Partlow MIC 1166 Specifications

Data Sheet
Customer Service +1 800.390.6405
Technical Support +1 800.866.6659
www.partlow.com www.danaherindustrialcontrols.com
Process Automation Worldwide Brands: LFE
TM
• Partlow
TM
• PMA
• Rustrak
TM
• West
TM
MIC 1166
Small Size - Maximum Functions
FEATURES/BENEFITS
Dual, 4-digit, LED displays
1/16 DIN panel mount
Universal Input for thermocouple, RTD, DC
linear mA/V/mV user-selectable
Up to 3 outputs; relay, 4-20mA, SSR driver, Triac
Alarm, control, retransmit, event output
functions
PID, ON/OFF, profile (ramp/soak) control
Optional RS-485 serial communications
Program security
DESCRIPTION
The Partlow brand MIC 1166 1/16 DIN profiler may seem small, but it packs a punch with holding up to 4 programs of 16 free-format segments each and includes an event output. The controller can be configured from the front of the instrument or by a PC through a configuration port. The configuration port has a dual purpose; first it can be used to modify the controller setups and secondly, it can be used to transfer programs or profiles.
This control has RaPID, Response Assisted PID, a fuzzy logic algorithm plus a pre-tune algorithm, that when combined provide shorter start-up times and reduced overshoot.
The Partlow brand MIC 1166 contains many of the features of larger more expensive profilers such as: guaranteed soak, delayed start, profile active output, profile recovery features, profile cycling, plus an optional digital input for remote run/hold. RS-485 communications is also available with convenient, full access to all profile data.
Modular I/O options allow for field upgrades by adding or replacing boards.
1/16 DIN Profile Controller
Controllers
APPLICATIONS:
Programmable profile device stores and implements temperature control sequences including ramp/soak profiles using exclusive PID techniques.
INDUSTRIES
Industrial and lab ovens/furnaces, plastics and
thermal forming
Form/fill and seal
Packaging applications
And any others where low costs, smaller size
and unmatched connectivity are critical requirements.
Process Automation Worldwide Brands: LFE
TM
• Partlow
TM
• PMA
• Rustrak
TM
• West
TM
Customer Service +1 800.390.6405
Technical Support +1 800.866.6659
www.partlow.com www.danaherindustrialcontrols.com
MIC 1166
Small Size - Maximum Functions
1/16 DIN Profile Controller
SPECIFICATIONS*
Deadband/Overlap: -20% to +20% of
proportional band 1 + proportional
band 2 ON/OFF Hysteresis: 0.1% to 10.0% of input span Auto/Manual Control: User-selectable with
"bumpless" transfer into and out of Manual
control. Cycle Times: Selectable for 0.5sec to 512sec in
binary steps Setpoint Range: Limited by Setpoint Upper and
Setpoint Lower Limits Setpoint Ramp: Ramp rate selectable
1-9999 LSDs per hour and infinite. Number
displayed is decimal point aligned with selected
range.
ALARMS
Maximum Number: Two "soft" alarms Maximum # Outputs: Up to 2 outputs can be
used for alarm purposes Combination Alarms: Logical OR or AND of
alarms to an individual hardware output is
available.
DISPLAY
Digital Display: Dual 7 segment LED;
Top: .36 high, Bottom .28 high. Status Indicators: Individual LED indictors for
OUT, Exceed, ALM, and when in Setup
PROGRAM/PROFILE SPECIFICATIONS
Programs: Four with 16 free form steps each Length of program: 16 steps per program Step Types: Ramp, dwell (soak), or end Program cycling: 1 to 9999 cycles, or infinite Delayed start: 0 to 99:59 hours:minutes or
minutes seconds, depending on the time base
selected. Control: Start, Run, Hold and Abort from keypad
if remote run/hold is not used. Remote start,
run, and hold if the option is turned on.
Start From: Current process value or setpoint. At End: Controlls at the last setpoint. Guaranteed Soak: During dwells (soak) the
controller can be programmed to stop
advancing the dwell time while the process
value is outside a specific band around
setpoint. This capability can be disabled or the
controller can be set to wait until instructed to
"run" after the soak time has expired.
