs and outputs.
Range Selection Method: Link jumper or DIP switch and front panel
code.
S077-A Volume II A-6
Page 70
OUTPUT 3 General
Types Available: Relay, SSR drive, DC linear (Recorder
Output only)
Relay
Contact Type: Single pole double throw (SPDT).
Rating: 2A resistive at 120/240V AC.
Lifetime: >500,000 operations at rated
voltage/current.
Isolation: Inherent.
PM-0077
SSR Drive/TTL
Drive Capability: SSR >4.2V DC into 1k minimum.
Isolation: Not isolated from input or other SSR outputs.
DC
Resolution: Eight bits in 250mS (10 bits in 1 second
typical, >10 bits in >1 second typical).
Update Rate: Every control algorithm execution.
Ranges: 0 - 20mA
4 - 20mA 0 - 10V 0 - 5V
(Changes between V and mA require link jumper movement.)
Load Impedance: 0 - 20mA: 500 maximum
4 - 20mA: 500 maximum 0 - 10V: 500 minimum 0 - 5V: 500 minimum
Isolation: Isolated from all other inputs and outputs.
Range Selection Method: Link jumper or DIP.
A -7 Volume II S077-A
Page 71
PM-0077

LOOP CONTROL

Automatic Tuning Types: Pre-Tune
Proportional Bands: 0 (OFF), 0.5% - 999.9% of input span at
0.1% increments.
Reset (Integral Time
1s - 99min 59s and OFF
Constant):
Rate (Derivative Time
0 (OFF) - 99 min 59 s.
Constant):
Manual Reset (Bias): Added each control algorithm execution.
Adjustable in the range 0 - 100% of output power (single output) or –100% to +100% of output power (dual output).
Deadband/Overlap: –20% to +20% of Proportional Band 1 +
Proportional Band 2.
ON/OFF Differential: 0.1% to 10.0% of input span.
Auto/Manual Control: User-selectable with “bumpless” transfer
into and out of Manual Control.
Cycle Times: Selectable from
1
s to 512 secs in binary
2
steps.
Setpoint Range: Limited by Range Maximum and Range
Minimum.

ALARM CONTROL

Maximum Number of Alarms:
Max. No. of Outputs Available:
Combinatorial Alarms: Logical OR or AND of alarms to an
Two “soft” alarms.
Up to two outputs can be utilised for alarm purposes.
individual hardware output is available.
S077-A Volume II A-8
Page 72
PERFORMANCE Reference Conditions
Generally as EN60546-1.
PM-0077
Ambient Temperature:
Relative Humidity: 60 - 70%
Supply Voltage: 90 - 264V AC 50Hz 1%
Source Resistance: <10Ω for thermocouple input
Lead Resistance: <0.1Ω/lead balanced (Pt100)
20°C ±2oC
Performance Under Reference Conditions
Common Mode Rejection: >120dB at 50/60Hz giving negligible effect
at up to 264V 50/60Hz.
Series Mode Rejection: >500% of span (at 50/60Hz) causes
negligible effect.
DC Linear Inputs
Measurement Accuracy:
±0.25% of span ±1LSD.
Thermocouple Inputs
Measurement Accuracy:
Linearisation Accuracy:
Cold Junction Compensation:
RTD Inputs
Measurement Accuracy:
Linearisation Accuracy:
±0.25% of span ±1LSD. NOTE: Reduced
performance with Type “B” Thermocouple
between 100 - 600 °C (212 - 1112 °F). Better than ±0.2 °C any point, any 0.1°C
range (± 0.05°C typical). Better than ±0.5 °C any point, any 1 °C range.
Better than ±0.7 °C.
±0.25% of span ±1LSD Better than ±0.2 °C any point, any 0.1°C
range (± 0.05°C typical). Better than ±0.5 °C any point, any 1 °C range.
A-9 Volume II S077-A
Page 73
PM-0077
DC Outputs - Accuracy
Output 1:
±0.5% (mA @ 250, V @ 2kΩ ); 2%
underdrive (4 - 20mA) and overdrive applies.
Output 2:
±0.5% (mA @ 250 , V @ 2kΩ ); 2%
underdrive (4 - 20mA) and overdrive applies.
Output 3 (Recorder Output):
±0.25% (mA @ 250 , V @ 2kΩ ); Degrades linearly to ± 0.5% for increasing burden (to
specification limits).
Operating Conditions
Ambient Temperature
0 °C to 55 °C
(Operating):
Ambient Temperature
–20 °C to 80°C
(Storage):
Relative Humidity: 20% - 95% non-condensing
Supply Voltage: 90 - 264V AC 50/60Hz (standard)
20 - 50V AC 50/60Hz or 22 - 65V DC (option)
Source Resistance: 1000 maximum (thermocouple)
Lead Resistance: 50 per lead maximum balanced (Pt100)
Performance Under Operating Conditions
Temperature Stability:
0.01% of span/°C change in ambient
temperature.
Cold Junction
Better than ±1 °C.
Compensation (thermocouple Only):
Supply Voltage Influence: Negligible.
Relative Humidity
Negligible
Influence:
Sensor Resistance Influence:
Thermocouple 100: <0.1% of span error Thermocouple 1000: <0.5% of span error RTD Pt100 50 /lead: <0.5% of span error
S077-A Volume II A-10
Page 74

