MIC 1166
™
Small Size - Maximum Functions
1/16 DIN Profile Controller
SPECIFICATIONS*
Deadband/Overlap: -20% to +20% of
proportional band 1 + proportional
band 2
ON/OFF Hysteresis: 0.1% to 10.0% of input span
Auto/Manual Control: User-selectable with
"bumpless" transfer into and out of Manual
control.
Cycle Times: Selectable for 0.5sec to 512sec in
binary steps
Setpoint Range: Limited by Setpoint Upper and
Setpoint Lower Limits
Setpoint Ramp: Ramp rate selectable
1-9999 LSDs per hour and infinite. Number
displayed is decimal point aligned with selected
range.
ALARMS
Maximum Number: Two "soft" alarms
Maximum # Outputs: Up to 2 outputs can be
used for alarm purposes
Combination Alarms: Logical OR or AND of
alarms to an individual hardware output is
available.
DISPLAY
Digital Display: Dual 7 segment LED;
Top: .36” high, Bottom .28” high.
Status Indicators: Individual LED indictors for
OUT, Exceed, ALM, and when in Setup
PROGRAM/PROFILE SPECIFICATIONS
Programs: Four with 16 free form steps each
Length of program: 16 steps per program
Step Types: Ramp, dwell (soak), or end
Program cycling: 1 to 9999 cycles, or infinite
Delayed start: 0 to 99:59 hours:minutes or
minutes seconds, depending on the time base
selected.
Control: Start, Run, Hold and Abort from keypad
if remote run/hold is not used. Remote start,
run, and hold if the option is turned on.
Start From: Current process value or setpoint.
At End: Controlls at the last setpoint.
Guaranteed Soak: During dwells (soak) the
controller can be programmed to stop
advancing the dwell time while the process
value is outside a specific band around
setpoint. This capability can be disabled or the
controller can be set to wait until instructed to
"run" after the soak time has expired.
Time Base: Hours:Minutes or Minutes:Seconds.
Step Time: 0 to 99:59 hours:minutes or minutes
seconds,depending on the time base selected.
Ramp Rate: 0 to 9999 least significant digits per
hour or minute, depending on the time base.
(this applies only when the program mode is
set to Rate.)
STANDARD FEATURES
Dual Display for fast view of process and control
parameters
Full PID capability
Universal input for voltage, current, thermocouple
and RTD
Profile Cycling
Program loading via communications port
ENVIRONMENTAL CHARACTERISTICS
Operating Temperature: 0 to 55°C, 32 to 131°F
Storage Temperature: -20 to 80°C, -4 to 176°F
Humidity: 20 to 95% RH, non condensing
ELECTRICAL
Line Voltage: 90 - 264VAC, 50/60 Hz
Power Consumption: 4 Watts
Common Mode Rej.: 120 db at 50/60 Hz
Series Mode Rej.: > 500% of span 50/60 Hz
INPUTS
Thermocouple types: J, K, T, R, S, B, L, and N.
RTD: Three-wire PT100, DIN 43760
Volts (VDC): 0 to 5, 1 to 5, 0 to 10, 2 to 10
Millivolts: 0 to 50mVDC, 10 to 50mVDC
Milliamps: 0 to 20 or 4 to 20mADC
Sample Rate: 250 ms
OUTPUTS
Relay: SPDT rated at 2 amps resistive at 120/240
VAC
SSR Driver: > 4.3 VDC into 250Ω minimum
Triac Output: 1 amp @ 40°C derated to
1/2 amp @ 80°C
Current Output: 0 - 20 mA, 4 - 20 mA, eight bit
resolution
Volts DC Output: 0 - 10 V, 0 - 5 V, eight bit
resolution
CONTROL
Control Types: RaPID, PID, PID/on-off, on-off
RaPID: Response Assisted PID is a fuzzy logic
mixing/weighting of P, I, and D terms to provide
dramatic performance improvements as
compared to conventional PID techniques.
Auto Tune Types: Pre-Tune
Proportional Bands: 0 (OFF), 0.5% to 999.9% of
input span @ 0.1% increments
Auto Reset: 1s-99min 59sec and OFF
Rate: 0 (OFF) - 99min 59sec
Manual Reset: Adjustable in the range
0-100% of output power (single output) or 100% to +100% of output power (dual output)
Event Output: Programmable to ON or OFF at the
beginning of each step. Output 2 or 3 can be used as
the event output.
Profile Active: Output 2 or 3 can be set to be energized
or de-energized whenever a profile/program is
running.
Power Loss Recovery: If power is removed and applied
while a profile is running, the unit can be
programmed to re-start or continue the profile.
REMOTE RUN/HOLD INPUT (OPTION)
Type: Voltage free or TTL compatible
ON - Currently selected program will run or (if currently
held) resuming running.
OFF - Currently running program will be held.
Voltage free Operation: Connection of contacts to
external switch or relay; contacts open = OFF
(minimum contact resistance = 5000Ω), contacts
closed = ON (maximum contact resistance = 50Ω)
TTL levels: ON: -0.6V to 0.8V
OFF: 2.0V to 24V
Maximum Input Delay (OFF-ON): 1 Second
Minimum Input Delay (ON-OFF): 1 Second
PHYSICAL DIMENSIONS
Dimensions: 1/16 DIN front panel, 110mm (4.3") deep
Front Panel Rating: NEMA 4X/IP65
Weight: 227 g. (8 oz.) maximum
COMMUNICATIONS
Type: RS-485 serial communication port
Protocol: MODBUS/RTU
RATINGS/AGENCY APPROVALS
CE, UL & cUL recognized (E67237),
WARRANTY
3 years
* Specifications are for base models with standard features
only unless otherwise noted. Specifications subject to
change without notice in accordance with our DBS policy
of continuous improvement. All product and brand names
are trademarks of their respective owners. All rights
reserved.
Partlow™ brand and MIC 1166™ are trademarks of Danaher Industrial
Controls Group. All rights reserved.
© 2005 DICG Corp.
Partlow Brand MIC 1166 Data Sheet (7/05)
Controllers