Time Base: Hours:Minutes or Minutes:Seconds. Step Time: 0 to 99:59 hours:minutes or minutes
seconds,depending on the time base selected. Ramp Rate: 0 to 9999 least significant digits per
hour or minute, depending on the time base.
(this applies only when the program mode is
set to Rate.)
STANDARD FEATURES
Dual Display for fast view of process and control
parameters Full PID capability Universal input for voltage, current, thermocouple
and RTD Profile Cycling Program loading via communications port
ENVIRONMENTAL CHARACTERISTICS
Operating Temperature: 0 to 55°C, 32 to 131°F Storage Temperature: -20 to 80°C, -4 to 176°F Humidity: 20 to 95% RH, non condensing
ELECTRICAL
Line Voltage: 90 - 264VAC, 50/60 Hz Power Consumption: 4 Watts Common Mode Rej.: 120 db at 50/60 Hz Series Mode Rej.: > 500% of span 50/60 Hz
INPUTS
Thermocouple types: J, K, T, R, S, B, L, and N. RTD: Three-wire PT100, DIN 43760 Volts (VDC): 0 to 5, 1 to 5, 0 to 10, 2 to 10 Millivolts: 0 to 50mVDC, 10 to 50mVDC Milliamps: 0 to 20 or 4 to 20mADC Sample Rate: 250 ms
OUTPUTS
Relay: SPDT rated at 2 amps resistive at 120/240
VAC
SSR Driver: > 4.3 VDC into 250minimum Triac Output: 1 amp @ 40°C derated to
1/2 amp @ 80°C
Current Output: 0 - 20 mA, 4 - 20 mA, eight bit
resolution
Volts DC Output: 0 - 10 V, 0 - 5 V, eight bit
resolution
CONTROL
Control Types: RaPID, PID, PID/on-off, on-off RaPID: Response Assisted PID is a fuzzy logic
mixing/weighting of P, I, and D terms to provide dramatic performance improvements as compared to conventional PID techniques.
Auto Tune Types: Pre-Tune Proportional Bands: 0 (OFF), 0.5% to 999.9% of
input span @ 0.1% increments
Auto Reset: 1s-99min 59sec and OFF Rate: 0 (OFF) - 99min 59sec Manual Reset: Adjustable in the range
0-100% of output power (single output) or ­100% to +100% of output power (dual output)
Event Output: Programmable to ON or OFF at the
beginning of each step. Output 2 or 3 can be used as the event output.
Profile Active: Output 2 or 3 can be set to be energized
or de-energized whenever a profile/program is running.
Power Loss Recovery: If power is removed and applied
while a profile is running, the unit can be programmed to re-start or continue the profile.
REMOTE RUN/HOLD INPUT (OPTION)
Type: Voltage free or TTL compatible
ON - Currently selected program will run or (if currently
held) resuming running. OFF - Currently running program will be held. Voltage free Operation: Connection of contacts to
external switch or relay; contacts open = OFF
(minimum contact resistance = 5000), contacts
closed = ON (maximum contact resistance = 50Ω) TTL levels: ON: -0.6V to 0.8V
OFF: 2.0V to 24V
Maximum Input Delay (OFF-ON): 1 Second Minimum Input Delay (ON-OFF): 1 Second
PHYSICAL DIMENSIONS
Dimensions: 1/16 DIN front panel, 110mm (4.3") deep Front Panel Rating: NEMA 4X/IP65 Weight: 227 g. (8 oz.) maximum
COMMUNICATIONS
Type: RS-485 serial communication port Protocol: MODBUS/RTU
RATINGS/AGENCY APPROVALS
CE, UL & cUL recognized (E67237),
WARRANTY
3 years
* Specifications are for base models with standard features
only unless otherwise noted. Specifications subject to change without notice in accordance with our DBS policy of continuous improvement. All product and brand names are trademarks of their respective owners. All rights reserved.
Partlow™ brand and MIC 1166™ are trademarks of Danaher Industrial Controls Group. All rights reserved.
© 2005 DICG Corp. Partlow Brand MIC 1166 Data Sheet (7/05)