ENVIRONMENTAL

PM-0077
Operating Conditions:
Approvals: CE, UL, cUL
EMI Susceptibility: Certified to EN50082-1:1992 and
EMI Emissions: Certified to EN50081-1:1992 and
Safety Considerations: Complies with EN61010-1:1993.
Supply Voltage: 90 - 264V AC 50/60Hz (standard)
See PERFORMANCE.
EN50082-2:1995. NOTE: For line-conducted disturbances induced by RF fields (10V 80% AM 1kHz), the product is self-recoverable in the frequency bands 17 - 47MHz and 68 ­80MHz.
EN50081-2:1994.
20 - 50V AC 50/60Hz or 22 - 65V DC (option)
Power Consumption: 4 watts approximately.
Front Panel Sealing: To IP66 (NEMA 4).

PHYSICAL

Dimensions: Depth - 110mm
Front Panel: Width - 48mm, Height - 48mm (1/16 DIN)
Mounting: Plug-in with panel mounting fixing strap.
Panel cut-out 45mm x 45mm.
Terminals: Screw type (combination head).
Weight: 0.21kg maximum
A-11 Volume II S077-A
Page 75
PM-0077
APPENDIX B SUMMARY OF DISPLAYS
The lower display on the Profiler/Controller front panel is used to identify the parameter being displayed. The parameter identifiers are as follows:
Legend Meaning Ref.

Base Mode Parameters Volume Section

Manual Power (xxx = power output value)
Setpoint
Delayed Start
Final (Target) Setpoint for Segment xx (01 - 16)
Time remaining
Cycles remaining
Automatic/Manual Control selection
Event/Alarm Status
Current Program (1 - 4)

Controller Set-Up Mode Parameters

Input Filter Time Constant
Process Variable Offset
Output 1 Power (0 - 100%)
Output 2 Power (0 - 100%)
I 1.12
I 1.1
I 1.2
I 1.6
I 1.6
I 1.6
I 1.6
I 1.6
I 1.6
I 3.1
I 3.1
I 3.1
I 3.1
Proportional Band 1
Proportional Band 2
Reset (Integral Time Constant)
Rate (Derivative Time Constant)
Deadband/Overlap
Bias (Manual Reset)
ON/OFF Differential (both outputs)
ON/OFF Differential (Output 1 only)
ON/OFF Differential (Output 2 only)
Setpoint Lock
Recorder Output Scale Maximum
Recorder Output Scale Minimum
I 3.1
I 3.1
I 3.1
I 3.1
I 3.1
I 3.1
I 3.1
I 3.1
I 3.1
I 3.1
I 3.1
I 3.1
S077-B Volume II B-1
Page 76
Legend Meaning Ref.
Controller Set-Up Mode Parameters (Continued) Volume Section
PM-0077
Output Power Maximum
Output 1 Cycle Time
Output 2 Cycle Time
Process High Alarm 1 value
Process Low Alarm 1 value
Deviation Alarm 1 value
Band Alarm 1 value
Alarm 1 Hysteresis value
Process High Alarm 2 value
Process Low Alarm 2 value
Deviation Alarm 2 value
Band Alarm 2 value
Alarm 2 Hysteresis value
Decimal Point Position (for linear input range)
I 3.1
I 3.1
I 3.1
I 3.1
I 3.1
I 3.1
I 3.1
I 3.1
I 3.1
I 3.1
I 3.1
I 3.1
I 3.1
I 3.1
Range Maximum (for linear input range)
Range Minimum (for linear input range)
Manual Power Selection enable/disable
Setpoint Strategy
Communications Write enable/disable
Lock Code

Program Define Mode Parameters

Ramp Rate for Segment xx (xx in range 01 - 16)
Segment xx is currently set as a Soak segment
Segment xx is currently set as an End segment
Final (Target) Setpoint value for Segment xx
Segment Time for Segment xx
Number of Cycles Programmed
Timebase (hours/minutes or minutes/seconds)
I 3.1
I 3.1
I 3.1
I 3.1
I 3.1
I 3.1
I 2.2.2
I 2.2.2-3
I 2.2.2-3
I 2.2.2-3
I 2.2.2-3
I 2.2.4
I 2.2.4
Guaranteed Soak Band value
Event Marker setting for Segment xx
B-2 Volume II S077-B
I 2.2.4
I 2.2.4
Page 77
PM-0077
Legend Meaning Ref.

Configuration Mode Parameters Volume Section

Hardware Definition Code
Hardware Option selection
Input Type selection
Control Action
Alarm 1 Type
Alarm 2 Type
Alarm Inhibit
Program Mode (Rate or Time)
Output 2 Usage
Output 3 Usage
LED Usage (∆ and ∇ )
Guaranteed Soak Action
Delayed Start enable/disable
Power Fail Recovery (Warm Start/Cold Start)
II 3.2
II 3.3
II 3.4
II 3.4
II 3.4
II 3.4
II 3.4
II 3.4
II 3.4
II 3.4
II 3.4
II 3.4
II 3.4
II 3.4
Program Start Setpoint (current PV/Controller SP)
MODBUS parity selection
Communications Baud rate
Communications Address (Zone)
Cold Junction Compensation enable/disable
Controller Set-Up Mode Lock Code
Program Define Mode Lock Code

Miscellaneous

Entry to Controller Set-Up or Program Define Mode
User to enter lock code to access either Controller Set-Up Mode or Program Define Mode
II 3.4
II 3.4
II 3.4
II 3.4
II 3.4
II 3.4
II 3.4
I 2.1 & 3.1
I 2.1 & 3.1
S077-B Volume II B-3
Page 78

ALPHABETICAL INDEX

PM-0077
Page references are shown in the form x/y-z, where x is the Volume Number (I or II), y is the Section Number within that Volume and z is the Page Number within that Section. Thus, the reference to the second page of the third Section in Volume II would be II/3-2.
A
Aborting a Program I/1-2 Active Program Setpoint
Display of I/1-3 Alarm 1 Hysteresis I/3-5 Alarm 1 Status
Display of I/1-1,I/1-3 Alarm 1 Type II/3-4 Alarm 2 Hysteresis I/3-5 Alarm 2 Status
Display of I/1-1,I/1-3 Alarm 2 Type II/3-5 Alarm Hysteresis
Description of I/3-8 Alarm Inhibit II/3-5 Alarm Operation
Description of I/3-7 Automatic Control
Selection of I/1-7
C
Cold Junction Compensation
Enabling/disabling II/3-8 Communications Enabling/disabling I/3-5 Communications Address
Selection of II/3-8 Communications Baud Rate
Selection of II/3-8 Communications Protocol
Selection of II/3-8 Control Mode
Display of I/1-1,I/1-3 Configuration Mode
Entry into II/3-1
Exit from II/3-9 Controller Dimensions II/A-11 Controller Set-Up Mode
Entry into I/3-1
Exit from I/3-9 Controller Set-Up Mode Lock Code
Display of II/3-8 Cycles Remaining
Display of I/1-3 Cyclic Redundancy Checksum
Description of I/4-5
B
Band Alarm 1 I/3-4 Band Alarm 2 I/3-5 Baud Rates Available I/4-1 Bias I/3-3 Bit Parameters I/4-7 Broadcast Messages I/4-2
1 Volume II S077-IDX
Page 79
PM-0077
D
Data Format I/4-2 Deadband I/3-3
Description of I/3-6
Delayed Start
Enabling/disabling II/3-8
Delay Time
Selection of I/1-2 Derivative Time Constant I/3-3 Deviation Alarm 1I/3-4 Deviation Alarm 2I/3-5
E
Error Responses I/4-5 Event Markers
Defining I/2-5 Event Output Status
Display of I/1-1,I/1-3 Exception Codes I/4-5 Exception Responses I/4-5
H
Hardware Definition Code
Adjustment of II/3-1 Display of I/1-6, II/3-1 Explanation of I/1-6 Input/Output Type selection
II/3-3
Holding a Program I/1-2
I
Input Connections
Linear inputII/1-5 Remote Run/Hold input II/1-5 RTD II/1-4
Thermocouple II/1-4 Input Filter Time ConstantI/3-3 Input Range II/3-4 Input Type
Selection of II/2-4 Integral Time Constant I/3-3
F
Final Setpoint
Display of I/1-3
Fuse Rating
24V AC/DC supplyII/1-4 Mains supply II/1-4
G
Guaranteed Soak
Enabling/Disabling/Manual
II/3-8
Guaranteed Soak Band
Defining I/2-5
Description of I/2-4
L
LEDs Usage II/3-8 Lock Code (Controller Set-Up Mode)
I/3-5 Lock Code (Program Define Mode)
Defining I/2-5 Logical Combination of Alarms
Example (AND) II/3-7
Example (OR) II/3-6
S077-IDX Volume II 2
Page 80
PM-0077
M
Making a Soak Segment
Rate Mode I/2-3 Time Mode I/2-4
Making a Ramp Segment
Rate Mode I/2-3 Time Mode I/2-4
Making an End Segment
Rate Mode I/2-3 Time Mode I/2-4
Manual Control
Selection of I/1-7
Manual Control Selection
Enabling/disabling I/3-5
Manual Guaranteed Soak
Description of I/2-6 Manual Reset I/3-3 Message formats I/4-2 Message termination I/4-2
N
Number of Cycles
Defining I/2-5
O
ON/OFF Differential I/3-4
Description of I/3-6 Option Selection II/3-3 Output 1 Action II/3-4 Output 1 Cycle Time I/3-4 Output 1 Power Limit I/3-4 Output 1 Type
Selection of II/2-5 Output 2 Cycle Time I/3-4 Output 2 Type
Selection of II/2-6 Output 2 Usage II/3-6
Output 2/Output 3 Option PCB
Removal/replacement II/2-3
Output 3 Type
Selection of II/2-6 Output 3 Usage II/3-7 Output Connections
DC II/1-6
Relay II/1-5
Solid State output II/1-5
SSR Drive II/1-5 Output Power 1 I/3-3 Output Power 2 I/3-3 Overlap I/3-3
Description of I/3-6
P
Panel-mounting
Procedure II/1-2 Panel-Mounting
Cut-out dimensions (multiple
installation) II/1-1
Cut-out dimensions (single
installation) II/1-1
Maximum panel thickness
II/1-1
Profiler/Controller dimensions
II/1-1
Panel-mounting the Profiler/Controller
II/1-1 PCB Positions II/2-1 Power Loss Recovery
Cold start/Hot start II/3-8 Pre-Tune
Dis-engaging I/1-4
Engaging I/1-4 Pre-Tune Facility
Activation of I/1-4 Pre-Tune Status
Indication of I/1-5
3 Volume II S077-IDX
Page 81
PM-0077
Process High Alarm 1 I/3-4 Process High Alarm 2 I/3-5 Process Low Alarm 1 I/3-4 Process Low Alarm 2 I/3-5 Process Variable
Display of I/1-1
Process Variable Offset I/3-3 Profiler Commands I/4-11 Profiler Status Byte I/4-11 Program Definition Mode
Entry into I/2-1 Exit from I/2-9
Program Mode
Selection of II/3-5
Program Number
Display of I/1-1,I/1-3 Selection ofI/1-1,I/1-2
Proportional Band
Description of I/3-6 Proportional Band 1 I/3-3 Proportional Band 2 I/3-3
R
RaPID Control
Dis-engaging I/1-4
Engaging I/1-4
RaPID Control Status
Indication of I/1-5 Rate I/3-3 Rear Terminal Connections II/1-2 Recorder Output
Scale Maximum I/3-4 Recorder Output
Scale Minimum I/3-4 Releasing a Currently-Held Program
I/1-2 Remote Run/Hold Option PCB
Removal/replacement II/2-3 Removing the Profiler/Controller from its
Housing II/2-1
Replacing the Instrument in its Housing
II/2-3 Reset I/3-3 RS485 Communications Option PCB
Removal/replacement II/2-3
S
Scale Range Decimal Point Position I/3-5
Scale Range Maximum I/3-5 Scale Range Minimum I/3-5 Segment Event Status
Description of I/2-7 Sensor Break
Effect on outputs
(DC linear inputs) II/A-3
Effect on outputs
(RTD inputs) II/A-2
Effect on outputs
(thermocouple inputs) II/A-2 Serial Communications
Connections II/1-6 Setpoint Adjustment (in Base Mode)
Enabling/disabling I/3-4 Setpoint High Limit I/3-4 Setpoint Lock I/3-4 Setpoint Low Limit I/3-4 Setpoint Strategy I/3-5 Supply Connections
24V AC/DC Option II/1-4
Mains (Line) voltage II/1-4
T
Time Remaining
Display of I/1-3 Timebase
Selection ofI/2-5
S077-IDX Volume II 4
Page 82
U
Unpacking Procedure II/1-1
W
Word Parameters I/4-8
PM-0077
5 Volume II S077-IDX
Loading...